wind farm reactive power coordination scheme using iec 61850

14
The 7th International Conference on Real-Time Simulation Technologies Montreal | 9-12 June, 2014 1 Shijia Li MEng. Candidate, Department of ECE, McGill University Supervisor: Prof. Geza Joos Email: [email protected] Wind Farm Reactive Power Coordination Scheme Using IEC 61850

Upload: others

Post on 08-Feb-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

1

Shijia LiMEng. Candidate, Department of ECE, McGill University

Supervisor: Prof. Geza Joos

Email: [email protected]

Wind Farm Reactive Power Coordination Scheme

Using IEC 61850

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

Outline

IEC 61850 and GOOSE messaging

Case study – Wind farm controller Configuration

Tools

Results

2

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

IEC 61850Overview & Benefits

Substation Automation Systems (SAS) Defines the communication between

intelligent electronic devices (IEDs).

Benefits Multi-vendor interoperability

Low cost (installation and commissioning)

Free configuration

Source: Special report IEC 61850—ABB Group 3

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

GOOSE Message

GOOSE message Time-critical activities

communication between IEDs

Multicasting

Publisher/subscriber mechanism

Source: IEC 61850-7-14

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

Publisher/Subscriber

SCL file Substation Configuration Language

IED configurations and communications

5

OPAL-RT GOOSE message blocks

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

Outline

IEC 61850 and GOOSE messaging

Case study – Wind farm controller Configuration

Tools

Results

6

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

System Configuration

Centralized wind farm control Utility grid code:E.12-01

PCC voltage (±6%)

Implement IEC 61850 protocol Communication between WTG and wind

farm controller

7System configuration

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

Wind Farm ReactivePower Coordination

Centralized wind farm control Voltage regulation at PCC

Q dispatch based on reactive power capability for each WTG

Send/receive information using IEC 61850 GOOSE Q set points for each WTG

Q capability from each WTG

8Wind farm reactive power coordination scheme

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

Tools

Hardware OPAL-RT simulator Network switch, cables Laptop

Software Modeling

• Matlab Simulink, RT-LAB

SCL file configuration• ICD designer, XML marker

Network protocol analyzer• Wireshark

Real-time simulation setup for wind farm reactive power coordination scheme

9

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

Real-Time Simulation Model

Network

Console

WTG1

WTG2

WTG3

10

ConsoleWTG1

WTG2

WTG3

Network

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

Troubleshooting

Wireshark Packet analyzer

Used to capture and analyze GOOSE packets

Decoding Destination address

Data set

Data attribute

Data value

Data set

Data attributes and values

11

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

Simulation Results

100 200 300 400 500 600-0.4

-0.3

-0.2

100 200 300 400 500 600-0.4

-0.3

-0.2

100 200 300 400 500 600-0.4

-0.3

-0.2

Time (s)R

eactive p

ow

er

at

WT

G (

pu)

WTG 1

WTG 2

WTG 3

Control mode Unity power factor Reactive power coordination

100 200 300 400 500 600

1

1.05

1.1

Time (s)

RM

S v

oltage a

t P

CC

(pu)

Unity Power Factor

Voltage Control

12

RMS voltage at PCC (pu)

Reactive power at WTG (pu)

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

Conclusion and Future work

Conclusion OPAL-RT simulators allow for the testing of IEC 61850 GOOSE

messaging.

Wind farm control strategy successfully implemented employing IEC 61850 GOOSE messaging.

Future work Agent-based decentralized controller

Other distributed energy resources

13

The 7th International Conferenceon Real-Time Simulation TechnologiesMontreal | 9-12 June, 2014

Q & A

Thank you!

14