100mm dual hydrant riser assembly (agc) - b.i.c. hydrant risers.pdf · hra (agc) - dual - b.i.c....
TRANSCRIPT
����������������
Issue 1.0 28-04-15 DCF210A - HBICD100AGCFLG
100mm Dual Hydrant RiserAssembly (AGC) - B.I.C.
Assembly Product Code: HBICD100AGCFLG
Hydrant Valves: 2050kPaRoll Groove Couplings: 2050kPa
Hydrant Valves: AS2419.2: 2009Roll Groove Couplings: UL/FM ListedRoll Groove Fittings: UL/FM ListedHDG Pipe: AS1074/AS2419.1
Alternative Fire Brigade ConnectionsRoll Groove x Copper AdaptorsCustomised HeightsBelow Ground Connection (BGC)
100mm HDG Pipe
80mm Roll Groove Coupling &65mm B.I.C. Roll Groove Hydrant Valve
100mmRoll GrooveCoupling
100mm Roll Groovex Table 'E' Flange Adaptor
Cap
Working Pressures Approvals Options & Connections
Fire: H
RA
(A
GC
) -
Dual -
B.I.C
.
80mm Roll Groove Coupling &65mm B.I.C. Roll Groove Hydrant Valve
100mmRoll GrooveCoupling
�������
������
Issue 1.0 28-04-15 DCF210A - HBICD100AGCFLG
100mm Dual Hydrant RiserAssembly (AGC) - B.I.C.Dimensions & Installation Details
Installation Layout
Cabinet Product Code: CABH100
Cabinet complies with the requirements of AS2419.1
Minimum plinth dimensions: 1300mm x 600mm (Only if installed in cabinet)Fix cabinet through feet to concrete plinth.Fire Brigade Connections: • Hydrant Outlets ~ Clearance of 300mm (Min) through 225º radius.See AS2419.1 for further installation details.
Installation Notes:
Fire / Civil Sales e: [email protected]
Civil / Fire Sales e: [email protected]
Civil / Fire Sales Manager e: [email protected]
Dobbie
430 Victoria Road, Malaga. WA 6090
T: 08 9249 7000 F: 08 9249 7700
����������������
Issue 1.0 28-04-15 DCF215A - HBICD100BGCFLG
100mm Dual Hydrant RiserAssembly (BGC) - B.I.C.
Assembly Product Code: HBICD100BGCFLG
Hydrant Valves: 2050kPaRoll Groove Couplings: 2050kPa
Hydrant Valves: AS2419.2: 2009Roll Groove Couplings: UL/FM ListedRoll Groove Fittings: UL/FM ListedHDG Pipe: AS1074/AS2419.1
Alternative Fire Brigade ConnectionsCustomised HeightsAbove Ground Connection (AGC)Cabinet - AS2419.1
100mm HDG Pipe
80mm Roll Groove Coupling &65mm B.I.C. Roll Groove Hydrant Valve
100mm Roll Groove Coupling
Table 'E' Flange
Working Pressures Approvals Options & Connections
Fire: H
RA
(B
GC
) -
Dual -
B.I.C
.
80mm Roll Groove Coupling &65mm B.I.C. Roll Groove Hydrant Valve
����������������
Issue 1.0 28-04-15 DCF215A - HBICD100BGCFLG
100mm Dual Hydrant RiserAssembly (BGC) - B.I.C.Dimensions & Installation Details
Installation Layout
Fire Brigade Connections: • Hydrant Outlets ~ 750mm - 1200mm above Finished Ground Level. Clearance of 300mm (Min) through 225º radius.
See AS2419.1 for further installation details.
Installation Notes:
Fire / Civil Sales e: [email protected]
Civil / Fire Sales e: [email protected]
Civil / Fire Sales Manager e: [email protected]
Dobbie
430 Victoria Road, Malaga. WA 6090
T: 08 9249 7000 F: 08 9249 7700