EXTERNAL ALARM’S AT BTS SITE

Page 2: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 2

INTRODUCTION

Alarm’s are used to monitor the site in case of any fault occur then

alarm panel automatically generate the alarm for corresponding fault occurred at site.

Page 3: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 3

Why alarm’s are used at site?

External alarm is important at BTS site because in case of any fault occur then as a maintenance engineer it will be easier for us to identify the problem and rectify it accordingly. We can check at DDF, where termination of alarm is done. It provide security and stability to whole BTS site.

Page 4: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 4

ALARM

BTSSITE

EXTERNAL

ALARM

INTERNAL

ALARM

TYPES OF ALARM AT BTS SITE

Page 5: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 5

PARAMETER OF EXTERNAL ALARM

These are parameter which may differ according to manufacturer.

ALARM NO ALARM TYPE(NO/NC)

ALARM SEVERITYALARM PORT NO/PIN NO

COLOUR CODEROUTE

OF ALARM

ALARM NAME OR SYNTAX OR TITLE

ROOT CAUSE

OF ALARM

CAUSE OF ALARM

Page 6: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 6

ALARM NAME OR SYNTAX OR TITLE

It define the name of the alarm at BTS site. It may differ according to the operator. Depending upon BTS used syntax or title can change. Some of the example of name of alarm operator are as follow’s..

BTS NAME ALARM NAME

NOKIA FLEXI BTS DG FAIL’S TO START MAIN’S FAILURE

ERICSSION RBS 2964 DG FAIL’S TO STOP DOOR OPEN

Page 7: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 7

NORMALLY OPEN

NORMALLY CLOSED

PARAMETER DESCRIPTION CONTINUED

ALARM TYPE

ALARM NO

Every operator decide a particular alarm no for it’s BTS site and accordingly series of alarm is decided. for eg-7401 in NOKIA flexi BTS case.

ALARM TYPE

Type of alarm mean’s that either alarm will be normally Closed or normally open. Normally open mean’s that state of alarm in normal condition is OPEN. Normally closed mean’s that state of alarm in normal condition is closed.

Page 8: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 8

PARAMETER DESCRIPTION

SE

VE

RIT

Y CRITICAL

MAJOR

MINOR

CRITICAL

Critical mean’s that ,it require immediate attention, if on BTS site any alarm is critical defined that mean’s that level of alarm severity is high. for eg : LLOP- low lubricant oil pressure.

MAJOR

Major mean’s that ,it’s severity level is lesser than critical but it is also needed attention as soon as possible. for eg: low fuel level

MINOR

Minor mean’s that ,it’s severity level is lesser in compare to other alarm and site may not get affected as much as in case of critical and major. for eg- site on DG.

Page 9: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 9

PORT NO/PIN

NO

COLOUR CODE

OPERATOR

SPECIFIC

ALARM PORT

Alarm port or pin no is decided by operator itself .

COLOUR CODE

The colour code of alarm wire is decided by operator itself. Always it will exist in pair for PCM cable’s used.

Page 10: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 10

ROUTE of

ALARM

• IT DECIDE ROUTE OF ALARM

ROOT CAUSE

• IT DECIDE THE CAUSE OF ALARM

ROUTE OF ALARM

It decide the route of alarm or we can say that where alarm connection start till termination of that alarm.

ROOT CAUSE

Root cause mean’s the exact cause of fault which led to the alarm at the site.

Page 11: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 11

ALARM CABLE CONNECTION Alarm cable are PCM cable. They exist in pair’s. Each alarm will be connected to ddf with these cable.(two wire is one pair) 37 pin D-type connector. Alarm ddf installed on shelter wall. Alarm’s are connected to sensor’s.

25 PAIR PCM CABLE

Page 12: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 12

DDF ALARM CONNECTION

D TYPE 37 PIN

For connection of alarm these are needed.

Page 13: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 13

TYPE OF EXTERNAL ALARM’S 1. DOOR OPEN2. HIGH TEMPERATURE3. DG FAIL’S TO START4. DG FAIL’S TO STOP5. LOW FUEL LEVEL6. FIRE OR SMOKE7. LOW LUBRICATION OIL PRESSURE8. LOAD ON DG9. AC FAIL’S TO START(AC-1/AC-2)10.RECTIFIER MODULE PAIR FAIL’S11.LOW BATTERY VOLTAGE12.SITE ON DG13.AC -1 FAIL’S14.AC-2 FAIL’S15.DG RUNNING WITHOUT LOAD

Page 14: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 14

TO ELABORATE ABOVE DESCRIPTION TAKE EXAMPLE OF NOKIA FLEXI BTS

There are 12 external alarm for nokia flexi BTS. For 12 alarm connection ,we need 37 pin D connector in which 24 pin’s will be used. For each alarm , we require one pair E1 cable having two wire. Termination of these cable is done on DDF i.e from BTS to DDF and from alarm sensor to DDF.

Page 15: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 15

ALARM NO-7401/ALARM

NO1

SYNTAX-MAIN’S FAILURE

SEVERITY-MINOR

ALARM TYPE-NORMALY

OPEN

PIN NO-7/25

COLOR CODE-

GREEN&GREEN/WHITE

ROOT CAUSE -MAIN’S FAILURE

ROUTE OF ALARM PIU/AMF DDF BTS

Page 16: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 16

ALARM NO-7402/ALARM

NO2

SYNTAX-RECTIFIER MODULEFAILURE

SEVERITY-MINOR

ALARM TYPE-NORMALY

OPEN

PIN NO-8/26COLOR

CODE-BLUE&BLUE/WHITE

ROOT CAUSE -RECTIFIER FAILURE

ALARM CONFIGURATION CONTINUED

ROUTE OF ALARM POWER PLANT DDF BTS

Page 17: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 17

ALARM NO-7403/ALARM

NO3

SYNTAX-BATTERY AT 47V/LOW BATTERY

VOLTAGE

SEVERITY-CRITICAL

ALARM TYPE-NORMALY

OPEN

PIN NO-9/27

COLOR CODE-VOILET&WHITEVOILET

ROOT CAUSE -BATTERY VOLTAGE IS BELOW -48V

ALARM CONFIGURATION CONTINUED

POWER PLANT DDF BTS ROUTE OF ALARM

Page 18: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 18

ALARM NO-7404/ALARM

NO4

SYNTAX-LOAD ON BATTERY

SEVERITY-MAJOR

ALARM TYPE-NORMALY

OPEN

PIN NO-10/28

COLOR CODE-GREY&

WHITE GREY

ROOT CAUSE -ALL RECTIFIER IN P.P FAILED

ALARM CONFIGURATION CONTINUED

POWER PLANT DDF BTS ROUTE OF ALARM

Page 19: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 19

ALARM NO-7405/ALARM

NO5

SYNTAX-LOAD ON DG

SEVERITY-MINOR

ALARM TYPE-NORMALY

OPEN

PIN NO-11/29COLOR

CODE-PINK&BLACK/RED

ROOT CAUSE-MAIN’S FAILURE

ALARM CONFIGURATION CONTINUED

PIU/ AMF DDF BTS ROUTE OF ALARM

Page 20: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 20

ALARM NO-7406/ALARM

NO6

SYNTAX-DG LLOP

SEVERITY-CRITICAL

ALARM TYPE-NORMALY

OPEN

PIN NO-12/30

COLOR CODE-LIGHTGREEN&

BLACK/GREEN

ROOT CAUSE-WHEN LUBRICANT OIL PRESSURE IN ENGINE GOES BELOW SPECIFIED LEVEL

ALARM CONFIGURATION CONTINUED

ROUTE OF ALARM PIU/AMF DDF BTSLLOP

SENSOR

Page 21: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 21

ALARM NO-7407/ALARM

NO7

SYNTAX-LOW FUEL LEVEL

SEVERITY-MINOR

ALARM TYPE-NORMALY

OPEN

PIN NO-13/31COLOR

CODE-LIGHT BLUE&BLACK

ROOT CAUSE -WHEN THE FUEL IN TANK GOES BELOW 40%.

ALARM CONFIGURATION CONTINUED

ROUTE OF ALARMFUEL

SENSORPIU/AMF DDF BTS

Page 22: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 22

ALARM NO-7408/ALARM

NO8

SYNTAX-DG FAIL TO START

SEVERITY-MAJOR

ALARM TYPE-NORMALY

OPEN

PIN NO-14/32

COLOR CODE-WHITE BLACK/WHIT

E

ROOT CAUSE-DG DOESN’T START AFTER 3 ATTEMPT’S BY PIU/AMF

ALARM CONFIGURATION CONTINUED

PIU/ AMF DDF BTS ROUTE OF ALARM

Page 23: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 23

ALARM NO-7409/ALARM

NO9

SYNTAX-AC FAIL’S

SEVERITY-MAJOR

ALARM TYPE-NORMALY

OPEN

PIN NO-15/33

COLOR CODE-LIGHT GREY&LIGHT GREY

/BLACK

ROOT CAUSE-BOTH AC FAIL’S

ALARM CONFIGURATION CONTINUED

ROUTE OF ALARM-MICRO

CONTROLLER

DDF BTS

Page 24: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 24

ALARM N0-7410/ALARM

NO10

SYNTAX-DOOROPEN

SEVERITY-MINOR

ALARM TYPE-NORMALY CLOSED

PIN NO-16/34

COLOR CODE-

GREEN&GREEN/WHITE

ROOT CAUSE -WHEN SHELTER DOOR IS OPEN.

ALARM CONFIGURATION CONTINUED

ROUTE OF ALARM- DOOR SENSOR

PIU/AMF DDF BTS

Page 25: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 25

ALARM NO-7411/ALARM

NO11

SYNTAX-HIGH

TEMPERATUR-E

SEVERITY-MAJOR

ALARM TYPE-NORMALY

OPEN

PIN NO-17/35

COLOR CODE-ORANGE/

RED&ORANGE/LIGHT GREY

ROOT CAUSE -WHEN TEMPERATURE REACHES ALARMING LEVEL.

ALARM CONFIGURATION CONTINUED

ROUTE OF ALARM-MICRO

CONTROLLER DDF BTS

Page 26: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 26

ALARM CONFIGURATION CONTINUED

ALARM NO-7412/ALARM

NO12

SYNTAX-FIRE/SMOKE

SEVERITY-CRITICAL

ALARM TYPE-NORMALY

OPEN

PIN NO-18/36

COLOR CODE-ORANGE

/BLACK&ORA-NGE/GREEN

ROOT CAUSE -WHEN TEMPERATURE REACHES ALARMING LEVEL.

ROUTE OF ALARM-FUEL

SENSORPIU/AMF DDF BTS

Page 27: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 27

APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S

SYNTAX-DG FAIL’S TO

STOP

COLOUR CODE-

OPERATOR SPECIFIC

PIN NO-OPERATOR SPECIFIC

ALARM NO-OPERATOR SPECIFIC

ALARM TYPE-NORMALLY

CLOSED

SEVERITY-MINOR

PIU/AMF DDF BTS ROUTE OF ALARM-

ROOT CAUSE-WHEN PIU OR AMF NOT ABLE TO STOP DG AFTER 3 ATTEMPT.

Page 28: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 28

SYNTAX-AC-1 FAIL’S

ALARM NO-OPERATOR SPECIFIC

COLOUR CODE-OPERATOR SPECIFIC

SEVERITY-MINOR

ALARM TYPE-NORMALLY

OPEN

PIN NO –OPERATOR SPECIFIC

APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S

MICRO CONTROLLER DDF BTS ROUTE OF ALARM-

ROOT CAUSE-WHEN AC-1 FAIL’S

Page 29: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 29

SYNTAX-AC-2 FAIL’S

ALARM NO-OPERATOR SPECIFIC

COLOUR CODE-OPERATOR SPECIFIC

SEVERITY-MINOR

ALARM TYPE-NORMALLY

OPEN

PIN NO –OPERATOR SPECIFIC

APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S

MICRO CONTROLLER DDF BTS ROUTE OF ALARM-

ROOT CAUSE-WHEN AC-2 FAIL’S

Page 30: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 30

LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

Ericsson RBS2954 DG on DG fail’s to start Main fail’s DG fuel level LLOP DG fails to stop Cabinet temperature Fire & smoke Door smoke BFU fault Spare SMPS input fail Battery low voltage DC disconnected alarm Battery breaker off Battery disconnected

Page 31: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 31

LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

Ericsson RBS2964 DG on DG fail’s to start Main fail’s DG fuel level LLOP DG fails to stop Cabinet temperature Fire & smoke Door open BFU fault Spare SMPS input fail Battery low voltage DC disconnected alarm Battery breaker off Battery disconnected

Page 32: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 32

LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

HUAWEI 3900 Intruder A/C failure High room temperature Fire alarm Fire fighting Main’s failure Generator failure Generator run Rectifier high voltage Tower light failure Rectifier 2/more failure Tower amplifier fail Rectifier low voltage Rectifier common alarm GN auto mode Low fuel in main tank

Page 33: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 33

LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

ZTE ZXG 10

Page 34: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 34

Sl. No External Alarms ID Breaking Closing Level1 DG ON 0 Closing 22 DG fail to Start 1 Closing 13 Mains Fail 2 Closing 14 High Shelter 3 Closing 1 Temperature5 DG Fuel Level Low 4 Closing 16 LLOP 5 Closing 27 DG Fail to Stop 6 Closing 18 Fire and Smoke 7 Closing 19 Door Open 8 Closing110 AC 1 - OFF 9 Closing 111 AC 2 – OFF A Closing 112 Spare B 13 Battery Fuse Fail C Closing 114 Rectifier Fail D Closing 115 Battery Low Voltage E Closing 116 SMPS Input Fail F Closing 1

ALARM DEFINED IN ERICSSON SITES:

Page 35: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 35

Port ID External Alarms Closing/Breaking Level1 0 DG ON Closing 22 1 DG FAIL TO START Closing 13 2 MAINS FAIL Closing 14 3 DG FUEL LEVEL LOW Closing 15 4 LLOP Closing 26 5 DG FAIL TO STOP Closing 17 6 CABINET TEMPERATRE Closing 1 HIGH 8 7 FIRE AND SMOKE Closing 19 8 BBS DOOR OPEN Closing 110 9 BFU FAULT Closing 111 10 SPARE 12 B SMPS INPUT FAIL Closing 113 C BATTERY LOW VOLTAGE Closing 114 D DC DISCONNECTED ALARM Closing 115 E BATTERY BREAKER OFF Closing 116 F BATTERY DISCONNECTED Closing1

EXTERNAL ALARMS FOR BTS (RBS 2954) SITES:

Page 36: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 36

S/N TTSL Requirement Node colour code1 AC mains fail blue-white2 High room temperature Orange-white3 fire alarm Green-white4 Battery Discharge Brown-white5 rectifier fail Blue-red6 intruder Orange-red7 DG low fuel Red-green8 DG running Brown-red

After we connect the cable on krone block we will give loop with krone tool one by one and check weather alarm get disappear in OMCR or not.Same way we have to check for all the 8 ports.

BELOW MENTIONED COLOUR CODE OF RBS(2954)-

Page 37: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 37

EXTERNAL ALARM IN HUAWEI 3900 BTS AND COLOUR CODE-

KRONE NO:1 KRONE NO:2

NO: port SLOT DDF ALARM NO: port SLOT DDF ALARM

1 0 18 1 INTRUDER 9 0 19 1RECTIFIER

HIGH VOLTAGE

2 1 18 2 A/C FAILURE 10 1 19 2

TOWER LIGHT

FAILURE

3 2 18 3

HIGH ROOM

TEMPERATURE

11 2 19 3RECTIFIER 2/MORE FAILURE

4 3 18 4 FIRE ALARM 12 3 19 4

TOWER AMPLIFIE

R FAIL

5 4 18 5 FIRE FIGHTING 13 4 19 5

RECTIFIER LOW

VOLTAGE

6 5 18 6 MAINS FAILURE 14 5 19 6

RECTIFIER COMMON

ALARM

7 6 18 7GENERAT

OR FAILURE

15 6 19 7 GN AUTO MODE

8 7 18 8 GENERATOR RUN 16 7 19 8

LOW FUEL IN MAIN

TANK

Page 38: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 38

HUAWEI EXTERNAL ALARMS(COLOURS)

EXTERNAL ALARM COLOUR CODES

CABLE NO: PAIR COLOUR

1 1 WHITE ORANGE

2 1 ORANGE

3 2 WHITE GREEN

4 2 GREEN

5 3 WHITE BLUE

6 3 BLUE

7 4 WHITE BROWN

8 4 BROWN

Page 39: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 39

INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

LIST OF ALARM’S (1)RECTIFIER & BTS DOOR CABINET ALARM(2)RECTIFIER MAJOR ALARM(3)RECTIFIER MINOR ALARM(4)LOW DC VOLTAGE(5)HEAT MANAGEMENT ALARM(FOR AC CABINET ONLY)(6)TEMPERATURE ALARM(FOR FAN COOL CABINE ONLY)

CORRESPONDING ALARM NO- ALARM NO1 ALARM NO2 ALARM NO3 ALARM NO4 ALARM N05 ALARM NO7

Page 40: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 40

INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

LIST OF COLOUR CODE OF ABOVE ALARM

ALARM NO1-RECTIFIER & BTS DOOR CABINET ALARM- GREEN & WHITE GREEN ALARM NO2-RECTIFIER MAJOR ALARM-BLUE & WHITE BLUE ALARM NO3-RECTIFIER MINOR ALARM-VIOLET & WHITE VIOLET ALARM NO4-LOW DC VOLTAGE-GREY & WHITE GREY ALARM NO5-HEAT MANAGEMENT ALARM(FOR AC CABINET ONLY)-BLUE/BLACK &BLACK BLUE ALARM NO7-TEMPERATURE ALARM(FOR FAN COOLED CABINET ONLY)-LIGHTBLUE &LIGHT BLUE/ BLACK

Page 41: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 41

INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

MATERIAL REQUIREMENT- ALARM CABLE KRONE RACK CAT-5 CABLE 7-9 METER SOLDERING IRON OTHRE BASIC TOOL’S

Page 42: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 42

INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

INSTALLATION PROCESS- Initial step before installation-

(1)Alarm cable is too long so cut it into two pieces.

(2)1st cable will be used to take alarm from rectifier smart pack i/o ports to crone.

(3)2nd cable with connector at one end will be used for taking alarms from krone to BTS EAC port(2G cabinet).

Page 43: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 43

INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

INSTALLATION PROCESS CONTINUE-

STEP-1 KRONE INSTALLATION

Install the krone on rack and fix this rack in rectifier cabinet. Use proper size bolt’s and washer.

Page 44: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 44

Alarm cable installation(BTS – KRONE)

INSTALLATION PROCESS CONTINUE-

Connect the alarm cable connector on EAC port at BTS(2G cabinet) Bring the other end of alarm cable to rectifier through roxtec. Punch the alarm cable on the lower side of krone according to the alarm’s sequence. The alarm cable should be fixed properly with ties and properly routed.

Page 45: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 45

INSTALLATION PROCESS CONTINUE-

Route this cable properly with ties and fix it near the Rectifier I/O ports

• Connect Green & White Green (Alarm nu 1) with Pins 8 & 9 of CON1

(X1)

• Connect Grey & White Grey (Alarm nu 4) with Pins 9 & 10 of CON2

(X2)

• Connect Violet & White Violet (Alarm nu 3) with Pins 15 & 16 of

CON2 (X2)

• Connect Blue & White Blue (Alarm nu 2) with Pins 18 & 19 of CON2

(X2)

• Connect Light Blue & Light Blue Black (Alarm nu 7) with Pins 12 & 13

of CON2 (X2) (Only for Fan Cool Rectifier Cabinets)

Page 46: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 46

CON 2

( X2 )

CON 1

( X1 )

Page 47: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 47

HEAT MANAGEMENT ALARM

INSTALLATION PROCESS CONTINUE-

Air condition in the door usuallyhas Red & Yellow cable for AirCondition Alarm. This cable is connected to Pins 3& 4 on CON1. Remove this cable from there &punch it on Krone.

AIR CON ALARM CABLE

Page 48: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 48

Remove this cable from pins & punch it on Krone as shown

Air Con Alarm cable

INSTALLATION PROCESS CONTINUE-

Page 49: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 49

To test Heat Management Alarm cover the AC from outside with plasticso that no air can go through as shown below

Air Condition covered with plastic sheet

TESTING HEAT MANAGEMENT ALARM-

INSTALLATION PROCESS CONTINUE-

Page 50: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 50

900 BTS CABINET DOOR SENSOR

INSTALLATION PROCESS CONTINUE-

The BTS Cabinet door sensor cable is verysmall so we have to extend it•Take 1 pair from CAT-5 Cable and solderit with the sensor wires in BTS (900Cabinet)•Route this cable properly and fix it nearSmart Pack I/O ports•Connect this pair with pins 3 & 4 ofCON 2

BTS Cabinet doorSensor

Page 51: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 51

INSTALLATION PROCESS CONTINUE-

RECTIFIER CABINET DOOR SENSOR

Usually Rectifier door Sensor cables are already connected to theCON 1 (X1)•

If it is not connected then connect Rectifier Door Alarm Cable withpins 1 & 2 of CON 1 (X1)

Rectifier Door cable connected topins 1 & 2 of CON 1

Rectifier Door Sensor

Page 52: ALARM'S AT BTS SITE.pptx

AMIT MISHRA 52

Overall summary is that on any BTS site external alarm’s are important. Alarm’s make fault finding easy. External alarm’s make BTS site safer and easy to maintain. Each alarm has it’s own importance cannot be neglected.

SUMMARY