PARAMETERS Size of Aluminium Bus Bar Proposed 1x125x6 mm 2 Site Ambient Temperature 45 o C Rise in Temperature allowed 40 o C Final Temperature Permitted 85 o C Fault current 50 kA A. MINIMUM CONDUCTOR SIZE Area of cross section Øt = (k/100) ( Isc/A) 2 (1+ α 20 . Ø) .t ( Ref: Industrial Power Engineering and application Handbook page no. 999) Øt= temperature rise above operating temp. in deg. C Isc= symmetrical fault current in r.m.s in Amps. A= cross sectional area of conductor in mm 2 α 20 = 0.00363 for Aluminium alloy & 0.00403 for pure Alluminium Ø= operating temperature of the conductor at which the fault occurs k= 1.166 for aluminium and 0.52 for copper t= duration of fault in seconds Final temp. allowed for busbar after short circuit is 185 deg C By putting all values in the above equation 100 = (1.166/100) ( 50000/A) 2 (1+ 0.00403 x 85) x 1 A= 625.6 mm2 CALCULATION FOR AL BUS BAR SUITABLE FOR 50KA FAULT LEVEL temperature coefficient of resistence at 20 deg C/deg C Considering 6mm thickness for Aluminium flat for Main horizontal bus bar , we have provided 125x6mm size. For vetical droppers minimum cross section 625sq. mm shall be provided. PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

Upload: anandgirgaonkar

Post on 15-Nov-2015

28 views

Category:

Documents


0 download

DESCRIPTION

Sample sizing calculation for busbar

TRANSCRIPT

  • PARAMETERS

    Size of Aluminium Bus Bar Proposed 1x125x6 mm2

    Site Ambient Temperature 45oC

    Rise in Temperature allowed 40oC

    Final Temperature Permitted 85oC

    Fault current 50 kA

    A. MINIMUM CONDUCTOR SIZE

    Area of cross section

    t = (k/100) ( Isc/A)2 (1+ 20 . ) .t( Ref: Industrial Power Engineering and application

    Handbook page no. 999)t= temperature rise above operating temp. in deg. CIsc= symmetrical fault current in r.m.s in Amps.

    A= cross sectional area of conductor in mm220=

    0.00363 for Aluminium alloy & 0.00403 for pure Alluminium= operating temperature of the conductor at which the fault occursk= 1.166 for aluminium and 0.52 for coppert= duration of fault in seconds

    Final temp. allowed for busbar after short circuit is 185 deg C By putting all values in the above equation

    100 = (1.166/100) ( 50000/A)2 (1+ 0.00403 x 85) x 1A= 625.6 mm2

    CALCULATION FOR AL BUS BAR SUITABLE FOR 50KA FAULT LEVEL

    temperature coefficient of resistence at 20 deg C/deg C

    Considering 6mm thickness for Aluminium flat for Main horizontal bus bar , we have provided 125x6mm size. For vetical droppers minimum cross section 625sq. mm shall be provided.