    2014 NatioNal ElEctrical codE

    Changes in Overcurrent and Surge Protection

  • 2 Mersen NEC Code 2014

    Selected 2014 NEC Code Changes in Overcurrent and Surge ProtectionContents

    1. New Circuit Breaker Requirements for 1200A Plus Circuits . . . . . . . . . . . . . 3 240.87Arcflashenergyreductionmandated

    2. Surge Protective Device Type 4 and New Requirement . . . . . . . . . . . . . . . . . 4 285.13Type4ComponentSPDs 700.8

    3. Surge Protection Without Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . 6 240.21(C)(2)1bexception

    4. Short-Circuit Current Rating (SCCR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 409.1Panelsnowincludeupto1000volts

    5. Solid State Motor Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 430.52C(5) 430.130 430.131

    6. Ground Fault Protection (GFP) for 1000A Plus Circuits. . . . . . . . . . . . . . . . 12 210.13Newrequirementsandexceptions

    7. Sizing Transformer Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Table450.3(A) Table450.3(B)

    8. PV Shut-off for First Responders. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 690.12

    9. Selective Coordination Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 620.62 700.28EmergencySystems 701.27LegallyrequiredStandbySystems 708.54

    10. Selective Coordination Not Required in Hospitals . . . . . . . . . . . . . . . . . . . . 18 517.2CriticalbranchDefinition 517.30(G)Coordination

    NationalElectricalCodeandN.E.C.areregisteredtrademarksoftheNationalFireProtectionAssociation(NFPA),Quincy,MA02269.ThispublicationdoesnotreflecttheofficialpositionoftheNFPA.

    TherecommendationsbyMerseninthispublicationareintendedtobeincompliancewiththe2014NEC,howeverjurisdictionsthatadoptthecodearesolelyresponsibleforanymodificationsandinterpretationstobeenforcedbytheirjurisdictions.

    TheuserofthecodeshouldidentifywhatregulatoryauthorityhasresponsibilityfortheinstallationapprovalandalwayscomplywithanyregulatoryauthoritymodificationstotheN.E.C.Mersencannotberesponsibleforerrorsandomissions.

  • Mersen NEC Code 2014 3

    1. New Arc Flash Circuit Breaker Requirements for 1200A or morePrevious Code requirements

    Forthefirsttimeinthe2011code,arcflashdangerfromcircuitssuppliedbycertaintypesofcircuitbreakerswasrecognized.Circuitbreakerswithoutaninstantaneoustripwererequiredtouseanadditionalmethodforreducinganarcflashdanger.

    TheSection240.87Non-instantaneousTripinthe2011codesaid,Whereacircuitbreakerisutilizedwithoutaninstantaneoustrip,oneofthefollowingorapprovedequivalentmeansshallbeprovided:

    1. Zone-selectiveinterlocking2. Differentialrelaying3. Energy-reducingmaintenanceswitchingwithlocalstatusindicator.

    Thesealternativesareeffective,butcostly.

    new Code

    240.87 Arc Energy Reduction. Wherethehighestcontinuouscurrenttripsettingforwhichtheactualovercurrentdeviceinstalledinacircuitbreakerisratedorcanbeadjustedis1200Aorhigher,240.87(A)and(B)shallapply.

    (A) Documentation. Documentationshallbeavailabletothoseauthorizedtodesign,install,operate,orinspecttheinstallationastothelocationofthecircuitbreaker(s).

    (B) Method to Reduce Clearing Time. Oneofthefollowingorapprovedequivalentmeansshallbeprovided: (1)Zone-selectiveinterlocking

    (2)Differentialrelaying

    (3)Energy-reducingmaintenanceswitchingwithlocalstatusindicator

    (4)Energy-reducingactivearcflashmitigationsystem

    (5)Anapprovedequivalentmeans

    Informational Note No. 1: Anenergy-reducingmaintenanceswitchallowsaworkertosetacircuitbreakertripunittonointentionaldelaytoreducetheclearingtimewhiletheworkerisworkingwithinanarc-flashboundaryasdefinedinNFPA 70E-2012, Standard for Electrical Safety in the Workplace,andthentosetthetripunitbacktoanormalsettingafterthepotentiallyhazardousworkiscomplete.

    Informational Note No. 2: Anenergy-reducingactivearcflashmitigationsystemhelpsinreducingarcingdurationintheelectricaldistributionsystem.NochangeinthecircuitbreakerorthesettingsofotherdevicesisrequiredduringmaintenancewhenaworkerisworkingwithinanarcflashboundaryasdefinedinNFPA 70E-2012, Standard for Electrical Safety in the Workplace.

  • 4 Mersen NEC Code 2014

    1. New Arc Flash Circuit Breaker Requirements for 1200A or more, Continuedreasons for Changes

    Manysystemswerecompletelydesignedusingonlyinstantaneoustripcircuitbreakers.Thatcompliedwiththecode,butwasnotmakinguseofavailablesafertechnology.

    Thenewcoderequiressafertechnologytobeusedforanycircuitusingacircuitbreakerthatcanbesetat1200ampsormore.Thisdoesnotapplytocircuitswithfuses1200ampsorlarger.

    how to ComPly

    Everylargecircuitismorelikelytohavehigher,morehazardouslevelsofarcflashdanger.Selectaneffectivedesignoptionthatisthemostcost-effectiveforthelargecircuits.Zone-selectiveinterlockingrequiresupstreamcircuitbreakerstohaveacommunicationschanneltothedownstreamunit.Differentialrelayingcanbecomplexforcommissioninganduse.Energyreducingmaintenanceswitchesandactivearcflashcontroloftenrequireexpensivesolid-statetripcircuitbreakers.Electricalinspectorsseldomapproveothermethodsbecauseoftheirpotentialliability.Apossiblecost-effectivesolutionistodesigninfusibleprotectioninsteadofcircuitbreakers.

    helPful ProduCts

    TheAmp-Trap2000familydeliverscurrentlimitingfusesthatcanreducecostsandreducearcflashdangertoaminimumwhentheavailablefaultcurrentisadequate.Thisisfrequentlymoreeconomicalthatothersolutions.

    TheAmp-Trap2000ClassL1200ampfusecanlimitthearcflashdanger.Forexample,theMersenA4BQ1200fusewithavailableboltedfaultcurrentat24,000ampsat600volts,willlimitthearcflashincidentenergyto3.8cal/cm2ata24inchworkingdistance.InthisexamplethefusereducesthePPErequireddowntoHazardRiskCategory1.Inhigheravailablefaultcurrentapplications,itcanreducethehazarddowntoHRC0.

    2. Surge Protective Device (SPD) Type 4Previous Code requirements

    Article285hadthetransitionalphrasingfrom2005tointroducethenewtermSPDandstillusetheoldtermTVSS.ULStandard1449Revision3wassubstantiallyrevisedsothatthenamewaschangedtoemphasizethemajordifferencebetweenthesafetyofaTVSSandanSPD.

    TherequirementsforapplyingSPDTypes1,2,and3weredocumented.SPDType1canbeusedanywhereinthecircuitbecauseitisself-protectingwithinitsrating.Type2unitsneedupstreamprotectionsuchastheserviceentrance.TheType3unitsaretobeusedmorethan30feetawayfromtheserviceentrance.ThecodeexplainedtheapplicationforTypes1,2and3SPDs,butwassilentonType4.

    ThepriorcodedidnotrequireSPDs,butthroughtheyearstheelectricalindustrydeterminedthattheywereeffectiveinpreventingdamagetoelectroniccircuitsfromvoltagespikesandsurges.ManySPDshavebeenvoluntarilyappliedwithoutanycoderequirements.Aselectronicequipmentbecomesmorecommononallcircuits,thepotentialdamageanddowntimeofcriticalcircuitswasbecomingapparent.

  • Mersen NEC Code 2014 5

    2. Surge Protective Device (SPD) Type 4, Continued

    new Code

    285.13 Type 4 and Other Component Type SPDs. Type4componentassembliesandothercomponenttypeSPDsshallonlybeinstalledbytheequipmentmanufacturer.

    700.8 Surge Protection. AlistedSPDshallbeinstalledinoronallemergencysystemsswitchboardsandpanelboards.

    reasons for Changes

    ThetermTVSSwaseditedoutofArticle285.ThecommitteedecidedthattherehadbeensufficienttimefortheindustrytoadjusttotheSPDterm.

    SomepeopleweremisapplyingType4SPDs.Paragraph285.13wasaddedtopreventpeoplefromapplyingType4SPDsinthefield.

    Type4SPDsdonothavecompliancewithsomeofthesafetyfeaturesmandatedbyType1,2,or3SPDs.Theyareintendedtobeselectedbyapanelshopthathasthecapabilityofchoosingtheappropriatecharacteristics.Type4unitsareoftenDIN-railmountandhaveexposedliveterminals.Thesearesuitableformountingintoanenclosure,butnotintheopen.

    Newparagraph700.8requiressurgeprotection.Article700pertainstoemergencysystems,whicharesystemslegallyrequiredtoautomaticallysupplypowertodesignatedloadsuponlossofnormalpower.Thiscanpreventdamageofemergencypowercontrolsanddamagetocriticalelectronicloads.

    how to ComPly

    UseonlyType1,2,and3SPDsforgeneralfieldaddition.Theyaredesignedtosafelymitigateharmfulsurgesandvoltagespikes.TheType4unitsshouldbecarefullychosenfortheapplication.Sometimesapplyingthemintoanenclosureisadequate.Sometimestheyhavespecificupstreamprotectionneeds.AqualifiedpersonhastoanalyzetheSPDlimitationsinordertoproperlyapplyType4units.

    NewormodifiedemergencysystemsshouldhaveSPDsintheirswitchboardsandpanelboards.ThisisthefirstcoderequirementformandatoryuseofSPDs.

    helPful ProduCts

    MersenhasalargearrayofSurgeProtectiveDevices.InadditiontotheType1and2generalapplicationproducts,MersenhasalargevarietyofType4units.

    MersenType4unitsareappliedtogeneralcontrolpanels,PVsystems,windturbines,andpowerelectronics.Type4unitscanbemodularorpluggable,ACorDC,andULorIECrated.

  • 6 Mersen NEC Code 2014

    3. Surge Protection Without Overcurrent ProtectionPrevious Code requirements

    Section240.1requiredovercurrentprotectiontobelocatedatthepointwheretheconductorsreceivetheirsupplywitheightexceptions.ThissectioniscommonlycalledtheTapRules.ThepriorcodedidnotreferenceanyexceptionsforinstallingType1SPDsthatareselfprotected.

    Paragraph285.23(A)(1)gavepermissiontowireType1SPDsbeforeoraftertheserviceentrance.Thisparagraphreferredto230.82(4)asgivingpermissiontoinstalltheseunitsonthesupplysideoftheservicedisconnectingmeans.

    new Code

    240.21(B) Feeder Taps. Conductorsshallbepermittedtobetapped,withoutovercurrentprotectionatthetap,toafeederasspecifiedin240.21(B)(1)through(B)(5).Theprovisionsof240.4(B)shallnotbepermittedfortapconductors.

    1. Taps Not over 3m (10 ft) Long. Ifthelengthofthetapconductorsdoesnotexceed3m(10ft)andthetapconductorscomplywithallofthefollowing:

    (1)Theampacityofthetapconductorsis

    a.Notlessthanthecombinedcalculatedloadsonthecircuitssuppliedbythetapconductors,and

    b.Notlessthantheratingoftheequipmentcontaininganovercurrentdevice(s)suppliedbythetapconductorsornotlessthantheratingoftheovercurrentprotectivedeviceattheterminationofthetapconductors.

    Exception to b: Where listed equipment, such as a surge protective device(s) [SPD(s)], is provided with specific instructions on minimum conductor sizing, the ampacity of the tap conductors supplying that equipment shall be permitted to be determined based on the manufacturers instructions.

    240.21(C) Transformer Secondary Conductors. Asetofconductorsfeedingasingleload,oreachsetofconductorsfeedingseparateloads,shallbepermittedtobeconnectedtoatransformersecondary,withoutovercurrentprotectionatthesecondary,asspecifiedin240.21(C)(1)through(C)(6).

    Exception to (C)(2)(1)b: Where listed equipment, such as a surge protective device(s) [SPD(s)], is provided with specific instructions on minimum conductor sizing, the ampacity of the tap conductors supplying that equipment shall be permitted to be determined based on the manufacturers instructions.

  • Mersen NEC Code 2014 7

    3. Surge Protection Without Overcurrent Protection, Continuedreasons for Changes

    ItwasunclearifType1SPDsshouldhaveovercurrentprotectionintheirsupplysidecircuitornot.TheoldcodeconsideredtheType1unitstobeself-protected,butwasthewiretobeconsideredasprotected?Ifwirewasconsideredprotected,howsmallcoulditbe?

    ManySPDmanufacturersmanagedthisbyrecommendingadditionalovercurrentprotectionsizedforthewiresupplyingtheSPD.Butiftheovercurrentprotectionwasnotused,manyelectricalinspectorswouldnotapprovetheinstallation.

    how to ComPly

    ThenewcodehasexceptionsallowingSPDsandotherlistedequipmenttobeinstalledwithoutadditionalovercurrentprotection.Thisnewexceptionpertainstofeedertapsandtransformersecondarytapswithdistancesnotexceeding10feet.

    SelectlistedSPDswithmanufacturerinstructionsthatincludeminimumwiresizing.Thiswiresizingandinstallationhavetocomplywiththeotherpreviousrequirementsforthe10footTapRule.

    helPful ProduCts

    MersenhaslistedSPDsformostapplications.TheMersenmodelsaredesignedtoprotectserviceentrances,panels,andend-useequipment.

  • 8 Mersen NEC Code 2014

    Previous Code requirements

    Forthefirsttimeinthe2005code,industrialcontrolmachineryandpanels,airconditioningequipment,refrigerationequipment,meterdisconnectswitches,andmotorcontrollershadtobemarkedwiththeirSCCR(Short-CircuitCurrentRating).

    The2008codedefinedSCCRas,Theprospectivesymmetricalfaultcurrentatanominalvoltagetowhichanapparatusorsystemisabletobeconnectedwithoutsustainingdamageexceedingdefinedacceptancecriteria.SeveralcodesectionshavespecificlabelingrequirementssuchasinSection409forIndustrialControlPanelsandSection670forIndustrialMachinery.

    The2011coderequiredin409.22andalsoin670.5-Anindustrialpanelshallnotbeinstalledwheretheavailablefaultcurrentexceedsitsmarkedshort-circuitcurrentrating.Thismadeitaclearcodeviolationtoinstallanindustrialcontrolpanelrated600voltsorlesswithalowerSCCRratingthantheavailableshortcircuitcurrent.

    Alsothe2011codecontainedaprovisionin110.24requiringfieldmarkingofnewserviceentranceequipmentwiththeavailableshortcircuitcurrent.ThatmadeiteasierforelectricalinspectorstocompareandquestiontheSCCRratings.

    new Code

    ARTICLE 409: Industrial Control Panels

    I.General

    409.1Scope.Thisarticlecoversindustrialcontrolpanelsintendedforgeneraluseandoperatingat1000voltsorless.

    reasons for Changes

    TheNationalElectricalCodewasoriginallyfocusedon600voltequipment.The2014codechangedthefocustoequipmentupto1000voltequipment.ThisincreasesthenumberofpanelsrequiredtohaveSCCRratingsandcompliance.Forexample,a750voltsolarinverterpanelnowhastocomply.

    ThecodeagainisemphasizingSCCRlabelingandinstallationrequirements.HistoricallymanufacturersbeganlabelingelectricalequipmentwiththeSCCR,butmanypeoplefailedtorealizeitssignificance.Somepeoplejustassumeditwasunimportantlabeling.Thecodemandatedthelabeling,butthepriorcodeswereunclearhowtousethisinformationuntil2011.

    Somepanelbuyersonlycheckedforthelabel,andthatthemanufacturersprovidedit.ButtheequipmentcouldbeatdangerouslylowSCCRlevelsfortheapplication.ThepanelusersneededmoredescriptiononhowtousetheSCCRlabelinformation,whichwasonlygivenin2011.

    4. Short Circuit Current Ratings for 1000V

  • Mersen NEC Code 2014 9

    4. Short Circuit Current Ratings for 1000V, Continuedhow to ComPly

    Thenewrequirementexpandsthecontrolpanelscoveredbythisrequirementfrom600voltsupto1000volts.

    IndustrialcontrolandmachinepanelshavetobemarkedwiththeirSCCR.ThemanufacturersordesignersofthepanelmustdoananalysisasdescribedinUL508A,evenifthepanelisnotbuilttotheUL508AStandardspecifications.

    ThentheinstallermustinsurethatthepanelsSCCRisnotlessthantheavailablefaultatthesupplyterminalsofthepanel.FinallytheelectricalinspectorhastoverifythattheSCCRisonthenameplateandhavesomeevidencethattheSCCRisnotexceeded.

    Compliancecanbecostlyifthepersonwhoisresponsibleforcodecomplianceignoresthiscodeissueuntiltheequipmentisinstalled.Extensivetimecanbeconsumedinnegotiatingwhoshouldpayfortheproblemresolution.Theinstallationfixoftenrequiresreturnofthepaneltothemanufacturerforupgrading.

    helPful ProduCts

    TheAmp-Trap2000familydeliverscurrent-limitingfusesthatcanincreasetheSCCRofindustrialcontrolpanels.ProductssuchastheUltraSafeTMUSFMfuseholderdirectlyreplacecircuitbreakershavingthesamewidthastypeIECstarters.TheSurge-Trapproductsprotectagainstvoltagespikesandhaveabuilt-inratingofupto200kASCCR.Thefinger-safepowerdistributionblockscanalsohavea100kAratingwithfuses.

  • 10 Mersen NEC Code 2014

    5. Solid-State Motor Protection with FusesPrevious Code requirements

    Theformer430.52textusedthephrasingSuitablefuses,insteadofsemiconductorfuses.ItgavepermissiontosubstitutesuitablefusesfortherequirementsofTable430.52aslongastheequipmentwasmarkedtoidentifysuitablereplacementfuses.

    SectionXAdjustable-Speed Drive SystemsofArticle430Motors,Motor Circuits and Controllershadnoinformationonshortcircuitandgroundfaultprotectiverequirements.Thatmeantthenon-adjustablespeeddrivecodesectionsprobablyapplied.

    new Code430.52 Rating or Setting for Individual Motor Circuit.

    (C) (5) Power Electronic Devices. SemiconductorfusesintendedfortheprotectionofelectronicdevicesshallbepermittedinlieuofdeviceslistedinTable430.52forpowerelectronicdevices,associatedelectromechanicaldevices(suchasbypasscontactorsandisolationcontactors),andconductorsinasolid-statemotorcontrollersystem,providedthatthemarkingforreplacementfusesisprovidedadjacenttothefuses.

    430.130 Branch-Circuit Short-Circuit and Ground-Fault Protection for Single Motor Circuits Containing Power Conversion Equipment.

    (A) Circuits Containing Power Conversion Equipment. Circuitscontainingpowerconversionequipmentshallbeprotectedbyabranch-circuitshort-circuitandground-faultprotectivedeviceinaccordancewiththefollowing:

    (1)Theratingandtypeofprotectionshallbedeterminedby430.52(C)(1),(C)(3),(C)(5),or(C)(6),usingthefull-loadcurrentratingofthemotorloadasdeterminedby430.6.

    (2)Wheremaximumbranch-circuitshort-circuitandground-faultprotectiveratingsarestipulatedforspecificdevicetypesinthemanufacturersinstructionsforthepowerconversionequipmentorareotherwisemarkedontheequipment,theyshallnotbeexceededevenifhighervaluesarepermittedby430.130(A)(1).

    (3)Aself-protectedcombinationcontrollershallonlybepermittedwherespecificallyidentifiedinthemanufacturersinstructionsforthepowerconversionequipmentorifotherwisemarkedontheequipment.

    InformationalNote:Thetypeofprotectivedevice,itsrating,anditssettingareoftenmarkedonorprovidedwiththepowerconversionequipment.

    (B) Bypass Circuit/Device. Branch-circuitshort-circuitandground-faultprotectionshallalsobeprovidedforabypasscircuit/device(s).Whereasinglebranch-circuitshort-circuitandground-faultprotectivedeviceisprovidedforcircuitscontainingbothpowerconversionequipmentandabypasscircuit,thebranch-circuitprotectivedevicetypeanditsratingorsettingshallbeinaccordancewiththosedeterminedforthepowerconversionequipmentandforthebypasscircuit/device(s)equipment.

    430.131 Several Motors or Loads on One Branch Circuit Including Power Conversion Equipment. Forinstallationsmeetingalltherequirementsof430.53thatincludeoneormorepowerconverters,thebranch-circuitshort-circuitandground-faultprotectivefusesorinversetimecircuitbreakersshallbeofatypeandratingorsettingpermittedforusewiththepowerconversionequipmentusingthefull-loadcurrentratingoftheconnectedmotorloadinaccordancewith430.53.Forthepurposesof430.53and430.131,powerconversionequipmentshallbeconsideredtobeamotorcontroller.

  • Mersen NEC Code 2014 11

    reasons for Changes

    Theprior430.52textdidnotexplainwhatwasasuitablefuse.Thatmadetherequirementdifficulttomeetorenforce.Semiconductorfusesareveryfastactingcurrent-limitingfuses.TheULStandard248-13doesnotrequireoverloadprotectioninthesefuses.Typicalbranch-circuitratedfusesdocontainoverloadprotection.Somefusesaremorecurrent-limitingandgivebettershort-circuitandground-faultprotection.

    Thesameselectionconcernsarepresentforbothpowerelectronicdevicesandpowerconversionequipment.Nowclearlysemiconductorfusescanbeusedforprotection.Iftheyareused,thefuseholderareamustbeclearlymarkedwhichfuseshouldbeusedforprotectingpowerconversionequipment.

    how to ComPly

    Powerconversionequipmentshouldbecoordinatedwiththemanufacturersinstructions.Ifthemanufacturersaysfuses,itcannotbeprotectedbycircuitbreakers.Forexample,ifthepowerconversionequipmentmanufacturerstatesamaximumampereofaULClassJfuse,thatbecomesacoderequirement.

    helPful ProduCts

    Mersenisthelargestsupplierofsemiconductorfusesintheworld.Semiconductorfusesareproducedinawidevarietyofshapes,sizesandratings.

    5. Solid-State Motor Protection with Fuses, Continued

  • 12 Mersen NEC Code 2014

    6. Ground Fault Protection (GFP) for 1000A BranchesPrevious Code requirements

    GFPisfortheprotectionofequipment.SometimesthisrequirementisconfusedwithGFCI,whichistoprotectpeoplefromshock.GFCIsarelookingformilliampsofcurrent.TheGFPcanbesettoignoregroundfaultsbelow1200ampsandcanhavetime-delayofonesecondforcurrentsof3,000ampsorabove.Thedetailsareinsection230.95.

    PriorcodemandatedGFPforsomeservicesandfeeders.Howeverifalargebranchcircuitfitthesamedescription,itwasnotrequiredtohaveaGFP.

    new Code

    210.13 Ground-Fault Protection of Equipment. Eachbranch-circuitdisconnectrated1000Aormoreandinstalledonsolidlygroundedwyeelectricalsystemsofmorethan150voltstoground,butnotexceeding600voltsphase-to-phase,shallbeprovidedwithground-faultprotectionofequipmentinaccordancewiththeprovisionsof230.95.

    InformationalNote:Forbuildingsthatcontainhealthcareoccupancies,seetherequirementsof517.17.

    Exception No. 1: The provisions of this section shall not apply to a disconnecting means for a continuous industrial process where a non-orderly shutdown will introduce additional or increased hazards.

    Exception No. 2: The provisions of this section shall not apply if ground-fault protection of equipment is provided on the supply side of the branch circuit and on the load side of any transformer supplying the branch circuit.

    reasons for Changes

    TheoriginalrequirementsforGFPinservicesandfeedersweretheresultofequipmentburn-downs.Althoughbranchcircuitsthislargeareuncommon,theyexistandsomeburn-downshaveoccurred.Thenewrequirementisintendedtopreventfutureburn-downsinlargebranchcircuitsofgrounded480voltsystems.

    how to ComPly

    ApplyGFPtobranchcircuitsof480groundedsystemswhentheovercurrentprotectionis1000ampsormore.

    helPful ProduCts

    MersenA4BQAmp-Trap2000fusesarefasteractingthanregularClassLfuses.Theycangivebetterprotectionevenifaburn-downstarts.

  • Mersen NEC Code 2014 13

    7. Sizing Transformer ProtectionPrevious Code requirements

    Transformerprotectionrequirementsaredividedintotwotables,oneforlowervoltagesandtheotheroneforhighervoltages.Thepriorcodeused600voltsasthethresholdbetweenthetwotables,450.3(A)and(B).

    Thesetablesusedifferentcriteriaformaximumovercurrentprotection.Table450.3(A)considerstheimpedanceofthetransformer,and450.3(B)considersfullloadcurrents.Thereweredifferentrulesdependinguponwhetherthevoltagewasover600voltsornot.

    new Code

    Table 450.3(A) MaximumRatingorSettingofOvercurrentProtectionforTransformersOver1000Volts(asaPercentageofTransformer-RatedCurrent)

    Table 450.3(B) MaximumRatingorSettingofOvercurrentProtectionforTransformers1000VoltsandLess(asaPercentageofTransformer-RatedCurrent)

    reasons for Changes

    TheNationalElectricalCodewaschangedinitsentiretytomoregenerallyapplytocircuitsupto1,000voltsinsteadof600volts.Manyrevisions,mostlyeditorial,weremadetothe2014code.Whensomanyrevisionsaremadeatonetime,sometimesunintendedconsequencesresult.

    how to ComPly

    Usethetablestoselectthemaximumovercurrentprotectionallowed.Mosttransformerapplicationswillnotchange.Anytransformerapplicationsover600voltsbutnotover1,000voltscouldhavedifferentrequirements.

    Manyhigherratedvoltagetransformerfuseselectionscouldbeimproved.Historicallyengineerssizedtheprimaryfusestothemaximumallowedbycodetoavoidnuisanceopenings.Inrecentyearspeoplebecamemoreknowledgeableaboutthedangersofarcflashandtheeffectsofsizingovercurrentprotection.

    Transformerfuseapplicationlessthanthemaximumsize,butstilllargeenoughtopreventnuisanceopening,canreducearcflashhazards.Arcflashincidentenergyisproportionaltothedurationofthearcflash.Asmallerampereratedfusewilloperatefasterwiththesameamountofarcfaultcurrent.Evenselectingamoreinverse,lesstime-delayfuse,canreducearcflashenergyusingthesameampererating.

    helPful ProduCts

    Mersenhasthewidestrangeofcurrent-limitingmediumvoltagefusesfortransformersthatmeettheNorthAmericanANSI/IEEEstandards.TheHMHmodelofmediumvoltagefusescanreduceincidentenergyonthesecondarysideofthetransformerbybeinginstalledintheprimary.Somemediumvoltagefusescanreducearcflashincidentenergytotolerablelevelsusingexistingfusiblegear.

  • 14 Mersen NEC Code 2014

    8. Solar System Shut-Down for First RespondersPrevious Code requirements

    TherewerenopreviousrequirementsforrapidpowershutdownonrooftopPVsystems.Thereonlywerenormalshutdownsystemsincorporatingdisconnects,inverters,andelectronicallycontrolledequipment.

    new Code

    690.12 Rapid Shutdown of PV Systems on Buildings. PVsystemcircuitsinstalledonorinbuildingsshallincludearapidshutdownfunctionthatcontrolsspecificconductorsinaccordancewith690.12(1)through(5)asfollows.

    (1)RequirementsforcontrolledconductorsshallapplyonlytoPVsystemconductorsofmorethan1.5m(5ft)inlengthinsideabuilding,ormorethan3m(10ft)fromaPVarray.

    (2)Controlledconductorsshallbelimitedtonotmorethan30voltsand240volt-ampereswithin10secondsofrapidshutdowninitiation.

    (3)Voltageandpowershallbemeasuredbetweenanytwoconductorsandbetweenanyconductorandground.

    (4)Therapidshutdowninitiationmethodsshallbelabeledinaccordancewith690.56(B).

    (5)Equipmentthatperformstherapidshutdownshallbelistedandidentified.

  • Mersen NEC Code 2014 15

    8. Solar System Shut-Down for First Responders, Continuedreasons for Changes

    Emergencyresponders,suchasfirefighters,areexposedtodangerousvoltagesfromPVsystemsiftheyareworkingonaroofwithsmokeobstructedview.Thenormalfirefighterproceduresofsuppression,ventilation,andoverhaulentailworkingontheroof.IftheroofhasPVsystemspresent,itcomplicatesaccessandpresentsdangerousshockhazards.

    EuropehasextensiveexperiencewiththeirPVsystemsandhasdevelopedsomerapidshutdownsystems.ThenewcodesectionwasdevelopedafterreviewingtherelatedportionofIEC61730,PVModuleSafetyQualification.

    how to ComPly

    Installarapidshutdownsystemthatwillbringthesystemdownto30voltsorlesswithin10secondsofinitiation.Thecoderequiresthattherapidshutdownsystembealistedproduct.Alistedunitmeetsthekeycriteriaandisalreadyevaluatedforeasycompliance.

    helPful ProduCts

    MersensPVSafetySystemhasbeenprovidinganIECrapidPVshutdowncapabilityinEuropeforsometime.ShortlythatunitwillbemodifiedandULlistedfortheAmericas.

    MersenhasawiderangeofotherPVproducts.Thetraditionalproductsincludefuses,fuseblocks,powerdistributionblocks,disconnectswitches,surgeprotectivedevices,coolingproducts,andlaminatedbusbarsolutions.

    RecentlyMersenintroducedamodularPVdatacollectionsystem.ThissystemcollectsimportantdatafromPVstrings,combinerboxes,andotherfieldinstruments,andthensendsthisdataoveraRS485communicationslink.

  • 16 Mersen NEC Code 2014

    9. Selective Coordination RequirementsPrevious Code requirements

    Thepreviouscodedefinedselectivecoordinationas,Localizationofanovercurrentconditiontorestrictoutagestothecircuitorequipmentaffected,accomplishedbythechoiceofovercurrentprotectivedevicesandtheirratingsorsettings.

    new Code

    Article 100 Definitions. Coordination (Selective). Localizationofanovercurrentconditiontorestrictoutagestothecircuitorequipmentaffected,accomplishedbytheselectionandinstallationofovercurrentprotectivedevicesandtheirratingsorsettingsforthefullrangeofavailableovercurrents,fromoverloadtothemaximumavailablefaultcurrent,andforthefullrangeofovercurrentprotectivedeviceopeningtimesassociatedwiththoseovercurrents.

    Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts 620.62 Selective Coordination. Wheremorethanonedrivingmachinedisconnectingmeansissuppliedbyasinglefeeder,theovercurrentprotectivedevicesineachdisconnectingmeansshallbeselectivelycoordinatedwithanyothersupplysideovercurrentprotectivedevices.

    Selectivecoordinationshallbeselectedbyalicensedprofessionalengineerorotherqualifiedpersonengagedprimarilyinthedesign,installation,ormaintenanceofelectricalsystems.Theselectionshallbedocumentedandmadeavailabletothoseauthorizedtodesign,install,inspect,maintain,andoperatethesystem.

    Emergency Systems 700.28 Selective Coordination. Emergencysystem(s)overcurrentdevicesshallbeselectivelycoordinatedwithallsupply-sideovercurrentprotectivedevices.

    Selectivecoordinationshallbeselectedbyalicensedprofessionalengineerorotherqualifiedpersonsengagedprimarilyinthedesign,installation,ormaintenanceofelectricalsystems.Theselectionshallbedocumentedandmadeavailabletothoseauthorizedtodesign,install,inspect,maintain,andoperatethesystem.

    Legally Required Standby Systems 701.27 SelectiveCoordination.Legallyrequiredstandbysystem(s)overcurrentdevicesshallbeselectivelycoordinatedwithallsupply-sideovercurrentprotectivedevices.

    Selectivecoordinationshallbeselectedbyalicensedprofessionalengineerorotherqualifiedpersonsengagedprimarilyinthedesign,installation,ormaintenanceofelectricalsystems.Theselectionshallbedocumentedandmadeavailabletothoseauthorizedtodesign,install,inspect,maintain,andoperatethesystem.

    708.54 Selective Coordination. Critical operations power system(s) overcurrent devices shall be selectively coordinated with allsupply-sideovercurrentprotectivedevices.

    Selectivecoordinationshallbeselectedbyalicensedprofessionalengineerorotherqualifiedpersonsengagedprimarilyinthedesign,installation,ormaintenanceofelectricalsystems.Theselectionshallbedocumentedandmadeavailabletothoseauthorizedtodesign,install,inspect,maintain,andoperatethesystem.Exception: Selective coordination shall not be required between two overcurrent devices located in series if no loads are connected in parallel with the downstream device.

  • Mersen NEC Code 2014 17

    9. Selective Coordination Requirements, Continuedreasons for Changes

    Thecodewasbeinginterpretedasallowinginstallationstohavelimitedcoordination,insteadoffullyselectivecoordination.Manypeoplewereunsureiftheyhadselectivecoordinationornot.Evensomeengineersdisagreedwhatthecoderequirementswereforcoordination.Someengineersreasonedthatifthesystemwascoordinatedonoverloads,itwasgoodenough.IEEEStandardshavedefinedselectivecoordinationformanyyearsandthemoreliberalinterpretationofselectivecoordinationwasnotincompliance.

    Anexampleofanon-selectivelycoordinatedsystemiswhenabranchcircuitisshortedout,causingthefeederandmaybeeventhemaintode-energize.Thiscanhappeninatypicalbuildingthatwasnotdesignedwithselectivecoordinationasagoal.Thenwhyisituncommontoseeentirebuildingslosetheirpowerduetoabranchovercurrent?

    Overcurrentscanbebrokenintotwotypesoverloadsandshortcircuits.Typicallyanoverloadislessthan10timestheratedcircuitcurrentandtheshortcircuitisover10times.Overloadsarethemostcommonelectricalproblem.Thesecommonoverloadsareveryeasytoselectivelycoordinatebecausemostfusesandcircuitbreakersaredesignedforthisperformance.Aslongastheupstreamovercurrentdevicehasahighertriprating,overloadsarealmostautomaticallycoordinated.

    Thelesscommonovercurrentistheshortcircuit.Thisiswhenselectivecoordinationcanbecomeanengineeringtask.Unfortunately,shortcircuitsaremorelikelyduringafireorexplosionandthatisthesametimethatelevatorsandemergencyelectricalsystemsaremostneeded.Shortcircuitshavehighcurrentsandtheovercurrentprotectivedevicesrespondveryrapidly.Therapidresponsetimeshavetobecoordinatedsothatthesmallestportionoftheelectricalsystemistakenoutofservice.Ifthisisaccomplished,thesystemisselectivelycoordinated.

    Electricalinspectorswerebeingaskedtoruleonthecomplianceofasystemtotheselectivecoordinationcoderequirements.Sinceevenengineerssometimesdisagreed,theelectricalinspectorswereputinadifficultposition.

    how to ComPly

    Thenewcodedefinitionisspecificthatthecoordinationmustbeforalltypesofovercurrentsindependentofhowlongtheprotectiondevicestaketooperate.Thisshouldresolvetheengineersdiscussionabouttheintentofselectivecoordination.

    Thecodecommitteefoundawaytohavetheelectricalinspectorenforcewithouthavingtobeanengineer.Thecoderequiresaqualifiedperson,acceptabletotheelectricalinspector,documenttheselectivecoordinationstatusoftheinstallation.Theelectricalinspectorcannowjustrequirethedocumentation.

    Selectivecoordinationcanbeaccomplishedveryeasilywhenoriginallyselectingelectricalequipment.However,oncetheequipmentisonthejobsite,sometimestheadjustmentrangesofequipmentdonotpermitselectivecoordinationwithoutreplacingequipment.Theleastexpensivecircuitbreakertype,moldedcase,isproblematicforselectivecoordination.

    helPful ProduCts

    TheeasiestwaytocomplyistouseAmp-Trap2000fuses.Aslongasthesupplyfusesareatleasttwicetheampereratingoftheloadfuses,theAmp-Trap2000fusesareselectivelycoordinated.Thisfamilyoffusesgoesupthrough6,000amps.

    TheMersenelevatorFusibleShuntPanelassistsineasyselectivecoordination.ItusesULClassJfusespermittingeasycoordinationbetweenupstreamfusesandupstreamcircuitbreakers.Thecurrent-limitingfusescutoffthefaultcurrentatalowenoughleveltoavoidtrippingtheupstreambreakerinmanyapplications.

  • 18 Mersen NEC Code 2014

    10. Selective Coordination Not Required in HospitalsPrevious Code requirements

    The2005Codeselectivecoordinationrequirementwasexpandedtohealthcarefacilities,emergencysystemsandlegallyrequiredstandbysystems.Theeffectsofthisexpansionwerewelldiscussedduringthe2008and2011codecycles,resultinginsomeclarification.Thecodemakingcommunityreviewedthebasicsofselectivecoordinationanddecidedtokeeptherequirementsforselectivecoordination.

    Selectivecoordinationisadescriptionofhowanelectricalsystemactsunderovercurrents.Mostpeopleexpectthatasingleovercurrentinthesystemwouldde-energizethelocalproblemandlettherestofthesystemcontinuetooperate.Iftheelectricalsystemwasnotengineeredtobehaveasaselectivelycoordinatedsystem,alocalproblemcanresultinshuttingoffsubstantiallymoreofthesystemthannecessarytoisolatetheproblem.

    Article517usedthephrase,emergencysysteminthedefinitionofhospitalessentialsystems.ThatmadehospitalessentialsystemssubjecttotherequirementsofArticle700EmergencySystems.ThereforeArticle517requiredselectivecoordination.

    new CodeHealth Care Facilities

    517.2 Definitions. Critical Branch. Asystemoffeedersandbranchcircuitssupplyingpowerfortask illumination,fixedequipment,selectreceptacles,andselectpowercircuitsservingareasandfunctionsrelatedtopatientcareandthatisautomaticallyconnectedtoalternatepowersourcesbyoneormoretransferswitchesduringinterruptionofnormalpowersource.[99:3.3.30]

    517.30 Essential Electrical Systems for Hospitals. (G) Coordination. Overcurrent protective devices serving the essential electrical system shall be coordinated for the periodoftimethatafaultsdurationextendsbeyond0.1second.

    Exception No. 1: Between transformer primary and secondary overcurrent protective devices, where only one overcurrent protective device or set of overcurrent protective devices exists on the transformer secondary.

    Exception No. 2: Between overcurrent protective devices of the same size (ampere rating) in series.

    Informational Note: The terms coordination and coordinated as used in this section do not cover the full range of overcurrent conditions.

    DeviceClosesttoFaultMustOpenWithoutOpeningUpstreamProtection

    FaultedCircuit

  • Mersen NEC Code 2014 19

    10. Selective Coordination Not Required in Hospitals, Continued

    reasons for Changes

    TheNFPAorganizationdefineswhichcommitteehasjurisdictionoveroccupancies.NFPAassignedtheultimateresponsibilityforHealthCareFacilitieselectricalsystemstotheNFPA99committee.ThisHealthCareFacilitiesCodehas15chapters,oneofwhichiselectricalsystems.

    Thismulti-disciplinecommitteedecidedthatselectivecoordinationshouldnotbearequirementinhospitals.TheNFPArulesdictatethattheNationalElectricalCodecannotcontradictNFPA99.AsresulttheNECCommitteeforHealthCareFacilitieswasdirectedtocomplywiththedeletionofselectivecoordinationrequirements.

    TheNECcommitteethencomplied.Theychangedthedefinitionofessentialelectricalsystemstodeleteanyreferencetoemergencysystems.Thatdeletedthelinktotherequirementforselectivecoordination.ThentheyaddedverbatimthecoordinationrequirementfromNFPA99:3.3.30.FinallytheyaddedanInformationalNoteremindingthatcoordinationinthisarticledoesnotcoverthefullrangeofcurrents.

    how to ComPly

    TheNECrequirementisdeletedforselectivecoordinationinhospitals.Becausethepriorcodewasstricter,thereisnonewrequirement.However,becauseofpotentiallegalliabilityofnotcomplyingwithpreviouscodes,goodpracticewouldbetocontinuethepracticeofselectivecoordinationwiththehospitalsapproval.

    Whendesigninganewelectricalsystem,thesectionsforselectivecoordinationshouldbeidentifiedfirst.Althoughcircuitbreakerscanbeselectivelycoordinatedforagivensystem,theuseoftheAmp-Trap2000familyoffusesismoreeconomical.

    WithintheAmp-Trap2000familyoffusesasimple2:1ratioofthefusesizesensuresselectivecoordination.Thisisduetothecurrent-limitingactionofthefuseswhicharemuchfaster-actingthancircuitbreakers.Thereductionoftimeandcomplexityfromusingcircuitbreakersystemscanreducetheengineeringefforttocomplywiththeselectivecoordinationrequirements.

    Ifthehospitalpreferscircuitbreakers,fusescanbeusedonlyasatransitionbetweensectionsoftheelectricalsystemthataredifficulttoselectivelycoordinate.

    helPful ProduCts

    TheselectivecoordinationrequirementcanbeeasilymetinnewsystemsdesignusingtheAmp-Trap2000familyoffuses.Thisfamilyenablesmeetingtherequirementseveniffutureelectricalsystemmodificationsvarytheavailablefaultcurrents.

    TheMersenFusedCoordinationPanelboardenablesselectivityindifficultapplications.Itconsistsofcircuitbreakersandfusesarrangedinapanelboardtoeasilyachieveselectivecoordination.

    TheElevatorSwitch,alsocalledtheFusibleShuntTripDisconnect,isbuiltforselectivecoordinationofelevatorapplications.Itfeaturesafiresafetyinterfacerelaywithafirealarmvoltagemonitoringrelayandmechanicallyinterlockedauxiliarycontacts.UseofMersensAmp-Trap2000ClassJfuseseasilypermitsselectivecoordination.

  • A WORLD LEADERin safety & reliability for electrical power.

    Main production sites

    Industrial or commercial branch

    Aglobalexpertinmaterialsandsolutionsforextremeenvironmentsaswellasin

    thesafetyandreliability ofelectricalequipment,

    Mersendesignsinnovativesolutionstoaddressits

    clientsspecificneedstoenablethemtooptimizetheirmanufacturingprocessinsectorssuchasenergy,transportation,electronics,chemical,pharmaceutical,andprocessindustries.

    A GLOBAL PLAYER

    ep.mersen.com

    BR-N

    EC14

    -001

    | 12.1

    3 | P

    DF |

    Mer

    sen 2

    013

    Mersen $4.99 USA $5.99 Canada

    MERSEN U.S.A. 374 Merrimac StreetNewburyport, MA 01950U.S.A.T : 978 462 6662F : 978 462 0181

    MERSEN France15 Rue Jacques de VaucansonF-69720 Saint Bonnet de Mure FranceT : +33 (0)4 72 22 66 11F : +33 (0)4 72 22 67 13

    MERSEN Toronto 6200 Kestrel RoadToronto, OntarioCanada L5T 1Z1T : 416 252 9371F : 416 252 6572

    MERSEN ShanghaiNo.55-A6. Shu Shan RoadSongjiang 201611 ShanghaiTel: +8621 67602388