1 control transformers transformers · 2019. 10. 12. · to: vde 0570 part2-4, din en 61558-2-4, en...
TRANSCRIPT
30 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 6348 STEU 6324 STEU 6323 STEU 10048 STEU 10024 STEU 10023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 63 VA 63 VA 63 VA 100 VA 100 VA 100 VA
Rated power VDE (KB cos phi=05) 175 VA 175 VA 175 VA 310 VA 310 VA 175 VA
No-load voltage (app x factor) 110 110 110 107 107 107
Efficiency 86 86 86 86 86 86
StandardsClassification Control- and safety isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 025 - 040 A 025 - 040 A 025 - 040 A 040 - 063 A 040 - 063 A 040 - 063 A
Setting value 230 plusmn15 Vac 035 A 035 A 035 A 050 A 050 A 050 A
Setting range 400 plusmn15 Vac 016 - 025 A 016 - 025 A 016 - 025 A 025 - 040 A 025 - 040 A 025 - 040 A
Setting value 400 plusmn15 Vac 020 A 020 A 020 A 029 A 029 A 029 A
Order numbersOrder Number STEU 6348 STEU 6324 STEU 6323 STEU 10048 STEU 10024 STEU 10023
+-
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 31
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 6348 STEU 6324 STEU 6323 STEU 10048 STEU 10024 STEU 10023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 63 VA 63 VA 63 VA 100 VA 100 VA 100 VA
Rated power VDE (KB cos phi=05) 175 VA 175 VA 175 VA 310 VA 310 VA 175 VA
No-load voltage (app x factor) 110 110 110 107 107 107
Efficiency 86 86 86 86 86 86
StandardsClassification Control- and safety isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 025 - 040 A 025 - 040 A 025 - 040 A 040 - 063 A 040 - 063 A 040 - 063 A
Setting value 230 plusmn15 Vac 035 A 035 A 035 A 050 A 050 A 050 A
Setting range 400 plusmn15 Vac 016 - 025 A 016 - 025 A 016 - 025 A 025 - 040 A 025 - 040 A 025 - 040 A
Setting value 400 plusmn15 Vac 020 A 020 A 020 A 029 A 029 A 029 A
Order numbersOrder Number STEU 6348 STEU 6324 STEU 6323 STEU 10048 STEU 10024 STEU 10023
+-Transformers Control transformers1
BLOCKWebsite
32 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 16048 STEU 16024 STEU 16023 STEU 25048 STEU 25024 STEU 25023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 160 VA 160 VA 160 VA 250 VA 250 VA 250 VA
Rated power VDE (KB cos phi=05) 490 VA 490 VA 490 VA 850 VA 850 VA 850 VA
No-load voltage (app x factor) 110 110 110 107 107 107
Efficiency 86 86 86 88 88 88
StandardsClassification Control- and isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 063 - 100 A 063 - 100 A 063 - 100 A 100 - 160 A 100 - 160 A 100 - 160 A
Setting value 230 plusmn15 Vac 080 A 080 A 080 A 120 A 120 A 120 A
Setting range 400 plusmn15 Vac 040 - 063 A 040 - 063 A 040 - 063 A 063 - 100 A 063 - 100 A 063 - 100 A
Setting value 400 plusmn15 Vac 046 A 046 A 046 A 070 A 070 A 070 A
Order numbersOrder Number STEU 16048 STEU 16024 STEU 16023 STEU 25048 STEU 25024 STEU 25023
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac
Rated power VDE (DB cos phi=1) 320 VA 320 VA 320 VA 400 VA 400 VA 500 VA
Rated power VDE (KB cos phi=05) 1120 VA 1120 VA 1120 VA 1440 VA 1440 VA 2000 VA
No-load voltage (app x factor) 107 107 107 104 104 104
Efficiency 90 90 90 90 90 92
StandardsClassification Control- and isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 100 - 160 A 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 230 plusmn15 Vac 150 A 150 A 150 A 190 A 190 A 240 A
Setting range 400 plusmn15 Vac 063 - 100 A 063 - 100 A 063 - 100 A 100 - 160 A 100 - 160 A 100 - 160 A
Setting value 400 plusmn15 Vac 088 A 088 A 088 A 110 A 110 A 140 A
Order numbersOrder Number STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
+-
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 33
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac
Rated power VDE (DB cos phi=1) 320 VA 320 VA 320 VA 400 VA 400 VA 500 VA
Rated power VDE (KB cos phi=05) 1120 VA 1120 VA 1120 VA 1440 VA 1440 VA 2000 VA
No-load voltage (app x factor) 107 107 107 104 104 104
Efficiency 90 90 90 90 90 92
StandardsClassification Control- and isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 100 - 160 A 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 230 plusmn15 Vac 150 A 150 A 150 A 190 A 190 A 240 A
Setting range 400 plusmn15 Vac 063 - 100 A 063 - 100 A 063 - 100 A 100 - 160 A 100 - 160 A 100 - 160 A
Setting value 400 plusmn15 Vac 088 A 088 A 088 A 110 A 110 A 140 A
Order numbersOrder Number STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
+-Transformers Control transformers1
BLOCKWebsite
34 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 50024 STEU 50023 STEU 63024 STEU 63023 STEU 80048 STEU 80024
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac 2x12 Vac
Rated power VDE (DB cos phi=1) 500 VA 500 VA 630 VA 630 VA 800 VA 800 VA
Rated power VDE (KB cos phi=05) 2000 VA 2000 VA 2350 VA 2350 VA 3400 VA 3400 VA
No-load voltage (app x factor) 104 104 104 104 103 103
Efficiency 92 92 92 92 94 94
StandardsClassification Control- and safety isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 160 - 250 A 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 250 - 400 A
Setting value 230 plusmn15 Vac 240 A 240 A 300 A 300 A 370 A 370 A
Setting range 400 plusmn15 Vac 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 400 plusmn15 Vac 140 A 140 A 170 A 170 A 220 A 220 A
Order numbersOrder Number STEU 50024 STEU 50023 STEU 63024 STEU 63023 STEU 80048 STEU 80024
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac 2x115 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 800 VA 1000 VA 1000 VA 1000 VA 1600 VA 2000 VA
Rated power VDE (KB cos phi=05) 3400 VA 5000 VA 5000 VA 5000 VA 7800 VA 10900 VA
No-load voltage (app x factor) 103 103 103 103 101 102
Efficiency 94 94 94 94 94 94
StandardsClassification Control- and isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 250 - 400 A 400 - 630 A 400 - 630 A 400 - 630 A 630 - 1000 A 800 - 1000 A
Setting value 230 plusmn15 Vac 370 A 460 A 460 A 460 A 730 A 910 A
Setting range 400 plusmn15 Vac 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 400 - 630 A 400 - 630 A
Setting value 400 plusmn15 Vac 220 A 270 A 270 A 270 A 420 A 520 A
Order numbersOrder Number STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
+-
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 35
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac 2x115 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 800 VA 1000 VA 1000 VA 1000 VA 1600 VA 2000 VA
Rated power VDE (KB cos phi=05) 3400 VA 5000 VA 5000 VA 5000 VA 7800 VA 10900 VA
No-load voltage (app x factor) 103 103 103 103 101 102
Efficiency 94 94 94 94 94 94
StandardsClassification Control- and isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 250 - 400 A 400 - 630 A 400 - 630 A 400 - 630 A 630 - 1000 A 800 - 1000 A
Setting value 230 plusmn15 Vac 370 A 460 A 460 A 460 A 730 A 910 A
Setting range 400 plusmn15 Vac 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 400 - 630 A 400 - 630 A
Setting value 400 plusmn15 Vac 220 A 270 A 270 A 270 A 420 A 520 A
Order numbersOrder Number STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
+-Transformers Control transformers1
BLOCKWebsite
36 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 250023
InputRated input voltage 230400 Vac
Tappings Input plusmn15 V
Frequency range 50 - 60 Hz
OutputRated output voltage 2x115 Vac
Rated power VDE (DB cos phi=1) 2500 VA
Rated power VDE (KB cos phi=05) 12400 VA
No-load voltage (app x factor) 102
Efficiency 94
StandardsClassification Control- and isolating
transformer
ApprovalsApprovals cURus
EnvironmentAmbient temperature max 40 degC
Cooling method self-cooling
Safety and protectionType Open type
Class of Insulation System VDE=B UL=class 130
Protection index IP 00
Safety class (prepared) I
Short circuit strength non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 1000 - 1600 A
Setting value 230 plusmn15 Vac 1120 A
Setting range 400 plusmn15 Vac 630 - 1000 A
Setting value 400 plusmn15 Vac 650 A
Order numbersOrder Number STEU 250023
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 37
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
Transformers Control transformers1
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 31
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Control- and safety isolating- resp isolatingtransformerSTEU
General Data
Rated input voltage 230 and 400 Vac
Rated output voltage 24 - 230 Vac
Rated power 63 - 2500 VA
Insulation class B
Maximum ambient temperature 40 degC
Efficiency up to 94
Degree of protection IP 00
Advantages
Dual input voltage 230 and 400 Vac
Very good switch-on behaviour thanks to reduced starting currents
High performance for the volume thanks to compact design
Primary side plusmn15 V tappings for voltage adjustment
Very good corrosion protection and low noise thanks to BLOCKIMPEXvacuum impregnation
Quick to cable up thanks to the use of spring-clamp terminals
Contact protected screw connection terminals complying with UVV BGV A3
Simple mounting thanks to robust metal footplate with oval slots
Up to 250 VA with combination footplate for bolted and rail mounting
Applications
As a control transformer for the electrical isolation of the input and outputsides The construction of the transformer to supply control systems accordingto VDE 0113 is designed
As an isolating transformer for the safe electrical isolation of the input andoutput sides The transformer may be used to set up protective separation as aprotective measure in accordance with VDE 0100
As a safety transformer for the safe electrical isolation of the input and outputsides The transformer is suitable for creating SELV and PELV circuits becauseof the limit on the output voltage
Sample application
Standards 2 | Z
Approvals W J Z
Control transformerto VDE 0570 Teil 2-2 DIN EN 61558-2-2 EN 61558-2-2 IEC 61558-2-2UL 5085-1-2 CSA 222 No66 Safety isolating transformerto VDE 0570 Teil 2-6 DIN EN 61558-2-6 EN 61558-2-6 IEC 61558-2-6 UL5085-1-2 CSA 222 No66 Isolating transformerto VDE 0570 Part2-4 DIN EN 61558-2-4 EN 61558-2-4 IEC 61558-2-4 UL5085-1-2 CSA 222 No66
UL 5085-1-2 CSA 222 No66
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 6348 STEU 6324 STEU 6323 STEU 10048 STEU 10024 STEU 10023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 63 VA 63 VA 63 VA 100 VA 100 VA 100 VA
Rated power VDE (KB cos phi=05) 175 VA 175 VA 175 VA 310 VA 310 VA 175 VA
No-load voltage (app x factor) 110 110 110 107 107 107
Efficiency 86 86 86 86 86 86
StandardsClassification Control- and safety isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 025 - 040 A 025 - 040 A 025 - 040 A 040 - 063 A 040 - 063 A 040 - 063 A
Setting value 230 plusmn15 Vac 035 A 035 A 035 A 050 A 050 A 050 A
Setting range 400 plusmn15 Vac 016 - 025 A 016 - 025 A 016 - 025 A 025 - 040 A 025 - 040 A 025 - 040 A
Setting value 400 plusmn15 Vac 020 A 020 A 020 A 029 A 029 A 029 A
Order numbersOrder Number STEU 6348 STEU 6324 STEU 6323 STEU 10048 STEU 10024 STEU 10023
+-Transformers Control transformers1
BLOCKWebsite
32 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 16048 STEU 16024 STEU 16023 STEU 25048 STEU 25024 STEU 25023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 160 VA 160 VA 160 VA 250 VA 250 VA 250 VA
Rated power VDE (KB cos phi=05) 490 VA 490 VA 490 VA 850 VA 850 VA 850 VA
No-load voltage (app x factor) 110 110 110 107 107 107
Efficiency 86 86 86 88 88 88
StandardsClassification Control- and isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 063 - 100 A 063 - 100 A 063 - 100 A 100 - 160 A 100 - 160 A 100 - 160 A
Setting value 230 plusmn15 Vac 080 A 080 A 080 A 120 A 120 A 120 A
Setting range 400 plusmn15 Vac 040 - 063 A 040 - 063 A 040 - 063 A 063 - 100 A 063 - 100 A 063 - 100 A
Setting value 400 plusmn15 Vac 046 A 046 A 046 A 070 A 070 A 070 A
Order numbersOrder Number STEU 16048 STEU 16024 STEU 16023 STEU 25048 STEU 25024 STEU 25023
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac
Rated power VDE (DB cos phi=1) 320 VA 320 VA 320 VA 400 VA 400 VA 500 VA
Rated power VDE (KB cos phi=05) 1120 VA 1120 VA 1120 VA 1440 VA 1440 VA 2000 VA
No-load voltage (app x factor) 107 107 107 104 104 104
Efficiency 90 90 90 90 90 92
StandardsClassification Control- and isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 100 - 160 A 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 230 plusmn15 Vac 150 A 150 A 150 A 190 A 190 A 240 A
Setting range 400 plusmn15 Vac 063 - 100 A 063 - 100 A 063 - 100 A 100 - 160 A 100 - 160 A 100 - 160 A
Setting value 400 plusmn15 Vac 088 A 088 A 088 A 110 A 110 A 140 A
Order numbersOrder Number STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
+-
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 33
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac
Rated power VDE (DB cos phi=1) 320 VA 320 VA 320 VA 400 VA 400 VA 500 VA
Rated power VDE (KB cos phi=05) 1120 VA 1120 VA 1120 VA 1440 VA 1440 VA 2000 VA
No-load voltage (app x factor) 107 107 107 104 104 104
Efficiency 90 90 90 90 90 92
StandardsClassification Control- and isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 100 - 160 A 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 230 plusmn15 Vac 150 A 150 A 150 A 190 A 190 A 240 A
Setting range 400 plusmn15 Vac 063 - 100 A 063 - 100 A 063 - 100 A 100 - 160 A 100 - 160 A 100 - 160 A
Setting value 400 plusmn15 Vac 088 A 088 A 088 A 110 A 110 A 140 A
Order numbersOrder Number STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
+-Transformers Control transformers1
BLOCKWebsite
34 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 50024 STEU 50023 STEU 63024 STEU 63023 STEU 80048 STEU 80024
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac 2x12 Vac
Rated power VDE (DB cos phi=1) 500 VA 500 VA 630 VA 630 VA 800 VA 800 VA
Rated power VDE (KB cos phi=05) 2000 VA 2000 VA 2350 VA 2350 VA 3400 VA 3400 VA
No-load voltage (app x factor) 104 104 104 104 103 103
Efficiency 92 92 92 92 94 94
StandardsClassification Control- and safety isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 160 - 250 A 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 250 - 400 A
Setting value 230 plusmn15 Vac 240 A 240 A 300 A 300 A 370 A 370 A
Setting range 400 plusmn15 Vac 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 400 plusmn15 Vac 140 A 140 A 170 A 170 A 220 A 220 A
Order numbersOrder Number STEU 50024 STEU 50023 STEU 63024 STEU 63023 STEU 80048 STEU 80024
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac 2x115 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 800 VA 1000 VA 1000 VA 1000 VA 1600 VA 2000 VA
Rated power VDE (KB cos phi=05) 3400 VA 5000 VA 5000 VA 5000 VA 7800 VA 10900 VA
No-load voltage (app x factor) 103 103 103 103 101 102
Efficiency 94 94 94 94 94 94
StandardsClassification Control- and isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 250 - 400 A 400 - 630 A 400 - 630 A 400 - 630 A 630 - 1000 A 800 - 1000 A
Setting value 230 plusmn15 Vac 370 A 460 A 460 A 460 A 730 A 910 A
Setting range 400 plusmn15 Vac 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 400 - 630 A 400 - 630 A
Setting value 400 plusmn15 Vac 220 A 270 A 270 A 270 A 420 A 520 A
Order numbersOrder Number STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
+-
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 35
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac 2x115 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 800 VA 1000 VA 1000 VA 1000 VA 1600 VA 2000 VA
Rated power VDE (KB cos phi=05) 3400 VA 5000 VA 5000 VA 5000 VA 7800 VA 10900 VA
No-load voltage (app x factor) 103 103 103 103 101 102
Efficiency 94 94 94 94 94 94
StandardsClassification Control- and isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 250 - 400 A 400 - 630 A 400 - 630 A 400 - 630 A 630 - 1000 A 800 - 1000 A
Setting value 230 plusmn15 Vac 370 A 460 A 460 A 460 A 730 A 910 A
Setting range 400 plusmn15 Vac 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 400 - 630 A 400 - 630 A
Setting value 400 plusmn15 Vac 220 A 270 A 270 A 270 A 420 A 520 A
Order numbersOrder Number STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
+-Transformers Control transformers1
BLOCKWebsite
36 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 250023
InputRated input voltage 230400 Vac
Tappings Input plusmn15 V
Frequency range 50 - 60 Hz
OutputRated output voltage 2x115 Vac
Rated power VDE (DB cos phi=1) 2500 VA
Rated power VDE (KB cos phi=05) 12400 VA
No-load voltage (app x factor) 102
Efficiency 94
StandardsClassification Control- and isolating
transformer
ApprovalsApprovals cURus
EnvironmentAmbient temperature max 40 degC
Cooling method self-cooling
Safety and protectionType Open type
Class of Insulation System VDE=B UL=class 130
Protection index IP 00
Safety class (prepared) I
Short circuit strength non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 1000 - 1600 A
Setting value 230 plusmn15 Vac 1120 A
Setting range 400 plusmn15 Vac 630 - 1000 A
Setting value 400 plusmn15 Vac 650 A
Order numbersOrder Number STEU 250023
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 37
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
Transformers Control transformers1
BLOCKWebsite
32 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 16048 STEU 16024 STEU 16023 STEU 25048 STEU 25024 STEU 25023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 160 VA 160 VA 160 VA 250 VA 250 VA 250 VA
Rated power VDE (KB cos phi=05) 490 VA 490 VA 490 VA 850 VA 850 VA 850 VA
No-load voltage (app x factor) 110 110 110 107 107 107
Efficiency 86 86 86 88 88 88
StandardsClassification Control- and isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 063 - 100 A 063 - 100 A 063 - 100 A 100 - 160 A 100 - 160 A 100 - 160 A
Setting value 230 plusmn15 Vac 080 A 080 A 080 A 120 A 120 A 120 A
Setting range 400 plusmn15 Vac 040 - 063 A 040 - 063 A 040 - 063 A 063 - 100 A 063 - 100 A 063 - 100 A
Setting value 400 plusmn15 Vac 046 A 046 A 046 A 070 A 070 A 070 A
Order numbersOrder Number STEU 16048 STEU 16024 STEU 16023 STEU 25048 STEU 25024 STEU 25023
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac
Rated power VDE (DB cos phi=1) 320 VA 320 VA 320 VA 400 VA 400 VA 500 VA
Rated power VDE (KB cos phi=05) 1120 VA 1120 VA 1120 VA 1440 VA 1440 VA 2000 VA
No-load voltage (app x factor) 107 107 107 104 104 104
Efficiency 90 90 90 90 90 92
StandardsClassification Control- and isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 100 - 160 A 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 230 plusmn15 Vac 150 A 150 A 150 A 190 A 190 A 240 A
Setting range 400 plusmn15 Vac 063 - 100 A 063 - 100 A 063 - 100 A 100 - 160 A 100 - 160 A 100 - 160 A
Setting value 400 plusmn15 Vac 088 A 088 A 088 A 110 A 110 A 140 A
Order numbersOrder Number STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
+-
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 33
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac
Rated power VDE (DB cos phi=1) 320 VA 320 VA 320 VA 400 VA 400 VA 500 VA
Rated power VDE (KB cos phi=05) 1120 VA 1120 VA 1120 VA 1440 VA 1440 VA 2000 VA
No-load voltage (app x factor) 107 107 107 104 104 104
Efficiency 90 90 90 90 90 92
StandardsClassification Control- and isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 100 - 160 A 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 230 plusmn15 Vac 150 A 150 A 150 A 190 A 190 A 240 A
Setting range 400 plusmn15 Vac 063 - 100 A 063 - 100 A 063 - 100 A 100 - 160 A 100 - 160 A 100 - 160 A
Setting value 400 plusmn15 Vac 088 A 088 A 088 A 110 A 110 A 140 A
Order numbersOrder Number STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
+-Transformers Control transformers1
BLOCKWebsite
34 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 50024 STEU 50023 STEU 63024 STEU 63023 STEU 80048 STEU 80024
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac 2x12 Vac
Rated power VDE (DB cos phi=1) 500 VA 500 VA 630 VA 630 VA 800 VA 800 VA
Rated power VDE (KB cos phi=05) 2000 VA 2000 VA 2350 VA 2350 VA 3400 VA 3400 VA
No-load voltage (app x factor) 104 104 104 104 103 103
Efficiency 92 92 92 92 94 94
StandardsClassification Control- and safety isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 160 - 250 A 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 250 - 400 A
Setting value 230 plusmn15 Vac 240 A 240 A 300 A 300 A 370 A 370 A
Setting range 400 plusmn15 Vac 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 400 plusmn15 Vac 140 A 140 A 170 A 170 A 220 A 220 A
Order numbersOrder Number STEU 50024 STEU 50023 STEU 63024 STEU 63023 STEU 80048 STEU 80024
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac 2x115 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 800 VA 1000 VA 1000 VA 1000 VA 1600 VA 2000 VA
Rated power VDE (KB cos phi=05) 3400 VA 5000 VA 5000 VA 5000 VA 7800 VA 10900 VA
No-load voltage (app x factor) 103 103 103 103 101 102
Efficiency 94 94 94 94 94 94
StandardsClassification Control- and isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 250 - 400 A 400 - 630 A 400 - 630 A 400 - 630 A 630 - 1000 A 800 - 1000 A
Setting value 230 plusmn15 Vac 370 A 460 A 460 A 460 A 730 A 910 A
Setting range 400 plusmn15 Vac 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 400 - 630 A 400 - 630 A
Setting value 400 plusmn15 Vac 220 A 270 A 270 A 270 A 420 A 520 A
Order numbersOrder Number STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
+-
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 35
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac 2x115 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 800 VA 1000 VA 1000 VA 1000 VA 1600 VA 2000 VA
Rated power VDE (KB cos phi=05) 3400 VA 5000 VA 5000 VA 5000 VA 7800 VA 10900 VA
No-load voltage (app x factor) 103 103 103 103 101 102
Efficiency 94 94 94 94 94 94
StandardsClassification Control- and isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 250 - 400 A 400 - 630 A 400 - 630 A 400 - 630 A 630 - 1000 A 800 - 1000 A
Setting value 230 plusmn15 Vac 370 A 460 A 460 A 460 A 730 A 910 A
Setting range 400 plusmn15 Vac 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 400 - 630 A 400 - 630 A
Setting value 400 plusmn15 Vac 220 A 270 A 270 A 270 A 420 A 520 A
Order numbersOrder Number STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
+-Transformers Control transformers1
BLOCKWebsite
36 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 250023
InputRated input voltage 230400 Vac
Tappings Input plusmn15 V
Frequency range 50 - 60 Hz
OutputRated output voltage 2x115 Vac
Rated power VDE (DB cos phi=1) 2500 VA
Rated power VDE (KB cos phi=05) 12400 VA
No-load voltage (app x factor) 102
Efficiency 94
StandardsClassification Control- and isolating
transformer
ApprovalsApprovals cURus
EnvironmentAmbient temperature max 40 degC
Cooling method self-cooling
Safety and protectionType Open type
Class of Insulation System VDE=B UL=class 130
Protection index IP 00
Safety class (prepared) I
Short circuit strength non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 1000 - 1600 A
Setting value 230 plusmn15 Vac 1120 A
Setting range 400 plusmn15 Vac 630 - 1000 A
Setting value 400 plusmn15 Vac 650 A
Order numbersOrder Number STEU 250023
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 37
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
Transformers Control transformers1
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 33
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x24 Vac 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac
Rated power VDE (DB cos phi=1) 320 VA 320 VA 320 VA 400 VA 400 VA 500 VA
Rated power VDE (KB cos phi=05) 1120 VA 1120 VA 1120 VA 1440 VA 1440 VA 2000 VA
No-load voltage (app x factor) 107 107 107 104 104 104
Efficiency 90 90 90 90 90 92
StandardsClassification Control- and isolating
transformerControl- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 100 - 160 A 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 230 plusmn15 Vac 150 A 150 A 150 A 190 A 190 A 240 A
Setting range 400 plusmn15 Vac 063 - 100 A 063 - 100 A 063 - 100 A 100 - 160 A 100 - 160 A 100 - 160 A
Setting value 400 plusmn15 Vac 088 A 088 A 088 A 110 A 110 A 140 A
Order numbersOrder Number STEU 32048 STEU 32024 STEU 32023 STEU 40024 STEU 40023 STEU 50048
+-Transformers Control transformers1
BLOCKWebsite
34 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 50024 STEU 50023 STEU 63024 STEU 63023 STEU 80048 STEU 80024
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac 2x12 Vac
Rated power VDE (DB cos phi=1) 500 VA 500 VA 630 VA 630 VA 800 VA 800 VA
Rated power VDE (KB cos phi=05) 2000 VA 2000 VA 2350 VA 2350 VA 3400 VA 3400 VA
No-load voltage (app x factor) 104 104 104 104 103 103
Efficiency 92 92 92 92 94 94
StandardsClassification Control- and safety isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 160 - 250 A 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 250 - 400 A
Setting value 230 plusmn15 Vac 240 A 240 A 300 A 300 A 370 A 370 A
Setting range 400 plusmn15 Vac 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 400 plusmn15 Vac 140 A 140 A 170 A 170 A 220 A 220 A
Order numbersOrder Number STEU 50024 STEU 50023 STEU 63024 STEU 63023 STEU 80048 STEU 80024
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac 2x115 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 800 VA 1000 VA 1000 VA 1000 VA 1600 VA 2000 VA
Rated power VDE (KB cos phi=05) 3400 VA 5000 VA 5000 VA 5000 VA 7800 VA 10900 VA
No-load voltage (app x factor) 103 103 103 103 101 102
Efficiency 94 94 94 94 94 94
StandardsClassification Control- and isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 250 - 400 A 400 - 630 A 400 - 630 A 400 - 630 A 630 - 1000 A 800 - 1000 A
Setting value 230 plusmn15 Vac 370 A 460 A 460 A 460 A 730 A 910 A
Setting range 400 plusmn15 Vac 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 400 - 630 A 400 - 630 A
Setting value 400 plusmn15 Vac 220 A 270 A 270 A 270 A 420 A 520 A
Order numbersOrder Number STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
+-
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 35
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac 2x115 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 800 VA 1000 VA 1000 VA 1000 VA 1600 VA 2000 VA
Rated power VDE (KB cos phi=05) 3400 VA 5000 VA 5000 VA 5000 VA 7800 VA 10900 VA
No-load voltage (app x factor) 103 103 103 103 101 102
Efficiency 94 94 94 94 94 94
StandardsClassification Control- and isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 250 - 400 A 400 - 630 A 400 - 630 A 400 - 630 A 630 - 1000 A 800 - 1000 A
Setting value 230 plusmn15 Vac 370 A 460 A 460 A 460 A 730 A 910 A
Setting range 400 plusmn15 Vac 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 400 - 630 A 400 - 630 A
Setting value 400 plusmn15 Vac 220 A 270 A 270 A 270 A 420 A 520 A
Order numbersOrder Number STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
+-Transformers Control transformers1
BLOCKWebsite
36 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 250023
InputRated input voltage 230400 Vac
Tappings Input plusmn15 V
Frequency range 50 - 60 Hz
OutputRated output voltage 2x115 Vac
Rated power VDE (DB cos phi=1) 2500 VA
Rated power VDE (KB cos phi=05) 12400 VA
No-load voltage (app x factor) 102
Efficiency 94
StandardsClassification Control- and isolating
transformer
ApprovalsApprovals cURus
EnvironmentAmbient temperature max 40 degC
Cooling method self-cooling
Safety and protectionType Open type
Class of Insulation System VDE=B UL=class 130
Protection index IP 00
Safety class (prepared) I
Short circuit strength non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 1000 - 1600 A
Setting value 230 plusmn15 Vac 1120 A
Setting range 400 plusmn15 Vac 630 - 1000 A
Setting value 400 plusmn15 Vac 650 A
Order numbersOrder Number STEU 250023
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 37
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
Transformers Control transformers1
BLOCKWebsite
34 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 50024 STEU 50023 STEU 63024 STEU 63023 STEU 80048 STEU 80024
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x12 Vac 2x115 Vac 2x12 Vac 2x115 Vac 2x24 Vac 2x12 Vac
Rated power VDE (DB cos phi=1) 500 VA 500 VA 630 VA 630 VA 800 VA 800 VA
Rated power VDE (KB cos phi=05) 2000 VA 2000 VA 2350 VA 2350 VA 3400 VA 3400 VA
No-load voltage (app x factor) 104 104 104 104 103 103
Efficiency 92 92 92 92 94 94
StandardsClassification Control- and safety isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and safety isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 160 - 250 A 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 250 - 400 A
Setting value 230 plusmn15 Vac 240 A 240 A 300 A 300 A 370 A 370 A
Setting range 400 plusmn15 Vac 100 - 160 A 100 - 160 A 160 - 250 A 160 - 250 A 160 - 250 A 160 - 250 A
Setting value 400 plusmn15 Vac 140 A 140 A 170 A 170 A 220 A 220 A
Order numbersOrder Number STEU 50024 STEU 50023 STEU 63024 STEU 63023 STEU 80048 STEU 80024
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac 2x115 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 800 VA 1000 VA 1000 VA 1000 VA 1600 VA 2000 VA
Rated power VDE (KB cos phi=05) 3400 VA 5000 VA 5000 VA 5000 VA 7800 VA 10900 VA
No-load voltage (app x factor) 103 103 103 103 101 102
Efficiency 94 94 94 94 94 94
StandardsClassification Control- and isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 250 - 400 A 400 - 630 A 400 - 630 A 400 - 630 A 630 - 1000 A 800 - 1000 A
Setting value 230 plusmn15 Vac 370 A 460 A 460 A 460 A 730 A 910 A
Setting range 400 plusmn15 Vac 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 400 - 630 A 400 - 630 A
Setting value 400 plusmn15 Vac 220 A 270 A 270 A 270 A 420 A 520 A
Order numbersOrder Number STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
+-
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 35
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac 2x115 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 800 VA 1000 VA 1000 VA 1000 VA 1600 VA 2000 VA
Rated power VDE (KB cos phi=05) 3400 VA 5000 VA 5000 VA 5000 VA 7800 VA 10900 VA
No-load voltage (app x factor) 103 103 103 103 101 102
Efficiency 94 94 94 94 94 94
StandardsClassification Control- and isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 250 - 400 A 400 - 630 A 400 - 630 A 400 - 630 A 630 - 1000 A 800 - 1000 A
Setting value 230 plusmn15 Vac 370 A 460 A 460 A 460 A 730 A 910 A
Setting range 400 plusmn15 Vac 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 400 - 630 A 400 - 630 A
Setting value 400 plusmn15 Vac 220 A 270 A 270 A 270 A 420 A 520 A
Order numbersOrder Number STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
+-Transformers Control transformers1
BLOCKWebsite
36 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 250023
InputRated input voltage 230400 Vac
Tappings Input plusmn15 V
Frequency range 50 - 60 Hz
OutputRated output voltage 2x115 Vac
Rated power VDE (DB cos phi=1) 2500 VA
Rated power VDE (KB cos phi=05) 12400 VA
No-load voltage (app x factor) 102
Efficiency 94
StandardsClassification Control- and isolating
transformer
ApprovalsApprovals cURus
EnvironmentAmbient temperature max 40 degC
Cooling method self-cooling
Safety and protectionType Open type
Class of Insulation System VDE=B UL=class 130
Protection index IP 00
Safety class (prepared) I
Short circuit strength non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 1000 - 1600 A
Setting value 230 plusmn15 Vac 1120 A
Setting range 400 plusmn15 Vac 630 - 1000 A
Setting value 400 plusmn15 Vac 650 A
Order numbersOrder Number STEU 250023
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 37
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
Transformers Control transformers1
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 35
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
InputRated input voltage 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac 230400 Vac
Tappings Input plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V plusmn15 V
Frequency range 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
OutputRated output voltage 2x115 Vac 2x24 Vac 2x12 Vac 2x115 Vac 2x115 Vac 2x115 Vac
Rated power VDE (DB cos phi=1) 800 VA 1000 VA 1000 VA 1000 VA 1600 VA 2000 VA
Rated power VDE (KB cos phi=05) 3400 VA 5000 VA 5000 VA 5000 VA 7800 VA 10900 VA
No-load voltage (app x factor) 103 103 103 103 101 102
Efficiency 94 94 94 94 94 94
StandardsClassification Control- and isolating
transformerControl- and isolatingtransformer
Control- and safety isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
Control- and isolatingtransformer
ApprovalsApprovals cURus cURus cURus cURus cURus cURus
EnvironmentAmbient temperature max 40 degC 40 degC 40 degC 40 degC 40 degC 40 degC
Cooling method self-cooling self-cooling self-cooling self-cooling self-cooling self-cooling
Safety and protectionType Open type Open type Open type Open type Open type Open type
Class of Insulation System VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130 VDE=B UL=class 130
Protection index IP 00 IP 00 IP 00 IP 00 IP 00 IP 00
Safety class (prepared) I I I I I I
Short circuit strength non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 250 - 400 A 400 - 630 A 400 - 630 A 400 - 630 A 630 - 1000 A 800 - 1000 A
Setting value 230 plusmn15 Vac 370 A 460 A 460 A 460 A 730 A 910 A
Setting range 400 plusmn15 Vac 160 - 250 A 250 - 400 A 250 - 400 A 250 - 400 A 400 - 630 A 400 - 630 A
Setting value 400 plusmn15 Vac 220 A 270 A 270 A 270 A 420 A 520 A
Order numbersOrder Number STEU 80023 STEU 100048 STEU 100024 STEU 100023 STEU 160023 STEU 200023
+-Transformers Control transformers1
BLOCKWebsite
36 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 250023
InputRated input voltage 230400 Vac
Tappings Input plusmn15 V
Frequency range 50 - 60 Hz
OutputRated output voltage 2x115 Vac
Rated power VDE (DB cos phi=1) 2500 VA
Rated power VDE (KB cos phi=05) 12400 VA
No-load voltage (app x factor) 102
Efficiency 94
StandardsClassification Control- and isolating
transformer
ApprovalsApprovals cURus
EnvironmentAmbient temperature max 40 degC
Cooling method self-cooling
Safety and protectionType Open type
Class of Insulation System VDE=B UL=class 130
Protection index IP 00
Safety class (prepared) I
Short circuit strength non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 1000 - 1600 A
Setting value 230 plusmn15 Vac 1120 A
Setting range 400 plusmn15 Vac 630 - 1000 A
Setting value 400 plusmn15 Vac 650 A
Order numbersOrder Number STEU 250023
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 37
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
Transformers Control transformers1
BLOCKWebsite
36 Subject to change
Control- and safety isolating- resp isolatingtransformerSTEU
Typ STEU 250023
InputRated input voltage 230400 Vac
Tappings Input plusmn15 V
Frequency range 50 - 60 Hz
OutputRated output voltage 2x115 Vac
Rated power VDE (DB cos phi=1) 2500 VA
Rated power VDE (KB cos phi=05) 12400 VA
No-load voltage (app x factor) 102
Efficiency 94
StandardsClassification Control- and isolating
transformer
ApprovalsApprovals cURus
EnvironmentAmbient temperature max 40 degC
Cooling method self-cooling
Safety and protectionType Open type
Class of Insulation System VDE=B UL=class 130
Protection index IP 00
Safety class (prepared) I
Short circuit strength non-short-circuit proof
PRI Fusing recommendationby circuit breaker withtripping characteristic type20 x Irated related to set)Setting range 230 plusmn15 Vac 1000 - 1600 A
Setting value 230 plusmn15 Vac 1120 A
Setting range 400 plusmn15 Vac 630 - 1000 A
Setting value 400 plusmn15 Vac 650 A
Order numbersOrder Number STEU 250023
+-Transformers Control transformers1
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 37
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
Transformers Control transformers1
BLOCKWebsite
11
12
51
13
21
22
31
32
33
52
40
Subject to change 37
Control- and safety isolating- resp isolatingtransformerSTEU
Typ
Term
inals
Fixing
met
hod
Fixing
scr
ews
Weig
ht
Dim
ensio
n pic
ture
(in
mm
)
A B C D E F
STEU 6348 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6324 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 6323 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 130 kg 1 84 85 88 64 64 46
STEU 10048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 10023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M4 210 kg 1 84 85 96 64 64 545
STEU 16048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 16023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 290 kg 1 96 102 104 84 87 56
STEU 25048 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 25024 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 102 104 84 87 625
STEU 25023 Spring terminal PE 63 x 08 Dual purpose base plate also forinstallation on mounting rails M5 360 kg 1 96 125 105 84 87 625
STEU 32048 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32024 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 32023 Spring terminal PE 63 x 08 Base plate M5 430 kg 2 120 107 121 90 74 55STEU 40024 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 40023 Spring terminal PE 63 x 08 Base plate M5 530 kg 2 120 104 121 90 86 60STEU 50048 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50024 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 50023 Spring terminal PE 63 x 08 Base plate M5 770 kg 2 120 124 121 90 106 71STEU 63024 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 113 143 122 91 59STEU 63023 Spring terminal PE 63 x 08 Base plate M6 790 kg 2 150 117 148 122 91 59STEU 80048 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80024 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 80023 Spring terminal PE 63 x 08 Base plate M6 1030 kg 2 150 130 143 122 1075 65STEU 100048 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 100024 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 180 185 122 134 82STEU 100023 Spring terminal PE 63 x 08 Base plate M6 1330 kg 2 150 156 143 122 134 82STEU 160023 Spring terminal PE 63 x 08 Base plate M8 2100 kg 2 192 161 185 155 133 80STEU 200023 Spring terminal PE 63 x 08 Base plate M8 2550 kg 2 192 183 185 156 155 91STEU 250023 Spring terminal PE 63 x 08 Base plate M8 2700 kg 2 192 190 185 156 161 94
30
Dimension pictures
Transformers Control transformers1
BLOCKWebsite