All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
UL Listed, FM Approved Fire Pump Sets
– Horizontal Split Case Pumps
• Flows from 200-5000 US GPM
– Vertical Turbine
• Flows to 5000 US GPM
– In-Line Pumps
• Flows to 750 US GPM
– End Suction
• Flows to 1500 US GPM
– Residential 13D
• Flows to 70 US GPM
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
What’s new and coming up…
Grooved end jockey pumps – Already standard
Grooved increasers standard with NBG packs
– New standard
– Class 250# flanges
Grooved fire pumps – Spring 2013
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Types of Fire Pumps
Split Case Fire Pumps
Inline Fire Pumps
Vertical Turbine Fire Pumps
End Suction Fire Pumps
Residential 13D Fire pumps
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Everything you need to
know about fire pumps….
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
HORIZONTAL SPLIT CASE ELECTRIC
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
HORIZONTAL SPLIT CASE DIESEL
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Split Case Fire Pump Models
• Ease of Installation and Maintenance
• Longevity and Durability
• Serviceability
• Reliability
• Typical applications
• Warehouse
• Hospital
• Manufacturing plant
• University or large school
• Office High Rise
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
VERTICAL INLINE (ELECTRIC ONLY)
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Vertical In-Line
Requires less space than split case pump of the same capacity
Typically Less expensive
Motor can be serviced without disconnecting suction & discharge flanges from piping
Typical applications
Small schools
Churches
Parking garages
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Vertical Turbine
Fire Pumps
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Vertical Turbine Design Features
No priming
Adaptability to water level
Adaptability to various driver combinations
Compact “footprint”
No alignment necessary
Minimal maintenance
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Vertical Turbine Applications
Vertical Turbines
Applications where city water is not available
Ponds and lakes to utilize water supply
Only pump approved for suction lift conditions
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
90% rule…
90% of what drives a pump quote is?
Flow
Pressure
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Electric or Diesel?
Electric sets are typically used where there is a reliable source of power
What to ask.. – What voltage?
• 208? 230? 460?
– Transfer Switch? • Transfer switch is used when the source of power may not be reliable and/or
precaution.
– Transfer switch for 2nd utility – Starting method?
• Full voltage?
– across the line • Reduced Voltage?
– Part winding
– Primary reactor
– Wye Delta Open
– Wye Delta closed
– Soft Start
– Auto Transformer
That’s all you need to know……. See rapid
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Typical Brands of Fire Pump Controllers
– Firetrol
– Master
– Metron
– Cutler Hammer
– Joslyn Clarke
– Tornatech
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Electric motors
Electric motors are used to drive
– Horizontal split case
– End suction
– Vertical inline
– Vertical turbine
Motors are selected based on
– Voltage
– HP required by the pump
– Frame size
– Configuration of pump (i.e. vertical or horizontal)
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Typical Brands of Electric Motors
– WEG Motors
– US Electric Motors
– Marathon
– GE
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Why Diesel?
Diesel units are used primarily where there is not a reliable source of power or by preference
Typical Engine Manufacturers – Clarke engines (John Deere)
– Cummins
– Caterpiller
Diesel units may drive – Horizontal split case
– Vertical turbine
– End suction
Engines are selected based on – HP of pump requirement
– RPM
– EPA emissions standards as stated on presentation below
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Diesel controllers
Diesel engine fire pumps are especially nice because of
how reliable they can be and by the inexpensive control
panel.
There are only a few options tend to be required on diesel
control panels. The most distinct difference is voltage of
the battery used to back up the engine
– 12 volt DC?
– 24 volt DC?
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
What is a jockey pump?
A jockey pump is a pressure maintenance pump set so that in the event of slight fluctuations in sprinkler system pressure, the fire pump will not need to turn on.
Typically set 10 psi over the fire pump
Jockey pumps are replaced frequently and can be purchased from you….
What to ask? In order to sell a jockey pump, you will need to know. If the customer is replacing a jockey pump, you will at least need to know the following
– Boost pressure (can be found by adding at least 10 psi to the fire pump pressure setting
– HP (should be on the motor nameplate or jockey pump controller)
– Voltage (also on motor nameplate or jockey pump controller)
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Jockey Pumps
Regenerative Turbine Pumps
Vertical Multi-stage
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Jockey pump controller
Jockey pump controllers
very small and meant to
supply power exclusively to
the jockey pump
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Fire pump accessories and NFPA 20
NFPA 20 suggests minimum pipe and accessory sizes
based on flow. In the chart below, you can see how based
on the flow, you can select what size flow meter you might
need, what size suction and discharge pipe is needed and
what size test header etc… Thought you do not need to
memorize this chart, it is a helpful tool….
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Fire Pump Standards
NFPA-20 Minimum Pipe Sizes For Fire Systems
Based on NFPA-20, 1996 Edition
Pump Rating in Suction Discharge Relief Relief Valve Meter Number and Size of Hose Hose Header GPM In. In. Valve In. Discharge In. Device In. Valves In. Supply In.
25 1 1 3/4 1 1-1/4 (1) 1-1/2 1
50 1-1/2 1-1/4 1-1/4 1-1/2 2 (1) 1-1/2 1-1/2
100 2 2 1-1/2 2 2-1/2 (1) 2-1/2 2-1/2
150 2-1/2 2-1/2 2 2-1/2 3 (1) 2-1/2 2-1/2
200 3 3 2 2-1/2 3 (1) 2-1/2 2-1/2
250 3-1/2 3 2 2-1/2 3-1/2 (1) 2-1/2 3
300 4 4 2-1/2 3-1/2 3-1/2 (1) 2-1/2 3
400 4 4 3 5 4 (2) 2-1/2 4
450 5 5 3 5 4 (2) 2-1/2 4
500 5 5 3 5 5 (2) 2-1/2 4
750 6 6 4 6 5 (3) 2-1/2 6
1000 8 6 4 8 6 (4) 2-1/2 6
1250 8 8 6 8 6 (6) 2-1/2 8
1500 8 8 6 8 8 (6) 2-1/2 8
2000 10 10 6 10 8 (6) 2-1/2 8
2500 10 10 6 10 8 (8) 2-1/2 10
3000 12 12 8 12 8 (12) 2-1/2 10
3500 12 12 8 12 10 (12) 2-1/2 12
4000 14 12 8 14 10 (16) 2-1/2 12
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Fire Pump System Components
Electric Fire Pumps
• Pump, base, coupling & guard
• Electric motor
• Controller - motor
• Suction and discharge gauges
• Automatic air release valve
• Casing relief valve
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Fire Pump System Components
Diesel Fire Pumps
• Pump, base, coupling & guard
• Diesel engine & fuel tank
• Controller - engine
• Suction and discharge gauges
• Automatic air release valve
• Batteries, racks & cables
• Cooling loop
• Commercial grade muffler, flexible exhaust connector & fittings
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Accessories for Fire Pump
ClaVal 55L Casing relief Valve
ClaVal 2050B-4KG Main Relief
Valve
ClaVal 90G-21 Pressure
Reducing Valve
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Additional Accessories for fire pump
Suction side eccentric reducer
Discharge side concentric increaser
Test Header
Hose valves caps and chains
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
Residential 13D
The Resistream comes in 2 styles both the open unit with
corrosion resistant base for mounting as well as the fully
enclosed unit for simple and complete installation.
Both units are available in either 115 or 220 volt single phase
power depending on horsepower
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
How well do you know Fire Pumps?
Fill in the blanks
The first thing to ask when looking for a fire pump quote is the
required ________________ and __________________
What are the 4 main types of fire pumps?
– Horizontal ___________ __________
– Vertical _______
– ___________ Turbine
– End ___________
Is the pump set driven by ____________ motor or
_________________ Engine
Do you need a __________ __________ (hint adds $13,000)
What is the site _____________? (hint 208/230/460)
All rights reserved by SPP Pumps Ltd All rights reserved by SPP Pumps Ltd
I need a 1000 gpm at 90 psi fire pump, what size jockey do I need?
What are the 3 points on a NFPA 20 pump curve? – ______________ (no flow)
– _______________ %
– _______________ %
You have a 500 gpm fire pump, what is the flow at 100%? – ______________________