10. io-link technology - russell smith
TRANSCRIPT
Russell Smith
Balluff Limited
IO-Link Technology
2 PROFIBUS UK
what is IO-link?
3 PROFIBUS UK 3
not another bus system!
point to point communications protocol from the fieldbus to the sensor and actuator level.
up
to
20
M
Pulse-width modulated 24V
Baud rates: 4.8 kBit/s (COM1), 38.4 kBit/s (COM2), 230,4 kBits/s (COM3)
Pin Signal Description
1 L + 24 Volt
2
3 L - 0 Volt
4 C / Q IO-Link
communication
+ switching signal
4 PROFIBUS UK 4
an open standard
standard - IEC 61131-9
network neutral
5 PROFIBUS UK 5
IO-Link system basic components:
IO-Link master … acts as a gateway between the IO-Link device and the higher level communication
system, such as a fieldbus (Profinet, EtherNet/IP, etc.) or a device-specific backplane bus.
IO-Link device … is the field device with communication capability: sensors, switching
devices, valve terminals, RFID devices, indicator lights, etc.
3-core unshielded standard cable – up to 20M long … is the standard interface between IO-Link master and device
IODD and engineering tool
… are used to configure and assign parameters to the IO-Link system and devices.
6 PROFIBUS UK 6
IO-Link devices
many different IO-Link devices are available.
7 PROFIBUS UK 7
IO-Link masters
panel
mounted unit
with terminals
IP67 field I/O
module
additional slice on existing PLC
8 PROFIBUS UK
why IO-Link?
9 PROFIBUS UK 9
easier handling of measurement devices
lower cost – no analogue card
lower cost vs IE networked device
less wiring effort
traditionally
better
best
10 PROFIBUS UK 10
low cost per I/O point – 496 I/O on one IP address
low cost
high density
less addresses
11 PROFIBUS UK 11
extensive diagnostics
available on sensors/devices and sensor hubs
troubleshoot problems quickly
maximise up-time
12 PROFIBUS UK 12
extensive diagnostics
Short circuit – LED for each I/O port
Short circuit does not impair the unit
Sensor/actuator under voltage LED for each I/O port
13 PROFIBUS UK 13
simplify valve manifold wiring
reduced installation time
reduced cost
14 PROFIBUS UK 14
IO-Link safety
15 PROFIBUS UK 15
extends communication
ERP
MES
SCADA
PLC
Network
Sensors and Actuators
Enterprise Level
Control Level
Management Level
Plant Control Level
Field Level
Sensor / Actuator Level
16 PROFIBUS UK 16
HMI
parameterisation – std pressure sensor
HMI
HMI HMI HMI HMI
17 PROFIBUS UK
parameterisation – std pressure sensor
Time consuming configuration of 10 – 15 Parameter. (e.g. upper/lower Pressure point, Hysteresis, Time – or Pressure window)
Machine Tools have often more than 10 Pressure sensors
Error prone due to manual entry
Very bad when Sensor failure / Sensor exchange (especially during night shift)
Manual
configuration
18 PROFIBUS UK 18
parameterisation – std pressure sensor
HMI
HMI
HMI
HMI
19 PROFIBUS UK 19
HMI integrated in sensor for set up means additional cost.
Expensive high-pressure hydraulic
hoses
parameterisation – std pressure sensor
machine tool
Additional cost for protective housing for sensors in the machine
20 PROFIBUS UK 20
parameterisation – pressure sensor with IO-Link
E.g. machine tool
21 PROFIBUS UK 21
PLC
Function-
blocks
Vendor_ID
Device_ID
Param1: 50bar
Param2: 100bar
Param3: 200ms
Step 1
Identify device
Step 3
Get Parameter Set
Step 2
Check identity
Step 4
Write Parameter
Set
parameterisation – pressure sensor with IO-Link
22 PROFIBUS UK 22
parameterisation – pressure sensor with IO-Link
sensor installed at point of measurement
no expensive measurement cables - use std un-shielded 3-wire standard cables
no protection case
no sensors with HMI but reliable parameterisation via controller and HMI of the machine
decentralised diagnostics for sensors
23 PROFIBUS UK 23
parameter server
IO-Link V1.1 master
24 PROFIBUS UK 24
automated tool changes
IO-Link inductive couplers for non-contact signal transmission
25 PROFIBUS UK 25
an i4.0 enabler
ERP
MES
SCADA
PLC
Network
Sensors and Actuators
Enterprise Level
Control Level
Management Level
Plant Control Level
Field Level
Sensor / Actuator Level
26 PROFIBUS UK 26
unabated IO-Link success!
27 PROFIBUS UK 27
how IO-Link?
28 PROFIBUS UK 28
connect the master to the PLC and install the GSDML file drag and drop the relevant file and make the PROFINET connection from the PLC to the master in TIA Portal
IO-Link master configuration
29 PROFIBUS UK 29
IO-Link master configuration
Drag the appropriate (process data length) IOL input / output byte from the catalogue and name & address the module
30 PROFIBUS UK 30
device configuration from PLC or using parameter server
1. controller parameter storage – parameterisation from the PLC using the function block
2. IO-Link master ver 1.1 parameter server
31 PROFIBUS UK 31
device configuration with USB master or webserver
3. Laptop via USB master (PROFIBUS) or Ethernet using Device Manager software
4. webserver entry with IO-Link master
32 PROFIBUS UK 32
device configuration with Device Manager
33 PROFIBUS UK 33
device configuration with Device Manager
34 PROFIBUS UK 34
device configuration with integrated web server
35 PROFIBUS UK 35
device configuration with integrated web server
36 PROFIBUS UK 36
device configuration - manual
Manual
configuration
5. Manual configuration
37 PROFIBUS UK 37