ca-mds r22-2009-5ohz

Post on 04-Jun-2018

243 Views

Category:

Documents

0 Downloads

Preview:

Click to see full reader

TRANSCRIPT

  • 8/13/2019 CA-MDS R22-2009-5OHz

    1/30

    MDS-R22-2009

    MULTI DIGITAL SCROLL UNITSMODEL: MDS030-MDS070A(R) MDS080-MDS320B(R)COOLING CAPACITY: 8.5kW-85kWHEATING CAPACITY: 9kW-92kW

    Catalogue

  • 8/13/2019 CA-MDS R22-2009-5OHz

    2/30

    For More Than a Century, McQuay has been Devoted to

    Different Buildings

    Global headquarters of McQuay (Minneapolis,USA)

    McQuay Staunton Factory, USA McQuay Aubum Factory, USA McQuay Cecchina Factory, Italy

    McQuay Shenzhen Factory, China Wo rk sh op o f McQ ua y Sh en zh en F ac to ry,China

    Test center of McQuay Shenzhen Factory,China

    Sound test room of McQuay Shenzhen Factory,China

  • 8/13/2019 CA-MDS R22-2009-5OHz

    3/30

    Unanimous Acclamation

    Research of Central Air Conditioning and Related Technologies

    For 130 years, we have been forging ahead at the forefront of HVACtechnology,

    creating many rsts in the development history of air conditioning.

    For most household and commercial users,

    McQuay is the incarnation of quality and trustworthiness.

    Today, McQuay introduces leading-edge central air conditioningtechnology to all over the world,

    With centurial expertise,

    we are providing end users with energy-saving, eco-friendly and

    comfortable air conditioning products.

    Quay Cramlington Factory, UK

  • 8/13/2019 CA-MDS R22-2009-5OHz

    4/30

    Page 4

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    imple

    anitary

    oft

    MDS Can Make Your Life BetterMDS (Multi Digital Scroll) system use the advantaged digital technology to meet the customer srequirement.

    It has some excellent performances as follows:1.Wide range of capacity modulation and application,2.More accuracy of temperature control and high EER,3.Much low noise level,4.Simple installation & management and maintenance.

    Because of these features, so it leads development of the air conditioning

  • 8/13/2019 CA-MDS R22-2009-5OHz

    5/30

    Page 5

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    ilence

    trong

    ave Energy

    Indoor Units Line-up

    Capacity range

    Model

    Capacity range

    0.8 HP 1.0 HP 1.5 HP 1.8 HP 2.0 HP 2.5 HP 3.0 HP 4.0 HP 5.0 HP 6.0 HP 8.0 HP 10.0 HP 12.0 HP 18.0 HP 22.0 HP 24.0HP

    Ceilingconcealedunits MCC

    Ceilingcassette unitsMCK

    High staticpressure ductunits MDB

    Ceilingexposed / oorstanding indoorunits MCM

    Wall mountedindoor unitsMWM

    Fresh air unitsMDBX

  • 8/13/2019 CA-MDS R22-2009-5OHz

    6/30

    Page 6

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Outdoor Unit

    MDS100B system 100%

    5%

    Loading

    operating

    operatingoperating

    Unloading

    1. High EER

    3. Large Capacity

    2. Easy Installation

    4. Quiet Running

    A optimization cooling-ci rcui t design makes theunit more efficient. Take MDS100B for example:it's EER is up to 3.3 (standard cooling condition atfull load), which is much higher than the old styling,and the power consumption decreased by 10%.

    With a truly modular form factor, the units canbe installed closely side by side. As all the unitsare of the same depth and height, the side-by-side installation can save more space. Take theinstallation of three 10HP units for example. Theinstallation space is 10.68 square meters only.By using the efficient refnet joint, the WPD of thesystem is reduced, which can save more energy.

    The maximum cooling capacity of a standard unit isup to 30 HP, which can meet the need of more than600 square meters. With a combination of modules,

    the units can be used even more widely.

    The outdoor unit has new-type spiral fan blades.The smooth air absorbing structure reduces theturbulent ow and noise signi cantly. The outdoorunit provides innovative quiet sleep mode (cooling).Unique sound insulation compressor design makes

    the system much quieter.

  • 8/13/2019 CA-MDS R22-2009-5OHz

    7/30

    Page 7

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Strong

    MDS system can bring you more fresh and comfortable life by means of superior cooling & heating perfor -mances, stepless capacity modulation and high accuracy of temperature control.

    Better Cooling and Heating PerformanceMDS system adopts advantaged design and passes rigorous test to ensure superior performance. From -15Cto 48C, MDS system can run in a very good condition, which will make you comfortable.

    Reaching the Setting Temperature QuicklyBoth the direct heat exchange between the refrigeration system and the air, and the intelligent temperaturecontrol ensure that the indoor temperature can reach the setting temperature quickly. Meanwhile, the lowtemperature fluctuation makes you much more comfortable.

    MDS system has a stepless capacity modulation from 10% to 100%. The output capacity can be closelymatched to the actual demanded capacity. Compared with the traditional inverter, MDS system has theadvantages of higher SEER (Seasonal EER), wider capacity modulation and more energy saving.

    Initial temperature

    Setting temperature

    Time

    Traditional air conditioning systemMDS system

    C o o

    l i n g c a p a c i

    t y %

    Capacity (%)

    MDS system

    Inverter system

    Wide Range of Capacity Modulation

  • 8/13/2019 CA-MDS R22-2009-5OHz

    8/30

    Page 8

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    AC PWM valve control

    Motor loss=5-10%

    VariableFrequency

    Capacity controller Capacity controller

    Digitalcompressor Compressor Invert Transformer

    AC AC AC

    DCDC DC

    Traditional invert system

    Modulation loss = 0% Modulation loss = 10%

    MDS digital variable multi system

    High EER

    MDS units feature leading-edge system design andhigh EER, thus saving more energy compared withtraditional air conditioners. For most time aroundthe year, air conditioners work at a partial load.Seasonal EER is the main index for judging whetherthe unit is more energy-ef cient. MDS digitalvariable multi systems feature high EER at fullcapacity, and even higher EER at partial capacity.Thanks to this, they can save more energy andeffectively reduce the electricity cost.

    Digital stepless capacity modulation with a widerrange

    Less on/off operations and smaller startup current5% ~ 20% less capacity modulation losscompared with invert systemsWhen the digital compressor is unloaded, thepower of the unit is reduced to 10% of the fullload power.

    MDS digital variable multi systems featurehigh seasonal EER. They can achieve betterheating and cooling performance with less powerconsumption. Compared with traditional systems,MDS digital variable multi systems can save up to45% electricity cost.

    Traditional central air conditioning system

    Energy Saving and Cost Effective

    Digital variable capacity system

    Save Energy

    No invert loss, thus reducing power consumptionWhile working at partial load, the outdoor unit supplies heating/cooling capacity to the indoor unitsexactly as necessary, thus eliminating bypass power consumption.

  • 8/13/2019 CA-MDS R22-2009-5OHz

    9/30

    Page 9

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Note: This chart is based on MDS 100B system

    Ambient temp. (C)

    0 4 8 12 16 20 24 28Cooling capacity (kW)

    MDS system

    Inverter system

    Atraditional residential air conditioning systemfluctuates within a range of 2 C.

    Atraditional frequency inverter system ctuateswithin a range of 0.5 C.MDS system fluctuates within a range of 0.3 C.

    15

    10

    20

    25

    30

    1 2 3 45

    Time

    Temp.

    Excellent Dehumidifying Performance

    The indoor relative humidity is very high in summer, which makes a bad environment on staying indoor. MDSsystem has excellent dehumidifying performance, which can reduce the indoor relative humidity, thus you canlive in a very comfortable environment.

    MDS system works at a lower sensible heat rate. It has a suction pressure which lower than a inverter system,therefore provides more powerful dehumidification.

    SoftMDS system is the perfect combination of advantaged air handling technology, accurate temperature controland reliable intelligent multi-scroll technology, which makes you more comfortable.

    Accurate Temperature Control, Quick ResponseThe indoor load depends on several factors, such as ambient temperature and sunshine. In order to makeyou more comfortable, the air conditioning system should be stepless modulated quickly to keep the indoor temperature in a low fluctuation range. MDS system can fulfill the function of stepless capacity modulationand output different capacities instantly. MDS is the future of the air conditioning system.

    Dry bulb temperature control can be as accurate as 0.3 oC.The unique dynamic forecast technology of load demanded.The continuous tracking technology of load.Quick response. The output can be changed from 10% to 100% very quickly.Quick action. The electronic expansion valve enables the system to provide more accurate temperaturecontrol and give more punctual response.

  • 8/13/2019 CA-MDS R22-2009-5OHz

    10/30

    Page 10

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    MCK

    Indoor unit model

    MDB

    MCC

    MCM

    Indoor unit capacity

    6HP

    0.8HP

    MWM

    MDBX 24HP

  • 8/13/2019 CA-MDS R22-2009-5OHz

    11/30

    Page 11

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    High frequency harmonic waveHigh frequency harmonic wave

    MDS digital variable capacity system

    EMC comparison diagram

    EMC regulationsVariable frequency system

    Excellent Electromagnetic Compatibility

    While modulating capacity, MDS digital variable multi systems only

    shift precision parts, and produce no high frequency harmonicwave. Therefore, they will not destroy with high delity soundboxes, computers, telephones etc. They can be widely used inplaces where interference with the power supply must be strictlyprohibited, such as computer rooms, telecom base stations, TVbroadcast reception stations and telecom equipment rooms.

    As the frequency signal changes, high frequency systems will

    generate high frequency harmonic waves with frequencies 5, 7,11, 13, 17 19 times as high as that of the power supply. Asa result, the power factor of the electricity network is reduced,the capacitor and transformer overheat, ashing points appearat the uoroscopes and oscillographs, and the precisionof precision instruments are lowered.The electromagneticinterference (EMI) of invert systems are now internationallydeemed as an environmental pollution. The electricity costspent on suppressing EMI also makes users sweat.

    Soft

  • 8/13/2019 CA-MDS R22-2009-5OHz

    12/30

  • 8/13/2019 CA-MDS R22-2009-5OHz

    13/30

    Page 13

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

  • 8/13/2019 CA-MDS R22-2009-5OHz

    14/30

    Page 14

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

  • 8/13/2019 CA-MDS R22-2009-5OHz

    15/30

    Page 15

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

  • 8/13/2019 CA-MDS R22-2009-5OHz

    16/30

    Page 16

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Ceiling Concealed Indoor Unit MCC Series

    FeaturesCentral air conditioning miniaturization, slim body, concealed type, spacing saving. ESP is optional,intelligent control and low noise.

    Speci cations

    Model MCC008TMCC010T

    MCC015T

    MCC018T

    MCC020T

    MCC025T

    MCC030T

    MCC040T

    MCC050T

    MCC060T

    Nominal cooling capacity W 2000 2500 3650 4500 5600 6500 7800 10600 12400 14400

    Nominal heating capacity W 2200 2600 3700 4700 6100 7400 8900 11600 14500 17300

    Nominal power input W 47 47 81 82 82 123 158 276 276 280

    Power supply V/Ph/Hz 220~240/1/50

    A i r f o w High m/h 450 450 580 800 800 960 1200 1900 1900 2100

    Medium m/h 370 370 470 650 650 780 950 1520 1520 1750

    Low m/h 280 280 380 540 540 600 800 1300 1300 1460

    External static pressure Pa 15(0/30/50) 30(15/50/70) 50(15/30/70)Dimension(W*D*H) mm 1054x469x220 1314x490x251 1664x490x251 1924x490x251

    Unit weight kg 22 22 22 25 25 27 28 39 39 45

    Sound level(H/M/L) dB(A) 31/29/27 31/29/27 34/32/30 35/32/29 35/32/29 37/36/35 42/40/38 47/45/43 47/45/43 48/46/44

    P i p i n

    g s

    i z e Liquid pipe mm(in) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8 9.52(3/8)

    Gas pipe mm(in) 9.52(3/8) 9.52(3/8) 12.7(1/2) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 19.05(3/4) 19.05(3/4) 19.05(3/4)

    Drain pipe R3/4

    Notes:1) All speci cations are subjected to change by the manufacturer without prior notice.2) Nominal speci cation are based on the conditions below: a) Cooling: 27 DB, 19 WB indoor temp. and 35 DB outdoor temp. b) Heating: 20 DB,15 WB indoor temp. and 7 DB, 6 WB outdoor temp.3) The external static pressure data in bracket are adjustable, they can be achieved by changing the

    connectors inside the junction box.4) Sound level are measured in an 11.5dB(A) background sound level anechoic chamber for units without

    return air plenum.

  • 8/13/2019 CA-MDS R22-2009-5OHz

    17/30

    Page 17

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Hot water coil HWT08-15 HWT18-32 HWT35-50 HWT60

    Applicable models MCC008TMCC010T

    MCC015T

    MCC018T

    MCC020T

    MCC025T

    MCC030T

    MCC040T

    MCC050T

    MCC060T

    Nominal heatingcapacity (W) 2200 2600 3700 4700 6100 7400 8900 11600 14500 17300

    Air rate (m 3/h) 450 450 580 850 850 1000 1200 1900 1900 2100Nominal heating

    capacity of the hotwater coil (W)

    3600 3600 4200 6300 6300 7200 8000 12000 12000 13500

    Water ow (m 3/h) 0.31 0.31 0.36 0.54 0.54 0.60 0.67 0.99 0.99 1.11 Air resistance (Pa) 7 7 13 12 12 17 23 31 31 26

    Water resistance (Pa) 2 2 3 6 6 7 9 11 11 17Net weight (kg) 9.5 9.5 9.5 11 11 11 11 14 14 15Coil rows (row) 2 2 2 2 2 2 2 2 2 2

    Optional Con gurations for MCC Series

    External accessory hot water coil

    Notes: Working condition for the heating capacity of the hot water coil: inlet water 60 C, outlet water 50 C.

    The air resistance listed in the above table is tested when the fan works in High mode. When the unit isequipped with a hot water coil, you must consider the air resistance of the hot water coil while setting theexternal static pressure.

    The hot water coil is externally installed at the air outlet of the indoor unit.

    Built-in accessory electric heater boxNominal heating capacity of the accessory electric heater (W) Model Power supply

    1000 MCC008T 220~240V/1Ph/50Hz

    1000 MCC010T 220~240V/1Ph/50Hz

    1200 MCC015T 220~240V/1Ph/50Hz

    2000 MCC018T 220~240V/1Ph/50Hz

    2000 MCC020T 220~240V/1Ph/50Hz

    2200 MCC025T 220~240V/1Ph/50Hz2200 MCC030T 220~240V/1Ph/50Hz

    3600 MCC040T 220~240V/1Ph/50Hz

    3600 MCC050T 220~240V/1Ph/50Hz

    3600 MCC060T 220~240V/1Ph/50Hz

    Notes: The permissible error for the above heating capacity of the electric heater must be within -10%~ +5%. The heating capacity of the accessory electric heater is tested when the indoor unit fan works at the

    rated air ow.

    External accessory electric heater box

    ModelNominal heating capacity of theaccessory electric heater (W) Power supply Applicable models

    HDP1.2T08-15 1200 220~240V/1Ph/50Hz MCC008T/MCC010T/MCC015T

    HDP2.4T08-15 2400 220~240V/1Ph/50Hz MCC008T/MCC010T/MCC015T

    HDP2.4TP18-15 2400 220~240V/1Ph/50Hz MCC018T/MCC020T/MCC025T/MCC030T

    HDP3.6T18-32 3600 220~240V/1Ph/50Hz MCC018T/MCC020T/MCC025T/MCC030T

    HDP2.4T35-45 2400 220~240V/1Ph/50Hz MCC040T

    HDP3.6T35-45 3600 220~240V/1Ph/50Hz MCC040T

    HDP4.8T35-50 4800 380~415V/3Ph/50Hz MCC040T/MCC050T

    HDP7.2T35-50 7200 380~415V/3Ph/50H MCC040T/MCC050T

    HDP5.4T60 5400 380~415V/3Ph/50H MCC060T

    HDP7.2T60 7200 380~415V/3Ph/50H MCC060T

    HDP10.8T60 10800 380~415V/3Ph/50H MCC060T

    Notes: The permissible error for the above heating capacity of the electric heater must be within -10%~ +5%. The electric heater box is externally installed at the air outlet of the indoor unit.

  • 8/13/2019 CA-MDS R22-2009-5OHz

    18/30

    Page 18

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Ceiling Cassette Indoor Unit MCK Series

    FeaturesElegant outlook, 4 way air supply, washable and build-in high ef ciency lter, fresh air introduction,micro-computer control, smooth drain and low noise.

    Speci cationsModel IndoorUnit

    MCK010T

    MCK015T

    MCK018T

    MCK020T

    MCK025T

    MCK030T

    MCK040T

    MCK050T

    MCK060T

    Nominal cool ing capacity W 2800 3600 4500 5400 6500 7500 10000 12500 14000

    Nominal heating capacity W 3200 3900 5000 5900 7200 8000 11000 13500 16000

    Nominal power input W 28 29 40 43 72 84 110 140 155

    Power supply V/Ph/Hz 220~240/1/50

    A i r f o w High m/h 500 590 670 720 1200 1300 1360 1650 1800

    Medium m/h 400 490 560 610 1100 1060 1200 1450 1500

    Low m/h 330 430 490 520 960 850 1110 1350 1350

    Dimension(W*D*H) mm 930x930x278 930x930x363

    Unit weight kg 34 38 47 .5Sound level(High/Medium/Low) dB(A) 32/28/24 34/29/26 37/32/29 39/35/31 42/40/38 45/43/41 46/44/42 48/45/42 50/47/44

    P i p i n g s i z e Liquid pipe mm(in) 6.35(1/4") 9.52(3/8" ) 9.52(3/8")

    Gas pipe mm(in) 9.52(3/8") 12.7(1/2") 15.8(5/8" ) 19.05(3/4")

    Drain pipe mm 20.5

    Notes: 1) All speci cations are subjected to change by the manufacturer without prior notice.2) Nominal speci cation are based on the conditions below: a) Cooling: 27 DB, 19 WB indoor temp. and 35 DB outdoor temp. b) Heating: 20 DB,15 WB indoor temp. and 7 DB, 6 WB outdoor temp.

    3) Sound level are measured in an 11.5dB(A) background sound level anechoic chamber for units withoutreturn air plenum.

  • 8/13/2019 CA-MDS R22-2009-5OHz

    19/30

    Page 19

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    High Static Pressure Duct Unit MDB Series

    Speci cations

    FeaturesInstalled above ceiling with supply air duct. Meet long distance air supply.

    Notes:1) All speci cations are subjected to change by the manufacturer without prior notice.2) Nominal speci cation are based on the conditions below: a) Cooling: 27 DB, 19 WB indoor temp. and 35 DB outdoor temp. b) Heating: 20 DB, 15 WB indoor temp. and 7 DB, 6 WB outdoor temp.3) Sound level are measured in an 11.5dB(A) background sound level anechoic chamber for units without

    return air plenum.

    Model Indoor Unit MDB050T MDB060T MDB080T MDB100TNominal cooling capacity W 12500 14000 22400 28000Nominal heating capacity W 14000 16500 25000 31500Nominal power input W 615 790 1700 1480

    Air ow(High/Medium/Low) m/h 2550/2040/1650 3000/2540/1920 4200/3740/3000 5000External static pressure Pa 100 100 100 150Power supply V/Ph/Hz 220~240/1/50 380~415/3/50Dimension(W*D*H) mm 1230X910X350 1430X910X350 1690x879x420 1690x1020x520Unit weight kg 69 75 100 150Sound level(High/Medium/Low) dB(A) 48/46/44 50/48/46 57/55/52 57

    Piping sizeLiquid pipe mm(in) 9.52(3/8") 9.52(3/8") 12.7(1/2") 12.7(1/2")Gas pipe mm(in) 19.05(3/4") 19.05(3/4") 28.6(1-1/8") 28.6(1-1/8")Drain pipe R3/4

  • 8/13/2019 CA-MDS R22-2009-5OHz

    20/30

    Page 20

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Ceiling Exposed and Floor Standing Indoor UnitMCM Series

    FeaturesElegant design, horizontal and vertical comfortable air supply, washable air lter, convenient installationand simple maintenance.

    Speci cations

    Notes:1) All speci cations are subjected to change by the manufacturer without prior notice.2) Nominal speci cation are based on the conditions below: a) Cooling: 27 DB, 19 WB indoor temp. and 35 DB outdoor temp. b) Heating: 20 DB, 15WB indoor temp. and 7 DB, 6 WB outdoor temp.3) Sound level are measured in an 11.5dB(A) background sound level anechoic chamber for units without

    return air plenum.

    Model Indoor Unit MCM020T MCM030T MCM050T

    Nominal cooling capacity W 5800 7500 12500

    Nominal heating capacity W 5800 8000 13500

    Air ow(High/Medium/Low) m/h 1100/970/750 1300/1100/870 1850/1550/1200

    Nominal power input W 81 116 161Power supply V/Ph/Hz 220~240/1/50

    Dimension(W*D*H) mm 1214X670X214 1214X670X249 1714X670X249

    Unit weight kg 39 44 64

    Sound level(High/Medium/Low) dB(A) 48/45/42 50/46/43 52/48/44

    Pipingsize

    Liquid pipe mm(in) 9.52(3/8" ) 9.52(3/8" ) 9.52(3/8" )

    Gas pipe mm(in) 15.88(5/8" ) 15.88(5/8" ) 19.05(3/4" )

    Drain pipe mm 20.5

  • 8/13/2019 CA-MDS R22-2009-5OHz

    21/30

    Page 21

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Wall Mounted Indoor Units MWM Series

    FeaturesElegant design, washable air lter, simple control and convenient maintenance.

    Speci cations

    Notes:1) All speci cations are subjected to change by the manufacturer without prior notice.2) Nominal speci cation are based on the conditions below: a) Cooling: 27 DB, 19 WB indoor temp. and 35 DB outdoor temp. b) Heating: 20 DB, 15WB indoor temp. and 7 DB, 6 WB outdoor temp.3) Sound level are measured in an 11.5dB(A) background sound level anechoic chamber for units without

    return air plenum.

    Model Indoor Unit MWM008T MWM010T MWM015T MWM020T MWM025T

    Nominal cooling capacity W 2200 2780 3520 5400 6500

    Nominal heating capacity W 2200 2780 3520 5400 6500

    Air ow(High/Medium/Low) m/h 460/330/270 510/420/320 590/500/370 860/720/590 1100/790/680

    Nominal power input W 24 36 40 48 68

    Power supply V/Ph/Hz 220~240/1/50

    Dimension(W*D*H) mm 799x198x260 899x198x260 899x198x260 1062x222x304 1062x222x304

    Unit weight kg 25 30 35 36 36

    Sound level(High/Medium/Low) dB(A) 39/34/28 39/34/28 42/36/29 44/40/35 49/43/40

    Pipingsize

    Liquid pipe mm(in) 6.35(1/4" ) 6.35(1/4" ) 6.35(1/4" ) 6.35(1/4" ) 9.52(3/8" )

    Gas pipe mm(in) 9.52(3/8" ) 9.52(3/8" ) 12.70(1/2" ) 15.88(5/8" ) 15.88(5/8" )Drain pipe mm 16.5 20.5

  • 8/13/2019 CA-MDS R22-2009-5OHz

    22/30

    Page 22

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Model MDBX050T MDBX080T MDBX100T MDBX120T MDBX180T MDBX220T MDBX240T

    Nominal cooling capacity W 14000 24500 28000 32500 45000 56000 65000

    Nominal heating capacity W 8100 12900 16200 18000 27000 33500 40000

    Air ow m 3/h 1100 1700 2100 2700 4000 5000 6000

    Power supply V/Ph/Hz 220~240/1/50 380~415V/3Ph/50Hz

    External static pressure Pa 105 120 150 150 200 250 250

    Sound level dB(A) 42 43 45 55 56 58 60

    P i P i n g

    S i z e

    Liquid pipe mm(in) 9.52(3/8") 12.7(1/2") 12.7(1/2") 15.88(5/8") 15.88(5/8") 19.05(3/4") 19.05(3/4")

    Gas pipe mm(in) 19.05(3/4") 28.6(9/8") 28.6(9/8") 28.6(9/8") 34.9(11/8") 38.1(3/2") 38.1(3/2")

    Drain pipe mm R3/4

    Dimension(W*D*H) mm 470x780x1250 470x1380x1250 470x1380x1250 470x1380x1250 520x1580x1020 520x1580x1020 52015801020

    Outdoor unit MDS060AR MDS080BR MDS100BR MDS120BR MDS180BR MDS220BR MDS240BR

    Notes:1) All speci cations are subjected to change by the manufacturer without prior notice.2) Nominal speci cation are based on the conditions below: a) Cooling capacity is based on 33/28 (DB/WB) outdoor air temperature (68%RH). b) Heating capacity is based on 0/-2.9 (DB/WB) outdoor air temperature (50%RH).

    3) Sound values are obtained before delivery. They may differ in practice due to environmental sound orother reasons. The sound level is measured in an 11.5dB(A) background sound level anechoic chamberfor units without return air plenum.

    4) The fresh air unit cannot share the same outdoor unit with other MDS indoor units.

    MDBX Fresh Air UnitsMDS fresh air system provides more flexibility in fresh air handing. The independent fresh air system cantreat outdoor air directly into either supply air or indoor air flow for cycle. The extra-high external staticpressure can carry the fresh air as far as to each room.

    MDS fresh air system MDS air conditioning system

    Speci cations

  • 8/13/2019 CA-MDS R22-2009-5OHz

    23/30

    Page 23

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Outdoor Unit Speci cation

    Notes:1) All speci cations are subjected to change by the manufacturer without prior notice.2) Nominal speci cation are based on the conditions below: a) Cooling capacity is based on 27/19 (DB/WB) indoor air temperature, 35/24 (DB/WB) outdoor air temperature.

    b) Heating capacity is based on 20/15 (DB/WB) indoor air temperature,7/6 (DB/WB) outdoor air temperature.3) Sound level are measured in an 11.5dB(A) background sound level. They may differ in practice due to

    environmental sound or other reasons.

    Model MDS030A MDS030AR MDS040A MDS040AR MDS050A MDS050AR MDS060A MDS060AR

    Nominal cooling capacity kW 8.5 8.5 10 10 12.5 12.5 14.5 14.5

    Nominal heating capacity kW - 9 - 11.5 - 13.5 - 16.5Power supply V/Ph/Hz 220~240/1/50

    Dimension(W*D*H) mm 840x408x900 1058x430x1044 1058x430x1247

    Unit weight kg 82 85 112 115 117 120 123 130

    Nominal cooling power input kW 3.0 3.0 3.6 3.6 4.4 4.4 5.0 5.0

    Nominal cooling current A 13.6 13.6 15.9 15.9 20 20 22.8 22.8

    Nominal heating power input kW - 2.5 - 3.4 - 4.2 - 4.2

    Nominal heating current A - 11.4 - 15.5 - 19 - 20.3

    Refrigerant R22Pipe

    connecttype

    Liquid pipe Flare and threaded connection

    Gas pipe Flare and threaded connection

    P i p

    i n g

    s i z e Liquid pipe mm (in.) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)

    Gas pipe mm (in.) 15.88 (5/8) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)

    Model MDS050A MDS050AR MDS060A MDS060AR MDS070A MDS070AR

    Nominal cooling capacity kW 12.5 12.5 15 15 18 18

    Nominal heating capacity kW - 13.5 - 17 - 20

    Power supply V/Ph/Hz 380~415/3/50

    Dimension(W*D*H) mm 1058x430x1044 1058x430x1247 1058x430x1445

    Unit weight kg 117 120 123 130 135 140

    Nominal cooling power input kW 4.4 4.4 5.0 5.0 6.2 6.2

    Nominal cooling current A 8.4 8.4 9.6 9.6 11.5 11.5

    Nominal heating power input kW - 4.2 - 4.23 - 6.0

    Nominal heating current A - 8.0 - 8.8 - 10.6

    Refrigerant R22

    Pipe connecttype

    Liquid pipe Flare and threaded connection

    Gas pipe Flare and threaded connection

    P i p i n g

    s i z e Liquid pipe mm (in.) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)

    Gas pipe mm (in.) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)

    MDS A Series

  • 8/13/2019 CA-MDS R22-2009-5OHz

    24/30

    Page 24

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Outdoor Unit Speci cation

    Model MDS080B MDS080BR MDS100B MDS100BR MDS120B MDS120BR

    Nominal cooling capacity kW 24.5 24.5 28.0 28.0 32.5 32.5

    Nominal heating capacity kW - 26.0 - 30.0 - 34.0

    Air ow m 3/h 11000 11000 11000 11000 12500 12500Power supply V/Ph/Hz 380~415/3/50

    Sound level dB(A) 62 62 64 64 66 66

    Dimension(W*D*H) mm 990x840x1840

    Unit weight kg 275 290 285 300 290 305

    Nominal cool ing power input kW 7.5 7.5 8.5 8.5 9.8 9.8

    Nominal cooling current A 14.6 14.6 16.8 16.8 18.8 18.8

    Nominal heating power input kW - 7.2 - 8.3 - 9.0

    Nominal heating current A - 13.6 - 15.7 - 16.7

    Refrigerant R22

    Pipe connect

    type

    Gas pipe Solder, ange connection

    Liquid pipe Flare and threaded connectionLiquid pipe mm(in) 12.7(1/2) 15.88(5/8)

    Gas pipe mm(in) 28.6(9/8)

    Model MDS150B MDS150BR MDS180B MDS180BR MDS200B MDS200BR

    Nominal cooling capacity kW 40.0 40.0 47.5 47.5 50.0 50.0

    Nominal heating capacity kW - 43.0 - 50.0 - 53.0

    Air ow m 3/h 13500 13500 11000x2 11000x2 11000x2 11000x2

    Power supply V/Ph/Hz 380~415/3/50

    Sound level dB(A) 67 67 66 66 66 66Dimension(W*D*H) mm 1290x840x1840 1990x840x1840

    Unit weight kg 355 370 520 550 560 590

    Nominal cooling power input kW 12.9 12.9 14.1 14.1 15.2 15.2

    Nominal cooling current A 23.1 23.1 28.2 28.2 31.1 31.1

    Nominal heating power input kW - 11.1 - 13.2 - 14.7

    Nominal heating current A - 22.6 - 27.1 - 29.4

    Refrigerant R22

    Pipe connecttype

    Gas pipe Solder, ange connection

    Liquid pipe Flare and threaded connection

    Liquid pipe mm(in) 15.88(5/8)

    Gas pipe mm(in) 34.9(11/8)

    Notes:1) All speci cations are subjected to change by the manufacturer without prior notice.2) Nominal speci cation are based on the conditions below:

    a) Cooling: 27 DB, 19 WB indoor temp. and 35 DB, 24 WB outdoor temp. b) Heating: 20 DB,15 WB indoor temp. and 7 DB, 6 WB outdoor temp.

    3) Sound level are measured in an 11.5dB(A) background sound level. They may differ in practice due toenvironmental sound or other reasons.

    MDS B Series

  • 8/13/2019 CA-MDS R22-2009-5OHz

    25/30

    Page 25

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Model MDS220B MDS220BR MDS240B MDS240BR MDS260B MDS260BR

    Combination -- -- -- -- MDS120BM+MDS150BSMDS120BRM+MDS150BRS

    Nominal cooling capacity kW 55.0 55.0 65.0 65.0 70.0 70.0

    Nominal heating capacity kW - 58.0 - 68.0 - 75.0

    Air ow m 3/h 11000x2 11000x2 12500x2 12500x2 12500+ 13500 12500+13500

    Power supply V/Ph/Hz 380~415/3/50

    Sound level dB(A) 66 66 68 68 68 68

    Dimension(W*D*H) mm 1990x840x1840 2280x840x1840

    Unit weight kg 560 590 570 600 645 675

    Nominal cooling power input kW 16.7 16.7 19.8 19.8 21.3 21.3

    Nominal cooling current A 32.7 32.7 38.5 38.5 40.0 40.0

    Nominal heating power input kW - 16.2 - 18.5 - 20.9

    Nominal heating current A - 31.0 - 33.8 - 37.2

    Refrigerant R22

    Pipe connect

    type

    Gas pipe Solder, ange connection

    Liquid pipe Flare and threaded connectionLiquid pipe mm(in) 19.05(3/4) 19.05(3/4)

    Gas pipe mm(in) 38.1(3/2) 41.3(13/8)

    Notes:1) All speci cations are subjected to change by the manufacturer without prior notice.2) Nominal speci cation are based on the conditions below:

    a) Cooling: 27 DB, 19 WB indoor temp. and 35 DB, 24 WB outdoor temp. b) Heating: 20 DB,15 WB indoor temp. and 7 DB, 6 WB outdoor temp.

    3) Sound level are measured in an 11.5dB(A) background sound level. They may differ in practice due toenvironmental sound or other reasons.

    Model MDS280B MDS280BR MDS300B MDS300BR MDS320B MDS320BR

    Combination MDS150BM+MDS130BSMDS150BRM+MDS130BRS

    MDS150BM+MDS150BS

    MDS150BRM+MDS150BRS

    MDS160BM+MDS160BS

    MDS160BRM+MDS160BRS

    Nominal cooling capacity kW 75.0 75.0 80.0 80.0 85.0 85.0

    Nominal heating capacity kW - 80.0 - 85.0 - 92.0

    Air ow m 3/h 13500x2 13500x2 13500x2 13500x2 13500x2 13500x2

    Power supply V/Ph/Hz 380~415/3/50

    Sound level dB(A) 69 69 69 69 69 69

    Dimension(W*D*H) mm 2580x840x1840

    Unit weight kg 710 740 710 740 720 750

    Nominal cooling power input kW 22.8 22.8 26.2 26.2 27.7 27.7

    Nominal cooling current A 42.5 42.5 46.5 46.5 49.5 49.5

    Nominal heating power input kW - 22.0 - 23.6 - 25.5

    Nominal heating current A - 41.0 - 43.1 - 46.0

    Refrigerant R22

    Pipe connecttype

    Gas pipe Solder, ange connection

    Liquid pipe Flare and threaded connection

    Liquid pipe mm(in) 19.05(3/4)

    Gas pipe mm(in) 41.3(13/8)

    Outdoor Unit Speci cation

  • 8/13/2019 CA-MDS R22-2009-5OHz

    26/30

    Page 26

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    MDS

    MDS

    Capable of monitoring 1536 (32x48) indoor unitssimultaneously in real time

    Central ControlMDS system can be connected up to 48 indoor units. 32 outdoor units can be controlled in a network througha centralized controller. The monitor software can monitor 1536 (32x48) indoor units in real time at the same

    time. The communication cables between indoor units and outdoor units are very easy to arrange. MDS systemhas a strong function of displaying the malfunction, which can save maintenance time and cost.

    MDS system real time control interface

    Reliable

    MDS system adopts the advantaged capacity modulation technology to reduce the control devices, whichreduce the malfunction odds mostly.

    MDS system has excellent oil return performance even at low capacities, which will make sure that all of theremovable parts of the compressor can be lubricated and cooled down. Thus, the compressor remainsreliable throughout operation.It reduces the start/stop times, which will reduce the attack to the electricity supply net.The PWM (Pulse Width Modulation) valve has the longevity of 40 million times.The design is simple and there is no requirement for bypass valve.

    Wired control + Remote control Remote control Central control

    Dongle Key

    McQuay Software Management System

  • 8/13/2019 CA-MDS R22-2009-5OHz

    27/30

    Page 27

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Real-time Monitor System monitor software: Powerful MDS real-time monitor software can implement indoor control, systemcontrol, circuit control and service control. It helps users or serving personnel to view detailed parameters andunit data.Description of main control functions:

    Indoor Monitoring

    System MonitoringDisplay the types and status of all the indoor units in the system, including alarm and timing.

    Circuit Monitoring *Select and view the system diagram, running parameters of outdoor units, andrunning parameters of all the indoor units.

    Service Monitoring *The current running parameters and the curves of history records of outdoor and indoor units can be displayed.

    Note: * Only authorized maintenance personnel can use this window.

    Set the mode, fan speed, auxiliary setting, and temperature of indoor units. Switch on/off indoor units.(Youcan operate several units or several machines in several units at the same time.)Set indoor units and outdoor units in groups. You can customize the group settings. (The default groups areby outdoor units.)Display alarms and check alarms. (You can check malfunction of outdoor or indoor units by selectingnumbers.)Set timing mode and set the timing mode of indoor units. (You can set and save the timing mode of the unitswithout any limitation.)

    Description of icons of indoor units:

    Small icon

    Description

    The timingfunction of this indoor unit isenabled

    The wiredcontroller of this indoor unitis locked. Youcannot controlit through thecable controller.

    Faults occur tothis indoor unit.Double-click thisicon to view thedetails.

    Description of icons of each type:

    Icon Switching off Cooling Heating Dehumidifying Ventilating

    MCK

    TYPE

    MCC

    MDB

  • 8/13/2019 CA-MDS R22-2009-5OHz

    28/30

    Page 28

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Flexible and Convenient Selection Software

    The selection software designed for different models allows you to select and verify unit models as requiredby customers, and determine the models of indoor and outdoor units as well as the required quantity of refnet

    joints and pipes. Thus, the selection software enables you to carry out complex unit design and selectionmore easily and quickly with a single click.

  • 8/13/2019 CA-MDS R22-2009-5OHz

    29/30

    Page 29

    Featuring Leading-edge Digital TechnologyMcQuay Multi Digital Scroll R22 Series

    Type Model Name Picture Units Remark

    Electronicexpansion valve

    box

    MEX MCC, MCK, MCM,MWM indoor units Standard

    Wireless Remotecontroller NA

    MCM, MCK, MWMindoor units Standard

    Wired controller NA MCC, MDB indoorunits Standard

    Remote control ler NA Working with thewired controller Optional

    Central controller MC-CCS02B All Optional

    Refnet joint MDS-Yl All Optional

    Refnet joint (with insulation)

    MDS-YI-A All Optional

    Twisted-pair NA All Optional

    Central controlsoftware MC-CCS01A All Optional

    Accessories

    Note:There are two types of refnet joint, Y-typeandC-type. We strongly recommend that the customer selectthe refnet joint provided by the factory. If other brands refnet joint is selected, it may result in bad effects to

    the system.

  • 8/13/2019 CA-MDS R22-2009-5OHz

    30/30

    2009 McQuay International +1 (800) 432-1342 www.mcquay.com

    While utmost care is taken in ensuring that all details in the publication are correct at the time of going

    to press, we are constantly striving for improvement and therefore reserve the right to alter model

    speci cations and equipment without notice.Details of speci cations and equipment are also subject to change to suit local conditions and requirements

    Literature No.: CA-MDS(R22)-0808A Supersedes: Nothing Part No.: M08039130004

top related