1MRK 580 152-BEN
������� ����
Page 1
Revision: -Issued: November 2002Data subject to change without notice
������ • Part of the apparatus control function
• Handling of bay-oriented functions
- reservation
- operator place selection
- supervision of select relays
����� ���� The complete apparatus control function han-dles open and close commands of high volt-age apparatuses and their status indications in a bay. Permission to operate is granted after that several conditions are evaluated, such as interlocking status, synchro-check, operator mode or other external conditions.
The purpose of this function block BAYCON is to handle bay-oriented functions such as reservation, operator place selection, and supervision of select relays. The reservation function is primarily used to transfer inter-locking information between bays in a safe way and to prevent double operation in a bay, switchgear, or complete substation.
������ The apparatus control function consists of totally four main types of standardized func-tion blocks BAYCON, COMCON, SWICON and BLKCON, all to be configured to reflect the switchyard arrangement. The number and type of blocks used in the terminal depends on the number and type of apparatuses to control.
This main type BAYCON is used one per bay and is available in four variants:
BAYCONA: The normal variant to be used.
BAYCONB: The same as A, but used when more than eight apparatuses are included in one bay.
BAYCONE: Is used when external selection relays with individual feedback signals are used.
BAYCONF: The same as E, but used when more than eight apparatuses are included in one bay.
������� ���� ������1MRK 580 152-BEN
Page 2
��� ������� �
xx00000596.vsd
BA01-�������
S_RS_SL_LRQ_SEL1RQ_SEL2RQ_SEL3RQ_SEL4RQ_SEL5RQ_SEL6RQ_SEL7RQ_SEL8BLK_REOVERRIDERE_B1RE_B2RE_B3RE_B4RE_B5RE_B6RE_B7RE_B8ACK_F_BANY_ACKV_TXEX_DA_UPRE_RQ_BV_RE_RQT_CAN_RE
REMOTESTATION
LOCALSEL1SEL2SEL3SEL4SEL5SEL6SEL7SEL8
RERE_BAYSACK_T_B
AU_OP_V1AU_OP_V2AU_OP_V3AU_OP_V4AU_OP_V5AU_OP_V6AU_OP_V7AU_OP_V8
xx00000602.vsd
BB01-�������
S_RS_SL_LEXCH_INRQ_SEL1RQ_SEL2RQ_SEL3RQ_SEL4RQ_SEL5RQ_SEL6RQ_SEL7RQ_SEL8BLK_REOVERRIDERE_B1RE_B2RE_B3RE_B4RE_B5RE_B6RE_B7RE_B8ACK_F_BANY_ACKV_TXEX_DA_UPRE_RQ_BV_RE_RQT_CAN_RE
REMOTESTATION
LOCALEXCH_OUT
SEL1SEL2SEL3SEL4SEL5SEL6SEL7SEL8
RERE_BAYSACK_T_B
AU_OP_V1AU_OP_V2AU_OP_V3AU_OP_V4AU_OP_V5AU_OP_V6AU_OP_V7AU_OP_V8
xx00000603.vsd
BE01-�������
S_RS_SL_LRQ_SEL1RQ_SEL2RQ_SEL3RQ_SEL4RQ_SEL5RQ_SEL6RQ_SEL7RQ_SEL8BLK_REOVERRIDERE_B1RE_B2RE_B3RE_B4RE_B5RE_B6RE_B7RE_B8ACK_F_BANY_ACKV_TXEX_DA_UPRE_RQ_BV_RE_RQSEL_ACT1SEL_ACT2SEL_ACT3SEL_ACT4SEL_ACT5SEL_ACT6SEL_ACT7SEL_ACT8SEL_CH1SEL_CH2INPBOERROUTBOERRSEL_FDB1SEL_FDB2SEL_FDB3SEL_FDB4SEL_FDB5SEL_FDB6SEL_FDB7SEL_FDB8T_CAN_RE
REMOTESTATION
LOCALSEL1SEL2SEL3SEL4SEL5SEL6SEL7SEL8
RERE_BAYSACK_T_B
FDB_SEL1FDB_SEL2FDB_SEL3FDB_SEL4FDB_SEL5FDB_SEL6FDB_SEL7FDB_SEL8
BINPERRBOUTERRBRLYERR
AU_OP_V1AU_OP_V2AU_OP_V3AU_OP_V4AU_OP_V5AU_OP_V6AU_OP_V7AU_OP_V8
������� ���� ������1MRK 580 152-BEN
Page 3
���������������������
�������� ��������������������������� ����!"���� ������� �
xx00000595.vsd
BF01-�������
S_RS_SL_LEXCH_INRQ_SEL1RQ_SEL2RQ_SEL3RQ_SEL4RQ_SEL5RQ_SEL6RQ_SEL7RQ_SEL8BLK_REOVERRIDERE_B1RE_B2RE_B3RE_B4RE_B5RE_B6RE_B7RE_B8ACK_F_BANY_ACKV_TXEX_DA_UPRE_RQ_BV_RE_RQSEL_ACT1SEL_ACT2SEL_ACT3SEL_ACT4SEL_ACT5SEL_ACT6SEL_ACT7SEL_ACT8SEL_CH1SEL_CH2INPBOERROUTBOERRSEL_FDB1SEL_FDB2SEL_FDB3SEL_FDB4SEL_FDB5SEL_FDB6SEL_FDB7SEL_FDB8T_CAN_RE
REMOTESTATION
LOCALEXCH_OUT
SEL1SEL2SEL3SEL4SEL5SEL6SEL7SEL8
RERE_BAYSACK_T_B
FDB_SEL1FDB_SEL2FDB_SEL3FDB_SEL4FDB_SEL5FDB_SEL6FDB_SEL7FDB_SEL8
BINPERRBOUTERRBRLYERR
AU_OP_V1AU_OP_V2AU_OP_V3AU_OP_V4AU_OP_V5AU_OP_V6AU_OP_V7AU_OP_V8
#����� ��� �����
S_R Input to change operator place to remote (pulse input)
S_S Input to change operator place to Station (pulse input)
L_L Input to change operator place to Local
RQ_SEL1 Request for selection and reservation of apparatus 1
RQ_SEL2 Request for selection and reservation of apparatus 2
RQ_SEL3 Request for selection and reservation of apparatus 3
RQ_SEL4 Request for selection and reservation of apparatus 4
RQ_SEL5 Request for selection and reservation of apparatus 5
RQ_SEL6 Request for selection and reservation of apparatus 6
RQ_SEL7 Request for selection and reservation of apparatus 7
RQ_SEL8 Request for selection and reservation of apparatus 8
BLK_RE Input for blocking all reservations
������� ���� ������1MRK 580 152-BEN
Page 4
������$� ��������������������������� ����!"���� ������� ��
OVERRIDE Overriding reservation function including blocking by
BLK_RE
RE_B1 Reservation of the own bay only (i.e. not other bays) at selection from apparatus 1
RE_B2 Reservation of the own bay only (i.e. not other bays) at
selection from apparatus 2
RE_B3 Reservation of the own bay only (i.e. not other bays) at selection from apparatus 3
RE_B4 Reservation of the own bay only (i.e. not other bays) at selection from apparatus 4
RE_B5 Reservation of the own bay only (i.e. not other bays) at
selection from apparatus 5
RE_B6 Reservation of the own bay only (i.e. not other bays) at selection from apparatus 6
RE_B7 Reservation of the own bay only (i.e. not other bays) at selection from apparatus 7
RE_B8 Reservation of the own bay only (i.e. not other bays) at
selection from apparatus 8
ACK_F_B Input for acknowledging reservation of other bays
ANY_ACK Input indicating that at least one acknowledge is still active
V_TX Indication for valid transmission of reservation signals
EX_DA_UP Supervision of the program that acknowledged the reserva-tion is running
RE_RQ_B Request for reservation from other bays
V_RE_RQ Input is 1 for valid request of reservation from any bay
T_CAN_RE Time-out when the reset of the reservation acknowledge-ment is not done by the requesting bays, for example,
because of communication error.
#����� ��� �����
REMOTE Indication of Remote operator place
STATION Indication of Station operator place
LOCAL Indication of Local operator place
SEL1 Apparatus 1 is selected after reservation acknowledgement from other bays
SEL3 Apparatus 3 is selected after reservation acknowledgement
from other bays
SEL4 Apparatus 4 is selected after reservation acknowledgement from other bays
SEL5 Apparatus 5 is selected after reservation acknowledgement from other bays
SEL6 Apparatus 6 is selected after reservation acknowledgement
from other bays
#����� ��� �����
������� ���� ������1MRK 580 152-BEN
Page 5
������%� ��������������������������� ����!"���� ������� ��
SEL7 Apparatus 7 is selected after reservation acknowledgement
from other bays
SEL8 Apparatus 8 is selected after reservation acknowledgement from other bays
SEL2 Apparatus 2 is selected after reservation acknowledgement
from other bays
RE A reservation has been made in this bay
RE_BAYS Request for reservation of other bays
ACK_T_B Acknowledge to other bays that this bay is reserved
AU_OP_V1 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 1
AU_OP_V2 Automatic operation permitted, i.e. the operator place selec-
tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 2
AU_OP_V3 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or
not manual selected for apparatus 3
AU_OP_V4 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 4
AU_OP_V5 Automatic operation permitted, i.e. the operator place selec-
tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 5
AU_OP_V6 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or
not manual selected for apparatus 6
AU_OP_V7 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 7
AU_OP_V8 Automatic operation permitted, i.e. the operator place selec-
tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 8
#����� ��� �����
S_R Input to change operator place to Remote (pulse input)
S_S Input to change operator place to Station (pulse input)
L_L Input to change operator place to Local
EXCH_IN Input for information exchange with other BAYCONs in bays
with more than 8 apparatuses
RQ_SEL1 Request for selection and reservation of apparatus 1
RQ_SEL2 Request for selection and reservation of apparatus 2
RQ_SEL3 Request for selection and reservation of apparatus 3
RQ_SEL4 Request for selection and reservation of apparatus 4
#����� ��� �����
������� ���� ������1MRK 580 152-BEN
Page 6
������&� ��������������������������� ����!"���� ������� �
RQ_SEL5 Request for selection and reservation of apparatus 5
RQ_SEL6 Request for selection and reservation of apparatus 6
RQ_SEL7 Request for selection and reservation of apparatus 7
RQ_SEL8 Request for selection and reservation of apparatus 8
OVERRIDE Overriding reservation function including blocking by BLK_RE
BLK_RE Input for blocking all reservations
RE_B1 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 1
RE_B2 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 2
RE_B3 Reservation of the own bay only (i.e. not other bays) at selec-
tion from apparatus 3
RE_B4 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 4
RE_B5 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 5
RE_B6 Reservation of the own bay only (i.e. not other bays) at selec-
tion from apparatus 6
RE_B7 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 7
RE_B8 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 8
ACK_F_B Input for acknowledging reservation of other bays
ANY_ACK Input indicating that an acknowledge is still active
V_TX Indication for valid transmission of reservation signals
EX_DA_UP Supervision of the program that acknowledged the reserva-
tion is running
RE_RQ_B Request for reservation from other bays
V_RE_RQ Input is 1 for valid request of reservation from any bay
T_CAN_RE Time-out when the reset of the reservation acknowledgement is not done by the requesting bays, for example, because of communication error.
#����� ��� �����
REMOTE Indication of Remote operator place
STATION Indication of Station operator place
LOCAL Indication of Local operator place
EXCH_OUT Output for information exchange with other BAYCONs in bays with more than 8 apparatuses
SEL1 Apparatus 1 is selected after reservation acknowledgement from other bays
SEL2 Apparatus 2 is selected after reservation acknowledgement
from other bays
#����� ��� �����
������� ���� ������1MRK 580 152-BEN
Page 7
SEL3 Apparatus 3 is selected after reservation acknowledgement
from other bays
SEL4 Apparatus 4 is selected after reservation acknowledgement from other bays
SEL5 Apparatus 5 is selected after reservation acknowledgement
from other bays
SEL6 Apparatus 6 is selected after reservation acknowledgement from other bays
SEL7 Apparatus 7 is selected after reservation acknowledgement from other bays
SEL8 Apparatus 8 is selected after reservation acknowledgement
from other bays
RE A reservation has been made in this bay
RE_BAYS Request for reservation of other bays
ACK_T_B Acknowledge to other bays that this bay is reserved
AU_OP_V1 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 1
AU_OP_V2 Automatic operation permitted, i.e. the operator place selec-
tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 2
AU_OP_V3 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or
not manual selected for apparatus 3
AU_OP_V4 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 4
AU_OP_V5 Automatic operation permitted, i.e. the operator place selec-
tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 5
AU_OP_V6 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or
not manual selected for apparatus 6
AU_OP_V7 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 7
AU_OP_V8 Automatic operation permitted, i.e. the operator place selec-
tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 8
#����� ��� �����
������� ���� ������1MRK 580 152-BEN
Page 8
������'� �������������������������(� �(��!"���� ������� �#����� ��� �����
S_R Input to change operator place to Remote (pulse input)
S_S Input to change operator place to Station (pulse input)
L_L Input to change operator place to Local
RQ_SEL1 Request for selection and reservation of apparatus 1
RQ_SEL2 Request for selection and reservation of apparatus 2
RQ_SEL3 Request for selection and reservation of apparatus 3
RQ_SEL4 Request for selection and reservation of apparatus 4
RQ_SEL5 Request for selection and reservation of apparatus 5
RQ_SEL6 Request for selection and reservation of apparatus 6
RQ_SEL7 Request for selection and reservation of apparatus 7
RQ_SEL8 Request for selection and reservation of apparatus 8
BLK_RE Input for blocking all reservations
OVERRIDE Input for overriding the reservation function including the blocking by BLK_RE
RE_B1 Reservation of the own bay only (i.e. not other bays) at selec-
tion from apparatus 1
RE_B2 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 2
RE_B3 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 3
RE_B4 Reservation of the own bay only (i.e. not other bays) at selec-
tion from apparatus 4
RE_B5 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 5
RE_B6 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 6
RE_B7 Reservation of the own bay only (i.e. not other bays) at selec-
tion from apparatus 7
RE_B8 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 8
ACK_F_B Input for acknowledging the reservation of other bays
ANY_ACK Input indicating that at least one acknowledge is still active
V_TX Indication for valid transmission of the reservation signals
EX_DA_UP Supervision of the program that acknowledged the reserva-tion is running
RE_RQ_B Request for reservation from other bays
V_RE_RQ Input is 1 for valid request of reservation from any bay
SEL_ACT1 Selection of apparatus 1 is activated by the program and the
selection relay should be energised
SEL_ACT2 Selection of apparatus 2 is activated by the program and the selection relay should be energised
SEL_ACT3 Selection of apparatus 3 is activated by the program and the selection relay should be energised
������� ���� ������1MRK 580 152-BEN
Page 9
������)� �������������������������(� �(��!"���� ������� �
SEL_ACT4 Selection of apparatus 4 is activated by the program and the
selection relay should be energised
SEL_ACT5 Selection of apparatus 5 is activated by the program and the selection relay should be energised
SEL_ACT6 Selection of apparatus 6 is activated by the program and the
selection relay should be energised
SEL_ACT7 Selection of apparatus 7 is activated by the program and the selection relay should be energised
SEL_ACT8 Selection of apparatus 8 is activated by the program and the selection relay should be energised
SEL_CH1 Indication that no selection or execution relay is energised
INPBOERR Input for binary input board error
OUTBOERR Input for binary output board error
SEL_FDB1 Input for individual selection relay energising of apparatus 1
SEL_FDB2 Input for individual selection relay energising of apparatus 2
SEL_FDB3 Input for individual selection relay energising of apparatus 3
SEL_FDB4 Input for individual selection relay energising of apparatus 4
SEL_FDB5 Input for individual selection relay energising of apparatus 5
SEL_FDB6 Input for individual selection relay energising of apparatus 6
SEL_FDB7 Input for individual selection relay energising of apparatus 7
SEL_FDB8 Input for individual selection relay energising of apparatus 8
T_CAN_RE Time-out when the reset of the reservation acknowledgement
is not done by the requesting bays, for example, because of communication error.
#����� ��� �����
REMOTE Indication of Remote operator place
STATION Indication of Station operator place
LOCAL Indication of Local operator place
SEL1 Apparatus 1 is selected after reservation acknowledgement
from other bays
SEL2 Apparatus 2 is selected after reservation acknowledgement from other bays
SEL3 Apparatus 3 is selected after reservation acknowledgement from other bays
SEL4 Apparatus 4 is selected after reservation acknowledgement
from other bays
SEL5 Apparatus 5 is selected after reservation acknowledgement from other bays
SEL6 Apparatus 6 is selected after reservation acknowledgement from other bays
SEL7 Apparatus 7 is selected after reservation acknowledgement
from other bays
#����� ��� �����
������� ���� ������1MRK 580 152-BEN
Page 10
SEL8 Apparatus 8 is selected after reservation acknowledgement
from other bays
RE A reservation has been made in this bay
RE_BAYS Request for reservation of other bays
ACK_T_B Acknowledgement to other bays that this bay is reserved
FDB_SEL1 Correct selection relay is energised for apparatus 1
FDB_SEL2 Correct selection relay is energised for apparatus 2
FDB_SEL3 Correct selection relay is energised for apparatus 3
FDB_SEL4 Correct selection relay is energised for apparatus 4
FDB_SEL5 Correct selection relay is energised for apparatus 5
FDB_SEL6 Correct selection relay is energised for apparatus 6
FDB_SEL7 Correct selection relay is energised for apparatus 7
FDB_SEL8 Correct selection relay is energised for apparatus 8
BINPERR Indication for binary input board error
BOUTERR Indication for binary output board error
BRLYERR Indication for external relay error
AU_OP_V1 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or
not manual selected for apparatus 1
AU_OP_V2 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 2
AU_OP_V3 Automatic operation permitted, i.e. the operator place selec-
tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 3
AU_OP_V4 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or
not manual selected for apparatus 4
AU_OP_V5 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 5
AU_OP_V6 Automatic operation permitted, i.e. the operator place selec-
tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 6
AU_OP_V7 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or
not manual selected for apparatus 7
AU_OP_V8 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 8
#����� ��� �����
������� ���� ������1MRK 580 152-BEN
Page 11
������*� ��������������������������� ����!"���� ������� �#����� ��� �����
S_R Input to change operator place to Remote (pulse input)
S_S Input to change operator place to Station (pulse input)
L_L Input to change operator place to Local
EXCH_IN Input for information exchange with other BAYCONs in bays with more than 8 apparatuses
RQ_SEL1 Request for selection and reservation of apparatus 1
RQ_SEL2 Request for selection and reservation of apparatus 2
RQ_SEL3 Request for selection and reservation of apparatus 3
RQ_SEL4 Request for selection and reservation of apparatus 4
RQ_SEL5 Request for selection and reservation of apparatus 5
RQ_SEL6 Request for selection and reservation of apparatus 6
RQ_SEL7 Request for selection and reservation of apparatus 7
RQ_SEL8 Request for selection and reservation of apparatus 8
BLK_RE Input for blocking all reservations
OVERRIDE Input for overriding the reservation function including the
blocking by BLK_RE
RE_B1 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 1
RE_B2 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 2
RE_B3 Reservation of the own bay only (i.e. not other bays) at selec-
tion from apparatus 3
RE_B4 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 4
RE_B5 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 5
RE_B6 Reservation of the own bay only (i.e. not other bays) at selec-
tion from apparatus 6
RE_B7 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 7
RE_B8 Reservation of the own bay only (i.e. not other bays) at selec-tion from apparatus 8
ACK_F_B Input for acknowledging the reservation of other bays
ANY_ACK Input indicating that at least one acknowledge is still active
V_TX Indication for valid transmission of the reservation signals
EX_DA_UP Supervision of the program that acknowledged the reserva-
tion is running
RE_RQ_B Request for reservation from other bays
V_RE_RQ Input is 1 for valid request of reservation from any bay
SEL_ACT1 Selection of apparatus 1 is activated by the program and the selection relay should be energised
SEL_ACT2 Selection of apparatus 2 is activated by the program and the selection relay should be energised
������� ���� ������1MRK 580 152-BEN
Page 12
������+� ��������������������������� ����!"���� ������� ��
SEL_ACT3 Selection of apparatus 3 is activated by the program and the
selection relay should be energised
SEL_ACT4 Selection of apparatus 4 is activated by the program and the selection relay should be energised
SEL_ACT5 Selection of apparatus 5 is activated by the program and the
selection relay should be energised
SEL_ACT6 Selection of apparatus 6 is activated by the program and the selection relay should be energised
SEL_ACT7 Selection of apparatus 7 is activated by the program and the selection relay should be energised
SEL_ACT8 Selection of apparatus 8 is activated by the program and the
selection relay should be energised
SEL_CH1 Indication that no selection or execution relay is energised
SEL_CH2 Indication that at least one selection or execution relay is energised
INPBOERR Input for binary input board error
OUTBOERR Input for binary output board error
SEL_FDB1 Input for individual selection relay energising of apparatus 1
SEL_FDB2 Input for individual selection relay energising of apparatus 2
SEL_FDB3 Input for individual selection relay energising of apparatus 3
SEL_FDB4 Input for individual selection relay energising of apparatus 4
SEL_FDB5 Input for individual selection relay energising of apparatus 5
SEL_FDB6 Input for individual selection relay energising of apparatus 6
SEL_FDB7 Input for individual selection relay energising of apparatus 7
SEL_FDB8 Input for individual selection relay energising of apparatus 8
T_CAN_RE Time-out when the reset of the reservation acknowledgement is not done by the requesting bays, for example, because of
communication error.
#����� ��� �����
REMOTE Indication of Remote operator place
STATION Indication of Station operator place
LOCAL Indication of Local operator place
EXCH_OUT Output for information exchange with other BAYCONs in bays with more than 8 apparatuses
SEL1 Apparatus 1 is selected after reservation acknowledgement
from other bays
SEL2 Apparatus 2 is selected after reservation acknowledgement from other bays
SEL3 Apparatus 3 is selected after reservation acknowledgement from other bays
SEL4 Apparatus 4 is selected after reservation acknowledgement
from other bays
#����� ��� �����
������� ���� ������1MRK 580 152-BEN
Page 13
SEL5 Apparatus 5 is selected after reservation acknowledgement
from other bays
SEL6 Apparatus 6 is selected after reservation acknowledgement from other bays
SEL7 Apparatus 7 is selected after reservation acknowledgement
from other bays
SEL8 Apparatus 8 is selected after reservation acknowledgement from other bays
RE A reservation has been made in this bay
RE_BAYS Request for reservation of other bays
ACK_T_B Acknowledgement to other bays that this bay is reserved
FDB_SEL1 Correct selection relay is energised for apparatus 1
FDB_SEL2 Correct selection relay is energised for apparatus 2
FDB_SEL3 Correct selection relay is energised for apparatus 3
FDB_SEL4 Correct selection relay is energised for apparatus 4
FDB_SEL5 Correct selection relay is energised for apparatus 5
FDB_SEL6 Correct selection relay is energised for apparatus 6
FDB_SEL7 Correct selection relay is energised for apparatus 7
FDB_SEL8 Correct selection relay is energised for apparatus 8
BINPERR Indication for binary input board error
BOUTERR Indication for binary output board error
BRLYERR Indication for external relay error
AU_OP_V1 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or
not manual selected for apparatus 1
AU_OP_V2 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 2
AU_OP_V3 Automatic operation permitted, i.e. the operator place selec-
tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 3
AU_OP_V4 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or
not manual selected for apparatus 4
AU_OP_V5 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 5
#����� ��� �����
������� ���� ������1MRK 580 152-BEN
Page 14
,����� ��
AU_OP_V6 Automatic operation permitted, i.e. the operator place selec-
tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 6
AU_OP_V7 Automatic operation permitted, i.e. the operator place selec-
tor is not in Local position, the apparatus is not reserved or not manual selected for apparatus 7
AU_OP_V8 Automatic operation permitted, i.e. the operator place selec-tor is not in Local position, the apparatus is not reserved or
not manual selected for apparatus 8
#����� ��� �����
�������-������� ������.�/��� ����