Page 1: BUrners TRAining CEntre CONTROL BOX RMO88.53. BUrners TRAining CEntre PRESS SERIES ONE STAGE TWO STAGE THREE STAGE Dedicated to: RL SERIES ONE STAGE TWO

BUrners TRAining CEntre

CONTROL BOX RMO88.53CONTROL BOX RMO88.53

Page 2: BUrners TRAining CEntre CONTROL BOX RMO88.53. BUrners TRAining CEntre PRESS SERIES ONE STAGE TWO STAGE THREE STAGE Dedicated to: RL SERIES ONE STAGE TWO

BUrners TRAining CEntre

PRESS SERIESONE STAGETWO STAGETHREE STAGE

Dedicated to:Dedicated to:

RL SERIESONE STAGETWO STAGE

Light oil burnersLight oil burners

Page 3: BUrners TRAining CEntre CONTROL BOX RMO88.53. BUrners TRAining CEntre PRESS SERIES ONE STAGE TWO STAGE THREE STAGE Dedicated to: RL SERIES ONE STAGE TWO

BUrners TRAining CEntre

PRESS SERIESTWO STAGETHREE STAGE

RN SERIESTWO STAGE

Dedicated to:Dedicated to:

Heavy oil burnersHeavy oil burners

Page 4: BUrners TRAining CEntre CONTROL BOX RMO88.53. BUrners TRAining CEntre PRESS SERIES ONE STAGE TWO STAGE THREE STAGE Dedicated to: RL SERIES ONE STAGE TWO

BUrners TRAining CEntre

FEATURES

MODELS

RMO88.53A2 RMO88.53A1

Main voltage…………….…... AC 220-240 V +10% -15% AC 100-120 V +10% -15%

Frequency…………….…... 50-60 Hz +/-6% 50-60 Hz +/-6%

Under Voltage protection…... Approx. AC 170 V Approx. AC 70 V

Primary fuse…………….…... Max 16 A Max 16 A

Power consumption……..…... 20 VA 20 VA

Internal fuse…….……..…... T6.3H250V (IEC 127-215) T6.3

Polarity...………….……..…... To be observed To be observed

Flame signal (photoresistence) >450 K (pre-purge)<200 K (operation)

>450 K (pre-purge)<200 K (operation)

Mode operation………….…... Intermittent Intermittent

Page 5: BUrners TRAining CEntre CONTROL BOX RMO88.53. BUrners TRAining CEntre PRESS SERIES ONE STAGE TWO STAGE THREE STAGE Dedicated to: RL SERIES ONE STAGE TWO

BUrners TRAining CEntre

Timings of cycleRMO88.530A2RLRMO88.530A1RL NOTES

Waiting time………….…... 2 sec………………………….. Beginning when both# 4 & # 8 are energised.If not input to # 4 within600 sec since # 8 is energised lock out

Pre-purge time (min)….…... 23 sec………………………….

Pre-ignition time………….…... 22 sec………………………...

Ignition safety time……..…... 5 sec

Interval 1st 2nd stage..…... 7 sec…………………………. Interval between # 10 # 13 outputs

Post-ignition time……….…... 5 sec(max)

Interval 2st 3rd stage..…... 7 sec…………………………... Interval between # 13 # 14 outputs

Interval between # 11 # 10 outputs

Interval between # 12 # 10 outputs

Page 6: BUrners TRAining CEntre CONTROL BOX RMO88.53. BUrners TRAining CEntre PRESS SERIES ONE STAGE TWO STAGE THREE STAGE Dedicated to: RL SERIES ONE STAGE TWO

BUrners TRAining CEntre

CONTROL PROGRAM IN EVENT OF FAULT

Cause Reponse

Mains failure Restart with program sequence

Voltage dropped belowundervoltage threshold

Restart with program sequence

Premature flame signal Lock-out

Burner does not ignitewithin safety time

Lock-out

Loss of flame duringoperation

3 repetitions, then lock out

Oil temperature doesnot reach set valuewithin 600 sec fromactivation of # 8

Lock-out

Page 7: BUrners TRAining CEntre CONTROL BOX RMO88.53. BUrners TRAining CEntre PRESS SERIES ONE STAGE TWO STAGE THREE STAGE Dedicated to: RL SERIES ONE STAGE TWO

BUrners TRAining CEntre

INDICATION OF OPERATION

Color code table

Stand-by and waiting statuses

Heating (since min. temperature achieved)

Ignition phase, ignition controlled

Operation, flame OK

Operation, poor flame

Undervoltage, built-in fuse

Fault, alarm

Extraneous light

Error code output (e.g. 2 blinks)

Page 8: BUrners TRAining CEntre CONTROL BOX RMO88.53. BUrners TRAining CEntre PRESS SERIES ONE STAGE TWO STAGE THREE STAGE Dedicated to: RL SERIES ONE STAGE TWO

BUrners TRAining CEntre

Operating concept

Burner control has initiated lockoutRed fault LED on

Reset Press lockout reset button for about 1 s

Diagnosis of cause of fault – Press lockout reset button for > 3 s– Read blink code of red fault LED

«Error code table A»

SELF-DIAGNOSTIC

Page 9: BUrners TRAining CEntre CONTROL BOX RMO88.53. BUrners TRAining CEntre PRESS SERIES ONE STAGE TWO STAGE THREE STAGE Dedicated to: RL SERIES ONE STAGE TWO

BUrners TRAining CEntre

Error code table A

Blink code Possible cause

2 x No establishment of flame at the end of ignition safety time– Faulty or soiled flame detector

– Faulty or soiled fuel valves– Poor adjustment of burner

– Faulty ingnion equipment

4 x Extraneous light during pre-purging– Or internal device fault

7 x Loss of flame during operation– Poor adjustment of burner

– Faulty or soiled fuel valves – Faulty or soiled flame detector

8 x Time-out release contact for oil pre-heater does not close

10 x Wiring error or internal fault, output contact, unidentifiable fault, e.g. faults that occurred simultaneously