zer-sequence earth fault currents

Upload: haiob

Post on 04-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 Zer-sequence Earth Fault Currents

    1/4

    High Order Harmonics In Zero-Sequence Earth Fault Currents Of

    Isolated Neutral MV Networks

    HANI OBEID

    Electrical & Computer DepartmentP.O.Box 950674, Amman 11195

    JORDAN

    [email protected] www.asu.edu.jo

    Abstract: - This paper investigates the effect of high-order harmonics on the value of earth fault current in isolated

    neutral MV networks. The relay protection in these networks is intended to give an alarm in case of earth faults.

    The selective protection of these networks requires the study of transient character of the current in order to

    develop relays that are sensible to small impulses of current during intermittent earth faults.

    Key-words:- Earth Fault Current, Zero Sequence, MV Network, Isolated Neutral.

    1 IntroductionA large number of public utilities adopted the concept

    of isolated networks to maintain availability and

    safety. Distribution networks continue to expand,

    however and so do zero-sequence fault current [1].

    Single phase earth faults are the most frequent and

    dangerous faults. The relay protection in these

    networks is intended to give an alarm in case of earth

    faults. Exception is the case of connecting motors to

    these networks, where it is required to trip in case offault currents [2]. If the protection is non-selective the

    network collapse is more possible.

    There are major contradictions between current

    practice of neutral earthing and methods of protection

    in these networks [3]. These contradictions are:

    a. The requirements of national codes state thatthe capacitive currents should be decreased or

    compensated. That leads to difficulties in

    construction of efficient and cheap relays to

    protect from earth faults.b. Decrease of capacitive currents lead to asituation when most of earth faults have

    intermittent character [4]. In that case, the

    duration of the fault could be a few

    milliseconds (during the period of industrialfrequency), and current in faulty and sound

    feeders has transient character. The value of

    the fault current depends on the network

    configuration, the time of fault occurrence,

    and the time of arc extension. Settings of the

    relay protection that are based on steady state

    condition have not been selected according to

    real fault conditions. The same could be

    applied to the directional relay, working zone

    of which is defined based on current voltage

    phasor diagrams in steady state condition;

    however, this relay should operate in transient

    condition when short term current impulses

    occur. Filter of the basic frequency in the

    input of some devices does not change the

    situation; because there is no way that the

    fault could be periodically at each instant.

    c. The devices type HSS-3, ZM HSS, which arewidely used in city cable and industrial

    networks, react on harmonics of high order,

    which contradict the current compensation

    principle by coil installed in the neutral. If

    earth faults current contains high order

    harmonics, capacitive compensation should

    not be applied, because compensation is

    applied for basic frequency and the harmonics

    of high order will lead to opposite.

    d. Protection of motors in networks with smallearth fault currents as usual lacks sensibility.

    Not only because the earth faults are of small

    currents, but also, because protection does not

    operate during intermittent faults. Moreover,

    protection cant sense the fault if it is being

    developed deep down in the winding.

    mailto:[email protected]:[email protected]
  • 7/30/2019 Zer-sequence Earth Fault Currents

    2/4

    It should be taken into consideration that these

    problems were discussed by relay protection

    developers [5]. Developers also discussed the need for

    protection during stable and intermittent faults. Some

    of them offered relay protection that reacts on the

    magnitude during transients. Others stated that relays

    based on harmonics of high order could not be usedduring short term intermittent faults.

    However, all devices that are based on transients are

    not popular because they are expensive, complicated,

    and there are doubts about their reliability.

    Many experiments confirm that in networks of large

    industrial facilities with dc convertors, selectivity of

    protection devices that react on harmonics of high

    order is very big. But those experiments do not answer

    two important questions, namely: how these devices

    (HSS-3, ZM HSS) operate in network without dcconvertors (source of harmonics of high order), and

    why these devices are efficient only in networks with

    large capacitive currents. This paper tries to answer

    those questions.

    2 MV network with isolated neutral

    Basic analytical results that define currents of

    high order harmonics when single phase earth

    fault occurs are calculated from network diagram

    Fig. 1.

    Fig. 1

    The source of high order harmonics is transformer

    T2 (10/0.4). All other elements of the network:

    power transformer T1, current limitation coil P,

    neutral coil are taken into account by their line

    inductances.

    Energy source that works as a system generates

    only basic frequency. The no-load current of

    transformer T2 could be changed. There is no

    point to consider a large number of those

    transformers in the network, because the result is

    defined by an equivalent source of the high orderharmonics, specter of which is always changed

    due to changes in the transformer load, changes in

    phases between high order harmonics of the

    transformers, and changes of the network

    diagram. Only odd harmonics are presented in

    magnetizing current of the transformer ( k=5, 7,11) when phase windings are connected in delta

    (if there is unsymmetrical magnet system, is, there

    could be odd harmonics k=3,9 ). Maximumvalues of harmonics in transformers current are in

    over voltage modes when transformer load is

    little. If we suppose that there is a symmetry ofphase parameters of the network and if all phase

    currents of the network generate high order

    harmonics with positive zero sequence,

    current will be equal to zero until single phaseearth fault occurs. When fault occurs, currentscould be detected by devices, however, these

    currents are only a small part of the currents that

    are generated by the source (a few amperes). Thatis why if there is no resonant enhancing of these

    currents, sensitivity of the protection will not be

    good enough.

    The equivalent circuit of network shown in Fig. 1is shown in Fig. 2.

    Fig. 2

    The faulted cable is simulated by four line

    capacitance diagram. The difference between

    positive and zero sequence capacitances is

    System

    Coil

    /Y

    10/0.4 KV

    /Y

    110/10 KV

    R

  • 7/30/2019 Zer-sequence Earth Fault Currents

    3/4

    considered by capacitance to neutral thatcould be calculated by the following formula:

    The inductive connections between cables areignored. Earth fault current and in faultedcable are defined in branches as shown in Fig. 2.

    The same model is applied to sound cables with

    capacitances and. Zero sequence current inthe sound feeder is .

    If the source of harmonics of the order k is

    presented (

    and based on

    equivalent diagram in Fig.2, the following

    equations may be used to determine the value of

    earth fault current:

    ( )

    ( )

    ( )

    Where: S=1,2

    Solving these equations, yields the value of current atplace of short circuit and triple value of zero sequence

    in faulted feeder () and in sound feeder ().

    Where:

    current of k-order harmonic in phase a of

    transformer (current source).

    - rotational speed of k-oreder harmonic. the sum of phase to earth and phase tophase capacitances.

    zero-sequence capacitance of faulted andsound feeders.

    Where:

    are positive sequence capacitances ofrespective feeders.

    inductance of the source network.number of sound feeders.

    It is easy to show that the value of current calculated

    by the first equation of equations system (1) may be

    obtained from the following equivalent circuit (the

  • 7/30/2019 Zer-sequence Earth Fault Currents

    4/4

    shunt resistance which is shown as dashed line is not

    included), which is shown in Fig. 3.

    Fig. 3

    We can conclude from studying equivalent circuit

    of Fig.3, that the increae of k-order harmonic of

    the current

    in place of fault is possible when

    the following condition is fulfilledthe total sum

    of admittances of the branch with L inductance of

    k-order harmonic is approximately equal the sum

    of admittances . If their absolutevalues are equal then the equivalent admittance of

    parallel branches to the current source will beequal to zero. That leads to current resonance,

    when voltage of capacitance will be increasedto infinity and the harmonic current will beincreased at place of fault.

    In real conditions this can not happen as the

    elements of the network have active resistance

    and admittance, and the active resistance of the

    current source is connected in parallel.

    3 Conclusions

    The value of high-order harmonic of zero-sequence

    earth fault current was obtained based on equivalentcircuit diagram shown in Fig. 3.

    The currents

    in faulted and sound feeders may

    be calculated as part of the total current

    .

    The value of current in faulted feeder

    is always

    greater than current in sound feeder

    by .

    Current resonance will take place if

    References

    [1] A.A.Meer, M.Popov. Directional relay

    coordination in ungrounded MV radial distributionnetworks using RTDS.International conference on

    power system transients (IPST 2009), Koyto, Japan.

    2009.

    [2] M.A. Shabad single phase earth fault protection in

    6-35 KV networks. , 2007. (Russian

    Language).

    [3] G.A.Evdokunen, S.S. Titenkof. The systems of

    neutral earthing in MV networks (6-35KV).

    Overvoltage and Reliability of Equipment. Collective

    works: , 2006.

    [4] Jozef Lorenc, Kazimierz Musierowicz, and

    Andrzej Kwapisz. Detection of the intermittent earth

    fault in compensated MV networks.IEEE Power Tech

    Conference, 2003, Bolonga-Italy.

    [5] L.E. Dudarof, B.B. Zubkov. Problems of

    protection against earth faults in 6-35 KV networks.

    Electrechestvo, No.2, 1999. (Russian Language).