718 Bradford Alley Philadelphia Historical Commission April/May 2021 718 BRADFORD ALY Proposal: Install solar panels Review Requested: Final Approval Owner: Michael Kessler Applicant: Evan Haberman, Pinnacle Exteriors History: 1882, Starr’s Row Individual Designation: 12/31/1984 District Designation: None Staff Contact: Megan Cross Schmitt, [email protected] BACKGROUND: The building at 718 Bradford Alley is part of a row of rowhouses with mansards that was constructed by philanthropist Theodore Starr in 1882. Starr was an early housing reformer who sought to improve unsanitary slums and provide social services for the poor. This application proposes to install solar panels at the flat roof of 718 Bradford Alley. Though the staff believes the solar panels themselves will be inconspicuous from the public right-of-way, the disconnect box is proposed to be attached onto the front façade of the house and would be highly visible. SCOPE OF WORK: Install solar panels and associated equipment. STANDARDS FOR REVIEW: The Secretary of the Interior’s Standards for the Treatment of Historic Properties and Guidelines include: Roofs Guideline: Recommended: Installing mechanical and service equipment on the roof (such as heating and air conditioning units, elevator housing, or solar panels) when required for a new use so that they are inconspicuous from the public right-of-way and do not damage or obscure character-defining features. o The proposed location of the six panels is at the flat roof of the house. Owing to the extremely narrow width of Bradford Alley, as well as the building’s mansard, the flat portion of the roof is not visible. The proposed location of the panels is appropriate. Standard 9: New additions, exterior alterations, or related new construction shall not destroy historic materials that characterize the property. The new work shall be differentiated from the old and shall be compatible with the massing, size, scale, and architectural features to protect the historic integrity of the property and its environment. o The disconnect box is proposed to attach directly on to the front façade and would be highly visible from the public right-of-way. The staff has worked with other applicants in the past to install these boxes at less conspicuous locations and recommends that this applicant find another location, including possibly at the interior or the rear of the house. Alternatively, the applicant could consider installing the disconnect box free-standing in front of the house if possible. o The staff asks the applicant to explain where any associated conduit would be located and how it would interact with the mansard. The staff recommends against running conduit across or over the mansard roof. STAFF RECOMMENDATION: Approval of location of panels as proposed, but denial of the disconnect box at the front façade, pursuant to the Roofs Guideline and Standard 9.

Upload: others

Post on 10-Nov-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 718 BRADFORD ALY - Philadelphia

718 Bradford Alley Philadelphia Historical Commission

April/May 2021

718 BRADFORD ALY Proposal: Install solar panels Review Requested: Final Approval Owner: Michael Kessler Applicant: Evan Haberman, Pinnacle Exteriors History: 1882, Starr’s Row Individual Designation: 12/31/1984 District Designation: None Staff Contact: Megan Cross Schmitt, [email protected] BACKGROUND: The building at 718 Bradford Alley is part of a row of rowhouses with mansards that was constructed by philanthropist Theodore Starr in 1882. Starr was an early housing reformer who sought to improve unsanitary slums and provide social services for the poor. This application proposes to install solar panels at the flat roof of 718 Bradford Alley. Though the staff believes the solar panels themselves will be inconspicuous from the public right-of-way, the disconnect box is proposed to be attached onto the front façade of the house and would be highly visible. SCOPE OF WORK:

• Install solar panels and associated equipment. STANDARDS FOR REVIEW: The Secretary of the Interior’s Standards for the Treatment of Historic Properties and Guidelines include:

• Roofs Guideline: Recommended: Installing mechanical and service equipment on the roof (such as heating and air conditioning units, elevator housing, or solar panels) when required for a new use so that they are inconspicuous from the public right-of-way and do not damage or obscure character-defining features.

o The proposed location of the six panels is at the flat roof of the house. Owing to the extremely narrow width of Bradford Alley, as well as the building’s mansard, the flat portion of the roof is not visible. The proposed location of the panels is appropriate.

• Standard 9: New additions, exterior alterations, or related new construction shall not destroy historic materials that characterize the property. The new work shall be differentiated from the old and shall be compatible with the massing, size, scale, and architectural features to protect the historic integrity of the property and its environment.

o The disconnect box is proposed to attach directly on to the front façade and would be highly visible from the public right-of-way. The staff has worked with other applicants in the past to install these boxes at less conspicuous locations and recommends that this applicant find another location, including possibly at the interior or the rear of the house. Alternatively, the applicant could consider installing the disconnect box free-standing in front of the house if possible.

o The staff asks the applicant to explain where any associated conduit would be located and how it would interact with the mansard. The staff recommends against running conduit across or over the mansard roof.

STAFF RECOMMENDATION: Approval of location of panels as proposed, but denial of the disconnect box at the front façade, pursuant to the Roofs Guideline and Standard 9.

Page 2: 718 BRADFORD ALY - Philadelphia

718 Bradford Alley Philadelphia Historical Commission

April/May 2021

Figure 1. Aerial view of 718 Bradford Alley and surrounding context, Atlas, 2020.

Figure 2. View from Kauffman Street, April 2021.

Figure 3. View from Kauffman Street, April 2021.

Figure 2. View of 700 block of Bradford Alley, courtesy of the applicant.

Page 3: 718 BRADFORD ALY - Philadelphia

718 Bradford Alley Philadelphia Historical Commission

April/May 2021

Figure 3. Front façade of subject property and proposed location of disconnect box, courtesy of the applicant.

Page 4: 718 BRADFORD ALY - Philadelphia

718 Bradford Alley Philadelphia Historical Commission

April/May 2021

Figure 4. Proposed layout of arrays, courtesy of the applicant.

Figure 5. Starr’s Row, c. 1900, Temple Universities Library.

Page 5: 718 BRADFORD ALY - Philadelphia

permit(s).

Page 1 of 2

Job Number: (for office use only)

(PERMIT TYPE PREFIX – YEAR – NUMBER)

***DO NOT MAIL THIS APPLICATION***

P_001_F

Application for Construction Permit Use this application to obtain permits for a residential or commercial construction proposal.

Mechanical / Fuel Gas, Electrical, Plumbing, and Fire Suppression trade details are found on page 2.

New Construction Addition and/or Alteration Shell (No Fit Out) – Option for Commercial Permits Only

Single-Family Two-Family Other, please describe:

Address Identify the locati on of work for the

If the activity will take place in a specific building, tenant space, floor level, or suite, note that detail in the ‘Specific Location’ field. If applicable, list PR #.

1 Parcel Address

Specific Location

2

Name Company

Address

Email Phone

I am the: Property Owner Tenant Equitable Owner Licensed Professional or Tradesperson

Property Owner Identify the deeded property

owner. If there was a recent change of ownership, documentation such as a deed or settlement sheet will be required.

3 Name

Address

professional who is legally responsible.

4

2

Name Firm

Project Scope Use this section to provide project

details; all fields are mandatory. (a) Choose the proposed occupancyof the entire building. If not one- or two-family, provide a description ofgroup(s) per code.

(b) Identify if the project will be new construction, an addition, or interior/exterior alterations.

(c) List the site area that will bedisturbed by construction, if any.Enter ‘zero’ if no disturbance.

(d) Note the new floor area created,including basements, cellars, and occupiable roofs. Where existing areas will be altered, list those areas separately.

(e) State the number of new oraffected stories.

(f) Provide a detailed description of the work proposed.

(g) Select all conditions that apply to this project (if any).

Applicant

5

(a) Occupancy

(b) Scope of Work

(d) Building Floor AreasNew Floor Area (Sq. Ft.) Existing Altered Area (Sq. Ft.)

(e) Number of Stories

Identify how you are associated with the property. Licensed professionals include design professionals, attorneys, and expediters. A tradesperson must have an active Philadelphia license for their trade or hold a PA Home Improvement Contractor Registration.

Email Phone

Design Professional in Responsible ChargeIdentify the PA- licensed design

PA License #

Email Phone

Phila. Commercial Activity License #

(f) Description of Work

(c) Earth Disturbance

Area of Earth Disturbance (Sq. Ft.)

(g) Project Conditions Project Impacts Street/Right-of-Way New High Rise Green Roof Included

Modular Construction Façade Work Initial Fit Out of Newly Constructed Space

Check box if this application is part of a project and provide project number: PR- 2 0 -

Check box if new owner is being listed

333 W Union St Allentown, PA 18102

[email protected] 4 8 4 3 5 0 6 8 2 9

718 Bradford Alley Philadelphia, PA 19147

[email protected] 9 1 7 9 6 9 2 4 1 2

Installation of rooftop solar panels onto an existing single family dwelling

718 Bradford Alley

Evan Haberman Pinnacle Exteriors

Michael Kessler

N/A

N/A

Page 6: 718 BRADFORD ALY - Philadelphia

Page 2 of 2

Job Number: (for office use only)

(PERMIT TYPE PREFIX – YEAR – NUMBER)

***DO NOT MAIL THIS APPLICATION***

P_001_F

RP or CP- 2 0 -

Building Mechanical & Fuel Gas Electrical Plumbing Fire Suppression

6

(a) Select all disciplines of workfor which permits are beingrequested. If ‘Building’ is notrequested, provide the numberof the associated permit thatwas previously issued (whereapplicable). If a Zoning Permitwas issued for this work, providethe related permit number.

(b) Identify the generalcontractor and estimated cost ofbuilding construction.

(c) Identify the mechanical contractor, estimated cost of mechanical work, equipmenttype, and quantity as:

• Number of registers/diffusers (separate new/relocated)

• Number of appliances• Number of Type I /

Type II kitchen hoodsWhere fuel gas work is included, note the estimated cost of fuel gas work.

(d) Identify the licensedelectrical contractor, estimated cost of electrical work, and a registered third-party electrical inspection agency.

(e) Identify the registered masterplumber, estimated cost of plumbing work, number offixtures, and check location ofwork as:

• Interior • Exterior Drainage and/or

Water Distribution

(f) Identify the licensed firesuppression contractor,estimated cost of firesuppression work, and numberof devices:

• Sprinkler Heads(separate new/relocated quantities)

• Standpipes• Fire Pumps• Stand-alone Backflow

Prevention Devices• Kitchen Extinguishing

Systems• Hydrants

*ROUGH-IN NOTICE: If you areseeking a rough-in permit, an application for plan review mustbe submitted already.

Name Cost of Building Work $

Project Details & Contractor Information

(a) Check all that apply:

Phone License Number

(b) General Building Construction Contractor Information

Note: Trades listed below are mandatory for all residential new construction jobs.

(c) Mechanical/Fuel Gas Work & Contractor Information

(d) Electrical Work & Contractor Information

(e) Plumbing Work & Contractor Information

(f) Fire Suppression Work & Contractor Information

Cost of Mechanical Work $

Cost of Plumbing Work $

Cost of Fire Supp. Work $

Number of Fixtures

Equipment Types:

Interior Work Exterior Building Drainage

Exterior Water Distribution; line size (in.)

Name

License Number

Name

License Number

Third-Party Inspection Agency Name

Name

License Number

Name

License Number

Declaration & Signature All provisions of the Building Code and other City ordinances will be complied with, whether specified herein or not. Plans approved by the Department form a part of this application. I hereby certify that the statements contained herein are true and correct to the best of my knowledge and belief. I further certify that I am authorized by the owner to make the foregoing application, and that, before I accept my permit for which this application is made, the owner shall be made aware of all conditions of the permit. I understand that if I knowingly make any false statements herein, I am subject to such penalties as may be prescribed by law or ordinance, inclusive of the penalties contained in 18 Pa. C.S. § 4904.

Applicant Signature:_____________________________________________________________ Date: __________ / __________ /___________________

Sprinkler Heads: Standpipes: Fire Pumps:

Phone

Phone

Phone

Phone

Cost of Electrical Work $

Provide the associated Zoning Permit number for this construction, if applicable: ZP- 2 0 -

Cost of Fuel Gas Work $

Equipment Detail & Quantities

Registers / Diffusers Appliances Hoods

Commercial Kitchen Systems: Backflow Devices: Hydrants:

6

New Installation Alteration *Rough-In

New Installation Alteration *Rough-In

New Installation Alteration *Rough-In

Check one:

Pinnacle Exteriors

4 8 4 3 5 0 6 8 2 9

900

PA-076641

3 31 21

Page 7: 718 BRADFORD ALY - Philadelphia
Page 8: 718 BRADFORD ALY - Philadelphia
Page 9: 718 BRADFORD ALY - Philadelphia
Page 10: 718 BRADFORD ALY - Philadelphia

-3

312

aw

g co

pper

free

air

20A

20A

20A

20A

20A

20A

Page 11: 718 BRADFORD ALY - Philadelphia
Page 12: 718 BRADFORD ALY - Philadelphia
Page 13: 718 BRADFORD ALY - Philadelphia

Q.Peak Duo BLK-G5 300-320

Page 14: 718 BRADFORD ALY - Philadelphia

Enphase X-IQ-AM1-240-B

Enphase IQ7+ Micro Inverter

Enphase IQ7 Micro Inverter

Page 15: 718 BRADFORD ALY - Philadelphia

Product data sheetCharacteristics

D222NRBSafety switch, general duty, fusible, 60A, 2 poles,15 hp, 120 VAC, NEMA 3R, bolt-on provision,neutral factory installed

Product availability : Stock - Normally stocked in distribution facility

Price* : 326.00 USD

MainProduct Single Throw Safety SwitchCurrent Rating 60 ACertifications UL listed file E2875Enclosure Rating NEMA 3RDisconnect Type Fusible disconnect switchFactory Installed Neutral Neutral (factory installed)Short Circuit Current Rating 100 kA maximum depending on fuse H, K or RMounting Type SurfaceNumber of Poles 2Electrical Connection LugsDuty Rating General dutyVoltage Rating 240 V ACWire Size AWG 12...AWG 3 aluminium

AWG 14...AWG 3 copper

ComplementaryMaximum Horse Power Rating 1.5 hp 120 V AC 60 Hz 1 phase NEC 240.6

3 hp 120 V AC 60 Hz 3 phase NEC 430.523 hp 240 V AC 60 Hz 1 phase NEC 240.67.5 hp 240 V AC 60 Hz 3 phase NEC 240.610 hp 240 V AC 60 Hz 1 phase NEC 430.5215 hp 240 V AC 60 Hz 3 phase NEC 430.52

Tightening torque 35 lbf.in (3.95 N.m) 0.00…0.01 in² (2.08…5.26 mm²) AWG 14...AWG 10)35 lbf.in (3.95 N.m) AWG 14...AWG 10)45 lbf.in (5.08 N.m) 0.01 in² (8.37 mm²) AWG 8)45 lbf.in (5.08 N.m) 0.02…0.03 in² (12.3…21.12 mm²) AWG 6...AWG 4)50 lbf.in (5.65 N.m) 0.04 in² (26.67 mm²) AWG 3)

Dis

clai

mer

: Thi

s do

cum

enta

tion

is n

ot in

tend

ed a

s a

subs

titut

e fo

r and

is n

ot to

be

used

for d

eter

min

ing

suita

bilit

y or

relia

bilit

y of

thes

e pr

oduc

ts fo

r spe

cific

use

r app

licat

ions

*  Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Feb 23, 2021

1

Page 16: 718 BRADFORD ALY - Philadelphia

Height 14.88 in (377.95 mm)Maximum Width 7.45 in (189.23 mm)Maximum Depth 4.87 in (123.70 mm)

Ordering and shipping detailsCategory 00106 - D & DU SW,NEMA3R, 30-200ADiscount Schedule DE1AGTIN 00785901460640Nbr. of units in pkg. 1Package weight(Lbs) 8.25 lb(US) (3.74 kg)Returnability YesCountry of origin US

Packing UnitsUnit Type of Package 1 PCEPackage 1 Height 5.20 in (13.208 cm)Package 1 width 7.70 in (19.558 cm)Package 1 Length 16.20 in (41.148 cm)Unit Type of Package 2 PALNumber of Units in Package 2 120Package 2 Weight 1022.00 lb(US) (463.571 kg)Package 2 Height 45.00 in (114.3 cm)Package 2 width 40.00 in (101.6 cm)Package 2 Length 48.00 in (121.92 cm)

Offer SustainabilitySustainable offer status Green Premium productCalifornia proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which

is known to the State of California to cause cancer and birth defects or other reproductive harm. Formore information go to www.P65Warnings.ca.gov

REACh Regulation REACh DeclarationREACh free of SVHC YesEU RoHS Directive Compliant

EU RoHS DeclarationMercury free YesRoHS exemption information YesChina RoHS Regulation China RoHS declaration

Product out of China RoHS scope. Substance declaration for your information.Environmental Disclosure Product Environmental ProfilePVC free Yes

Contractual warrantyWarranty 18 months

2

Page 17: 718 BRADFORD ALY - Philadelphia

Product data sheetDimensions Drawings

D222NRB

Approximate Dimensions

3

Page 18: 718 BRADFORD ALY - Philadelphia

Product data sheetConnections and Schema

D222NRB

Connections and Wiring Diagrams

4

Page 19: 718 BRADFORD ALY - Philadelphia
Page 20: 718 BRADFORD ALY - Philadelphia
Page 21: 718 BRADFORD ALY - Philadelphia