BUrners TRAining CEntre

CONTROL BOX RMO88.53CONTROL BOX RMO88.53

BUrners TRAining CEntre

PRESS SERIESONE STAGETWO STAGETHREE STAGE

Dedicated to:Dedicated to:

RL SERIESONE STAGETWO STAGE

Light oil burnersLight oil burners

BUrners TRAining CEntre

PRESS SERIESTWO STAGETHREE STAGE

RN SERIESTWO STAGE

Dedicated to:Dedicated to:

Heavy oil burnersHeavy oil burners

BUrners TRAining CEntre

FEATURES

MODELS

RMO88.53A2 RMO88.53A1

Main voltage…………….…... AC 220-240 V +10% -15% AC 100-120 V +10% -15%

Frequency…………….…... 50-60 Hz +/-6% 50-60 Hz +/-6%

Under Voltage protection…... Approx. AC 170 V Approx. AC 70 V

Primary fuse…………….…... Max 16 A Max 16 A

Power consumption……..…... 20 VA 20 VA

Internal fuse…….……..…... T6.3H250V (IEC 127-215) T6.3

Polarity...………….……..…... To be observed To be observed

Flame signal (photoresistence) >450 K (pre-purge)<200 K (operation)

>450 K (pre-purge)<200 K (operation)

Mode operation………….…... Intermittent Intermittent

BUrners TRAining CEntre

Timings of cycleRMO88.530A2RLRMO88.530A1RL NOTES

Waiting time………….…... 2 sec………………………….. Beginning when both# 4 & # 8 are energised.If not input to # 4 within600 sec since # 8 is energised lock out

Pre-purge time (min)….…... 23 sec………………………….

Pre-ignition time………….…... 22 sec………………………...

Ignition safety time……..…... 5 sec

Interval 1st 2nd stage..…... 7 sec…………………………. Interval between # 10 # 13 outputs

Post-ignition time……….…... 5 sec(max)

Interval 2st 3rd stage..…... 7 sec…………………………... Interval between # 13 # 14 outputs

Interval between # 11 # 10 outputs

Interval between # 12 # 10 outputs

BUrners TRAining CEntre

CONTROL PROGRAM IN EVENT OF FAULT

Cause Reponse

Mains failure Restart with program sequence

Voltage dropped belowundervoltage threshold

Restart with program sequence

Premature flame signal Lock-out

Burner does not ignitewithin safety time

Lock-out

Loss of flame duringoperation

3 repetitions, then lock out

Oil temperature doesnot reach set valuewithin 600 sec fromactivation of # 8

Lock-out

BUrners TRAining CEntre

INDICATION OF OPERATION

Color code table

Stand-by and waiting statuses

Heating (since min. temperature achieved)

Ignition phase, ignition controlled

Operation, flame OK

Operation, poor flame

Undervoltage, built-in fuse

Fault, alarm

Extraneous light

Error code output (e.g. 2 blinks)

BUrners TRAining CEntre

Operating concept

Burner control has initiated lockoutRed fault LED on

Reset Press lockout reset button for about 1 s

Diagnosis of cause of fault – Press lockout reset button for > 3 s– Read blink code of red fault LED

«Error code table A»

SELF-DIAGNOSTIC

BUrners TRAining CEntre

Error code table A

Blink code Possible cause

2 x No establishment of flame at the end of ignition safety time– Faulty or soiled flame detector

– Faulty or soiled fuel valves– Poor adjustment of burner

– Faulty ingnion equipment

4 x Extraneous light during pre-purging– Or internal device fault

7 x Loss of flame during operation– Poor adjustment of burner

– Faulty or soiled fuel valves – Faulty or soiled flame detector

8 x Time-out release contact for oil pre-heater does not close

10 x Wiring error or internal fault, output contact, unidentifiable fault, e.g. faults that occurred simultaneously