48 volt volta drop calculator

Upload: angelo26033

Post on 05-Apr-2018

232 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 48 Volt Volta Drop Calculator

    1/12

    length

    Conductor cross- sectional

    area Resistance per metre run (mm) (m ohms / m)

    1 18.1

    1.5 12.1

    2.5 7.41

    4 4.61

    6 3.08

    10 1.83

    16 1.1525 0.727

    ABLE SIZE MV/A/MTR LENGTH CURRENT2.5 7.41 80 MTRS 11 10 FTTO 1.1 AMP MAX PER UNIT4 4.61 80 MTRS 11 10 FTTO6 3.08 80 MTRS 11 10 FTTO

    ABLE SIZE VOLTAGE DROP2.5 6.5 FAIL4 4.1 FAIL6 2.7 OLTS DROP PASS

    MAXIMUM VD TO BE LESS THAN 4 VOLTS ON 48 VOLT SYSTEM AS ADVISED BY MANUFACURER

    ---------------- calculation of R1 + R2

  • 7/31/2019 48 Volt Volta Drop Calculator

    2/12

    CABLE SIZE MV/A/MTR LENGTH CURRENT2.5 7.41 70 MTRS 8.8 8 FTTO 1.1 AMP MAX PER UNIT4 4.61 70 MTRS 8.8 8 FTTO6 3.08 50 MTRS 8.8 8 FTTO

    CABLE SIZE VOLTAGE DROP2.5 4.6 FAIL4 2.8 PASS6 1.355 VOLTS DROP PASS

    MAXIMUM VD TO BE LESS THAN 4 VOLTS ON 48 VOLT SYSTEM AS ADVISED BY MANUFACURER

    examplel = 70

    I = 8.8 ampscable size = 6mm

  • 7/31/2019 48 Volt Volta Drop Calculator

    3/12

  • 7/31/2019 48 Volt Volta Drop Calculator

    4/12

  • 7/31/2019 48 Volt Volta Drop Calculator

    5/12

  • 7/31/2019 48 Volt Volta Drop Calculator

    6/12

    1 1.12 2.23 3.34 4.45 5.56 6.67 7.78 8.89 9.9

    10 1111 12.112 13.213 14.314 15.415 16.516 17.617 18.718 19.819 20.920 2221222324252627282930

  • 7/31/2019 48 Volt Volta Drop Calculator

    7/12

    31323334353637383940414243444546474849505152535455565758596061

  • 7/31/2019 48 Volt Volta Drop Calculator

    8/12

    62636465666768697071727374757677787980818283848586878889909192

  • 7/31/2019 48 Volt Volta Drop Calculator

    9/12

    93949596979899

    100101102103104105

  • 7/31/2019 48 Volt Volta Drop Calculator

    10/12

    CIRCUIT REFERENCE VOLTAGE LENGTH CURRENT CONSTANT COPPER RISISTIVITY CABLE SIZE RADIAL RING1 48V DC 50 14.3 0.017 6 1 22 48V DC 50 13.2 0.017 6 1 2 30/5/20123 48V DC 50 1.1 0.017 2.5 1 2

    1 c = 0.4% vd rise above 25 deg Cexample L = 50 mtr

    CIRC No 1 13 FTTO 2.5 MM =total current = 8.8 amps 4.00 MM=

    cable size = 4 mm sq 6.00MM=

    VD at 25C = 2.025833 VD IF RING 1.0737 VDadditional temp = 15c installed

    vd based at 40 C = 2.147383

    terminal voltage at FTTO = 45.85262 VOLTS

    0.4% = 0.00810333 VDactual voltage drop 2.147383 VOLTS

    CIRC No 2 12 FTTO VD IF RING 0.9958total current = 7.7 amps installed

    cable size = 4 mm sqVD at 25C = 1.87

    additional temp = 15c 1vd based at 40 C = 1.99155 2

    3

    terminal voltage at FTTO = 46.00845 VOLTS 45

    actual voltage drop 1.99155 VOLTS 67

    COST SAVINGS TO TRADITIONAL INSTALL AT C3

    Reduction in future maintenance costs.

    Angelo Franklin

    ALEC CONSTRUCTION

    FORMULA USED = CABLE LTH X CURRENT USED X RISISTIVITY CONSTANT AT 25 DEG C / CROSS SECTIONAL AREA OF CABLE

    CABLE RATINGS

    80/85% less cables.80/85% less conduits.Reduction in containement sizes.

    Reduction in distribution board sizes.

    Reduction in engineering/coordination.Reduction labour costs.

  • 7/31/2019 48 Volt Volta Drop Calculator

    11/12

    1.92

  • 7/31/2019 48 Volt Volta Drop Calculator

    12/12

    1.1 52.2 103.3 154.4 205.5 256.6 30

    7.7 358.8 409.9 4511 50

    12.1 5513.2 6014.3 6515.4 7016.5 7517.6 80

    859095

    100105110115120125130