abb swbd vd4 brochure.pdf

6
Power IT MV Air Insulated Switchgear, Model Unisafe MV Indoor Vacuum Circuit Breaker, Model VD4

Upload: anandgirgaonkar

Post on 02-Dec-2015

209 views

Category:

Documents


7 download

DESCRIPTION

VD4 breaker

TRANSCRIPT

Page 1: ABB SWBD VD4 Brochure.pdf

PowerIT

MV Air Insulated Switchgear, Model Unisafe

MV Indoor Vacuum Circuit Breaker, Model VD4

Page 2: ABB SWBD VD4 Brochure.pdf

Site installation of Unisafe panel

ABB - a global leader in powerand automation technologies

ABB (www.abb.com) is a global leader in power andautomation technologies that enable utility andindustry customers to improve performance whilelowering environmental impact. The ABB Group ofcompanies operates in around 100 countries.

ABB’s Power Technologies Division serves electric,gas and water utilities, as well as industrial andcommercial customers with a wide range of products,services and solutions for power transmission anddistribution. ABB offers turnkey solutions forsubstations, utility automation, HVDC and FACTS(Flexible AC Transmission System).

ABB’s power technologies product portfolio includesoutdoor and indoor circuit breakers, gas insulatedswitchgear, power transformers, instrumenttransformers, disconnectors, capacitor banks andreactive power compensators.

ABB’s medium voltage product offering encompassesa complete range of innovative products, systemsand technologies for applications in the 1 to 50 kVclass. This includes indoor air insulated and gasinsulated panels with vacuum and SF6 gas circuitbreakers, outdoor vacuum and SF6 gas circuitbreakers, ring main units, auto-reclosers, fuses,switch disconnectors and prefabricated modularsolutions for power distribution. Industrial IT

The Unisafe panel andVD4 circuit breaker arecertified as complyingwith the ABBIndustrialIT architecture.In this architecture theUnisafe panel and VD4 circuit breaker are part ofthe PowerIT suite. The products complying with theIndustrialIT architecture can be effectivelyintegrated in a system with high added value and atrue ‘Plug & Produce’ mode.

This product has been tested and certified asIndustrialIT Enabled, Level 0 - Information.All product information is supplied in interactiveelectronic format, compatible with ABB AspectObjectTM technology. The IndustrialIT commitmentfrom ABB ensures that every enterprise buildingblock is equipped with the integral tools necessaryto install, operate, and maintain efficientlythroughout the product lifecycle.

Further information about the advantages ofABB IndustrialIT architecture is available atwww.abb.com/industrialit.

Salient Features - Unisafe Cubicle

n Metal clad construction - all compartmentsare segregated from each other with metalsheets

n IP4X degree of protection externally & IP5Xavailable as an option

n Internal arc tested

n Independent exhaust vents for all HTcompartments

n Internal earthing switch (optional)

n The normal service performances areguaranteed under the following conditions:– Min. Ambient Temp.: -50C– Max. Ambient Temp.: -400C– Max. Rel. Humidity: 95%

n Small width panel - 600mm up to 1250Abusbar rating

n Insulation level of 95kVp available on request

n Option of REF 542+, composite unit forprotection, measurement, control, signalling,interlock, automation and communication

Page 3: ABB SWBD VD4 Brochure.pdf

Air insulated indoor switchgear cubicle type UnisafeThe Unisafe cubicle is designed and type tested to meet requirements of IEC 60694 / IS:3427.

Breaker compartment

n Test position of circuit breakerbehind closed door

n Racking in/out of breaker from‘test’ to ‘service’ position andvice-versa with cubicle doorclosed

n Mechanical interlock to preventracking in/out of breaker, whenbreaker is in closed position

n Live parts covered by automaticmetallic shutters when breakeris racked out

Metering compartment

n Metering compartment withnumerical / static /electromagnetic relays,indicating meters, lamps andcontrol switches

n Protection and measuringapparatus customised as perrequirement

Cable and CTcompartment

n Spacious compartment toaccommodate 1 set of CTs and2 runs of cable

n Option of rear extension toaccommodate extra CTs orcables

n Adequate height for cabletermination

Busbar compartment

n Spacious busbar compartmentfor adequate air clearances

n Option for busbar insulationavailable

n Option for shroud on jointsavailable

PT compartment

n Withdrawable line PT providedin the breaker panel

n Removable fuses mounted onthe PT

n Safety shutters between PT andcable compartment closeautomatically on PT withdrawal

Page 4: ABB SWBD VD4 Brochure.pdf

General arrangement drawing

Technical details

Description Unit Rating

Rated Voltage kV 12

Rated Frequency Hz 50

Rated Busbar Current A up to 2000

Short time withstand current (3 sec) kA 26.3kAp 66

Insulation levels kVrms/kVp 28/75*

Width x Depth x Heightup to 1250A mm 600 x 1550 x 2500above 1250A mm 750 x 1550 x 2500

Weight with circuit breaker (approx) Kg 1000

Degree of protectionEnclosure – IP4XBetween the compartments – IP2X

*95 kVp on request

VD4 BREAKER

Dimensions in mm

Page 5: ABB SWBD VD4 Brochure.pdf

Quality assurance

All of ABB’s manufacturing facilities in India are ISO 9001certified which reflects ABB’s commitment to quality.ABB is equally committed to environmental sustainability.The Nashik facility is certified under ISO 14001.

Indoor switchgear – vacuum circuit breaker type VD4The VD4 type circuit breaker is designed and tested to meet requirements of IEC - 62271-100 / IS: 13118.

n Vacuum used as insulation and arc interruptionmedium

n Operationally safe and reliable in a wide rangeof ambient temperatures (-)50 to 400C

n Capable of interrupting small magnetising andcapacitive currents

Salient features

n Features of operating mechanism:

– O-C-O operation without recharging

– Closing spring charged by motor in less than15 seconds

– Electrical anti-pumping

– Provision for manual charging

– Synchronisation and fast auto reclosure duty

Description Unit Rating

Type VD4 12.06.13E 12.12.25 12.16.25 12.20.25

Rated Voltage kV 12

Insulation Levels kVrms/kVp 28/75

Normal Current(400C amb.) A 800 1250 1600 2000

Breaking Capacity kA 13.1 26.3 26.3 26.3

Making Capacity kAp 33 66 66 66

Short time withstand current kA(3sec) 13.1 26.3 26.3 26.3

Opening time ms 55 (max)

Arcing time ms 15 (max)

Total Break time ms 70 (max)

Making time ms 75 (max)

Operating Sequence – 0 - 3min - CO - 3min - CO/0 - 0.3sec - CO - 3min - CO

Weight (approx.) Kg 110 110 120 250

Technical details

Page 6: ABB SWBD VD4 Brochure.pdf

Data and illustration without engagement. We reserve the right to make changes in the course of technical development.

Dimensional drawing of VD4 (up to 1600 A)

Dimensional drawing of VD4 (up to 2000 A)

1VD

S22

004-

YN03

/200

4/10

00

abbMedium Voltage EquipmentStreet No. 17MIDC, SatpurNashik 422 007Tel: +91 253-2351095 – 98Fax: +91 253-2350644

Exports Marketing Office:ManejaVadodara 390 013Tel: +91 265-2638930Fax: +91 265-2638908Email: [email protected]

Regional Marketing Offices:

NBCC Tower4th FloorNo. 15, Bhikaji Cama PlaceNew Delhi 110 066Tel: +91 11 26186000Fax: +91 11 26197592/84035

4th FloorNo. 9Elgin RoadKolkata 700 020Tel: +91 33 22832911/906Fax: +91 33 22832990

ABB HouseDr. S B PathBallard EstateMumbai 400 038Tel: +91 22 56318231 – 39Fax: +91 22 56318276/77

Sona Towers4th Floor71, Millers RoadBangalore 560 052Tel: +91 80 22949815-24Fax: +91 80 22949825-26

Century PlazaNo. 3C, 3D, 3F, 3rd Floor561 / 562, Anna SalaiTeynampetChennai 600 018Tel: +91 44 24340201/203Fax: +91 44 24340282

Vandana House1st FloorG E Road, RamkundRaipur 492 001Tel: +91 771 5060816-8Fax: +91 771 5023051

www.abb.com/in

North East West SouthCentral

210

588636

310

280

865

210

680

FRONT

VD4ABB

Front View Side View

Front View Side View

Dimensions in mm

Dimensions in mm