x800uc2
TRANSCRIPT
-
8/8/2019 X800UC2
1/5
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort toimprove the quality of its products.
DESCRIPTIVE
Electronic governor
Mechanically welded chassis with antivibrationsuspension
Radiator for wiring temperature of 48/50C max withmechanical fan
Exhaust compensators with flanges
24 V charge alternator and starter
Delivered with oil and coolant -30C
Manual for use and installation
POWER DEFINITION
PRP : Prime Power is available for an unlimited number
of annual operating hours in variable load applications, inaccordance with ISO 8528-1.
ESP : The standby power rating is applicable for
supplying emergency power in variable load applications inaccordance with ISO 8528-1.
Overload is not allowed.
TERMS OF USE
Standard reference conditions 25C Air Intlet Temp. 1000 mA.S.L. 60% relative humidity.
X800UC2
Engine type 12V2000G85E
Alternator type LSA491L9A
GENERAL CHARACTERISTICS
Frequency (Hz) 60
Reference voltage (V) T61A1
Max power ESP (kVA) 1000
Max power ESP (kWe) 800
Max power PRP (kVA) 909.1
Max power PRP (kWe) 727.3
Intensity (A) 1203
Optional control panel M80
Optional Control Panel TELYS
Optional control panel KERYS
DIMENSIONS AND NOISE LEVELS
DIMENSIONS COMPACT VERSION
Length (mm) 3971
Width (mm) 1848
Height (mm) 2150
Dry weight (kg) 5274
DIMENSIONS SOUNDPROOFED VERSION
Canopy M427
Length (mm). 6400
Width (mm). 2170
Height (mm). 2721
Dry weight (kg). 8580
Tank capacity (L). 930
Acoustic pressure level @1m in dB(A) 93
Acoustic pressure level @7m in dB(A) 83
POWERS
VoltageESP PRP
kWe kVA kWe kVAStandby Amps
480/277 800 1000 727 909 1203440/254 800 1000 727 909 1312
240 TRI 800 1000 727 909 2406
-
8/8/2019 X800UC2
2/5
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort toimprove the quality of its products.
X800UC2
TECHNICAL SPECIFICATIONS
GENERAL ENGINE DATAS
Engine model
MTU
12V2000G85E ,4-temps, TURBO ,AIR/AIR 12 X
Cylinder arrangement V
Displacement (C.I.) 23.89
Bore (mm) x Stroke (mm) 130 x 150
Compression ratio 16
Speed (RPM) 1800
Pistons speed (m/s) 9
Maximum stand-by power at ratedRPM (kW)
890
Frequency regulation (%) N/ABMEP (bar) 22.6
Governor type Electronique
COOLING SYSTEM
Radiator & Engine capacity (L) 180
Max water temperature (C) 102
Outlet water temperature (C) 95
Fan power (kW) 43
Fan air flow w/o restriction (m3/s) 20.61
Available restriction on air flow (mmEC)
20
Type of coolant GLYCOL
Thermostat (C) N/A
EMISSIONS
Emission PM (g/kWh) N/A
Emission CO (g/kW.h) N/A
Emission HCNOx (g/kWh) N/A
Emission HC (g/kW.h) N/A
EXHAUST
Exhaust gas temperature (C) 565
Exhaust gas flow (L/s) 2700
Max. exhaust back pressure (mm EC) 500
FUEL
Fuel consumption 110% load (L/hr) 217
Fuel consumption 100% load (L/hr) 197
Fuel consumption 75% (L/h) 148
Fuel consumption 50% (L/h) 100
Maximum fuel pump flow (L/h) 480
OIL
Oil capacity (L) 77
Min. oil pressure (bar) 4.7
Max. oil pressure (bar) 7.5
Oil consumption 100% load (L/h) 1.97
Carter oil capacity (L) 67
HEAT BALANCE
Heat rejection to exhaust (kW) N/A
Radiated heat to ambiant (kW) 40
Haet rejection to coolant (kW) 310
AIR INTAKE
Max. intake restriction (mm EC) 150
Intake air flow (L/s) 1050
-
8/8/2019 X800UC2
3/5
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort toimprove the quality of its products.
X800UC2
ALTERNATOR SPECIFICATIONS
GENERAL DATAS
Alternator brand LEROY SOMER
Alternator type LSA491L9A
Number of phase 3
Power factor (Cos Phi) 0.8
Altitude (m) 0-1000
Overspeed (rpm) 2250
Number of pole 4
Excitation system AREP
Insulation class / T class, continuous40C
H / H-125
Regulation R448
Harmonic factor, no load TGH/THC
-
8/8/2019 X800UC2
4/5
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort toimprove the quality of its products.
X800UC2
CONTROL PANEL
M80, transfer of information
The M80 is a dual-function control unit. It can be usedas a basic terminal block for connecting a control boxand as an instrument panel with a direct read facility,with displays giving a global view of your generatingset's basic parameters.
Offers the following functions:
Engine parameters: tachometer, working hours
counter, coolant temperature indicator, oil pressureindicator, emergency stop button, customerconnection terminal block, CE
TELYS, ergonomic and user-friendly
The highly versatile TELYS control unit is complex yetaccessible, thanks to the particular attention paid tooptimising its ergonomics and ease of use. With itslarge display screen, buttons and scroll wheel, itplaces the accent on simplicity and communication.
The TELYS offers the following functions:
Electrical measurements: voltmeter, frequency
meter, ammeter.
Engine parameters: working hours counter, oil
pressure, coolant temperature, fuel level, enginespeed, battery voltage.
Alarms and faults: oil pressure, coolant
temperature, failure to start, overspeed, alternatormin./max., battery voltage min./max., emergency stop,fuel level.
Ergonomics: wheel for navigating around the
various menus.
Communication: remote control and operation
software, USB connections, PC connection.
For more information on the product and its options,please refer to the sales documentation.
-
8/8/2019 X800UC2
5/5
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort toimprove the quality of its products.
KERYS, coupling and adaptability
The KERYS control unit has been designed to fulfilthe specific requirements of professionals in terms ofoperating and monitoring generating sets. It thereforeoffers a wide range of functions.This control unit is fitted as standard to all generatingsets designed to be used for coupling and is offeredas an option across the rest of our range.The KERYS can be built into the central console, fitteddirectly on the generating set, or in a separate cabinet,to fulfil all the requirements for low and high outputpower plants.
>The KERYS offers the following functions:
Electrical measurements: voltmeter, frequency
meter, ammeter.
Engine parameters: working hours counter, oil
pressure, coolant temperature, fuel level, engine
speed, battery voltage.
Alarms and faults: oil pressure, coolant
temperature, failure to start, overspeed, alternatormin./max., battery voltage min./max., emergency stop.
Additional functions: coupling, website,
diagnostic aid, assistance and maintenance, graphsand archiving, load impact management, 8 availableinstallation configurations, certification in line withinternational standards.
For more information, please refer to the salesdocumentation.Additional specifications :Website, Troubleshooting,Assistance and Maintenance, Plotting and logging,Load impact, 8 configurations available, Compliancewith international standards...