1 Instruction Bulletin 63230-216-235A2 06/2009 LaVergne, TN, USA ACE969-2 Multi-Protocol Communication Interface Install Sheet Retain for future use. Function The ACE969-2 multi-protocol communication interfaces function with Sepam™ Series 20, 40, or 80. They have two communication ports (one S- LAN and one E-LAN) to connect a Sepam to two independent communication networks: The S-LAN (Supervisory Local Area Network) port connects a Sepam device to a supervision network using one of the three following protocols: IEC 60870-5-103 DNP3 Modbus RTU The communication protocol is selected when setting Sepam parameters. The E-LAN (Engineering Local Area Network) port, reserved for Sepam remote parameter setting and operation using the SFT2841 software There are two versions of the ACE969-2 interfaces. Each has different S- LAN ports: ACE969TP-2 (Twisted Pair) is for connecting to an S-LAN network using a two wire RS485 connection ACE969FO-2 (Fiber Optic) is for connecting to an S-LAN network using a fiber-optic connection (star or ring) The E-LAN port is always a two-wire RS485, Modbus RTU connection. Characteristics Dimensions ACE969TP-2 Communication Interface PB103454 ACE969FO-2 Communication Interface Sepam Series 20 Sepam Series 40 Sepam Series 80 V0526 V3.00 Base V3.00 Appli V3.00 Install1 51.2 2.0 ACE969TP-2 Rx e1 e2 Tx on Rx Tx service V+ V- A B 1 2 3 4 5 V+ V- A B 1 2 3 4 5 S-LAN E-LAN 12345 E-LAN Rc Rc Rc Rc 12345 mm in 94 3.70 144 5.67 DB114880 PB103453

Upload: nguyenhanh

Post on 28-Apr-2018

220 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: 63230-216-235A2 06/2009 Instruction Bulletin LaVergne, … El… · 63230-216-235A2 06/2009 LaVergne, TN, USA ACE969-2 Multi-Protocol Communication Interface Install Sheet Retain

1

Instruction Bulletin63230-216-235A2

06/2009LaVergne, TN, USA

ACE969-2 Multi-Protocol Communication InterfaceInstall Sheet

Retain for future use.

Function

The ACE969-2 multi-protocol communication interfaces function with Sepam™ Series 20, 40, or 80. They have two communication ports (one S-LAN and one E-LAN) to connect a Sepam to two independent communication networks:

The S-LAN (Supervisory Local Area Network) port connects a Sepam device to a supervision network using one of the three following protocols:

• IEC 60870-5-103

• DNP3

• Modbus RTU

The communication protocol is selected when setting Sepam parameters. The E-LAN (Engineering Local Area Network) port, reserved for Sepam remote parameter setting and operation using the SFT2841 software

There are two versions of the ACE969-2 interfaces. Each has different S-LAN ports:

• ACE969TP-2 (Twisted Pair) is for connecting to an S-LAN network using a two wire RS485 connection

• ACE969FO-2 (Fiber Optic) is for connecting to an S-LAN network using a fiber-optic connection (star or ring)

The E-LAN port is always a two-wire RS485, Modbus RTU connection.

Characteristics Dimensions

ACE969TP-2 Communication Interface

PB

103

454

ACE969FO-2 Communication Interface

Sepam Series 20

Sepam Series 40

Sepam Series 80

≥ V0526

≥ V3.00 Base ≥ V3.00 Appli ≥ V3.00

Inst

all1

51.22.0

ACE969TP-2Rx

e1 e2

Tx on Rx Tx

serv

ice

V+V-AB1 22 3 4 5

V+V-AB1 2 3 4 5

S-LAN E-LAN

1 2 3 4 5

E-LAN

Rc

Rc

Rc

Rc

1 2 3 4 5

mmin

943.70

1445.67

DB

1148

80

PB

1034

53

Page 2: 63230-216-235A2 06/2009 Instruction Bulletin LaVergne, … El… · 63230-216-235A2 06/2009 LaVergne, TN, USA ACE969-2 Multi-Protocol Communication Interface Install Sheet Retain

ACE969-2 Multi-Protocol Communication Interface 63230-216-235A206/2009

© 2009 Schneider Electric. All Rights Reserved.2

1. The ACE969-2 has a built in communications power source which derives it’s power from the unit’s power supply.

Maximum length is calculated with:

• Minimum optical power available

• Maximum fiber attenuation

• Losses in two ST connectors: 0.6 dBm

• Optical power margin: 3 dBm (according to IEC 60870 standard)

Example for a 62.5/125 m fiber

Lmax = (9.4 - 3 - 0.6)/3.2 = 1.8 km (1.12 mi)

ACE969-2 Module

Technical Characteristics

Weight 0.628 lb (0.285 kg)

Assembly On symmetrical DIN rail

Operating Temperature –13°F to +158°F (–25°C to +70°C)

Environmental Characteristics Same characteristics as Sepam base units

Power Supply

Voltage 24 to 250 VDC 110 to 240 VAC

Range –20%/+10% –20%/+10%

Maximum Burden 2 W 3 VA

Inrush Current < 10 A 100 s

Acceptable Ripple Current 12%

Acceptable momentary outages 20 ms

Two-Wire RS485 Communication Ports

Electrical Interface

Standard EIA 2-wire RS485 differential

Distributed power supply Not required on the ACE969-21

Communication Port Setup (Configured using SFT2841)

Baud Rate 4800, 9600, 19200 or 38400

Sepam Address 1 to 247

Parity Even, Odd or None

Fiber Optic Communication Port

Fiber Optic Interface

Fiber Type Graded-index multimode silica

Wavelength 820 nm (invisible infra-red)

Type of Connector ST (BFOC bayonet fiber optic connector)

Communication Port Setup (Configured using SFT2841)

Sepam Address 1 to 247

Parity Even, Odd or None

Link Idle State Light On or Light Off

Echo Mode Yes or No

Maximum Length of Fiber Optic Network

Fiber Diameter (m)

Numerical Aperture (NA)

Attenuation (dBm/km)

Min. Optical Pwr Available (dBm)

Maximum Fiber Length

50/125 0.2 2.7 5.6 2300 ft (700 m)

62.5/125 0.275 3.2 9.4 5900 ft (1800 m)

100/140 0.3 4 14.9 9200 ft (2800 m)

200 (HCS) 0.37 6 19.2 8500 ft (2600 m)

Page 3: 63230-216-235A2 06/2009 Instruction Bulletin LaVergne, … El… · 63230-216-235A2 06/2009 LaVergne, TN, USA ACE969-2 Multi-Protocol Communication Interface Install Sheet Retain

63230-216-235A2 ACE969-2 Multi-Protocol Communication Interface06/2009

© 2009 Schneider Electric. All Rights Reserved. 3

Component Descriptions ACE969-2 Communication Interfaces

Ctrl Power

ACE969TP-2Rx

e1 e2

Tx on Rx Tx

serv

ice

V+V-AB1 22 3 4 5

V+V-AB1 2 3 4 5

S-LAN E-LAN

1 2 3 4 5

E-LAN

RcRc

RcRc

1 2 3 4 5

RS485 RS485

ACE969TP-2: 59720

V DC / V ACCtrl Power

ACE969FO-2Rx

e1 e2

Tx on Rx Tx

serv

ice

V+V-AB1 22 3 4 5

V+V-AB1 2 3 4 5

E-LAN

1 2 3 4 5

E-LAN

RcRc

RS485FO

ACE969FO-2: 59721

V DC / V AC

Inst

all2

1. Grounding terminal using supplied braid

2. Power-supply terminal block

3. RJ45 socket to connect the interface to the base unit with a CCA612 cable

4. Green LED: ACE969-2 energized

5. Red LED: ACE969-2 interface status

• LED off = ACE969-2 set up and communication operational

• LED flashing = ACE969-2 not set up or setup incorrect

• LED remains on = ACE969-2 failed

6. Service connector: reserved for software upgrades

7. E-LAN 2-wire RS485 communication port (ACE969TP-2 and ACE969FO-2)

8. S-LAN 2-wire RS485 communication port (ACE969TP-2)

9. S-LAN fiber-optic communication port (ACE969FO-2)

ACE969TP-2

Rx Txon

Rx Tx

B AV- V+

54321

4 5

S-LANE-LAN

S E N S D E L E C T U R E

1 2 3

1 2 3 4 5

1 8 72

3 4 5 6

ACE969FO-2

Rx Txon

Rx Tx

B AV- V+

54321

1 2 3 4 5

S-LANE-LAN

S E N S D E L E C T U R E

1 9 72

3 4 5 6D

B1

1462

8

DB

114

629

ACE969TP-2 ACE969FO-2

Page 4: 63230-216-235A2 06/2009 Instruction Bulletin LaVergne, … El… · 63230-216-235A2 06/2009 LaVergne, TN, USA ACE969-2 Multi-Protocol Communication Interface Install Sheet Retain

ACE969-2 Multi-Protocol Communication Interface 63230-216-235A206/2009

© 2009 Schneider Electric. All Rights Reserved.4

RS485 Connection

Two-Wire RS485 Communication Ports

21

4 5

NE-LAN

1 2 3

2 3 4 5

V+V-

543

4 5

E-LAN

1 2 3

4 5

V 54

ACE969TP-2

RxTx

onRx

Tx

B AV+

V-54321

4 5

S-LANE-LAN

S E N S D E L E C T U R E

1 2 3

1 2 3 4 5

B AV+

V-54321

4 5

E-LAN

1 2 35

Inst

all3

a

1. Two-Wire RS485 Network Terminal Block:

• 1 (B) RS485 Data Terminal B

• 2 (A) RS485 Data Terminal A

• 3 (.) Chassis Common Ground

• 4 (V-) Negative Power Connection

• 5 (V+) Positive Power Connection

NOTE: 3 (.) is also connected to common ground

2. LEDs:

• Flashing Tx LED: Sepam sending

• Flashing Rx LED: Sepam receiving

3. Jumper for 2-wire RS485 network line-end impedance matching with the load resistor (Rc = 150 ), is set to:

• , if the module is not at one end of the network (default position). The "X" over the "Rc" indicates that the resistor is not in use

• Rc, if the module is at one end of the network. This means the resistor is jumpered in

Rc

Rx Tx on Rx Tx

s

V+V-AB1 22 3 4 5

S-LAN E-LAN

1 2 3 4 5

E-LAN

Rc

Rc

Rc

Rc

1 2 3 4 5

12

3

Rx Tx on Rx Tx

s

V+V-AB1 22 3 4 5

-LAN E-LAN

1 2 3 4 5

E-LAN

Rc

Rc

12

3

DB

114

630

DB

114

631

S-LAN Port (ACE969TP-2) E-LAN Port (ACE969TP-2 or ACE969FO-2)

Page 5: 63230-216-235A2 06/2009 Instruction Bulletin LaVergne, … El… · 63230-216-235A2 06/2009 LaVergne, TN, USA ACE969-2 Multi-Protocol Communication Interface Install Sheet Retain

63230-216-235A2 ACE969-2 Multi-Protocol Communication Interface06/2009

© 2009 Schneider Electric. All Rights Reserved. 5

Fiber-Optic Communication Port

AC/D

C +

AC/D

C –

ACE969FO-2

Control Power

CommonGround

Chassis Common Ground

DE

5207

8a

1. LEDs:

• Flashing Tx LED: Sepam sending

• Flashing Rx LED: Sepam receiving

2. Rx, female ST type connector (Sepam receiving)

3. Tx, female ST type connector (Sepam sending)

S-LAN Port (ACE969FO-2)

Rx Tx on Rx Tx

s

V+AB1 22 3 4 5

S-LAN E-LAN

1 2 3 4 5

E-LAN

Rc

Rc

1

23

DB

1146

32

Inst

all6

AC/DC +

AC/DC –

AC/DC +

AC/DC –

ACE969TP-2Rx

e1 e2

Tx on Rx Tx

service

V+V-AB1 22 3 4 5

V+V-AB1 2 3 4 5

S-LAN E-LAN

1 2 3 4 5

E-LAN

RcRc

RcRc

1 2 3 4 5

Page 6: 63230-216-235A2 06/2009 Instruction Bulletin LaVergne, … El… · 63230-216-235A2 06/2009 LaVergne, TN, USA ACE969-2 Multi-Protocol Communication Interface Install Sheet Retain

ACE969-2 Multi-Protocol Communication Interface 63230-216-235A206/2009

© 2009 Schneider Electric. All Rights Reserved.6

Connecting the ACE969-2 Power Supply and Sepam

The ACE969-2 interface connects to on the Sepam base unit using a CCA612 cable (length = 9.8 ft or 3 m, with white RJ45 fittings)

The ACE969-2 requires a supply voltage of 24 to 250 V DC or 110 to 240 V AC to operate.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Only qualified electrical workers should install this equipment. Such work should be performed only after reading this entire set of instructions.

• NEVER work alone.

• Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources of electric power. Assume that all circuits are live until they have been completely de-energized, tested, and tagged. Pay particular attention to the design of the power system.

• Consider all sources of power, including the possibility of backfeeding.

• Always use a properly rated voltage sensing device to confirm that all power is off.

• Screw tight all terminals, even those not in use.

Failure to follow these instructions will result in death or serious injury.

Terminals Type Wiring

e1-e2 - supply Screw terminals Wiring with no fittings:

• One wire with maximum cross-section 0.2 to 2.5 mm2 ( AWG 24 - 12) or two wires with maximum cross-section 0.2 to 1 mm (AWG 24 - 18)

• Stripped length: 0.31 to 0.39 in (8 to 10 mm)

Wiring with fittings:

• recommended wiring with Telemecanique fitting:

- DZ5CE015D for 1 wire 1.5 mm² (AWG 16)

- DZ5CE025D for 1 wire 2.5 mm² (AWG 12)

- AZ5DE010D for 2 wires 1 mm² (AWG 18)

• Wire length: 0.32 in (8.2 mm)

• Stripped length: 0.31 in (8 mm)

Protective ground Screw terminal

Control Power ground conductor

1 green/yellow wire, max. length 9.8 ft (3 m) and max. cross-section 2.5 mm² (AWG 12)

Functional gnd

(Common Gnd)0.16 in (4 mm) ring lug

Grounding braid, supplied for connection to cubicle grounding

CAUTIONESD SENSITIVE COMPONENTS

• Before touching the Memory Cartridge you must ground yourself and discharge any static charge.

• Ground yourself every time before touching the memory cartridge

Failure to follow this instruction can result in equipment damage.

C

ACE969TP-2

Rx Txon

Rx Tx

B AV+

V-54321

4 5

S-LANE-LAN

S E N S D E L E C T U R E

1 2 3

1 2 3 4 5

B AV+

V-54321

CCA612ACE969TP-2

CV DC/V AC

DB

114

795

DE

5184

5D

E51

962

Page 7: 63230-216-235A2 06/2009 Instruction Bulletin LaVergne, … El… · 63230-216-235A2 06/2009 LaVergne, TN, USA ACE969-2 Multi-Protocol Communication Interface Install Sheet Retain

63230-216-235A2 ACE969-2 Multi-Protocol Communication Interface06/2009

© 2009 Schneider Electric. All Rights Reserved. 7

Connections Two-Wire RS485 Communication Ports (S-LAN or E-LAN)

1. Connect the RS485 twisted pair (S-LAN or E-LAN) to black terminals A and B.

2. Connect the 4(V-) and 5(V+) terminals.

• If ACE969 and ACE969-2 devices are being used on the same RS485 serial network then the power connections on terminals 4(V-) and 5(V+) must be connected to a 12Vdc or 24Vdc external power supply.

• If the ACE969-2 is the only device type on the RS485 network then no external power supply is necessary. However connect terminal 4(V-) for ground continuity.

3. The cable shielding must be connected to the 3(.) terminal.An internal connection links all cable clamps to the ACE969 Interface grounding terminals (protective and functional grounding), with the shielding of the RS485 cables is grounded as well.

4. On the ACE969TP-2 interface, the 3(.) terminal for the S-LAN and E-LAN RS485 networks are grounded.

NOTE: The cable shielding shown at left should only be done at one point, preferably at one end of the RS485 communication network.

Fiber Optic Communication Port (S-LAN)

The fiber optic connection can be made point-to-point to an optic star system, or in a ring system (active echo). The transmitting and receiving optic fibers must have male ST type connectors. The fiber optics screw-lock to Rx and Tx connectors.

CommonGround

ChassisCommonGround

DE

5207

8

ACE969FO-2

ACE969FO-2

ACE969FO-2

DE

5216

5

CAUTIONHAZARD OF BLINDING

• Never look directly into the fiber optic

Failure to follow this instruction can cause serious injury.

ACE969FO-2Rx

e1 e2

Tx on Rx Tx

serv

ice

V+V-AB1 22 3 4 5

S-LAN E-LAN

1 2 3 4 5

E-LAN

Rc

Rc

Fiber Optic (FO)

Inst

all7

Page 8: 63230-216-235A2 06/2009 Instruction Bulletin LaVergne, … El… · 63230-216-235A2 06/2009 LaVergne, TN, USA ACE969-2 Multi-Protocol Communication Interface Install Sheet Retain

ACE969-2 Multi-Protocol Communication Interface 63230-216-235A2Instruction Bulletin 06/2009

Square DTM, Schneider ElectricTM and SepamTM are trademarks or registered trademarks of Schneider Electric. Other trademarks used herein are the property of their respective owners.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

© 2009 Schneider Electric. All Rights Reserved.