VESDAAccreditation Course
Robert F. Lopez Technical Instructor
VISION SYSTEMS has a new name.
VISION SYSTEMS has a new name.
-
8/10/2019 Xtralis Training 1
3/97
Introduction
XtralisVESDARobert F. Lopez
Technical InstructorOffice: (800)229 - 4434
Avon, Massachusetts
E-Mail [email protected]
Website: www.xtralis.com
-
8/10/2019 Xtralis Training 1
4/97
Website Information
www.xtralis.com Registration required: all information available here
Other website being discontinued
Previous websites (automatically forwarded to above) www.vesda.com
www.visionusa.com/vesda
http://www.vesda.com/http://www.visionusa.com/vesdahttp://www.visionusa.com/vesdahttp://www.vesda.com/ -
8/10/2019 Xtralis Training 1
5/97
Course Outline
Air Sampling Overview
Applications: Drivers for VESDA
Detector Specifications
Codes & Standards for Air Sampling
Design & Pipe Layout Flow Calcs: Pipe Modeling Software
Detector Parts & Pieces
Installation Details
Programming Exercise - VSC
Commissioning
Maintenance & Troubleshooting
TEST for Certification
-
8/10/2019 Xtralis Training 1
6/97
Course Objectives
Describe air-sampling techniques and benefits of an air
sampling detection system
Learn the principles of air sampling to allow design,
installation, and maintenance of a VESDA system
Gain VESDA certification
-
8/10/2019 Xtralis Training 1
7/97
Topic 1
Air Sampling Overview
-
8/10/2019 Xtralis Training 1
8/97
VESDA Detection Range
-
8/10/2019 Xtralis Training 1
9/97
How Does VESDA Work?
A detection
system that
actively draws air
from a fire zone
to a centrallymounted detector
http://localhost/My%20Documents/VESDA%20Info/Presentations/Shortcut%20to%20How%20VESDA%20Works.avi.lnk -
8/10/2019 Xtralis Training 1
10/97
How Does VESDA Work?
A detection
system that
actively draws air
from a fire zoneto a centrally
mounted detector
-
8/10/2019 Xtralis Training 1
11/97
VESDA Sampling Detection principles
NFPA 72, the max spacing for sampling holes is 30 ft centers
-
8/10/2019 Xtralis Training 1
12/97
Active vs. Passive Detection
VESDA: ActiveDetection Non reliant on air currentsfor smoke delivery
Functions effectively in wide range of environments
from high airflow to still air
Passivespot and beam type
detectors rely on thermal lift
to deliver smoke to detection
chamber.
-
8/10/2019 Xtralis Training 1
13/97
Performance Comparison
Spot Ionization 1.0 - 1.5 % obs per foot
Spot Photo-electric 2.0 - 3.5 % obs per foot
Spot Laser 0.031.0 % obs per foot
Beam 0.2 - 2.0 % obs per foot Heat / Linear Heat Detectiondetects heat from flaming fire
VESDA Laser-Based Detection0.00156 % per foot
One detector fits most Applications
4 programmable levels of alarm
Staged outputs
Suppression / Pre-action Interface Friendly
-
8/10/2019 Xtralis Training 1
14/97
Measurement by % Obscuration per Foot
~ 0.002%/ft ~2.0%/ft
-
8/10/2019 Xtralis Training 1
15/97
Application Drivers
-
8/10/2019 Xtralis Training 1
16/97
Early warning
Maintenance access
Smoke is difficult to detect (high airflow, high ceiling)
Challenging environment (temperature, dirty, RF)
Installation and long term cost considerations
Aesthetics
Vandalism
Application Drivers
-
8/10/2019 Xtralis Training 1
17/97
Application Drivers - Early Warning
VESDA provides reliable detection during the incipient
stage of a fire
TIME to investigate
Maintain business continuity
Avoid smoke contamination
Avoid unnecessary suppression release
-
8/10/2019 Xtralis Training 1
18/97
What Does VESDA Try to Avoid?
Detects in the smoldering
stage before visible smoke
Prevents damage,
downtime, pre-mature
suppression
Gives the earliest possible
warning in pre-combustion
conditions
-
8/10/2019 Xtralis Training 1
19/97
Application Drivers - Early Warning
-
8/10/2019 Xtralis Training 1
20/97
Application Drivers - Early Warning
Unions
-
8/10/2019 Xtralis Training 1
21/97
Application Drivers - Early Warning
-
8/10/2019 Xtralis Training 1
22/97
Application Drivers - Early Warning
-
8/10/2019 Xtralis Training 1
23/97
Application DriversMaintenance Access
-
8/10/2019 Xtralis Training 1
24/97
Application DriversMaintenance Access
-
8/10/2019 Xtralis Training 1
25/97
Multiple Level Sampling
Expansion Joint
Saddle Clip
Multi-LevelSampling
Points
Smoke
Stratification
To overcome
smoke
stratification,
VESDA cansample from
multiple
levels of the
warehouse.
Stratification occurs when smoke rises until it reaches a layer of air with the same temp & stops rising
-
8/10/2019 Xtralis Training 1
26/97
-
8/10/2019 Xtralis Training 1
27/97
Warehouse: Jack Daniel Distillery
-
8/10/2019 Xtralis Training 1
28/97
Warehouse: Jack Daniel Distillery
-
8/10/2019 Xtralis Training 1
29/97
Application DriversChallenging Environment
Aggressive environments
with pollution and/or
extreme temperatures
Cold storage facilities
Paper mills
Industrial Plants
Tunnels
Coal Mines
-
8/10/2019 Xtralis Training 1
30/97
Application DriversChallenging Environment
-
8/10/2019 Xtralis Training 1
31/97
Application DriversChallenging Environment
-
8/10/2019 Xtralis Training 1
32/97
Application DriversChallenging Environment
-
8/10/2019 Xtralis Training 1
33/97
Application DriversChallenging Environment
-
8/10/2019 Xtralis Training 1
34/97
Anechoic Chamber Detail
-
8/10/2019 Xtralis Training 1
35/97
-
8/10/2019 Xtralis Training 1
36/97
InstallationCost Considerations
-
8/10/2019 Xtralis Training 1
37/97
Application Driver - Aesthetics
Museums, Estates, Mansions Detection must be hidden
-
8/10/2019 Xtralis Training 1
38/97
Application Driver - Aesthetics
-
8/10/2019 Xtralis Training 1
39/97
Application Driver - Aesthetics
-
8/10/2019 Xtralis Training 1
40/97
Application Driver - Aesthetics
-
8/10/2019 Xtralis Training 1
41/97
Application Driver - Aesthetics
-
8/10/2019 Xtralis Training 1
42/97
Application Driver - Aesthetics
-
8/10/2019 Xtralis Training 1
43/97
Vandalism
Where damage to conventional systems is a problem
Sampling network used in the return air system
Detector located in a Centralized safe area
Safe and easy to service/maintain
Typical installations: Prisons
Changing rooms
Any public areas
-
8/10/2019 Xtralis Training 1
44/97
Correctional facilities
-
8/10/2019 Xtralis Training 1
45/97
Correctional facilities
Tampering and Security
-
8/10/2019 Xtralis Training 1
46/97
Sample Point
Tampering and Security
Discrete detection pointinside the prison cell
-
8/10/2019 Xtralis Training 1
47/97
VESDA Product Overview
Features & Benefits
-
8/10/2019 Xtralis Training 1
48/97
VESDA - A history of VESDA ASD
MK2 (1982)
MK3E700 (1987)
MK4 E70-D (1992) LaserPLUS (1997)
-
8/10/2019 Xtralis Training 1
49/97
LaserPLUS (VLP)
LaserSCANNER (VLS)
LaserCOMPACT (VLC)
LaserFOCUS (VLF)
Accessories
Current VESDA Product Range
-
8/10/2019 Xtralis Training 1
50/97
VESDA LaserPLUS see Product Guide for complete specs
Up to 20,000ft2coverage area
4 pipe inlets with individual flow
sensors
4 programmable alarm thresholds
(0.0015-6.0 %obs/ft)
Modular design
7 programmable relays
18,000 events in event log
100 maximum sample holes per
UL
-
8/10/2019 Xtralis Training 1
51/97
VESDA LaserSCANNER
In addition to VLP
Individual pipe annunciation
Available with 7 or 12 onboard relays
-
8/10/2019 Xtralis Training 1
52/97
VESDA LaserCOMPACT
Up to 8,000ft2coverage area
1 pipe inlet
3 programmable alarm thresholds
(0.0015-6.0 %obs/ft)
3 relays (rated at 2 Amps @ 30 VDC) FIRE, Pre-Alarm, Alert/Fault
Two basic versions
VLC-500 (RO) Relay Only
VLC-505 (VN) VESDAnet compatible
Event log up to 12,000 events FIFO Volatile
-
8/10/2019 Xtralis Training 1
53/97
VESDA LaserFOCUS
VLF-250: 2,500ft2
coverage area
VLF-500: 5,000ft2
coverage area
4 programmable alarmthresholds (Alert,
Action, Fire 1, Fire 2)
Modular interface cards
are available for extra
relays, Vnet, Ethernet,and specific FACP
protocol
-
8/10/2019 Xtralis Training 1
54/97
0.008 % obs/ft6 %obs/ft
VLF-250
Max 12 sample holes
Max 80 sampling pipe
Flow rate 1224 L/min
VLF-500
Max 24 sample holes
Max 150' length
Flow rate 1224 L/min
3 relays (Action, Fire1, Fault)
Segmented event log (up to 18,000 events) stores info on faults,
Access & exit commands and smoke change & alarm.
2 alarm threshold sets
VESDA LaserFOCUS
-
8/10/2019 Xtralis Training 1
55/97
Absolute Smoke Detection
Instant Fault Finder
Ultrasonic Flow Sensing
Separate Event Logging
Event log up to 18 000 events
Up to 5,000 sq.ft area coverage
Out of Box design
VESDA LaserFOCUS LOGIN: DST PW: 7244
-
8/10/2019 Xtralis Training 1
56/97
VESDA ECO Gas Detector
-
8/10/2019 Xtralis Training 1
57/97
VESDA ECO Positioning
VESDA ECO adds gas detection capability to existing or
new installations of VESDA smoke detection systems.
VESDA ECO can detect a range of flammable, toxic and
oxygen gas hazards.
VESDA ECO can provide a greater area of coverage than
fixed point gas detection systems.
VESDA ECO is for indoor non Hazardous classified areas
only.
VESDA ECO is not intended to be a stand alone gas
detection system.
-
8/10/2019 Xtralis Training 1
58/97
A Cautionary Note
To ensure correct application of VESDA ECO, only fully
trained and accredited distributors / installers will be
permitted to sell VSDA ECO
VESDA ECO is for use exclusively with compatible
Xtralis manufactured ASD.
VESDA ECO has been third-party validated, ensuringXtralis ASD smoke performance is not compromised.
VESDA ECO is not approved or warranted for use on
other (non Xtralis) ASD products.
No other third party gas detector is approved for use with
Xtralis ASD and would void the Xtralis ASD warranty.
-
8/10/2019 Xtralis Training 1
59/97
Features (Detectable Gases)
VESDA ECO detectors have a sensor cartridge containing 1 or 2 gas sensors.
VESDA ECO uses industry proven electrochemical & catalytic sensors.
Additional gases will be added to the range. All new requests welcomed.
Gas Formula Range Density : Air = 1
Carbon Monoxide CO 0-500 ppm 0.97Nitrogen Dioxide NO2 0-10 ppm 2.62
Ammonia NH3 0-100 ppm 0.59
Oxygen O2 0-25% v/v ~1.0
Sulphur Dioxide SO2 0-10 ppm 2.26
Hydrogen Sulphide H2S 0-100 ppm 1.19
Hydrogen H2 0-2000 ppm 0.07
Hydrogen H2 0-100% LFL 0.07
Methane CH4 0-100% LFL 0.55
Propane C3H8 0-100% LFL 1.56
-
8/10/2019 Xtralis Training 1
60/97
Features (User Interfaces)
LED Single gas cartridge Dual gas cartridge
Green Power (On)
Serial comms (Flashing)
Power (On)
Serial comms (Flashing)
Yellow Warning (Flashing)
Fault (On)
Warning (Flashing)
Fault (On)
Red 1 Gas sensor 1
Low gas alarm (Flashing)High Alarm (On)
Gas sensor 1
Low gas alarm (Flashing)High Alarm (On)
Red 2 Not used Gas sensor 2
Low gas alarm (Flashing)
High Alarm (On)
High visibility status LEDS indicate alarms and faults
Configuration via USB or RS485 interface using Xtralis VSC software
Real-time monitoring via RS485 using Xtralis VSM software
-
8/10/2019 Xtralis Training 1
61/97
Features (Integration Options)
Stand alone operation Using on board relays
Integration to Fire alarm systems
Using on board relays
Integration to 3rdparty systems e.g. BMS / fire panel
Using on board relays or 4-20mA signals
Using Modbus RS 485 serial link.
Integration to Xtralis VSM management software
Using Modbus RS 485 serial link.
Output Specification Function
Relays 4x 30VDC 1A Fully configurable. Default: Fault, Low gas
alarm, 2x High gas alarm
Analogue 2x 4-20mA (1 per sensor) 2mA calibration, 3.5mA fault, 4mA zero
gas, 20mA full scale, 21mA over-range
Serial USB & RS 485 (Modbus) Configuration & real time monitoring.
-
8/10/2019 Xtralis Training 1
62/97
VESDA ECO is compatible with all VESDA systems Must use 25mm OD or BSP sample pipe work
Limitations: Dependant on the gas being detected and size of area being monitored
See generic application guidelines and contact VESDA Field Applications Engineer
System Compatibility
VESDA System VESDA ECO
VLF single zone (
-
8/10/2019 Xtralis Training 1
63/97
VFT15
VFT-15
15areashighsensitivitylaserdetection IFT-15
0.001%to20%obs/m(0.0003to6.10%obs/ft)
15x50m(15x164ft)microboresamplingpipe
4Alarms-Alert,Action,Fire1,Fire2
TCP/IPEthernetinterface
Powerfuladjustablesuctionrotaryvanevacuumpump0,7Barwithsensitiveairflowmonitor
Sensitiveair-pressureperpipe
RS232andRS485MODBUSselectable
Modularrelayoutputunits OptionalanalogueI/Oandgasreleasemodules
Withorwithoutdisplay
VLI (VESDA L I d t i l
-
8/10/2019 Xtralis Training 1
64/97
Purpose built solution significantly reduces additional
engineering in the field while prolonging detector life
SolutionsThrough Innovation
Next Generation Solutions
Introducing yet another detection innovation from Xtralis
the VESDA VLI. Industrial strength smoke detection. A
smoke detector that works where you work
25 years of experience in one box
VLI (VESDA Laser Industrial
VLI S t C t
-
8/10/2019 Xtralis Training 1
65/97
Outside View Secure steel supportbracket for ease of
mounting
Five (5) high-intensity
status LEDs for greater
visibility. Provides
instant status of
detectors operation
Robust IP 54
enclosure to address
various industrialapplications with easy
mounting via robust
steel support bracket
Rubberised finish toexternal housing
VLI System Components
VLI K F t d B fit
-
8/10/2019 Xtralis Training 1
66/97
Up to 20,000 sq. ft. coverage
4 inlet pipes
Total pipe length up to 1,200 ft
Four levels of alarm
Wide Programmable Sensitivity Range: 0.0075 to 6.25% obs/ft (0.025 to
20% obs/ft)
Five (5) high-intensity status LEDs for greater visibility
Referencing (VESDAnet version)
AutoLearn Smoke and Flow
Air-path monitoring
Five (5) relays (Fire, Fault and 3 configurable)
Xtralis VSC, VSM and ASPIRE2 software support
Easy mounting via steel support bracket
Easy cable termination access
Standard GPI feature
VLI Key Features and Benefits
-
8/10/2019 Xtralis Training 1
67/97
VESDAnet
-
8/10/2019 Xtralis Training 1
68/97
VSM 4 System Management
Aspire 2
-
8/10/2019 Xtralis Training 1
69/97
Aspire 2
The ASPIRE2 programIs used to validate air
Sampling network designs
Main parts of the detector
-
8/10/2019 Xtralis Training 1
70/97
Main parts of the detector
Inlet
Manifold
connects
to pipes
The Detection Chamber
-
8/10/2019 Xtralis Training 1
71/97
Absolute smoke measurement
Optical light-scatteringdetection
principle
High stability fixed calibration
No scheduled re-calibration
Clean Air Barrier for Optics
-
8/10/2019 Xtralis Training 1
72/97
Laser Chamber
0.01
0.1
10
Clean
Air
Manifold
Flow monitoring
-
8/10/2019 Xtralis Training 1
73/97
g
Flow sensor in each inlet port (for VLP/VLS/VLC) Major and minor thresholds are configurable
Sensors are platinum film thermistors
For maximum performance - No bends within 19 inches of
the detector
VLF uses ultrasonic flow sensing
Importance of Normalizing
LaserPLUS Aspirator
-
8/10/2019 Xtralis Training 1
74/97
p
Motor incorporates integrated Hall Effect
tachometer
Microprocessor controlled feedback sensing
allowing speed regulation
Brushless 24VDC Lower power consumption
Lower noise emission
(new impeller intro early 1999)
Filter Technology
-
8/10/2019 Xtralis Training 1
75/97
gy
Disposable Filter (No Cleaning required)
Cartridge 2 stage foam filter
1st stage foam removes dust & dirt from smoke sample
2nd stage ultra fine filtration for clean air supply to maintain clean air
barrier in Laser Chamber
Recommended to replace every 2 years
Filter Technology
-
8/10/2019 Xtralis Training 1
76/97
gy
dust particles are counted as they pass through the
detector chamber.
You can enter a predetermine time stamp i.e.. 730
days (2 years) and at the end of that time a filterwarning is given to re-visit the detector to determine if
a new filter needs to be inserted.
Replace filters every 24 months, or as needed for
challenging environments. When the filter is removed from the VLP, the aspirator
shuts off, the buzzer sounds (if enabled) and an
urgent fault is raised.
2 Stage Filter
-
8/10/2019 Xtralis Training 1
77/97
Filter Technology
High efficiency
filter
(0.3 microns)
Sample to
laser
chamber
To clean
air manifold
Dust
Filter
Air inlet
2 Stage Filter
LaserPLUS Main Components
-
8/10/2019 Xtralis Training 1
78/97
LaserPLUS Main Components
Mounting box
head termination card
Chassis
Detector, Head processor card, Filter,
Aspirator, Manifold flow sensors Cover
Blank, Display,
& Programmer
The head card, aspirator, manifold, and laser must be
replaced as a unit - CHASSIS
Display Module
Compact remote display
-
8/10/2019 Xtralis Training 1
79/97
Display Module
LCD Programmer
-
8/10/2019 Xtralis Training 1
80/97
LCD Programmer
One can program all VESDAnet parameters from a single location
P d t G id P t N b i
-
8/10/2019 Xtralis Training 1
81/97
VLP-002
VLP-400
VLP-012
Product GuidePart Numbering
LaserScanner
-
8/10/2019 Xtralis Training 1
82/97
LaserScanner
Consists of a LaserPLUS with these additional features:
Continuously samples from all pipes
When smoke is detected initiates scan sequence
Identifies the first pipe to go into alarm
Continues scanning to monitorspread of fire
Adaptive Scan Threshold
LaserFOCUS
-
8/10/2019 Xtralis Training 1
83/97
LaserFOCUS
VESDA L FOCUS
-
8/10/2019 Xtralis Training 1
84/97
VESDA LaserFOCUS
Continued market leading technology 2 stage filter
Clean air bleed
Absolute smoke detection
New features include
VESDA LaserFOCUS
-
8/10/2019 Xtralis Training 1
85/97
Alarm threshold indicators
Smoke dial / instant fault
finder
Disable
Power
Fault
Instant Recognition Display
Ultrasonic Flow Sensing
-
8/10/2019 Xtralis Training 1
86/97
Measures time of flight to provide true volumetric flow measurement(L/min)
Not affected by temperature fluctuation or contamination
g
VESDA LaserFOCUS
-
8/10/2019 Xtralis Training 1
87/97
VESDA LaserFOCUS
RS232 connectivity VSC software
No pipe adaptorsaccepts both metric and imperial pipe
Out of box operation
Simplified setup and maintenance
Autolearn Smoke and Flow
Manual filter switch
Pre-engineered design
VLF Demo
To reset filter on Focus, depress switch (behind filter) 5 times within
5 sec. Other detector need to be reset via VSC or Programmer.
VESDA Accessories
-
8/10/2019 Xtralis Training 1
88/97
VESDA Accessories
Remote Modules
Sub-racks
High Level Interfacing PC Monitoring
Remote Modules
-
8/10/2019 Xtralis Training 1
89/97
Any of the VESDAnet modules can be
located remotely
displays to provide status information
programmers to allow centralized
programming of a whole VESDAnet system
VESDAnet sockets to allow convenient
VESDA HLI and PC access to a VESDAsystem
19 Sub- Racks
-
8/10/2019 Xtralis Training 1
90/97
Ideal for placing VESDAmodules in standard control
equipment
Fully configurable integrating
all VESDAnet product module
types
Products to meet customerneeds
VESDA High Level Interface (HLI)
-
8/10/2019 Xtralis Training 1
91/97
VESDA High Level Interface (HLI)
Standard HLI (VHX -200) Converts VESDAnet RS-485 to RS-
232
Enables connection to IBM
compatible PC
Interfaces the VESDA LaserPLUS
family to VESDA software:
VConfigPro
VSM3
VSC
The HLI provides an interface between VESDAnet and Intelligent systems
Pipe accessories
-
8/10/2019 Xtralis Training 1
92/97
p
VESDAnet
-
8/10/2019 Xtralis Training 1
93/97
Fault tolerant closed communications loop
Best classified under NFPA 72 as Style 7 Wiring
Cost effective configuration solutions
Duplicate items eliminated
Easy configuration
No DIP switches Connects up to 250 VESDAnet Nodes
VLP, VLS, VLC, displays, programmers,
Typically max 100 detectors
VESDAnetTechnical Features
-
8/10/2019 Xtralis Training 1
94/97
19.2K BPS RS485 Physical Interface which runs over shielded twisted pair wire up to 4,000 feet
in length (from node to node)
Use of Belden 9841or equivalent data cable is recommended (24 gauge, 120
ohmcharacteristic impedance), which provides good noise immunity and
maximum cable length
Daisy chain loop configuration, half duplex, peer-peer architecture
Fault tolerant
Auto detects communications failures
Single point failures tolerated - each node has dual ports
Easy configuration
Each manufactured node has unique 24-bit address
all addressable nodes automatically software configured
Network Connections
-
8/10/2019 Xtralis Training 1
95/97
Network Connections
Vnet A
Vnet B
Vnet A
Vnet B
Vnet A
Vnet B
Vnet A
Vnet B
Vnet A
Vnet B
Vnet A
Vnet BVnet A
Vnet B
Cabling can run from
Any Port to Any Port
Open Loop optional(not recommended)
VESDAnet
-
8/10/2019 Xtralis Training 1
96/97
VESDAnet
VESDAnet links all VESDA networkable modules (nodes)
OSID (Open-area Smoke Imaging Detector)
-
8/10/2019 Xtralis Training 1
97/97
OSID (Open area Smoke Imaging Detector)
Emitter
Emitter lensUV/IR LED
Imager
Imager lens
filterI l
Imager PCA