Alarmline Linear Heat SensorTypical Applications

Page 2: Alarmline Linear Heat Sensor Typical Applications

Alarmline Applications

• Heavy industry

• Warehousing / storage tanks

• Conveyors and escalators

• Cable trays

• Floor & ceiling voids

• Tunnels

• Car parks

Page 3: Alarmline Linear Heat Sensor Typical Applications

Applications - Case Study 1 Electricity Generation

- Cable trays and risers

- Boiler fronts

- Conveyors

- Cooling towers

- Transformers.

Page 4: Alarmline Linear Heat Sensor Typical Applications

Typical Cable Tray

End of line

To Junction Box

At end of tray Sensor Cableto be fixed to rear wall to

change levels

Page 5: Alarmline Linear Heat Sensor Typical Applications

Cable Trays

Traywork width 600mm maximum

Alarmline cable

Powercables

Sensorsupports

Page 6: Alarmline Linear Heat Sensor Typical Applications

AlarmLine

Cable Traywith Cables

Tray Support

Cable Flats

Page 7: Alarmline Linear Heat Sensor Typical Applications

Typical Island Cable Tray

Page 8: Alarmline Linear Heat Sensor Typical Applications

Transformers

• AlarmLine Recommendation:

– Nylon Coated AlarmLine

• Application Notes:

– Mount on Water Spray pipe around Main Body, Radiators & Oil Tank

Page 9: Alarmline Linear Heat Sensor Typical Applications

Escalator Protection

Analogue Bronze braided orNylon coated cableDigital cable ofrequired temperature.

Sensor cable.Located under escalatorprotecting pits and roller bearings.

Dust collection pit

Dust collection / Drive motor pit

Page 10: Alarmline Linear Heat Sensor Typical Applications

Typical Installation 2 lanetraffic road tunnel

ToControlPanel

JunctionBox

JunctionBox

Detection Cable(of specified temperature)

10

2.5 2. 5

5

Page 11: Alarmline Linear Heat Sensor Typical Applications

Typical Car Park Installation

Control InterfaceUnit(Analogue)Junction Box(Digital)

9mtypical

Page 12: Alarmline Linear Heat Sensor Typical Applications

Typical method of fixing sensor cable where beams are part of construction ‘T’ clips used.

1m Typically

Page 13: Alarmline Linear Heat Sensor Typical Applications

Residential Car Park

Page 14: Alarmline Linear Heat Sensor Typical Applications

Applications - Case Study 2Warehousing & Bulk Storage

- Alarmline Digital cable with conventional control unit or

- Alarmline Analogue high resistance / Nylon extruded cable with LHD 4 controller

- Fixing clips as required- “T” Clips- Edge connectors- Cable tray fixings.

Page 15: Alarmline Linear Heat Sensor Typical Applications

Warehouse/High Rack Storage

PIPE

ALARMLINE SENSORAT CEILING LEVEL BACK TO BACK

RACKS

AISLE

AISLE

ALARMLINESENSOR SPRINKLER

PIPE

16’

ALARMLINE SENSORAT TOP RACK LEVEL

ATTACHED TO SPRINKLERTOP VIEW END VIEW

Page 16: Alarmline Linear Heat Sensor Typical Applications

ChillerWarehouseApplication

Food Distribution

Page 17: Alarmline Linear Heat Sensor Typical Applications

Racking

Alarmline Cable

Page 18: Alarmline Linear Heat Sensor Typical Applications

Conveyor belt fire detectionAlarmline sensor cable installed directly at the support roller bearings location. This is to monitor what has been independently proven to be the greatest risk- an overheated condition generated by friction igniting the build up of material spilled from the belt. A wide range of clips and fastenings are available to match the environment and installation method.

Alarmline sensor cable can be installed directly over the conveyor to detect a fire/overheat on a stationary conveyor.

Bronze braided sensor cable is recommended as this provides greater protection against possible mechanical damage.

The Alarmline sensor cable should be run down both sides of the conveyor belt To give greater protection against build up of material under the bed of the conveyor Alarmline can be installed under the conveyor as shown in figure

Page 19: Alarmline Linear Heat Sensor Typical Applications

LINEAR HEAT SENSORTypical installation on Single Conveyor

BEARING SUPPORT

SENSOR CABLE

OPTIONALSENSOR CABLE

Digital Sensor Cable mountedon conveyor bed plateand roller bearings(both sides of conveyor)

Page 20: Alarmline Linear Heat Sensor Typical Applications

O ptional

A larm lineCable

Id le ro llers

Conveyor Belt

Conveyor return belt

Page 21: Alarmline Linear Heat Sensor Typical Applications

Floating Roof Storage Tanks

• Install between primary & weather seal.

• Use Intrinsic Safety Barriers for Fuel related applications

Page 22: Alarmline Linear Heat Sensor Typical Applications

Schematic diagram Alarmline Digital Linear Heat Sensor Protection Floating Roof Tank

JU N C TIO N BO X W ITHC ABLE C O LLEC TIN G ASSEM BLY

R ETR AC TABLE C ABLE

JU N C TIO N BO X

R IM SEAL

C O N TR O L C U BIC LELO C ATED IN SAFEAR EA

ZEN N ER BAR R IERC O M PARTM EN T

2 C O R E IN TER PO SIN G C ABLESU PPLIED AN D IN STALLED BY O TH ER S

SU PPO RT BR AC KETS

D IG ITAL LIN EARH EAT SEN SO RC ABLE AR O U N DR IM SEAL

TAN K

Page 23: Alarmline Linear Heat Sensor Typical Applications

Typical Cable Schematic Diagram Alarmline DigitalNote: Resistors R1 & R2 supplied by panel manufacturer and fitted by others

1

H9650 LHS DigitalR1

EOL

B6782-044Retractable Cable

2 Core cableto controlPanel(by others)

1

2

3

4

1

2

2

4

3

B6782Junction Box

located onFixed Tank Top

B6782Junction Box

located onTank Floating Roof

R2

CableFitted toRim Seal

Page 24: Alarmline Linear Heat Sensor Typical Applications

JU N C TIO N BO X W ITHC ABLE C O LLEC TIN G A S SE M BLYR ETR A C TAB LE C AB LE

JU N C TIO N BO X

R IM SEA L

C O N TR O L C U BIC LELO C ATED IN SA FEA R EA

ZEN N E R B AR R IERC O M PARTM EN T

4 C O R E IN TER P O SIN G C A BLES U PP LIED A N D IN S TA LLE D B Y O TH E R S

S U PP O RT BR AC KE TS

A LA R M LIN E LIN EAR H EATS EN S O R C ABLEA R O U N D R IM S EA L

TA N K

Schematic diagram Alarmline Analogue Linear Heat Sensor ProtectionFloating Roof Tank

Page 25: Alarmline Linear Heat Sensor Typical Applications

Typical Connection Diagram Alarmline Analogue

Junction Box Tank Roof Top

1

2

3

4

5

6

7

8

Alarmline

Cable onTank

Junction BoxTank Top

1

2

3

4

Blue

Red

White

OrangeLink 2

Link 1

RetractableCable

4 Core Blue

Red

White

Orange

Page 26: Alarmline Linear Heat Sensor Typical Applications

Detail showing collector installation typical

Bund Wall

Tank

3

7

HD Cable1

Typical Local Plan

1. LHD Cable2. LHD Mounting Piece S.S.3. Junction Box4. Mounting Bracket5. Cable Collector6. Flexicable7. Junction Box8. Mounting Bracket9. Neoprene Sleeve

10. Tie Wrap

Tank Mounting Detail

8

7 Tank

Foam Dam

6

5

3

1Cable CollectorFixed to Dam

Note:Retractable cable falls into collector not around centre section.

4

10

8

1

Site to confirmfixing arrangement

FoamDam

LHD Cable Mounting Detail

Page 27: Alarmline Linear Heat Sensor Typical Applications

RIMSEAL RETAININGPLATE

3

2

1

4

6

5

JUNCTIONBOX

TANK WALL

INTERCONNECTING 4-CORE CABLE TO TANK LADDER

1

PART PLAN

RIM SEAL RETAINING PLATE

6

SHOWING CABLE TERMINATION INTO JUNCTION BOX

1. Edge Clip

2. M6 Nut, washer & bolt, St.St.

3. Distance piece, St. St.

4. Neoprene sleeve

5. Tywrap

6. Alarmline high resolution cable assembly

Note:

1. Maximum spacing between supports to be 1000mm

2. Alarm Cable to be terminated directly into Junction Box on cable Collector Drum which is to be secured adjacent to Rim Seal Protector Plate so the cable is not obstructed in its entry into Junction Box

RIM SEAL

400mm(NTS)

TANKWALL200mm

Page 28: Alarmline Linear Heat Sensor Typical Applications

AlarmlineSensor

WeatherSeal

Tank WallFloating Roof

Retractable Cableto Tank TopJunction Box

EarthStrap

Tank Top

Typical Application without Foam Dam

Page 29: Alarmline Linear Heat Sensor Typical Applications

500.0

100.0

200.0

4 HOLES25.0ON 400.00 PCD(FOR DRAINAGE)

4 HOLES25.0ON 300.00 PCD(FOR DRAINAGE)

620.

0

Page 30: Alarmline Linear Heat Sensor Typical Applications

N um ber of C ores: 4C ore C olours: 1 B lue, 2 B row n, 3 B lack, 4 Ye llowC ore S ize: 0.75m m (24/.2)C ore Insu lation: H ytre lInner Sheath: PolyurethaneO uter Sheath: H ytre lLengths: 10-25m , 30 extended

2

230N om inal

340

Nom

inal

5000

1500

Page 31: Alarmline Linear Heat Sensor Typical Applications

Fixed Roof Storage Tanks

• Install AlarmLine at 1 metre intervals on shell

• Use Intrinsic Safety Barriers for Fuel related applications

Page 32: Alarmline Linear Heat Sensor Typical Applications

Dust Collectors/Bag Houses

Bag House - Top View

LHS SENSOR

Page 33: Alarmline Linear Heat Sensor Typical Applications

Dust Collectors/Bag Houses

• Typical Hazards

– Grain and Feed Processing Facilities

– Fabric and Cotton Processing Facilities

– Metal Grinding/Polishing Facilities

– Wood Working Plants

• AlarmLine Recommendations

– Non-Abrasive: Nylon Coated

– Abrasive applications: Bronze Braided