VOLUME FLOW CONTROLLERS

Description

1

CONSTANT VOLUME FLOW CONTROLLERS – RECTANGULAR KP

Shock absorber

Casing

Control lever

Mechanism

Damper blade

Constant volume flow controllers KP and KP-I are mechanical controllers used to maintain a constant volume flow rate independently of the pressure variations in ventilation and air conditioning systems. Controllers can be installed in a supply and extract air systems.

Each controller is set to the required flow rate and subjected to the aerodynamic function test conducted in our test facility. The flow rate can be easily set or reset by adjusting the control lever on the calibrated scale. This is done by loosing the control lever's wing bolt and turning the control lever's arrow pointer to the desired value. When adjusted, the control lever is fixed by tightening the wing bolt.

Controllers work at the differential pressure range from 50 to 1000 Pa and the air velocity range from 3 to 10 m/s. As a reference value, recomended air velocity is around 6,5 m/s, where the accuracy of a constant flow rate is usually within a tolerance from ±5% of the set value.

The controller can operate, without the direct influence of weather conditions on the operation, within a temperature range of -20°C up to 80°C and relative humidity up to 80%.

Controllers should be stored in closed and dry places at temperatures from -20°C to +60°C.

Controller versions:KP - Constant volume flow controller, rectangularKP-I - Constant volume flow controller, rectangular - insulated

Technical data

VOLUME FLOW CONTROLLERS

KP

CASING - made of galvanised sheet steel

MECHANISM - control lever mechanism adjusts the spring tension to control the air flow

DAMPER BLADE - provides resistance to the air flow

SHOCK ABSORBER - serves to absorbe the damper blade vibration coused by the air flow

INSULATION CLADDING - 30 mm mineral wool layer with galvanised sheet steel outer cover

Insulation Cladding

Construction

2

Dimensions

Single controller Dual controller

30

30

B385

B + 60

H

H +

60

30

385

30

B

HH

+ 6

0

Q (m³/h)

BxH

(m

m)

600050004000350030002500200018001600140012001000900800700600500400300200

260400400

600600

600600

600

700

700800

800

900

900

900

970

10001080

1080

11001300

1200

12001400

1500

15001900

19001900 6100

45004200

4000

40003600

360034003300

2500

25002100

1800

18001200

17001400

32002600

21902900

4000

3800

3800

33002900

36004300

1700

740150x150960200x150

250x150300x150

400x150450x150

200x200250x200

300x200

350x200400x200450x200500x200

550x200600x200

250x250

300x250350x250

400x250

450x250

500x250550x250600x250

300x300

350x300400x300450x300

500x300

550x300600x300

DimensionsRequired flow rate ( 3m /h)

VOLUME FLOW CONTROLLERS

Quick selection Table

Order codes

KP/KP-I - BxH - Q

Constant volume flow controller,rectangular - insulated

H

B

200150

150

250300

350400

450

550500

600

Constant volume flowcontroller, rectangular

200 250 300

POOO

PPPPPP

PPPPPPP

PPP

PPPPPPP

PPP

PPPPPPP

PPP

H

B

450400

400

500550

600

450 500 550

PPPPP

PPPPP

PPPPP

PPPPP

600

PPPPP

KP

B+60

*Flow rate calibration possible at air velocities from 3 to 10 m/s

Legend:

7000 1900

1500

1000900800700

600500

400

300

200

150

10090807060

50

40

30

6000

5000

4000

3000

2000

1500900800700600

500

400

300

200

100

0,0

2

0,0

25

0,0

3

0,0

35

0,0

4

0,0

5

0,0

6

0,0

7

0,0

8

0,0

9

0,1

0,1

5

0,2

ρ=1,2 kg/m³

3 m/s

10 m/s

250

225

200

175

150

125

100

75

50

25

0

0

1 2 3 4 5 6 7 8 9 10 11 12

Flow rate range in relation to duct cross section

VOLUME FLOW CONTROLLERS

3

2A [m ]

Q [

I/s]

Q [

m/H

Minimum static pressure difference at the controller.

v (m/s)

Dp

[P

a]

3Q (m /h or l/s)v (m/s)

2A (m )Dp (Pa)

flow rateair velocityeffective outlet areastatic pressure difference

KP

Single controller

Flow noise levels

VOLUME FLOW CONTROLLERS

4

B [m

m]

H [m

m]

v [

m/s

]

Q [m

3/h

]

63 H

z

125 H

z

250 H

z

500 H

z

1000 H

z

2000 H

z

4000 H

z

8000 H

z

TO

T

Hz

63 H

z

125 H

z

250 H

z

500 H

z

1000 H

z

2000 H

z

4000 H

z

8000 H

z

TO

T

Hz

63 H

z

125 H

z

250 H

z

500 H

z

1000 H

z

2000 H

z

4000 H

z

8000 H

z

TO

T

Hz

3 243 48 47 46 44 42 40 38 35 48 56 55 54 52 50 48 46 43 56 62 61 60 58 56 54 52 49 62

6 486 53 53 51 50 48 47 44 42 54 61 60 59 58 56 54 52 50 62 67 66 65 64 62 61 58 56 68

9 729 56 55 55 53 52 50 48 46 57 64 63 62 61 60 58 56 54 65 70 69 68 67 66 64 62 60 71

3 486 51 49 48 46 44 42 39 36 49 59 57 56 54 52 50 47 44 57 65 63 62 60 58 56 53 50 63

6 972 55 55 53 52 50 48 46 43 56 63 63 61 60 58 56 54 51 64 69 69 67 66 64 62 60 57 70

9 1458 58 58 57 55 54 52 50 47 59 66 65 65 63 62 60 58 55 67 72 72 71 69 68 66 64 61 73

3 432 51 49 48 46 44 42 39 36 49 59 57 56 54 52 50 47 44 57 65 63 62 60 58 56 53 50 63

6 864 55 55 53 52 50 48 46 43 56 63 63 61 60 58 56 54 51 64 69 69 67 66 64 62 60 57 69

9 1296 58 58 57 55 54 52 50 47 59 66 65 65 63 62 60 58 55 67 72 72 71 69 68 66 64 61 70

3 648 52 51 49 47 45 43 40 37 50 60 59 57 55 53 51 48 45 58 66 65 63 61 59 57 54 51 64

6 1296 57 56 55 53 51 49 47 44 57 65 64 63 61 59 57 55 52 65 71 70 69 67 65 63 61 58 71

9 1944 60 59 58 56 55 53 51 48 60 68 67 66 64 63 61 58 56 68 74 73 72 70 69 67 64 62 74

3 864 53 51 50 48 46 43 40 37 51 61 59 58 56 54 51 48 45 59 67 65 64 62 60 57 54 51 65

6 1728 58 57 55 54 52 50 47 44 57 66 65 63 62 60 58 55 52 65 72 71 69 68 666 64 61 58 71

9 2592 60 60 59 57 55 53 51 48 61 68 68 67 65 63 61 59 56 69 74 74 73 71 69 67 65 62 75

3 972 53 52 50 48 46 44 41 38 52 61 60 58 56 54 52 49 46 60 67 66 64 62 60 58 55 52 66

6 1944 59 57 56 55 53 50 48 45 58 66 65 64 62 61 58 56 53 66 73 71 70 68 67 64 62 59 72

9 2916 61 61 59 58 56 54 52 49 62 69 68 67 66 64 62 60 57 70 75 74 73 72 70 68 66 63 76

3 1458 55 53 52 49 47 45 42 38 53 63 61 59 57 55 52 50 46 61 69 67 66 63 61 58 56 52 67

6 2916 60 59 57 56 54 51 49 46 59 68 67 65 64 62 59 57 54 67 74 73 71 70 68 65 63 60 73

9 4374 63 62 61 59 57 55 53 50 63 71 70 69 67 65 63 61 58 71 77 76 75 73 71 69 67 64 77

3 1944 55 54 52 50 48 45 42 39 53 63 62 60 58 56 53 50 47 61 69 68 66 64 62 59 56 53 67

6 3888 61 59 58 56 54 52 49 46 60 69 67 66 64 62 60 57 54 68 75 73 72 70 68 66 63 60 74

9 5832 64 63 61 60 58 56 53 50 63 72 71 69 68 66 64 61 58 71 78 77 75 74 72 70 67 64 77

Model Dp = 100 Pa Dp = 250 Pa Dp = 500 Pa

Sound power Lw [dB(A)]

150 150

300 150

200 200

450 300

600 300

300 200

400 200

300 300

KP

Sound power Lw [dB(A)] Sound power Lw [dB(A)]

VOLUME FLOW CONTROLLERS

5

Single controller - insulated

-12Sound power level in dB(A)/octave in relation to reference sound power (10 W)

B [m

m]

H [m

m]

v [

m/s

]

Q [m

3/h

]

63 H

z

125 H

z

250 H

z

500 H

z

1000 H

z

2000 H

z

4000 H

z

8000 H

z

TO

T

Hz

63 H

z

125 H

z

250 H

z

500 H

z

1000 H

z

2000 H

z

4000 H

z

8000 H

z

TO

T

Hz

63 H

z

125 H

z

250 H

z

500 H

z

1000 H

z

2000 H

z

4000 H

z

8000 H

z

TO

T

Hz

3 243 39 38 37 35 33 31 29 26 39 47 46 45 43 41 39 37 34 47 53 52 51 49 47 45 43 40 53

6 486 44 44 42 41 39 38 35 33 45 52 51 50 49 47 45 43 41 53 58 57 56 55 53 52 49 47 59

9 729 47 46 46 44 43 41 39 37 48 55 54 53 52 51 49 47 45 56 61 60 59 58 57 55 53 51 62

3 486 42 40 39 37 35 33 30 27 40 50 48 47 45 43 41 38 35 48 56 54 53 51 49 47 44 41 54

6 972 46 46 44 43 41 41 39 36 49 56 56 54 53 51 49 47 44 57 62 60 58 57 55 53 51 48 61

9 1458 49 49 48 46 45 45 41 38 50 57 56 56 54 53 51 49 46 58 63 63 62 60 59 57 55 52 64

3 432 42 40 39 37 35 35 30 27 40 50 48 47 45 43 41 38 35 48 56 54 53 51 49 47 44 41 54

6 864 46 46 44 43 41 41 37 34 47 54 54 52 51 49 47 45 42 55 60 60 58 57 55 53 51 48 60

9 1296 49 49 48 46 45 45 41 38 50 57 56 56 54 53 51 49 46 58 63 63 62 60 59 57 55 52 61

3 648 43 42 40 38 36 36 31 28 41 51 50 48 46 44 42 39 36 49 57 56 54 52 50 48 45 42 55

6 1296 48 47 46 44 42 42 38 35 48 56 55 54 52 50 48 46 43 56 62 61 60 58 56 54 52 49 62

9 1944 51 50 49 47 46 46 42 39 51 59 58 57 55 54 52 49 47 59 65 64 63 61 60 58 55 53 65

3 864 44 42 41 39 37 36 31 28 42 52 50 49 47 45 42 39 36 50 58 56 55 53 51 48 45 42 56

6 1728 49 48 46 45 43 43 38 35 48 57 56 54 53 51 49 46 43 56 63 62 60 59 56 55 52 49 62

9 2592 51 51 50 48 46 44 42 39 52 59 59 58 56 54 52 50 47 60 65 65 64 62 60 58 56 53 66

3 972 44 43 41 39 37 35 32 29 43 52 51 49 47 45 43 40 37 51 58 57 55 53 51 49 46 43 57

6 1944 50 48 47 46 44 41 39 36 49 57 56 55 53 52 49 47 44 57 64 62 61 59 58 55 53 50 63

9 2916 52 52 50 49 47 45 43 40 53 60 59 58 57 55 53 51 48 61 66 65 64 63 61 59 57 54 67

3 1458 46 44 43 40 38 36 33 29 44 54 52 50 48 46 43 41 37 52 60 58 57 54 52 49 47 43 58

6 2916 51 50 48 47 45 42 40 37 50 59 58 56 55 53 50 48 45 58 65 64 62 61 59 56 54 51 64

9 4374 54 53 52 50 48 46 44 41 54 62 61 60 58 56 54 52 49 62 68 67 66 64 62 60 58 55 68

3 1944 46 45 43 41 39 36 33 30 44 54 53 51 49 47 44 41 38 52 60 59 57 55 53 50 47 44 58

6 3888 52 50 49 47 45 43 40 37 51 60 58 57 55 53 51 48 45 59 66 64 63 61 59 57 54 51 65

9 5832 55 54 52 51 49 47 44 41 54 63 62 60 59 57 55 52 49 62 69 68 66 65 63 61 58 55 68

Model Dp = 100 Pa Dp = 250 Pa Dp = 500 Pa

150 150

300 150

200 200

450 300

600 300

300 200

400 200

300 300

KP

Sound power Lw [dB(A)] Sound power Lw [dB(A)] Sound power Lw [dB(A)]

Dual controller

VOLUME FLOW CONTROLLERS

6

B [m

m]

H [m

m]

v [

m/s

]

Q [m

3/h

]

63

Hz

12

5 H

z

25

0 H

z

50

0 H

z

10

00

Hz

20

00

Hz

40

00

Hz

80

00

Hz

TO

T

Hz

63

Hz

12

5 H

z

25

0 H

z

50

0 H

z

10

00

Hz

20

00

Hz

40

00

Hz

80

00

Hz

TO

T

Hz

63

Hz

12

5 H

z

25

0 H

z

50

0 H

z

10

00

Hz

20

00

Hz

40

00

Hz

80

00

Hz

TO

T

Hz

3 1728 55 54 52 50 48 45 42 39 53 63 62 60 58 56 53 50 47 61 69 68 66 64 62 59 56 53 67

6 3456 61 59 58 56 54 52 49 46 60 69 5 66 64 62 60 57 54 68 5 73 72 70 68 66 63 60 74

9 5184 - - - - - - - - - 72 71 69 68 66 64 61 58 71 78 77 75 74 72 70 67 64 77

3 2160 56 55 53 51 48 45 42 39 54 64 63 61 59 56 53 50 47 62 70 69 67 65 62 59 56 53 68

6 4320 61 60 59 57 55 52 50 47 60 69 68 67 65 63 60 58 55 68 75 74 73 71 69 66 64 61 74

9 6480 - - - - - - - - - 72 71 70 68 68 64 62 59 72 78 77 76 74 72 70 68 65 78

3 2592 57 55 53 51 49 46 43 40 54 65 63 61 59 57 54 51 47 62 71 69 67 65 63 60 57 53 68

6 5184 62 61 59 57 55 53 50 47 61 70 69 67 65 63 61 58 55 68 76 75 73 71 69 67 64 61 75

9 776 - - - - - - - - - 73 72 70 69 67 64 62 59 72 79 78 76 75 73 70 68 65 78

3 2700 57 55 53 51 49 46 43 40 54 65 63 61 59 57 54 51 48 62 71 69 67 65 63 60 57 54 68

6 5400 62 61 59 57 55 53 50 47 61 71 69 67 65 63 61 58 55 69 76 75 73 72 69 67 64 61 75

9 8100 - - - - - - - - - 73 72 71 69 67 65 62 59 72 79 78 77 75 73 71 68 65 78

3 3240 57 55 54 52 49 46 43 40 55 65 64 62 60 57 54 51 48 63 71 70 68 66 63 60 57 54 75

6 6480 63 61 60 58 56 53 50 47 61 71 69 68 66 63 61 58 55 69 77 76 74 72 70 67 64 61 75

9 9720 - - - - - - - - - 74 73 71 0 67 65 62 60 73 80 79 77 76 73 71 69 66 79

3 3888 58 56 54 52 50 47 44 40 55 66 64 62 60 58 55 52 48 63 72 70 68 66 64 61 58 54 69

6 7776 64 62 61 59 56 54 51 48 62 71 70 68 67 64 61 59 56 70 77 76 75 73 70 68 65 62 76

9 11664 - - - - - - - - - 74 73 72 70 68 66 63 60 73 81 79 78 76 74 72 69 66 79

500 500

600 500

600 600

400 400

500 400

600 400

Model Dp = 100 Pa Dp = 250 Pa Dp = 500 Pa

KP

Sound power Lw [dB(A)] Sound power Lw [dB(A)] Sound power Lw [dB(A)]

VOLUME FLOW CONTROLLERS

7

Dual controller - insulated

-12 Sound power level in dB(A)/octave in relation to reference sound power (10 W)

B

[mm

]

H

[mm

]

v [

m/s

]

Q

[m3

/h]

63

Hz

12

5 H

z

25

0 H

z

50

0 H

z

10

00

Hz

20

00

Hz

40

00

Hz

80

00

Hz

TO

T

Hz

63

Hz

12

5 H

z

25

0 H

z

50

0 H

z

10

00

Hz

20

00

Hz

40

00

Hz

80

00

Hz

TO

T

Hz

63

Hz

12

5 H

z

25

0 H

z

50

0 H

z

10

00

Hz

20

00

Hz

40

00

Hz

80

00

Hz

TO

T Hz

3 1728 46 45 43 41 39 36 33 30 44 54 53 51 49 47 44 41 38 52 60 59 57 55 53 50 47 44 58

6 3456 52 50 49 47 45 43 40 37 51 60 -4 57 55 53 51 48 45 59 -4 64 63 61 59 57 54 51 65

9 5184 - - - - - - - - - 63 62 60 59 57 55 52 49 62 69 68 66 65 63 61 58 55 68

3 2160 47 46 44 42 39 36 33 30 45 55 54 52 50 47 44 41 38 53 61 60 58 56 53 50 47 44 59

6 4320 52 51 50 48 46 43 41 38 51 60 59 58 56 54 51 49 46 59 66 65 64 62 60 57 55 52 65

9 6480 - - - - - - - - - 63 62 61 59 59 55 53 50 63 69 68 67 65 63 61 59 56 69

3 2592 48 46 44 42 40 37 34 31 45 56 54 52 50 48 45 42 38 53 62 60 58 56 54 51 48 44 59

6 5184 53 52 50 48 46 44 41 38 52 61 60 58 56 54 52 49 46 59 67 66 64 62 60 58 55 52 66

9 776 - - - - - - - - - 64 63 61 60 58 55 53 50 63 70 69 67 66 64 61 59 56 69

3 2700 48 46 44 42 40 37 34 31 45 56 54 52 50 48 45 42 39 53 62 60 58 56 54 51 48 45 59

6 5400 53 52 50 48 46 44 41 38 52 62 60 58 56 54 52 49 46 60 67 66 64 63 60 58 55 52 66

9 8100 - - - - - - - - - 64 63 62 60 58 56 53 50 63 70 69 68 66 64 62 59 56 69

3 3240 48 46 45 43 40 37 34 31 46 56 55 53 51 48 45 42 39 54 62 61 59 57 54 51 48 45 66

6 6480 54 52 51 49 47 44 41 38 52 62 60 59 57 54 52 49 46 60 68 67 65 63 61 58 55 52 66

9 9720 - - - - - - - - - 65 64 62 -9 58 56 53 51 64 71 70 68 67 64 62 60 57 70

3 3888 49 47 45 43 41 38 35 31 46 57 55 53 51 49 46 43 39 54 63 61 59 57 55 52 49 45 60

6 7776 55 53 52 50 47 45 42 39 53 62 61 59 58 55 52 50 47 61 68 67 66 64 61 59 56 53 67

9 11664 - - - - - - - - - 65 64 63 61 59 57 54 51 64 72 70 69 67 65 63 60 57 70

500 500

600 500

600 600

400 400

500 400

600 400

Model Dp = 100 Pa Dp = 250 Pa Dp = 500 Pa

KP

Sound power Lw [dB(A)] Sound power Lw [dB(A)] Sound power Lw [dB(A)]

Installation

VOLUME FLOW CONTROLLERS

8

Rectangular controllers are flanged on both sides for connection with the standard 30 mm ventilation duct flange.The controller can be installed in horizontal, vertical or inclined mounted duct in a manner that the rotational axis of the dampe blade is always in a horizontal position. Also it is necessary to pay attention to the correct mounting direction shown with the air flow direction arrow on the controller. Required length of the straight duct section is Lmin≥3dek before and Lmin≥1,5dek after the the controller. If this lengths are smaller, deviations of the set flow rate can occure and the stated accuracy of the flow rate may not be achived; therefore, such installations are not recommended. Controllers are maintenance free.

AIR FLOW

INCORRECTINSTALLATION

H×B

Lmin = 3×dek

d = ek

2×B×HB+H

CORRECTINSTALLATION

KP

Technical data

Description

Construction

VOLUME FLOW CONTROLLERS

9

CONSTANT VOLUME FLOW CONTROLLERS – CIRCULAR KC

Controller versionsKC - Constant volume flow controller, circularKC-I - Constant volume flow controller, circular – insulated

:

The damper blades shaft is supported by two smooth-running maintenance-free brass bearings. Pneumatic shock absorber smooths out the damping shock impulse, preventing the vibration and oscillation of the damper blade to ensure sensitive responding behaviour and a precise control.

INSULATION CLADDING - 30 mm mineral wool layer with galvanised sheet steel outer

CASING - made of galvanised sheet steel

MECHANISM - control lever mechanism adjusts the spring tension to control the air flow

DAMPER BLADE - provides resistance to the air flow

SHOCK ABSORBER - serves to absorbe the damper blade vibration coused by the air flow

Insulated version:

Controllers are available with 30 mm acoustic and thermal insulation.

CasingShock absorber

Controllever

MechanismDamper blade

Insulation Cladding

KC

400 Q=1000 Q=4000

Q=900

Q=800

Q=2800

Q=2400

Q=560 Q=1560

Q=250 Q=900

Q=180 Q=500

Q=100 Q=280

Q=70 Q=220

Q=45 Q=145

20

30

40

50

60

70

80

90

100

200

300

400

500

600

700

800

900

1000

2000

3000

4000

5000

6000

355

250

315

200

160

125

100

80

Dimensions

VOLUME FLOW CONTROLLERS

10

100

125160

200250

315

400355

Diameter (ØN)

ØN

[mm]

Length (L)

[mm]

80300300

300300

300400

400

400400

Quick selection Table

Order codes

3Q (m /h)

ØN

[m

]m

L

Dimension

3Required flow rate (m /h)

KC/KC-I - - QØN

Constant volume flowcontroller, circular - insulated

Constant volume flowcontroller, circular

KC

4545

Flow rate range in relation to duct cross section

VOLUME FLOW CONTROLLERS

11

Minimum static pressure difference at the controller.

KC

8910

20

30

40

50

6070809010 0

20 0

30 0

50 0

60 070 080 090 01000

30

40

50

60708090

100

20 0

30 0

40 0

50 0

60070 080090 0

1000

2000

3000

4000

5000 1300

= 1,2 kg/ m3

150

Ø80

Ø80

ØØ11

0000

ØØ11

2255

ØØ11

6600

ØØ22

0000

ØØ22

5500

ØØ33

1155

ØØ44

0000

150

1500

ρ

Q [

I/s]

Q [

m/H

0 1 2 3 4 5 6 7 8 9 10 11 12

0

25

50

75

100

125

150

175

200

225

250

v (m/s)

Dp

[P

a]

Legend:

3Q (m /h or l/s)v (m/s)

2A (m )Dp (Pa)

flow rateair velocityeffective outlet areastatic pressure difference

40 010 m/s

3 m/s

*Flow rate calibration possible at air velocities from 3 to 10 m/s

Constant volume flow controller, circular - KC

Flow noise levels [dB(A)]

VOLUME FLOW CONTROLLERS

12

If air is blown into a room, additional attenuation occurs as a result of the duct outlet attenuation and room attenuation and because of that, a reduction in the sound level.

The room and outlet attenuation can be calculated according to VDI 2081. As a rough estimate, approx. 8 dB can be deducted. To maintain a required noise pressure level, it may be necessary to install a suitable sound attenuator between the volume flow controller and the room, or to insulate the duct.

The flow noise is heavily dependent on local conditions, like dimensions of the duct (height, width, length) behind the sound attenuator and the insulation of the duct. The specified data can provide only a reference values. The noise pressure level can rise if there is an additional noise source such as a ventilator or unfavorable air flow conditions. If this additional noise pressure level is smaller than approx. 10 dB of the noise pressure level of the volume flow controller, it will have no increasing effect on the addition of both.

Φ[m

m]

Q [

3m

/h]

63

Hz

12

5

Hz

25

0

Hz

50

0

Hz

10

00

Hz

20

00

Hz

40

00

Hz

80

00

Hz

TO

T

Hz

63

Hz

12

5

Hz

25

0

Hz

50

0

Hz

10

00

Hz

20

00

Hz

40

00

Hz

80

00

Hz

TO

T

Hz

63

Hz

12

5

Hz

25

0

Hz

50

0

Hz

10

00

Hz

20

00

Hz

40

00

Hz

80

00

Hz

TO

TH

z

40 48 47 46 44 42 40 38 35 48 56 55 54 52 50 48 46 43 56 62 61 60 58 56 54 52 49 62

82 53 53 51 50 48 47 44 42 54 60 60 59 58 57 54 52 50 62 67 66 65 64 62 61 58 56 68

125 56 55 55 53 52 50 48 46 57 64 63 62 61 60 58 56 54 65 70 69 68 67 66 64 62 60 71

70 51 49 48 46 44 42 39 36 49 58 57 56 54 52 50 47 44 57 65 63 62 60 58 56 53 50 63

135 55 55 53 52 50 48 46 43 58 63 63 61 60 58 56 54 51 64 69 69 67 66 64 62 60 57 70

200 58 58 57 55 54 52 50 47 59 66 65 65 63 62 60 58 55 67 72 72 71 69 68 66 64 61 73

100 51 49 48 46 44 42 39 36 49 59 57 56 54 52 50 47 44 57 67 63 62 60 58 56 53 50 63

190 55 55 53 52 50 48 46 43 56 63 63 61 60 58 56 54 51 64 69 69 67 66 64 62 60 57 69

280 58 58 57 55 54 52 50 47 59 66 65 65 63 62 60 58 55 67 72 72 71 69 68 66 64 61 70

180 52 51 49 47 45 43 40 37 50 60 59 57 55 53 51 48 45 58 66 65 63 61 59 57 54 51 64

340 57 56 55 53 51 49 47 44 57 68 64 63 61 59 57 55 52 65 71 70 69 67 65 63 61 58 71

500 60 59 58 56 55 53 51 48 60 68 67 66 64 63 61 57 56 68 74 73 72 70 69 67 64 62 74

250 53 51 50 48 46 43 40 37 51 61 59 58 56 54 51 48 45 59 67 65 64 62 60 57 54 51 67

575 58 57 55 54 52 50 47 46 57 66 65 63 62 60 58 55 52 65 72 71 69 68 65 64 61 58 71

900 60 60 59 57 55 53 51 58 61 68 68 67 65 63 61 59 56 69 74 74 73 71 69 67 65 62 75

500 53 52 50 48 46 44 41 38 52 61 60 58 56 54 52 49 46 60 67 66 64 62 60 58 55 52 66

1000 59 57 56 55 53 50 48 45 58 66 65 64 62 61 58 56 53 66 73 71 70 68 67 64 62 59 72

1500 61 61 59 58 56 54 52 59 62 69 68 67 66 64 62 60 57 70 75 74 73 72 70 68 66 63 76

600 55 53 52 49 47 45 42 38 53 63 61 59 57 55 52 50 46 61 69 67 66 63 61 58 56 52 67

1400 60 59 57 56 54 51 49 46 59 68 67 65 64 62 59 57 54 67 74 73 71 70 68 65 63 60 73

2200 63 62 61 59 57 55 53 50 63 71 70 69 67 65 63 61 58 71 77 76 75 73 71 69 67 64 77

1000 55 54 52 50 48 45 42 39 53 63 62 60 58 56 53 50 47 61 69 68 66 64 62 59 56 53 67

2200 61 59 58 56 54 52 49 46 60 69 67 66 64 62 60 57 54 68 75 72 72 70 68 66 63 60 74

3800 65 63 61 60 58 56 53 50 63 72 71 69 68 66 64 61 58 71 78 77 75 74 72 70 67 64 77

315

400

160

200

250

80

100

125

Model Dp = 100 Pa Dp = 250 Pa Dp = 500 Pa

KC

Sound power Lw [dB(A)] Sound power Lw [dB(A)] Sound power Lw [dB(A)]

VOLUME FLOW CONTROLLERS

13

Constant volume flow controller, circular – insulated - KC-I

Φ[m

m]

3Q

[m

/h]

63 H

z

125 H

z

250 H

z

500 H

z

1000 H

z

2000 H

z

4000 H

z

8000 H

z

TO

T H

z

63 H

z

125 H

z

250 H

z

500 H

z

1000 H

z

2000 H

z

4000 H

z

8000 H

z

TO

T H

z

63 H

z

125 H

z

250 H

z

500 H

z

1000 H

z

2000 H

z

4000 H

z

8000 H

z

TO

T H

z

40 38 37 36 34 32 30 28 25 38 46 45 44 42 40 38 36 33 46 52 51 50 48 46 44 42 39 52

82 43 43 41 40 38 37 34 32 44 50 50 49 48 47 44 42 40 52 57 56 55 54 52 51 48 46 58

125 46 45 45 43 42 40 38 36 47 54 53 52 51 50 48 46 44 55 60 59 58 57 56 54 52 50 61

70 41 39 38 36 34 32 29 26 39 48 47 46 44 42 40 37 34 47 55 53 52 50 48 46 43 40 53

135 45 45 43 42 40 38 36 33 48 53 53 51 50 48 46 44 41 54 59 59 57 56 54 52 50 47 60

200 48 48 47 45 44 42 40 37 49 56 55 55 53 52 50 48 45 57 62 62 61 59 58 56 54 51 63

100 41 39 38 36 34 32 29 26 39 49 47 46 44 42 40 37 34 47 57 53 52 50 48 46 43 40 53

190 45 45 43 42 40 38 36 33 46 53 53 51 50 48 46 44 41 54 59 59 57 56 54 52 50 47 59

280 48 48 47 45 44 42 40 37 49 56 55 55 53 52 50 48 45 57 62 62 61 59 58 56 54 51 60

180 42 41 39 37 35 33 30 27 40 50 49 47 45 43 41 38 35 48 56 55 53 51 49 47 44 41 54

340 47 46 45 43 41 39 37 34 47 58 54 53 51 49 47 45 42 55 61 60 59 57 55 53 51 48 61

500 50 49 48 46 45 43 41 38 50 58 57 56 54 53 51 47 46 58 64 63 62 60 59 57 54 52 64

250 43 41 40 38 36 33 30 27 41 51 49 48 46 44 41 38 35 49 57 55 54 52 50 47 44 41 57

575 48 47 45 44 42 40 37 36 47 56 55 53 52 50 48 45 42 55 62 61 59 58 55 54 51 48 61

900 50 50 49 47 45 43 41 48 51 58 58 57 55 53 51 49 46 59 64 64 63 61 59 57 55 52 65

500 43 42 40 38 36 34 31 28 42 51 50 48 46 44 42 39 36 50 57 56 54 52 50 48 45 42 56

1000 49 47 46 45 43 40 38 35 48 56 55 54 52 51 48 46 43 56 63 61 60 58 57 54 52 49 62

1500 51 51 49 48 46 44 42 49 52 59 58 57 56 54 52 50 47 60 65 64 63 62 60 58 56 53 66

600 45 43 42 39 37 35 32 28 43 53 51 49 47 45 42 40 36 51 59 57 56 53 51 48 46 42 57

1400 50 49 47 46 44 41 39 36 49 58 57 55 54 52 49 47 44 57 64 63 61 60 58 55 53 50 63

2200 53 52 51 49 47 45 43 40 53 61 60 59 57 55 53 51 48 61 67 66 65 63 61 59 57 54 67

1000 45 44 42 40 38 35 32 29 43 53 52 50 48 46 43 40 37 51 59 58 56 54 52 49 46 43 57

2200 51 49 48 46 44 42 39 36 50 59 57 56 54 52 50 47 44 58 65 62 62 60 58 56 53 50 64

3800 55 53 51 50 48 46 43 40 53 62 61 59 58 56 54 51 48 61 68 67 65 64 62 60 57 54 67

Model Dp = 100 Pa Dp = 250 Pa Dp = 500 Pa

315

400

80

100

125

160

200

250

KC

Sound power Lw [dB(A)]Sound power Lw [dB(A)] Sound power Lw [dB(A)]

-12 Sound power level in dB(A)/octave in relation to reference sound power (10 W)

Installation

VOLUME FLOW CONTROLLERS

14

Curcular controllers are connected to a duct like a standard ventilation duct fitting.The controller can be installed in horizontal, vertical or inclined mounted duct in a manner that the rotational axis of the dampe blade is always in a horizontal position. Also it is necessary to pay attention to the correct mounting direction shown with the air flow direction arrow on the controller. Required length of the straight duct section is L≥3d before and L≥1,5d after the the controller. If this lengths are smaller, deviations of the set flow rate can occure and the stated accuracy of the flow rate may not be achived; therefore, such installations are not recommended. Controllers are maintenance free.

AIR FLOW

ØN

Lmin = 3 x ØN

min

. 150

KC

INCORRECTINSTALLATION

CORRECTINSTALLATION

VOLUME FLOW CONTROLLERS

15

VARIABLE VOLUME FLOW CONTROLLERS – RECTANGULAR VP

Description

Insulated version:

Variable volume flow controllers are used for pressure-independent volume flow regulation in variable or constant capacity ventilation and air conditioning systems. Controllers can be installed in a supply and extract air systems. The controller consists of a casing, damper blades, flow probes and VAV actuator. Depending on project requirements, variable volume flow controllers can be controlled by the room temperature sensor, air quality sensor or pressure sensor. The controller compares the actual value signal with the setpoint value and sends an output signal to the electric actuator which adjusts the damper blades to maintain the set point value.

CASING - made of galvanised sheet steel

DAMPER BLADES - opposite moving, made of galvanised sheet steel, with sealing. Thermal insulated blades in insulated version

FLOW PROBES - sending the actual value signal to the controller which compares it with the setpoint value and sends an output signal to the electric actuator which adjusts the damper blades to maintain the set point value

ACTUATOR / CONTROLLER - Electric actuator with controll components

Insulated version: Controllers are available with 30 mm acoustic and thermal insulation.

INSULATION CLADDING - 30 mm mineral wool layer with galvanised sheet steel outer cover

Insulation Cladding

Flow Probes

Actuator/ Controller

Blade rotation mechanism

Damper Blades

Casing

VP

Technical data

Construction

60

30

H

H+

60

B

L

B+60

VOLUME FLOW CONTROLLERS

16

Dimensions

Order codes

B [mm] - from 200 to 1000 mm in steps of 100 mm

H [mm] - from 100 to 1000 mm in steps of 100 mm

30

DimensionsRequired minimum and maximumflow rate [m³/h] (if there is nospecification from the customer,controller will be set to thestandard values)

VP/VP-I - - QB×H

Variable volumeflow controller,rectangular - insulated

Variable volume flowcontroller, rectangular

Effective Outlet Area [m²]

H/B 200 300 400 500 600 700 800 900 1000

100 0,017 0,0255

200 0,034 0,051 0,068 0,085 0,102

300 0,051 0,0765 0,102 0,1275 0,153 0,1785 0,204 0,2295

400 0,068 0,102 0,136 0,17 0,204 0,238 0,272 0,306 0,34

500 0,085 0,1275 0,17 0,2125 0,255 0,2975 0,34 0,3825 0,425

600 0,102 0,153 0,204 0,255 0,306 0,357 0,408 0,459 0,51

700 0,1785 0,238 0,2975 0,357 0,4165 0,476 0,5355 0,595

800 0,204 0,272 0,34 0,408 0,476 0,544 0,612 0,68

900 0,2295 0,306 0,3825 0,459 0,5355 0,612 0,6885 0,765

1000 0,34 0,425 0,51 0,595 0,68 0,765 0,85

VP

H

B

300

200

100

400

500

600

700

800

1000

900

200 300 400

OO

PPP

PPPPPPP

PPPPPPP

PP

PPPPPPP

PP

500 600 700 800

P

O

PPPPPP

PPPPPPP

PP

PPPPPPP

PP

PPPPPPP

PP

900 1000

PPPPPP

PP

PPPPPP

PPO

O

OO

O

OO

O

PP

400

0,034

0,119 0,136

O

O

O

O

O

O O O O O

O O

O

VOLUME FLOW CONTROLLERSB

[mm

]

H [m

m]

v [m

/s]

Q [

m3/h

]

12

5 H

z

25

0

Hz

50

0

Hz

10

00

Hz

20

00

Hz

40

00

Hz

12

5

Hz

25

0

Hz

50

0

Hz

10

00

Hz

20

00

Hz

40

00

Hz

12

5

Hz

25

0

Hz

50

0

Hz

10

00

Hz

20

00

Hz

40

00

Hz

12

5

Hz

25

0

Hz

50

0

Hz

10

00

Hz

20

00

Hz

40

00

Hz

3 183,6 46 45 44 43 40 36 52 52 51 51 49 47 58 58 57 57 55 53 65 66 65 65 64 61

6 367,2 52 51 50 49 47 42 57 57 56 55 53 51 62 63 62 61 60 58 68 69 68 68 68 66

9 550,8 57 57 57 55 53 49 63 62 62 60 59 57 63 64 65 64 64 62 70 72 71 71 70 69

12 734,4 59 58 58 56 54 51 66 65 65 63 62 60 69 69 68 68 67 65 72 74 73 74 73 72

3 280,8 47 46 45 44 41 37 53 53 52 52 50 48 59 59 58 58 56 54 66 67 66 66 65 62

6 561,6 53 52 51 50 48 43 58 58 57 56 54 52 63 64 63 62 61 59 69 70 69 69 69 67

9 842,4 58 58 58 56 54 50 64 63 63 61 60 58 64 65 66 65 65 63 71 73 72 72 71 70

12 1123 60 59 59 57 55 52 67 66 66 64 63 61 70 70 69 69 68 66 73 75 74 75 74 73

3 367,2 48 47 46 45 42 38 54 54 53 53 51 49 60 60 59 59 57 55 67 68 67 67 66 63

6 734,4 54 53 52 51 49 44 59 59 58 57 55 53 64 65 64 63 62 60 70 71 70 70 70 68

9 1102 59 59 59 57 55 51 65 64 64 62 61 59 65 66 67 66 66 64 72 74 73 73 72 71

12 1469 61 60 60 58 56 53 68 67 67 65 64 62 71 71 70 70 69 67 74 76 75 76 75 74

3 550,8 49 48 47 46 43 39 55 55 54 54 52 50 61 61 60 60 58 56 68 69 68 68 67 64

6 1102 55 54 53 52 50 45 60 60 59 58 56 54 65 66 65 64 63 61 71 72 71 71 71 69

9 1652 60 60 60 58 56 52 66 65 65 63 62 60 66 67 68 67 67 65 73 75 74 74 73 72

12 2203 62 61 61 59 57 54 69 68 68 66 65 63 72 72 71 71 70 68 75 77 76 77 76 75

3 734,4 50 49 48 47 44 40 56 56 55 55 53 51 62 62 61 61 59 57 69 70 69 69 68 65

6 1469 56 55 54 53 51 46 61 61 60 59 57 55 66 67 66 65 64 62 72 73 72 72 72 70

9 2203 61 61 61 59 57 53 67 66 66 64 63 61 67 68 69 68 68 66 74 76 75 75 74 73

12 2938 63 62 62 60 58 55 70 69 69 67 66 64 73 73 72 72 71 69 76 78 77 78 77 76

3 918 51 50 49 48 45 41 57 57 56 56 54 52 63 63 62 62 60 58 70 71 70 70 69 66

6 1836 57 56 55 54 52 47 62 62 61 60 58 56 67 68 67 66 65 63 73 74 73 73 73 71

9 2754 62 62 62 60 58 54 68 67 67 65 64 62 68 69 70 69 69 67 75 77 76 76 75 74

12 3672 64 63 63 61 59 56 71 70 70 68 67 65 74 74 73 73 72 70 77 79 78 79 78 77

3 1102 52 51 50 49 46 42 58 58 57 57 55 53 64 64 63 63 61 59 71 72 71 71 70 67

6 2203 58 57 56 55 53 48 63 63 62 61 59 57 68 69 68 67 66 64 74 75 74 74 74 72

9 3305 63 63 63 61 59 55 69 68 68 66 65 63 69 70 71 70 70 68 76 78 77 77 76 75

12 4406 65 64 64 62 60 57 72 71 71 69 68 66 75 75 74 74 73 71 78 80 79 80 79 78

3 831,6 51 50 49 48 45 41 57 57 56 56 54 52 63 63 62 62 60 58 70 71 70 70 69 66

6 1663 57 56 55 54 52 47 62 62 61 60 58 56 67 68 67 66 65 63 73 74 73 73 73 71

9 2495 62 62 62 60 58 54 68 67 67 65 64 62 68 69 70 69 69 67 75 77 76 76 75 74

12 3326 64 63 63 61 59 56 71 70 70 68 67 65 74 74 73 73 72 70 77 79 78 79 78 77

3 1102 52 51 50 49 46 42 58 58 57 57 55 53 64 64 63 63 61 59 71 72 71 71 70 67

6 2203 58 57 56 55 53 48 63 63 62 61 59 57 68 69 68 67 66 64 74 75 74 74 74 72

9 3305 63 63 63 61 59 55 69 68 68 66 65 63 69 70 71 70 70 68 76 78 77 77 76 75

12 4406 65 64 64 62 60 57 72 71 71 69 68 66 75 75 74 74 73 71 78 80 79 80 79 78

3 1382 53 52 51 50 47 43 59 59 58 58 56 54 65 65 64 64 62 60 72 73 72 72 71 68

6 2765 59 58 57 56 54 49 64 64 63 62 60 58 69 70 69 68 67 65 75 76 75 75 75 73

9 4147 64 64 64 62 60 56 70 69 69 67 66 64 70 71 72 71 71 69 77 79 78 78 77 76

12 5530 66 65 65 63 61 58 73 72 72 70 69 67 76 76 75 75 74 72 79 81 80 81 80 79

3 1652 54 53 52 51 48 44 60 60 59 59 57 55 66 66 65 65 63 61 73 74 73 73 72 69

6 3305 60 59 58 57 55 50 65 65 64 63 61 59 70 71 70 69 68 66 76 77 76 76 76 74

9 4957 65 65 65 63 61 57 71 70 70 68 67 65 71 72 73 72 72 70 78 80 79 79 78 77

12 6610 67 66 66 64 62 59 74 73 73 71 70 68 77 77 76 76 75 73 80 82 81 82 81 80

200 100

300 100

Dp = 1000 Pa

Type

Dp = 100 Pa

Sound power Lw [dB(A)]

Dp = 250 Pa Dp = 500 Pa

600 200

300 300

200 200

500 200

400 200

200300

400 300

500 300

600 300

17VP

Sound power Lw [dB(A)] Sound power Lw [dB(A)] Sound power Lw [dB(A)]

Flow noise levels [dB(A)]

Siemens GDB 181.1E/3

Wiring diagram:

Conventional controll

The input signal

Actuator / Controller

VOLUME FLOW CONTROLLERS

Nominal torqueTorque: 5 Nm /10NmNominal / maximum rotation angle: 90°/95° ± 2°Operating voltage / frequency: AC 24V ± 20% / 50/60 HzDegree of protection acc. to EN 60529: IP 54Safety class acc. to EN 60730: IIIOperation temperature: 0 - 50°CStorage temperature: -25 ± 70°C

(G)

18

(Y2) (Y1) (YC)

( )

1 7 6 8

(G0) (U)

2 9

ToolMp

Belimo LMV-D3-MP

Belimo MP-Bus® controll

The output signal

Technical data

VP

Installation

AIR FLOW

H×B

H×B

min. 2B

AIR FLOW

min. B

VOLUME FLOW CONTROLLERS

19VP

Rectangular controllers are flanged on both sides for connection with the standard 30 mm ventilation duct flange.Recomended length of the straight duct section before the controller is Lmin≥2B at the bends and Lmin≥B at the take-offs.

VARIABLE VOLUME FLOW CONTROLLERS – CIRCULAR VC

Technical data

Insulation Cladding

Actuator / Controller

Casing

Dimensions

ØN L

CASING - made of galvanised sheet steel

ACTUATOR / CONTROLLER - Electric actuator with controll components

DAMPER BLADE - made of galvanised sheet steel

FLOW PROBES - sending the actual value signal to the controller which compares it with the setpoint value and sends an output signal to the electric actuator which adjusts the damper blades to maintain the set point value

Insulated version: Controllers are available with 30 mm acoustic and thermal insulation.

INSULATION CLADDING - 30 mm mineral wool layer with galvanised sheet steel outer cover

Flow Probes

DamperBlade

VOLUME FLOW CONTROLLERS

20 VC

100

125160

200250

315400

Diameter (ØN)

[mm]

Length (L)

[mm]

550

550550

550550

715715

45

Construction

Insulated version:

Quick selection Table

3Q (m /h)

ØN

[m

]m

Order codes

400

315

250

160

125

100

50

60

70

80

90

100

200

300

400

500

600

700

800

900

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

Vk 2 5 10 15 m/s

DimensionsRequired minimum and maximumflow rate [m³/h] (if there is nospecification from the customer,controller will be set to thestandard values)

VC/VC-I N - - QØ

Variable volume flowcontroller, circular - insulated

Variable volume flowcontroller, circular

VOLUME FLOW CONTROLLERS

21VC

Flow noise levels [dB(A)]

VOLUME FLOW CONTROLLERS

22 VC

Curcular controllers are connected to a duct like a standard ventilation duct fitting.

Recomended length of the straight duct section before the controller:

Installation

VOLUME FLOW CONTROLLERS

23

AIR FLOW

Ø

ØN

min. 2 Ø

min. 2 Ø

min. 2 Ø

ØN

ØN

VC

Actuator control, insulated version

DAMPER CONTROLLERS

24

Description

Manual control

MULTI-BLADE REGULATION DAMPERS – GALVANIZED

Rectangular multi-blade regulation damper with opposite moving blades, used to control or shut of f the air flow in ventilation and air conditioning systems. Made of galvanised sheet steel, unit length 200 mm.

Actuator control

Casing

Blade rotation mechanism

Control lever

Damper blades

Casing

Actuator

Damper blades

CASING - made of galvanised sheet steel

DAMPER BLADES - opposite moving, made of galvanised sheet steel, with sealing. Thermal insulated blades in insulated version

CONTROL LEVER - for manual adjustment according to the scale

BLADE ROTATION MECHANISM - consists of a brass control shaft and synchronized nylon gear wheels with bearings

ACTUATOR - electric actuator, non-spring return / spring return (safety function - in case of a power failure the actuator closes the damper), open-close or modulating control, 24V or 230V power supply

INSULATION CLADDING - 30 mm mineral wool layer with galvanised sheet steel outer cover

Blade rotation mechanism

Insulation Cladding

RZPP

Dimensions

DAMPER CONTROLLERS

25

NOTE: It is possible to produce a damper with the width (B) over 2100 mm, in that case the damper is split in three air shaft openings. When the width (B) is over 1400 mm the damper is split in two air shaft openings.

Width (B) in steps of 50 mm and height (H) in steps of 100 mm.Non-standard dimensions are available upon customer's request.

min

max

200B

2100

H100

1500

Manual control

Actuator control, insulated version

15

30

30

B

B+60

H

H+

60

200

60

30

30

B

B+60

H

H+

60

200

RZPP

DAMPER CONTROLLERS

26

Description

Manual control

MULTI-BLADE REGULATION DAMPERS – ALUMINIUM

Rectangular multi-blade regulation damper with opposite moving blades, used to control orshut off the air flow in ventilation and air conditioning systems. Made of extruded aluminium profiles, unit length 125 mm.

Casing

Casing

Blade rotationmechanism

Control handle

Actuator

Blade rotationmechanism

Damperblades

Damperblades

CASING - made of galvanised sheet steel

DAMPER BLADES - opposite moving, made of extruded aluminium profiles, with sealing gaskets

CONTROL HANDLE - for manual adjustment of the damper blades

BLADE ROTATION MECHANISM - consists of a brass control shaft and synchronized nylon gear wheels with bearings

ACTUATOR - electric actuator, non-spring return / spring return (safety function - in case of a power failure the actuator closes the damper), open-close or modulating control, 24V or 230V power supply

Actuator control

RZPP

Dimensions

DAMPER CONTROLLERS

27

min

max

200B

2100

H210

1510

Actuator control

50

35

25

B

B+70

H

H+

50

125

NOTE: It is possible to produce a damper with the width (B) over 2100 mm, in that case the damper is split in three air shaft openings. When the width (B) is over 1400 mm the damper is split in two air shaft openings.

Width (B) and height (H) in steps of 100 mm.Non-standard dimensions are available upon customer's request.

Order codes

Dimensions

RZPP-material - - controlB×H

Zn - galvanised sheet steelAl - aluminium

Multi-blade regulationdamper, rectangular,opposed

125

95

R - manualM - actuator

RZPP

Manual control

DPt (type B) = Kp x DPt (type A)

CORRECTION FACTOR FOR DPt type B: Kp

1,33

10Kp

0

2,7

40

1,161,15

20

1,25

30

1,21,16

50 60

H/B 200 300 400 500 600 700 800 900 1000

100 0,017 0,0255 0,034 0,0425 0,051 0,0595 0,068 0,0765 0,085

200 0,034 0,051 0,068 0,085 0,102 0,119 0,136 0,153 0,17

300 0,051 0,0765 0,102 0,1275 0,153 0,1785 0,204 0,2295 0,255

400 0,068 0,102 0,136 0,17 0,204 0,238 0,272 0,306 0,34

500 0,085 0,1275 0,17 0,2125 0,255 0,2975 0,34 0,3825 0,425

600 0,102 0,153 0,204 0,255 0,306 0,357 0,408 0,459 0,51

700 0,119 0,1785 0,238 0,2975 0,357 0,4165 0,476 0,5355 0,595

800 0,136 0,204 0,272 0,34 0,408 0,476 0,544 0,612 0,68

900 0,153 0,2295 0,306 0,3825 0,459 0,5355 0,612 0,6885 0,765

1000 0,17 0,255 0,34 0,425 0,51 0,595 0,68 0,765 0,85

Technical data

type A type B

B

B

Dpt(

Pa)

Dpt(

Pa)

DAMPER CONTROLLERS

28

Effective Outlet Area [m²] for galvanized and aluminium multi-blade regulation dampers

RZPP

a

a a

1.5

3.5

1.5

80006500

300

200

50

1100900700

500400

16001300

3500300025001800

55004500

40

10

20

30

10000

1400012000

64 532

Q(m3/h)

15 17 20129 107 8

9500080000

125000110000

33000

4800040000280002400017000

7000060000

150000

0.4

0.04

0,03

1000

150020000,02

60700

200

300400500

150

0.050.06

0.1

0.08

0.2

0.3

0.15

4 1

A f

ace (

m²)

1

0.8

0.50.6

2

2.53

080

3

11

2

1.5

2015

45

10

60

40

80100

30

40

2 3 4 65 127 8 9 10 1715 20

60

Lwa1

=( dB

(A))

55

50

45

70

65

75

Face velocity, pressure loss and sound power level: type A

V face (m/s)

DP

t (P

a)

V face (m/s)

DAMPER CONTROLLERS

29RZPP

a

DAMPER CONTROLLERS

30

Description

Manual control

SINGLE-BLADE REGULATION DAMPERS – RECTANGULAR

Single-blade regulation dampers are mainly used for regulation and balancing of ventilation and air conditioning systems. Blade angle adjustment 0°–90°. Made of galvanised sheet steel with working temperature range from -20°C up to +90°C for manual and +50°C for actuator controlled version. Easy installation and rigid construction.

Actuator control

Casing

Control handle

Damper blade

CASING - made of galvanised sheet steel

DAMPER BLADE - made of galvanised sheet steel

CONTROL HANDLE - for manual adjustment of the damper blade

ACTUATOR - electric actuator, 24V or 230V power supply

Dimensions

Casing

Actuator

Damper blade

B L=H+5020

60

H

min

max

100B

500

H100

500

Width (B) and height (H) in steps of 50 mm.Non-standard dimensions are available upon customer's request.

RZ-P

DAMPER CONTROLLERS

31

Manual control

SINGLE-BLADE REGULATION DAMPERS – CIRCULAR

Actuator control

Casing

Control handle

Damper blade

Casing

Actuator

Damper blade

ØN 80 L

Dimensions

RZ-C

RZC-100

Type

RZC-125

RZC-150

RZC-160

RZC-200

RZC-250

RZC-315

RZC-355

RZC-400

RZC-450

RZC-500

100

125

150

160

200

250

315

355

400

450

500

250

250

250

250

250

350

350

350

600

600

600

Diameter (ØN)

[mm]

Lenght (L)

[mm]

45

Order codes

RZ -material - - controlP/C - dimension

Regulationdamper

P - rectangularC - circular

Zn - galvanised sheet steel - aluminium

Inox – stainless steelAl

DAMPER CONTROLLERS

32 RZ

Regulation Damper

Closed end with connection for round duct

Regulation Damper

Closed end with connection for round duct

Actuator control

B×H - N - circular

rectangularØ

R - manualM - actuator

Manual control

Dimensions

RZC-560

Tip

RZC-600

RZC-630

RZC-650

RZC-710

RZC-800

RZC-900

RZC-1000

RZC-1250

RZC-1400

RZC-1600

560

600

630

650

710

800

900

1000

1250

1400

1600

Promjer (ØN)

[mm]

ØN

ØN

45

ØN+6532,5 203

36380

MULTI-BLADE REGULATION DAMPERS WITH ROUND CONNECTION

Description

Used to control or shut off the air flow in round ducts with diameters over Ø500 mm. It consists of a rectangular multi-blade regulation damper with opposite moving blades and specially constructed connection for the round duct.

Gornjostupnička 126