2 PROFIBUS UK

what is IO-link?

Page 3: 10. IO-Link technology - russell smith

3 PROFIBUS UK 3

not another bus system!

point to point communications protocol from the fieldbus to the sensor and actuator level.

up

to

20

M

Pulse-width modulated 24V

Baud rates: 4.8 kBit/s (COM1), 38.4 kBit/s (COM2), 230,4 kBits/s (COM3)

Pin Signal Description

1 L + 24 Volt

2

3 L - 0 Volt

4 C / Q IO-Link

communication

+ switching signal

Page 4: 10. IO-Link technology - russell smith

4 PROFIBUS UK 4

an open standard

standard - IEC 61131-9

network neutral

Page 5: 10. IO-Link technology - russell smith

5 PROFIBUS UK 5

IO-Link system basic components:

IO-Link master … acts as a gateway between the IO-Link device and the higher level communication

system, such as a fieldbus (Profinet, EtherNet/IP, etc.) or a device-specific backplane bus.

IO-Link device … is the field device with communication capability: sensors, switching

devices, valve terminals, RFID devices, indicator lights, etc.

3-core unshielded standard cable – up to 20M long … is the standard interface between IO-Link master and device

IODD and engineering tool

… are used to configure and assign parameters to the IO-Link system and devices.

Page 6: 10. IO-Link technology - russell smith

6 PROFIBUS UK 6

IO-Link devices

many different IO-Link devices are available.

Page 7: 10. IO-Link technology - russell smith

7 PROFIBUS UK 7

IO-Link masters

panel

mounted unit

with terminals

IP67 field I/O

module

additional slice on existing PLC

Page 8: 10. IO-Link technology - russell smith

8 PROFIBUS UK

why IO-Link?

Page 9: 10. IO-Link technology - russell smith

9 PROFIBUS UK 9

easier handling of measurement devices

lower cost – no analogue card

lower cost vs IE networked device

less wiring effort

traditionally

better

best

Page 10: 10. IO-Link technology - russell smith

10 PROFIBUS UK 10

low cost per I/O point – 496 I/O on one IP address

low cost

high density

less addresses

Page 11: 10. IO-Link technology - russell smith

11 PROFIBUS UK 11

extensive diagnostics

available on sensors/devices and sensor hubs

troubleshoot problems quickly

maximise up-time

Page 12: 10. IO-Link technology - russell smith

12 PROFIBUS UK 12

extensive diagnostics

Short circuit – LED for each I/O port

Short circuit does not impair the unit

Sensor/actuator under voltage LED for each I/O port

Page 13: 10. IO-Link technology - russell smith

13 PROFIBUS UK 13

simplify valve manifold wiring

reduced installation time

reduced cost

Page 14: 10. IO-Link technology - russell smith

14 PROFIBUS UK 14

IO-Link safety

Page 15: 10. IO-Link technology - russell smith

15 PROFIBUS UK 15

extends communication

ERP

MES

SCADA

PLC

Network

Sensors and Actuators

Enterprise Level

Control Level

Management Level

Plant Control Level

Field Level

Sensor / Actuator Level

Page 16: 10. IO-Link technology - russell smith

16 PROFIBUS UK 16

HMI

parameterisation – std pressure sensor

HMI

HMI HMI HMI HMI

Page 17: 10. IO-Link technology - russell smith

17 PROFIBUS UK

parameterisation – std pressure sensor

Time consuming configuration of 10 – 15 Parameter. (e.g. upper/lower Pressure point, Hysteresis, Time – or Pressure window)

Machine Tools have often more than 10 Pressure sensors

Error prone due to manual entry

Very bad when Sensor failure / Sensor exchange (especially during night shift)

Manual

configuration

Page 18: 10. IO-Link technology - russell smith

18 PROFIBUS UK 18

parameterisation – std pressure sensor

HMI

HMI

HMI

HMI

Page 19: 10. IO-Link technology - russell smith

19 PROFIBUS UK 19

HMI integrated in sensor for set up means additional cost.

Expensive high-pressure hydraulic

hoses

parameterisation – std pressure sensor

machine tool

Additional cost for protective housing for sensors in the machine

Page 20: 10. IO-Link technology - russell smith

20 PROFIBUS UK 20

parameterisation – pressure sensor with IO-Link

E.g. machine tool

Page 21: 10. IO-Link technology - russell smith

21 PROFIBUS UK 21

PLC

Function-

blocks

Vendor_ID

Device_ID

Param1: 50bar

Param2: 100bar

Param3: 200ms

Step 1

Identify device

Step 3

Get Parameter Set

Step 2

Check identity

Step 4

Write Parameter

Set

parameterisation – pressure sensor with IO-Link

Page 22: 10. IO-Link technology - russell smith

22 PROFIBUS UK 22

parameterisation – pressure sensor with IO-Link

sensor installed at point of measurement

no expensive measurement cables - use std un-shielded 3-wire standard cables

no protection case

no sensors with HMI but reliable parameterisation via controller and HMI of the machine

decentralised diagnostics for sensors

Page 23: 10. IO-Link technology - russell smith

23 PROFIBUS UK 23

parameter server

IO-Link V1.1 master

Page 24: 10. IO-Link technology - russell smith

24 PROFIBUS UK 24

automated tool changes

IO-Link inductive couplers for non-contact signal transmission

Page 25: 10. IO-Link technology - russell smith

25 PROFIBUS UK 25

an i4.0 enabler

ERP

MES

SCADA

PLC

Network

Sensors and Actuators

Enterprise Level

Control Level

Management Level

Plant Control Level

Field Level

Sensor / Actuator Level

Page 26: 10. IO-Link technology - russell smith

26 PROFIBUS UK 26

unabated IO-Link success!

Page 27: 10. IO-Link technology - russell smith

27 PROFIBUS UK 27

how IO-Link?

Page 28: 10. IO-Link technology - russell smith

28 PROFIBUS UK 28

connect the master to the PLC and install the GSDML file drag and drop the relevant file and make the PROFINET connection from the PLC to the master in TIA Portal

IO-Link master configuration

Page 29: 10. IO-Link technology - russell smith

29 PROFIBUS UK 29

IO-Link master configuration

Drag the appropriate (process data length) IOL input / output byte from the catalogue and name & address the module

Page 30: 10. IO-Link technology - russell smith

30 PROFIBUS UK 30

device configuration from PLC or using parameter server

1. controller parameter storage – parameterisation from the PLC using the function block

2. IO-Link master ver 1.1 parameter server

Page 31: 10. IO-Link technology - russell smith

31 PROFIBUS UK 31

device configuration with USB master or webserver

3. Laptop via USB master (PROFIBUS) or Ethernet using Device Manager software

4. webserver entry with IO-Link master

Page 32: 10. IO-Link technology - russell smith

32 PROFIBUS UK 32

device configuration with Device Manager

Page 33: 10. IO-Link technology - russell smith

33 PROFIBUS UK 33

device configuration with Device Manager

Page 34: 10. IO-Link technology - russell smith

34 PROFIBUS UK 34

device configuration with integrated web server

Page 35: 10. IO-Link technology - russell smith

35 PROFIBUS UK 35

device configuration with integrated web server

Page 36: 10. IO-Link technology - russell smith

36 PROFIBUS UK 36

device configuration - manual

Manual

configuration

5. Manual configuration

Page 37: 10. IO-Link technology - russell smith

37 PROFIBUS UK 37

THANKS FOR LISTENING!

Russell Smith

Product Marketing Manager Industrial Networking

+44 (0)777 331 7984

[email protected]