welcome to basic pump operations !

103
Welcome to Basic Pump Operations ! Basic Pump Operations

Upload: lirit

Post on 25-Feb-2016

55 views

Category:

Documents


1 download

DESCRIPTION

Welcome to Basic Pump Operations !. Hardest class to teach and hardest class to learn. WHY ??. Years of doing it one way and unwillingness to change. Lack of training. Not wanting to look like you don’t know what you’re doing. Fear of math. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Welcome to Basic Pump Operations !

Welcome to Basic Pump Operations

!Basic Pump Operations

Page 2: Welcome to Basic Pump Operations !

Hardest class to teach and hardest class to learn

Basic Pump Operations

WHY ??Years of doing it one way

and unwillingness to change

Lack of training

Fear of mathNot wanting to look like

you don’t know what you’re doing

Page 3: Welcome to Basic Pump Operations !

Basic Pump Operations

Who is the most important firefighter on the fireground ?

Pump operator, of course !Chiefs can give orders, officers can direct, but without the pump operator delivering

enough water, the fire wont go out and the situation will not get better

Are you comfortable with whomever is the pump operator that day or moment ?

Page 4: Welcome to Basic Pump Operations !

Basic Pump Operations

The Golden Truth

There is a difference between simply being assigned as the pump operator and being

a good pump operator

Page 5: Welcome to Basic Pump Operations !

Basic Pump Operations

Learn From Experience

What you should take away from every fire you go to

Whether or not you were the pump operator, find out what the static and residual flow pressures were and how much total water was flowing per minute so next time you have a fire in that area, you have an idea of how much water you have to work with Take a practical look at how much fire you had on arrival. If you only end up using tank water for extinguishment, take a look at how much water is left in the tank after the fire is out. See how much water you needed to put out the amount if fire you had when you first arrived. Write down this information in a log of some sort so you remember it months down the line, otherwise you will forget. If you forget, you have lost this information forever. This is something I refer to as ‘negative experience gain’. Don’t let your past experience go to waste.

Page 6: Welcome to Basic Pump Operations !

Basic Pump Operations

Learn From Experience

What you should take away from every fire you go to

If you weren’t the pump operator, talk to whomever was and find out if they had any problems and what they did to correct them, if they could. Experiment with your nozzles. Test them under different conditions. Can two of your firefighters hold onto a 1 ¾ line flowing 200 gpm ? Not sure ? You should be ! These are some of the key points to remember so you can be a GOOD pump operator, engine company chauffer, engineer, or what ever your department calls you.

Page 7: Welcome to Basic Pump Operations !

Basic Pump Operations

What will be covered in this presentation

Knowing your response area, equipment, and SOP’sHow your pump worksThe basic steps to pump operationsVehicle positioningEngaging the pumpDetermining and establishing water supplyPriming the pumpCalculating total engine pressureNozzles and flow ratesFriction lossTroubleshootingOperating relief valvesPractice problems

Page 8: Welcome to Basic Pump Operations !

Basic Pump Operations

What will not be covered

As I mentioned before, this is an introductory course, meant to give you beginning knowledge and add to your current knowledge. There are other topics you should be aware of and know. Some of them I will cover in my advanced class, some I won’t.

The following topics will not be discussed in this PowerPoint, I am taking some of these topics out of the IFSTA Pumping Apparatus Driver/Operator handbook, which is an excellent book to purchase:

Skills and Physical Abilities Apparatus TestingMaintenance Characteristics Of WaterEmergency Vehicle Driving Water ShuttlesHigh Rise/Standpipe & Sprinkler Operation Foam

Page 9: Welcome to Basic Pump Operations !

Basic Pump Operations

KNOW YOUR…EQUIPMENTPump - HaleTank size - 500 GallonsPump Capacity - 1750 gpm

Pump - WaterousTank size - 750 GallonsPump Capacity - 1250 gpm

Pump - HaleTank size - 2600 gallonsPump Capacity - 1250 gpm

Pump and Tank

Manufacturer ?Tank Size ?

Pump Capacity ?

Page 10: Welcome to Basic Pump Operations !

Basic Pump Operations

KNOW YOUR…AREAWater Supply

HydrantsStatic SourcesWater Flow Capabilities

Building Construction

Type I,II,III,IV,V

Maps

Single Family HomesCommercialMultifamily

Page 11: Welcome to Basic Pump Operations !

Basic Pump Operations

KNOW YOUR…SOP’sPast practice may apply

Who’s getting the hydrant ?Minimum flow rates ?Who’s taking the nozzle ?Who pumps into a standpipe ?LDH or smaller hose ?Forward or reverse lay ?

Page 12: Welcome to Basic Pump Operations !

Basic Pump Operations

How Your Pump Work

s

There are several styles of pumps. Early fire department pumpers used what’s called a positive displacement pump. There are two types of positive displacement pumps, piston and rotary. However, centrifugal pumps are used as the main fire pump on today’s fire apparatus. Positive displacement pumps are still used today as part of the priming system. Their capability to pump air makes them ideal for that purpose. We will discuss the centrifugal pump in this presentation.

Page 13: Welcome to Basic Pump Operations !

Basic Pump Operations

How Your Pump Work

sEvery pump has a plate on it like this one that tells you what the maximum amount of water the pump can flow at 150 psi. All newer pumpers max out their flow at 15o psi. So does that mean that the pump this plate is referring to can only pump a maximum of 1510 gallons per minute ?

Page 14: Welcome to Basic Pump Operations !

Basic Pump Operations

How Your Pump Work

s

The answer is NO…because of a simple concept known as ‘net pump pressure’ or

NPP. This is probably one of the most unknown concepts pump operators will face.

Some operators would look at their discharge gauge and see that it was reading 150 psi and think the pump was maxed out, and its not. When pumps get their ratings, they are rated while drafting at about 6 - 8 feet. When receiving additional pressure from a hydrant or other source, the pump can exceed its rated flow. Even at draft it may be possible to exceed its rated flow if

multiple intake lines are used.

Page 15: Welcome to Basic Pump Operations !

Basic Pump Operations

How Your Pump Work

s

NET PUMP PRESSURE (NPP)

NPP is the pressure that the pump is creating on its own, without any additional pressure from hydrants, pumper relays, etc. It is the difference between intake and discharge pressure Discharge pressure - Intake pressure = NPP Example: If discharge gauge reads 175 psi and residual intake pressure reads 50 psi, the NPP is 125 psi. The pump is not maxed out, yet. Once the NPP hits 150 psi, the pump is not at its max flow

Page 16: Welcome to Basic Pump Operations !

Basic Pump Operations

How Your Pump Work

s

REMEMBER !!!!

An increase in throttle does not always mean an increase in flow. At some point, as your net pump pressure increases past 150 psi, you will actually be flowing LESS water. So monitor your net pump pressure. If your net pump pressure goes above 150psi, you will

be at your maximum pumping capacity. Take a look at the pump plate, and you will see

how the flow drops as the pressure increases past 15o psi.

Page 17: Welcome to Basic Pump Operations !

Basic Pump Operations

How Your Pump Work

s

PTO Pump

Page 18: Welcome to Basic Pump Operations !

Basic Pump Operations

How Your Pump Work

s

Page 19: Welcome to Basic Pump Operations !

Basic Pump Operations

How Your Pump Work

s

Single Stage Pump

Intakes Intakes

Discharges

Impeller

Page 20: Welcome to Basic Pump Operations !

Basic Pump Operations

How Your Pump Work

s

Dual Stage Pump

Page 21: Welcome to Basic Pump Operations !

Basic Pump Operations

How Your Pump Work

sVideo from Waterous Company

Page 22: Welcome to Basic Pump Operations !

Basic Pump Operations

How Your Pump Work

sVideo from Waterous Company

Page 23: Welcome to Basic Pump Operations !

Basic Pump Operations

The General Pump Operator Steps To Follow1. Position Vehicle - Chock Wheels, When Possible2. Engage Pump3. Determine & Establish Water Supply4. Determine Total Engine Pressure

(FL+NP+EL+DL)5. Open Appropriate Discharge Valve6. Throttle Up Or Down As Needed To Set Pressure7. Adjust Pressure8. Monitor Vacuum Side Of Pump9. Monitor Tank Water Level10.Monitor Pump Temperature

We will follow these steps throughout the presentation

Page 24: Welcome to Basic Pump Operations !

Basic Pump Operations

1. VEHICLE POSITIONINGForward

Lay

Direction Of Travel

What type of lay you use is largely dependent on what and where your water source is. If you’re using a hydrant for supply, and you are going to pass the hydrant en route to the building on fire, a firefighter will wrap the hydrant and either re-board the engine or stay at the hydrant to turn it on. Check your local SOP on how to handle that situation.

Attack Line

Supply Line

Page 25: Welcome to Basic Pump Operations !

Basic Pump Operations

1. VEHICLE POSITIONINGForward

Lay

Direction Of Travel

A major benefit of a forward lay is that the engine will be parked directly in front of or close to the building on fire, allowing for quick and easy access to your equipment. The downside of the forward lay is that you either have to leave a firefighter at the hydrant or wait for a second in company to complete the connection. The firefighter at the hydrant wont be available for attack or any other operation until their return to the scene.

Attack Line

Supply Line

Page 26: Welcome to Basic Pump Operations !

Basic Pump Operations

1. VEHICLE POSITIONINGReverse

Lay

Attack Line

Supply Line

Direction Of Travel

A reverse lay would be a situation where the engine goes directly to the fire building, drops off firefighters and necessary equipment along with a stretch of the attack line, and then proceeds to the supply source.

Page 27: Welcome to Basic Pump Operations !

Basic Pump Operations

1. VEHICLE POSITIONINGReverse

Lay

Attack Line

Supply Line

Direction Of Travel

The major advantage to the reverse lay is that the attack line stretch is expedited. The major disadvantage is that the all of the equipment is still on the vehicle away from the scene.

Page 28: Welcome to Basic Pump Operations !

Basic Pump Operations

1. VEHICLE POSITIONINGCommunicatio

ns

Attack Line

Supply Line

Direction Of Travel

Regardless of what type of lay you use, its vital that the pump operator has good communication with whomever is either making hose connections to the hydrant (as in a forward lay) or when the attack team is ready for water as in a reverse lay. If your department has a standard hand signal, or radio communication code, to acknowledge that everyone is ready, learn what those are.

Page 29: Welcome to Basic Pump Operations !

Basic Pump Operations

1. VEHICLE POSITIONINGSome additional vehicle positioning

pointersTry to stay out of the potential building collapse zone. Especially on commercial fires where you are pulling into a parking lot. Eyeball the size of the walls and try to keep at least 1.5 times the distance away.

Have an idea of how long your supply lines are, specifically the lines you use to make direct hydrant connections when the hydrant is close to where you will be operating. You want enough room to make sure the hose plays out without any kinks.

Don’t be nervous about pulling past a building and being ‘too far away’ from the fire because you left the front of the building open for ladder companies to operate. The best thing about hose is that its plenty long and plenty flexible. Its easier to add hose to a stretch than to move fire vehicles around.

Page 30: Welcome to Basic Pump Operations !

Basic Pump Operations

2. ENGAGING THE PUMP1. Position the truck for the best hydrant hookupand discharge hose layout.2. Bring the truck to a complete stop before youattempt to shift from road to pump.3. Apply the truck parking brake.4. Shift the truck transmission to the NEUTRALposition. Wait for the RPM gauge to drop to zero.5. Move the in-cab pump shift control valve fromthe ROAD position to the PUMP position. Theshift warning lights should come on in asecond or two, indicating a complete shift.

Page 31: Welcome to Basic Pump Operations !

Basic Pump Operations

2. ENGAGING THE PUMP cont.If the truck manufacturer has used another in-cabvalve to achieve pump shift or has anelectric switch, follow the instructions suppliedwith that valve.6. After pump shift is completed, put the trucktransmission in the proper pump operatingrange or gear.7. The speedometer should read 5 to 15 MPH after theshift has been completed. If the shift does notseem to be completed, shift truck transmissionto “N” and repeat the entire procedure.

Page 32: Welcome to Basic Pump Operations !

Basic Pump Operations

2. ENGAGING THE PUMP cont.8. Exit the driving compartment only after all theabove steps are completed and you are surethat the shift completed lights in the cab andpanel are on.9. Chock the wheels

DO NOT OPEN THROTTLE UNLESS ALLGREEN PUMP INDICATOR LIGHTS ARE ON.

Page 33: Welcome to Basic Pump Operations !

Basic Pump Operations

3. DETERMINE AND ESTABLISH WATER SUPPLY

Determine where your water supply is coming from. Either one of the following:

1. Tank2. Hydrant

3. Tanker Shuttle4. Relay

5. Pond or Other Static Source

Page 34: Welcome to Basic Pump Operations !

Basic Pump Operations

3. DETERMINE AND ESTABLISH WATER SUPPLYTank Water

1. Typically the initial choice at the scene of a working fire

2. Available until a more steady source is secured

3. Does not last long. A 500 gallon tank flowing 150 gpm will only last a little over 3 minutes. Flowing 250 gpm, you have 2 minutes.

4. Activated by use of tank to pump valve

5. Tanks allow the ability to have foams placed in them and create a pre-mixed solution in order to save time

6. Need to continuously monitor tank water level.

7. Re-fill off hydrant asap to use as back-up

Page 35: Welcome to Basic Pump Operations !

Basic Pump Operations

3. DETERMINE AND ESTABLISH WATER SUPPLY

If operating from tank….

1. Open tank to pump. Allow 30 seconds for the pump to fill.

2. Priming the pump may be necessary because of trapped air

3. Open appropriate discharge valve4. Increase throttle to desired pressure5. Set relief valves if necessary

Page 36: Welcome to Basic Pump Operations !

Basic Pump Operations

3. DETERMINE AND ESTABLISH WATER SUPPLY

1. Hydrants are usually the source of choice for constant water supply.

2. Flow rates vary, from several hundred gallons to nearly 2000 gpm.

3. Usually located every 300 feet 4. Will determine whether you have a

reverse or forward lay5. Can connect to either front, side or rear

of vehicles6. Must not let residual pressure drop

below 20 psi

Hydrants

Page 37: Welcome to Basic Pump Operations !

Basic Pump Operations

3. DETERMINE AND ESTABLISH WATER SUPPLY

Transitioning From Tank Water To Hydrant

At some point, your tank will run empty and you will need to switch over to your alternative water supply. This is a delicate procedure that needs to be practiced routinely. Of course, you

should make the switch BEFORE you run out of water. Pressures from the hydrant will most likely vary from what your

current total engine pressure. Usually the hydrant will be higher. It will be important to know if your vehicle’s tank to

pump (TTP) valve has a check valve that will not allow hydrant pressure to back fill the tank. This was an NFPA requirement dating back to the early 90’s. If this is the case, you may be

allowed to leave the TTP valve open when making the switch. Keeping the valve open will allow there to be an unimpeded

flow of water if the hydrant were to fail. It would also give the engineer, OIC, and interior teams time to come up with an

alternative option or retreating time. Check your local protocol and pump set up.

Page 38: Welcome to Basic Pump Operations !

Basic Pump Operations

3. DETERMINE AND ESTABLISH WATER SUPPLY

Transitioning From Tank Water To HydrantProcedure

This procedure assumes you are already in pump gear and that you have been flowing water at the appropriate pressure and now notice that your tank water is low enough to begin the switch

1. Open the bleeder valve of the supply line to allow air to escape and not enter the pump

2. Once water is flowing out of the bleeder, close the bleeder3. Remove the cap off the intake you are using and connect

the hose. If you are using a piston intake valve, connect the hose

4. Make sure the hydrant you are using has been flushed and the proper fittings attached according to your SOP

5. Set relief valves

Page 39: Welcome to Basic Pump Operations !

Basic Pump Operations

3. DETERMINE AND ESTABLISH WATER SUPPLY

Transitioning From Tank Water To HydrantProcedure

6. Open the hydrant slowly to make the switch. As you are opening the hydrant, you can close the tank to pump, if necessary. You may need to make throttle adjustments.

7. Close tank fill and re-circulating valves after tank has reached full. If tank fill was not open, crack the tank fill until your tank is full, so you have the back-up water if you need it.

8. If discharge lines are shut down at any point after this, re-open tank to pump and tank fill to re-circulate water.

Page 40: Welcome to Basic Pump Operations !

Basic Pump Operations

3. DETERMINE AND ESTABLISH WATER SUPPLY

If operating from hydrant….

1. Communicate to firefighter making hydrant connection that you are ready for water

2. Open bleeder valves for the suction line to bleed out air.

3. Open intake valve and read the static pressure, if possible

4. Open appropriate discharge valve5. Increase throttle to desired pressure6. Set relief valves if necessary

Page 41: Welcome to Basic Pump Operations !

Basic Pump Operations

3. DETERMINE AND ESTABLISH WATER SUPPLYREMEMBER !!!!

There is friction loss in supply lines when connected to

hydrants, relays, etc. Know how much total water you are discharging and be sure

you are not discharging more water than you know is

possible as supply from the hydrant.

Page 42: Welcome to Basic Pump Operations !

Basic Pump Operations

3. DETERMINE AND ESTABLISH WATER SUPPLY

Priming the pump

Sometimes air can get trapped in the pump and cause you to ‘lose prime’. Fire pumps are good at pumping water, not so good at pumping air !

Priming is not always necessary If pump is kept wet, priming should normally not be needed Head pressure created by onboard tank and hydrant pressure are usually enough to prime the pump. You must have an open discharge or tank fill open in order for this to work Make sure bleeder valves are open on intake valves to bleed off air.

Page 43: Welcome to Basic Pump Operations !

Basic Pump Operations

3. DETERMINE AND ESTABLISH WATER SUPPLY

Priming the pump

If you need to use the primer valve

This would be most necessary if you are drafting from a static water source.

1. Engage the pump2. Connect hydrant supply hose to truck3. Open hydrant supply bleeder4. Close all discharges5. Engage primer6. Check for prime - when discharge

changes from oil and air to oil and water, you have prime. There may also be a sound change

7. You should a positive change in discharge pressure

Page 44: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

The Total Engine Pressure PieNozzle Pressure

Friction LossElevation LossDevice Loss

TEP = NP + FL + EL + DLSo how do we determine our required operating pressures ? There are four

pieces of information that are listed below that you will need in order to find out what your operating or, total engine pressure needs to be so that you are

delivering the appropriate amount of water out of your nozzles

Page 45: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLAs much as the 4 parts of the total engine pressure (TEP) pie as listed above and on the previous slide are important, the biggest question to ask yourself as you are determining what your TEP will be, is…

“What is my flow rate ?”

In other words, how much total water will I be flowing out of nozzles, master streams, etc. ?

Remember that question because that will always be your starting point in determining TEP.

Page 46: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLWhen we talk about total engine pressure what exactly are we talking about ? We are trying to figure out what this gauge on the right should be reading. This is the main discharge gauge usually found on the right side of the pump panel. It usually says ‘PRESSURE’ as opposed to ‘VACUUM’ for the intake gauge. The formula above will give you that answer. Don’t get caught up in friction loss only. Friction loss is only one piece of the pie

Page 47: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLNozzles &

Nozzle PressureNozzles help us determine our

flow rate or how much water we are flowing out of the nozzle. ‘Nozzle pressure’ or NP in the formula refers to the amount of pressure required at the nozzle in order for the nozzle to operate properly. Depending on the nozzle, the pressures vary. If a nozzle were to say operate at 100 psi, for example, that means if we put a gauge at the end of the line before the nozzle, it would need to read 100 psi for the nozzle to work right.

Page 48: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLThe smooth bore, fog nozzle

debate This is an ongoing debate that will never end. Each side has good points and bad points My own personal suggestions: Heavy, advanced fire and a direct attack = smooth bore nozzle Indirect attack, fog nozzle Foam applications, fog nozzle Standpipe operations, smooth bore Exposure protection, fog nozzle Let your own personal experience dictate which one you choose

Page 49: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DL

Smooth Bore

Nozzle(Flow rates

depend on tip size)

30-300 gpm @ min. 50 psi

The smooth bore nozzles resurgence in recent years has led to many firefighters believing this is a do all end all nozzle. As good as this nozzle is, remember the previous slide, which suggests choosing the right nozzle for the right job. The smooth bore offers easy tip adjustment if needed (Stacked tips). Low operating pressures are also ideal for low pressure areas and high rise operations. The reach of the nozzles is also excellent. The resistance to become clogged with small rocks and other debris is an added safety feature. One important point to note is that they operate at 50 psi. It should be noted they operate at a minimum of 50 psi, but they will pump more at higher psi’s. You will get more flow, but higher nozzle reaction, so be careful.

Page 50: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DL

Automatic NozzleDesigned to maintain 100 psi (or close to it) at the nozzle and compensate

for pressure and flow fluctuations60-200 gpm @ 100-200

psi

Page 51: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DL As the debates on nozzles go, the automatic

nozzle is not far behind the smooth bore in its controversy. The original automatics were created to control water flow fluctuations during master stream operations. The nozzle has a spring loaded baffle that will adjust the stream as the pressure decreases or increases. When the pressure is low, the baffle retracts to ‘tighten’ the stream and increase reach. This had lead to the “good looking stream” with not enough gpm’s. This good looking stream used to be good until departments realized they were sacrificing flow for reach. Reach isn't going to be effective if the amount of water is not enough. Akron Brass actually stopped making this type of nozzle in early 2002. They are bulky and expensive as well. Pump operators and nozzle operators become dangerously unaware of flow changes because of the nozzles ability to automatically adjust. There can be sudden changes in flow that result in sudden changes in nozzle reaction force, which could injure firefighters.

Automatic Nozzle

Page 52: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DL Adjustabl

e Gallonag

e Constant

Flow95-200 gpm

@ 100 psi for 1

¾”95-250 gpm

@ 100 psi for

2 ½”

This is one of our standard nozzles, and widely popular in the fire service for it’s ability to provide a fog stream and ‘straight stream’. Mind you that the straight stream on this nozzle is not the same as a stream from a smooth bore nozzle. The nozzle has a ring on it that allows the nozzle operator to adjust the flow as necessary. The pump operator must know what the nozzle is set at. Check your nozzles in the morning to see what they are set at so you can provide the right discharge pressures. Another problem with this nozzle is what I call “Control of the ring” that adjusts the flow. It can accidentally be changed and therefore suffer an unknown change in flow. The firefighters on the line must communicate with the pump operator so the P.O. can adjust the pressure when needed.

Page 53: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

CombinationSmooth Bore and

Fog

1” tip Smooth Bore = 210 gpmFog Pattern - 135 gpm

This is a unique nozzle that combines the smooth bore concept and fog concept in one nozzle. It seems like a great idea, but this one falls a bit short. Our department has these nozzles on our engine, but we caution our firefighters NOT to use them on fog for a fire attack due to the low flow, we have other nozzles that are better for that use. We have one on our 2 ½ line and one on our 1 ¾ line, they both flow the same amount !! Bizarre. Can also be dangerous to other departments who may use them and be unfamiliar with them. They could open up in fog thinking they were in smooth bore. Very bulky as well, and do not automatically adjust when switched from smooth bore to fog.

Page 54: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLWhat are the operating

pressures of our nozzles ? Lets talk about the nozzles we have here first and how they work.

Fixed Pressure

Fixed Gallonage

(AKALow Pressure

Fog)150 gpm @ 75 psi

We have these on the volunteer department I work for. They are nice because of their simplicity. It is one pressure and one set gallonage. Very easy for pump operators to remember. But that can also be part of the problem. You are stuck with one set gallonage. If in the case of the nozzle pictured, you need more that 150 gpm, you are in trouble. There are other styles with higher GPM’s available if that’s what you need.

Page 55: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLMaster

StreamsGreater

than 300 gpm @ 80

psi

Page 56: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DL

Master Streams

80 psi

Smooth Bore

Min50 psi

Adjustable Gallonage Constant Flow

100 psi

Combination fog and smooth bore

50 and 100 psi

Fixed Gallonage - Fixed Pressure

50, 75 and 100 psiREVIE

W

Page 57: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DL

Friction Loss

Friction loss is defined as the resistance to flow. In the fire service, friction loss is caused by water coming in contact with the hose, and the water coming in contact with itself. For a given size of hose, the more you try to ‘push’ through it, the more friction loss you get. We measure this loss in pounds per square inch, or psi.

How do we determine friction

loss ?

Page 58: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLHow do

we determine friction

loss ?

Friction Loss Formula

FL =C*Q2*LC = coefficientQ = gpm/100

L = hose Length

Page 59: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLHow do

we determine friction

loss ?

Of all the methods available for determining friction loss, using the friction loss formula is the hardest for most firefighters to use. You can, however, with constant practice, use this method effectively. It is a great method for pre-determining your specific attack lines. The absolute most exact method to determine friction loss would be to attach in line gauges with flow meters and test your own hose yourself. That’s assuming you have all those items, many fire departments do not.

Friction Loss Formula

Page 60: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLHow do we determine

friction loss ?Friction Loss Formula Example

You are the pump operator and are on the scene of a working fire. You need to determine the friction loss for a 200’ long 1 ¾” line flowing 200 gpm.

FL =C*Q2*LThe coefficient for 1 ¾” hose is 15.5 FL = 15.5*Q2*LQ is gpm/100 then squared FL = 15.5*(200/100)2*LL is length/ 1oo FL = 15.5*(200/100)2*200/100So… FL = 15.5*4*2Finally FL = 124 psi

FL =C*Q2*LC =

coefficient (listed below)

Q = gpm/100L = hose Length

Coefficients

1” hose is -150

1.5" -24.01.75"-15.5

2" - 82.5" -2 3" -0.84" -0.2

5" -0.08

Page 61: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLHow do

we determine friction

loss ?

Slide Calculator

The slide calculator is a good way to determine friction loss. The problem with the calculator is, is you have to buy one. I use the one pictured above, made by Akron Brass. They are about 20 dollars or so.

Page 62: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSUREHow do we determine

friction loss ? Slide Calculator

So where do we start when determining friction loss using the slide calculator ? Same place we start with every other method, yes, you should know it by now, we start with the question “What is our flow rate ?” The calculator will help you determine what your flow rate is if you’re not sure, but only if you’re using a smooth bore nozzle. Otherwise you will need to find that information out.

Page 63: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSUREHow do we determine

friction loss ? Slide Calculator

If you want to know what you are flowing using a smooth bore nozzle, go to the side of the calculator shown above. On the top of the calculator, set your nozzle pressure (arrow 1), in this case it is set at 50 psi for a handline. Go to line 2 and locate the tip size listed just above the line that you are using. Lets say we are using a 7/8” tip. Locate 7/8” above line 2. The number below 7/8” will indicate your flow rate for a 7/8” tip smooth bore nozzle at 50 psi. Which in our example would be 160 gpm. I will explain lines 3,4, and 5 later.

32

1

4

5

Page 64: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSUREHow do we determine

friction loss ? Slide Calculator

All right, so we know what our flow rate is, what’s next ? Flip the calculator over to the side listed above with “U.S. GPM FLOW” on top. In line 1, slide the calculator over to the appropriate flow rate, in this example we are using the 160 gpm number from the previous slide. Go to line 2 and locate the hose size in the white section. The handline, for the example, is let’s say an 1 ¾” line. If you follow the 1 ¾” mark to the numbers above, you will see the number 40. So, 40 psi would be your friction loss PER 100 feet. If we were using a 200 foot line, our example would have an 80 psi total friction loss, 40 psi for each 100 foot section.

3

2

1

Page 65: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSUREHow do we determine

friction loss ? Slide Calculator

The list of black numbers just below line 2 would be the numbers you would use if you were using multiple lines to supply the given flow rate. For example, if you were using 2 lines to flow our 160 gpm, (we were using 1 ¾” lines) the friction loss would be 10 psi. You do have to use the same size lines to use this part of the slide calculator. Line 3 would be used for 3 or 4 lines to supply a given flow rate.

3

2

1

Page 66: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSUREHow do we determine

friction loss ? Slide Calculator

Getting back to lines 3,4, and 5 from the “NOZZLE PRESSURE” side of the calculator. This side of the calculator, if you remember, allows you to determine flow rates. Lines 3,4, and 5 let you know what your flow rates are for fog nozzles when you either over or under supply the tip. We know nozzles operate at different pressures, but if for some reason your supply pressures cant supply 100 psi at the nozzle (If that is the operating pressure of the nozzle), you can flow them at under that amount.

32

1

4

5

Page 67: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSUREHow do we determine

friction loss ? Slide Calculator

Using the above example, let’s say you are using a fog nozzle that operates at 100 psi. You don’t have enough pressure to maintain that 100 psi operating pressure, so you decide to operate it at 50 psi. Go to line 3. If the nozzle is set at 125 gpm on the collar (or whatever the flow rate), look at line 4 to see what you are actually flowing. In reality you would be flowing about only 90 gpm. If you had a nozzle that operates at 75 psi, go to line 5. A 75 psi nozzle operating at 50 psi with the collar set at 125 would only be flowing about 100 gpm.

32

1

4

5

Page 68: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLHow do

we determine friction

loss ?

Pump ChartFlow charts are usually ‘home made’ items that someone in your department ends up making. You can put whatever information on your charts you would like. Coming up in the following slides, I will explain how to use the charts I created.

Page 69: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLHow do

we determine friction

loss ?

Pump ChartThe pump chart has, for me, become my method of choice for determining friction loss. I enclosed a copy of the pump chart we use here in my department. Keep in mind these are theoretical flows. For them to be perfect, you would need to flow test your own hose. However, I have used these numbers repeatedly for years and they are near exact, varying maybe by about 5 psi when used with our flow meters to confirm.

Page 70: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLPump Chart

To use the pump chart I have provided, use the following steps:1. There are two charts on the page. The chart on top is needed

when using smooth bore tips. If you are using any other nozzle, go to chart 2.

2. Determine what your flow rate is, depending on the nozzle. If you are using a smooth bore, locate the psi you will be using on the left side, usually 50 psi for handlines and 80 psi for master streams. Then locate the tip size on the top. The point they intersect will be the flow rate. Take that number to chart 2.

3. Start by locating the closest flow rate in GPM on the left hand side. If the rate is not exact, you can move to the next highest number. Next, locate the hose size across the top. The point they intersect will be the friction loss per 100 ft. of hose.

Page 71: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLPump Chart

To use the pump chart I have provided, use the following steps:

4. I listed information on the side I felt was helpful to me and my department. I included total engine pressures for some of our pre-connects. It seems like that would not be necessary since the charts you need to come up with those answers are right next to you. This was just something I did, if you want to do something else, please do so.

Page 72: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLElevation

LossFor every floor, add

5 psi to your calculation. If you're going

downhill, for every 10 ft, subtract 5 psi

What is the elevation loss for this building ?

Page 73: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLDevice Loss

As water passes through objects such

as deck guns, portable monitors, gated wyes, gated

manifolds, etc, there is pressure loss. This

can be figured anywhere from 5 psi for a small gated wye

to 25-35 psi for manifolds

Page 74: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLPractice ProblemsProblem 1

You arrive on the scene of a working house fire and are ordered to stretch a 200 foot 2 ½” attack line. The line has a fixed pressure, fixed gallonage (FP/FG) nozzle. What is your discharge pressure ? Assume your nozzle is a 75 psi 250 gpm

Problem 2

En route to a car fire on I-71, you are told by the OIC that you will be stretching the front bumper line to fight the fire. The line is a 150 foot long 1 ¾” line with an adjustable gallonage constant flow nozzle set at 150 gpm. What is the discharge pressure ?

Page 75: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

TEP = NP + FL + EL + DLPractice ProblemsProblem 3

The ‘Smithville FD’ is requesting mutual aid to The Regal Park Apartment Building in their city for an apartment fire. You are the pump operator and arrive on scene to find fire blowing out of the 3rd floor window. Their captain has ordered your company to stretch a 250 foot 2 ½” attack line with a 1” tip smooth bore nozzle on it. What is your discharge pressure ?

Problem 4

The tones go off at 3 a.m. for a large fire at the nearby lumber company. While en route, you are ordered by the chief already on scene to set up for master stream operations. What would be your discharge pressure ? Your master stream tip is 1 3/8”.

Page 76: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

Practice Problems AnswersProblem 1You arrive on the scene of a working house fire and are ordered to stretch a 200 foot 2 ½” attack line. The line has a fixed pressure, fixed gallonage (FP/FG) nozzle. What is your total engine pressure ? Assume your nozzle is a 75 psi 250 gpm model.

ANSWER : 101 psi (using the pump chart and friction loss calculator) Explanation of pump chart method below

First question to ask yourself, “What is my flow rate ?” ..the answer is in this case 250 gpm. Using the chart, you can skip the first chart because this isnt a smooth bore nozzle so go to chart 2. Find 250 gpm on the left hand side. Follow it over to the 2 ½ “ hose, and you will see 13, for 13 psi loss per 100 feet. Since there is 200 feet here, you double the 13 psi to get 26 psi friction loss. 26 psi plus the 75 psi for the nozzle, with no elevation loss or gain and no device loss, puts you at a total discharge pressure of 101 or simply 100 psi.

Page 77: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

Practice Problems AnswersProblem 2En route to a car fire on I-71, you are told by the OIC that you will be stretching the front bumper line to fight the fire. The line is a 150 foot long 1 ¾” line with an adjustable gallonage constant flow nozzle set at 150 gpm. What is the discharge pressure ?

ANSWER : 145 psi (using the pump chart and 154 psi using the slide calculator) Slide rule explanation below

On the side of the slide rule with the U.S. GPM FLOW on top, slide the calculator over to the 150 mark. Go to the middle white row section, the one just below the white U.S. GPM FLOW section. Find the 1 ¾” mark in the block. Locate the amount of friction loss on top of the block, denoting a single line flow.

Page 78: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

Practice Problems AnswersProblem 3The ‘Smithville FD’ is requesting mutual aid to The Regal Park Apartment Building in their city for an apartment fire. You are the pump operator and arrive on scene to find fire blowing out of the 3rd floor window. Their captain has ordered your company to stretch a 250 foot 2 ½” attack line with a 1” tip smooth bore nozzle on it. What is your discharge pressure ?

ANSWER : 85 psi (both the pump chart and slide calculator were nearly identical)

Your flow rate here is 210 gpm. You figured that out by starting with chart 1, since you are using a smooth bore nozzle at 50 psi, the minimum pressure. Take your 210 gpm and go to chart 2. Find the closest match to 210 gpm. In this case you round up to 220. Follow that over to the 2 ½” block, and you will see 10 psi friction loss per 100 feet. For a 250 foot line, that would be 25 psi loss. There are 3 stories, but 2 above the ground floor. You can include or exclude the first floor, the 5 psi difference should not be too detrimental. Excluding it, you have 10 psi elevation loss. There is generally considered to be no friction loss in the standpipe, usually a 4” line. So add the 25 psi for friction loss, 10 psi for elevation, and 50 psi for the nozzle, and you get 85 psi.

Page 79: Welcome to Basic Pump Operations !

Basic Pump Operations

4. CALCULATING TOTAL ENGINE PRESSURE

Practice Problems AnswersProblem 4The tones go off at 3 a.m. for a large fire at the nearby lumber company. While en route, you are ordered by the chief already on scene to set up for master stream operations. What would be your discharge pressure ? Your deluge/ deck gun master stream tip is 1 3/8”.

ANSWER : It varies, but approximately 95 psi

The reason this answer varies is because of the device loss. I have routinely used 15 psi friction loss as my deluge gun friction loss standard. Otherwise, this is a pretty easy one to figure out. Your nozzle is a 1 3/8” tip smooth bore. Go to chart one and find 1 3/8”. Remember, master streams operate at a minimum of 80 psi. In this case, there is no hose friction loss, just device loss. So 80 psi for the tip, and 15 psi for the device puts you at 95 psi. Keep in mind, if you have a master stream device with fog nozzles on them, it’s a distinct possibility they operate at 100 psi.

Page 80: Welcome to Basic Pump Operations !

Basic Pump Operations

Operating The Relief ValveThe main function of the relief valve is to divert excess pressure surges from the firefighters operating on the attack lines.

Common Misconceptions Regarding The Relief

Valve

The valve does not dump water onto the ground. It sends the water back into the suction side of the pump

The spring does not develop a memory. You can leave it preset.

There are actually two types of relief valves. Most are familiar with the DISCHARGE relief valve. There is also an INTAKE relief valve.

Some vehicles have a pressure governor that

controls pressure surges by reducing

the rpm’s of the engine.

More on the pressure governor

in later slides

Page 81: Welcome to Basic Pump Operations !

Basic Pump Operations

Operating The Relief Valve

Pilot ValveOften confused with the relief valve, the pilot valve controls the relief valve

4 Way Valve

Page 82: Welcome to Basic Pump Operations !

Basic Pump Operations

Operating The Relief ValveThe main function of the relief valve is to divert excess pressure surges from the firefighters operating on the attack lines.

Pilot ValveOften confused with the relief valve, the pilot valve controls the relief valve

Page 83: Welcome to Basic Pump Operations !

Basic Pump Operations

Operating The Relief Valve

BEFORE YOU SET THE RELIEF VALVE…

1. There has to be a 50 psi differential between intake and discharge pressure

2. If your required discharge pressure is below 90 psi, the relief valve will not work

3. You must have multiple lines flowing in order for it to work. Tank fill can be one of the lines.

Page 84: Welcome to Basic Pump Operations !

Basic Pump Operations

Operating The Relief Valve1. After making sure the previous rules are checked,

go back to your discharge gauge and make sure the pressure is correct.

2. Increase your throttle to go about 5 psi above your operating pressure. This is done so that the relief valve doesn’t open for minor pressure surges. Lets pretend that our operating pressure is 15o psi. In this case we would set it to 155 psi.

3. For the Waterous relief valve, you would switch the on/off switch (4 way valve) to the on position. For the Hale, continue to step 4.

4. Make sure the light is not on to indicate that the valve is open. If it is, you will need to increase the pressure to get the light to turn off.

5. With the light off, rotate the control knob counter-clockwise until the light comes on.

Page 85: Welcome to Basic Pump Operations !

Basic Pump Operations

Operating The Relief Valve6. When the light comes on, stop and rotate the

control knob clockwise until the light goes off. Once the light goes off, rotate the handle back about a half turn back counterclockwise. The relief valve is now set.

Page 86: Welcome to Basic Pump Operations !

Basic Pump Operations

Operating The Relief Valve

This is a diagram of the entire relief valve system. In this

example, the diagram is showing the flow of water when the relief valve opens in a pressure surge

situation.

Page 87: Welcome to Basic Pump Operations !

Basic Pump Operations

Operating The Relief Valve

I have a demonstration on the next slide of how to operate the relief valve. The demo will begin once you click the slide. As the

demo starts, each step described along the right side will blink. After the blink is over, you will see the operation occur. There

will be a 5 second delay in-between steps.

Page 88: Welcome to Basic Pump Operations !

Basic Pump Operations

Operating The Relief Valve1. Increase your

throttle to 155 psi, 5 psi above our example of 150 psi .2. Turn on/off switch to the on position3. Rotate pilot valve counterclockwise until open light comes on.4. When the open light comes on, rotate the pilot valve slowly clockwise until the open light turns off and the closed light comes on5. Once the closed light comes on, rotate the pilot valve counterclockwise ½ or 1 full turn

Page 89: Welcome to Basic Pump Operations !

Basic Pump Operations

5-7. Open Appropriate Discharge1. Check to see which line needs to be opened. SLOWLY

open the line and adjust pressure.2. If multiple lines need to be opened, you need to

determine the operating pressure for all the lines.3. Find the line that has the highest operating pressure

and set the main discharge for that pressure.4. Use the controls and gauges for the other lines and gate

them down to the proper pressure.

Always open and close all

valves slowly !

Page 90: Welcome to Basic Pump Operations !

Basic Pump Operations

8-10. Monitor1. Monitor your vacuum pressure. Make sure your residual

pressure pressure does not drop below 20 psi.2. Monitor tank water level3. Monitor pump temperature

1. Recirculate pump water to prevent overheatinga. Use recirc valveb. crack tank to pump ½ way

2. Feel your intakes for heat build upBAD RANGE

Page 91: Welcome to Basic Pump Operations !

Basic Pump Operations

Pressure GovernorsToday’s newer fire apparatus may contain what is called a pressure governor. The pressure governor is an electronically controlled device that does a number of functions. It’s primary function is to control the pressure of the pump. It does this by way of controlling the engine RPM’s. It also acts as a replacement for the discharge relief valve. When an attack line is shut down, the governor will react by decreasing the RPM’s. You set the discharge pressure by pressing an up or down button. There are many different types of governor’s, so you will have to acclimate yourself to the type of governor you have. The one I’m familiar with is the Class 1 Captain Pressure governor, which is picture above in the left hand corner. It takes some

This Replaces

This

And This

time to get used to these, especially if you’re used to the old style vernier throttles. We will review the Captain governor and its operation.

Page 92: Welcome to Basic Pump Operations !

Basic Pump Operations

Pressure Governors1. Follow all previous instructions and department SOP’s on getting your

pump into gear and to the point you are out of the vehicle and now in front of the pump panel.

2. When initially powered on, the pressure governor will default to [MODE] on the display. If you are going to operate from the tank or a hydrant for your INITIAL water supply, you should start in pressure mode.

3. If drafting from a static water source such as pond or tanker shuttle, you should start in RPM mode.

4. Press the [MODE] button once to go into pressure mode. The display will read ‘pressure’. After you have figured out what your total engine pressure should be, you can either select your preset button or throttle up using the yellow ‘INC’ and ‘DEC’ buttons. You will have to determine what your factory set ‘preset’ pressure is.

5. Open appropriate discharge valves and the governor will automatically throttle up to adjust.

6. Gate back the controls as necessary on other attack lines to their appropriate pressure.

Page 93: Welcome to Basic Pump Operations !

Basic Pump Operations

Pressure GovernorsItems To Be Aware Of When Using A Pressure

GovernorDO NOT fall victim to the belief that you can hit the preset button and walk away. The preset on the attack lines on our engine where I work is the incorrect pressure for all of the lines.

Make sure that you are in PSI mode when attack lines are in use, or you will not have the protection of the governor for pressure spikes.

If on hydrant pressure alone, you will NOT have pressure surge protection, regardless of what mode the governor is in.

When making the transition from tank to hydrant, you need to switch to RPM mode and throttle down, the manufacturer does not feel the governor can react quickly enough to hydrant surges to offer the optimal protection

It it also critical to rid your mind of the commonly heard phrase “Set it and walk away”. Despite the fact pressure governors help us out, you as the pump operator are still responsible for any problems, and problems can occur. Please take the time to look over the owners manual and know what to do when certain prompts appear on the display.

Page 94: Welcome to Basic Pump Operations !

Basic Pump Operations

TROUBLESHOOTINGTroubles with pumping can usually be traced

back to one of four problem areas1. Procedural 2. Supply 3. Pump 4. Discharge

Procedural problems

Somehow a problem or procedure specific with your fire engine during pump engagement such as switch, lever, was not properly done. Go back and check pump switches, make sure pump engaged and ok to pump lights are on

Page 95: Welcome to Basic Pump Operations !

Basic Pump Operations

TROUBLESHOOTING1. Procedural 2. Supply 3. Pump 4. Discharge

Even though we discussed procedural problems first, the best way to troubleshoot pump problems is to back track

the water flow from the point of the problem back to the source. The 3 final causes of trouble are best solved

by using this method.

Page 96: Welcome to Basic Pump Operations !

Basic Pump Operations

TROUBLESHOOTING1. Procedural 2. Supply 3. Pump 4. Discharge

Supply ProblemsHow do you know you are having a supply problem to begin with ?

Monitor your intake gauge. Make sure the residual pressure does not drop below 20psi. If it does, it’s supply troubleshooting time.

If you allow the pressure to drop below zero, you will cavitate the pump. Cavitation is the grinding sound the pump will make when there is no or low water in it. This can cause irreversible damage to the pump and bring the operation to a complete stop. DO NOT ALLOW THIS TO HAPPEN !

Cavitation can occur while using any water source, not just a hydrant. In this powerpoint, we will address tank and hydrant supply problems

When deciding how to solve your supply problem, remember, back track your supply until you reach the source

Page 97: Welcome to Basic Pump Operations !

Basic Pump Operations

TROUBLESHOOTING1. Procedural 2. Supply 3. Pump 4. Discharge

Supply ProblemsHow do you fix supply problems ?

Start by determining what your water source is, which hopefully shouldn’t be hard! Either tank, hydrant, static source (drafting), pumper relay, or tanker shuttle.

We will start with tank problems. Is the tank to pump valve completely open and did you lock it open ? Are there valves open that could be ‘stealing water’ and draining your supply

quicker than you anticipated ? Check tank fill, main pump drain, and other discharges

Did you check that the tank was full prior to starting the operation ? There may be air in the pump. Pull the primer for no more than 30 seconds until

you see an increase in the discharge pressure.

Page 98: Welcome to Basic Pump Operations !

Basic Pump Operations

TROUBLESHOOTING1. Procedural 2. Supply 3. Pump 4. Discharge

Supply ProblemsHow do you fix supply problems ?

On to hydrant problems. Many of the issues we discussed with tank problems can also be the cause of hydrant supply issues. Check the previous list.

Firefighters making hydrant connections can get overexcited and not completely open the hydrant. Make sure the hydrant is open completely.

I feel the biggest cause of supply problems are kinks in the line. This results from what I call an ‘improper supply stretch’. We practice stretching ATTACK lines, but rarely do we practice our supply stretch. I don’t specifically mean forward and reverse lays. The kinks tend to occur when the hydrant is close to the building on fire. The pump operator must get comfortable with however long the supply lines are and position the truck in such a way that the hose has enough room to fully play out.

Page 99: Welcome to Basic Pump Operations !

Basic Pump Operations

TROUBLESHOOTING1. Procedural 2. Supply 3. Pump 4. Discharge

Supply ProblemsHow do you fix supply problems ?

Make sure the valve that allows water to enter the pump from the hydrant is fully open.

One of the final items to check would be the strainer on the intake that protects the pump from debris from hydrants, drafts, etc.

A piece or several pieces of something may be blocking the strainer. If you have checked everything else and nothing else seems to be wrong, you will have to check the strainer. This is an especially difficult event because if you have a piston intake valve like the one pictured above, its going to require a lot of work to remove.

Page 100: Welcome to Basic Pump Operations !

Basic Pump Operations

TROUBLESHOOTING1. Procedural 2. Supply 3. Pump 4. Discharge

Pump Problems Pump problems usually focus on the pump not being in gear or somehow not engaged properly. Once you have determined that you do not have a supply problem, you can move to pump problems. Check your pump panel lights and make sure that they are all on and indicating that it is “OK to pump” Go back into the cab and check to see that the vehicle is in the appropriate drive range Was there an increase in MPH when you engaged the pump ? Is there one now ?

Page 101: Welcome to Basic Pump Operations !

Basic Pump Operations

TROUBLESHOOTING1. Procedural 2. Supply 3. Pump 4. Discharge

Pump Problems If you are having problems engaging the pump, you may have to use the manual pump shift. This is a procedure that may require two peopleto correct. The procedures for this operation vary, socheck with your owners manual’s and SOP’s. Look underneath the vehicle to see if the drive shaft is spinning. If its spinning very slowly, the pump is probably not engaged. Below is a picture of our 1990 Pierce Lance on the right and1979 Sutphen Tower on the left.

Page 102: Welcome to Basic Pump Operations !

Basic Pump Operations

TROUBLESHOOTING1. Procedural 2. Supply 3. Pump 4. Discharge

Discharge Problems Discharge problems begin from the time the water leaves the pump and exits the nozzle. If the previous 3 troubleshooting areas are ok, you may be having discharge problems. Most of the discharge problems will revolve around hose. If the attack team is asking for water, and you have opened the discharge, you could have the following problems Check to see that the proper valve is opened. Sometimes names used to identify specific lines can be confusing. Crosslays and speedlays are commonly mixed up. Know what your flow pressures are and always monitor them. If, for example, No. 1 discharge was supposed to flow say, 150 psi and its now its flowing at 50 psi and the master discharge is still at 150 along with the hose team asking for water and you don’t notice any significant increase in pressure with an increase of the throttle, you may have a burst line.

Page 103: Welcome to Basic Pump Operations !

Basic Pump Operations

TROUBLESHOOTING1. Procedural 2. Supply 3. Pump 4. Discharge

Discharge Problems If the attack team is asking for water and the gauge, as in our example, on the No. 1 discharge is reading the same as the master discharge gauge, you have a blockage. The blockage could be in the form of a kink, a vehicle on the line, or an obstruction right at the nozzle, or the nozzle somehow has broke and or malfunctioned. Find and fix the kink if you can or have the attack team find the kink. If you don’t have pre-connected lines, its possible that someone connected a line to an intake. See the pictures below to help remember the difference.

Both are intakes, as indicated by

the female connection. The right picture has

the cap off