15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4 Fuses Bulletin 745-114 Page 1 2015 Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com Mini-Rupter ® and Uni-Rupter ® are registered trademarks of S&C Electric Company. Elastimold ® is a registered trademark of ABB Asea Brown Boveri Ltd. C L C L Tamper-Resistant Enclosure meets National and Regional Enclosure Integrity Standards and virtually eliminates the entrance of airborne contamination to reduce maintenance Heavy duty 11-gauge steel enclosure is all-welded construction for long life S&C Mini-Rupter ® Switch with side-mounted non-removable handle, padlockable in “Open” or “Close” position. Provisions for key interlock are standard. Removable lift provisions with blind holes for tamper resistance Glass reinforced barriers meet NEMA GPO-3 Standards Coordinated padlock and penta-head or optional hex-head bolt (top and bottom) provides bolted door security with visual confirmation by supervisory personnel. Security bolt is made captive with a stainless steel washer compressed to an oval shape to severely discourage removal. Clear polycarbonate door safety barrier. Safety latches on the door safety barrier are insulating and require a positive action to remove the safety barrier. Barrier lift handles are insulating and keyed to prevent rotation. Overlapping door and enclosure flanges - with other features - provide tamper resistance to meet national and regional standards S&C Mini-Rupter ® Switch with front-mounted non-removable handle, padlockable in “Open” or “Close” position. Provisions for key interlock are standard. Fuse Mountings accept S&C SMU-20 or SM-4 Fuses Door-holder rods are stainless steel and hold the door open 100 degrees or 140 degrees Elliott Live Terminal Thru-Bushings connect to the switch terminals with 0.25” x 2” copper bus ENCLOSURE OPTIONS: 1) 0.125” #5052H32 Aluminum 2) 12-gauge #304L Stainless Steel Ground lugs accept #6 - #2/0 ground cable Stainless steel hinges are welded to the door and the enclosure – 0.375” pins are standard “In-Air” Insulation eliminates leaking or contamination of insulating medium for long trouble-free operation “In-Air” Visibility allows visual inspection of all components without the inconvenience or expense associated with equipment which must be de-energized for inspection Corrosion proof nameplate is located to provide easy access for the operator Kinked roof prevents standing moisture Superlife Finish includes phosphatizing, rust-inhibiting epoxy primer and Pad-Mount Green (Munsell 7GY 3.29/1.5) polyurethane top coat - over 5 mils dry Optional Paint: Grey (Munsell 5BG 7.0/0.4) Clear Polycarbonate Impact Resistant Bushing Guard with Open Top is available

Upload: others

Post on 15-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 1 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

CL

CL

Tamper-Resistant Enclosuremeets National and Regional Enclosure Integrity Standards and virtually eliminates the entrance of airbornecontamination to reducemaintenance

Heavy duty 11-gauge steelenclosure is all-weldedconstruction for long life

S&C Mini-Rupter® Switch with side-mounted non-removable handle, padlockable in “Open”or “Close” position. Provisionsfor key interlock are standard.

Removable lift provisionswith blind holes fortamper resistance

Glass reinforced barriers meetNEMA GPO-3Standards

Coordinated padlock and penta-head or optional hex-head bolt (top and bottom) provides bolted door security with visualconfirmation by supervisory personnel.Security bolt is made captive with astainless steel washer compressed to an oval shape to severely discourage removal.

Clear polycarbonate door safety barrier.Safety latches on the doorsafety barrier are insulatingand require a positiveaction to remove thesafety barrier. Barrier lifthandles are insulating andkeyed to prevent rotation.

Overlapping door andenclosure flanges - withother features - providetamper resistance to meetnational and regionalstandards

S&C Mini-Rupter® Switch with front-mounted non-removable handle, padlockable in “Open”or “Close” position. Provisionsfor key interlock are standard.

Fuse Mountingsaccept S&C SMU-20 or SM-4 Fuses

Door-holder rods are stainlesssteel and hold the door open100 degrees or 140 degrees

Elliott Live TerminalThru-Bushings connectto the switch terminalswith 0.25” x 2” copper bus

ENCLOSURE OPTIONS:1) 0.125” #5052H32 Aluminum2) 12-gauge #304L Stainless Steel

Ground lugs accept#6 - #2/0 ground cable

Stainless steel hinges are welded to the door and the enclosure – 0.375” pins are standard

“In-Air” Insulation eliminates leaking orcontamination ofinsulating medium forlong trouble-freeoperation

“In-Air” Visibilityallows visual inspectionof all components withoutthe inconvenience or expense associated with equipment which must be de-energized for inspection

Corrosion proof nameplateis located toprovide easyaccess for the operator

Kinked roof prevents standing moisture

Superlife Finishincludes phosphatizing,rust-inhibiting epoxy primerand Pad-Mount Green(Munsell 7GY 3.29/1.5)polyurethane top coat -over 5 mils dryOptional Paint:Grey (Munsell 5BG 7.0/0.4)

Clear PolycarbonateImpact Resistant Bushing Guard withOpen Top is available

Page 2: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 2 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

600 Amp S&C #255243-S1Mini-Rupter® Switch, with side-mounted non-removable handle, padlockable in “Open” or “Close” position. Provisions for key interlock are standard.

Option G1: Ground studs at bottom terminal of SwitchOption G2: Ground studs at main contact of SwitchOption K: Key interlock

Three-Phase – Two Ways per Phase600 Amp S&C Mini-Rupter® Switch8.3/14.4 kV Grounded Wye Max Design95 kV BIL

Side View Front ViewDoor & Door Safety Barrier Removed

Section AA

Section BB

Catalog Number OperatingHandle

FuseMounting

Fuse EndFittings/Holder

FuseUnit/Refill Dim. “A”

EMEHGL-15-311S-LT-RHMR Right Side(Shown Above)

NotApplicable

NotApplicable

NotApplicable 41”

EMEHGL-15-311S-LT-LHMR Left Side(Opposite Hand)

NotApplicable

NotApplicable

NotApplicable 41”

Page 3: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 3 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

Option G1: Ground studs at bottom terminal of SwitchOption G2: Ground studs at main contact of SwitchOption K: Key interlock

600 Amp S&C #255243-S1Mini-Rupter® Switch, with front-mounted non-removable handle, padlockable in “Open” or “Close” position. Provisions for key interlock are standard.

Three-Phase – Two Ways per Phase600 Amp S&C Mini-Rupter® Switch8.3/14.4 kV Grounded Wye Max Design95 kV BIL

Section BB

Front ViewDoor & Door Safety Barrier Removed

Section AA

Catalog Number OperatingHandle

FuseMounting

Fuse EndFittings/Holder

FuseUnit/Refill Dim. “A”

EMEHGL-15-311S-LT-MR Front(Shown Above)

NotApplicable

NotApplicable

NotApplicable 41”

Page 4: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 4 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

Three-Phase – Two Ways per Phase600 Amp S&C Mini-Rupter® Switch8.3/14.4 kV Grounded Wye Max Design95 kV BIL

Option G2: Ground studs at main contact of SwitchOption G3: Ground studs at bottom terminal of FusesOption K: Key interlock

600 Amp S&C #255243-S1Mini-Rupter® Switch, with side-mounted non-removable handle, padlockable in “Open” or “Close” position. Provisions for key interlock are standard.

Side View Front ViewDoor & Door Safety Barrier Removed

Section AA

Section BB

Catalog Number OperatingHandle

FuseMounting

Fuse EndFittings/Holder

FuseUnit/Refill Dim. “A”

EMEHGL-15-311S-LT-RHMR-SM20 Right Side(Shown Above)

SM-20 withoutUni-Rupter®

SML-20Catalog #3097

SMU-20200K or 200E Max 22”

EMEHGL-15-311S-LT-LHMR-SM20 Left Side(Opposite Hand)

SM-20 withoutUni-Rupter®

SML-20Catalog #3097

SMU-20200K or 200E Max 22”

EMEHGL-15-311S-LT-RHMR-SMX4 Right Side(Shown Above)

SMX-4 withoutUni-Rupter®

SML-4ZCatalog #92352

SM-4200E Max 22”

EMEHGL-15-311S-LT-LHMR-SMX4 Left Side(Opposite Hand)

SMX-4 withoutUni-Rupter®

SML-4ZCatalog #92352

SM-4200E Max 22”

Page 5: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 5 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

Three-Phase – Two Ways per Phase600 Amp S&C Mini-Rupter® Switch8.3/14.4 kV Grounded Wye Max Design95 kV BIL

Option G2: Ground studs at main contact of SwitchOption G3: Ground studs at bottom terminal of FusesOption K: Key interlock

600 Amp S&C #255243-S1Mini-Rupter® Switch, with front-mounted non-removable handle, padlockable in “Open” or “Close” position. Provisions for key interlock are standard.

Section BB

Front ViewDoor & Door Safety Barrier Removed

Section AA

Catalog Number OperatingHandle

FuseMounting

Fuse EndFittings/Holder

FuseUnit/Refill Dim. “A”

EMEHGL-15-311S-LT-MR-SM20 Front(Shown Above)

SM-20 withoutUni-Rupter®

SML-20Catalog #3097

SMU-20200K or 200E Max 22”

EMEHGL-15-311S-LT-MR-SMX4 Front(Shown Above)

SMX-4 withoutUni-Rupter®

SML-4ZCatalog #92352

SM-4200E Max 22”

Page 6: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 6 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

Three-Phase – Two Ways per Phase600 Amp S&C Mini-Rupter® Switch8.3/14.4 kV Grounded Wye Max Design95 kV BIL

Option G1: Ground studs at bottom terminal of SwitchOption G2: Ground studs at main contact of SwitchOption K: Key interlockOption LBG: Impact-resistant clear polycarbonate Bushing Guard

600 Amp S&C #255243-S1Mini-Rupter® Switch, with side-mounted non-removable handle, padlockable in “Open” or “Close” position. Provisions for key interlock are standard.

Side View Front ViewDoor & Door Safety Barrier Removed

Section AA

Section BB

Catalog Number OperatingHandle

FuseMounting

Fuse EndFittings/Holder

FuseUnit/Refill Dim. “A”

EMEHGL-15-311S-EL6-RHMR Right Side(Shown Above)

NotApplicable

NotApplicable

NotApplicable 41”

EMEHGL-15-311S-EL6-LHMR Left Side(Opposite Hand)

NotApplicable

NotApplicable

NotApplicable 41”

Page 7: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 7 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

Three-Phase – Two Ways per Phase600 Amp S&C Mini-Rupter® Switch8.3/14.4 kV Grounded Wye Max Design95 kV BIL

Option G1: Ground studs at bottom terminal of SwitchOption G2: Ground studs at main contact of SwitchOption K: Key interlockOption LBG: Impact-resistant clear polycarbonate Bushing Guard

600 Amp S&C #255243-S1Mini-Rupter® Switch, with front-mounted non-removable handle, padlockable in “Open” or “Close” position. Provisions for key interlock are standard.

Section BB

Front ViewDoor & Door Safety Barrier Removed

Section AA

Catalog Number OperatingHandle

FuseMounting

Fuse EndFittings/Holder

FuseUnit/Refill Dim. “A”

EMEHGL-15-311S-EL6-MR Front(Shown Above)

NotApplicable

NotApplicable

NotApplicable 41”

Page 8: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 8 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

Three-Phase – Two Ways per Phase600 Amp S&C Mini-Rupter® Switch8.3/14.4 kV Grounded Wye Max Design95 kV BIL

Option G2: Ground studs at main contact of SwitchOption G3: Ground studs at bottom terminal of FusesOption K: Key interlockOption LBG: Impact-resistant clear polycarbonate Bushing Guard

600 Amp S&C #255243-S1Mini-Rupter® Switch, with side-mounted non-removable handle, padlockable in “Open” or “Close” position. Provisions for key interlock are standard.

Side View Front ViewDoor & Door Safety Barrier Removed

Section AA

Section BB

Catalog Number OperatingHandle

FuseMounting

Fuse EndFittings/Holder

FuseUnit/Refill Dim. “A”

EMEHGL-15-311S-EL6-RHMR-SM20 Right Side(Shown Above)

SM-20 withoutUni-Rupter®

SML-20Catalog #3097

SMU-20200K or 200E Max 22”

EMEHGL-15-311S-EL6-LHMR-SM20 Left Side(Opposite Hand)

SM-20 withoutUni-Rupter®

SML-20Catalog #3097

SMU-20200K or 200E Max 22”

EMEHGL-15-311S-EL6-RHMR-SMX4 Right Side(Shown Above)

SMX-4 withoutUni-Rupter®

SML-4ZCatalog #92352

SM-4200E Max 22”

EMEHGL-15-311S-EL6-LHMR-SMX4 Left Side(Opposite Hand)

SMX-4 withoutUni-Rupter®

SML-4ZCatalog #92352

SM-4200E Max 22”

Page 9: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 9 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

Three-Phase – Two Ways per Phase600 Amp S&C Mini-Rupter® Switch8.3/14.4 kV Grounded Wye Max Design95 kV BIL

Option G2: Ground studs at main contact of SwitchOption G3: Ground studs at bottom terminal of FusesOption K: Key interlockOption LBG: Impact-resistant clear polycarbonate Bushing Guard

600 Amp S&C #255243-S1Mini-Rupter® Switch, with front-mounted non-removable handle, padlockable in “Open” or “Close” position. Provisions for key interlock are standard.

Section BB

Front ViewDoor & Door Safety Barrier Removed

Section AA

Catalog Number OperatingHandle

FuseMounting

Fuse EndFittings/Holder

FuseUnit/Refill Dim. “A”

EMEHGL-15-311S-EL6-MR-SM20 Front(Shown Above)

SM-20 withoutUni-Rupter®

SML-20Catalog #3097

SMU-20200K or 200E Max 22”

EMEHGL-15-311S-EL6-MR-SMX4 Front(Shown Above)

SMX-4 withoutUni-Rupter®

SML-4ZCatalog #92352

SM-4200E Max 22”

Page 10: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 10 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

Typical Specification - Page 1 of 2

GeneralThe switchgear shall be 15 kV Class, 95 kV BIL, 600 ampere

continuous current, suitable for use on 8.3/14.4 kV grounded wye max design systems. The switchgear shall be constructed for connection to the utility system with bolt-on cable terminals and stress-relief devices (Elastimold® modular terminators, Joslyn PS terminators or equal to be supplied by the user). The switchgear shall be designed for and contain three-pole, group-operated, load-interrupter switches and/or fuse mountings that accept S&C fuses as described below. A door safety barrier shall be provided inside the door(s) as recommended in IEEE Standard C2 (National Electrical Safety Code) Rule 381G. Tamper resistance shall meet the Enclosure Security requirements of IEEE Standard C57.12.28 (Pad-Mounted Equipment—Enclosure Integrity). Together, the tamper resistance and the door safety barrier(s) shall resist unauthorized entry, protect authorized and unauthorized persons, and provide positive safety features when installed in areas accessible to the general public. The switchgear shall be constructed for outdoor installation in areas subject to heavy precipitation and in areas with windblown contamination. The equipment shall be “air-insulated” and completely assembled prior to shipment.

Enclosure ConstructionThe enclosure shall be tamper-resistant, all-welded

construction utilizing 11-gauge minimum sheet steel. Corner plates and braces shall be used as necessary to assure rigidity. The enclosure top shall be kinked to provide watershed and rigidity. The enclosure shall be open bottom with a 1-inch flange inside, all around. The door(s) shall be furnished with a stainless steel door holder that will latch the door open 100 degrees and 140 degrees and resist accidental closing. Door(s) shall be provided with provisions for padlocking and a recessed penta-head (or hex-head) security bolt to prevent unauthorized entry (coordinated to prevent installation of the padlock until the security bolt is tightened when closing the door(s) and to prevent a wrench from operating the security bolt until the padlock is removed when opening the door(s)). The security bolt shall be made captive with a stainless steel washer compressed to an oval shape to severely discourage removal. Hinges shall be stainless steel (with stainless steel pins not less than 0.3125-inch diameter) and shall be welded to both the enclosure and the door(s) to maintain door alignment for the life of the equipment. The enclosure shall be nonventilated to minimize the entrance of airborne contamination, insects, rodents or reptiles. The protective finish shall include necessary grinding, cleaning and phosphatizing, two-component rust-inhibiting epoxy primer and a Pad-Mount Green two-component polyurethane top coat finish (Munsell color 7GY 3.29/1.5). The primer and top coat shall be electronically monitored during application to insure proper ratio and mixing of each component. Total average thickness of paint (after curing) shall be not less than 5 mils. The protective coating shall meet the Enclosure Coating System requirements of IEEE Standard C57.12.28 (Pad-Mounted Equipment—Enclosure

Integrity). Removable lift provisions, adequate to withstand handling with normal utility equipment, shall be provided on the outside of the enclosure. Threaded openings for lift provision bolts shall be blind holes to prevent the entrance of wire or other foreign objects into the enclosure when lift provisions are removed.

Interrupter SwitchThe three-pole, group-operated interrupter switch shall

be S&C 15 kV class, 95 kV BIL, 600 amp Mini-Rupter® that includes an external nonremovable side-mounted (or front-mounted) operating handle. The interrupter switch shall include a quick-make quick-break mechanism that will quickly and positively open and close the switch blades independent of the switch-operating hub speed. An arc-chute shall be provided for each switched pole and circuit interruption shall take place within the arc-chute. Any exhaust from the arc-chute shall be vented in a controlled manner. The interrupter switch and other electrical components shall be “air-insulated” and positioned to allow visual inspection of the switch position and all internal connections and components without removing the clear-polycarbonate door safety barrier, de-energizing or removing the equipment from service. The operating handle shall be padlockable in the open or the close position. When Option G1 is specified, ground studs shall be provided for each terminal at the hinge end of the interrupter switch. When Option G2 is specified, ground studs shall be provided for each terminal at the main contact end of the interrupter switch. When Option K is specified, key interlocks shall be provided that require operations in a given sequence.

Key InterlockWhen specified, a key-interlock system shall be provided

that will require the operator to lock the interrupter switch open to obtain the key that is required to open the access door to the fuses.

Bushings and TerminalsBushings shall be 600 ampere Elliott #1351-615TB, 15 kV

class (8.3 kV to ground) Air-Insulated Live-Terminal Thru-Bushings, 95 kV BIL, for use with 8.3/14.4 kV systems. The bushings shall be pressure-molded cycloaliphatic epoxy with a 1.25-inch diameter tin-plated aluminum conductor that is drilled and tapped 0.625-inch – 11UNC x 1-inch deep on both ends to provide for connection of the bus and/or live parts. Integral shielding shall be provided to eliminate partial discharge caused by off-center mounting and mounting holes that may have sharp edges or burrs. Bushings shall mount in a 3.125-inch diameter opening and bolt in place to allow field replacement with standard tools. The bushing mounting bolts shall be self-locking stainless steel serrated-flange hex-head bolts that “cut” through the enclosure protective finish to ground the integral shielding of each bushing. To assure adequate strength for apparatus support, the bushing shall withstand a minimum cantilever loading of 500 pounds for five minutes without damage. Each bushing shall be tested in free air, mounted in a grounded steel plate not less than 10 inches

Page 11: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 11 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

Typical Specification - Page 2 of 2x 10 inches and shall meet the requirements for 15 kV devices in accordance with the test values of IEEE Standard 386 (latest revision), including 100 percent production testing.

Bushing GuardWhen Option LBG is specified for switchgear with roof

mounted Elliott #1351-615TB Thru-Bushings, a Bushing Guard will be provided to prevent inadvertent contact with bushing terminals. The Bushing Guard will be constructed with 0.25-inch clear poloycarbonate (Lexan or equal) that extends 18-inches above the top of the enclosure and shall enclose the bushings.

Bus and Fuse MountingsBus shall be copper with all burrs and sharp corners removed

prior to installation. Fuse clips and/or fuse hinges shall be keyed to prevent rotation and to maintain alignment. Positive pressure shall be assured by use of stainless steel fasteners and lock washers or compression washers at all connection points. All connections shall provide direct contact of current-carrying parts and shall not depend on current transfer through fastener thread-to-thread contact. The bus shall be arranged to allow inspection and tightening of all connections (with standard hand tools) without the necessity of removing phase barriers, ground barriers, parts of the switch or fuse mountings. Fuses and their blown-fuse indicators shall be visible (when the fuse compartment door(s) are open) without removal of the clear-polycarbonate door safety barrier to allow easy identification of blown fuses without de-energizing or removing the fuse from service. Electrical components shall be “air-insulated” and positioned to allow visual inspection of all internal connections and components without removing the clear-polycarbonate door safety barrier, de-energizing or removing the equipment from service. When Option G3 is specified, ground studs shall be provided for each terminal at the bottom of the fuse mounting.

Alternate 1: Fuse provisions without S&C Uni-Rupter® shall accommodate S&C Fuse-Unit End Fittings Type SML-20. Fuse-Unit End Fittings, when supplied, shall accept 200 amp (max) Type SMU-20 fuse units.

Alternate 2: Fuse provisions without S&C Uni-Rupter® shall accommodate S&C Fuse Holder Type SML-4Z. Fuse holders, when supplied, shall accept 200 amp (max) Type SM-4 fuse refills.

InsulatorsThe switch and bus insulators shall be nontracking, self-

scouring, nonweathering pressure-molded cycloaliphatic epoxy with cast-in-place inserts. Surface damage to insulators shall expose material of the same composition and characteristics so insulators with minor surface damage will not require replacement. The insulators shall provide adequate thermal cycle withstand to assure trouble-free field service in the most severe climatic conditions established by in-house testing and field-operating experience. The insulators shall be 15 kV class, 95 kV BIL and

produced by a manufacturer with ten or more years experience with cycloaliphatic epoxy.

BarriersPhase and ground barriers shall be provided to assure

correct phase-to-phase and phase-to-ground clearances for proper operation at rated voltage. These barriers shall be glass-reinforced polyester (NEMA GPO-3 class material) not less than 0.1875-inch thick.

A removable insulating barrier with a “DANGER – Keep Out! – Hazardous voltage” sign, Elliott #7203-D2003-309, shall be located inside the door(s) as recommended in Rule 381G of IEEE Standard C2 (National Electrical Safety Code). The door safety barriers shall be constructed of 0.25-inch clear-polycarbonate (Lexan or equal) and shall completely close the door opening and be provided with a non-conductive safety latch requiring a positive action to remove the barrier. Handles and other hardware extending through this door safety barrier shall be nonconductive material. Handles shall be keyed to prevent rotation for secure handling. Complete visual inspection of the internal components shall be possible without removing the door safety barrier.

Grounding ProvisionsHigh-conductivity bronze eyebolt-type ground lugs, which

accept #6 through #2/0 stranded copper conductor, shall be provided in each compartment (located on each side of the door opening in an accessible position).

Accessory EquipmentA corrosion proof nameplate with permanent thermal transfer

printing shall be installed inside the compartment door. It shall be located at the top corner farthest from the enclosure when the door is open. The nameplate will provide Type of Equipment, Model Number, Amps Continuous, kV Maximum, BIL, Serial Number, Job Number, Date Manufactured and Weight of Equipment.

When specified, four anchor-bolt brackets, Elliott #6102-A81-7 or approved equal, shall be supplied with each switchgear to provide a means of clamping the equipment to the concrete pad.

PackagingEach switchgear shall be bolted to a solid-top wood pallet (to

prevent the forks of a forklift truck from entering the open bottom of the equipment) to prevent hidden damage. The equipment shall be wrapped with 0.125-inch thick polyethylene foam or other suitable material to minimize damage to the finish during shipment.

DrawingsWhen specified, drawings shall be furnished for each

switchgear that include:1) enclosure dimensions and location of components.2) proposed pad dimensions and location of anchor bolts.

Page 12: 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed ... · 15-kV Live Terminal 600 Amp Group Operated Metal-Enclosed Indoor/Outdoor Switchgear 200 Amp (Max) S&C SMU-20 and SM-4

15-kV Live Terminal 600 Amp Group OperatedMetal-Enclosed Indoor/Outdoor Switchgear

200 Amp (Max) S&C SMU-20 and SM-4 Fuses

Bulletin

745-114Page 12 2015

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2015 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Mini-Rupter® and Uni-Rupter® are registered trademarks of S&C Electric Company. Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.

SM-20 Power Fuse Mounting45° Opening

SMX-4 Power Fuse Mounting45° Opening

Complete mounting shown - live parts may be utilized separately.

StyleFuse

MountingType

Ratings

kV Amperes, Rms

Nominal Max Design BIL Max Interrupting 1 (Sym.)

Disconnect45° Opening

SilencerVertical

SM-20 13.8 17.0 95 200K or 200E 14,000

Disconnect45° Opening

SilencerVertical

SMX-4 13.8 17.0 95 200E Max 12,500

1 Refer to S&C catalog for additional, detailed information on interrupting ratings.