airoil ratio mb

7
_03_AirOil_Ratio_MB - Ladder Diagram Page 1 PP_D1_D1C:MainTask:MainProgram 2/1/2012 7:47:33 AM Total number of rungs in routine: 40 ...ant\CCP\Logics\Under Development\Dryer#1\D1C 120111_SIM.ACD RSLogix 5000 Previous Logics 0 NOP Previous Logics 1 Scaling function to Ladder Scaling MBDF_To_Fuel ... Input01 FIC221052.PID.OUT  34.0 MaxRaw01 100  MinRaw01 0  MaxEu01 MB_Heat_Max  24000000.0 MinEu01 0  Output01 MBDF_to_Heat  8160000.0 Scaling Scaling function to Ladder 2 / MB_CoalSP_Tmr.DN EN DN Timer On Delay Timer MB_CoalSP_Tmr Preset 3000 Accum 2771 TON 3 Limit Test (CIRC) Low Limit 0  Test MB_CoalPrcnt_HMI  0 High Limit 80  LIM Greater Than (A>B) Source A MB_CoalPrcnt_HMI  0 Source B MB_CoalPrcnt_SP  0 GRT MB_CoalSP_Tmr.DN Add Source A MB_CoalPrcnt_SP  0 Source B 1  Dest MB_CoalPrcnt_SP  0 ADD 4 Less Than (A<B) Source A MB_CoalPrcnt_HMI  0 Source B MB_CoalPrcnt_SP  0 LES MB_CoalSP_Tmr.DN Subtract Source A MB_CoalPrcnt_SP  0 Source B 1  Dest MB_CoalPrcnt_SP  0 SUB

Upload: munzii

Post on 06-Apr-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AirOil Ratio MB

8/2/2019 AirOil Ratio MB

http://slidepdf.com/reader/full/airoil-ratio-mb 1/6

_AirOil_Ratio_MB - Ladder Diagram Page 1D1_D1C:MainTask:MainProgram 2/1/2012 7:47:33 AMal number of rungs in routine: 40 ...ant\CCP\Logics\Under Development\Dryer#1\D1C_120111_SIM.ACD

RSLogix 5000

Previous Logics

NOP

Previous Logics

Scaling function to LadderScaling MBDF_To_Fuel ...Input01 FIC221052.PID.OUT  34.0MaxRaw01 100 MinRaw01 0 MaxEu01 MB_Heat_Max  24000000.0MinEu01 0 Output01 MBDF_to_Heat  8160000.0

Scaling

Scaling function toLadder

/ MB_CoalSP_Tmr.DN

EN

DN

Timer On DelayTimer MB_CoalSP_TmrPreset 3000Accum 2771

TON

Limit Test (CIRC)Low Limit 0 

Test MB_CoalPrcnt_HMI  0High Limit 80 

LIMGreater Than (A>B)Source A MB_CoalPrcnt_HMI  0

Source B MB_CoalPrcnt_SP  0

GRT MB_CoalSP_Tmr.DN

AddSource A MB_CoalPrcnt_SP  0Source B 1 Dest MB_CoalPrcnt_SP  0

ADD

Less Than (A<B)Source A MB_CoalPrcnt_HMI  0Source B MB_CoalPrcnt_SP  0

LES MB_CoalSP_Tmr.DNSubtractSource A MB_CoalPrcnt_SP  0Source B 1 Dest MB_CoalPrcnt_SP  0

SUB

Page 2: AirOil Ratio MB

8/2/2019 AirOil Ratio MB

http://slidepdf.com/reader/full/airoil-ratio-mb 2/6

_AirOil_Ratio_MB - Ladder Diagram Page 2D1_D1C:MainTask:MainProgram 2/1/2012 7:47:34 AMal number of rungs in routine: 40 ...ant\CCP\Logics\Under Development\Dryer#1\D1C_120111_SIM.ACD

RSLogix 5000

CoalSelect_Test

Limit Status:Main Burner Coal

SelectMsg_BMS_to_PLC[17].2

 / 

Damper Positioned toLow Fire

Dam_Pos_LF MB_CoalSel.0

ComputeDest MB_Coal_RunPrcnt  0.0Expression (MB_CoalPrcnt_SP*MB_CoalSel)/100

CPT

ComputeDest MB_Oil_RunPrcnt  1.0Expression 1-MB_Coal_RunPrcnt

CPT

ComputeDest MB_Coal_Flow_SP  0.0Expression ((MB_Coal_RunPrcnt*MBDF_to_Heat)/LHV_Coal)

CPT

ComputeDest MB_Oil_Flow_SP  847.79224Expression ((MB_Oil_RunPrcnt*MBDF_to_Heat)/LHV_Oil)

CPT

0 ComputeDest MB_Oil_AirReq  14344.6455Expression MB_Oil_Flow_SP*OilStoich*MB_AF_Ratio

CPT

ComputeDest MB_Coal_AirReq  0.0Expression MB_Coal_Flow_SP*CoalStoich*MB_AF_Ratio

CPT

2 ComputeDest MB_AuxAir  3007.4998Expression (FI_2211X.Eng +FI_221Y5A.Eng)*AirFactor

CPT

3 ComputeDest MB_PrimAir_SP  11337.1455

Expression ((MB_Oil_AirReq+MB_Coal_AirReq))-MB_AuxAir

CPT

Page 3: AirOil Ratio MB

8/2/2019 AirOil Ratio MB

http://slidepdf.com/reader/full/airoil-ratio-mb 3/6

_AirOil_Ratio_MB - Ladder Diagram Page 3D1_D1C:MainTask:MainProgram 2/1/2012 7:47:34 AMal number of rungs in routine: 40 ...ant\CCP\Logics\Under Development\Dryer#1\D1C_120111_SIM.ACD

RSLogix 5000

Convert Air Flow From Nm3/Hr to KG/hr.The density in 0 deg C and 1 atm = 1.2929 kg/m³ (convertion Factor = 1.2929)

4 ComputeDest FIT22106_Nmph  10620.0Expression FIT22106*60

CPT

Dryer#1 PRimary AirFlow in Nm3/Hr

Convert Air Flow From Nm3/Hr to KG/hr.The density in 0 deg C and 1 atm = 1.2929 kg/m³ (convertion Factor = 1.2929)

5 MultiplySource A FIT22106_Nmph  10620.0Source B AirFactor  1.203Dest FIT22106_Kgph  12775.859

MUL

Dryer#1 Primary AirFan Flow in Kg/Hr

6 ComputeDest MB_TotalAirFlow  15783.359Expression FIT22106_Kgph+MB_AuxAir

CPT

7 DivideSource A OilStoich  14.1Source B LHV_Oil

  9625.0Dest OilPerLHV  1.46493514e-003

DIV

8 DivideSource A CoalStoich  0.0Source B LHV_Coal  5639.0Dest CoalPerLHV  0.0

DIV

9 ComputeDest MB_FiringRate_Lim  10774101.0Expression MB_TotalAirFlow/(OilPerLHV+((CoalPerLHV-OilPerLHV)*MB_Coal_RunPrcnt))

CPT

0 ComputeDest MB_CoalAir_Act  0.0Expression MB_FiringRate_Lim*MB_Coal_RunPrcnt*CoalPerLHV

CPT

Page 4: AirOil Ratio MB

8/2/2019 AirOil Ratio MB

http://slidepdf.com/reader/full/airoil-ratio-mb 4/6

_AirOil_Ratio_MB - Ladder Diagram Page 4D1_D1C:MainTask:MainProgram 2/1/2012 7:47:34 AMal number of rungs in routine: 40 ...ant\CCP\Logics\Under Development\Dryer#1\D1C_120111_SIM.ACD

RSLogix 5000

ComputeDest MB_OilAir_Act  15783.359Expression MB_FiringRate_Lim*(1-MB_Coal_RunPrcnt)*OilPerLHV

CPT

2 Compute

Dest MB_Coal_SP  1.$Expression MB_CoalAir_Act/CoalStoich/MB_AF_Ratio

CPT

3 ComputeDest MB_Oil_SP  932.82263Expression MB_OilAir_Act/OilStoich/MB_AF_Ratio

CPT

4 Less Than (A<B)Source A MB_Oil_SP  932.82263Source B MB_Oil_Flow_SP  847.79224

LES OIL_LES_MBDF

5OIL_LES_MBDF

MoveSource MB_Oil_SP  932.82263Dest FIT22205_SP_CAS  847.79224

MOV

6 / OIL_LES_MBDF

MoveSource MB_Oil_Flow_SP  847.79224Dest FIT22205_SP_CAS  847.79224

MOV

7 Less Than (A<B)Source A MB_Coal_SP  1.$

Source B MB_Coal_Flow_SP  0.0

LES COAL_LES_MBDF

8COAL_LES_MBDF

MoveSource MB_Coal_SP  1.$Dest WIC221X3A_SP  0.0

MOV

Setpoint of CoalFiring Rate in Kg/Hr

Page 5: AirOil Ratio MB

8/2/2019 AirOil Ratio MB

http://slidepdf.com/reader/full/airoil-ratio-mb 5/6

_AirOil_Ratio_MB - Ladder Diagram Page 5D1_D1C:MainTask:MainProgram 2/1/2012 7:47:34 AMal number of rungs in routine: 40 ...ant\CCP\Logics\Under Development\Dryer#1\D1C_120111_SIM.ACD

RSLogix 5000

9 / COAL_LES_MBDF

MoveSource MB_Coal_Flow_SP  0.0Dest WIC221X3A_SP  0.0

MOV

Setpoint of CoalFiring Rate in Kg/Hr

0 ComputeDest MB_Tot_FueltoAir  0.0Expression (FIT22105*OilStoich)+(WIT221X3A*CoalStoich)

CPT

Old Formula for Total Aeration =( Prim Air Flow + Side Burner Flow)/((Main Oil Flow + Side Oil Flow)*0.1744074)*100

ComputeDest MB_PrimAir_Req  -3007.4998Expression (((FIT22105*OilStoich)+(WIT221X3A*CoalStoich))*MB_AF_Ratio)-MB_AuxAir

CPTOld Formula for Total Aeration =( Prim Air Flow + Side Burner Flow)/((Main Oil Flow + Side Oil Flow)*0.1744074)*100

2 Greater Than (A>B)Source A MB_PrimAir_SP  11337.1455Source B MB_PrimAir_Req  -3007.4998

GRT MB_AIRSP_GRT

3MB_AIRSP_GRT

Move

Source MB_PrimAir_SP  11337.1455Dest FIC22106_SP_CAS  11337.1455

MOV

4 / MB_AIRSP_GRT

MoveSource MB_PrimAir_Req  -3007.4998Dest FIC22106_SP_CAS  11337.1455

MOV

5 ComputeDest MB_ActHeat  0.0Expression ((FIT22105*LHV_Oil)+(WIT221X3A*LHV_Coal))/1000000

CPT

MAin Burner TotalHeat Actual Produced

(GCal/Hr)

Page 6: AirOil Ratio MB

8/2/2019 AirOil Ratio MB

http://slidepdf.com/reader/full/airoil-ratio-mb 6/6

_AirOil_Ratio_MB - Ladder Diagram Page 6D1_D1C:MainTask:MainProgram 2/1/2012 7:47:34 AMal number of rungs in routine: 40 ...ant\CCP\Logics\Under Development\Dryer#1\D1C_120111_SIM.ACD

6 DivideSource A MB_TotalAirFlow  15783.359Source B MB_Tot_FueltoAir

  0.0Dest MB_Stoichometric  1.$

DIV

Ratio Between TotalAir Flow and Fuel

Stoich Converted toAir

7

Main HSFO OperatedStatus from BMS

MainHSFOOperate PilotBurnerON AirOn_Pilot

8AirOn_Pilot

AddSource A 3976 Source B FIC22106_SP_CAS  11337.1455Dest FIC22106_SP_CAS  11337.1455

ADD

9 Less Than (A<B)

Source A MB_Stoichometric  1.$Source B 1 

LES

Ratio Between TotalAir Flow and Fuel

Stoich Converted toAir

Main HSFO OperatedStatus from BMS

MainHSFOOperate

User Data Type foralarms Alarm Delay

TimerMBLowStoich.Tmr.DN

User Data Type foralarms Alarm Active

(1 = Alarm)MBLowStoich.Alm

EN

DN

Timer On DelayTimer MBLowStoich.TmrPreset 0Accum 0

TON

User Data Type foralarms Alarm Delay

Timer

nd)