Page 1: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58 B121DC Power System

Product Description

Product Version: V2.0R01M05

ZTE CORPORATIONNo. 55, Hi-tech Road South, ShenZhen, P.R.ChinaPostcode: 518057Tel: +86-755-26771900Fax: +86-755-26770801URL: http://support.zte.com.cnE-mail: [email protected]

Page 2: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

LEGAL INFORMATIONCopyright © 2014 ZTE CORPORATION.

The contents of this document are protected by copyright laws and international treaties. Any reproduction or

distribution of this document or any portion of this document, in any form by any means, without the prior written

consent of ZTE CORPORATION is prohibited. Additionally, the contents of this document are protected by

contractual confidentiality obligations.

All company, brand and product names are trade or service marks, or registered trade or service marks, of ZTE

CORPORATION or of their respective owners.

This document is provided “as is”, and all express, implied, or statutory warranties, representations or conditions

are disclaimed, including without limitation any implied warranty of merchantability, fitness for a particular purpose,

title or non-infringement. ZTE CORPORATION and its licensors shall not be liable for damages resulting from the

use of or reliance on the information contained herein.

ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications

covering the subject matter of this document. Except as expressly provided in any written license between ZTE

CORPORATION and its licensee, the user of this document shall not acquire any license to the subject matter

herein.

ZTE CORPORATION reserves the right to upgrade or make technical change to this product without further notice.

Users may visit the ZTE technical support website http://support.zte.com.cn to inquire for related information.

The ultimate right to interpret this product resides in ZTE CORPORATION.

Revision History

Revision No. Revision Date Revision Reason

R1.0 2014-03-03 First edition

Serial Number: SJ-20140210154807-001

Publishing Date: 2014-03-03 (R1.0)

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 3: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ContentsAbout This Manual ......................................................................................... I

Chapter 1 System Overview ...................................................................... 1-11.1 System Introduction............................................................................................ 1-1

1.2 System Features ................................................................................................ 1-2

1.3 Technical Specifications...................................................................................... 1-2

1.4 Design Standards............................................................................................... 1-4

Chapter 2 Structure and Components...................................................... 2-12.1 System Structure................................................................................................ 2-1

2.2 AC/DC Distribution Components ......................................................................... 2-2

2.3 ZXD1500 Rectifier .............................................................................................. 2-3

2.4 Centralized Supervision Unit ............................................................................... 2-5

2.5 Signal Interfaces on the SIB Board ...................................................................... 2-7

Chapter 3 ZXD1500 (V4.0) Rectifier Specifications ................................ 3-13.1 AC Input Over/Under-Voltage Protection.............................................................. 3-1

3.2 PFC Output Over/Under-Voltage Protection ......................................................... 3-2

3.3 Output Over-Voltage Protection........................................................................... 3-2

3.4 Output Over-Current Protection........................................................................... 3-3

3.5 Over-Temperature Protection and Fan Speed Control........................................... 3-3

Appendix A Alarm List .............................................................................. A-1

Appendix B Electrical Connection Diagram ........................................... B-1

Glossary .......................................................................................................... I

I

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 4: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

This page intentionally left blank.

II

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 5: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

About This ManualPurpose

This manual applies to the ZXDU58 B121 (V2.0R01M05) DC power system (the ZXDU58B121 (V2.0R01M05) for short). The ZXDU58 B121 (V2.0R01M05) system provides powerfor -48 V communication equipment.

This manual describes the structure and characteristics the ZXDU58 B121 (V2.0R01M05).

Intended Audience

This manual is intended for:

l Planning engineersl Maintenance engineers

What Is in This Manual

This manual contains the following chapters/appendixes:

Chapter/Appendix Summary

1, System Overview Describes the appearance, dimensions, system features, and

technical specifications.

2, Structure and Components Describes the system structure , AC/DC Distribution

Components, the ZXD1500 (4.0) rectifier, the Centralized

Supervision Unit (CSU) and the Signal Interface Board (SIB).

3, ZXD1500 (V4.0) Rectifier

Specifications

Describes the input features, output features, over-temperature

protection and fan speed control of the ZXD1500 (V4.0) rectifier.

A, Alarm List Describes the alarm name, and the default alarm level and

output relays.

B, Electrical Connection Diagram Provides the electrical connection diagram of the ZXDU58

B121 (V2.0R01M05).

I

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 6: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Conventions

This document uses the following typographical conventions.

Typeface Meaning

Danger: Indicates an imminently hazardous situation, which if not avoided,

will result in death or serious injury.

Warning: Indicates a hazard that, if not avoided, could result in serious

injuries, equipment damages or interruptions of major services.

Caution: Indicates a potential hazard that, if not avoided, could result in

moderate injuries, equipment damages or partial service interruption.

Note: Provides additional information about a certain topic.

II

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 7: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Chapter 1System OverviewTable of Contents

System Introduction....................................................................................................1-1System Features ........................................................................................................1-2Technical Specifications .............................................................................................1-2Design Standards.......................................................................................................1-4

1.1 System IntroductionThe ZXDU58 B121 (V2.0R01M05) is an embeded DC power system. It provides -53.5 Vpower for communication equipment.

l Two-phase four-wire (L1/L2/N/PE) AC input, 127 V/220 V (phase voltage/line voltage),50 Hz/60 Hz.

l In full configuration, the ZXDU58 B121 (V2.0R01M05) is equipped with four ZXD1500(V4.0) rectifiers, which form a rated output current of 120 A (42 V - 58 V).

The ZXDU58 B121 (V2.0R01M05) is 6U in height and 19 inches in width. It will fit in a 19inches rack or cabinet. See Figure 1-1 for its appearance and dimensions.

Figure 1-1 Appearance and Dimensions of the ZXDU58 B121 (V2.0R01M05)

• Unit: mm

1-1

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 8: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58 B121 Product Description

1.2 System FeaturesThe ZXDU58 B121 (V2.0R01M05) system has the following features:

l A wide range of AC input line voltage (80 V - 300 V) makes the system suitable forareas with unstable sources.

l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit,rectifiers, and a monitoring unit.

l The ZXDU58 B121 (V2.0R01M05) system supports multiple networking modes, suchas RS232 and RS485.

l Intelligent monitoring unit.l High reliability with Mean Time Between Failures (MTBF) ≥ 2.2 × 105 h.l Signal interfaces on the rear panel for monitoring.

1.3 Technical SpecificationsRefer to Table 1-1 for the technical specifications of the ZXDU58 B121 (V2.0R01M05).

Table 1-1 Technical Specifications

Item Description

Appearance dimensions 266 mm × 483 mm × 350 mm (H × W × D)

Model B121-CSUCSU

Software version V2.20

Rectifier ZXD1500 (V4.0) rectifier, at most four sets

Rated output l Rated output current: 120 A (42 V - 58 V)

l Rated output power: 6.4 kW (at 53.5 V)

System efficiency ≥ 90%

AC input mode Two-phase, four-wire (L1/L2/N/PE)

AC input voltage l Rated input voltage: 127 V/220 V (phase voltage/line

voltage)

l Range: 80 V - 300 V (line voltage)

AC input frequency l Rated frequency: 50 Hz/60 Hz

l Frequency range: 45 Hz - 66 Hz

AC input circuit

breaker

l One AC input branch

l 1×63 A/2P MCB

AC Surge Protection

Device

Class C, maximum discharge current: Imax = 40 kA (8/20µs)

AC distribution

Auxiliary AC output None

1-2

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 9: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Chapter 1 System Overview

Item Description

DC output voltage l Rated output voltage: -53.5 V

l Range: -42 V to -58 V (The DC output voltage can be

adjusted through the CSU)

Battery input circuit

breakers

l Two battery input branches

l 2×100 A/1P MCBs

Load disconnection

modes

LLVD1 + LLVD2

DC output circuit

breakers

Six DC output branches:

l LLVD1 (F101 - F102): 2×40 A/1P MCBs

l LLVD2 (F201 - F204): 1×32 A + 2×10 A + 1×6 A /1P

MCBs

DC distribution

DC Surge Protection

Device

Maximum discharge current: Imax = 15 kA (8/20µs)

Communication

interface

l One RS232 communication interface

l One RS485 communication interface

Input/output relays l Four input relays

l Five output relays

l One CSU fault output relay

Supervision

interface

Environment

detection

l One flood alarm interface

l One door status alarm interface

l One smog status alarm interface

l One environment temperature interface

l One temperature control interface

l Two battery temperature interfaces

Operational

temperature

-5℃ to +45℃ (+15℃ to +25℃, recommended)

Storage temperature -40 ℃ to +70 ℃

Relative humidity 10% to 95% (non-condensing), 40% to 60% recommended

Altitude l 0 to 2000 m: 100% output power

l 2000 to 3000: The power derating percentage is 1% for

each 100 m increase in altitude above 2000 m.

Environment

specifications

Other requirements l The cabinet should be stable and erect.

l No conductive dusts or corrosive gases.

l No explosion hazard, no shake or jolt.

l No strong Electromagnetic Interference (EMI).

1-3

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 10: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58 B121 Product Description

1.4 Design StandardsEMC Standards

The ZXDU58 B121 (V2.0R01M05) system complies with the following ElectromagneticCompatibility (EMC) standards:

l EN55022l IEC61000-3-3; IEC61000-3-2; IEC61000-4-2; IEC61000-4-3; IEC61000-4-4;

IEC61000-4-6; IEC61000-4-8; and IEC61000-4-11

Safety Standards

The ZXDU58 B121 (V2.0R01M05) system is in compliance with the IEC/UL/EN 60950safety standards.

Other Standards

The ZXDU58 B121 (V2.0R01M05) system is also in compliance with the followingstandards:

l The Restriction of Hazardous Substances (RoHS) directive (2002/95/EC) of theEuropean Union.

l This device complies with Part 15 of the FCC Rules. Operation is subject to thefollowing two conditions: (1) This device may not cause harmful interference. (2)This device must accept any interference received, including interference that maycause undesired operations.

1-4

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 11: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Chapter 2Structure and ComponentsTable of Contents

System Structure........................................................................................................2-1AC/DC Distribution Components ................................................................................2-2ZXD1500 Rectifier ......................................................................................................2-3Centralized Supervision Unit ......................................................................................2-5Signal Interfaces on the SIB Board.............................................................................2-7

2.1 System StructureThe ZXDU58 B121 (V2.0R01M05) consists of the ZXD1500 (V4.0) rectifiers, CentralizedSupervision Unit (CSU), Signal Interface Board (SIB), and AC/DC distribution unit.

For the layout of the components, see Figure 2-1.

Figure 2-1 System Composition of the ZXDU58 B121 (V2.0R01M05)

1. AC/DC distribution unit(Front view)

2. CSU

3. ZXD1500 (V4.0) rectifiers4. PE connection terminal5. Signal Interface Board

6. AC/DC distribution unit(Rear view)

2-1

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 12: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58 B121 Product Description

For a description of the components, refer to Table 2-1.

Table 2-1 System Composition of the ZXDU58 B121 (V2.0R01M05)

S.N. Component Description

1 AC/DC distribution unit Provide AC and DC power distribution. For the further

details, refer to 2.2 AC/DC Distribution Components.

2 Centralized Supervision Unit

(CSU)

Collects the power device operation data and manages

the power device. For the further details, refer to 2.4

Centralized Supervision Unit.

3 ZXD1500 (V4.0) rectifiers Converts AC power to DC power. For the further details,

refer to 2.3 ZXD1500 Rectifier.

4 Signal Interface Board (SIB) Provide supervision interfaces for supervision.

For the further details, refer to 2.5 Signal Interfaces on

the SIB Board.

2.2 AC/DC Distribution ComponentsFor the layout of the AC/DC distribution components, see Figure 2-2.

Figure 2-2 AC/DC Distribution Components

For a description of the components, refer to Table 2-2.

Table 2-2 AC/DC Distribution Components

Label Component Description

AC Output - -

2-2

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 13: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Chapter 2 Structure and Components

Label Component Description

AC input circuit breaker Controls the connection and disconnection of AC

input power.

AC Input

AC input connection

terminals (L1/L2/PE)

Connect AC input L1/L2 cables and PE cable.

AC SPD AC surge protection

device

Provides surge protection for the AC input power.

DC Output DC output circuit breaker Controls the connection and disconnection of a DC

output circuit.

l LLVD1 load groups are labeled as F101 - F102

(DC output 1, 2).

l LLVD2 load groups are labeled as F201 - F204

(DC output 3, 4, 5, 6).

DC output (+)

DC output (-48V)

DC output connection

terminals

Connect the DC load.

Battery Input Battery input circuit

breakers

Controls the connection and disconnection of a

battery circuit.

BATT (-)

BATT (+)

Battery input connection

terminals

Connect two battery packs.

DC Surge

Arrester

DC surge protection

device

Provides surge protection for a DC circuit.

2.3 ZXD1500 RectifierThe ZXD1500 (V4.0) rectifiers convert AC to DC, provide power to the loads and chargethe batteries.

AppearanceFor the appearance of a ZXD1500 (V4.0) rectifier, see Figure 2-3.

2-3

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 14: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58 B121 Product Description

Figure 2-3 ZXD1500 (V4.0) Rectifier

1. Indicators2. Grille

3. Handle4. Stop pin

5. Input/output integratedsocket

Indicators

The indicators indicate the working state of the rectifier. For a description of the status ofthese indicators, refer to Table 2-3.

Table 2-3 Indicators Description

Designation Description Status Indication

IN Input Lit (green) AC input is normal.

OUT Output Lit (green) DC output is normal.

CL Current limit Lit (yellow) Current limit has occurred (the rectifier output

current has reached the current limit).

ALM Alarm Lit (red) An alarm has occurred.

Note:

When the rectifier is in sleep mode, only the IN indicator is lit.

Input/Output Integrated Socket

The input/output integrated socket of the rectifier is shown in Figure 2-4. It is used for theconnection to the DC power system.

2-4

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 15: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Chapter 2 Structure and Components

Figure 2-4 Input/Output Integrated Socket

The pins of the socket are defined in Table 2-4.

Table 2-4 Pins Description

Pin No. Signal Description

1 OUTPUT 48V+ DC output +

3 OUTPUT 48V- DC output -

11 REMOTE l High–level input (amplitude at 5 V): to turn off the rectifier.

l Low–level input or high resistance: to turn on the rectifier.

12 ALARM l Low–impedance output: startup process, internal

fault/alarm or overheat status of the rectifier.

l High–impedance output: normal status.

13 COM Common end for the control signals.

14 ON-LINE Rectifier online signal: Directly connected to the COM signal on

the MAIN board.

15 PWM An input pulse signal with the amplitude of 5 V is required.

16 SHARE-BUS Current equalizing bus.

17 FOUT Output signal: Frequency/Current = 1.5 kHz/15 A.

26 AC input PE Protection ground.

27 AC input N Neutral

28 AC input L Live

2.4 Centralized Supervision UnitThe Centralized Supervision Unit (B121-CSU) manages the power distribution unit,rectifiers and batteries of the ZXDU58 B121 (V2.0R01M05) system.

Functions

l Collects the operational data and monitors the operation of the system.l Provides alarm and necessary protection if the system is operating abnormally.

2-5

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 16: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58 B121 Product Description

l Sends data to the background Supervision Center (SC) and receives the commandsfrom the SC. In this way, the system can be monitored remotely.

StructureFor the CSU structure, see Figure 2-5.

Figure 2-5 Centralized Supervision Unit (B121-CSU)

1. LCD screen2. Indicators3. Reset button

4. Buttons5. Handle6. Power switch

7. Fastening screw8. (Rear) Interface

IndicatorsThe indicators indicate the current operational status of the CSU. For a description of theCSU indicators, refer to Table 2-5.

Table 2-5 CSU Indicators

Designation Description Status Indication

PWR Power Lit (green) Power is applied to the CSU.

RUN Run Flashing (green) CSU is operating normally.

EQU Charge equalization Lit (green) Battery equalized charge is in-process.

COMM Communication Flashing (yellow) CSU is communicating with the

connected PC.

ALM Alarm Flashing (red) An alarm or fault has occurred.

Buttons

l The RST button is used to restart the CSU.l Users can perform querying and setting operations through the buttons laid on the

front panel of the CSU. For the function description of the buttons, refer to Table 2-6.

Table 2-6 Button Function

Button Function

▲ Turns pages (or items) upwards / increases values.

▼ Turns pages (or items) downwards / decreases values.

2-6

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 17: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Chapter 2 Structure and Components

Button Function

Esc Exits and returns to the upper-level interface.

Enter Confirms the current menu items/saves the current parameter

setting/enters the lower-lever interface.

▲ + Enter Displays help information.

2.5 Signal Interfaces on the SIB BoardThe Signal Interface Board (SIB) provides external communication interfaces and signalinterfaces. For the layout of the interfaces on the SIB and pin configuration of theinterfaces, see Figure 2-6. For a description of the interfaces, refer to Table 2-7.

Figure 2-6 SIB

Table 2-7 Signal Interface Description

Interface Description

Battery temperature sampling interfaces and environment detection interfaces

X4 Battery 1 temperature Connects to temperature sensor of battery pack 1

2-7

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 18: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58 B121 Product Description

Interface Description

X5 Battery 2 temperature Connects to temperature sensor of battery pack 2

X12 Temperature control Used for low temperature disconnection function

X23 Flood alarm Connects to flood detect sensor

X24 Smoke alarm Connects to smoke detect sensor

X25 Ambient temperature Connects to environment temperature sensor

X26 Door status alarm Connects to door entrance detect sensor

Communication Interfaces

X21 RS485 interface The interface for RS485 communication

X22 RS232 interface The interface for RS232 communication

Input/output relay interfaces

X13 Input relay 1 and 2

X14 Input relay 3 and 4

The four input relays can be customized by the user for alarm

input.

The default alarm status of the input relays in the CSU are

“close”.

X15 Output relay for CSU

fault

This output relay is reserved for CSU fault.

X16 Output relay 1

X17 Output relay 2

X18 Output relay 3

X19 Output relay 4

X20 Output relay 5

l The output relays 1 to 5 correspond to the software codes

A1 to A5 in the CSU.

l For the default output relays for the alarms, refer to the

Alarm List.

l Users can customize these output relays for alarm output.

2-8

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 19: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Chapter 3ZXD1500 (V4.0) RectifierSpecificationsTable of Contents

AC Input Over/Under-Voltage Protection ....................................................................3-1PFC Output Over/Under-Voltage Protection ...............................................................3-2Output Over-Voltage Protection..................................................................................3-2Output Over-Current Protection..................................................................................3-3Over-Temperature Protection and Fan Speed Control ................................................3-3

3.1 AC Input Over/Under-Voltage ProtectionFor the AC input over/under-voltage protection and power decrease control, refer to Table3-1 and see Figure 3-1.

Table 3-1 AC Input Over/Under-Voltage Protection and Power Control

AC Input Voltage Protection and Power Control

≤ 70 V Auxiliary power supply startup

≤ 80 V The post-DC/DC conversion circuit and the pre-PFC circuit stop working.

80 V - 110 V Current limit Imax = (10 ± 2) A.

110 V - 150 V Current limit Imax = (20 ± 2) A

150 V - 300 V Current limit Imax = (32 ± 1) A

≥ 300 V The post-DC/DC conversion circuit and the pre-PFC circuit stop working.

3-1

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 20: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58 B121 Product Description

Figure 3-1 AC Input Over/Under-Voltage Protection

l The protection function is implemented through hardware.l The precision of the voltage is ± 10 V and the hysteresis width is (15 ± 10) V.

3.2 PFC Output Over/Under-Voltage ProtectionThe PFC output over/under-voltage protection is as follows:

l When the PFC output voltage > 440 V DC, the post-DC/DC conversion circuit and thepre-PFC circuit stop working.

l When the PFC output voltage < 340 V DC, the post-DC/DC conversion circuit stopsworking.

The PFC output over/under-voltage protection is implemented through hardware. Theprecision of the voltage is ±10 V and the hysteresis width is (15 ± 10) V.

3.3 Output Over-Voltage ProtectionThe output over-voltage protection circuit prevents the DC output filter capacitor andpowered devices from damage due to voltage loop failure.

The output over-voltage protection threshold is (61 ± 1) V, which is unmodifiable. Whenthe output voltage exceeds (61 ± 1) V, the rectifier disables output and will not enable ituntil the fault is eliminated after power-off and the rectifier is restarted.

3-2

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 21: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Chapter 3 ZXD1500 (V4.0) Rectifier Specifications

3.4 Output Over-Current ProtectionThe output over-current protection circuit prevents the rectifier from being damaged dueto the fault of output current limit circuit.

To avoid over-current protection prior to current limit protection, the response ofover-current protection is set to be slower than current limit protection, and the over-currentprotection threshold is set to be higher than the maximum current limit threshold.

The over-current protection threshold of the rectifier is (36 ± 2) A.

The output over-current protection is a kind of backup protection and is configured as"unrecoverable". It does not act generally; however, once the over-current protectionis activated, the function will not recover until the fault is eliminated and the rectifier isrestarted.

3.5 Over-Temperature Protection and Fan SpeedControl

According to the temperature of the radiator, the fan may work at full speed or half speed.

l When the temperature is over 50 °C, the fan works at full speed.l When the temperature is below 50 °C, the fan works at half speed.

The radiator temperature may keep increasing when the fan is faulty or it is working atfull speed. Therefore, a negative temperature coefficient thermistor is used to prevent therectifier from being damaged due to over-temperature. The over-temperature protectionis as follows:

l When the temperature exceeds the temperature protection threshold, the post-DC/DCconversion circuit stops working.

l When the temperature is below the temperature protection threshold, the post-DC/DCconversion circuit starts to work.

3-3

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 22: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58 B121 Product Description

This page intentionally left blank.

3-4

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 23: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Appendix AAlarm ListTable A-1 lists the alarms that can be detected by the B121-CSU (SV2.20) supervisionunit, and describes their default alarm levels and output relays.

l A1 - A5 refer to 5 output relays for the alarms.l Multiple alarms can share one output relay. Each alarm cannot correspond to multiple

output relays but one output relay only. “0” means that no output relay is assignedto an alarm. When an alarm is reported, it indicates that problems occur on thecorresponding output relay.

l Except for “Total Alarm” and “Start GEN”, the output relay of an alarm will not takeeffect when its alarm level is set to “Mask”.

Table A-1 Alarm List

S.N. Alarm Name AlarmLevel

OutputRelay

Alarm Description

1 Total Alarm Mask A1 The CSU detects that an alarm occurred.

AC Related

2 AC Aux SW Off Minor A2 The AC auxiliary switch is Off.

3 AC Main SW Off Major A2 The AC input air switch is Off.

4 AC Power Off Major A2 The mains supply is cut off and there is no

standby AC input available.

5 ACArrester Brk. Minor A2 The surge arrester is faulty.

6 AC Under-Vol Minor A2 The AC input voltage is lower than ACVol.Min.

7 AC Over-Vol Minor A2 The AC input voltage is higher than ACVol.Max.

8 AC Phase Lost Minor A2 AC input phase lost.

9 AC Current Over Minor A2 The AC input current is higher than the preset

maximum AC current.

SMR Related

10 SMR Alarm Minor A3 A rectifier is faulty. If one rectifier is faulty, it

is a minor alarm; if two or more rectifiers are

faulty at the same time, it is a major alarm.

11 SMR Abnormal Minor A3 The rectifier is activated but has no output.

DC and Battery Related

A-1

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 24: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58 B121 Product Description

S.N. Alarm Name AlarmLevel

OutputRelay

Alarm Description

12 DC Under-Vol Minor A4 The DC output voltage is lower than DCVol.Min.

13 DC Over-Vol Minor A4 The DC output voltage is higher than DCVol.Max.

14 DC Loop Break Minor A4 The DC output branch n is disconnected.

15 Bat Loop Break Minor A4 The battery branch n is disconnected.

16 Bat Under-Vol Major A4 The battery voltage is lower than BatVol Min.

17 Bat Over-Temp Minor A4 The temperature of battery n is higher than

Bat. Temp.Max.

18 1st Shut-down Major A4 When the battery voltage is lower than 1-ShutVol., the secondary loads are shut down.

19 2nd Shut-down Major A4 When the battery voltage is lower than 2-ShutVol., all the loads are shut down.

20 DCArrester Brk. Minor A4 The DC arrester is faulty.

21 DCBreaker Alarm Minor A4 The DC contactor of the DC loop n is faulty

(n ranges from 1 to 2)

22 Battery Fault Major A4 The battery cannot supply power online.

23 Bat Under-Temp Minor A4 The temperature of group N battery is less

than Bat Under-Temp.

24 Bat.Temp.Void Minor A4 The system is configured with batteries, but

battery temperature sensor is not properly

connected.

25 Bat.Discharge Minor A4 Battery discharge current is higher than

Bat.Discharge.

Environmental Related

26 Env Under-Temp Minor A5 Environment temperature is lower than

Env.Temp.Min.

27 Env Over-Temp Minor A5 The environment temperature is higher than

Env.Temp.Max.

28 Env Under-Hum Minor A5 The environment humidity is lower than

Env.Hum.Min.

29 Env Over-Hum Minor A5 The environment humidity is higher than

Env.Hum.Max.

30 Smoke Alarm Minor A5 The sensor detects the smoke.

31 Flood Alarm Minor A5 The sensor detects the entrance of water.

A-2

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 25: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Appendix A Alarm List

S.N. Alarm Name AlarmLevel

OutputRelay

Alarm Description

32 Intrusion Alarm Minor A5 The sensor detects the intrusion of a foreign

object.

33 Door Magnet Alm Minor A5 The door with door magnet switch is opened.

34 Glass Broken Minor A5 The sensor detects broken glasses.

35 EnvUn.LostTouch Minor A5 The communication between the CSU and the

Environment Monitor Board (EMB) failed.

36 HeatExch.Alm Major A5 The heat exchanger is faulty.

37 Env.Temp.Void Minor A5 No valid battery temperature sensor is

configured.

38 Start GEN Mask 0 The generator has been activated.

A-3

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 26: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58 B121 Product Description

This page intentionally left blank.

A-4

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 27: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

Appendix BElectrical ConnectionDiagramFor the operating principle diagram of the ZXDU58 B121 (V2.0R01M05), see Figure B-1.

Figure B-1 Operating Principle Diagram of the ZXDU58 B121 (V2.0R01M05)

The components are described as follows.

l AC distribution unit: Connects AC input to the system and distributes AC power.l Rectifiers: Convert AC to DC.l DC distribution unit: Provides DC output to the loads and connects the batteries to

the system.l CSU: Controls and manages the system.l Batteries: Provide standby DC power to the loads when the mains is failure.

For the detailed electrical connection diagrams of the ZXDU58 B121 (V2.0R01M05), seeFigure B-2.

B-1

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential

Page 28: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

ZXDU58B121Pro

ductDescrip

tion

Figure B-2 Electrical Connection Diagram of the ZXDU58 B121 (V2.0R01M05)

B-2

SJ-20140210154807-001|2014-03-03(R1.0)

ZTEPro

prietary

andConfidential

Page 29: ZXDU58B121 - libertyport.com · l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit, rectifiers,andamonitoringunit

GlossaryAC- Alternating Current

CSU- Centralized Supervision Unit

DC- Direct Current

EMB- Environment Monitor Board

EMC- Electromagnetic Compatibility

EMI- Electromagnetic Interference

LLVD- Load Low Voltage Disconnect

MCB- Miniature Circuit Breaker

MTBF- Mean Time Between Failures

PC- Personal Computer

PE- Protective Earth

PFC- Power Factor Correction

RoHS- Restriction of Hazardous Substances

SIB- Signal Interface Board

SPD- Surge Protection Device

I

SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential