Benefits of thermography
Quick inspection Results clearly shown in pictures Shows precise location of fault Shows severity of fault Shows compliance with
regulations Improves build quality
![Page 3: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/3.jpg)
3
Limitations
Needs temperature difference Needs clear view of surface Building surveys limited by
Wind Rain Past temperatures Not an accurate heat loss assessment
Cameras are not cheap They are more affordable than they were And you can hire by the week
![Page 4: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/4.jpg)
4
Typical applications
Building insulation and air leakage Building energy efficiency Building moisture surveys Pipework Electrical installations
![Page 5: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/5.jpg)
5
Building insulation and air leakage
Meet requirements of Building Regulations Part L ‘reasonably continuous thermal insulation’
Show air leakage paths to help re-sealing
![Page 6: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/6.jpg)
6
Air tightness testing
![Page 7: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/7.jpg)
7
Testing to include effect of leakage through the floor
Can include smoke testing
Can include both pressurisation and depressurisation tests
![Page 8: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/8.jpg)
8
Locating air leakage
4.6°C
13.4°C
6
8
10
12
SP01
![Page 9: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/9.jpg)
9
![Page 10: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/10.jpg)
10
Understand how thermography is affected by:
features of buildings, surface properties acceptable temperatures, understanding the environment you are
working in, obtaining a good image, differentiating between anomalies faults and normal temperature variations.
![Page 11: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/11.jpg)
Thermal Imaging
11
10oC temperature difference for at least 4 hours.
Dry, no sun, wind speed < 8m/s.
320 x 240 pixels minimum infrared resolution.
![Page 12: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/12.jpg)
12
Features of buildings important for Thermography
Masonry or framed construction Glass Rainscreen cladding Air outlets Light fittings Heaters
![Page 13: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/13.jpg)
13
Framed construction - roof
![Page 14: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/14.jpg)
14
Framed Construction - walls
![Page 15: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/15.jpg)
15
Glass not transparent
10.0°C
14.5°C
10
11
12
13
14AR01: 11.6°C
SP01: 15.8°C
![Page 16: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/16.jpg)
16
Heat sources under windows
7.0°C
13.0°C
8
10
12
![Page 17: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/17.jpg)
17
Acceptable temperatures
Need to have sufficient temperature difference to detect defects
Normally means at least 10°C between inside and out
![Page 18: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/18.jpg)
18
Understand the environment
Heat exchange by radiation and convection Sky can be –50°C Sunshine can raise surface temperature to
+70°C in the UK Set the ‘ambient temperature’ in your camera Wind can eliminate surface temperature
difference in external surveys
![Page 19: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/19.jpg)
19
Effects of cold sky
-18.0°C
-3.1°C
-15
-10
-5
SP01: <-20.0°CSP02: -14.1°C
SP03: -3.9°C
SP04: <-20.0°C
![Page 20: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/20.jpg)
20
In buildings with no heating
![Page 21: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/21.jpg)
21
Solar gain can be used to an advantage
![Page 22: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/22.jpg)
22
Obtain a good image
At survey time: Subject Distance/resolution Focus Broad temperature range
In analysis Correct temperature range Correct environmental settings
![Page 23: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/23.jpg)
23
Zoom in to focus
7.0°C
13.0°C
8
10
12
![Page 24: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/24.jpg)
24
Zoom out for full image
7.0°C
13.0°C
8
10
12
![Page 25: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/25.jpg)
25
Benefits of high resolution
![Page 26: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/26.jpg)
26
Defect, anomaly or feature
30.0°C
36.0°C
30
32
34
36
![Page 27: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/27.jpg)
27
Cold bridges - steelwork
21.2°C
26.5°C
22
23
24
25
26SP01
SP02 SP03
SP04
![Page 28: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/28.jpg)
28
Thermography locates air leakage
behind plasterboard
![Page 29: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/29.jpg)
29
Thermography locates air leakage
25.5°C
31.0°C
26
27
28
29
30
31
behind plasterboard
![Page 30: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/30.jpg)
30
Extract from the thermographic
report
Note: this is inside of building but outside was warmer so the poorly insulated areas show up as warm
![Page 31: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/31.jpg)
31
Case study 1
retail building, 130x75 metres and 6-9 m high interface detail left a 73mm strip uninsulated =30 square metres of cladding with a U value
of 3.5W/m²K instead of 0.35W/m²K. would require an extra 2kW of heating nearly 8000 kWh a year extra heating cost of over £600 a year generating nearly 4000kg of additional CO2.
![Page 32: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/32.jpg)
32
Building fabric thermography
Construction defects
![Page 33: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/33.jpg)
33
Building fabric thermography
Construction defects
Remedial action
![Page 34: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/34.jpg)
34
Case study 2
Traditional brick - cavity - block wall Note surface temperature variations Effect of missing cavity bat Effect of mortar joint Condensation Mould growth
![Page 35: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/35.jpg)
35
Mortar in poor structure U value 1.41
![Page 36: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/36.jpg)
36
Mortar in poor structure U value 1.41
![Page 37: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/37.jpg)
37
Energy surveys
Temperature differences between similar areas
Hidden features
Buried services
-18.2°C
-3.3°C
-15
-10
-5
SP01SP02
SP03
![Page 38: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/38.jpg)
38Wasted Energy ?
![Page 39: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/39.jpg)
39
Roof Moisture
Warm area shows moisture in roof structure
![Page 40: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/40.jpg)
40
Roof moisture survey
Relies on change in temperature Survey after sunset on a sunny day Avoid surface water or debris Moist insulation has high thermal capacity Stays warm for some time after sunset Sharp contrast with dry insulation
![Page 41: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/41.jpg)
41
Underfloor heating
Warm areas shows underfloor heating pipes
![Page 42: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/42.jpg)
42
Underfloor heating
What can go wrong?
13.7°C
31.0°C
15
20
25
30
12.4°C
21.2°C
14
16
18
20
9.7°C
17.0°C
10
12
14
16
11.9°C
16.4°C
12
13
14
15
16
![Page 43: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/43.jpg)
43
Chilled ceilings
Cold areas are working, warm are not
![Page 44: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/44.jpg)
44
Busbars
65.0°C
120.0°C
70
80
90
100
110
120
SP01
SP02
![Page 45: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/45.jpg)
45
What to inspect
Critical items Where no other method
– don’t forget conventional test & inspection
Consider failure modes Cost / benefit Access / safety
![Page 46: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/46.jpg)
46UPS Battery Systems
![Page 47: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/47.jpg)
47
Electrical thermography to avoid fires
![Page 48: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/48.jpg)
48
Commissioning lighting panel
12.0°C
74.0°C
20
40
60
AR01: 13.1°C
12.0°C
74.0°C
20
40
60
AR01: 26.2°C
12.0°C
74.0°C
20
40
60
AR01: 36.9°C
12.0°C
74.0°C
20
40
60
AR01: 44.6°C
12.0°C
74.0°C
20
40
60
AR01: 54.0°C
12.0°C
74.0°C
20
40
60
AR01: 61.0°C
12.0°C
74.0°C
20
40
60
AR01: 68.8°C
12.0°C
74.0°C
20
40
60
AR01: 72.8°C
12.0°C
74.0°C
20
40
60
AR01: 79.3°C
12.0°C
74.0°C
20
40
60
AR01: 81.7°C
![Page 49: 1 Thermography of Buildings Stacey Ward - BSRIA Instrument Solutions - - Sales Manager -](https://reader034.vdocuments.net/reader034/viewer/2022051517/56649ced5503460f949bae41/html5/thumbnails/49.jpg)
49
Summary
Thermography has almost limitless applications Quick and easy way of checking quality and
condition New regulations will increase use Standards are being established Training and Certification essential BSRIA at the centre of development