annual fire alarm inspection - forsyth.k12.ga.us...smoke detectors 4098-9714 interstate control...

520
Annual Fire Alarm Inspection Job # Date Name Address City State Zip Fire Control Panel Inspection Manufacturer Panel Location Account # Total Devices Number of Devices Failed 1 0 6 0 14 8 32 0 129 0 1 0 21 0 3 0 5 0 Inspector Name : Signature: Heat Detectors Simplex 4098-9733 Duct Detectors Simplex 4098-9756 David Piorkowski Pass Pullstations Smoke Detectors 4098-9714 Interstate 4100U Control Panel Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex 2099-9101 Who Was Notified Prior to the Start of Testing Monitoring Company & Office Staff Batteries SLA1116 Open Circuits are Detected by Fire Alarm Control Panel Pass Pass Loss of AC is Detected by the Fire Alarm Control Panel Ground Faults Detected by Control Panel Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival Ground fault Panel Secondary power loss Open Circuit Detection Power Supplies Simplex 4009 All- Star Fire LLC Model Device Summary Manufacturer TBD EMC Security Monitoring Company Loss of Secondary Power (Batteries/Generator) is Detected 3284 Medlock Bridge Rd Suite 300 Norcross, GA 30092 Interfaced Equipment Tested for Circuit Supervision Pass Pass Panel Power Loss Pass Are Lamps and Displays Operating Properly (678) 691-0011 6800 Little Mill Road 30041 Simplex Rm 2500 Parent Reception Model Name Cumming GA Is the Panel Monitored Yes 4100U EI1273 Little Mill Middle School 6/16/2020 Waterflow Switches Potter VSR-F Tamper Switches AnvilStar AE7722-3A All-Star Fire, LLC 3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Upload: others

Post on 31-Aug-2021

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

6 0

14 8

32 0

129 0

1 0

21 0

3 0

5 0

Inspector Name : Signature:

Heat Detectors Simplex 4098-9733

Duct Detectors Simplex 4098-9756

David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Interstate

4100UControl Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Simplex

Simplex

2099-9101

Who Was Notified Prior to the Start of Testing Monitoring Company & Office Staff

Batteries SLA1116

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Simplex 4009

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Pass

Are Lamps and Displays Operating Properly

(678) 691-0011

6800 Little Mill Road

30041

Simplex

Rm 2500 Parent Reception

Model Name

Cumming GA

Is the Panel Monitored Yes

4100U

EI1273

Little Mill Middle School

6/16/2020

Waterflow Switches Potter VSR-F

Tamper Switches AnvilStar AE7722-3A

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 2: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.3 Pass

Good (2019) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Pass

N/A

Pass

Pass

Pass

N/A

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Continued on Page 3 - Battery Testing

FACP (Right) 12V 18AH

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Magnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 18AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 3: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Floor Condition Voltage Load Test

2 Fair (2017) 13.6 Fail

2 Fair (2017) 13.5 Fail

2 Fair (2017) 14.1 Fail

2 Fair (2017) 10.8 Fail

2 Good (2018) 13.6 Pass

2 Good (2018) 13.7 Pass

1 Good (2018) 13.8 Pass

1 Good (2018) 13.7 Pass

1 Fair (2017) 13.5 Fail

1 Fair (2017) 13.4 Fail

1 Poor (2017) 13.4 Fail

1 Poor (2017) 13.4 Fail

BPS #4 Rm 1120 (Right) 12V 7AH

BPS #3 Rm 2121 (Left) 12V 7AH

BPS #3 Rm 2121 (Right) 12V 7AH

BPS #4 Rm 1120 (Left) 12V 7AH

BPS #2 Rm 2592 (Left) 12V 7AH

BPS #2 Rm 2592 (Right) 12V 7AH

BPS #1 Rm 2592 (Right) 12V 7AH

Battery Testing (continued)

Location Size

BPS #1 Rm 2592 (Left) 12V 7AH

BPS #5 Rm 1243 (Left) 12V 7AH

BPS #5 Rm 1243 (Right) 12V 7AH

BPS #6 Rm 1275 (Left) 12V 7AH

BPS #6 Rm 1275 (Right) 12V 7AH

Page 4: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Pull Station 1100 HALL @ STAIRWELL Lower M1 1 Pass

Smoke Detector 1100 HALL @ STAIRWELL SMK DRS Lower M1 2 Pass

Smoke Detector 1100 HALL END OF CORR SMK DRS Lower M1 3 Pass

Smoke Detector 1100 HALL END OF CORR SMK DRS Lower M1 4 Pass

Duct Detector 1100 HALL GIRLS REST RM Lower M1 5 No Access

Duct Detector 1100 HALL GIRLS REST RM Lower M1 6 Pass

Monitor HALL KITCHEN 1218 HOOD Lower M1 7 Pass

Smoke Detector 1100 HALL ELECT RM 1120 Lower M1 8 Pass

Smoke Detector 1100 HALL SMK DRS Lower M1 9 Pass

Smoke Detector 1100 HALL SMK DRS Lower M1 10 Pass

Smoke Detector 1100 HALL COMMONS AREA SMK DRS Lower M1 11 Pass

Smoke Detector 1100 HALL COMMONS AREA SMK DRS Lower M1 12 Pass

Smoke Detector ELEVATOR LOBBY 1012 Lower M1 13 Pass

Smoke Detector 2500 HALL MAIN OFF. EXIT DOOR Upper M1 14 Pass

Heat Detector ELEVATOR EQUIP RM 1010 Lower M1 16 Pass

Smoke Detector ELEVATOR EQUIP RM 1010 Lower M1 17 Pass

Pull Station EXIT LOWER LEVEL COMMONS Lower M1 18 Pass

Smoke Detector 1200 COMMONS AREA SMK DRS Lower M1 19 Pass

Smoke Detector 1200 COMMONS AREA SMK DRS Lower M1 20 Pass

Pull Station EXIT LOWER LEVEL COMMONS Lower M1 21 Pass

Smoke Detector 1200 HALL SMK DRS Lower M1 22 Pass

Smoke Detector 1200 HALL SMK DRS Lower M1 23 Pass

Duct Detector 1200 HALL MECH RM 1230 Lower M1 26 Pass

Duct Detector 1200 HALL MECH RM 1230 Lower M1 27 Pass

Pull Station HALL @ RM 1233 Lower M1 28 Pass

Pull Station 1200 HALL MECH RM 1230 Lower M1 29 Pass

Pull Station 1200 HALL ART LAB RM 1240 Lower M1 30 Pass

Pull Station OUTSIDE MECH RM 1301 Lower M1 31 Pass

Pull Station 1200 HALL TECH LAB RM 1235 Lower M1 32 Pass

Pull Station OUTSIDE MECH RM Lower M1 33 Pass

Smoke Detector 1200 HALL ELEC RM 1243 Lower M1 34 Pass

Smoke Detector 1200 HALL CLASS RM 1215 Lower M1 35 Pass

Duct Detector MECH RM THRU RM 2532 Upper M1 36 Pass

Pull Station HALL EXIT ACROSS FROM 1255 Lower M1 37 Pass

Smoke Detector 1200 HALL @ STAIR 1255 SMK DRS Lower M1 39 Pass

Smoke Detector 1200 HALL @ STAIR 1255 SMK DRS Lower M1 40 Pass

Smoke Detector 1200 HALL @ STAIR 1255 SMK DRS Lower M1 41 Pass

Smoke Detector 1200 HALL SMK DRS @ GYM LOBBY Lower M1 42 Pass

Smoke Detector HALL SMK DRS @ GYM LOBBY Lower M1 43 Pass

Smoke Detector 1200 HALL IN STAIR 1255 SMK DRS Lower M1 44 Pass

Pull Station 1200 HALL IN STAIR 1255 Lower M1 45 Pass

Smoke Detector 1200 HALL SMK DRS @ GYM LOBBY Lower M1 46 Pass

Smoke Detector 1200 HALL SMK DRS @ GYM LOBBY Lower M1 47 Pass

Smoke Detector GYM ENTRANCE LOBBY Lower M1 48 Pass

Smoke Detector GYM ENTRANCE Lower M1 49 Pass

Pull Station 1200 HALL EXIT IN RM 1261 Lower M1 50 Pass

Smoke Detector GYM ENTRANCE LOBBY Lower M1 51 Pass

Smoke Detector GYM ENTRANCE Lower M1 52 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 5: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector GYM ELEC RM 1275 Lower M1 53 Pass

Pull Station GYM BY GIRLS LOCKER RM Lower M1 54 Pass

Pull Station GYM BY BOYS LOCKER RM Lower M1 55 Pass

Pull Station 1200 HALL BUS DOOR EXIT Lower M1 56 Pass

Pull Station 1200 HALL EXIT IN RM 1263 Lower M1 57 Pass

Smoke Detector 2100 HALL IN STAIR 2150 SMK DRS Upper M1 58 Pass

Smoke Detector 2100 HALL IN STAIR 2150 SMK DRS Upper M1 59 Pass

Pull Station 2100 HALL @ STAIR 2150 Upper M1 60 Pass

Smoke Detector 2100 HALL ELEC RM 2120 Upper M1 61 Pass

Smoke Detector 2100 HALL SMK DRS Upper M1 62 Pass

Smoke Detector 2100 HALL SMK DRS Upper M1 63 Pass

Smoke Detector 2100 HALL COMMONS SMK DRS Upper M1 64 Pass

Smoke Detector 2100 HALL COMMONS SMK DRS Upper M1 65 Pass

Smoke Detector UPPER LEV ELEVATOR LOBBY 2012 Upper M1 66 Pass

Pull Station UPPER LEVEL COMMONS AREA Upper M1 67 Pass

Smoke Detector ELEVATOR TOP OF SHAFT Upper M1 68 Pass

Smoke Detector UPPER LEVEL COMMON AREA @ STAIR Upper M1 69 Pass

Smoke Detector 2500 HALL @ SMK DRS Upper M1 70 Pass

Smoke Detector 2500 HALL @ SMK DRS Upper M1 71 Pass

Smoke Detector 2500 HALL @ SMK DRS Upper M1 72 Pass

Smoke Detector 2500 HALL @ SMK DRS Upper M1 73 Pass

Smoke Detector 2500 HALL ELECT RM 2592 Upper M1 74 Pass

Smoke Detector 2500 HALL @ RM 2560 Upper M1 75 Pass

Smoke Detector 2500 HALL FOOD COURT 2560 Upper M1 76 Pass

Smoke Detector 2500 HALL @ SMK DRS Upper M1 77 Pass

Smoke Detector 2500 HALL @ SMK DRS Upper M1 78 Pass

Smoke Detector 2500 HALL @ SMK DRS Upper M1 79 Pass

Smoke Detector 2500 HALL @ SMK DRS Upper M1 80 Pass

Smoke Detector 2500 HALL ROLL UP DR @ BOOKSTORE Upper M1 81 Pass

Smoke Detector BOOKSTORE 2530 ROLL UP DR Upper M1 82 Pass

Smoke Detector 2500 HALL FOOD COURT SMK DRS Upper M1 83 Pass

Smoke Detector 2500 HALL LUNCH RM SMK DRS Upper M1 84 Pass

Smoke Detector 2500 HALL LUNCH RM SMK DRS Upper M1 85 Pass

Smoke Detector 2500 HALL FOOD COURT SMK DRS Upper M1 86 Pass

Waterflow Switch SPRINKLER RISER SYS #3 Upper M1 87 Pass

Tamper Switch SPRINKLER RISER SYS #3 Upper M1 87 Pass

Smoke Detector 2500 HALL LUNCH RM @ RM 2566 Upper M1 88 Pass

Smoke Detector 2500 HALL KITCHEN DISHWASHER Upper M1 89 Pass

Pull Station 2500 HALL ELECT RM 2310 Upper M1 90 Pass

Monitor HALL KITCHEN 2576 HOOD Upper M1 91 Pass

Pull Station 2500 HALL LUNCH RM EXIT Upper M1 92 Pass

Pull Station 2500 HALL KITCHEN EXIT IN 2576 Upper M1 93 Pass

Pull Station MAIN ENTRANCE Upper M1 94 Pass

Tamper Switch OUTSIDE PIV Upper M1 95 Pass

Pull Station MAIN ENTRANCE Upper M1 96 Pass

Smoke Detector 2500 HALL ELEC RM 2522 Upper M1 97 Pass

Pull Station 2500 HALL ADMIN REAR EXIT Upper M1 98 Pass

Pull Station 2500 HALL MECH RM 2533 Upper M1 99 Pass

Pull Station 2500 HALL EXIT BY RM 2542 Upper M1 100 Pass

Smoke Detector 2200 HALL @ SMK DRS Upper M1 101 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 6: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector 2200 HALL @ STAIR 2255 SMK DRS Upper M1 102 Pass

Smoke Detector 2200 HALL UPPER LEV STAIR 2255 Upper M1 103 Pass

Pull Station 2200 HALL @ STAIR 2255 Upper M1 104 Pass

Pull Station 2200 HALL @ SMK DRS Upper M1 105 Pass

Smoke Detector 2200 HALL @ SMK DRS Upper M1 106 Pass

Smoke Detector 2200 COMMONS @ SMK DRS Upper M1 107 Pass

Smoke Detector 2200 COMMONS @ SMK DRS Upper M1 108 Pass

Pull Station LOWER LEV COMMONS AREA Lower M1 110 Pass

Pull Station LOWER LEV COMMONS AREA Lower M1 111 Pass

Pull Station HALL MEDIA CENTER REAR EXIT Upper M1 116 Pass

Pull Station HALL LUNCH RM EXIT Upper M1 117 Pass

Smoke Detector 1100 HALL CLASS RM 1138 Lower M1 118 Pass

Smoke Detector 1100 HALL CLASS RM 1134 Lower M1 119 Pass

Smoke Detector 1100 HALL CLASS RM 1128 Lower M1 120 Pass

Smoke Detector 1100 HALL CLASS RM 1124 Lower M1 121 Pass

Smoke Detector 1100 HALL CLASS RM 1116 Lower M1 122 Pass

Smoke Detector 1100 HALL CLASS RM 1112 Lower M1 123 Pass

Smoke Detector 1100 HALL CLASS RM 1106 Lower M1 124 Pass

Smoke Detector 1100 HALL CLASS RM 1102 Lower M1 125 Pass

Duct Detector 2500 HALL RTU-CAFÉ 1 Upper M1 126 Pass

Smoke Detector 2500 HALL RTU-CAFÉ 2 Upper M1 127 Pass

Duct Detector 2500 HALL RTU-CAFÉ 3 Upper M1 128 Pass

Smoke Detector 1200 HALL CLASS RM 1233 Lower M1 129 Pass

Smoke Detector 1200 HALL CLASS RM 1237 Lower M1 130 Pass

Smoke Detector 1200 HALL CLASS RM 1245 Lower M1 131 Pass

Duct Detector GYM BOYS LOCKER RM RTU Lower M1 132 Pass

Duct Detector GYM GIRLS LOCKER RM RTU Lower M1 133 Pass

Duct Detector GYM REAR HALL BOYS RTU Lower M1 134 Pass

Duct Detector GYM REAR HALL BOYS RTU Lower M1 135 Pass

Duct Detector GYM REAR HALL GIRLS RTU Lower M1 136 Pass

Smoke Detector 1200 HALL CLASS RM 1240 Lower M1 137 Pass

Smoke Detector 1200 HALL CLASS RM 1232 Lower M1 138 Pass

Smoke Detector 1200 HALL CLASS RM 1224 Lower M1 139 Pass

Smoke Detector 1200 HALL CLASS RM 1212 Lower M1 140 Pass

Smoke Detector 2100 HALL CLASS RM 2138 Upper M1 142 Pass

Smoke Detector 2100 HALL CLASS RM 2134 Upper M1 143 Pass

Smoke Detector 2100 HALL CLASS RM 2128 Upper M1 144 Pass

Smoke Detector 2100 HALL CLASS RM 2124 Upper M1 145 Pass

Smoke Detector 2100 HALL CLASS RM 2116 Upper M1 146 Pass

Smoke Detector 2100 HALL CLASS RM 2112 Upper M1 147 Pass

Smoke Detector 2100 HALL CLASS RM 2106 Upper M1 148 Pass

Smoke Detector 2100 HALL CLASS RM 2102 Upper M1 149 Pass

Smoke Detector 2200 HALL CLASS RM 2241 Upper M1 150 Pass

Duct Detector UPPER LEV COMMONS AREA Upper M1 151 Pass

Smoke Detector 2200 HALL CLASS RM 2203 Upper M1 152 Pass

Smoke Detector 2200 HALL CLASS RM 2207 Upper M1 153 Pass

Smoke Detector 2200 HALL CLASS RM 2215 Upper M1 154 Pass

Smoke Detector 2200 HALL CLASS RM 2219 Upper M1 155 Pass

Smoke Detector 2200 HALL CLASS RM 2227 Upper M1 156 Pass

Smoke Detector 2200 HALL CLASS RM 2231 Upper M1 157 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 7: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector 2200 HALL CLASS RM 2241 Upper M1 158 Pass

Smoke Detector 2200 HALL CLASS RM 2245 Upper M1 159 Pass

Duct Detector HALL MECH RM 2270 Upper M1 160 Pass

Duct Detector HALL MECH RM 2270 Upper M1 161 Pass

Smoke Detector 2200 HALL CLASS RM 2250 Upper M1 162 Pass

Smoke Detector 2200 HALL CLASS RM 2246 Upper M1 163 Pass

Smoke Detector 2200 HALL CLASS RM 2240 Upper M1 164 Pass

Smoke Detector 2200 HALL CLASS RM 2236 Upper M1 165 Pass

Smoke Detector 2200 HALL CLASS RM 2220 Upper M1 166 Pass

Smoke Detector 2200 HALL CLASS RM 2216 Upper M1 167 Pass

Smoke Detector 2200 HALL CLASS RM 2212 Upper M1 168 Pass

Smoke Detector 2100 HALL CLASS RM 2208 Upper M1 169 Pass

Smoke Detector 2100 HALL CLASS RM 2204 Upper M1 170 Pass

Smoke Detector 2100 HALL CLASS RM 2101 Upper M1 171 Pass

Smoke Detector 2100 HALL CLASS RM 2107 Upper M1 172 Pass

Smoke Detector 2100 HALL CLASS RM 2111 Upper M1 173 Pass

Smoke Detector 2100 HALL CLASS RM 2113 Upper M1 174 Pass

Smoke Detector 2100 HALL CLASS RM 2117 Upper M1 175 Pass

Smoke Detector 2100 HALL CLASS RM 2129 Upper M1 176 Pass

Smoke Detector 2100 HALL CLASS RM 2133 Upper M1 177 Pass

Smoke Detector 2100 HALL CLASS RM 2137 Upper M1 178 Pass

Smoke Detector 2100 HALL CLASS RM 2141 Upper M1 179 Pass

Duct Detector 2500 HALL MEDIA PRODUCTION Upper M1 180 Pass

Duct Detector 2500 HALL MEDIA PRODUCTION Upper M1 181 Pass

Duct Detector 2500 HALL MEDIA OFFICE Upper M1 182 Pass

Duct Detector 2500 HALL SERVING LINE RTU Upper M1 183 Pass

Duct Detector 2500 HALL SERVING LINE RTU Upper M1 184 Pass

Smoke Detector 1200 HALL CLASS RM 1217 Lower M1 185 Pass

Smoke Detector 1200 HALL CLASS RM 1227 Lower M1 186 Pass

Smoke Detector 1200 HALL CLASS RM 1231 Lower M1 187 Pass

Duct Detector 2500 HALL ADMIN OFFICE ACU Upper M1 188 Pass

Smoke Detector 1100 HALL CLASS RM 1101 Lower M1 190 Pass

Smoke Detector 1100 HALL CLASS RM 1107 Lower M1 191 Pass

Smoke Detector 1100 HALL CLASS RM 1111 Lower M1 192 Pass

Smoke Detector 1100 HALL CLASS RM 1113 Lower M1 193 Pass

Smoke Detector 1100 HALL CLASS RM 1117 Lower M1 194 Pass

Smoke Detector 1100 HALL CLASS RM 119 Lower M1 195 Pass

Smoke Detector 1100 HALL CLASS RM 1133 Lower M1 196 Pass

Smoke Detector 1100 HALL CLASS RM 1137 Lower M1 197 Pass

Smoke Detector 1100 HALL CLASS RM 1141 Lower M1 198 Pass

Waterflow Switch SPRINKLER RISER SYS #2 Upper M1 200 Pass

Tamper Switch SPRINKLER RISER SYS #2 Upper M1 200 Pass

Waterflow Switch SPRINKLER RISER SYS #1 Upper M1 201 Pass

Tamper Switch SPRINKLER RISER SYS #1 Upper M1 201 Pass

Tamper Switch SPRINKLER MAIN VALVE Upper M1 202 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 8: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1: (8) 12V 7AH Back up batteries failed load test and need replacement.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 9: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 10: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 6 0

16 2

38 0

69 2

59 0

4 0

4 0

4 0

Inspector Name : Signature:

Pass

Simplex 4009

EMC Security

Fail

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

PotterWater flow VSR

All-Star Fire, LLC

Power Patrol

Simplex 4099-9004

SLA1116

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4100U

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

2565 Echols Road

Lakeside Middle School

Ground Fault

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name 4100 USimplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

4098-9688

Tamper Butterball TBD

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

Heat Detectors Simplex 4098-9734

30041

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

6/19/2020

EI1273

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 11: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Fail

Fail

N/A

N/A

N/A

Condition Voltage Load Test

Fair (2017) 12.9 Fail

Fair (2017) 12.9 Fail

Poor (no date) 13.6 Pass

Poor (no date) 13.5 Pass

Fair (2017) 13.3 Pass

Fair (2017) 13.3 Pass

Fair (2015) 13.1 Pass

Fair (2015) 13.1 Pass

Good (2019) 13.3 Pass

Good (2019) 13.4 Pass

Good (2019) 13.4 Pass

Good (2019) 13.4 Pass

Fair (2017) 13.4 Pass

Fair (2017) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Fail

N/A

N/A

Pass

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) rm 1120a

FCPS (left) rm 1589

FCPS (left) rm 1120a

FCPS (right) rm 1589

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) rm 1243

FCPS (right) rm 1243

FCPS (left) rm 1275

FCPS (right) rm 1275

FCPS (left) rm 2120

FCPS (right) rm 2120

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

FACP (left)

12v 18ahFACP (right)

12v 18ah

12v 7ah

FCPS (right) rm 2224

FCPS (left) rm2224

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 12: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Duct Detector Special Ed rm1222 LL M1-56 Pass

Duct Detector Media Ctr LL M2-40 Pass

Smoke Detector Commons Elev Equip rm LL M1-1 Pass

Duct Detector Book Storage rm 1012 LL M1-10 No Key

Duct Detector Girls Gym Office LL M1-101 Pass

Duct Detector Girls Vestibule rm 1292 LL M1-102 Pass

Pull Station Girls Locker rm 1293 LL M1-103 Pass

Duct Detector Girls Locker rm 1293 LL M1-105 Pass

Smoke Detector Stair 2265 UL M1-106 Pass

Smoke Detector Stair 2265 UL M1-107 Pass

Pull Station By Stair 2265 LL M1-108 Pass

Smoke Detector Elevator Lobby 2251 UL M1-109 Pass

Pull Station Commons Rear Exit LL M1-11 Pass

Smoke Detector Elev Top of Shaft UL M1-110 Visual

Duct Detector Rm 2240 UL M1-112 Pass

Duct Detector Rm 2241 UL M1-113 Pass

Duct Detector Rm 2241 UL M1-114 Pass

Duct Detector Rm 2236 UL M1-115 Pass

Smoke Detector Elect rm 2223 UL M1-116 Too High

Duct Detector Rm 2216 UL M1-117 Pass

Duct Detector Rm 2215 UL M1-118 Pass

Duct Detector Rm 2215 UL M1-119 Pass

Pull Station Stair 1014 Rear Exit LL M1-12 Pass

Duct Detector Corr by rm 2204 UL M1-120 Pass

Smoke Detector Corr 2200 Smoke drs UL M1-121 Pass

Pull Station Corr by rm 2203 UL M1-122 Pass

Smoke Detector Commons at Smoke dr UL M1-123 Pass

Duct Detector Commons in rm 2004 UL M1-124 Pass

Duct Detector Commons in rm 2008 UL M1-125 Pass

Smoke Detector Commons by Stair UL M1-126 Pass

Smoke Detector Commons by Stair UL M1-127 Pass

Pull Station Commons by Stair UL M1-128 Pass

Smoke Detector Commons at Smoke dr UL M1-129 Pass

Duct Detector Commons in rm 2012 UL M1-130 Not Found

Duct Detector Commons in rm 2016 UL M1-131 Pass

Smoke Detector Commons Elev Lobby UL M1-132 Pass

Smoke Detector Commons Elev Top of Shaft UL M1-133 Visual

Smoke Detector Corr Smoke drs UL M1-136 Pass

Pull Station Corr by rm 2102 UL M1-137 Pass

Duct Detector Rm 2101 UL M1-138 Pass

Duct Detector Rm 2106 UL M1-139 Pass

Duct Detector Rm 2106 UL M1-140 Pass

Duct Detector Rm 2113 UL M1-141 Pass

Smoke Detector Elect rm 2120 UL M1-142 Pass

Duct Detector Rm 2129 UL M1-143 See Notes

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 13: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Rm 2128 UL M1-144 Pass

Duct Detector Rm 2128 UL M1-145 Pass

Duct Detector Rm 2133 UL M1-146 Pass

Smoke Detector Corr Smoke drs UL M1-147 Pass

Pull Station Corr by rm 2141 UL M1-148 Pass

Smoke Detector Corr Smoke drs UL M1-149 Pass

Smoke Detector Commons at Smoke dr UL M1-15 Pass

Pull Station Corr by Girls rm UL M1-150 Pass

Pull Station Corr by Girls rm UL M1-151 Pass

Pull Station Corr by Mech rm 1230 LL M1-155 Pass

Pull Station Corr by Girls rm LL M1-156 Pass

Heat Detector Commons Elev Pit LL M1-157 Visual

Heat Detector Gym Elev Pit LL M1-158 Visual

Smoke Detector Corr 1100 Smoke drs LL M1-17 Pass

Duct Detector Rm 1101 LL M1-18 Pass

Duct Detector Science rm 1106 LL M1-19 See Notes

Heat Detector Commons Elev Equip rm LL M1-2 Visual

Duct Detector HVAC closet by rm 1106 LL M1-20 No Access

Duct Detector Science rm 1106 LL M1-21 Pass

Duct Detector Science rm 1106 LL M1-22 Pass

Duct Detector Rm 1113 LL M1-23 Pass

Duct Detector Science rm 1112 LL M1-24 See Notes

Duct Detector HVAC closet by rm 1112 LL M1-25 Pass

Smoke Detector Elect rm 1120 LL M1-26 Pass

Duct Detector Science rm 1128 LL M1-27 See Notes

Duct Detector HVAC closet by rm 1128 LL M1-28 No Access

Duct Detector Prep rm 1120 LL M1-29 Not Found

Duct Detector Prep rm 1130 LL M1-30 See Notes

Duct Detector English rm 1129 LL M1-31 Pass

Duct Detector English rm 1129 LL M1-32 Pass

Duct Detector Rm 1137 LL M1-33 See Notes

Duct Detector Rm 1134 LL M1-34 Pass

Duct Detector HVAC closet by rm 1134 LL M1-35 No Access

Smoke Detector Corr 1100 Smoke drs LL M1-36 Pass

Pull Station Corr by rm 1141 LL M1-37 Pass

Smoke Detector Corr 1100 Smoke drs LL M1-38 Pass

Pull Station Stair 1150 LL M1-39 Pass

Duct Detector Outside in Rear Unit ERU 1 LL M1-40 No Key

Pull Station Commons Rear Exit LL M1-41 Pass

Smoke Detector Commons at Smoke dr LL M1-43 Pass

Smoke Detector Commons at Smoke dr LL M1-44 Pass

Pull Station Commons at Smoke dr LL M1-45 Pass

Smoke Detector Commons in Book Store LL M1-46 No Key

Duct Detector Work rm 1208 LL M1-47 Pass

Duct Detector Book Storage rm 1202A LL M1-48 No Key

Duct Detector Work rm 1208 LL M1-49 Pass

Duct Detector Records rm 1004 LL M1-51 No Key

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 14: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Records rm 1004 LL M1-52 Pass

Duct Detector Computer Lab rm 1221 LL M1-57 Pass

Pull Station Mech rm 1230 LL M1-59 Pass

Duct Detector Mech rm 1230 LL M1-60 Pass

Duct Detector Rm 1236 LL M1-61 Pass

Pull Station Art Lab rm1240 LL M1-62 Pass

Smoke Detector Elect rm 1243 LL M1-63 Pass

Pull Station HVAC rm 1301 LL M1-64 No Key

Smoke Detector Corr 1250 Smoke dr. LL M1-65 Pass

Smoke Detector Corr 1250 Smoke dr. LL M1-66 Pass

Duct Detector Corr 1250 LL M1-67 Pass

Pull Station Corr 1250 Rear Exit LL M1-68 Pass

Smoke Detector Elevator Lobby 1251 LL M1-69 Pass

Smoke Detector Commons Elev Lobby LL M1-7 Pass

Smoke Detector Elev Equip rm 1255 LL M1-70 Pass

Heat Detector Elev Equip rm 1255 LL M1-71 Visual

Pull Station Stair 1257 Front Exit LL M1-76 Pass

Smoke Detector Stair 1257 LL M1-77 Pass

Smoke Detector Stair 1257 LL M1-78 Pass

Smoke Detector Corr 1250 Smoke dr. LL M1-79 Pass

Smoke Detector Corr 1260 Smoke dr. LL M1-80 Pass

Smoke Detector Corr 1250 Smoke dr. LL M1-81 Visual

Smoke Detector Corr 1260 Smoke dr. LL M1-82 Visual

Smoke Detector Corr 1260 Smoke dr. LL M1-83 Pass

Smoke Detector Concession rm 1271 LL M1-84 Pass

Duct Detector Mech rm 2260 UL M1-85 Pass

Duct Detector Mech rm 2260 UL M1-86 Pass

Pull Station Choral rm 1263 LL M1-87 Pass

Pull Station Band rm 1261 LL M1-88 Pass

Pull Station Corr 1260 Side Exit LL M1-89 Pass

Duct Detector Book Storage rm 1012 LL M1-9 No Key

Smoke Detector Corr 1260 Smoke dr. LL M1-90 Visual

Duct Detector Mech rm 2260 UL M1-91 Pass

Duct Detector Gym Vestibule 1270 LL M1-92 Fail

Smoke Detector Corr 1260 Smoke dr. LL M1-93 Pass

Smoke Detector Elect rm 1275 LL M1-94 Pass

Pull Station Boys Locker rm 1284 LL M1-95 Pass

Duct Detector Boys Gym Office LL M1-96 Pass

Duct Detector Boys Lockers rm 1284 LL M1-97 Pass

Duct Detector Boys Vestibule 1283 LL M1-98 Pass

Duct Detector Boys Lockers rm 1284 LL M1-99 Pass

Smoke Detector Parent Reception LL M2-1 Pass

Pull Station Mech rm outside Admin LL M2-11 No Key

Pull Station Front Entrance LL M2-12 Pass

Pull Station Lunch rm 1540 LL M2-13 Pass

Pull Station Lunch rm 1540 LL M2-14 Pass

Pull Station Elect rm 1310 LL M2-16 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 15: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Elect rm 1310 LL M2-17 Not Found

Duct Detector Kitchen Dish Return LL M2-18 Pass

Duct Detector Food Court LL M2-20 Pass

Duct Detector Kitchen LL M2-21 Pass

Pull Station Kitchen 1566 LL M2-22 Pass

Smoke Detector Food Court 1550 Entrance LL M2-23 Visual

Smoke Detector Food Court 1550 Entrance LL M2-24 Visual

Pull Station Sprinkler rm 1320a LL M2-25 Pass

Flow Switch Riser 2 rm 1320a LL M2-28 Pass

Flow Switch Riser 3 rm 1320a LL M2-30 Pass

Flow Switch Riser 4 rm 1320a LL M2-32 Pass

Duct Detector Janitor Closet LL M2-34 Fail

Smoke Detector Media Ctr MDF rm LL M2-35 Pass

Smoke Detector Media Ctr 1589 Main Entry LL M2-36 Pass

Smoke Detector Media Ctr 1589 Main Entry LL M2-37 Pass

Duct Detector Media Ctr LL M2-38 Pass

Duct Detector Media Ctr LL M2-39 Pass

Pull Station Media Center LL M2-41 Pass

Smoke Detector Conn Smoke dr LL M2-42 Visual

Smoke Detector Conn Smoke dr LL M2-43 Pass

Pull Station Connector Exit LL M2-44 Pass

Smoke Detector Conn Smoke dr LL M2-45 Pass

Smoke Detector Conn Smoke dr LL M2-46 Pass

Smoke Detector Lunch room Corr 1570 Dr LL M2-53 Visual

Smoke Detector Lunch room Corr 1570 Dr LL M2-54 Visual

Smoke Detector Lunch room Corr 1570 Dr LL M2-55 Pass

Smoke Detector Lunch room Corr 1570 Dr LL M2-56 Visual

Smoke Detector Admin at Roll Fire Screen LL M2-6 Pass

Duct Detector Amin Corr 1520 LL M2-7 Not Found

Smoke Detector Admin Elect rm 1522 LL M2-8 Visual

Pull Station Admin 1521 Side Exit LL M2-9 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 16: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Arrived to find 2 troubles on panel: duct M1-9 wrong device, card (1) ground fault.

5. HVAC failed to shut down when detectors went into alarm.

Note:

While testing duct detectors, panel would crash leaving (78) troubles on panel.

Some duct detectors were in rooms with freshly waxed floors and could not be accessed for testing.

Deficiencies

1. The following strobes failed to flash in Room #1124.

2. The following horn strobes failed to flash or sound - Hall by Room #1013 and Hall by Room #2131.

3. 2 Batteries failed load test.

Only way to eliminate troubles was a total reboot of system.

4. The following duct detectors failed ro report to panel: M1-92, & M2-34.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 17: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

Fire alarm technician was unable to access certain areas due to the waxing of the floors.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 18: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 6 0

16 0

22 0

30 0

7 0

Inspector Name : Signature:

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/27/2020

EI1273

DNR

Other

Batteries

Pullstations

NotifierSmoke Detectors FSP-851

Duct Detectors System Sendor

Pass

1180 Chamblee Gap Road

Kelly Mill Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name NFS2-3030DNotifier

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC

All-Star Fire, LLC

Power Patrol

Notifier NBG12LX

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

NFS2-3030D

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Notifier

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

Pass

Notifier FCPS24S8

EMC Security

Fail

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 19: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Fair (2017) 13.4 Pass

Fair (2017) 13.4 Pass

Good (2019) 13.2 Pass

Good (2019) 13.1 Pass

Poor (2017) 13.1 Pass

Poor (2017) 13 Pass

Poor (2017) 13.1 Pass

Poor (2017) 13.3 Pass

Poor (2017) 13.3 Pass

Poor (2017) 13.4 Pass

Poor (2017) 13.1 Pass

Poor (2017) 13.3 Pass

Poor (2017) 13.1 Pass

Poor (2017) 13.3 Pass

Poor (2016) 13.1 Pass

Poor (2016) 13.1 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

FCPS (right) #1 rm 133

FCPS (left) #1 rm 133

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FCPS (left) #6 rm 232

FCPS (right) #6 rm 232

Voice Evac (left) rm 157

Voice Evac (right) rm 157

12v 7ah

12v 7ah

12v 7ah

12v 7ah

FCPS (right) #4 rm 349A

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 157

FCPS (right) #2 rm 157

FCPS (left) #3 rm 388A

FCPS (right) #3 rm 388A

12v 7ah

12v 7ah

12v 7ah

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #5 rm 302

FCPS (left) #4 rm 349A

FCPS (left) #5 rm 302

Fire Pump Running

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 20: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

N/AFM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 21: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Smoke Detector Main Office above FACP 1 D01 Pass

Smoke Detector Elect rm 138 1 D02 Pass

Duct Detector Corr 201 1 D03 Pass

Duct Detector Corr 138 1 D04 Pass

Duct Detector Kitchen 1 D05 Visual

Duct Detector Cafeteria 1 D06 No Access

Smoke Detector Elect rm 157 1 D07 Visual

Duct Detector Gym Mech rm 421 1 D08 Pass

Duct Detector Corr 400 1 D09 Pass

Duct Detector Corr 400 1 D10 Pass

Duct Detector Corr 400 Mech rm 1 D11 Pass

Duct Detector Corr 395 Mech rm 1 D12 Pass

Duct Detector Corr 395 Mech rm 1 D13 Pass

Duct Detector Corr 376 Mech rm 1 D14 Pass

Duct Detector Corr 376 Mech rm 1 D15 Pass

Duct Detector Corr 356 Mech rm 1 D16 Pass

Duct Detector Corr 356 Mech rm 1 D17 Pass

Smoke Detector Elect rm 349 1 D18 Pass

Duct Detector Corr 337 Mech rm 1 D19 Pass

Duct Detector Corr 337 Mech rm 1 D20 Pass

Duct Detector Corr 337 1 D21 Visual

Duct Detector Corr 311 Mech rm 1 D22 Pass

Duct Detector Corr 311 Mech rm 1 D23 Pass

Duct Detector Corr 300 Mech rm 1 D24 Pass

Duct Detector Corr 300 Mech rm 1 D25 Pass

Duct Detector Corr 241 Mech rm 1 D26 Pass

Duct Detector Corr 241 Mech rm 1 D27 Pass

Duct Detector Corr 229 Mech rm 1 D28 Pass

Smoke Detector Elect rm 232 1 D29 Pass

Duct Detector RTU 4 1 D30 Not found

Duct Detector Corr 400 1 D31 Pass

Smoke Detector Elect rm 388 1 D32 Pass

Duct Detector Corr 356 1 D33 Pass

Smoke Detector Elect rm 298 1 D34 Not found

Duct Detector Corr 300 Mech rm 1 D35 Pass

Duct Detector Corr 290 1 D36 Visual

Duct Detector Corr 241 Mech rm 1 D37 Pass

Pull Station Front Lobby 1 M01 Pass

Pull Station Front Lobby 1 M02 Pass

Pull Station Cafe Lobby 1 M03 Pass

Pull Station Corr 262 1 M04 Pass

Pull Station Corr 279 1 M05 Pass

Pull Station Corr 241 1 M06 Pass

Pull Station Corr 268 Main Hall 1 M07 Pass

Pull Station Gym 1 M08 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 22: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station Gym 1 M09 Pass

Pull Station Gym Storage rm 424 1 M10 Pass

Pull Station Gym 1 M11 Pass

Pull Station Corr 400 1 M12 Pass

Pull Station Corr 395 1 M13 Pass

Pull Station Corr 376 1 M14 Pass

Pull Station Corr 356 1 M15 Pass

Pull Station Corr 337 1 M16 Pass

Pull Station Corr 311 1 M17 Pass

Pull Station Corr 200 1 M18 Pass

Pull Station Corr 300 1 M19 Pass

Pull Station Corr 268 Main Hall 1 M20 Pass

Pull Station Mech rm 158 1 M68 Pass

Pull Station Kitchen 1 M72 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 23: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 24: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 25: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 1

Power Supplies 1 N/A

4 N/A

TBD N/A

TBD N/A

TBD N/A

Inspector Name : Signature:

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

6/17/2020

EI1273

136 Elm Street

Hill Education Center / Gateway Academy

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredVault rm 107

Model Name NFS 320Notifier

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

30040

All-Star Fire, LLC

Power Patrol

TBD TBD

FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

NFS 320

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Notifier

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

Fail

Notifier FCPS 24S8

Control Panel

Device

TBD

Batteries

Pullstations

TBDSmoke Detectors TBD

Duct Detectors TBD

EMC Security

Fail

Fail

Fail

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Fail

Fail

Fail

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 26: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Fail

Fail

N/A

N/A

N/A

Condition Voltage Load Test

TBD TBD TBD

TBD TBD TBD

TBD TBD TBD

TBD TBD TBD

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

FACP (left)

TBDFACP (right)

TBD

TBD

FCPS (right)

FCPS (left)

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Correct Switching and Operation Verified

TBD

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

Fire Pump Power Loss

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 27: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 28: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 29: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 30: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 31: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 32: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

Panel has 120 vac but panel is not functional.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 33: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 34: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 8 0

18 2

34 0

26 1

781 0

4 0

3 0

3 0

Inspector Name : Signature:

30041

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

6/22/2020

EI1273

4098-9688

Tamper Global Safety TBD

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

Heat Detector Simplex 4098-9734

Pass

2555 Echols Road

Haw Creek Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name 4100USimplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

All-Star Fire, LLC

Ultra Sonic

Simplex 4099-9006

SLA 1116

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4100U

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

System SensorWater flow WFD 40

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 35: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Fair (2018) 13.1 Fail

Fair (2018) 13.1 Fail

Good (2019) 13.4 Pass

Good (2019) 13.4 Pass

Good (2019) 13.6 Pass

Good (2019) 13.6 Pass

Poor (2016) 13.1 Pass

Poor (2016) 13.1 Pass

Good (2019) 13 Pass

Good (2019) 13 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.4 Pass

Good (2019) 13.4 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Fair (2017) 13.2 Pass

Fair (2017) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Fail

N/A

FCPS (right) #7 rm 1106

FCPS (left) #8 rm 1055

FCPS (right) #8 rm 1055

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Fire Alarm Properly Recall ElevatorsElevator Recall

Are stairwell Pressurization Fans Activated by Fire Alarm

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Stairwell Pressurization

FACP (left)

12v 18ah FACP (right)

12v 18ah

12v 7ah

FCPS (right) #1 rm 1106

FCPS (left) #1 rm 1106

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #4 rm 1106

FCPS (right) #4 rm 1106

FCPS (left) #5 rm 1106

FCPS (right) #5 rm 1106

FCPS (left) #6 rm 1106

FCPS (right) #6 rm 1106

FCPS (left) #7 rm 1106

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #3 rm 1106

FCPS (left) #2 rm 1106

FCPS (left) #3 rm 1106

FCPS (right) #2 rm 1106

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 36: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

N/A

N/A

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Fire Alarm Release Maglocks

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 37: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station Vestibule Principals Office LL ID1-4 Pass

Pull Station Vestibule Main Entrance LL ID1-6 Pass

Pull Station Corr Exit @ Lunch rm LL ID1-9 Pass

Smoke Detector Corr @ Lunch rm LL ID1-10 Too High

Pull Station Media Center Exit rm 1050 LL ID1-22 Pass

Pull Station Lunch rm LL ID1-23 Pass

Pull Station Lunch rm LL ID1-24 Pass

Pull Station Kitchen Exit LL ID1-42 Pass

Pull Station Front/Rear Corr LL ID1-48 Pass

Pull Station Corr @ Art rm Exit LL ID1-64 Pass

Pull Station Stair 1326 Exit LL ID1-66 Pass

Pull Station Gym Exit LL ID1-69 Pass

Pull Station Gym Exit LL ID1-70 Pass

Pull Station Corr @ Music rm LL ID1-76 Pass

Pull Station Stair by Vestibule Exit LL ID1-78 Pass

Pull Station Lobby Rear Exit LL ID1-89 Pass

Pull Station Corr by Bookstore LL ID1-96 Pass

Pull Station Stair by Vestibule LL ID1-98 Pass

Pull Station Corr @ Bookstore LL ID1-105 Pass

Pull Station Stairs LL ID1-107 Pass

Pull Station Mech rm 1041 Exit LL ID1-108 Pass

Pull Station Corr @ Special Ed LL ID1-118 Pass

Pull Station Corr @Workroom LL ID1-119 Pass

Pull Station Corr @ Bookstore LL ID1-120 Pass

Pull Station Corr @ Kindergarden LL ID1-121 Pass

Pull Station Mech rm 1224 LL ID1-122 Pass

Pull Station Elect rm 1044 LL ID1-123 Pass

Pull Station Mech rm 1015 LL ID1-124 Pass

Pull Station Exit @ Book Storage 2420 LL ID2-3 Pass

Pull Station Rear Commons Exit LL ID2-6 Pass

Pull Station Corr Exit @ Bookstore LL ID2-13 Pass

Pull Station Front Common Area LL ID2-18 Pass

Pull Station Corr Exit @Art rm 2322 LL ID2-26 Pass

Pull Station Corr Exit @Music rm UL ID2-42 Pass

Pull Station Corr Exit @Music rm UL ID2-44 Not Found

Smoke Detector Clerical rm 1001 LL ID1-1 Pass

Smoke Detector Front/Rear Corr LL ID1-46 Pass

Smoke Detector Front/Rear Corr LL ID1-49 Pass

Smoke Detector Corr @ Bookstore LL ID1-106 Pass

Smoke Detector Corr @ Bookstore LL ID1-104 Pass

Smoke Detector Corr @ Music rm LL ID1-77 Pass

Smoke Detector Gym @ Music rm LL ID1-75 Pass

Smoke Detector By Elev Lobby 1 LL ID1-79 Pass

Smoke Detector By Elev Lobby 1 LL ID1-80 Pass

Smoke Detector Corr @ Special Ed LL ID1-90 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 38: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Corr @ Special Ed LL ID1-91 Pass

Smoke Detector Stairs LL ID1-95 Pass

Smoke Detector Stairs LL ID1-97 Pass

Smoke Detector Stair2525 Exit UL ID2-43 Pass

Smoke Detector Elev 2 Lobby UL ID2-38 Pass

Smoke Detector Corr Stair 2422 UL ID2-2 Pass

Smoke Detector Stair 2422 Exit UL ID2-1 Pass

Smoke Detector Music rm 2519 UL ID2-41 Pass

Smoke Detector Lobby 1 UL ID2-20 Pass

Smoke Detector Lobby 1 UL ID2-21 Pass

Smoke Detector Art rm 2322 UL ID2-25 Pass

Smoke Detector Stair 2322 Exit UL ID2-27 Pass

Smoke Detector Corr @ Art rm Exit LL ID1-65 Pass

Smoke Detector Corr @ Art rm LL ID1-63 Pass

Smoke Detector Smoke drs at Stair 2225 UL ID2-12 Pass

Smoke Detector Amin Reception Window LL ID1-126 Pass

Smoke Detector Dish Return 1031 LL ID1-15 Pass

Smoke Detector Media Center Main Entrance LL ID1-161 Pass

Smoke Detector Media Center Main Entrance LL ID1-162 Pass

Smoke Detector Lobby Smoke drs Front LL ID1-51 Pass

Smoke Detector Kindergarten Corr Smoke drs LL ID1-61 Pass

Smoke Detector Kindergarten Corr Smoke drs LL ID1-62 Pass

Smoke Detector Gym Smoke dr by Art rm 1322 LL ID1-67 Pass

Smoke Detector Mech. Rm 1108 LL ID1-71 Pass

Smoke Detector Mech. Rm 1108 LL ID1-72 Pass

Smoke Detector Gym Smoke dr by Music rm 1519 LL ID1-74 Pass

Smoke Detector Eleavtor 2 Lobby LL ID1-110 Pass

Smoke Detector IDF rm 1106 LL ID1-125 Pass

Smoke Detector Smoke drs by Book Store 1201 LL ID1-102 Pass

Smoke Detector Smoke drs by Book Store 1201 LL ID1-103 Pass

Smoke Detector Mech. Rm 1109 LL ID1-101 Pass

Smoke Detector Mech. Rm 1109 LL ID1-100 Pass

Smoke Detector Elevator Equip rm1118 LL ID1-83 Pass

Smoke Detector Eleavtor 1 Lobby LL ID1-109 Pass

Smoke Detector Elect rm 1013 LL ID1-3 Visual

Smoke Detector Lunch rm Smoke drs LL ID1-11 Visual

Smoke Detector Lunch rm Smoke drs LL ID1-12 Visual

Smoke Detector Lunch rm Smoke drs LL ID1-13 Visual

Smoke Detector Corr @ Dish Return LL ID1-14 Visual

Smoke Detector Mech rm 1015 LL ID1-5 No Key

Smoke Detector MDF rm LL ID1-16 Visual

Smoke Detector Mech rm 1040 LL ID1-25 Pass

Smoke Detector Corr Smoke drs LL ID1-45 Not Found

Smoke Detector Elevator Equip rm 1102 LL ID1-53 Visual

Smoke Detector Elevator 1 Pit LL ID1-59 Visual

Smoke Detector Elevator 2 Pit LL ID1-81 Visual

Smoke Detector Special Education Kitchen LL ID1-93 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 39: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Mech rm 1244 LL ID1-99 Not Found

Smoke Detector Eleavtor 2 Lobby UL ID2-35 Pass

Smoke Detector Smoke drs at Elevator 2 Lobby UL ID2-37 Pass

Smoke Detector Rear Commons Smoke drs UL ID2-34 Pass

Smoke Detector Rear Commons Smoke drs UL ID2-4 Pass

Smoke Detector Stair 2525 Smoke drs UL ID2-43 Pass

Smoke Detector Eleavtor 1 Lobby UL ID2-23 Pass

Smoke Detector Front Common @ Smoke drs UL ID2-16 Pass

Smoke Detector Front Common @ Smoke drs UL ID2-14 Pass

Smoke Detector Stair 2225 Smoke drs UL ID2-11 Pass

Smoke Detector Mech. Rm 2109 UL ID2-8 Pass

Smoke Detector Corr @ Bookstore UL ID2-3 Not Found

Smoke Detector Rear Commons Smoke drs UL ID2-5 Visual

Smoke Detector Rear Commons Smoke drs UL ID2-6 Visual

Smoke Detector Mech. Rm 2109 UL ID2-10 Not Found

Smoke Detector Front Common Area UL ID2-15 Visual

Smoke Detector Front Common Area UL ID2-17 Visual

Smoke Detector Mech. Rm 2108 UL ID2-31 Not Found

Smoke Detector Mech. Rm 2108 UL ID2-32 Not Found

Smoke Detector Rear Commons Smoke drs UL ID2-33 Visual

Smoke Detector Eleavtor 2 Top of Shaft UL ID2-45 Visual

Heat Detector Elevator Equip rm 1102 LL ID1-54 Visual

Heat Detector Elevator 1 Pit LL ID1-60 Visual

Heat Detector Elevator 2 Pit LL ID1-82 Visual

Heat Detector Elevator Equip rm 1118 LL ID1-84 Visual

Duct Detector Janitors rm 1206 LL ID1-17 Pass

Duct Detector Media Center 1050 RTU 6 LL ID1-19 Pass

Duct Detector Media Center 1050 RTU 3 LL ID1-20 Pass

Duct Detector Media Center 1050 RTU 4 LL ID1-21 No Access

Duct Detector Mech rm 1041 LL ID1-34 Pass

Duct Detector Lunch rm by Serving LL ID1-35 No Access

Duct Detector Kitchen RTU 5 Return LL ID1-36 Pass

Duct Detector Lunch rm RTU 5 LL ID1-37 Not Found

Duct Detector Lunch rm RTU 1 LL ID1-38 Pass

Duct Detector Lunch rm RTU 1 LL ID1-39 Not Found

Duct Detector Lunch rm RTU 7 LL ID1-41 No Access

Duct Detector Kindergarten class 1203 LL ID1-112 Pass

Duct Detector Lobby 1100 LL ID1-115 Pass

Duct Detector Eleavtor 1 Lobby LL ID1-117 Pass

Duct Detector Mech. Rm 2109 UL ID2-7 Pass

Duct Detector Mech. Rm 2109 UL ID2-9 Pass

Duct Detector Corr @ 5th Grade rm 2301 UL ID2-19 Pass

Duct Detector Multipurpose rm 2315 UL ID2-28 Pass

Duct Detector Multipurpose rm 2315 UL ID2-29 Pass

Duct Detector Multipurpose rm 2315 UL ID2-30 Pass

Duct Detector Work rm 2506 UL ID2-39 Pass

Duct Detector Mech. Rm 2108 UL ID2-40 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 40: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Outside girls rm UL ID2-46 Fail

Duct Detector Eleavtor 2 Lobby UL ID2-50 Pass

Duct Detector Outside girls rm 2103 UL ID2-51 Pass

Duct Detector Outside Book Store UL ID2-52 Not Found

Flow Switch Mech rm 1041 LL ID1-30 Pass

Flow Switch Mech rm 1041 LL ID1-28 Pass

Flow Switch Mech rm 1041 LL ID1-26 Pass

Tamper Switch Mech rm 1041 LL ID1-31 Pass

Tamper Switch Mech rm 1041 LL ID1-29 Pass

Tamper Switch Mech rm 1041 LL ID1-27 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 41: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. 2 Batteries failed load test.

2. Duct Detector at ID2-46 failed to report to panel.

3. HVAC units fail to shut down with duct detector in alarm.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 42: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 43: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 8 0

18 2

34 0

26 1

781 0

4 0

3 0

3 0

Inspector Name : Signature:

30041

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

6/22/2020

EI1273

4098-9688

Tamper Global Safety TBD

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

Heat Detector Simplex 4098-9734

Pass

2555 Echols Road

Haw Creek Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name 4100USimplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

All-Star Fire, LLC

Ultra Sonic

Simplex 4099-9006

SLA 1116

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4100U

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

System SensorWater flow WFD 40

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 44: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Fair (2018) 13.1 Fail

Fair (2018) 13.1 Fail

Good (2019) 13.4 Pass

Good (2019) 13.4 Pass

Good (2019) 13.6 Pass

Good (2019) 13.6 Pass

Poor (2016) 13.1 Pass

Poor (2016) 13.1 Pass

Good (2019) 13 Pass

Good (2019) 13 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.4 Pass

Good (2019) 13.4 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Fair (2017) 13.2 Pass

Fair (2017) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Fail

N/A

FCPS (right) #7 rm 1106

FCPS (left) #8 rm 1055

FCPS (right) #8 rm 1055

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Fire Alarm Properly Recall ElevatorsElevator Recall

Are stairwell Pressurization Fans Activated by Fire Alarm

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Stairwell Pressurization

FACP (left)

12v 18ah FACP (right)

12v 18ah

12v 7ah

FCPS (right) #1 rm 1106

FCPS (left) #1 rm 1106

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #4 rm 1106

FCPS (right) #4 rm 1106

FCPS (left) #5 rm 1106

FCPS (right) #5 rm 1106

FCPS (left) #6 rm 1106

FCPS (right) #6 rm 1106

FCPS (left) #7 rm 1106

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #3 rm 1106

FCPS (left) #2 rm 1106

FCPS (left) #3 rm 1106

FCPS (right) #2 rm 1106

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 45: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

N/A

N/A

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Fire Alarm Release Maglocks

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 46: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station Vestibule Principals Office LL ID1-4 Pass

Pull Station Vestibule Main Entrance LL ID1-6 Pass

Pull Station Corr Exit @ Lunch rm LL ID1-9 Pass

Smoke Detector Corr @ Lunch rm LL ID1-10 Too High

Pull Station Media Center Exit rm 1050 LL ID1-22 Pass

Pull Station Lunch rm LL ID1-23 Pass

Pull Station Lunch rm LL ID1-24 Pass

Pull Station Kitchen Exit LL ID1-42 Pass

Pull Station Front/Rear Corr LL ID1-48 Pass

Pull Station Corr @ Art rm Exit LL ID1-64 Pass

Pull Station Stair 1326 Exit LL ID1-66 Pass

Pull Station Gym Exit LL ID1-69 Pass

Pull Station Gym Exit LL ID1-70 Pass

Pull Station Corr @ Music rm LL ID1-76 Pass

Pull Station Stair by Vestibule Exit LL ID1-78 Pass

Pull Station Lobby Rear Exit LL ID1-89 Pass

Pull Station Corr by Bookstore LL ID1-96 Pass

Pull Station Stair by Vestibule LL ID1-98 Pass

Pull Station Corr @ Bookstore LL ID1-105 Pass

Pull Station Stairs LL ID1-107 Pass

Pull Station Mech rm 1041 Exit LL ID1-108 Pass

Pull Station Corr @ Special Ed LL ID1-118 Pass

Pull Station Corr @Workroom LL ID1-119 Pass

Pull Station Corr @ Bookstore LL ID1-120 Pass

Pull Station Corr @ Kindergarden LL ID1-121 Pass

Pull Station Mech rm 1224 LL ID1-122 Pass

Pull Station Elect rm 1044 LL ID1-123 Pass

Pull Station Mech rm 1015 LL ID1-124 Pass

Pull Station Exit @ Book Storage 2420 LL ID2-3 Pass

Pull Station Rear Commons Exit LL ID2-6 Pass

Pull Station Corr Exit @ Bookstore LL ID2-13 Pass

Pull Station Front Common Area LL ID2-18 Pass

Pull Station Corr Exit @Art rm 2322 LL ID2-26 Pass

Pull Station Corr Exit @Music rm UL ID2-42 Pass

Pull Station Corr Exit @Music rm UL ID2-44 Not Found

Smoke Detector Clerical rm 1001 LL ID1-1 Pass

Smoke Detector Front/Rear Corr LL ID1-46 Pass

Smoke Detector Front/Rear Corr LL ID1-49 Pass

Smoke Detector Corr @ Bookstore LL ID1-106 Pass

Smoke Detector Corr @ Bookstore LL ID1-104 Pass

Smoke Detector Corr @ Music rm LL ID1-77 Pass

Smoke Detector Gym @ Music rm LL ID1-75 Pass

Smoke Detector By Elev Lobby 1 LL ID1-79 Pass

Smoke Detector By Elev Lobby 1 LL ID1-80 Pass

Smoke Detector Corr @ Special Ed LL ID1-90 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 47: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Corr @ Special Ed LL ID1-91 Pass

Smoke Detector Stairs LL ID1-95 Pass

Smoke Detector Stairs LL ID1-97 Pass

Smoke Detector Stair2525 Exit UL ID2-43 Pass

Smoke Detector Elev 2 Lobby UL ID2-38 Pass

Smoke Detector Corr Stair 2422 UL ID2-2 Pass

Smoke Detector Stair 2422 Exit UL ID2-1 Pass

Smoke Detector Music rm 2519 UL ID2-41 Pass

Smoke Detector Lobby 1 UL ID2-20 Pass

Smoke Detector Lobby 1 UL ID2-21 Pass

Smoke Detector Art rm 2322 UL ID2-25 Pass

Smoke Detector Stair 2322 Exit UL ID2-27 Pass

Smoke Detector Corr @ Art rm Exit LL ID1-65 Pass

Smoke Detector Corr @ Art rm LL ID1-63 Pass

Smoke Detector Smoke drs at Stair 2225 UL ID2-12 Pass

Smoke Detector Amin Reception Window LL ID1-126 Pass

Smoke Detector Dish Return 1031 LL ID1-15 Pass

Smoke Detector Media Center Main Entrance LL ID1-161 Pass

Smoke Detector Media Center Main Entrance LL ID1-162 Pass

Smoke Detector Lobby Smoke drs Front LL ID1-51 Pass

Smoke Detector Kindergarten Corr Smoke drs LL ID1-61 Pass

Smoke Detector Kindergarten Corr Smoke drs LL ID1-62 Pass

Smoke Detector Gym Smoke dr by Art rm 1322 LL ID1-67 Pass

Smoke Detector Mech. Rm 1108 LL ID1-71 Pass

Smoke Detector Mech. Rm 1108 LL ID1-72 Pass

Smoke Detector Gym Smoke dr by Music rm 1519 LL ID1-74 Pass

Smoke Detector Eleavtor 2 Lobby LL ID1-110 Pass

Smoke Detector IDF rm 1106 LL ID1-125 Pass

Smoke Detector Smoke drs by Book Store 1201 LL ID1-102 Pass

Smoke Detector Smoke drs by Book Store 1201 LL ID1-103 Pass

Smoke Detector Mech. Rm 1109 LL ID1-101 Pass

Smoke Detector Mech. Rm 1109 LL ID1-100 Pass

Smoke Detector Elevator Equip rm1118 LL ID1-83 Pass

Smoke Detector Eleavtor 1 Lobby LL ID1-109 Pass

Smoke Detector Elect rm 1013 LL ID1-3 Visual

Smoke Detector Lunch rm Smoke drs LL ID1-11 Visual

Smoke Detector Lunch rm Smoke drs LL ID1-12 Visual

Smoke Detector Lunch rm Smoke drs LL ID1-13 Visual

Smoke Detector Corr @ Dish Return LL ID1-14 Visual

Smoke Detector Mech rm 1015 LL ID1-5 No Key

Smoke Detector MDF rm LL ID1-16 Visual

Smoke Detector Mech rm 1040 LL ID1-25 Pass

Smoke Detector Corr Smoke drs LL ID1-45 Not Found

Smoke Detector Elevator Equip rm 1102 LL ID1-53 Visual

Smoke Detector Elevator 1 Pit LL ID1-59 Visual

Smoke Detector Elevator 2 Pit LL ID1-81 Visual

Smoke Detector Special Education Kitchen LL ID1-93 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 48: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Mech rm 1244 LL ID1-99 Not Found

Smoke Detector Eleavtor 2 Lobby UL ID2-35 Pass

Smoke Detector Smoke drs at Elevator 2 Lobby UL ID2-37 Pass

Smoke Detector Rear Commons Smoke drs UL ID2-34 Pass

Smoke Detector Rear Commons Smoke drs UL ID2-4 Pass

Smoke Detector Stair 2525 Smoke drs UL ID2-43 Pass

Smoke Detector Eleavtor 1 Lobby UL ID2-23 Pass

Smoke Detector Front Common @ Smoke drs UL ID2-16 Pass

Smoke Detector Front Common @ Smoke drs UL ID2-14 Pass

Smoke Detector Stair 2225 Smoke drs UL ID2-11 Pass

Smoke Detector Mech. Rm 2109 UL ID2-8 Pass

Smoke Detector Corr @ Bookstore UL ID2-3 Not Found

Smoke Detector Rear Commons Smoke drs UL ID2-5 Visual

Smoke Detector Rear Commons Smoke drs UL ID2-6 Visual

Smoke Detector Mech. Rm 2109 UL ID2-10 Not Found

Smoke Detector Front Common Area UL ID2-15 Visual

Smoke Detector Front Common Area UL ID2-17 Visual

Smoke Detector Mech. Rm 2108 UL ID2-31 Not Found

Smoke Detector Mech. Rm 2108 UL ID2-32 Not Found

Smoke Detector Rear Commons Smoke drs UL ID2-33 Visual

Smoke Detector Eleavtor 2 Top of Shaft UL ID2-45 Visual

Heat Detector Elevator Equip rm 1102 LL ID1-54 Visual

Heat Detector Elevator 1 Pit LL ID1-60 Visual

Heat Detector Elevator 2 Pit LL ID1-82 Visual

Heat Detector Elevator Equip rm 1118 LL ID1-84 Visual

Duct Detector Janitors rm 1206 LL ID1-17 Pass

Duct Detector Media Center 1050 RTU 6 LL ID1-19 Pass

Duct Detector Media Center 1050 RTU 3 LL ID1-20 Pass

Duct Detector Media Center 1050 RTU 4 LL ID1-21 No Access

Duct Detector Mech rm 1041 LL ID1-34 Pass

Duct Detector Lunch rm by Serving LL ID1-35 No Access

Duct Detector Kitchen RTU 5 Return LL ID1-36 Pass

Duct Detector Lunch rm RTU 5 LL ID1-37 Not Found

Duct Detector Lunch rm RTU 1 LL ID1-38 Pass

Duct Detector Lunch rm RTU 1 LL ID1-39 Not Found

Duct Detector Lunch rm RTU 7 LL ID1-41 No Access

Duct Detector Kindergarten class 1203 LL ID1-112 Pass

Duct Detector Lobby 1100 LL ID1-115 Pass

Duct Detector Eleavtor 1 Lobby LL ID1-117 Pass

Duct Detector Mech. Rm 2109 UL ID2-7 Pass

Duct Detector Mech. Rm 2109 UL ID2-9 Pass

Duct Detector Corr @ 5th Grade rm 2301 UL ID2-19 Pass

Duct Detector Multipurpose rm 2315 UL ID2-28 Pass

Duct Detector Multipurpose rm 2315 UL ID2-29 Pass

Duct Detector Multipurpose rm 2315 UL ID2-30 Pass

Duct Detector Work rm 2506 UL ID2-39 Pass

Duct Detector Mech. Rm 2108 UL ID2-40 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 49: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Outside girls rm UL ID2-46 Fail

Duct Detector Eleavtor 2 Lobby UL ID2-50 Pass

Duct Detector Outside girls rm 2103 UL ID2-51 Pass

Duct Detector Outside Book Store UL ID2-52 Not Found

Flow Switch Mech rm 1041 LL ID1-30 Pass

Flow Switch Mech rm 1041 LL ID1-28 Pass

Flow Switch Mech rm 1041 LL ID1-26 Pass

Tamper Switch Mech rm 1041 LL ID1-31 Pass

Tamper Switch Mech rm 1041 LL ID1-29 Pass

Tamper Switch Mech rm 1041 LL ID1-27 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 50: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. 2 Batteries failed load test.

2. Duct Detector at ID2-46 failed to report to panel.

3. HVAC units fail to shut down with duct detector in alarm.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 51: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 52: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Job #Date

NameAddressCity State Zip

Fire Control Panel InspectionManufacturerPanel LocationAccount #

Total Devices

Number of Devices Failed

1 04 43 01 02 11 02 0

Inspector Name : Signature:

3284 Medlock Bridge Rd, Suite 300Norcross, GA 30092 (678) 691-0011

8/7/2020EI1273

Smoke Detectors FSP-851Duct Detectors TBD

30040

Control Panel

Device

Pass

TBD

BatteriesPullstations

Notifier

Device Summary

Panel Power Loss

Open Circuit DetectionPanel Secondary Power Loss

520 Tribble Gap RoadForsyth Central High School Field House

Ground Fault

TBDWho Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredMain LobbyModel Name NFS-320Notifier

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring CompanyEMC

Pass

All-Star Fire, LLC

Power SonicNotifier NBG12LX

FAS 1075

Open Circuits are Detected by Fire Alarm Control PanelLoss of Secondary Power (Batteries/Generator) is Detected

NFS 320

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Notifier

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

NotifierVoice Evac NFC-50/100Heat Detectors Notifier FST-851

Interface Equipment

Pass

Pass

EMC Security

FailPass

Pass

Page 53: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

N/APass

YPassPass

N/AN/AN/A

Condition Voltage Load TestPoor (2016) 12.8 FailPoor (2016) 12.9 FailPoor (2016) 13 FailPoor (2016) 13 Fail

N/AN/AN/AN/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/AFire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/AN/A

N/AN/AN/AN/AN/AN/AN/A

Supervisory Signals

Are the Notification Appliance Circuits Monitored for IntegrityDoes the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation VerifiedEmergency Communications Equipment

Each Strobe Operates ProperlyStrobesWhat Style are the Notification Circuits

Each Device Operates Properly

NAC CircuitsCircuit Style

Phone Sets

Horns

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock ReleaseStairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door HoldersKitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire AlarmFire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Correct Switching and Operation Verified

12v 18ah

Visually Inspected and Operation VerifiedPhone JacksAmplifiers/Tone Generators

FACP (left) 12v 18ahFACP (right)12v 18ah

12v 18ahVoice Evac (right)Voice Evac (left)

Interface Equipment

Generator In Auto

LocationBattery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to PanelFire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump RunningFire Pump Power Loss

Water Level/Water Temp Sensors Report CorrectlySite Water Level /TempTemperature Switch Reports to Panel When ActivatedBuilding Temp

Page 54: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Initating Device TestingDevice Type Location Floor Address/Zone Results

Smoke Detector Lobby above FACP 1 1D001 FailHeat Detector Mech rm 1 1D002 Visual

Smoke Detector Elect rm 1 1D003 PassHeat Detector Mech rm 1 1D004 VisualDuct Detector Freshman Restroom 1 1D006 Not Found

Pull Station Varsity Entry 1 1M001 PassPull Station Lobby Entrance 1 1M002 PassPull Station Freshman Entry 1 1M003 Pass

Page 55: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

3. Failed water flow switch.

Trouble on panel on arrival, waterflow 1M049 INVREP.

Deficiencies 1. 4 Batteries failed load test.2. Smoke detector 1D001 failed to go into alarm, failed to report to panel.

Page 56: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

RecommendationsNone.

Page 57: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 2 0

6 0

14 0

10 0

25 0

2 0

Inspector Name : Signature:

Pass

Firelite FCPS 24FS8

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

System SensorWaterflow WFD40

All-Star Fire, LLC

Yuasa

Firelite BG12-LX

NP7-12

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

MS 9200

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Firelite

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

1130 Dahlonega Highway

Forsyth Academy/ Forsuth Virtual / Academy of Creative Education - PLC

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredElect Room 152

Model Name MS-9200Firelite

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC

D4120

Other

Batteries

Pullstations

FireliteSmoke Detectors SD300

Duct Detectors System Sensor

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/20/2020

EI1273 / WO # 155436

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 58: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.4 Pass

Good (2019) 13.4 Pass

Good (no date) 13 Pass

Good (no date) 13.2 Pass

Good (2020) 13.2 Pass

Good (2020) 13.1 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

Fire Pump Power Loss

FCPS (left) #2 rm 148

FCPS (right) #2 rm 148

12v 7ah

12v 7ah

Correct Switching and Operation Verified

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FCPS (right) #1 rm

FCPS (left) #1 rm

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 59: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station Lobby 1 M01 Pass

Pull Station Exit 150 Hall 1 M02 Pass

Pull Station N Exit 100 Hall 1 M03 Pass

Pull Station S Exit 100 Hall 1 M04 Pass

Pull Station N Exit rm 130 1 M05 Pass

Pull Station S Exit rm 130 1 M06 Pass

Pull Station Entry rm 130 1 M07 Pass

Flow Switch Mech rm 132 1 M08 Pass

Tamper Switch Mech rm 132 1 M09 Pass

Pull Station F/NS Cafe Exit 1 M23 Pass

Pull Station F/NS Cafe Exit 1 M24 Pass

Pull Station F/NS rm 107 1 M25 Pass

Pull Station F/NS Cafe Exit 1 M26 Pass

Pull Station F/NS Dock Exit 1 M34 Pass

Pull Station F/NS Corr Exit 1 M35 Pass

Flow Switch F/NS rm 102 1 M39 Pass

Tamper Switch F/NS rm 102 1 M40 Pass

Ansul Hood rm 112 1 M41 Visual

Duct Detector F/NS rm 142 1 M45 Not found

Pull Station Exit rm 134 1 M96 Pass

Tamper Switch PIV rm 132 1 M97 Not found

Duct Detector F/NS ITS DD 1 P01 Not found

Duct Detector F/NS ITR DD 1 P02 Not found

Smoke Detector 100 Hall rm 102 1 P08 Pass

Smoke Detector 100 Hall rm 108 1 P09 Pass

Smoke Detector 100 Hall rm 122 1 P10 Pass

Smoke Detector 100 Hall rm 130 1 P11 Pass

Smoke Detector Mech rm 132 1 P12 Pass

Smoke Detector Elect rm 133 1 P14 Pass

Smoke Detector Vault rm 112 1 P15 Pass

Smoke Detector Elect rm 152 1 P16 Pass

Smoke Detector Cust rm 154 1 P17 Pass

Smoke Detector 150 Hall rm 154 1 P18 Pass

Smoke Detector 150 Hall rm 159 1 P19 Pass

Smoke Detector 150 Hall rm 163 1 P20 Pass

Smoke Detector Mech rm 116 1 P21 Pass

Smoke Detector F/NS rm 102 1 P22 Visual

Smoke Detector F/NS rm 110 1 P27 Pass

Smoke Detector F/NS rm 110 1 P28 Pass

Smoke Detector F/NS rm 112 1 P29 Pass

Smoke Detector F/NS rm 112 1 P30 Pass

Smoke Detector F/NS rm 140 1 P31 Pass

Smoke Detector F/NS rm 144 1 P32 Pass

Smoke Detector F/NS rm 120 1 P33 Not found

Smoke Detector F/NS rm 148A 1 P36 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 60: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector F/NS rm 150 1 P37 Visual

Smoke Detector F/NS DD rm 102 1 P42 Visual

Duct Detector F/NS DD rm 100 1 P43 Visual

Duct Detector F/NS DD rm 100 1 P44 Not found

Smoke Detector Rm 114 1 P50 Not found

Duct Detector 100 Hall rm 130 1 P51 Pass

Duct Detector AHU #1 DD rm 130 1 P95 Visual

Duct Detector AHU #2 DD rm 135 1 P96 No Access

Duct Detector EHU #1 DD rm 135 1 P97 No Access

Duct Detector DHU #1 DDrm 130 1 P98 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 61: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 62: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 63: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 4 0

12 2

30 0

15 0

56 0

3 0

1 0

Inspector Name : Signature:

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

PotterWaterflow VSR-F

All-Star Fire, LLC

Power patrol

Simplex 4099-9004

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Suwanee

Are Lamps and Displays Operating Properly

Pass

3595 Old Atlanta Road

Sharon Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredHall by Front Desk

Model Name 4010Simplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

4098-9685

Voice Evac Simplex 4003

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

30024

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/8/2020

EI1273 / WO # 155462

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 64: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (no date) 13.5 Pass

Good (no date) 13.5 Pass

Fair (no date) 12.7 FailFair (no date) 12.8 Fail

Fair (no date) 12.9 Pass

Fair (no date) 13 Pass

Good (no date) 13.7 Pass

Good (no date) 13.5 Pass

Good (no date) 13.3 Pass

Good (no date) 13 Pass

Good (no date) 13.1 Pass

Good (no date) 13.1 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

See Note

N/A

N/A

Pass

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Voice Evac rm 1181

FCPS (left) #4 rm 2022

Voice Evac rm 1181

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 1012

FCPS (right) #2 rm 1012

FCPS (left) #3 rm 2115

FCPS (right) #3 rm 2115

12v 7ah

12v 7ah

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ahFCPS (right) #1 rm 1118 FCPS (left) #1 rm 1118

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FCPS (right) #4 rm 2022

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 65: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Duct Detector Storage rm 1058 1hp-ad2 1 M1-2 Not found

Duct Detector Corr 1061 @ rm 1080 1 M1-3 Pass

Smoke Detector Corr 1061 @ smoke Drs 1 M1-4 Not found

Smoke Detector Corr 1061 @ smoke Drs 1 M1-5 Pass

Smoke Detector Corr 1061 @ smoke Drs 1 M1-6 Pass

Smoke Detector Corr 1061 @ smoke Drs 1 M1-7 Pass

Smoke Detector Gym Entrance rm 1200 1 M1-8 Pass

Smoke Detector Gym Entrance rm 1200 1 M1-9 Pass

Smoke Detector Main Lobby Wing D Drs 1 M1-10 Pass

Smoke Detector Gym Exit to Main Lobby 1 M1-11 Pass

Smoke Detector Gym Exit to Main Lobby 1 M1-12 Pass

Smoke Detector Elevator Lobby rm 1010 1 M1-13 Pass

Smoke Detector Elevator Equip rm 1008 1 M1-14 Pass

Smoke Detector D Wing Main Lobby Drs 1 M1-16 Pass

Smoke Detector D Wing Corr 1210 @ Smoke Drs 1 M1-19 Pass

Smoke Detector D Wing Corr 1210 @ Smoke Drs 1 M1-21 Pass

Duct Detector Book Storage rm 1011 WSHP-cc3 1 M1-24 Not found

Smoke Detector C Wing Main Lobby Drs 1 M1-26 Pass

Smoke Detector C Wing Main Lobby Drs 1 M1-27 Pass

Smoke Detector C Wing Elect rm 1012 1 M1-29 Pass

Smoke Detector C Wing @ Smoke Drs 1 M1-31 Pass

Smoke Detector C Wing @ Stair 1047 1 M1-32 Pass

Duct Detector Lunchroom 1180 RTU-3 1 M1-34 Pass

Duct Detector Lunchroom 1180 RTU-2 1 M1-37 Not found

Smoke Detector MDF rm 1077 1 M1-38 Pass

Smoke Detector Corr 1061 Lobby 1100 Smoke Drs 1 M1-39 Pass

Smoke Detector Corr 1061 Lobby 1100 Smoke Drs 1 M1-40 Pass

Smoke Detector Lobby 1100 Corr 1061 Drs 1 M1-41 Pass

Smoke Detector Lobby 1100 Corr 1061 Drs 1 M1-42 Pass

Smoke Detector Lobby 1100 Lunchroom 1180 1 M1-43 Pass

Smoke Detector Lunchroom 1180 Lobby 1100 1 M1-44 Pass

Smoke Detector Lunchroom 1180 Lobby 1100 1 M1-45 Pass

Smoke Detector Lobby 1100 Lunchroom 1180 1 M1-46 Pass

Smoke Detector Lobby 1100 A Wing Drs 1 M1-47 Pass

Smoke Detector A Wing Lobby 1100 Drs 1 M1-48 Pass

Smoke Detector A Wing Elect rm 1183 1 M1-50 Pass

Smoke Detector A Wing @ Smoke Drs 1 M1-51 Pass

Smoke Detector A Wing Printer rm 1176 1 M1-53 Pass

Smoke Detector A Wing @ Stair 1178 1 M1-54 Pass

Duct Detector A Wing Kitchen RTU-K1 1 M1-58 Pass

Smoke Detector A Wing Elect rm 1199A 1 M1-62 Pass

Duct Detector B Wing rm 1112 cc1 1 M1-63 Not found

Smoke Detector B Wing Lobby 1100 @ Smoke Drs 1 M1-64 Pass

Smoke Detector B Wing Lobby 1100 @ Smoke Drs 1 M1-65 Pass

Smoke Detector Elevator Lobby rm 1108 1 M1-67 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 66: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Elevator Equip rm 1108 1 M1-68 Pass

Smoke Detector Elect rm 1118 1 M1-72 Pass

Smoke Detector B Wing @ Stair 1153 1 M1-73 Pass

Smoke Detector B Wing @ Stair 1153 1 M1-75 Pass

Smoke Detector G Wing @ Stair 2041 2 M1-77 Pass

Smoke Detector G Wing @ Smoke Drs 2 M1-78 Pass

Duct Detector Lobby 2000 cc5 2 M1-81 Pass

Smoke Detector Lobby 2000 @ Elevator 2 M1-82 Pass

Smoke Detector Elevator Lobby rm 2010 2 M1-83 Pass

Smoke Detector H Wing @ Smoke Drs 2 M1-84 Pass

Smoke Detector H Wing @ Stair 2225 2 M1-86 Pass

Duct Detector Media Center rm 2050 RTU MC1 2 M1-87 Pass

Duct Detector Rm 2117 WSHP-cc4 2 M1-88 Not found

Smoke Detector F Wing @ Smoke Drs 2 M1-89 Pass

Smoke Detector F Wing @ Stair 2147 2 M1-90 Pass

Smoke Detector Elevator 2 Top of Shaft 2 M1-92 Visual

Smoke Detector Elevator Lobby rm 2112 2 M1-93 Pass

Smoke Detector Lobby 2100 @ Elevator 2 M1-94 Pass

Smoke Detector E Wing @ Smoke Drs 2 M1-100 Pass

Smoke Detector E Wing @ Stair 2173 2 M1-101 Pass

Heat Detector Kitchen rm 2219 2 M1-102 Visual

Smoke Detector Elevator 1 Top of Shaft 2 M1-103 Visual

Heat Detector A Wing Kitchen 1187 1 M1-115 Visual

Duct Detector Mezz above Wrkrm 2002 2 M1-118 Not found

Duct Detector Mezz above Spec Ed rm 2006 2 M1-119 Not found

Duct Detector Mezz above Spec Ed rm 2102 2 M1-120 Not found

Duct Detector Mezz above Reception rm 2108 2 M1-121 Not found

Heat Detector Elevator Equip rm 1006 1 M1-130 Visual

Heat Detector Elevator 2 Top of Shaft 2 M1-131 Visual

Heat Detector Elevator Equip rm 1008 1 M1-132 Visual

Heat Detector Elevator 1 Top of Shaft 2 M1-133 Visual

Duct Detector Gym 1 M1-220 Visual

Monitor A Wing Storage rm 1181 1 M1-1 Not found

Pull Station Main Lobby 1000 1 M1-15 Pass

Pull Station D Wing Corr 1210 @ Main Lobby 1 M1-17 Pass

Pull Station D Wing Storage rm 1209 1 M1-18 Pass

Pull Station D Wing Corr 1210 @ Smoke Drs 1 M1-20 Pass

Pull Station D Wing @ Stair 1233 1 M1-22 Pass

Pull Station Main Lobby 1000 1 M1-23 Pass

Pull Station C Wing Main Lobby Drs 1 M1-28 Pass

Pull Station C Wing @ Smoke Drs 1 M1-30 Pass

Pull Station C Wing @ Stair 1047 1 M1-33 Pass

Pull Station Lunchroom 1180 1 M1-35 Pass

Pull Station Gym rm 1200 1 M1-36 Pass

Pull Station A Wing Lobby @ 1100 Drs 1 M1-49 Pass

Pull Station A Wing @ Printer rm 1176 1 M1-52 Pass

Pull Station A Wing @ Stair 1178 1 M1-55 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 67: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station A Wing Mech rm 1198 1 M1-56 Pass

Pull Station A Wing Receiving rm 1194 1 M1-57 Pass

Ansul Kitchen Hood rm 1187 1 M1-59 Visual

Pull Station Riser rm 1199 1 M 1-60 Pass

Tamper Switch Riser rm 1199 Riser 1 1 M1-61 Pass

Pull Station B Wing Lobby 1100 @ Smoke Drs 1 M1-66 Pass

Pull Station Lobby 1100 1 M1-69 Pass

Pull Station Lobby 1100 1 M1-70 Pass

Pull Station B Wing @ Smoke Drs 1 M1-74 Pass

Pull Station B Wing @ Stair 1153 1 M1-76 Pass

Pull Station G Wing @ Smoke Drs 2 M1-79 Pass

Pull Station Lobby 2000 2 M1-80 Pass

Pull Station H Wing @ Smoke Drs 2 M1-85 Pass

Pull Station F Wing @ Smoke Drs 2 M1-91 Pass

Pull Station Lobby 2100 2 M1-95 Pass

Pull Station Lobby 2100 2 M1-96 Pass

Pull Station Lobby 2100 @ rm 2106 2 M1-98 Pass

Pull Station E Wing @ Smoke Drs 2 M1-99 Pass

Tamper Switch Riser rm 1199 Riser 2 1 M1-134 Pass

Tamper Switch Riser rm 1199 Riser 3 1 M1-135 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 68: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Notes:

Could not test HVAC shutdown as air handlers were turned off.

Deficiencies

1.(2) Batteries failed load test.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 69: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 70: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 5 0

12 4

21 0

34 2

7 0

Inspector Name : Signature:

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

All-Star Fire, LLC

Power Patrol

Simplex 4099-9004

SEC1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

2890 Vaughan Drive

Brookwood Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name 4010Simplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC

4098-9686

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

8/5/2020

EI1273

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 71: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2016) 13.2 Pass

Good (2016) 13.2 Pass

Good (2016) 13.2 Pass

Good (2016) 13.1 Pass

Poor (2016) 12.7 Fail

Poor (2016) 12.8 Fail

Poor (2016) 12.8 Pass

Poor (2016) 12.9 Pass

Poor (2016) 13 Fail

Poor (2016) 13 Fail

Poor (2016) 12.9 Pass

Poor (2016) 12.9 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #5 rm 388

FCPS (left) #4 rm 157

FCPS (left) #5 rm 388

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 257

FCPS (right) #2 rm 257

FCPS (left) #3 rm 257

FCPS (right) #3 rm 257

12v 7ah

12v 7ah

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FCPS (right) #1 rm 257

FCPS (left) #1 rm 257

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FCPS (right) #4 rm 157

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 72: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device testing

Device Type Location Floor Address/Zone Results

Duct Detector Corr @ Multi Classroom 130 1 M1-3 Pass

Duct Detector Mech rm 344 1 M1-6 Pass

Duct Detector Corr @ Elect/Stor rm 345 1 M1-7 Pass

Duct Detector Mech rm 352 1 M1-8 Pass

Duct Detector Corr @ Classroom 320 1 M1-10 Pass

Duct Detector Corr @ Mech rm 322 1 M1-11 Pass

Duct Detector Corr @ Mech rm 322 1 M1-12 Pass

Duct Detector Corr @ Classroom 332 1 M1-13 Pass

Duct Detector Mech rm 344 1 M1-14 Not Found

Duct Detector Corr @ IDF rm 226 1 M1-16 Pass

Duct Detector Corr @ Classroom 233 1 M1-17 Pass

Duct Detector Mech rm 304 1 M1-20 Pass

Duct Detector Mech rm 314 1 M1-22 Pass

Duct Detector Corr @ Classroom 280 1 M1-25 Fail

Duct Detector Mech rm 286 1 M1-26 Pass

Duct Detector Mech rm 296 1 M1-27 Pass

Duct Detector Mech rm 267a 1 M1-29 Pass

Duct Detector Mech rm 277 1 M1-30 Pass

Duct Detector Corr @ Classroom 364 1 M1-32 Pass

Duct Detector Mech rm 366 1 M1-33 Pass

Duct Detector Mech rm 372 1 M1-34 Pass

Duct Detector Mech rm 384 1 M1-36 Pass

Duct Detector Mech rm 392 1 M1-38 Pass

Duct Detector Corr @ Music rm 1 M1-40 Pass

Duct Detector Corr @ Classroom 401 1 M1-41 Pass

Duct Detector Corr @ Mech rm 403 1 M1-42 Pass

Duct Detector Corr @ Classroom 405 1 M1-43 Pass

Duct Detector Corr @ Classroom 412 1 M1-44 Pass

Duct Detector Mech rm 414 1 M1-45 Fail

Duct Detector Kitchen Receiving 1 M1-48 Pass

Duct Detector Kitchen Serving Line 1 M1-49 Pass

Duct Detector Cafeteria @ Elect rm 1 M1-51 Pass

Duct Detector Entry near Cafe 1 M1-52 Pass

Duct Detector Mech rm 421 in Gym 1 M1-57 Not Found

Pull Station Main Lobby Exit 1 M1-4 Pass

Pull Station Main Lobby Exit 1 M1-5 Pass

Pull Station Corr 337 Rear Exit 1 M1-15 Pass

Pull Station Kindergarten Exit 1 M1-19 Pass

Pull Station Corr 317 Rear Exit 1 M1-23 Pass

Pull Station Corr 257 Side Exit 1 M1-24 Pass

Pull Station Corr 287 Rear Exit 1 M1-28 Pass

Pull Station Corr 267 Front Exit 1 M1-31 Pass

Pull Station Corr 376 Rear Exit 1 M1-35 Pass

Pull Station Corr 395 Rear Exit 1 M1-39 Pass

Pull Station Corr 400 Rear Exit 1 M1-46 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 73: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station Front Exit @ Cafeteria 1 M1-53 Pass

Pull Station Cafeteria Exit 1 M1-54 Pass

Pull Station Corr 257 Side Exit 1 M1-55 Pass

Pull Station Mech rm 158 Exit 1 M1-56 Pass

Pull Station Gym Exit 1 M1-58 Pass

Pull Station Gym Exit 1 M1-59 Pass

Pull Station Gym Exit 1 M1-60 Pass

Pull Station Kitchen Receiving Exit 1 M1-64 Pass

Pull Station Storage rm 424 outside a Gym 1 M1-65 Pass

Pull Station Main Office @ FACP 1 M1-69 Pass

Smoke Detector Main Office Above FACP 1 M1-1 Pass

Smoke Detector Elect/Stor rm 133 1 M1-2 Pass

Smoke Detector Elect rm 257a 1 M1-18 Pass

Smoke Detector Elect rm 309 1 M1-21 Pass

Smoke Detector Elect/Stor rm 388 1 M1-37 Pass

Smoke Detector Elect rm 157 1 M1-47 Visual

Smoke Detector Elect/Stor rm 345 1 M1-66 Pass

Pull Station Corr 376 Rear Exit 1 M1-9 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 74: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. 4 Batteries fail load test.

2. The following duct detectors failed to report to panel: M1-25 & M1-45.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 75: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 76: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

2 0

2 0

13 0

40 4

83 0

266 1

215 0

37 0

5 0

5 0

Inspector Name : Signature: David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Power Patrol

4100UControl Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Simplex

Simplex

4099-9001

Who Was Notified Prior to the Start of Testing Monitoring Company & Office Staff

Batteries FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Simplex 4009

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

No

Are Lamps and Displays Operating Properly

(678) 691-0011

4155 Drew Road

30040

Simplex

Admin Main Office

Model Name

Cumming GA

Is the Panel Monitored Yes

4100U

EI1273 / WO # 155469

West Forsyth High School Main Building & Field House

7/13/2020

Waterflow Switches Potter VSR-F

Tamper Switches Kennedy Butterfly

Heat Detectors Simplex 4098-9733EA

Duct Detectors Simplex 4098-9756

Voice Evacuation Panel Simplex 4003

Sub Panel Simplex 4100ES

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 77: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Fail

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2017) 13.6 Pass

Good (2017) 13.5 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Pass

N/A

Pass

Pass

Fail

N/A

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Continued on Page 3 - Battery Testing

FACP (Rear) 12V 18AH

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Magnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 18AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Front)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 78: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Floor Condition Voltage Load Test

1 Good (2019) 13.8 Pass

1 Good (2019) 13.9 Pass

1 Good (2018) 13.8 Pass

1 Good (2018) 13.7 Pass

1 Good (2017) 13.6 Pass

1 Good (2017) 13.8 Pass

1 Good (2017) 13.6 Pass

1 Good (2017) 13.7 Pass

1 Good (2019) 13.9 Pass

1 Good (2019) 13.9 Pass

2 Good (2019) 13.8 Pass

2 Good (2019) 13.8 Pass

2 Good (2017) 13.3 Fail

2 Good (2017) 13.3 Fail

2 Good (2018) 13.4 Pass

2 Good (2018) 13.4 Pass

1 Good (2017) 13.6 Pass

1 Good (2017) 13.7 Pass

1 Good (2019) 13.3 Pass

1 Good (2019) 13.8 Pass

1 Good (2019) 13.8 Pass

1 Good (2019) 13.8 Pass

1 Good (2019) 13.8 Pass

1 Good (2019) 13.8 Pass

1 Good (2017) 12.8 Fail

1 Good (2017) 12.8 Fail

2 Good (2019) 13.8 Pass

2 Good (2019) 13.8 Pass

2 Good (2019) 13.9 Pass

2 Good (2019) 13.9 Pass

1 Good (2019) 13.3 Pass

1 Good (2019) 13.3 Pass

1 Good (2019) 13.4 Pass

1 Good (2019) 13.5 Pass

1 Good (2017) 13.4 Pass

1 Good (2017) 13.4 Pass

2 Good (2019) 13.7 Pass

2 Good (2019) 13.7 Pass

BPS#4 Rm 1607 (Right) 12V 7AH

BPS#3 Rm 1419 (Left) 12V 7AH

BPS#3 Rm 1419 (Right) 12V 7AH

BPS#4 Rm 1607 (Left) 12V 7AH

BPS#2 Rm 1123 (Left) 12V 7AH

BPS#2 Rm 1123 (Right) 12V 7AH

BPS#1 Rm 1241 (Right) 12V 7AH

Battery Testing (cont.)

Location Size

BPS#1 Rm 1241 (Left) 12V 7AH

BPS#5 Rm 1138 (Left) 12V 7AH

BPS#5 Rm 1138 (Right) 12V 7AH

BPS#6 Rm 2245 (Left) 12V 7AH

BPS#6 Rm 2245 (Right) 12V 7AH

BPS#7 Rm 2106 (Left) 12V 7AH

BPS#7 Rm 2106 (Right) 12V 7AH

BPS#8 Rm 2841 (Left) 12V 7AH

BPS#8 Rm 2841 (Right) 12V 7AH

BPS#9 Rm 1725 (Left) 12V 7AH

BPS#9 Rm 1725 (Right) 12V 7AH

BPS#10 Rm 1845 (Left) 12V 7AH

BPS#10 Rm 1845 (Right) 12V 7AH

BPS#11 Rm 1153 (Left) 12V 7AH

BPS#11 Rm 1153 (Right) 12V 7AH

BPS#12 Rm 2153 (Left) 12V 7AH

BPS#12 Rm 2153 (Right) 12V 7AH

BPS#15 IDF Rm 2839 (Left) 12V 7AH

BPS#15 IDF Rm 2839 (Right) 12V 7AH

BPS#13 Rm 1267 (Left) 12V 7AH

BPS#13 Rm 1267 (Right) 12V 7AH

BPS#14 IDF Rm 2839 (Left) 12V 7AH

BPS#14 IDF Rm 2839 (Right) 12V 7AH

Sub Panel IDF Rm 2839 (Right) 12V 18AH

Voice Evac 1100 Hall Gym (Right) 12V 7AH

Voice Evac 1100 Hall Auditorium (Left) 12V 7AH

Voice Evac 1100 Hall Auditorium (Right) 12V 7AH

Voice Evac 1100 Hall Gym (Left) 12V 7AH

Sub Panel IDF Rm 2839 (Left) 12V 18AH

Sub Panel@Football Field House (Left) 12V 7AH

Sub Panel@Football Field House (Right) 12V 7AH

Page 79: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Smoke Detector LL MAIN OFFICE 1 M1 1 Pass

Heat Detector MAIN OFFICE VAULT 1 M1 2 Visual

Pull Station MAIN ENTRANCE SOUTH 1 M1 3 Pass

Pull Station MAIN ENTRANCE NORTH 1 M1 4 Pass

Smoke Detector CORRIDOR BY ELECTRIC RM 1138 1 M1 5 Pass

Heat Detector ELECTRIC RM 1138 1 M1 6 Visual

Heat Detector LL MAIN OFFICE REF RM 1009 1 M1 7 Visual

Smoke Detector LL MAIN OFFICE RM 1007 1 M1 8 Pass

Pull Station LL BY INFO RESOURCE RM 1142 1 M1 9 Pass

Smoke Detector BY INFORMATIOIN RESOURCE RM 1142 1 M1 10 Pass

Smoke Detector CLINIC 1082 1 M1 11 Pass

Heat Detector CLINIC STORAGE RM 1084 1 M1 12 Visual

Smoke Detector LL CORRIDOR NEAR RM 1073 1 M1 13 Pass

Smoke Detector LL ISS RM 1073 1 M1 14 Pass

Smoke Detector LL CORRIDOR BY RM 1069 1 M1 15 Pass

Heat Detector STUDENT RECORD RM 1058 1 M1 16 Visual

Heat Detector LL CAREER CENTER RM 1067 1 M1 17 Visual

Smoke Detector LL CAREER CENTER RM 1053 1 M1 19 Pass

Pull Station LL CORRIDOR BY ISS RM 1073 1 M1 20 Pass

Smoke Detector LL CORRIDOR BY ISS RM 1073 1 M1 21 Pass

Smoke Detector LL CORRIDOR BY SCHL STR 1133 1 M1 22 Pass

Pull Station LL CORRIDOR BY SCHL STR 1133 1 M1 23 Pass

Smoke Detector LL CORRIDOR BY STAIR 3 1 M1 24 Pass

Smoke Detector LL CORRIDOR BY STAIR 3 1 M1 25 Pass

Smoke Detector LL CORRIDOR BY STAIR 3 1 M1 26 Pass

Smoke Detector LL BY SCIENCE LAB 1303 1 M1 27 Pass

Smoke Detector LL BY SCIENCE LAB 1303 1 M1 28 Pass

Heat Detector LL MECHANICAL RM 1305 1 M1 29 Visual

Smoke Detector LL RM 1307 1 M1 30 Pass

Smoke Detector SCIENCE LAB 1301 1 M1 31 Pass

Smoke Detector CORRIDOR BY SCIENCE LAB 1309 1 M1 32 Pass

Heat Detector MECHANICAL RM 1313 1 M1 33 Visual

Heat Detector MECHANICAL RM 1317 1 M1 34 Visual

Smoke Detector LL CORRIDOR BY STAIR 4 1 M1 35 Pass

Smoke Detector LL CORRIDOR BY STAIR 4 1 M1 36 Pass

Pull Station LL CORRIDOR BY STAIR 4 1 M1 37 Pass

Pull Station LL STAIR 4 EXIT 1 M1 38 Pass

Heat Detector MECHANICAL RM 1254 1 M1 39 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET 1243 1 M1 40 Pass

Heat Detector MECHANICAL RM 1234 1 M1 41 Visual

Smoke Detector CORRIDOR BY STAIR 2 1 M1 42 Pass

Smoke Detector LL STAIR 2 1 M1 43 Pass

Pull Station LL STAIR 2 EXIT 1 M1 44 Pass

Pull Station LL CORRIDOR BY STAIR 2 1 M1 45 Pass

Heat Detector MECHANICAL RM 1218 1 M1 46 Visual

Heat Detector MECHANICAL RM 1214 1 M1 47 Visual

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 80: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector CORRIDOR BY SCIENCE LAB 1210 1 M1 48 Pass

Smoke Detector CORRIDOR BY SCIENCE LAB 1210 1 M1 49 Pass

Heat Detector MECH ROOM 1206 1 M1 50 Visual

Smoke Detector SCIENCE LAB STORAGE 1204 1 M1 51 Pass

Smoke Detector SCIENCE LAB 1202 1 M1 52 Pass

Smoke Detector CORRIDOR BY SCIENCE LAB 1202 1 M1 53 Pass

Smoke Detector CORRIDOR BY STAIR 1 1 M1 54 Pass

Smoke Detector CORRIDOR BY STAIR 1 1 M1 55 Pass

Smoke Detector STAIR 1 2 M1 56 Pass

Pull Station EXIT BY NW AUDITORIUM DOOR 1 M1 57 Pass

Smoke Detector CORRIDOR BY NW AUD LOBBY 1 M1 58 Pass

Pull Station EXIT BY NW AUD DOOR 1 M1 59 Pass

Pull Station EXIT BY NW AUD DOOR 1 M1 60 Pass

Heat Detector IDF RM 1112 1 M1 61 Visual

Heat Detector ELECTRICAL RM 1114 1 M1 62 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET 1116 1 M1 63 Pass

Smoke Detector PRINT CLOSET 1116 1 M1 64 Pass

Smoke Detector SCIENCE LAB STORAGE 1205 1 M1 65 Pass

Smoke Detector CORRIDOR BY CUST CLOSET RM 1126 1 M1 66 Pass

Heat Detector CUSTODIAN CLOSET 1126 1 M1 67 Visual

Smoke Detector SCIENCE LAB RM 1302 1 M1 68 Pass

Heat Detector MECHANICAL RM 1304 1 M1 69 Visual

Smoke Detector SCIENCE LAB STORAGE RM 1306 1 M1 70 Pass

Smoke Detector SCIENCE LAB RM 1308 1 M1 71 Pass

Smoke Detector GIS BUSINESS LAB RM 1310 1 M1 72 Pass

Heat Detector MECHANICAL RM 1312 1 M1 73 Visual

Heat Detector MECHANICAL RM 1251 1 M1 74 Visual

Smoke Detector PRINT CLOSET 1243 1 M1 75 Pass

Smoke Detector STORAGE RM 1245 1 M1 76 Pass

Heat Detector IDF RM 1239 1 M1 77 Visual

Heat Detector ELECTRICAL RM 1241 1 M1 78 Visual

Heat Detector CUSTODIAN CLOSET 1233 1 M1 79 Visual

Heat Detector MECHANICAL RM 1215 1 M1 80 Visual

Smoke Detector SCIENCE LAB RM 1211 1 M1 81 Pass

Heat Detector MECHANICAL RM 1207 1 M1 82 Visual

Smoke Detector SCIENCE LAB STORAGE RM 1209 1 M1 83 Pass

Smoke Detector SCIENCE LAB RM 1203 1 M1 84 Pass

Smoke Detector CORRIDOR BY RM 1123 1 M1 85 Pass

Smoke Detector BY COMMUNICATION RM 1502 1 M1 86 Pass

Smoke Detector CHORAL STORAGE RM 1513 1 M1 87 Pass

Duct Detector CHORAL RM 1511 EAST ENTRY 1 M1 88 Pass

Heat Detector MECHANICAL RM 1529 1 M1 89 Visual

Duct Detector CORRIDOR BY RM 1529 ERU-6 1 M1 90 Pass

Smoke Detector CORRIDOR BY MECHANICAL RM 1529 1 M1 91 Pass

Heat Detector ELECTRICAL RM 1541 1 M1 94 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET 1545 1 M1 95 Pass

Smoke Detector PRINT CLOSET 1545 1 M1 96 Pass

Smoke Detector IDF RM 1547 1 M1 97 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 81: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector CORRIDOR BY ART LAB 1551 1 M1 99 Pass

Smoke Detector ART LAB 1551 1 M1 100 Pass

Pull Station ART LAB 1551 EXIT 1 M1 101 Pass

Heat Detector ELECTRICAL RM 1123 1 M1 102 Visual

Heat Detector CUSTODIAN CLOSET 1121 1 M1 103 Visual

Heat Detector MECHANICAL RM 1119 1 M1 104 Visual

Heat Detector NORTH ELEVATOR MACHINE RM 1113 1 M1 105 Visual

Smoke Detector NORTH ELEVATOR MACHINE RM 1113 1 M1 106 Pass

Smoke Detector NORTH ELEVATOR LOBBY 1 M1 111 Pass

Duct Detector PERC STORAGE RM 1525 RTU-C1 1 M1 112 Pass

Heat Detector STORAGE RM 1412 1 M1 115 Visual

Heat Detector MECHANICAL RM 1416 1 M1 116 Visual

Heat Detector ART LAB KILN RM 1422 1 M1 117 Visual

Smoke Detector ART LAB STORAGE RM 1555 1 M1 118 Pass

Smoke Detector ART LAB 1420 1 M1 120 Pass

Pull Station CORRIDOR BY CONSTRUCTION RM 1435 1 M1 121 Pass

Pull Station ART LAB 1420 EXIT 1 M1 122 Pass

Smoke Detector CORRIDOR BY NORTH ELEVATOR 1 1 M1 123 Pass

Smoke Detector CORRIDOR BY ELECTRIC RM 1404 1 M1 124 Pass

Smoke Detector ELECTRICAL RM 1224 1 M1 125 Pass

Smoke Detector AUDITORIUM SEATING 1 M1 126 Visual

Smoke Detector AUDITORIUM SEATING 1 M1 127 Visual

Smoke Detector CORRIDOR BY BAND RM 1517 1 M1 128 Pass

Heat Detector AUD SOUTH CAR WALK STAIRS 1 M1 129 Visual

Smoke Detector AUDITORIUM SEATING 1 M1 130 Visual

Smoke Detector AUDITORIUM SEATING 1 M1 131 Visual

Smoke Detector AUD SOUND RM 1408 1 M1 132 Pass

Pull Station AUD N BUILDING EXIT 1 M1 133 Pass

Heat Detector AUD STAGE STORAGE RM 1417 1 M1 134 Visual

Heat Detector ELECTRIC RM 1419 1 M1 135 Visual

Duct Detector STAGE STORAGE RM 1417 RTU-C7 1 M1 136 Pass

Smoke Detector AUDITORIUM STAGE SOUTH 1 M1 137 Visual

Smoke Detector AUDITORIUM STAGE NORTH 1 M1 139 Visual

Duct Detector AUD STAGE STORAGE RM 1421 RTU-C6 1 M1 140 Pass

Heat Detector AUD STAGE STORAGE RM 1421 1 M1 141 Visual

Pull Station AUD STAGE NORTH BUILDING EXIT 1 M1 142 Pass

Smoke Detector CORRIDOR BY DRAMA RM 1423 1 M1 143 Pass

Duct Detector PROP CONSTRUCTION RM 1425 RTU-C5 1 M1 144 Pass

Duct Detector CONSTRUCTION TECH RM 1435 RTU-C11 1 M1 145 Pass

Heat Detector CONSTRUCTION TECH RM 1435 PLUMBING 1 M1 146 Visual

Heat Detector CONSTRUCTION TECH RM 1435 CARP 1 M1 148 Visual

Pull Station CONSTRUCTION TECH RM 1435 EXIT 1 M1 149 Pass

Heat Detector CONSTRUCTION TECH STORAGE RM 1437 1 M1 150 Visual

Duct Detector AUD OFFICE 1107 RTU-C12 1 M1 151 Pass

Smoke Detector AUD OFFICE 1107 1 M1 152 Pass

Smoke Detector AUD SW ENTRANCE 1 M1 153 Pass

Smoke Detector BY AUD OFFICE RM 1107 1 M1 154 Pass

Smoke Detector BY AUD NORTH STORAGE RM 1101 1 M1 155 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 82: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector AUD CONTROL RM 1406 1 M1 156 Pass

Smoke Detector AUD NORTH STORAGE RM 1101 1 M1 157 Pass

Heat Detector DISPLAY CASE RM 1603 1 M1 158 Visual

Heat Detector MECHANICAL RM 1131 1 M1 159 Visual

Heat Detector MECHANICAL RM 1534 1 M1 160 Visual

Smoke Detector STORAGE RM 1532 (CLASSRM 1528) 1 M1 161 Pass

Heat Detector ELECTRICAL RM 1530 1 M1 162 Visual

Smoke Detector STORAGE 1613 1 M1 163 Pass

Smoke Detector STORAGE RM 1135 1 M1 164 Pass

Heat Detector ELECTRICAL RM 1536 1 M1 165 Visual

Heat Detector MECHANICAL RM 1540 1 M1 166 Visual

Heat Detector LAUNDRY RM 1544 1 M1 167 Visual

Heat Detector WHPC TECHRM 1546 1 M1 168 Visual

Heat Detector MECHANICAL RM 1548 1 M1 169 Visual

Smoke Detector STORAGE RM 1550 1 M1 170 Pass

Pull Station CORRIDOR BY CLASSRM 1554 1 M1 171 Pass

Heat Detector STORAGE RM 1637 1 M1 172 Visual

Heat Detector STORAGE 1635 1 M1 173 Visual

Heat Detector COSMOTOLOGY LAB 1542 1 M1 174 Visual

Heat Detector OUTSIDE STORAGE BY AUTO 1631 1 M1 175 Visual

Pull Station AUTO TECH RM 1631 NE EXIT 1 M1 176 Pass

Heat Detector AUTO TECH RM 1631 1 M1 177 Visual

Monitor UL IDF 2104 ERRCS BATTERY FAIL 2 M1 178 Pass

Smoke Detector MAIN OFFICE BY VAULT 1008 1 M1 179 Pass

Heat Detector UL RM 2245 2 M1 180 Visual

Heat Detector UL IDF RM 2243 2 M1 181 Visual

Smoke Detector PRINT CLOSET RM 2247 2 M1 182 Pass

Smoke Detector STORAGE RM 2249 2 M1 183 Pass

Heat Detector CUSTODIAN CLOSET 2237 2 M1 184 Visual

Smoke Detector CORRIDOR BY CLOSET 2247 2 M1 185 Pass

Heat Detector HEALTH OCCUPATION RM 2318 2 M1 186 Visual

Heat Detector MECHANICAL RM 2320 2 M1 187 Visual

Smoke Detector HELATH OCCUPATION LAB RM 2310 2 M1 188 Pass

Smoke Detector HEALTH OCCUPATION LAB RM 2310 EAST 2 M1 189 Pass

Smoke Detector HEALTH OCCUPATION EXAM 2 M1 190 Pass

Smoke Detector SCIENCE LAB 2308 2 M1 191 Pass

Heat Detector MECHANICAL RM 2304 2 M1 192 Visual

Smoke Detector SCIENCE LAB STORAGE RM 2306 2 M1 193 Pass

Smoke Detector SCIENCE LAB RM 2302 2 M1 194 Pass

Pull Station UL CORRIDOR BY STAIR 3 2 M1 195 Pass

Smoke Detector UL CORRIDOR BY STAIR 3 2 M1 196 Pass

Smoke Detector UL CORRIDOR BY STAIR 3 2 M1 197 Pass

Smoke Detector UL STAIR 3 2 M1 198 Pass

Pull Station UL CORRIDOR BY SCIENCE LAB 2303 2 M1 199 Pass

Smoke Detector UL CORRIDOR BY SCIENCE LAB 2303 2 M1 200 Pass

Smoke Detector SCIENCE LAB 2303 2 M1 201 Pass

Heat Detector MECHANICAL RM 2307 2 M1 202 Visual

Smoke Detector SCIENCE LAB STORAGE RM 2305 2 M1 203 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 83: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector SCIENCE LAB 2309 2 M1 204 Pass

Duct Detector CORRIDOR AT SCIENCE LAB 2309 ERU-2 2 M1 205 Pass

Smoke Detector CORRIDOR BY SCIENCE LAB 2309 2 M1 206 Pass

Heat Detector MECHANICAL RM 2313 2 M1 207 Visual

Heat Detector MECHANICAL RM 2317 2 M1 208 Visual

Smoke Detector UL STAIR 4 2 M1 209 Pass

Smoke Detector UL CORRIDOR BY STAIR 4 2 M1 210 Pass

Pull Station UL CORRIDOR BY STAIR 4 2 M1 211 Pass

Heat Detector BOOK STORAGE RM 2252 2 M1 212 Visual

Heat Detector MECHANICAL RM 2250 2 M1 213 Visual

Smoke Detector CORRIDOR SE OF STAIR 3 2 M1 214 Pass

Heat Detector CUSTODIAN CLOSET 2116 2 M1 215 Visual

Smoke Detector CORRIDOR BY TEACHER WORKRM 2110 2 M1 216 Pass

Smoke Detector SCIENCE LAB STORAGE RM 2205 2 M1 217 Pass

Smoke Detector PRINT CLOSET RM 2108 2 M1 218 Pass

Smoke Detector CORRIDOR BY PRINT CLOSET 2108 2 M1 219 Pass

Smoke Detector NORTH ELEVATOR #1 LOBBY 2 M1 220 Pass

Heat Detector NORTH ELEVATOR TOP OF SHAFT 2 M1 221 Visual

Smoke Detector NORTH ELEVATOR TOP OF SHAFT 2 M1 222 Visual

Heat Detector IDF RM 2104 2 M1 223 Visual

Heat Detector ELECTRIC RM 2106 2 M1 224 Visual

Pull Station CORRIDOR BY SCIENCE LAB 2203 2 M1 226 Pass

Smoke Detector PHYSICS SCIENCE LAB 2203 2 M1 227 Pass

Heat Detector MECHANICAL RM 2207 2 M1 228 Visual

Smoke Detector SCIENCE LAB STORAGE RM 2209 2 M1 229 Pass

Smoke Detector SCIENCE LAB 2211 2 M1 230 PassHeat Detector MECHANICAL RM 2215 2 M1 231 Visual

Smoke Detector CORRIDOR BY STAIR 1 2 M1 232 Pass

Smoke Detector CORRIDOR BY SCIENCE LAB 2202 2 M1 233 Pass

Smoke Detector UL STAIR 1 2 M1 234 Pass

Pull Station CORRIDOR BY STAIR 1 2 M1 235 Pass

Smoke Detector CORRIDOR BY STAIR 1 2 M1 236 Pass

Smoke Detector SCIENCE LAB 2302 2 M1 237 Pass

Heat Detector MECHANICAL RM 2206 2 M1 238 Visual

Smoke Detector SCIENCE LAB STORAGE RM 2208 2 M1 239 Pass

Smoke Detector SCIENCE LAB 2210 2 M1 240 Pass

Duct Detector CORRIDOR AT SCIENCE LAB 2210 ERU-1 2 M1 241 Pass

Smoke Detector UL CORRIDOR BY SCIENCE 2210 2 M1 242 Pass

Heat Detector MECHANICAL RM 2214 2 M1 243 Visual

Heat Detector MECHANICAL 2218 2 M1 244 Visual

Pull Station CORRIDOR BY STAIR 2 2 M1 245 Pass

Smoke Detector CORRIDOR BY STAIR 2 2 M1 246 Pass

Smoke Detector STAIR 2 2 M1 247 Pass

Heat Detector MECHANICAL 2232 2 M1 248 Visual

Smoke Detector BY INFORMATIOIN RESOURCE RM 1142 1 M2 1 Pass

Smoke Detector CORRIDOR BY HEALTH RM 1702 1 M2 2 Pass

Heat Detector FOOD COURT CHAIR STORAGE RM 1614 1 M2 3 Visual

Smoke Detector FOOD COURT 1612 SW 1 M2 4 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 84: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector FOOD COURT 1612 SW ERU-E2 1 M2 5 Pass

Smoke Detector FOOD COURT 1612 SE 1 M2 6 Visual

Duct Detector FOOD COURT 1612 SE ERU-E1 1 M2 7 Pass

Smoke Detector CORRIDOR BY WEIGHT RM 1714 1 M2 8 Pass

Smoke Detector CORRIDOR BY SOUTH KITCHEN ENTRANCE 1 M2 9 Pass

Heat Detector KITCHEN DISHWASH AREA RM 1642 1 M2 10 Visual

Heat Detector KITCHEN SERVING AREA SOUTH 1 M2 12 Visual

Smoke Detector BY STORAGE RM 1715 1 M2 13 Pass

Pull Station CORRIDOR BY STORAGE RM 1715 1 M2 14 Pass

Heat Detector STORAGE RM 1715 1 M2 15 Visual

Heat Detector KITCHEN DRY STORAGE RM 1638 1 M2 16 No Access

Smoke Detector CORRIDOR BY ISS RM 1073 1 M2 18 Pass

Smoke Detector CORRIDOR BY ELECTRIC RM 1607 1 M2 19 Pass

Heat Detector FOOD COURT CHAIR STORAGE RM 1616 1 M2 20 Visual

Duct Detector FOOD COURT 1612 NW ERU-E3 1 M2 21 Pass

Smoke Detector CORRIDOR BY PC TECH DECH 1611 1 M2 22 Pass

Smoke Detector FOOD COURT 1612 NE 1 M2 23 Visual

Duct Detector FOOD COURT 1612 NE ERU-E4 1 M2 24 Pass

Smoke Detector CORRIDOR BY AUTO TECH 1621 1 M2 25 Pass

Heat Detector KITCHEN SERVING AREA NORTH 1 M2 26 Visual

Duct Detector KITCHEN SERVING AREA NORTH RTU-E7 1 M2 27 Pass

Duct Detector KITCHEN SERVING AREA CENTER ERU-5 1 M2 28 Pass

Pull Station CORRIDOR BY AUTO TECH RM 1631 1 M2 29 Pass

Duct Detector KITCHEN 1620 N RTU-5 1 M2 30 Pass

Heat Detector KITCHEN 1620 N 1 M2 31 Visual

Heat Detector KITCHEN RM 1620 SOUTH 1 M2 33 Visual

Heat Detector KITCHEN CUSTODIAN CLOSET 1624 1 M2 34 Visual

Heat Detector KITCHEN UTILITY RM 1632 1 M2 35 Visual

Smoke Detector KITCHEN OFFICE CLOSET 1628 1 M2 36 Pass

Pull Station KITCHEN RM 1620 EAST EXIT 1 M2 37 Pass

Heat Detector ELECTRIC RM 1607 1 M2 38 Visual

Heat Detector MECHANICAL RM 1609 1 M2 39 Visual

Duct Detector PROFFESIONAL FOODS LAB RM 1617 RTU-D1 1 M2 40 Pass

Heat Detector PROFFESIONAL FOODS LAB RM 1617 1 M2 41 Visual

Heat Detector MECHANICAL RM 1623 1 M2 43 Visual

Smoke Detector FOOD LAB LINEN STORAGE 1621 1 M2 44 Pass

Duct Detector AUTO TECHNOLOGY 1631 SW 1 M2 45 Visual

Smoke Detector PROFFESIONAL FOOD LAB PANTRY 1619 1 M2 46 Pass

Heat Detector STORAGE 1703 1 M2 47 Visual

Smoke Detector S ELEVATOR 2 LOBBY 1 M2 48 Pass

Heat Detector STORAGE RM 1708 1 M2 49 Visual

Smoke Detector S ELEVATOR 2 MACHINE RM 1739 1 M2 50 Pass

Heat Detector S ELEVATOR 2 MACHINE RM 1739 1 M2 53 Visual

Smoke Detector MAIN GYM NORTHEAST ELECTRIC RM 1741 1 M2 56 Pass

Heat Detector CUSTODIAN 1745 1 M2 57 Visual

Heat Detector MECHANICAL RM 1704 1 M2 58 Visual

Heat Detector ELECTRIC RM 1153 1 M2 59 Visual

Heat Detector MAIN GYM NORTHWEST STORAGE RM 1737 1 M2 60 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 85: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector MAIN GYM SOUTHWEST STORAGE RM 1 M2 61 Visual

Smoke Detector CORRIDOR BY MAIN GYM SOUTHWEST ENTRY 1 M2 62 Pass

Pull Station BUILDING EXIT BY MAIN GYM SW ENTRY 1 M2 63 Pass

Pull Station BUILDING EXIT BY MAIN GYM SW ENTRY 1 M2 64 Pass

Heat Detector OUTSIDE STORAGE RM 1712 1 M2 65 Visual

Heat Detector CUSTODIAN RM 1733 1 M2 66 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET RM 2156 2 M2 67 Pass

Smoke Detector GIRLS RESTROOM BY RUNNING TRACK 2 M2 68 Pass

Heat Detector MECHANICAL RM 2803 2 M2 69 Visual

Heat Detector MECHANICAL RM 2809 2 M2 70 Visual

Heat Detector MECHANICAL RM 2815 2 M2 71 Visual

Heat Detector CUSTODIAN CLOSET 2833 2 M2 72 Visual

Heat Detector IDF RM 2839 2 M2 73 Visual

Heat Detector ELECTRIC RM 2841 2 M2 74 Visual

Smoke Detector PRINT CLOSET RM 2843 2 M2 75 Pass

Heat Detector MECHANICAL RM 2910 2 M2 76 Visual

Heat Detector MECHANICAL RM 2904 2 M2 77 Visual

Heat Detector AUTO TECH 1631 SE 1 M2 78 Visual

Smoke Detector STAIR 8 2 M2 79 Pass

Smoke Detector STAIR 8 2 M2 80 Pass

Smoke Detector CORRIDOR BY STAIR 9 2 M2 81 Pass

Smoke Detector STAIR 9 2 M2 82 Pass

Smoke Detector CORRIDOR BY MAIN GYM NW ENTRY 1 M2 96 Pass

Pull Station CORRIDOR BY MAIN GYM NW ENTRY 1 M2 97 Pass

Smoke Detector LL STAIR 5 1 M2 98 Pass

Heat Detector MECHANICAL RM 1806 1 M2 99 Visual

Heat Detector MECHANICAL RM 1812 1 M2 100 Visual

Heat Detector MECHANICAL RM 1816 1 M2 101 Visual

Heat Detector BOOK STORAGE RM 1820 1 M2 102 Visual

Smoke Detector STAIR 6 EXIT 1 M2 103 Pass

Pull Station STAIR 6 EXIT 1 M2 104 Pass

Heat Detector BOOK STORAGE RM 1819 1 M2 105 Visual

Smoke Detector SPECIAL ED CLASSRM 1834 1 M2 106 Pass

Pull Station CORRIDOR BY STAIR 6 1 M2 107 Pass

Smoke Detector CORRIDOR BY STAIR 6 1 M2 108 Pass

Heat Detector MECHANICAL RM 1832 1 M2 109 Visual

Heat Detector MECHANICAL RM 1836 1 M2 110 Visual

Smoke Detector SPECIAL ED CLASSRM 1938 CLOSET 1 M2 111 Pass

Smoke Detector SPECIAL ED CLASSRM 1938 1 M2 112 Pass

Heat Detector MECHANICAL RM 1850 1 M2 113 Visual

Smoke Detector SPECIAL ED CLASSRM 1846 1 M2 114 Pass

Smoke Detector LL CORRIDOR BY STAIR 7 1 M2 115 Pass

Pull Station CORRIDOR BY STAIR 7 1 M2 116 Pass

Smoke Detector STAIR 7 1 M2 117 Pass

Pull Station LL STAIR 7 1 M2 118 Pass

Heat Detector MECHANICAL RM 1919 1 M2 119 Visual

Heat Detector MECHANICAL RM 1913 1 M2 120 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 86: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector MECHANICAL RM 1905 1 M2 121 Visual

Heat Detector ELECTRIC RM 1901 1 M2 122 Visual

Heat Detector BOOK STORAGE RM 1172 1 M2 123 Visual

Smoke Detector CORRIDOR BY SOCIAL STUDIES RM 1902 1 M2 124 Pass

Smoke Detector CORRIDOR BY MAIN GYM 1 M2 125 Pass

Pull Station EXIT BY MAIN GYM SOUTHWEST 1 M2 126 Pass

Heat Detector CUSTODIAL CLOSET 1168 1 M2 127 Visual

Smoke Detector CORRIDOR BY CUSTODIAN CLOSET 1168 1 M2 128 Pass

Heat Detector IDF RM 1154 1 M2 129 Visual

Heat Detector PRINT CLOSET 1156 1 M2 130 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET 1156 1 M2 131 Pass

Smoke Detector CORRIDOR BY STAIR 5 1 M2 132 Pass

Smoke Detector CORRIDOR BY STAIR 5 1 M2 133 Pass

Heat Detector MECH RM 1803 1 M2 134 Visual

Smoke Detector CORRIDOR BY LANG. ARTS RM 1604 1 M2 135 Pass

Heat Detector MECH RM 1809 1 M2 136 Visual

Smoke Detector CORRIDOR BY LANG. ARTS RM 1610 1 M2 137 Pass

Heat Detector MECHANICAL RM 1815 1 M2 138 Visual

Smoke Detector CORRIDOR BY MECHANICAL RM 1832 1 M2 139 Pass

Smoke Detector CORRIDOR BY RM 1836 1 M2 140 Pass

Heat Detector CUSTODIAN CLOSET 1837 1 M2 141 Visual

Smoke Detector CORRIDOR BY SPECIAL ED LIVING RM 1844 1 M2 142 Pass

Heat Detector IDF RM 1843 1 M2 143 Visual

Smoke Detector PRINT CLOSET 1847 1 M2 144 Pass

Smoke Detector BOOK STORAGE RM 1849 1 M2 145 Pass

Heat Detector ELECTRIC RM 1845 1 M2 146 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET 1847 1 M2 147 Pass

Smoke Detector CORRIDOR BY SPECIAL ED RM 1846 1 M2 148 Pass

Smoke Detector BOOK STORAGE RM 1851 1 M2 149 Pass

Smoke Detector CORRIDOR BY RM 1852 1 M2 150 Pass

Heat Detector MECHANICAL RM 1916 1 M2 151 Visual

Smoke Detector CORRIDOR BY RM 1909 1 M2 152 Pass

Heat Detector MECHANICAL RM 1910 1 M2 153 Visual

Heat Detector MECHANICAL RM 1904 1 M2 154 Visual

Heat Detector ELECTRIC RM 2144 2 M2 155 Visual

Smoke Detector MEDIA CENTER EAST 2 M2 156 Pass

Smoke Detector MEDIA CENTER SOUTH 2 M2 157 Pass

Smoke Detector MEDIA CENTER 2000 W 2 M2 158 Pass

Smoke Detector MAIN ENTRANCE LOBBY 1 M2 159 Visual

Smoke Detector CORRIDOR BY MEDIA CENTER S 2 M2 160 Pass

Smoke Detector CORRIDOR BY MEDIA CENTER N 2 M2 161 Pass

Duct Detector CORRIDOR BY MEDIA CENTER RTU-MED7 2 M2 162 Pass

Smoke Detector AV STORAGE RM 2001 2 M2 163 Pass

Heat Detector MEDIA CENTER MDF RM 2006 2 M2 164 Visual

Smoke Detector MEDIA CENTER WORK RM 2004 2 M2 165 Pass

Smoke Detector MEDIA CENTER 2000 S 2 M2 166 Pass

Smoke Detector CORRIDOR BY AV STORAGE RM 2001 2 M2 167 Pass

Duct Detector BY RM 2146 RTU-MED3 2 M2 168 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 87: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector CORRIDOR BY INFO. RESOURCE RM 2146 2 M2 169 Pass

Heat Detector ELECTRIC RM 2153 2 M2 170 Visual

Pull Station RUNNING TRACK NORTHWEST ENTRY 2 M2 171 Pass

Smoke Detector SOUTH ELEVATOR 2 LOBBY 2 M2 172 Pass

Smoke Detector SOUTH ELEVATOR TOP OF SHAFT 2 M2 173 Visual

Heat Detector S ELEVATOR 2 TOP OF SHAFT 2 M2 174 Visual

Smoke Detector RUNNING TRACK NE STORAGE RM 2745 2 M2 175 Pass

Pull Station RUNNING TRACK STAIR 8 2 M2 176 Pass

Heat Detector RUNNING TRACK ROOF ACCESS RM 2 M2 177 Visual

Pull Station RUNNING TRACK STAIR 9 2 M2 178 Pass

Smoke Detector RUNNING TRACK STORAGE RM 2767 2 M2 179 Pass

Heat Detector MECH RM 2769 2 M2 180 Visual

Duct Detector MAIN GYM NORTH CENTER 1 M2 181 Visual

Duct Detector MAIN GYM NORTHWEST 1 M2 182 Visual

Heat Detector GYM NORTHWEST 1 M2 183 Visual

Duct Detector MAIN GYM NORTH CENTER 1 M2 184 Visual

Duct Detector MAIN GYM NORTHEAST 1 M2 185 Visual

Heat Detector GYM NORTHEAST 1 M2 186 Visual

Heat Detector GYM NORTH CENTER 1 M2 187 Visual

Duct Detector MAIN GYM CENTER WEST 1 M2 188 Visual

Heat Detector GYM CENTER 1 M2 190 Visual

Duct Detector MAIN GYM CENTER EAST 1 M2 191 Visual

Heat Detector GYM CENTER EAST 1 M2 192 Visual

Duct Detector MAIN GYM SOUTHWEST 1 M2 193 Visual

Heat Detector GYM SOUTHWEST 1 M2 194 Visual

Duct Detector MAIN GYM SOUTH CENTER 1 M2 195 Visual

Duct Detector MAIN GYM SOUTH CENTER 1 M2 196 Visual

Heat Detector GYM SOUTH CENTER 1 M2 197 Visual

Duct Detector MAIN GYM SOUTHEAST 1 M2 198 Visual

Heat Detector GYM SOUTHEAST 1 M2 199 Visual

Pull Station RUNNING TRACK SOUTHWEST ENTRY (W) 2 M2 200 Pass

Pull Station RUNNING TRACK SOUTHWEST ENTRY (E) 2 M2 201 Pass

Pull Station UL EXIT BY CONCESSION STAND 2 M2 202 Pass

Pull Station UL EXIT BY CONCESSION STAND 2 M2 203 Pass

Smoke Detector BY RUNNING TRACK SOUTHWEST ENTRY 2 M2 204 Pass

Duct Detector RUNNING TRACK SOUTHWEST RTU-M1 2 M2 205 Pass

Duct Detector AUX GYM WEST 1 M2 206 Visual

Heat Detector AUX GYM NORTHWEST 1 M2 207 Visual

Heat Detector AUX GYM SOUTHWEST 1 M2 208 Visual

Duct Detector AUX GYM EAST 1 M2 209 Visual

Heat Detector AUX GYM NORTHEAST 1 M2 210 Visual

Heat Detector AUX GYM SOUTHEAST 1 M2 211 Visual

Smoke Detector RUNNING TRACK NORTHWEST 2 M2 212 Pass

Pull Station CORRIDOR BY STAIR 5 2 M2 213 Pass

Smoke Detector STAIR 5 2 M2 214 Pass

Smoke Detector CORRIDOR BY STAIR 5 2 M2 215 Pass

Smoke Detector CORRIDOR BY STAIR 5 2 M2 216 Pass

Smoke Detector CORRIDOR BY LANG. ARTS RM 2604 2 M2 217 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 88: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector MECHANICAL RM 2806 2 M2 218 Visual

Smoke Detector CORRIDOR BY RM 2810 2 M2 219 Pass

Heat Detector MECH RM 2812 2 M2 220 Visual

Duct Detector CORRIDOR BY RM 2814 ERU-4 2 M2 221 Pass

Heat Detector MECH RM 2816 2 M2 222 Visual

Heat Detector BOOK STORAGE RM 2820 2 M2 223 Visual

Smoke Detector STAIR 6 EXIT 2 M2 224 Pass

Smoke Detector CORRIDOR BY STAIR 6 2 M2 225 Pass

Pull Station CORRIDOR BY STAIR 6 2 M2 226 Pass

Heat Detector MECH RM 2834 2 M2 227 Visual

Smoke Detector CORRIDOR BY 2843 2 M2 228 Pass

Heat Detector MECHANICAL RM 2844 2 M2 229 Visual

Smoke Detector CORRIDOR BY STAIR 7 2 M2 230 Pass

Pull Station CORRIDOR BY STAIR 7 2 M2 231 Pass

Smoke Detector UL STAIR 7 2 M2 232 Fail

Heat Detector MECHANICAL RM 2917 2 M2 233 Visual

Duct Detector CORRIDOR BY 2911 ERU3 2 M2 234 Pass

Heat Detector MECHANICAL RM 2913 2 M2 235 Visual

Smoke Detector CORRIDOR BY FOREIGN LANGUAGE RM 2909 2 M2 236 Pass

Heat Detector MECHANICAL RM 2905 2 M2 237 Visual

Heat Detector ELECTRIC RM 2901 2 M2 238 Visual

Heat Detector UL CONCESSION 2163 2 M2 239 Visual

Heat Detector CONCESSION STAND STORAGE RM 2165 2 M2 240 Visual

Smoke Detector CORRIDOR BY SOCIAL STUDIES RM 2902 2 M2 241 Pass

Smoke Detector CORRIDOR BY CONCESSION STAND RM 2163 2 M2 242 Pass

Pull Station CORRIDOR BY ASSISTANT PRINCIPAL 2 M2 243 Pass

Heat Detector IDF RM 2154 2 M2 244 Visual

Smoke Detector PRINT CLOSET RM 2156 2 M2 245 Pass

Smoke Detector FOOD COURT 1612 1 M2 246 Visual

Smoke Detector SPECIAL ED LIVING 1844 1 M2 247 Pass

Smoke Detector SPECIAL ED RM 1852 1 M2 248 Pass

Heat Detector MECH RM 1717 1 M3 1 Visual

Waterflow Switch LL RISER #1 (MAIN MECH RM 1717) 1 M3 2 Pass

Tamper Switch LL RISER #1 (MAIN MECH RM 1717) 1 M3 2 Pass

Waterflow Switch LL RISER #2 (MAIN MECH RM 1717) 1 M3 3 Pass

Tamper Switch LL RISER #2 (MAIN MECH RM 1717) 1 M3 3 Pass

Waterflow Switch LL RISER #3 (MAIN MECH RM 1717) 1 M3 4 Pass

Tamper Switch LL RISER #3 (MAIN MECH RM 1717) 1 M3 4 Pass

Waterflow Switch LL RISER #4 (MAIN MECH RM 1717) 1 M3 5 Pass

Tamper Switch LL RISER #4 (MAIN MECH RM 1717) 1 M3 5 Pass

Waterflow Switch LL RISER #5 (MAIN MECH RM 1717) 1 M3 6 Pass

Tamper Switch LL RISER #5 (MAIN MECH RM 1717) 1 M3 6 Pass

Pull Station MAIN MECHANICAL RM 1717 EAST EXIT 1 M3 7 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 89: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector MECH RM 1717 1 M3 8 Visual

Heat Detector MECH RM 1721 WEST 1 M3 9 Visual

Heat Detector MECH RM 1721 EAST 1 M3 10 Visual

Pull Station STAIR 8 EXIT 1 M3 11 Pass

Pull Station MAIN ELECTRIC RM 1721 1 M3 12 Pass

Smoke Detector CORRIDOR BY STAIR 8 1 M3 13 Pass

Pull Station CORRIDOR BY STAIR 8 1 M3 14 Pass

Smoke Detector STAIR 8 1 M3 15 Pass

Heat Detector BOYS LOCKER RM 1751 1 M3 16 Visual

Heat Detector GIRLS LOCKER RM 1757 1 M3 17 Visual

Pull Station STAIR 9 EXIT 1 M3 18 Pass

Smoke Detector CORRIDOR BY STAIR 9 1 M3 19 Pass

Pull Station CORRIDOR BY STAIR 9 1 M3 20 Pass

Smoke Detector STAIR 9 1 M3 21 Pass

Pull Station CORRIDOR BY BOYS COACH'S OFFICE 1769 1 M3 22 Pass

Heat Detector CUSTODIAN CLOSET 1716 1 M3 23 Visual

Heat Detector MAIN GYM NOETHEAST STORAGE RM 1749 1 M3 24 Visual

Heat Detector MECHANICAL RM 1747 (GYM B LOCKERS) 1 M3 25 Visual

Smoke Detector IDF RM 1718 1 M3 26 Pass

Smoke Detector CORRIDOR BY LOCKER RM 1751 1 M3 27 Pass

Smoke Detector CORRIDOR BY GIRLS LOCKER RM 1757 1 M3 28 Pass

Heat Detector ELECTRIC RM 1725 1 M3 29 Visual

Smoke Detector BY GIRLS COACH'S OFFICE 1765 1 M3 30 Pass

Heat Detector LAUNDRY 1766 BY COACH'S OFFICE 1 M3 31 Visual

Heat Detector MAIN GYM SOUTHEST STORAGE RM 1727 1 M3 32 Visual

Pull Station CORRIDOR BY BOYS COACH'S OFFICE 1769 1 M3 33 Pass

Pull Station FINE ARTS VESTIBULE 1260 1 M3 34 Pass

Pull Station FINE ARTS CORRIDOR 1262 1 M3 35 Pass

Smoke Detector FINE ARTS COMPUTER LAB 1 M3 37 Pass

Smoke Detector FINE ARTS MUSIC LIBRARY 1 M3 38 Pass

Smoke Detector FINE ARTS CHORAL STORAGE 1264 1 M3 39 Pass

Smoke Detector FINE ARTS INSTRUMENT STORAGE 1 M3 43 Pass

Pull Station FINE ARTS CHORAL ROOM 1263 1 M3 45 Pass

Pull Station FINE ARTS SMALL ENSEMBLE 1 M3 46 Pass

Pull Station FINE ARTS BAND ROOM 1270 1 M3 47 Pass

Smoke Detector LL 1600 HALL OF FIREDOORS 1 M3 48 Pass

Smoke Detector LL CORRIDOR 1600 HALL AT FIREDOORS 1 M3 49 Pass

Smoke Detector LL CORRIDOR 1643 AT RESTROOM 1 M3 50 Pass

Pull Station LL CORRIDOR 1643 EXIT DOOR 1 M3 53 Pass

Heat Detector FIELD HOUSE MECH RM 21 1 M4 13 Visual

Pull Station FIELD HOUSE MECHANICAL RM 21 1 M4 14 Pass

Heat Detector FIELD HOUSE HOMELOCKER CUSTODIAN RM 1 M4 15 Visual

Heat Detector FIELD HOUSE HOME LOCKER RM 1 M4 16 Visual

Smoke Detector FIELD HOUSE HOME LOCKER TRAINING 1 M4 17 Pass

Heat Detector FIELD HOUSE MECH RM 25 1 M4 18 Visual

Pull Station FIELD HOUSE MECHANICAL RM 25 1 M4 19 Pass

Pull Station FIELD HOUSE HOME LOCKER EAST EXIT 1 M4 20 Pass

Heat Detector FIELD HOUSE HOME LOCKER RM 1 M4 21 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 90: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector FIELD HOUSE MECH RM 59 1 M4 22 Visual

Pull Station FIELD HOUSE MECHANICAL RM 59 1 M4 23 Pass

Heat Detector FIELD HOUSE STORAGE RM 11 1 M4 24 Visual

Pull Station FIELD HOUSE HOME LOCKER NORTH ENTRY 1 M4 25 Pass

Heat Detector FIELD HOUSE LAUNDRY RM 1 M4 26 Visual

Smoke Detector FIELD HOUSE COACH'S OFFICE RM 22 1 M4 27 Pass

Pull Station FIELD HOUSE COACH'S OFFICE RM 22 1 M4 28 Pass

Pull Station FIELD HOUSE CONCESSIONS 33 SOUTH 1 M4 29 Pass

Heat Detector FIELD HOUSE CONCESSION STAND 33 1 M4 30 Visual

Pull Station FIELD HOUSE CONCESSIONS 33 NORTH 1 M4 31 Pass

Pull Station FIELD HOUSE BOYS LOCKER RM 42 1 M4 32 Pass

Heat Detector FIELD HOUSE BOYS LOCKER RM 42 1 M4 33 Visual

Pull Station FIELD HOUSE VISITOR LOCKER RM 55 1 M4 34 Pass

Pull Station FIELD HOUSE REFEREE LOCKER RM 54 1 M4 35 Pass

Pull Station FIELD HOUSE UTILITY CLOSET 53 1 M4 36 Pass

Heat Detector FIELD HOUSE UTILITY CLOSET 53 1 M4 37 Visual

Heat Detector FIELD HOUSE STORAGE RM 50 1 M4 38 Visual

Heat Detector FIELD HOUSE ELECTRIC RM 52 1 M4 39 Visual

Pull Station FIELD HOUSE ELECTRIC RM 52 1 M4 40 Pass

Pull Station FIELD HOUSE STORAGE RM 50 1 M4 41 Pass

Heat Detector FIELD HOUSE STORAGE RM 51 1 M4 42 Visual

Heat Detector FIELD HOUSE MECH RM 58 1 M4 43 Visual

Pull Station FIELD HOUSE MECH RM 58 (S.) 1 M4 44 Pass

Pull Station FIELD HOUSE MECH RM 58 (N.) 1 M4 45 Pass

Heat Detector FIELD HOUSE VISITOR LOCKER RM 55 1 M4 46 Visual

Heat Detector FIELD HOUSE GIRLS LOCKER RM 40 1 M4 47 Visual

Pull Station FIELD HOUSE GIRLS LOCKER RM 40 1 M4 48 Pass

Heat Detector ELEC RM 1852 1 M5 2 Visual

Heat Detector IDF RM 1853 1 M5 3 Visual

Heat Detector STORAGE RM 1851 1 M5 4 Visual

Smoke Detector STORAGE RM 1851 1 M5 5 Pass

Smoke Detector CORR @ CLASSROOM 1861 1 M5 7 Pass

Smoke Detector CLASSROOM 1861 1 M5 8 Pass

Heat Detector MECH RM 1855 1 M5 9 Visual

Smoke Detector CLASSROOM 1863 1 M5 10 Pass

Pull Station CORR @ CLASSROOM 1863 1 M5 11 Pass

Heat Detector MECH RM 1854 1 M5 12 Visual

Smoke Detector CORRIDOR 1958 1 M5 13 Pass

Smoke Detector CLASSROOM 1864 1 M5 14 Pass

Smoke Detector CLASSROOM 1862 1 M5 15 Pass

Heat Detector MECH RM 1856 1 M5 16 Visual

Smoke Detector CORRIDOR 1958 1 M5 17 Pass

Smoke Detector CLASSROOM 1865 1 M5 18 Pass

Smoke Detector CORRIDOR 1958 1 M5 19 Pass

Smoke Detector SPECIAL ED 1866 1 M5 20 Pass

Heat Detector MECH RM 1955 1 M5 21 Visual

Smoke Detector CLASSROOM 1964 1 M5 22 Pass

Smoke Detector CLASSROOM 1965 1 M5 23 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 91: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector CORRIDOR 1958 1 M5 24 Pass

Heat Detector MECH RM 1954 1 M5 25 Visual

Heat Detector MECH RM 1953 1 M5 26 Visual

Smoke Detector CORRIDOR 1958 1 M5 27 Pass

Smoke Detector CLASSROOM 1962 1 M5 28 Pass

Smoke Detector CLASSROOM 1963 1 M5 29 Pass

Pull Station CORR @ STAIRS S10-1 1 M5 30 Pass

Pull Station STAIRS S10-1 1 M5 31 Pass

Heat Detector STORAGE RM 1952 1 M5 32 Visual

Heat Detector MECH RM 1951 1 M5 33 Visual

Smoke Detector CLASSROOM 1961 1 M5 34 Pass

Smoke Detector CORR @ CLASSROOM 1961 1 M5 35 Pass

Smoke Detector UL IDF RM 2839 FOR FACP SUBPANEL 2 M5 51 Pass

Smoke Detector CORR @ CLASSROOM 2861 2 M5 55 Pass

Smoke Detector CLASSROOM 2861 2 M5 56 Pass

Heat Detector MECH RM 2855 2 M5 57 Visual

Smoke Detector CLASSROOM 2863 2 M5 58 Pass

Heat Detector MECH RM 2854 2 M5 59 Visual

Smoke Detector CORR @ RM 2862 2 M5 60 Pass

Heat Detector EQUIP STORE 2867 2 M5 61 Visual

Heat Detector RESTROOM 2858 2 M5 62 Visual

Smoke Detector MULTI LAB 2864 2 M5 63 Pass

Monitor MULTI LAB 2864 KH 2 M5 64 Pass

Monitor MULTI LAB 2864 KH 2 M5 65 Pass

Monitor MULTI LAB 2864 KH 2 M5 66 Fail

Monitor MULTI LAB 2864 KH 2 M5 67 Pass

Monitor MULTI LAB 2864 KH 2 M5 68 Pass

Monitor MULTI LAB 2864 KH 2 M5 69 Pass

Monitor MULTI LAB 2864 KH 2 M5 70 Pass

Smoke Detector MULTI LAB 2864 2 M5 71 Pass

Smoke Detector CORR @ RM 2862 2 M5 72 Pass

Smoke Detector COMP LAB 2862 2 M5 73 Pass

Smoke Detector COMP LAB 2862 2 M5 74 Pass

Duct Detector CORR @ GIRLS RM 2858 2 M5 75 Pass

Smoke Detector CORR @ BOYS RM 2860 2 M5 76 Pass

Heat Detector IDF RM 2956 2 M5 77 Visual

Smoke Detector CLASSROOM 2964 2 M5 78 Pass

Smoke Detector CLASSROOM 2965 2 M5 79 Pass

Smoke Detector CORR @ MECH 2953 2 M5 80 Pass

Heat Detector MECH RM 2954 2 M5 81 Visual

Heat Detector MECH RM 2953 2 M5 82 Visual

Smoke Detector CORRIDOR 2 M5 83 Pass

Smoke Detector CLASSROOM 2962 2 M5 84 Pass

Smoke Detector CLASSROOM 2963 2 M5 85 Pass

Smoke Detector CORRIDOR 2 M5 86 Pass

Pull Station STAIRS S10-2 2 M5 87 Pass

Heat Detector STORAGE RM 2952 2 M5 88 Visual

Heat Detector MECH RM 2951 2 M5 89 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 92: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector CLASSROOM 2961 2 M5 90 Pass

Smoke Detector CORR @ CLASSROOM 2961 2 M5 91 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 93: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

(1) Simplex 4090-9001 monitor module M5-66 No Answer trouble on arrival. Module monitors kitchen hood system

temperature sensors on 2nd floor in room 2864.

Deficiencies

(4) 12V 7AH batteries failed load testing and need replacement.

(1) Red wall mounted Simplex speakerstrobe in cafeteria failed to activate visual notification during alarm.

(1) Smoke Detector (M2-232) on 2nd fl Upper Level Stair 7 fails to report to FACP.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 94: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

(1) Smoke Detector (M2-132) on 1st Floor Corridor by Stair 5 reports to FACP,

but base isn't fully secured to ceiling

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 95: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

2 0

2 0

13 0

40 4

83 0

266 1

215 0

37 0

5 0

5 0

Inspector Name : Signature:

Voice Evacuation Panel Simplex 4003

Sub Panel Simplex 4100ES

Heat Detectors Simplex 4098-9733EA

Duct Detectors Simplex 4098-9756

Waterflow Switches Potter VSR-F

Tamper Switches Kennedy Butterfly

(678) 691-0011

4155 Drew Road

30040

Simplex

Admin Main Office

Model Name

Cumming GA

Is the Panel Monitored Yes

4100U

EI1273 / WO # 155469

West Forsyth High School Main Building & Field House

7/13/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

No

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing Monitoring Company & Office Staff

Batteries FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Simplex 4009

David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Power Patrol

4100UControl Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Simplex

Simplex

4099-9001

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 96: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Fail

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2017) 13.6 Pass

Good (2017) 13.5 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Pass

N/A

Pass

Pass

Fail

N/A

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 18AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Front)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Continued on Page 3 - Battery Testing

FACP (Rear) 12V 18AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 97: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Floor Condition Voltage Load Test

1 Good (2019) 13.8 Pass

1 Good (2019) 13.9 Pass

1 Good (2018) 13.8 Pass

1 Good (2018) 13.7 Pass

1 Good (2017) 13.6 Pass

1 Good (2017) 13.8 Pass

1 Good (2017) 13.6 Pass

1 Good (2017) 13.7 Pass

1 Good (2019) 13.9 Pass

1 Good (2019) 13.9 Pass

2 Good (2019) 13.8 Pass

2 Good (2019) 13.8 Pass

2 Good (2017) 13.3 Fail

2 Good (2017) 13.3 Fail

2 Good (2018) 13.4 Pass

2 Good (2018) 13.4 Pass

1 Good (2017) 13.6 Pass

1 Good (2017) 13.7 Pass

1 Good (2019) 13.3 Pass

1 Good (2019) 13.8 Pass

1 Good (2019) 13.8 Pass

1 Good (2019) 13.8 Pass

1 Good (2019) 13.8 Pass

1 Good (2019) 13.8 Pass

1 Good (2017) 12.8 Fail

1 Good (2017) 12.8 Fail

2 Good (2019) 13.8 Pass

2 Good (2019) 13.8 Pass

2 Good (2019) 13.9 Pass

2 Good (2019) 13.9 Pass

1 Good (2019) 13.3 Pass

1 Good (2019) 13.3 Pass

1 Good (2019) 13.4 Pass

1 Good (2019) 13.5 Pass

1 Good (2017) 13.4 Pass

1 Good (2017) 13.4 Pass

2 Good (2019) 13.7 Pass

2 Good (2019) 13.7 PassSub Panel IDF Rm 2839 (Right) 12V 18AH

Voice Evac 1100 Hall Gym (Right) 12V 7AH

Voice Evac 1100 Hall Auditorium (Left) 12V 7AH

Voice Evac 1100 Hall Auditorium (Right) 12V 7AH

Voice Evac 1100 Hall Gym (Left) 12V 7AH

Sub Panel IDF Rm 2839 (Left) 12V 18AH

Sub Panel@Football Field House (Left) 12V 7AH

Sub Panel@Football Field House (Right) 12V 7AH

BPS#12 Rm 2153 (Right) 12V 7AH

BPS#15 IDF Rm 2839 (Left) 12V 7AH

BPS#15 IDF Rm 2839 (Right) 12V 7AH

BPS#13 Rm 1267 (Left) 12V 7AH

BPS#13 Rm 1267 (Right) 12V 7AH

BPS#14 IDF Rm 2839 (Left) 12V 7AH

BPS#14 IDF Rm 2839 (Right) 12V 7AH

BPS#11 Rm 1153 (Left) 12V 7AH

BPS#11 Rm 1153 (Right) 12V 7AH

BPS#12 Rm 2153 (Left) 12V 7AH

BPS#9 Rm 1725 (Right) 12V 7AH

BPS#10 Rm 1845 (Left) 12V 7AH

BPS#10 Rm 1845 (Right) 12V 7AH

BPS#8 Rm 2841 (Left) 12V 7AH

BPS#8 Rm 2841 (Right) 12V 7AH

BPS#9 Rm 1725 (Left) 12V 7AH

BPS#6 Rm 2245 (Right) 12V 7AH

BPS#7 Rm 2106 (Left) 12V 7AH

BPS#7 Rm 2106 (Right) 12V 7AH

BPS#5 Rm 1138 (Left) 12V 7AH

BPS#5 Rm 1138 (Right) 12V 7AH

BPS#6 Rm 2245 (Left) 12V 7AH

Battery Testing (cont.)

Location Size

BPS#1 Rm 1241 (Left) 12V 7AH

BPS#2 Rm 1123 (Left) 12V 7AH

BPS#2 Rm 1123 (Right) 12V 7AH

BPS#1 Rm 1241 (Right) 12V 7AH

BPS#4 Rm 1607 (Right) 12V 7AH

BPS#3 Rm 1419 (Left) 12V 7AH

BPS#3 Rm 1419 (Right) 12V 7AH

BPS#4 Rm 1607 (Left) 12V 7AH

Page 98: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Smoke Detector LL MAIN OFFICE 1 M1 1 Pass

Heat Detector MAIN OFFICE VAULT 1 M1 2 Visual

Pull Station MAIN ENTRANCE SOUTH 1 M1 3 Pass

Pull Station MAIN ENTRANCE NORTH 1 M1 4 Pass

Smoke Detector CORRIDOR BY ELECTRIC RM 1138 1 M1 5 Pass

Heat Detector ELECTRIC RM 1138 1 M1 6 Visual

Heat Detector LL MAIN OFFICE REF RM 1009 1 M1 7 Visual

Smoke Detector LL MAIN OFFICE RM 1007 1 M1 8 Pass

Pull Station LL BY INFO RESOURCE RM 1142 1 M1 9 Pass

Smoke Detector BY INFORMATIOIN RESOURCE RM 1142 1 M1 10 Pass

Smoke Detector CLINIC 1082 1 M1 11 Pass

Heat Detector CLINIC STORAGE RM 1084 1 M1 12 Visual

Smoke Detector LL CORRIDOR NEAR RM 1073 1 M1 13 Pass

Smoke Detector LL ISS RM 1073 1 M1 14 Pass

Smoke Detector LL CORRIDOR BY RM 1069 1 M1 15 Pass

Heat Detector STUDENT RECORD RM 1058 1 M1 16 Visual

Heat Detector LL CAREER CENTER RM 1067 1 M1 17 Visual

Smoke Detector LL CAREER CENTER RM 1053 1 M1 19 Pass

Pull Station LL CORRIDOR BY ISS RM 1073 1 M1 20 Pass

Smoke Detector LL CORRIDOR BY ISS RM 1073 1 M1 21 Pass

Smoke Detector LL CORRIDOR BY SCHL STR 1133 1 M1 22 Pass

Pull Station LL CORRIDOR BY SCHL STR 1133 1 M1 23 Pass

Smoke Detector LL CORRIDOR BY STAIR 3 1 M1 24 Pass

Smoke Detector LL CORRIDOR BY STAIR 3 1 M1 25 Pass

Smoke Detector LL CORRIDOR BY STAIR 3 1 M1 26 Pass

Smoke Detector LL BY SCIENCE LAB 1303 1 M1 27 Pass

Smoke Detector LL BY SCIENCE LAB 1303 1 M1 28 Pass

Heat Detector LL MECHANICAL RM 1305 1 M1 29 Visual

Smoke Detector LL RM 1307 1 M1 30 Pass

Smoke Detector SCIENCE LAB 1301 1 M1 31 Pass

Smoke Detector CORRIDOR BY SCIENCE LAB 1309 1 M1 32 Pass

Heat Detector MECHANICAL RM 1313 1 M1 33 Visual

Heat Detector MECHANICAL RM 1317 1 M1 34 Visual

Smoke Detector LL CORRIDOR BY STAIR 4 1 M1 35 Pass

Smoke Detector LL CORRIDOR BY STAIR 4 1 M1 36 Pass

Pull Station LL CORRIDOR BY STAIR 4 1 M1 37 Pass

Pull Station LL STAIR 4 EXIT 1 M1 38 Pass

Heat Detector MECHANICAL RM 1254 1 M1 39 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET 1243 1 M1 40 Pass

Heat Detector MECHANICAL RM 1234 1 M1 41 Visual

Smoke Detector CORRIDOR BY STAIR 2 1 M1 42 Pass

Smoke Detector LL STAIR 2 1 M1 43 Pass

Pull Station LL STAIR 2 EXIT 1 M1 44 Pass

Pull Station LL CORRIDOR BY STAIR 2 1 M1 45 Pass

Heat Detector MECHANICAL RM 1218 1 M1 46 Visual

Heat Detector MECHANICAL RM 1214 1 M1 47 Visual

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 99: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector CORRIDOR BY SCIENCE LAB 1210 1 M1 48 Pass

Smoke Detector CORRIDOR BY SCIENCE LAB 1210 1 M1 49 Pass

Heat Detector MECH ROOM 1206 1 M1 50 Visual

Smoke Detector SCIENCE LAB STORAGE 1204 1 M1 51 Pass

Smoke Detector SCIENCE LAB 1202 1 M1 52 Pass

Smoke Detector CORRIDOR BY SCIENCE LAB 1202 1 M1 53 Pass

Smoke Detector CORRIDOR BY STAIR 1 1 M1 54 Pass

Smoke Detector CORRIDOR BY STAIR 1 1 M1 55 Pass

Smoke Detector STAIR 1 2 M1 56 Pass

Pull Station EXIT BY NW AUDITORIUM DOOR 1 M1 57 Pass

Smoke Detector CORRIDOR BY NW AUD LOBBY 1 M1 58 Pass

Pull Station EXIT BY NW AUD DOOR 1 M1 59 Pass

Pull Station EXIT BY NW AUD DOOR 1 M1 60 Pass

Heat Detector IDF RM 1112 1 M1 61 Visual

Heat Detector ELECTRICAL RM 1114 1 M1 62 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET 1116 1 M1 63 Pass

Smoke Detector PRINT CLOSET 1116 1 M1 64 Pass

Smoke Detector SCIENCE LAB STORAGE 1205 1 M1 65 Pass

Smoke Detector CORRIDOR BY CUST CLOSET RM 1126 1 M1 66 Pass

Heat Detector CUSTODIAN CLOSET 1126 1 M1 67 Visual

Smoke Detector SCIENCE LAB RM 1302 1 M1 68 Pass

Heat Detector MECHANICAL RM 1304 1 M1 69 Visual

Smoke Detector SCIENCE LAB STORAGE RM 1306 1 M1 70 Pass

Smoke Detector SCIENCE LAB RM 1308 1 M1 71 Pass

Smoke Detector GIS BUSINESS LAB RM 1310 1 M1 72 Pass

Heat Detector MECHANICAL RM 1312 1 M1 73 Visual

Heat Detector MECHANICAL RM 1251 1 M1 74 Visual

Smoke Detector PRINT CLOSET 1243 1 M1 75 Pass

Smoke Detector STORAGE RM 1245 1 M1 76 Pass

Heat Detector IDF RM 1239 1 M1 77 Visual

Heat Detector ELECTRICAL RM 1241 1 M1 78 Visual

Heat Detector CUSTODIAN CLOSET 1233 1 M1 79 Visual

Heat Detector MECHANICAL RM 1215 1 M1 80 Visual

Smoke Detector SCIENCE LAB RM 1211 1 M1 81 Pass

Heat Detector MECHANICAL RM 1207 1 M1 82 Visual

Smoke Detector SCIENCE LAB STORAGE RM 1209 1 M1 83 Pass

Smoke Detector SCIENCE LAB RM 1203 1 M1 84 Pass

Smoke Detector CORRIDOR BY RM 1123 1 M1 85 Pass

Smoke Detector BY COMMUNICATION RM 1502 1 M1 86 Pass

Smoke Detector CHORAL STORAGE RM 1513 1 M1 87 Pass

Duct Detector CHORAL RM 1511 EAST ENTRY 1 M1 88 Pass

Heat Detector MECHANICAL RM 1529 1 M1 89 Visual

Duct Detector CORRIDOR BY RM 1529 ERU-6 1 M1 90 Pass

Smoke Detector CORRIDOR BY MECHANICAL RM 1529 1 M1 91 Pass

Heat Detector ELECTRICAL RM 1541 1 M1 94 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET 1545 1 M1 95 Pass

Smoke Detector PRINT CLOSET 1545 1 M1 96 Pass

Smoke Detector IDF RM 1547 1 M1 97 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 100: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector CORRIDOR BY ART LAB 1551 1 M1 99 Pass

Smoke Detector ART LAB 1551 1 M1 100 Pass

Pull Station ART LAB 1551 EXIT 1 M1 101 Pass

Heat Detector ELECTRICAL RM 1123 1 M1 102 Visual

Heat Detector CUSTODIAN CLOSET 1121 1 M1 103 Visual

Heat Detector MECHANICAL RM 1119 1 M1 104 Visual

Heat Detector NORTH ELEVATOR MACHINE RM 1113 1 M1 105 Visual

Smoke Detector NORTH ELEVATOR MACHINE RM 1113 1 M1 106 Pass

Smoke Detector NORTH ELEVATOR LOBBY 1 M1 111 Pass

Duct Detector PERC STORAGE RM 1525 RTU-C1 1 M1 112 Pass

Heat Detector STORAGE RM 1412 1 M1 115 Visual

Heat Detector MECHANICAL RM 1416 1 M1 116 Visual

Heat Detector ART LAB KILN RM 1422 1 M1 117 Visual

Smoke Detector ART LAB STORAGE RM 1555 1 M1 118 Pass

Smoke Detector ART LAB 1420 1 M1 120 Pass

Pull Station CORRIDOR BY CONSTRUCTION RM 1435 1 M1 121 Pass

Pull Station ART LAB 1420 EXIT 1 M1 122 Pass

Smoke Detector CORRIDOR BY NORTH ELEVATOR 1 1 M1 123 Pass

Smoke Detector CORRIDOR BY ELECTRIC RM 1404 1 M1 124 Pass

Smoke Detector ELECTRICAL RM 1224 1 M1 125 Pass

Smoke Detector AUDITORIUM SEATING 1 M1 126 Visual

Smoke Detector AUDITORIUM SEATING 1 M1 127 Visual

Smoke Detector CORRIDOR BY BAND RM 1517 1 M1 128 Pass

Heat Detector AUD SOUTH CAR WALK STAIRS 1 M1 129 Visual

Smoke Detector AUDITORIUM SEATING 1 M1 130 Visual

Smoke Detector AUDITORIUM SEATING 1 M1 131 Visual

Smoke Detector AUD SOUND RM 1408 1 M1 132 Pass

Pull Station AUD N BUILDING EXIT 1 M1 133 Pass

Heat Detector AUD STAGE STORAGE RM 1417 1 M1 134 Visual

Heat Detector ELECTRIC RM 1419 1 M1 135 Visual

Duct Detector STAGE STORAGE RM 1417 RTU-C7 1 M1 136 Pass

Smoke Detector AUDITORIUM STAGE SOUTH 1 M1 137 Visual

Smoke Detector AUDITORIUM STAGE NORTH 1 M1 139 Visual

Duct Detector AUD STAGE STORAGE RM 1421 RTU-C6 1 M1 140 Pass

Heat Detector AUD STAGE STORAGE RM 1421 1 M1 141 Visual

Pull Station AUD STAGE NORTH BUILDING EXIT 1 M1 142 Pass

Smoke Detector CORRIDOR BY DRAMA RM 1423 1 M1 143 Pass

Duct Detector PROP CONSTRUCTION RM 1425 RTU-C5 1 M1 144 Pass

Duct Detector CONSTRUCTION TECH RM 1435 RTU-C11 1 M1 145 Pass

Heat Detector CONSTRUCTION TECH RM 1435 PLUMBING 1 M1 146 Visual

Heat Detector CONSTRUCTION TECH RM 1435 CARP 1 M1 148 Visual

Pull Station CONSTRUCTION TECH RM 1435 EXIT 1 M1 149 Pass

Heat Detector CONSTRUCTION TECH STORAGE RM 1437 1 M1 150 Visual

Duct Detector AUD OFFICE 1107 RTU-C12 1 M1 151 Pass

Smoke Detector AUD OFFICE 1107 1 M1 152 Pass

Smoke Detector AUD SW ENTRANCE 1 M1 153 Pass

Smoke Detector BY AUD OFFICE RM 1107 1 M1 154 Pass

Smoke Detector BY AUD NORTH STORAGE RM 1101 1 M1 155 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 101: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector AUD CONTROL RM 1406 1 M1 156 Pass

Smoke Detector AUD NORTH STORAGE RM 1101 1 M1 157 Pass

Heat Detector DISPLAY CASE RM 1603 1 M1 158 Visual

Heat Detector MECHANICAL RM 1131 1 M1 159 Visual

Heat Detector MECHANICAL RM 1534 1 M1 160 Visual

Smoke Detector STORAGE RM 1532 (CLASSRM 1528) 1 M1 161 Pass

Heat Detector ELECTRICAL RM 1530 1 M1 162 Visual

Smoke Detector STORAGE 1613 1 M1 163 Pass

Smoke Detector STORAGE RM 1135 1 M1 164 Pass

Heat Detector ELECTRICAL RM 1536 1 M1 165 Visual

Heat Detector MECHANICAL RM 1540 1 M1 166 Visual

Heat Detector LAUNDRY RM 1544 1 M1 167 Visual

Heat Detector WHPC TECHRM 1546 1 M1 168 Visual

Heat Detector MECHANICAL RM 1548 1 M1 169 Visual

Smoke Detector STORAGE RM 1550 1 M1 170 Pass

Pull Station CORRIDOR BY CLASSRM 1554 1 M1 171 Pass

Heat Detector STORAGE RM 1637 1 M1 172 Visual

Heat Detector STORAGE 1635 1 M1 173 Visual

Heat Detector COSMOTOLOGY LAB 1542 1 M1 174 Visual

Heat Detector OUTSIDE STORAGE BY AUTO 1631 1 M1 175 Visual

Pull Station AUTO TECH RM 1631 NE EXIT 1 M1 176 Pass

Heat Detector AUTO TECH RM 1631 1 M1 177 Visual

Monitor UL IDF 2104 ERRCS BATTERY FAIL 2 M1 178 Pass

Smoke Detector MAIN OFFICE BY VAULT 1008 1 M1 179 Pass

Heat Detector UL RM 2245 2 M1 180 Visual

Heat Detector UL IDF RM 2243 2 M1 181 Visual

Smoke Detector PRINT CLOSET RM 2247 2 M1 182 Pass

Smoke Detector STORAGE RM 2249 2 M1 183 Pass

Heat Detector CUSTODIAN CLOSET 2237 2 M1 184 Visual

Smoke Detector CORRIDOR BY CLOSET 2247 2 M1 185 Pass

Heat Detector HEALTH OCCUPATION RM 2318 2 M1 186 Visual

Heat Detector MECHANICAL RM 2320 2 M1 187 Visual

Smoke Detector HELATH OCCUPATION LAB RM 2310 2 M1 188 Pass

Smoke Detector HEALTH OCCUPATION LAB RM 2310 EAST 2 M1 189 Pass

Smoke Detector HEALTH OCCUPATION EXAM 2 M1 190 Pass

Smoke Detector SCIENCE LAB 2308 2 M1 191 Pass

Heat Detector MECHANICAL RM 2304 2 M1 192 Visual

Smoke Detector SCIENCE LAB STORAGE RM 2306 2 M1 193 Pass

Smoke Detector SCIENCE LAB RM 2302 2 M1 194 Pass

Pull Station UL CORRIDOR BY STAIR 3 2 M1 195 Pass

Smoke Detector UL CORRIDOR BY STAIR 3 2 M1 196 Pass

Smoke Detector UL CORRIDOR BY STAIR 3 2 M1 197 Pass

Smoke Detector UL STAIR 3 2 M1 198 Pass

Pull Station UL CORRIDOR BY SCIENCE LAB 2303 2 M1 199 Pass

Smoke Detector UL CORRIDOR BY SCIENCE LAB 2303 2 M1 200 Pass

Smoke Detector SCIENCE LAB 2303 2 M1 201 Pass

Heat Detector MECHANICAL RM 2307 2 M1 202 Visual

Smoke Detector SCIENCE LAB STORAGE RM 2305 2 M1 203 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 102: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector SCIENCE LAB 2309 2 M1 204 Pass

Duct Detector CORRIDOR AT SCIENCE LAB 2309 ERU-2 2 M1 205 Pass

Smoke Detector CORRIDOR BY SCIENCE LAB 2309 2 M1 206 Pass

Heat Detector MECHANICAL RM 2313 2 M1 207 Visual

Heat Detector MECHANICAL RM 2317 2 M1 208 Visual

Smoke Detector UL STAIR 4 2 M1 209 Pass

Smoke Detector UL CORRIDOR BY STAIR 4 2 M1 210 Pass

Pull Station UL CORRIDOR BY STAIR 4 2 M1 211 Pass

Heat Detector BOOK STORAGE RM 2252 2 M1 212 Visual

Heat Detector MECHANICAL RM 2250 2 M1 213 Visual

Smoke Detector CORRIDOR SE OF STAIR 3 2 M1 214 Pass

Heat Detector CUSTODIAN CLOSET 2116 2 M1 215 Visual

Smoke Detector CORRIDOR BY TEACHER WORKRM 2110 2 M1 216 Pass

Smoke Detector SCIENCE LAB STORAGE RM 2205 2 M1 217 Pass

Smoke Detector PRINT CLOSET RM 2108 2 M1 218 Pass

Smoke Detector CORRIDOR BY PRINT CLOSET 2108 2 M1 219 Pass

Smoke Detector NORTH ELEVATOR #1 LOBBY 2 M1 220 Pass

Heat Detector NORTH ELEVATOR TOP OF SHAFT 2 M1 221 Visual

Smoke Detector NORTH ELEVATOR TOP OF SHAFT 2 M1 222 Visual

Heat Detector IDF RM 2104 2 M1 223 Visual

Heat Detector ELECTRIC RM 2106 2 M1 224 Visual

Pull Station CORRIDOR BY SCIENCE LAB 2203 2 M1 226 Pass

Smoke Detector PHYSICS SCIENCE LAB 2203 2 M1 227 Pass

Heat Detector MECHANICAL RM 2207 2 M1 228 Visual

Smoke Detector SCIENCE LAB STORAGE RM 2209 2 M1 229 Pass

Smoke Detector SCIENCE LAB 2211 2 M1 230 PassHeat Detector MECHANICAL RM 2215 2 M1 231 Visual

Smoke Detector CORRIDOR BY STAIR 1 2 M1 232 Pass

Smoke Detector CORRIDOR BY SCIENCE LAB 2202 2 M1 233 Pass

Smoke Detector UL STAIR 1 2 M1 234 Pass

Pull Station CORRIDOR BY STAIR 1 2 M1 235 Pass

Smoke Detector CORRIDOR BY STAIR 1 2 M1 236 Pass

Smoke Detector SCIENCE LAB 2302 2 M1 237 Pass

Heat Detector MECHANICAL RM 2206 2 M1 238 Visual

Smoke Detector SCIENCE LAB STORAGE RM 2208 2 M1 239 Pass

Smoke Detector SCIENCE LAB 2210 2 M1 240 Pass

Duct Detector CORRIDOR AT SCIENCE LAB 2210 ERU-1 2 M1 241 Pass

Smoke Detector UL CORRIDOR BY SCIENCE 2210 2 M1 242 Pass

Heat Detector MECHANICAL RM 2214 2 M1 243 Visual

Heat Detector MECHANICAL 2218 2 M1 244 Visual

Pull Station CORRIDOR BY STAIR 2 2 M1 245 Pass

Smoke Detector CORRIDOR BY STAIR 2 2 M1 246 Pass

Smoke Detector STAIR 2 2 M1 247 Pass

Heat Detector MECHANICAL 2232 2 M1 248 Visual

Smoke Detector BY INFORMATIOIN RESOURCE RM 1142 1 M2 1 Pass

Smoke Detector CORRIDOR BY HEALTH RM 1702 1 M2 2 Pass

Heat Detector FOOD COURT CHAIR STORAGE RM 1614 1 M2 3 Visual

Smoke Detector FOOD COURT 1612 SW 1 M2 4 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 103: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector FOOD COURT 1612 SW ERU-E2 1 M2 5 Pass

Smoke Detector FOOD COURT 1612 SE 1 M2 6 Visual

Duct Detector FOOD COURT 1612 SE ERU-E1 1 M2 7 Pass

Smoke Detector CORRIDOR BY WEIGHT RM 1714 1 M2 8 Pass

Smoke Detector CORRIDOR BY SOUTH KITCHEN ENTRANCE 1 M2 9 Pass

Heat Detector KITCHEN DISHWASH AREA RM 1642 1 M2 10 Visual

Heat Detector KITCHEN SERVING AREA SOUTH 1 M2 12 Visual

Smoke Detector BY STORAGE RM 1715 1 M2 13 Pass

Pull Station CORRIDOR BY STORAGE RM 1715 1 M2 14 Pass

Heat Detector STORAGE RM 1715 1 M2 15 Visual

Heat Detector KITCHEN DRY STORAGE RM 1638 1 M2 16 No Access

Smoke Detector CORRIDOR BY ISS RM 1073 1 M2 18 Pass

Smoke Detector CORRIDOR BY ELECTRIC RM 1607 1 M2 19 Pass

Heat Detector FOOD COURT CHAIR STORAGE RM 1616 1 M2 20 Visual

Duct Detector FOOD COURT 1612 NW ERU-E3 1 M2 21 Pass

Smoke Detector CORRIDOR BY PC TECH DECH 1611 1 M2 22 Pass

Smoke Detector FOOD COURT 1612 NE 1 M2 23 Visual

Duct Detector FOOD COURT 1612 NE ERU-E4 1 M2 24 Pass

Smoke Detector CORRIDOR BY AUTO TECH 1621 1 M2 25 Pass

Heat Detector KITCHEN SERVING AREA NORTH 1 M2 26 Visual

Duct Detector KITCHEN SERVING AREA NORTH RTU-E7 1 M2 27 Pass

Duct Detector KITCHEN SERVING AREA CENTER ERU-5 1 M2 28 Pass

Pull Station CORRIDOR BY AUTO TECH RM 1631 1 M2 29 Pass

Duct Detector KITCHEN 1620 N RTU-5 1 M2 30 Pass

Heat Detector KITCHEN 1620 N 1 M2 31 Visual

Heat Detector KITCHEN RM 1620 SOUTH 1 M2 33 Visual

Heat Detector KITCHEN CUSTODIAN CLOSET 1624 1 M2 34 Visual

Heat Detector KITCHEN UTILITY RM 1632 1 M2 35 Visual

Smoke Detector KITCHEN OFFICE CLOSET 1628 1 M2 36 Pass

Pull Station KITCHEN RM 1620 EAST EXIT 1 M2 37 Pass

Heat Detector ELECTRIC RM 1607 1 M2 38 Visual

Heat Detector MECHANICAL RM 1609 1 M2 39 Visual

Duct Detector PROFFESIONAL FOODS LAB RM 1617 RTU-D1 1 M2 40 Pass

Heat Detector PROFFESIONAL FOODS LAB RM 1617 1 M2 41 Visual

Heat Detector MECHANICAL RM 1623 1 M2 43 Visual

Smoke Detector FOOD LAB LINEN STORAGE 1621 1 M2 44 Pass

Duct Detector AUTO TECHNOLOGY 1631 SW 1 M2 45 Visual

Smoke Detector PROFFESIONAL FOOD LAB PANTRY 1619 1 M2 46 Pass

Heat Detector STORAGE 1703 1 M2 47 Visual

Smoke Detector S ELEVATOR 2 LOBBY 1 M2 48 Pass

Heat Detector STORAGE RM 1708 1 M2 49 Visual

Smoke Detector S ELEVATOR 2 MACHINE RM 1739 1 M2 50 Pass

Heat Detector S ELEVATOR 2 MACHINE RM 1739 1 M2 53 Visual

Smoke Detector MAIN GYM NORTHEAST ELECTRIC RM 1741 1 M2 56 Pass

Heat Detector CUSTODIAN 1745 1 M2 57 Visual

Heat Detector MECHANICAL RM 1704 1 M2 58 Visual

Heat Detector ELECTRIC RM 1153 1 M2 59 Visual

Heat Detector MAIN GYM NORTHWEST STORAGE RM 1737 1 M2 60 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 104: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector MAIN GYM SOUTHWEST STORAGE RM 1 M2 61 Visual

Smoke Detector CORRIDOR BY MAIN GYM SOUTHWEST ENTRY 1 M2 62 Pass

Pull Station BUILDING EXIT BY MAIN GYM SW ENTRY 1 M2 63 Pass

Pull Station BUILDING EXIT BY MAIN GYM SW ENTRY 1 M2 64 Pass

Heat Detector OUTSIDE STORAGE RM 1712 1 M2 65 Visual

Heat Detector CUSTODIAN RM 1733 1 M2 66 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET RM 2156 2 M2 67 Pass

Smoke Detector GIRLS RESTROOM BY RUNNING TRACK 2 M2 68 Pass

Heat Detector MECHANICAL RM 2803 2 M2 69 Visual

Heat Detector MECHANICAL RM 2809 2 M2 70 Visual

Heat Detector MECHANICAL RM 2815 2 M2 71 Visual

Heat Detector CUSTODIAN CLOSET 2833 2 M2 72 Visual

Heat Detector IDF RM 2839 2 M2 73 Visual

Heat Detector ELECTRIC RM 2841 2 M2 74 Visual

Smoke Detector PRINT CLOSET RM 2843 2 M2 75 Pass

Heat Detector MECHANICAL RM 2910 2 M2 76 Visual

Heat Detector MECHANICAL RM 2904 2 M2 77 Visual

Heat Detector AUTO TECH 1631 SE 1 M2 78 Visual

Smoke Detector STAIR 8 2 M2 79 Pass

Smoke Detector STAIR 8 2 M2 80 Pass

Smoke Detector CORRIDOR BY STAIR 9 2 M2 81 Pass

Smoke Detector STAIR 9 2 M2 82 Pass

Smoke Detector CORRIDOR BY MAIN GYM NW ENTRY 1 M2 96 Pass

Pull Station CORRIDOR BY MAIN GYM NW ENTRY 1 M2 97 Pass

Smoke Detector LL STAIR 5 1 M2 98 Pass

Heat Detector MECHANICAL RM 1806 1 M2 99 Visual

Heat Detector MECHANICAL RM 1812 1 M2 100 Visual

Heat Detector MECHANICAL RM 1816 1 M2 101 Visual

Heat Detector BOOK STORAGE RM 1820 1 M2 102 Visual

Smoke Detector STAIR 6 EXIT 1 M2 103 Pass

Pull Station STAIR 6 EXIT 1 M2 104 Pass

Heat Detector BOOK STORAGE RM 1819 1 M2 105 Visual

Smoke Detector SPECIAL ED CLASSRM 1834 1 M2 106 Pass

Pull Station CORRIDOR BY STAIR 6 1 M2 107 Pass

Smoke Detector CORRIDOR BY STAIR 6 1 M2 108 Pass

Heat Detector MECHANICAL RM 1832 1 M2 109 Visual

Heat Detector MECHANICAL RM 1836 1 M2 110 Visual

Smoke Detector SPECIAL ED CLASSRM 1938 CLOSET 1 M2 111 Pass

Smoke Detector SPECIAL ED CLASSRM 1938 1 M2 112 Pass

Heat Detector MECHANICAL RM 1850 1 M2 113 Visual

Smoke Detector SPECIAL ED CLASSRM 1846 1 M2 114 Pass

Smoke Detector LL CORRIDOR BY STAIR 7 1 M2 115 Pass

Pull Station CORRIDOR BY STAIR 7 1 M2 116 Pass

Smoke Detector STAIR 7 1 M2 117 Pass

Pull Station LL STAIR 7 1 M2 118 Pass

Heat Detector MECHANICAL RM 1919 1 M2 119 Visual

Heat Detector MECHANICAL RM 1913 1 M2 120 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 105: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector MECHANICAL RM 1905 1 M2 121 Visual

Heat Detector ELECTRIC RM 1901 1 M2 122 Visual

Heat Detector BOOK STORAGE RM 1172 1 M2 123 Visual

Smoke Detector CORRIDOR BY SOCIAL STUDIES RM 1902 1 M2 124 Pass

Smoke Detector CORRIDOR BY MAIN GYM 1 M2 125 Pass

Pull Station EXIT BY MAIN GYM SOUTHWEST 1 M2 126 Pass

Heat Detector CUSTODIAL CLOSET 1168 1 M2 127 Visual

Smoke Detector CORRIDOR BY CUSTODIAN CLOSET 1168 1 M2 128 Pass

Heat Detector IDF RM 1154 1 M2 129 Visual

Heat Detector PRINT CLOSET 1156 1 M2 130 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET 1156 1 M2 131 Pass

Smoke Detector CORRIDOR BY STAIR 5 1 M2 132 Pass

Smoke Detector CORRIDOR BY STAIR 5 1 M2 133 Pass

Heat Detector MECH RM 1803 1 M2 134 Visual

Smoke Detector CORRIDOR BY LANG. ARTS RM 1604 1 M2 135 Pass

Heat Detector MECH RM 1809 1 M2 136 Visual

Smoke Detector CORRIDOR BY LANG. ARTS RM 1610 1 M2 137 Pass

Heat Detector MECHANICAL RM 1815 1 M2 138 Visual

Smoke Detector CORRIDOR BY MECHANICAL RM 1832 1 M2 139 Pass

Smoke Detector CORRIDOR BY RM 1836 1 M2 140 Pass

Heat Detector CUSTODIAN CLOSET 1837 1 M2 141 Visual

Smoke Detector CORRIDOR BY SPECIAL ED LIVING RM 1844 1 M2 142 Pass

Heat Detector IDF RM 1843 1 M2 143 Visual

Smoke Detector PRINT CLOSET 1847 1 M2 144 Pass

Smoke Detector BOOK STORAGE RM 1849 1 M2 145 Pass

Heat Detector ELECTRIC RM 1845 1 M2 146 Visual

Smoke Detector CORRIDOR BY PRINT CLOSET 1847 1 M2 147 Pass

Smoke Detector CORRIDOR BY SPECIAL ED RM 1846 1 M2 148 Pass

Smoke Detector BOOK STORAGE RM 1851 1 M2 149 Pass

Smoke Detector CORRIDOR BY RM 1852 1 M2 150 Pass

Heat Detector MECHANICAL RM 1916 1 M2 151 Visual

Smoke Detector CORRIDOR BY RM 1909 1 M2 152 Pass

Heat Detector MECHANICAL RM 1910 1 M2 153 Visual

Heat Detector MECHANICAL RM 1904 1 M2 154 Visual

Heat Detector ELECTRIC RM 2144 2 M2 155 Visual

Smoke Detector MEDIA CENTER EAST 2 M2 156 Pass

Smoke Detector MEDIA CENTER SOUTH 2 M2 157 Pass

Smoke Detector MEDIA CENTER 2000 W 2 M2 158 Pass

Smoke Detector MAIN ENTRANCE LOBBY 1 M2 159 Visual

Smoke Detector CORRIDOR BY MEDIA CENTER S 2 M2 160 Pass

Smoke Detector CORRIDOR BY MEDIA CENTER N 2 M2 161 Pass

Duct Detector CORRIDOR BY MEDIA CENTER RTU-MED7 2 M2 162 Pass

Smoke Detector AV STORAGE RM 2001 2 M2 163 Pass

Heat Detector MEDIA CENTER MDF RM 2006 2 M2 164 Visual

Smoke Detector MEDIA CENTER WORK RM 2004 2 M2 165 Pass

Smoke Detector MEDIA CENTER 2000 S 2 M2 166 Pass

Smoke Detector CORRIDOR BY AV STORAGE RM 2001 2 M2 167 Pass

Duct Detector BY RM 2146 RTU-MED3 2 M2 168 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 106: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector CORRIDOR BY INFO. RESOURCE RM 2146 2 M2 169 Pass

Heat Detector ELECTRIC RM 2153 2 M2 170 Visual

Pull Station RUNNING TRACK NORTHWEST ENTRY 2 M2 171 Pass

Smoke Detector SOUTH ELEVATOR 2 LOBBY 2 M2 172 Pass

Smoke Detector SOUTH ELEVATOR TOP OF SHAFT 2 M2 173 Visual

Heat Detector S ELEVATOR 2 TOP OF SHAFT 2 M2 174 Visual

Smoke Detector RUNNING TRACK NE STORAGE RM 2745 2 M2 175 Pass

Pull Station RUNNING TRACK STAIR 8 2 M2 176 Pass

Heat Detector RUNNING TRACK ROOF ACCESS RM 2 M2 177 Visual

Pull Station RUNNING TRACK STAIR 9 2 M2 178 Pass

Smoke Detector RUNNING TRACK STORAGE RM 2767 2 M2 179 Pass

Heat Detector MECH RM 2769 2 M2 180 Visual

Duct Detector MAIN GYM NORTH CENTER 1 M2 181 Visual

Duct Detector MAIN GYM NORTHWEST 1 M2 182 Visual

Heat Detector GYM NORTHWEST 1 M2 183 Visual

Duct Detector MAIN GYM NORTH CENTER 1 M2 184 Visual

Duct Detector MAIN GYM NORTHEAST 1 M2 185 Visual

Heat Detector GYM NORTHEAST 1 M2 186 Visual

Heat Detector GYM NORTH CENTER 1 M2 187 Visual

Duct Detector MAIN GYM CENTER WEST 1 M2 188 Visual

Heat Detector GYM CENTER 1 M2 190 Visual

Duct Detector MAIN GYM CENTER EAST 1 M2 191 Visual

Heat Detector GYM CENTER EAST 1 M2 192 Visual

Duct Detector MAIN GYM SOUTHWEST 1 M2 193 Visual

Heat Detector GYM SOUTHWEST 1 M2 194 Visual

Duct Detector MAIN GYM SOUTH CENTER 1 M2 195 Visual

Duct Detector MAIN GYM SOUTH CENTER 1 M2 196 Visual

Heat Detector GYM SOUTH CENTER 1 M2 197 Visual

Duct Detector MAIN GYM SOUTHEAST 1 M2 198 Visual

Heat Detector GYM SOUTHEAST 1 M2 199 Visual

Pull Station RUNNING TRACK SOUTHWEST ENTRY (W) 2 M2 200 Pass

Pull Station RUNNING TRACK SOUTHWEST ENTRY (E) 2 M2 201 Pass

Pull Station UL EXIT BY CONCESSION STAND 2 M2 202 Pass

Pull Station UL EXIT BY CONCESSION STAND 2 M2 203 Pass

Smoke Detector BY RUNNING TRACK SOUTHWEST ENTRY 2 M2 204 Pass

Duct Detector RUNNING TRACK SOUTHWEST RTU-M1 2 M2 205 Pass

Duct Detector AUX GYM WEST 1 M2 206 Visual

Heat Detector AUX GYM NORTHWEST 1 M2 207 Visual

Heat Detector AUX GYM SOUTHWEST 1 M2 208 Visual

Duct Detector AUX GYM EAST 1 M2 209 Visual

Heat Detector AUX GYM NORTHEAST 1 M2 210 Visual

Heat Detector AUX GYM SOUTHEAST 1 M2 211 Visual

Smoke Detector RUNNING TRACK NORTHWEST 2 M2 212 Pass

Pull Station CORRIDOR BY STAIR 5 2 M2 213 Pass

Smoke Detector STAIR 5 2 M2 214 Pass

Smoke Detector CORRIDOR BY STAIR 5 2 M2 215 Pass

Smoke Detector CORRIDOR BY STAIR 5 2 M2 216 Pass

Smoke Detector CORRIDOR BY LANG. ARTS RM 2604 2 M2 217 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 107: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector MECHANICAL RM 2806 2 M2 218 Visual

Smoke Detector CORRIDOR BY RM 2810 2 M2 219 Pass

Heat Detector MECH RM 2812 2 M2 220 Visual

Duct Detector CORRIDOR BY RM 2814 ERU-4 2 M2 221 Pass

Heat Detector MECH RM 2816 2 M2 222 Visual

Heat Detector BOOK STORAGE RM 2820 2 M2 223 Visual

Smoke Detector STAIR 6 EXIT 2 M2 224 Pass

Smoke Detector CORRIDOR BY STAIR 6 2 M2 225 Pass

Pull Station CORRIDOR BY STAIR 6 2 M2 226 Pass

Heat Detector MECH RM 2834 2 M2 227 Visual

Smoke Detector CORRIDOR BY 2843 2 M2 228 Pass

Heat Detector MECHANICAL RM 2844 2 M2 229 Visual

Smoke Detector CORRIDOR BY STAIR 7 2 M2 230 Pass

Pull Station CORRIDOR BY STAIR 7 2 M2 231 Pass

Smoke Detector UL STAIR 7 2 M2 232 Fail

Heat Detector MECHANICAL RM 2917 2 M2 233 Visual

Duct Detector CORRIDOR BY 2911 ERU3 2 M2 234 Pass

Heat Detector MECHANICAL RM 2913 2 M2 235 Visual

Smoke Detector CORRIDOR BY FOREIGN LANGUAGE RM 2909 2 M2 236 Pass

Heat Detector MECHANICAL RM 2905 2 M2 237 Visual

Heat Detector ELECTRIC RM 2901 2 M2 238 Visual

Heat Detector UL CONCESSION 2163 2 M2 239 Visual

Heat Detector CONCESSION STAND STORAGE RM 2165 2 M2 240 Visual

Smoke Detector CORRIDOR BY SOCIAL STUDIES RM 2902 2 M2 241 Pass

Smoke Detector CORRIDOR BY CONCESSION STAND RM 2163 2 M2 242 Pass

Pull Station CORRIDOR BY ASSISTANT PRINCIPAL 2 M2 243 Pass

Heat Detector IDF RM 2154 2 M2 244 Visual

Smoke Detector PRINT CLOSET RM 2156 2 M2 245 Pass

Smoke Detector FOOD COURT 1612 1 M2 246 Visual

Smoke Detector SPECIAL ED LIVING 1844 1 M2 247 Pass

Smoke Detector SPECIAL ED RM 1852 1 M2 248 Pass

Heat Detector MECH RM 1717 1 M3 1 Visual

Waterflow Switch LL RISER #1 (MAIN MECH RM 1717) 1 M3 2 Pass

Tamper Switch LL RISER #1 (MAIN MECH RM 1717) 1 M3 2 Pass

Waterflow Switch LL RISER #2 (MAIN MECH RM 1717) 1 M3 3 Pass

Tamper Switch LL RISER #2 (MAIN MECH RM 1717) 1 M3 3 Pass

Waterflow Switch LL RISER #3 (MAIN MECH RM 1717) 1 M3 4 Pass

Tamper Switch LL RISER #3 (MAIN MECH RM 1717) 1 M3 4 Pass

Waterflow Switch LL RISER #4 (MAIN MECH RM 1717) 1 M3 5 Pass

Tamper Switch LL RISER #4 (MAIN MECH RM 1717) 1 M3 5 Pass

Waterflow Switch LL RISER #5 (MAIN MECH RM 1717) 1 M3 6 Pass

Tamper Switch LL RISER #5 (MAIN MECH RM 1717) 1 M3 6 Pass

Pull Station MAIN MECHANICAL RM 1717 EAST EXIT 1 M3 7 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 108: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector MECH RM 1717 1 M3 8 Visual

Heat Detector MECH RM 1721 WEST 1 M3 9 Visual

Heat Detector MECH RM 1721 EAST 1 M3 10 Visual

Pull Station STAIR 8 EXIT 1 M3 11 Pass

Pull Station MAIN ELECTRIC RM 1721 1 M3 12 Pass

Smoke Detector CORRIDOR BY STAIR 8 1 M3 13 Pass

Pull Station CORRIDOR BY STAIR 8 1 M3 14 Pass

Smoke Detector STAIR 8 1 M3 15 Pass

Heat Detector BOYS LOCKER RM 1751 1 M3 16 Visual

Heat Detector GIRLS LOCKER RM 1757 1 M3 17 Visual

Pull Station STAIR 9 EXIT 1 M3 18 Pass

Smoke Detector CORRIDOR BY STAIR 9 1 M3 19 Pass

Pull Station CORRIDOR BY STAIR 9 1 M3 20 Pass

Smoke Detector STAIR 9 1 M3 21 Pass

Pull Station CORRIDOR BY BOYS COACH'S OFFICE 1769 1 M3 22 Pass

Heat Detector CUSTODIAN CLOSET 1716 1 M3 23 Visual

Heat Detector MAIN GYM NOETHEAST STORAGE RM 1749 1 M3 24 Visual

Heat Detector MECHANICAL RM 1747 (GYM B LOCKERS) 1 M3 25 Visual

Smoke Detector IDF RM 1718 1 M3 26 Pass

Smoke Detector CORRIDOR BY LOCKER RM 1751 1 M3 27 Pass

Smoke Detector CORRIDOR BY GIRLS LOCKER RM 1757 1 M3 28 Pass

Heat Detector ELECTRIC RM 1725 1 M3 29 Visual

Smoke Detector BY GIRLS COACH'S OFFICE 1765 1 M3 30 Pass

Heat Detector LAUNDRY 1766 BY COACH'S OFFICE 1 M3 31 Visual

Heat Detector MAIN GYM SOUTHEST STORAGE RM 1727 1 M3 32 Visual

Pull Station CORRIDOR BY BOYS COACH'S OFFICE 1769 1 M3 33 Pass

Pull Station FINE ARTS VESTIBULE 1260 1 M3 34 Pass

Pull Station FINE ARTS CORRIDOR 1262 1 M3 35 Pass

Smoke Detector FINE ARTS COMPUTER LAB 1 M3 37 Pass

Smoke Detector FINE ARTS MUSIC LIBRARY 1 M3 38 Pass

Smoke Detector FINE ARTS CHORAL STORAGE 1264 1 M3 39 Pass

Smoke Detector FINE ARTS INSTRUMENT STORAGE 1 M3 43 Pass

Pull Station FINE ARTS CHORAL ROOM 1263 1 M3 45 Pass

Pull Station FINE ARTS SMALL ENSEMBLE 1 M3 46 Pass

Pull Station FINE ARTS BAND ROOM 1270 1 M3 47 Pass

Smoke Detector LL 1600 HALL OF FIREDOORS 1 M3 48 Pass

Smoke Detector LL CORRIDOR 1600 HALL AT FIREDOORS 1 M3 49 Pass

Smoke Detector LL CORRIDOR 1643 AT RESTROOM 1 M3 50 Pass

Pull Station LL CORRIDOR 1643 EXIT DOOR 1 M3 53 Pass

Heat Detector FIELD HOUSE MECH RM 21 1 M4 13 Visual

Pull Station FIELD HOUSE MECHANICAL RM 21 1 M4 14 Pass

Heat Detector FIELD HOUSE HOMELOCKER CUSTODIAN RM 1 M4 15 Visual

Heat Detector FIELD HOUSE HOME LOCKER RM 1 M4 16 Visual

Smoke Detector FIELD HOUSE HOME LOCKER TRAINING 1 M4 17 Pass

Heat Detector FIELD HOUSE MECH RM 25 1 M4 18 Visual

Pull Station FIELD HOUSE MECHANICAL RM 25 1 M4 19 Pass

Pull Station FIELD HOUSE HOME LOCKER EAST EXIT 1 M4 20 Pass

Heat Detector FIELD HOUSE HOME LOCKER RM 1 M4 21 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 109: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector FIELD HOUSE MECH RM 59 1 M4 22 Visual

Pull Station FIELD HOUSE MECHANICAL RM 59 1 M4 23 Pass

Heat Detector FIELD HOUSE STORAGE RM 11 1 M4 24 Visual

Pull Station FIELD HOUSE HOME LOCKER NORTH ENTRY 1 M4 25 Pass

Heat Detector FIELD HOUSE LAUNDRY RM 1 M4 26 Visual

Smoke Detector FIELD HOUSE COACH'S OFFICE RM 22 1 M4 27 Pass

Pull Station FIELD HOUSE COACH'S OFFICE RM 22 1 M4 28 Pass

Pull Station FIELD HOUSE CONCESSIONS 33 SOUTH 1 M4 29 Pass

Heat Detector FIELD HOUSE CONCESSION STAND 33 1 M4 30 Visual

Pull Station FIELD HOUSE CONCESSIONS 33 NORTH 1 M4 31 Pass

Pull Station FIELD HOUSE BOYS LOCKER RM 42 1 M4 32 Pass

Heat Detector FIELD HOUSE BOYS LOCKER RM 42 1 M4 33 Visual

Pull Station FIELD HOUSE VISITOR LOCKER RM 55 1 M4 34 Pass

Pull Station FIELD HOUSE REFEREE LOCKER RM 54 1 M4 35 Pass

Pull Station FIELD HOUSE UTILITY CLOSET 53 1 M4 36 Pass

Heat Detector FIELD HOUSE UTILITY CLOSET 53 1 M4 37 Visual

Heat Detector FIELD HOUSE STORAGE RM 50 1 M4 38 Visual

Heat Detector FIELD HOUSE ELECTRIC RM 52 1 M4 39 Visual

Pull Station FIELD HOUSE ELECTRIC RM 52 1 M4 40 Pass

Pull Station FIELD HOUSE STORAGE RM 50 1 M4 41 Pass

Heat Detector FIELD HOUSE STORAGE RM 51 1 M4 42 Visual

Heat Detector FIELD HOUSE MECH RM 58 1 M4 43 Visual

Pull Station FIELD HOUSE MECH RM 58 (S.) 1 M4 44 Pass

Pull Station FIELD HOUSE MECH RM 58 (N.) 1 M4 45 Pass

Heat Detector FIELD HOUSE VISITOR LOCKER RM 55 1 M4 46 Visual

Heat Detector FIELD HOUSE GIRLS LOCKER RM 40 1 M4 47 Visual

Pull Station FIELD HOUSE GIRLS LOCKER RM 40 1 M4 48 Pass

Heat Detector ELEC RM 1852 1 M5 2 Visual

Heat Detector IDF RM 1853 1 M5 3 Visual

Heat Detector STORAGE RM 1851 1 M5 4 Visual

Smoke Detector STORAGE RM 1851 1 M5 5 Pass

Smoke Detector CORR @ CLASSROOM 1861 1 M5 7 Pass

Smoke Detector CLASSROOM 1861 1 M5 8 Pass

Heat Detector MECH RM 1855 1 M5 9 Visual

Smoke Detector CLASSROOM 1863 1 M5 10 Pass

Pull Station CORR @ CLASSROOM 1863 1 M5 11 Pass

Heat Detector MECH RM 1854 1 M5 12 Visual

Smoke Detector CORRIDOR 1958 1 M5 13 Pass

Smoke Detector CLASSROOM 1864 1 M5 14 Pass

Smoke Detector CLASSROOM 1862 1 M5 15 Pass

Heat Detector MECH RM 1856 1 M5 16 Visual

Smoke Detector CORRIDOR 1958 1 M5 17 Pass

Smoke Detector CLASSROOM 1865 1 M5 18 Pass

Smoke Detector CORRIDOR 1958 1 M5 19 Pass

Smoke Detector SPECIAL ED 1866 1 M5 20 Pass

Heat Detector MECH RM 1955 1 M5 21 Visual

Smoke Detector CLASSROOM 1964 1 M5 22 Pass

Smoke Detector CLASSROOM 1965 1 M5 23 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 110: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector CORRIDOR 1958 1 M5 24 Pass

Heat Detector MECH RM 1954 1 M5 25 Visual

Heat Detector MECH RM 1953 1 M5 26 Visual

Smoke Detector CORRIDOR 1958 1 M5 27 Pass

Smoke Detector CLASSROOM 1962 1 M5 28 Pass

Smoke Detector CLASSROOM 1963 1 M5 29 Pass

Pull Station CORR @ STAIRS S10-1 1 M5 30 Pass

Pull Station STAIRS S10-1 1 M5 31 Pass

Heat Detector STORAGE RM 1952 1 M5 32 Visual

Heat Detector MECH RM 1951 1 M5 33 Visual

Smoke Detector CLASSROOM 1961 1 M5 34 Pass

Smoke Detector CORR @ CLASSROOM 1961 1 M5 35 Pass

Smoke Detector UL IDF RM 2839 FOR FACP SUBPANEL 2 M5 51 Pass

Smoke Detector CORR @ CLASSROOM 2861 2 M5 55 Pass

Smoke Detector CLASSROOM 2861 2 M5 56 Pass

Heat Detector MECH RM 2855 2 M5 57 Visual

Smoke Detector CLASSROOM 2863 2 M5 58 Pass

Heat Detector MECH RM 2854 2 M5 59 Visual

Smoke Detector CORR @ RM 2862 2 M5 60 Pass

Heat Detector EQUIP STORE 2867 2 M5 61 Visual

Heat Detector RESTROOM 2858 2 M5 62 Visual

Smoke Detector MULTI LAB 2864 2 M5 63 Pass

Monitor MULTI LAB 2864 KH 2 M5 64 Pass

Monitor MULTI LAB 2864 KH 2 M5 65 Pass

Monitor MULTI LAB 2864 KH 2 M5 66 Fail

Monitor MULTI LAB 2864 KH 2 M5 67 Pass

Monitor MULTI LAB 2864 KH 2 M5 68 Pass

Monitor MULTI LAB 2864 KH 2 M5 69 Pass

Monitor MULTI LAB 2864 KH 2 M5 70 Pass

Smoke Detector MULTI LAB 2864 2 M5 71 Pass

Smoke Detector CORR @ RM 2862 2 M5 72 Pass

Smoke Detector COMP LAB 2862 2 M5 73 Pass

Smoke Detector COMP LAB 2862 2 M5 74 Pass

Duct Detector CORR @ GIRLS RM 2858 2 M5 75 Pass

Smoke Detector CORR @ BOYS RM 2860 2 M5 76 Pass

Heat Detector IDF RM 2956 2 M5 77 Visual

Smoke Detector CLASSROOM 2964 2 M5 78 Pass

Smoke Detector CLASSROOM 2965 2 M5 79 Pass

Smoke Detector CORR @ MECH 2953 2 M5 80 Pass

Heat Detector MECH RM 2954 2 M5 81 Visual

Heat Detector MECH RM 2953 2 M5 82 Visual

Smoke Detector CORRIDOR 2 M5 83 Pass

Smoke Detector CLASSROOM 2962 2 M5 84 Pass

Smoke Detector CLASSROOM 2963 2 M5 85 Pass

Smoke Detector CORRIDOR 2 M5 86 Pass

Pull Station STAIRS S10-2 2 M5 87 Pass

Heat Detector STORAGE RM 2952 2 M5 88 Visual

Heat Detector MECH RM 2951 2 M5 89 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 111: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector CLASSROOM 2961 2 M5 90 Pass

Smoke Detector CORR @ CLASSROOM 2961 2 M5 91 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 112: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

(4) 12V 7AH batteries failed load testing and need replacement.

(1) Red wall mounted Simplex speakerstrobe in cafeteria failed to activate visual notification during alarm.

(1) Smoke Detector (M2-232) on 2nd fl Upper Level Stair 7 fails to report to FACP.

(1) Simplex 4090-9001 monitor module M5-66 No Answer trouble on arrival. Module monitors kitchen hood

system temperature sensors on 2nd floor in room 2864.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 113: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

(1) Smoke Detector (M2-132) on 1st fl Corridor by Stair 5 reports to FACP, but base isn't

fully secured to ceiling.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 114: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 3 0

10 4

30 0

13 0

42 0

8 0

1 1

Inspector Name : Signature:

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

All-Star Fire, LLC

Power Patrol

Simplex 4099-9004

FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

6240 Post Road

Vickery Creek Middle School

Model Name 4010Simplex

GA 30040

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Monitoring Company

EMC

4098-9755

Voice Evac Evac 25

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

Heat Detector Simplex 4098-9733

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/23/2020

EI1273 / WO # 155508

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 115: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Fail

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.3 Pass

Good (2020) 13.3 Pass

Poor (2015) 13.3 Fail

Poor (2015) 13.3 Fail

Good (2020) 13 Pass

Good (2020) 13.3 Pass

Good (2020) 12.9 Fail

Good (2020) 13 Fail

Good (2020) 13.3 Pass

Good (2020) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

N/A

Pass

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Voice Evac rm 106

Voice Evac rm 106

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FCPS (left) #2 rm 138

FCPS (right) #2 rm 138

FCPS (left) #3 rm 542

FCPS (right) #3 rm 542

12v 7ah

12v 7ah

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FCPS (right) #1 rm 103

FCPS (left) #1 rm 103

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 116: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device testing

Device Type Location Floor Address/Zone Results

Duct Detector Mech rm 601 1 M1-1 Visual

Smoke Detector Corr 100 @ Cafe Entrance 1 M1-2 Pass

Duct Detector Mech rm 601 1 M1-3 Visual

Smoke Detector Corr @ rm 131 1 M1-4 Pass

Smoke Detector Food Service @ rm 131 1 M1-5 Pass

Heat Detector Food Service @ rm 131 1 M1-6 Pass

Heat Detector Food Service @ rm 132 1 M1-7 Visual

Smoke Detector Cafeteria @ Food Service 1 M1-8 Pass

Smoke Detector Cafeteria @ Food Service 1 M1-9 Pass

Smoke Detector Cafeteria @ Food Service 1 M1-10 Pass

Duct Detector Mech rm 609 @Cafe Exit 1 M1-11 Pass

Heat Detector Kitchen 131 1 M1-12 Visual

Smoke Detector Food Service Entrance @ Main Corr 1 M1-13 Pass

Smoke Detector Food Service Entrance @ Main Corr 1 M1-14 Pass

Smoke Detector 200 Corr @ Food Service Exit 1 M1-15 Visual

Smoke Detector 200 Corr @ Food Service Exit 1 M1-16 Visual

Smoke Detector 200 Corr @ rm 205 1 M1-17 Pass

Smoke Detector 200 Corr @ rm 139 1 M1-18 Pass

Smoke Detector 200 Corr @ rm 231 1 M1-19 Pass

Smoke Detector 200 Corr @ rm 230 1 M1-20 Pass

Smoke Detector 300 Corr @ rm 320 1 M1-21 Pass

Smoke Detector 300 Corr @ rm 321 1 M1-22 Pass

Smoke Detector 300 Corr @ rm 331 1 M1-23 Pass

Smoke Detector 300 Corr @ rm 332 1 M1-24 Pass

Smoke Detector 400 Corr @ rm 414 1 M1-25 Pass

Smoke Detector 400 Corr @ rm 413 1 M1-26 Pass

Smoke Detector 400 Corr @ rm 431 1 M1-27 Pass

Smoke Detector 400 Corr @ rm 432 1 M1-28 Pass

Heat Detector Rm 409 1 M1-29 Visual

Duct Detector Mech rm 607 1 M1-32 Pass

Duct Detector Outside Mech rm @ Media 1 M1-33 Pass

Heat Detector Home Ec rm 509 1 M1-34 Visual

Heat Detector Home Ec rm 509 1 M1-35 Visual

Heat Detector Home Ec rm 509 1 M1-36 Visual

Heat Detector Home Ec rm 509 1 M1-37 Visual

Smoke Detector Corr @ rm 147 1 M1-38 Pass

Smoke Detector Corr @ rm 508 1 M1-39 Pass

Smoke Detector Corr @ rm 509 1 M1-40 Pass

Smoke Detector Corr @ rm 512 1 M1-41 Pass

Duct Detector Mech rm 606 1 M1-42 Pass

Smoke Detector Corr @ rm 520 1 M1-43 Pass

Smoke Detector Corr @ rm 526 1 M1-44 Pass

Smoke Detector Corr @ rm 527 1 M1-45 Visual

Smoke Detector Corr @ rm 527 1 M1-46 Visual

Duct Detector Mech rm 603 1 M1-47 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 117: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Mech rm 603 1 M1-48 Pass

Smoke Detector Mech rm @ rm 522 1 M1-49 Pass

Smoke Detector Mech rm @ rm 523 1 M1-50 Not found

Smoke Detector Corr @ Gym 1 M1-51 Visual

Smoke Detector Gym @ rm 570 1 M1-52 Visual

Smoke Detector Corr @ Gym 1 M1-53 Visual

Smoke Detector Gym @ Storage 1 M1-54 Not found

Smoke Detector Gym @ rm 570 1 M1-55 Visual

Smoke Detector Gym Corr @ rm 579 1 M1-56 Pass

Smoke Detector Gym Corr @ rm 590 1 M1-57 Pass

Smoke Detector Gym @ rm 570 1 M1-58 Visual

Smoke Detector Corr to Media rm 140 1 M1-59 Visual

Smoke Detector Media rm 140 to Corr 1 M1-60 Pass

Pull Station Main Office Exit 1 M1-74 Pass

Pull Station Engineering rm 1 M1-76 Pass

Pull Station Corr Exit @ rm 117 1 M1-101 Pass

Pull Station Front Corr Exit @ rm 101 1 M1-102 Pass

Pull Station Cafeteria Front Exit 1 M1-104 Pass

Pull Station Cafeteria Front Exit 1 M1-105 Pass

Pull Station Band rm 1 M1-106 Pass

Pull Station Cafeteria Side Exit 1 M1-107 Pass

Pull Station Corr Exit @ rm 138 1 M1-109 Pass

Pull Station 200 Corr Exit @ rm 252 1 M1-112 Pass

Pull Station Corr Exit @ rm 324 1 M1-113 Pass

Pull Station 300 Corr Exit @ rm 352 1 M1-116 Pass

Pull Station Corr Exit @ rm 439 1 M1-117 Pass

Pull Station 400 Corr Exit @ rm 452 1 M1-120 Pass

Pull Station 400 Corr Exit @ rm 413 1 M1-121 Pass

Pull Station Media rm 140 Exit 1 M1-122 Pass

Pull Station Corr Exit @ rm 147 1 M1-123 Pass

Pull Station Home Ec Exit rm 509 1 M1-124 Pass

Pull Station Rm 520 Exit 1 M1-125 Pass

Pull Station Corr Exit @ rm 524 1 M1-126 Pass

Pull Station Corr Exit @ rm 530 1 M1-127 Pass

Pull Station Corr Exit @ rm 561 1 M1-128 Pass

Pull Station Gym Exit @ rm 570 1 M1-129 Pass

Pull Station Gym Exit @ rm 572 1 M1-130 Pass

Pull Station Mech rm 265 1 M1-132 Not found

Pull Station Corr @ rm 605 1 M1-133 Pass

Pull Station Corr Exit @ rm 604 1 M1-134 Pass

Pull Station Corr Exit @ rm 271 1 M1-138 Pass

Pull Station Corr Exit @ rm 371 1 M1-140 Pass

Pull Station Corr Exit @ rm 471 1 M1-144 Pass

Duct Detector Behind Gym 1 M1-201 Pass

Duct Detector Behind Gym 1 M1-202 Pass

Duct Detector Mech rm 603 1 M1-205 Pass

Duct Detector Corr 500 1 M1-220 No Access

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 118: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Corr 500 1 M1-221 No Access

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 119: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. 4 Batteries failed load test.

2. Voice Evac failed to operate in alarm. Power light out.

3. 2 Ceiling strobes at far end of gym failed to flash in alarm.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 120: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 121: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 5 0

12 2

27 0

3 0

78 0

Inspector Name : Signature:

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Pass

Pass

D K WomackKen Womack

Pass

Simplex 4009

Control Panel

Device

All-Star Fire, LLC

Interstate

Simplex 4099-9754

SLA1156

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4100 ES

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

6280 Post Road

Vickery Creek Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name 4100ESSimplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC

4098-9685

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

8/5/2020

EI1273 / WO # 155468

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 122: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Fair (no date) 13.1 Fail

Fair (no date) 12.9 Fail

Good (2019) 13.4 Pass

Good (2019) 13.3 Pass

Good (2019) 13.1 Pass

Good (2019) 13.1 Pass

Good (2019) 13.1 Pass

Good (2019) 13.1 Pass

Good (2019) 13.3 Pass

Good (2019) 13.1 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #5 rm 122

FCPS (left) #4 rm 265

FCPS (left) #5 rm 122

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 510

FCPS (right) #2 rm 510

FCPS (left) #3 rm 207

FCPS (right) #3 rm 207

12v 7ah

12v 7ah

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FACP (left)

12v 35ahFACP (right)

12v 35ah

12v 7ah

FCPS (right) #1 rm 122

FCPS (left) #1 rm 122

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FCPS (right) #4 rm 265

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 123: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station Corr Exit @ rm 240-233 M1-100 Pass

Pull Station Corr Exit @ rm 240-233 M1-101 Pass

Smoke Detector Corr @ rm 236 Fire drs M1-105 Pass

Smoke Detector Corr @ rm 236 Fire drs M1-106 Pass

Smoke Detector Multi Purpose bldg Rear Exit M1-108 Pass

Pull Station Multi Purpose bldg Front Exit M1-109 Pass

Pull Station Exit @ rm 170 M1-115 Pass

Pull Station Corr Exit @ rm 156 M1-118 Pass

Pull Station Corr Exit @ rm 219 M1-119 Pass

Pull Station Corr Exit @ rm 296 M1-120 Pass

Pull Station Corr Exit @ rm 329 M1-121 Pass

Pull Station Corr Exit @ rm 361 M1-122 Pass

Pull Station Corr Exit @ rm 361 M1-123 Pass

Pull Station Corr Exit @ rm 440 M1-124 Pass

Smoke Detector Room 143 M1-14 Pass

Smoke Detector Room 134 M1-15 Pass

Smoke Detector Mail rm 133 M1-18 Pass

Smoke Detector Room 121 M1-19 Pass

Pull Station Gym M1-2 Pass

Smoke Detector Bldg A Custodial rm 115 M1-22 Pass

Smoke Detector Gym Storage M1-23 Pass

Smoke Detector Gym Storage M1-24 Pass

Smoke Detector Media Ctr rm 146 M1-26 Pass

Smoke Detector A/V Storage rm 150 M1-28 Pass

Smoke Detector Room 154 M1-29 Pass

Pull Station Gym M1-3 Pass

Smoke Detector Cafeteria rm 175 M1-31 Pass

Smoke Detector Kitchen Elect rm M1-34 Pass

Smoke Detector Ktchen Dry Storage rm 181 M1-36 Pass

Smoke Detector Ktchen Dry Storage rm 181 M1-37 Pass

Smoke Detector Room 185 M1-38 Pass

Smoke Detector Corr @ rm 302 Fire drs M1-39 Pass

Pull Station Gym M1-4 Pass

Smoke Detector Corr @ rm 302 Fire drs M1-40 Pass

Smoke Detector Storage rm 304 in rm 302 M1-41 Pass

Smoke Detector Storage rm 303 in rm 301 M1-43 Pass

Smoke Detector Storage rm 311 in rm 309 M1-44 Pass

Smoke Detector Storage rm 319 in rm 315 M1-45 Pass

Smoke Detector Storage rm 331 in rm 329 M1-46 Pass

Smoke Detector Storage rm 323 in rm 321 M1-47 Pass

Smoke Detector Storage rm 332 in rm 330 M1-48 Pass

Smoke Detector Storage rm 324 in rm 322 M1-49 Pass

Pull Station Gym M1-5 Pass

Smoke Detector Custodial rm 316 M1-50 Pass

Smoke Detector Storage rm 343 in rm 341 M1-52 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 124: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Storage rm 304 in rm 302 M1-53 Pass

Smoke Detector Storage rm 344 in rm 342 M1-54 Pass

Smoke Detector Storage rm 352 in rm 350 M1-55 Pass

Smoke Detector Storage rm 355 in rm 353 M1-56 Pass

Smoke Detector Storage rm 363 in rm 361 M1-57 Pass

Smoke Detector Storage rm 363 in rm 361 M1-58 Pass

Smoke Detector Storage rm 363 in rm 361 M1-59 Pass

Pull Station Cafeteria Exit Into Bldg M1-6 Pass

Smoke Detector 100/200 Corr @ Fire drs M1-60 Pass

Smoke Detector 100/200 Corr @ Fire drs M1-61 Pass

Smoke Detector Storage rm 282 M1-62 Pass

Smoke Detector Storage rm 205 M1-63 Pass

Smoke Detector Storage rm 207 M1-64 Pass

Smoke Detector Elect rm 279 M1-66 Pass

Smoke Detector Storage rm 283 M1-67 Pass

Pull Station Cafe Rear Exit M1-7 Pass

Pull Station Cafe Front Exit M1-8 Pass

Smoke Detector Corr @ rm 361 Fire drs M1-80 Pass

Smoke Detector Corr @ rm 361 Fire drs M1-81 Pass

Smoke Detector Corr @ rm 401 Fire drs M1-82 Pass

Smoke Detector Corr @ rm 401 Fire drs M1-83 Pass

Smoke Detector Rm 405 in rm 401 M1-84 Pass

Smoke Detector Storage rm 426 in rm 424 M1-85 Pass

Smoke Detector Custodial rm 421 M1-86 Pass

Smoke Detector Storage rm 425 in rm 423 M1-87 Pass

Smoke Detector Storage rm 433 in rm 431 M1-88 Pass

Smoke Detector Storage rm 441 in rm 439 M1-89 Pass

Pull Station Cafeteria Exit @ rm 187 M1-9 Pass

Smoke Detector Storage rm 434 in rm 432 M1-90 Pass

Smoke Detector Storage rm 442 in rm 440 M1-91 Pass

Smoke Detector Storage rm 417 in rm 415 M1-92 Pass

Smoke Detector Storage rm 409 in rm 407 M1-93 Pass

Smoke Detector Storage rm 416 in rm 414 M1-94 Pass

Smoke Detector Storage rm 408 in rm 406 M1-95 Pass

Pull Station Corr 2.131 Exit East M1-98 Pass

Pull Station Corr 2.131 Exit West M1-99 Pass

Pull Station Bldg A Gym Corr Exit M2-3 Pass

Pull Station Bldg A & D Corr Exit M2-4 Pass

Pull Station Bldg A Main Entrance M2-5 Pass

Smoke Detector Bldg A Mech rm 120 M1-16 Not Found

Pull Station Media Ctr rm 140 Exit M1-117 Pass

Smoke Detector Bldg A Elect rm110 M1-17 Not Found

Smoke Detector Bldg A Vault M1-21 Pass

Smoke Detector Gym Storage M1-25 Not Found

Smoke Detector Bldg B rm 210 M1-27 Not Found

Smoke Detector Bldg B Mech rm M1-30 Not Found

Smoke Detector Bldg B Elect rm 304 M1-32 Not Found

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 125: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Bldg B Storage rm 210 M1-33 Not Found

Smoke Detector Mail rm 318 M1-35 Not Found

Smoke Detector Bldg C Kiln rm 404 M1-42 Not Found

Smoke Detector Bldg C Elect rm 408 M1-51 Pass

Smoke Detector Bldg D Closet 535 M1-65 Not Found

Smoke Detector Bldg D Closet 510 M1-68 Not Found

Smoke Detector Bldg D Closet 513 M1-69 Not Found

Smoke Detector Bldg D Closet 516 M1-71 Not Found

Smoke Detector Bldg D Storage rm 526 M1-72 Not Found

Smoke Detector Bldg C Storage rm 301 M1-73 Not Found

Duct Detector Outside Gym Storage M1-10 Visual

Duct Detector Multi Purpose bldg M1-107 No Access

Duct Detector Boys Restroom 251 M1-127 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 126: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. 2 Batteries failed load test.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 127: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 128: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 5 0

14 8

27 0

19 2

72 0

1 0

5 0

Inspector Name : Signature:

30041

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/21/2020

EI1273 / WO # 155466

4098-9756

Waterflow Potter VSR F

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

Pass

4670 Windermere Parkway

South Forsyth Middle School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name 4010Simplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

All-Star Fire, LLC

Yuasa

Simplex 4099-9004

NP7-12

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

Evax25Voice Evac UOXX

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 129: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Fail

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Fair (2019) 12.7 Fail

Fair (2019) 12.7 Fail

Good (2019) 13.2 Pass

Good (2019) 13.2 Pass

Good (2018) 13.3 Pass

Good (2018) 13.4 Pass

Fair (2019) 12.1 Fail

Fair (2019) 13.3 Fail

Good (2019) 13.3 Pass

Good (2019) 13.6 Pass

Fair (2019) 12.8 Fail

Fair (2019) 12.7 Fail

Fair (2019) 12.6 Fail

Fair (2019) 12.8 Fail

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

N/A

Pass

N/A

N/A

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

FCPS (right) #1

FCPS (left) #1

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FCPS (right) #4 rm 265

Voice Evac

Voice Evac

12v 7ah

12v 7ah

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 542

FCPS (right) #2 rm 542

FCPS (left) #3 rm 138

FCPS (right) #3 rm 138

12v 7ah

12v 7ah

12v 7ah

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #5 rm 464

FCPS (left) #4 rm 265

FCPS (left) #5 rm 464

Fire Pump Running

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 130: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station Main Lobby & Exit 1 M1-1 Pass

Pull Station Cafeteria 130 Exit 1 M1-2 Pass

Pull Station Cafeteria 130 Exit 1 M1-3 Pass

Pull Station Admin 101 Rear Exit 1 M1-4 Pass

Pull Station Kitchen 133 Rear Exit 1 M1-5 Pass

Ansul Room 409 Hood 1 M1-6 See Notes

Pull Station Front Office Exit 1 M1-8 Pass

Pull Station Hall 285 @ Copy rm 415 1 M1-11 Pass

Pull Station Media Center 140 Rear Exit 1 M1-12 Pass

Pull Station Hall Exit @ rm 147 1 M1-13 Pass

Pull Station Music rm 509 Rear Exit 1 M1-14 Pass

Pull Station Art rm 525 Rear Exit 1 M1-16 Pass

Pull Station Gym Hall Exit @ Elect rm 542 1 M1-17 Pass

Pull Station Gym 570 @ Storage rm 1 M1-18 Pass

Pull Station Gym 570 @ Storage rm 571 1 M1-19 Pass

Pull Station Gym Lobby 540 Side Exit 1 M1-20 Pass

Pull Station Gym 570 @ Boys Locker Rear Exit 1 M1-21 Pass

Pull Station Gym 570 @ Girls Locker Rear Exit 1 M1-22 Pass

Ansul Kitchen 133 Hood 1 M1-27 Visual

Flow Switch Mech rm 609 1 M1-28 Pass

Flow Switch Gym 570 Outside Mech rm 604 1 M1-29 Pass

Pull Station Corr 200 Exit @ rm 257 1 M1-36 Pass

Pull Station Corr 300 Exit @ rm 357 1 M1-40 Pass

Pull Station Corr 400 Exit @ rm 457 1 M1-44 Pass

Pull Station Health Care Science Lab 532 Exit 1 M1-194 Pass

Pull Station Corr 531 @ Health Science 1 M1-195 Pass

Tamper Switch Office 361 Riser Main 1 M1-196 Pass

Tamper Switch Office 361 Riser 3 1 M1-197 Pass

Tamper Switch Office 361 Riser 4 1 M1-198 Pass

Tamper Switch Office 361 Riser 5 1 M1-199 Pass

Duct Detector Kitchen Roof AHU 1 M1-200 Not Found

Pull Station Corr 261 Exit @ rm 288 1 M1-210 Pass

Tamper Switch Office 361 Riser 1 1 M1-213 Pass

Tamper Switch Office 361 Riser 2 1 M1-214 Pass

Pull Station Corr 262 Exit @ rm 288 1 M1-215 Not Found

Pull Station Corr 388 Exit @ rm 393 1 M1-227 Pass

Pull Station Corr 461 Exit @ rm 485 1 M1-230 Pass

Pull Station Band rm 561 Exit 1 M1-235 Pass

Duct Detector Mech rm 603 FCU 102 1 M1-50 Not Found

Duct Detector Mech rm 609 1 M1-51 Pass

Duct Detector Mech rm 603 FCU 103 1 M1-55 Pass

Duct Detector Mech rm 606 1 M1-57 Pass

Duct Detector Mech rm 603 FCU 101 1 M1-58 Pass

Duct Detector Mech rm 602 1 M1-60 Pass

Smoke Detector Corr 100 @ Smoke drs 1 M1-101 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 131: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Corr 100 @ Smoke drs 1 M1-102 Pass

Smoke Detector Cafe 130 @ Serv Line Exit 1 M1-103 Pass

Smoke Detector Cafe 130 @ Serv Line Exit 1 M1-104 Pass

Smoke Detector Cafe 130 @ Tray Return 1 M1-105 Pass

Smoke Detector Serving Line 131 1 M1-106 Pass

Smoke Detector Serving Line 131 1 M1-107 Pass

Heat Detector Kitchen 133 @ Dishwasher 1 M1-108 Visual

Smoke Detector Serving Line Entrance @ Smoke drs 1 M1-109 Pass

Smoke Detector Serving Line Entrance @ Smoke drs 1 M1-110 Pass

Smoke Detector Serving Line Entrance @ Smoke drs 1 M1-111 Visual

Smoke Detector Serving Line Entrance @ Smoke drs 1 M1-112 Visual

Smoke Detector Corr 200 Smoke drs 1 M1-113 Pass

Smoke Detector Corr 200 Smoke drs 1 M1-114 Pass

Smoke Detector Corr 200 Smoke drs 1 M1-115 Pass

Smoke Detector Corr 200 Smoke drs 1 M1-116 Pass

Smoke Detector Corr 300 Smoke drs 1 M1-118 Pass

Smoke Detector Corr 300 Smoke drs 1 M1-119 Pass

Smoke Detector Corr 300 Smoke drs 1 M1-120 Pass

Smoke Detector Corr 300 Smoke drs 1 M1-121 Pass

Smoke Detector Corr 400 Smoke drs 1 M1-122 Pass

Smoke Detector Corr 400 Smoke drs 1 M1-123 Pass

Smoke Detector Corr 400 Smoke drs 1 M1-124 Pass

Smoke Detector Corr 400 Smoke drs 1 M1-125 Pass

Smoke Detector Corr 500 @ rm 508 Smoke drs 1 M1-126 Pass

Smoke Detector Corr 500 @ rm 508 Smoke drs 1 M1-127 Pass

Smoke Detector Corr 500 @ rm 512 Smoke drs 1 M1-128 Pass

Smoke Detector Corr 500 @ rm 512 Smoke drs 1 M1-129 Pass

Smoke Detector Corr 500 @ Gym Lobby Smoke drs 1 M1-130 Pass

Smoke Detector Corr 500 @ Gym Lobby Smoke drs 1 M1-131 Pass

Smoke Detector Gym Lobby @ Corr 500 Smoke drs 1 M1-132 Pass

Smoke Detector Gym Lobby @ Corr 500 Smoke drs 1 M1-133 Pass

Smoke Detector Concession 549 1 M1-134 Pass

Smoke Detector Gym Lobby @ Concession 549 1 M1-135 Visual

Smoke Detector Gym Lobby @ Entrance 1 M1-136 Visual

Smoke Detector Gym 570 Entrance @ Storage rm 1 M1-137 Visual

Smoke Detector Gym Lobby @ Entrance 1 M1-138 Visual

Smoke Detector Gym 570 Entrance @ Storage rm 571 1 M1-139 Visual

Smoke Detector Gym 570 Rear Smoke drs 1 M1-140 Visual

Smoke Detector Gym Corr Smoke drs @ rm 587 1 M1-141 Not Found

Smoke Detector Gym Corr Smoke drs @ rm 576 1 M1-142 Not Found

Smoke Detector Gym 570 Rear Smoke drs 1 M1-143 Visual

Heat Detector Kitchen 133 @ Elect rm 134 1 M1-144 Visual

Heat Detector Break rm 409 @ Kitchen A163 1 M1-145 Visual

Heat Detector Music rm 509 1 M1-146 Visual

Heat Detector Music rm 509 1 M1-147 Visual

Heat Detector Music rm 509 1 M1-148 Visual

Heat Detector Music rm 509 1 M1-149 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 132: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector Music rm 509 1 M1-150 Visual

Smoke Detector 8th Grade Classrm 258 1 M1-164 Pass

Smoke Detector 8th Grade Classrm 257 1 M1-165 Pass

Smoke Detector 8th Grade Classrm 255 1 M1-166 Pass

Smoke Detector 7th Grade Classrm 354 1 M1-167 Pass

Smoke Detector 7th Grade Classrm 358 1 M1-168 Pass

Smoke Detector 7th Grade Classrm 357 1 M1-169 Pass

Smoke Detector 7th Grade Classrm 355 1 M1-170 Pass

Smoke Detector 6th Grade Classrm 454 1 M1-171 Pass

Smoke Detector 6th Grade Classrm 458 1 M1-172 Pass

Smoke Detector 6th Grade Classrm 457 1 M1-173 Pass

Smoke Detector 6th Grade Classrm 455 1 M1-174 Pass

Smoke Detector 8th Grade Classrm 254 1 M1-175 Pass

Duct Detector Outside ERU3 Supply 1 M1-189 Fail

Duct Detector Outside ERU3 Return 1 M1-190 Fail

Duct Detector Media Ctr Comp rm RTU 18 1 M1-191 See Notes

Duct Detector Health Care Sci Lab 532 RTU 37 1 M1-192 Pass

Smoke Detector Health Care Sci Lab 532 Storage 1 M1-193 Pass

Duct Detector Outside Gym 570 1 M1-201 Not Found

Duct Detector Outside Gym 570 RTU 101 1 M1-202 Pass

Smoke Detector Corr 260/261 Smoke drs 1 M1-203 Pass

Smoke Detector Corr 260/261 Smoke drs 1 M1-204 Pass

Heat Detector Elect rm 265 1 M1-205 Visual

Smoke Detector Data rm 268 1 M1-206 Pass

Smoke Detector Work rm Storage 268 1 M1-207 Pass

Smoke Detector Corr 280/284 Smoke drs 1 M1-208 Pass

Smoke Detector Corr 280/284 Smoke drs 1 M1-209 Pass

Duct Detector Outside Classrm 288 ERU 1 M1-211 Pass

Duct Detector Outside Classrm 288 ERU 1 M1-212 Pass

Duct Detector Outside Classrm 369 ERU 1 M1-216 Pass

Duct Detector Outside Classrm 369 ERU 1 M1-217 Pass

Smoke Detector Corr 352/357 Smoke drs 1 M1-218 Pass

Smoke Detector Corr 352/357 Smoke drs 1 M1-219 Pass

Heat Detector Elect rm 462 1 M1-222 Visual

Smoke Detector Data rm 464 1 M1-223 Pass

Smoke Detector Work rm Storage 468 1 M1-224 Pass

Duct Detector Outside Classrm 393 ERU 1 M1-225 Pass

Duct Detector Outside Classrm 393 ERU 1 M1-226 Pass

Smoke Detector Corr 378/384 Smoke drs 1 M1-228 Pass

Smoke Detector Corr 378/384 Smoke drs 1 M1-229 Pass

Duct Detector Outside Classrm 485 ERU 1 M1-231 Pass

Duct Detector Outside Classrm 485 ERU 1 M1-232 Pass

Smoke Detector Corr 490/494 Smoke drs 1 M1-233 Pass

Smoke Detector Corr 490/494 Smoke drs 1 M1-234 Pass

Smoke Detector Band rm Storage 563 1 M1-236 Pass

Smoke Detector Sports Dressing rm 591 1 M1-237 Not Found

Smoke Detector Corr 460/461 Smoke drs 1 M1-238 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 133: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Corr 460/461 Smoke drs 1 M1-239 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 134: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

M1-6 not connected to ansul system.

Note:

M1-191 not installed in duct.

Deficiencies

1. 8 Batteries failed load test .

2. The following strobes failed to flash: Boys Restroom Ceiling on 261 Hall, Gym Ceiling by Dr #571.

3. Duct detectors M1-189 & M1-190 did not flash or report to panel.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 135: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 136: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

3 0

2 0

9 0

Inspector Name : Signature:

(678) 691-0011

585 Peachtree Parkway

30041

Honeywell

Server Rack in Rm 1642

Model Name

Cumming GA

Is the Panel Monitored Yes

VISTA-128FBP

EI1273

South Forsyth High School - Mobile Classroom

8/12/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Yes

Are Lamps and Displays Operating Properly

Monitoring Company & Office Staff

Batteries FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Silent Knight 5495

Who Was Notified Prior to the Start of Testing

David Piorkowski

Pass

Pullstations

Smoke Detectors 5193SD

Power Patrol

VISTA-128FBPControl Panel

Pass

Device

Honeywell

Interface Equipment

David Piorkowski

Fire-Lite

Honeywell

BG-12

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 137: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.5 Pass

Good (2019) 13.6 Pass

Good (2019) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 18AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Site Water Level /Temp

FACP

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

BPS (Left) 12V 7AH

BPS (Right) 12V 7AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 138: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Zone Results

Pull Station HALL ENTRY 1 10 Pass

Pull Station HALL EXIT 1 11 Pass

Smoke Detector EXIT HALL 1 13 Pass

Smoke Detector ENTRY HALL 1 14 Pass

Smoke Detector ROOM 1637 1 21 Pass

Smoke Detector ROOM 1638 1 22 Pass

Smoke Detector ROOM 1639 1 23 Pass

Smoke Detector ROOM 1640 1 24 Pass

Smoke Detector ROOM 1641 1 25 Pass

Smoke Detector ROOM 1642 1 26 Pass

Smoke Detector ROOM 1642 ABOVE FACP 1 27 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 139: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 140: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 141: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

2 0

5 0

Inspector Name : Signature:

(678) 691-0011

585 Peachtree Parkway

30041

Simplex

Mech Rm 607

Model Name

Cumming GA

Is the Panel Monitored Yes

4001

EI1273

South Forsyth High School - Field House

8/12/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Yes

Are Lamps and Displays Operating Properly

Monitoring Company & Office Staff

Batteries FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Who Was Notified Prior to the Start of Testing

David Piorkowski

Pass

Pullstations

Power Patrol

4001Control Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Simplex 2099-9101

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 142: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.6 Pass

Good (2019) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Site Water Level /Temp

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

FACP (Left) 12V 7AH

FACP (Right) 12V 7AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 143: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 144: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Zone Results

Pull Station HALL ENTRY BY 901 1 1 Pass

Pull Station HALL ENTRY BY 916 1 1 Pass

Pull Station EXIT RM 922 1 1 Pass

Pull Station EXIT RM 903 1 1 Pass

Pull Station EXIT RM 913 1 1 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 145: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 146: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 147: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

3 0

19 0

46 0

80 0

97 0

117 0

34 0

9 0

8 3

Inspector Name : Signature:

Voice Evacuation Panel Notifier / Silent Knight DAA2 / NFS-50/100 / SKE-450

Heat Detectors Notifier FST-851

FCPS-24S8&PS-12/24-8

Duct Detectors System Sensor DNR

Waterflow Switches Potter VSR

Tamper Switches Potter OSYSU-2

(678) 691-0011

585 Peachtree Parkway

30041

Notifier

Mech Rm 650

Model Name

Cumming GA

Is the Panel Monitored Yes

NFS2-3030D

EI1273

Forsyth County School - South Forsyth High School Main Building

8/6/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

No

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing Monitoring Company & Admin Staff

Batteries FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Notifier / Wheelock

David Piorkowski

Pass

Pullstations

Smoke Detectors FSP-851

Power Patrol

NFS2-3030DControl Panel

Pass

Device

Notifier

Interface Equipment

David Piorkowski

Notifier

Notifier

NBG-12LX

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 148: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Condition Voltage

Good (2019) 13.5

Good (2019) 13.6

Good (2019) 13.6

Good (2019) 13.6

Fire Pump Controller Troubles Report to Panel

Phase Reversal on Pump Controller Reports to Panel

Voice Evac. (Left) 12V 75AH

Voice Evac. (Right) 12V 75AH

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 75AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Continued on Page 3 - Battery Testing

FACP (Right) 12V 75AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 149: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Fail

Pass

Y

Fail

Fail

N/A

N/A

N/A

Load Test

Pass

Pass

Pass

Pass

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Pass

Pass

N/A

Pass

Pass

Pass

Pass

Supervisory Signals

Interface Equipment

Emergency Communications Equipment

Battery Testing

Notification Devices

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 150: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Floor Condition Voltage Load Test

1 Good (2019) 13.7 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.4 Pass

1 Good (2019) 13.4 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.5 Pass

1 Good (2019) 13.5 Pass

1 Good (2019) 13.3 Pass

1 Good (2019) 13.3 Pass

1 Good (2019) 13.4 Pass

1 Good (2019) 13.4 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

2 Good (2019) 13.7 Pass

2 Good (2019) 13.7 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.5 Pass

1 Good (2019) 13.6 Pass

BPS in Data Rm 863 (Right) 12V 7AH

BPS in Elec Rm 837 (Right) 12V 7AH

NFS-50/100 in Elec Rm 837 (Left) 12V 20AH

NFS-50/100 in Elec Rm 837 (Right) 12V 20AH

BPS in Elec Rm 837 (Left) 12V 7AH

BPS in Data Rm 863 (Left) 12V 7AH

BPS in Elec Rm 837 (Left) 12V 7AH

BPS in Elec Rm 837 (Right) 12V 7AH

BPS in Elec Rm 543 (Right) 12V 7AH

BPS in Mech Rm 1291 (Left) 12V 7AH

BPS in Mech Rm 1291 (Right) 12V 7AH

BPS in Elec Rm 1196 (Left) 12V 7AH

BPS in Elec Rm 1196 (Right) 12V 7AH

BPS in Elec Rm 1196 (Left) 12V 7AH

BPS in Elec Rm 1196 (Right) 12V 7AH

Right BPS in Cust Rm 482 (Left) 12V 7AH

Right BPS in Cust Rm 482 (Right) 12V 7AH

BPS in Elec Rm 543 (Left) 12V 7AH

Right BPS in Mech Rm 362 (Right) 12V 7AH

Left BPS in Cust Rm 482 (Left) 12V 7AH

Left BPS in Cust Rm 482 (Right) 12V 7AH

Left BPS in Mech Rm 362 (Left) 12V 7AH

Left BPS in Mech Rm 362 (Right) 12V 7AH

Right BPS in Mech Rm 362 (Left) 12V 7AH

BPS in Rm 360 (Right) 12V 7AH

BPS in Elec Rm 230 (Left) 12V 7AH

BPS in Elec Rm 230 (Right) 12V 7AH

Right BPS in IDF Rm 182 (Left) 12V 7AH

Right BPS in IDF Rm 182 (Right) 12V 7AH

BPS in Rm 360 (Left) 12V 7AH

Battery Testing (cont.)

Location Size

Left BPS in Mech Rm 650 (Left) 12V 7AH

Middle BPS in Mech Rm 650 (Left) 12V 7AH

Middle BPS in Mech Rm 650 (Right) 12V 7AH

Left BPS in Mech Rm 650 (Right) 12V 7AH

Left BPS in IDF Rm 182 (Right) 12V 7AH

Right BPS in Mech Rm 650 (Left) 12V 7AH

Right BPS in Mech Rm 650 (Right) 12V 7AH

Left BPS in IDF Rm 182 (Left) 12V 7AH

SKE-540 by Auditorium (Right) 12V 7AH

BPS by Auditorium (Left) 12V 7AH

BPS by Auditorium (Right) 12V 7AH

SKE-450 by Auditorium (Left) 12V 7AH

Page 151: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Heat Detector STORAGE ROOM 331 1 L01 D001 Pass

Duct Detector STORAGE ROOM 331 1 L01 D002 Pass

Heat Detector LOCKER ROOM 333 1 L01 D003 Pass

Heat Detector STORAGE ROOM 357 1 L01 D004 Pass

Heat Detector TEAM ROOM 339 1 L01 D005 Pass

Heat Detector TEAM ROOM 327 1 L01 D006 Pass

Smoke Detector CUSTODIAL 204 1 L01 D007 Pass

Smoke Detector HALL 200 @ 206 1 L01 D008 Pass

Smoke Detector HALL 200 @ 210 1 L01 D009 Pass

Smoke Detector STORAGE ROOM 212 1 L01 D010 Pass

Smoke Detector HEALTH OCC 1 L01 D011 Pass

Smoke Detector STORAGE ROOM 226 1 L01 D014 No Access

Heat Detector MECHANICAL ROOM 229 1 L01 D015 Pass

Smoke Detector HALL 200 @ 229 1 L01 D016 Pass

Smoke Detector MARKETING ROOM 240 1 L01 D017 Pass

Heat Detector RISER ROOM 242 1 L01 D018 Pass

Smoke Detector STORAGE ROOM 237 1 L01 D019 Pass

Smoke Detector STORAGE ROOM 241 1 L01 D020 Pass

Heat Detector STORAGE ROOM 227 1 L01 D021 Pass

Heat Detector STORAGE ROOM 215 1 L01 D022 Pass

Smoke Detector GRAPHIC ARTS 213 1 L01 D023 Pass

Heat Detector LOCKERS 321 1 L01 D024 Pass

Duct Detector STORAGE ROOM 329 1 L01 D025 Pass

Heat Detector STORAGE ROOM 329 1 L01 D026 Pass

Pull Station 200 HALLWAY 1 L01 M002 Pass

Pull Station RM 242 RISER RM 200 BLDG 1 L01 M004 Pass

Pull Station CLASS ROOM EXIT 232 1 L01 M006 Pass

Pull Station MARKETING EXIT 240 1 L01 M007 Pass

Waterflow Switch CTAE/200 BLDG RM 242 1 L01 M008 Pass

Tamper Switch CTAE/200 BLDG RM 242 1 L01 M009 Pass

Pull Station GRAPHIC ARTS 213 1 L01 M010 Pass

Pull Station HALL 200 EXIT 1 L01 M011 Pass

Smoke Detector FOYER 100 1 L02 D001 Pass

Smoke Detector STORAGE ROOM 105 1 L02 D002 Pass

Smoke Detector HALL 110 1 L02 D003 Pass

Smoke Detector SPECIAL EDUCATION 102 1 L02 D004 Pass

Smoke Detector SPECIAL EDUCATION 108 1 L02 D005 Pass

Heat Detector CUSTODIAL 126 1 L02 D006 Pass

Smoke Detector HALL 130 FIRE DOORS 1 L02 D007 Pass

Smoke Detector HALL 130 FIRE DOORS 1 L02 D008 Pass

Smoke Detector STORAGE ROOM 137 1 L02 D009 Pass

Smoke Detector STORAGE ROOM 1 L02 D010 Pass

Smoke Detector COMP ROOM 135 1 L02 D011 Pass

Smoke Detector HALL 130 ENTRY 1 L02 D013 Pass

Smoke Detector MARKETING LAB 158 1 L02 D014 Pass

Smoke Detector CLASS ROOM 156 1 L02 D015 Pass

Duct Detector CLASS ROOM 156 1 L02 D016 Pass

Smoke Detector CLASS ROOM 156 1 L02 D017 Pass

Heat Detector STORAGE ROOM 154 1 L02 D018 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 152: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector STORAGE ROOM 188 1 L02 D019 Pass

Smoke Detector ENG TECH LAB 184 1 L02 D020 Pass

Smoke Detector IDF ROOM 182 1 L02 D021 Pass

Heat Detector PRODUCTION ROOM 186 1 L02 D022 Pass

Smoke Detector ELECTRICAL ROOM 199 1 L02 D023 Pass

Smoke Detector HALL 180 FIRE DOORS 1 L02 D024 Pass

Smoke Detector HALL 180 FIRE DOORS 1 L02 D025 Pass

Heat Detector ELECTRICAL ROOM 199 1 L02 D026 Pass

Heat Detector STORAGE ROOM 315 1 L02 D027 Pass

Heat Detector STORAGE ROOM 313 1 L02 D028 Pass

Pull Station HALL 110 EXIT 1 L02 M001 Pass

Pull Station HALL 130 ENTRY 1 L02 M003 Pass

Smoke Detector HALL 170 FIRE DOORS 1 L03 D001 Pass

Smoke Detector HALL 170 FIRE DOORS 1 L03 D002 Pass

Heat Detector DRESSING ROOM 153 1 L03 D003 Pass

Duct Detector RTU-113 CR157 1 L03 D004 Pass

Heat Detector DINING 160 1 L03 D005 Pass

Heat Detector CULINARILY KITCHEN 1 L03 D006 Pass

Heat Detector CULINARILY KITCHEN 1 L03 D007 Pass

Heat Detector PANTRY 163 1 L03 D008 Pass

Heat Detector CHEM STORAGE 165 1 L03 D009 Pass

Heat Detector LAUNDRY 164 1 L03 D010 Pass

Heat Detector LINNENS 162 1 L03 D011 Pass

Duct Detector MECHANICAL ROOM 170 1 L03 D012 Pass

Heat Detector MECHANICAL ROOM 170 1 L03 D013 Pass

Heat Detector MECHANICAL ROOM 170 1 L03 D014 Pass

Heat Detector ELECTRICAL ROOM 177 1 L03 D015 Pass

Smoke Detector STORAGE ROOM 176 1 L03 D016 Pass

Smoke Detector STORAGE ROOM 185 1 L03 D018 Pass

Heat Detector PRODUCTION 189 1 L03 D019 Pass

Heat Detector TECH LAB 183 1 L03 D020 Pass

Smoke Detector STORAGE TECH LAB 183 1 L03 D022 Pass

Heat Detector LAB 311 1 L03 D023 Pass

Pull Station CORRIDOR EXIT 150 1 L03 M002 Pass

Monitor CULINARY KITCHEN 161 HOOD 1 L03 M003 Pass

Pull Station CULINARY KITCHEN 161 1 L03 M004 Pass

Pull Station MECHANICAL ROOM 170 1 L03 M006 Pass

Pull Station HALL 170 EXIT 1 L03 M008 Pass

Pull Station PRODUCTION 189 1 L03 M009 Pass

Waterflow Switch PRODUCTION 189 1 L03 M010 Pass

Tamper Switch PRODUCTION 189 1 L03 M011 Pass

Pull Station LAB 312 EXIT 1 L03 M014 Pass

Waterflow Switch PRODUCTION 189 1 L03 M020 Pass

Tamper Switch PRODUCTION 189 1 L03 M021 Fail

Heat Detector SCIENCE LAB 441 1 L04 D001 Pass

Heat Detector PREP ROOM 443 1 L04 D002 Pass

Smoke Detector HALL 400 FIRE DOORS 1 L04 D003 Pass

Smoke Detector HALL 400 FIRE DOORS 1 L04 D004 Pass

Smoke Detector HALL 400 FIRE DOORS 1 L04 D005 Pass

Smoke Detector HALL 400 FIRE DOORS 1 L04 D006 Pass

Heat Detector CUSTODIAL ROOM 344 1 L04 D007 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 153: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector STORAGE ROOM @ 364 1 L04 D008 Pass

Smoke Detector HALL 360 @ CLASS ROOM 371 1 L04 D009 Pass

Smoke Detector HALL 360 FIRE DOORS 1 L04 D010 Pass

Smoke Detector HALL 360 FIRE DOORS 1 L04 D011 Pass

Duct Detector GYM 320 1 L04 D012 Visual

Duct Detector GYM 320 1 L04 D013 Visual

Heat Detector GYM 320 1 L04 D014 Visual

Heat Detector GYM 320 1 L04 D015 Visual

Duct Detector GYM 320 1 L04 D016 Visual

Duct Detector GYM 320 1 L04 D017 Visual

Smoke Detector MEDIA CENTER 300 1 L04 D018 Pass

Smoke Detector MEDIA CENTER 300 1 L04 D019 Pass

Smoke Detector MEDIA PRODUCTION ROOM 306 1 L04 D020 Pass

Heat Detector STORAGE ROOM 305 1 L04 D021 Pass

Heat Detector ROOM 402 1 L04 D022 Pass

Smoke Detector STORAGE ROOM 414 1 L04 D023 Pass

Smoke Detector COMP LAB 410 1 L04 D024 Pass

Heat Detector LAB 416 1 L04 D025 Pass

Smoke Detector SPECIAL EDUCATION ROOM426 1 L04 D026 Pass

Smoke Detector HALL 427 @ 425 1 L04 D027 Pass

Smoke Detector SPECIAL EDUCATION 466 1 L04 D028 Pass

Smoke Detector STORAGE ROOM 470 1 L04 D029 Pass

Smoke Detector SPECIAL EDUCATION 468 1 L04 D030 Pass

Smoke Detector COMP ROOM 474 1 L04 D031 Pass

Smoke Detector HALL 400 @ 466 1 L04 D032 Pass

Smoke Detector HALL 440 FIRE DOORS 1 L04 D033 Pass

Smoke Detector HALL 440 FIRE DOORS 1 L04 D034 Pass

Pull Station SCIENCE LAB 441 1 L04 M001 Pass

Pull Station HALL 440 EXIT 1 L04 M002 Pass

Pull Station HALL 400 EXIT 1 L04 M003 Pass

Pull Station HALL 360 EXIT 1 L04 M006 Pass

Pull Station HALL 340 EXIT 1 L04 M007 Pass

Pull Station HALL 460 EXIT 1 L04 M014 Pass

Heat Detector PREP ROOM 447 1 L05 D001 Pass

Heat Detector SCIENCE ROOM 449 1 L05 D002 Pass

Heat Detector MECHANICAL ROOM 451 1 L05 D003 Pass

Heat Detector CUSTODIAL ROOM 484 1 L05 D004 Pass

Heat Detector ELECTRICAL ROOM 483 1 L05 D005 Pass

Heat Detector PREP ROOM 488 1 L05 D006 Pass

Heat Detector PREP ROOM 492 1 L05 D007 Pass

Heat Detector LAB 486 1 L05 D008 Pass

Smoke Detector HALL 481 1 L05 D009 Pass

Smoke Detector HALL 481 1 L05 D010 Pass

Heat Detector LAB ROOM 490 1 L05 D011 Pass

Smoke Detector STORAGE ROOM 471 1 L05 D012 Pass

Heat Detector LAB ROOM 467 1 L05 D013 Pass

Heat Detector PREP ROOM 496 1 L05 D014 Pass

Heat Detector LAB ROOM 494 1 L05 D015 Pass

Heat Detector PREP ROOM 497 1 L05 D016 Pass

Heat Detector PREP ROOM 491 1 L05 D017 Pass

Smoke Detector STORAGE ROOM 446 1 L05 D018 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 154: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector FIRE DOORS O/S ROOM 611 1 L05 D019 Pass

Smoke Detector FIRE DOORS O/S ROOM 611 1 L05 D020 Pass

Heat Detector FILES ROOM 613 1 L05 D021 Pass

Heat Detector MECHANICAL ROOM 609 1 L05 D022 Pass

Smoke Detector STORAGE ROOM 607 1 L05 D023 Pass

Smoke Detector STORAGE ROOM 617 1 L05 D024 Pass

Heat Detector VAULT ROOM 605 1 L05 D025 Pass

Smoke Detector ADMIN ROOM 606 1 L05 D026 Pass

Heat Detector VAULT ROOM 623 1 L05 D027 Pass

Smoke Detector ENTRY CORRIDOR 620 1 L05 D028 Pass

Smoke Detector ROOM 702 1 L05 D029 Pass

Smoke Detector CLINIC 701 1 L05 D030 Pass

Smoke Detector CORRIDOR 700 O/S CLINIC 1 L05 D031 Pass

Pull Station SCIENCE LAB 449 1 L05 M001 Pass

Pull Station MECHANICAL ROOM 451 1 L05 M002 Pass

Pull Station HALL 481 EXIT 1 L05 M004 Pass

Pull Station ENTRY CORRIDOR 600 1 L05 M005 Pass

Pull Station MAIN OFFICE FOYER 600 1 L05 M006 Pass

Waterflow Switch MECHANICAL RM 451 1 L05 M010 Pass

Tamper Switch MECHANICAL RM 451 1 L05 M011 Fail

Smoke Detector ROLL DOOR BACKSTAGE AUDITORIUM 1 L06 D001 Pass

Smoke Detector ROLL DOOR BACKSTAGE AUDITORIUM 1 L06 D002 Pass

Heat Detector MECHANICAL ROOM 650 1 L06 D003 Pass

Heat Detector CHEMICAL STORAGE ROOM 691 1 L06 D004 Pass

Heat Detector BULK STORAGE ROOM 687 1 L06 D005 Pass

Heat Detector DRY STORAGE ROOM 689 1 L06 D006 Pass

Heat Detector KITCHEN @ SERVING ROOM 686 1 L06 D007 Pass

Heat Detector KITCHEN ROOM 686 1 L06 D008 Pass

Heat Detector KITCHEN ROOM 686 1 L06 D009 Pass

Heat Detector CUSTODIAL ROOM 688 1 L06 D010 Pass

Heat Detector UTILITY ROOM 690 1 L06 D011 Pass

Heat Detector PERCUSSION ROOM 728 1 L06 D012 Pass

Heat Detector INSTRUMENT ROOM 726 1 L06 D013 Pass

Heat Detector UNIFORMS ROOM 724 1 L06 D014 Pass

Heat Detector LIBRARY ROOM 722 1 L06 D015 Pass

Duct Detector CORRIDOR 700 1 L06 D016 Pass

Duct Detector CORRIDOR 700 1 L06 D017 Pass

Duct Detector DRAMA 780 1 L06 D018 Pass

Duct Detector DRAMA 780 1 L06 D019 Pass

Duct Detector DRAMA 780 1 L06 D020 Pass

Duct Detector DRAMA 780 1 L06 D021 Pass

Smoke Detector CORRIDOR 740 1 L06 D022 Pass

Smoke Detector CORRIDOR 740 1 L06 D023 Pass

Heat Detector STORAGE ROOM 716 1 L06 D024 Pass

Duct Detector DRY STORAGE KITCHEN 1 L06 D025 Pass

Duct Detector DRY STORAGE KITCHEN 1 L06 D026 Pass

Duct Detector DRY STORAGE KITCHEN 1 L06 D027 Pass

Duct Detector KITCHEN @DISHWASHING 1 L06 D028 Pass

Heat Detector ELECTRICAL ROOM 648 1 L06 D031 Pass

Smoke Detector DATA ROOM 646 1 L06 D032 Pass

Waterflow Switch LOCKERS 696 1 L06 M005 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 155: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Tamper Switch LOCKERS 696 1 L06 M006 Fail

Pull Station KITCHEN REAR EXIT ROOM 686 1 L06 M007 Pass

Pull Station CORRIDOR 740 1 L06 M010 Pass

Pull Station CHORUS SUIT 709 1 L06 M017 Pass

Waterflow Switch LOCKERS 696 1 L06 M029 Pass

Tamper Switch LOCKERS 696 1 L06 M030 Pass

Monitor KITCHEN HOOD MAIN BLDG 1 L06 M033 Pass

Pull Station KITCHEN SIDE EXIT ROOM 686 1 L06 M034 Pass

Tamper Switch AUDITORIUM RM 741 1 L06 M061 Pass

Waterflow Switch AUDITORIUM RM 741 1 L06 M062 Pass

Pull Station LOBBY AUDITORIUM 1 L06 M067 Pass

Pull Station WEST HALL AUDITORIUM 1 L06 M068 Pass

Pull Station RAMP AUDITORIUM 1 L06 M069 Pass

Pull Station CLASS ROOM AUDITORIUM 1 L06 M070 Pass

Pull Station STAGE AREA AUDITORIUM 1 L06 M071 Pass

Pull Station SIDE ENTRANCE AUDITORIUM 1 L06 M072 Pass

Smoke Detector SCHOOL STORE 1 L07 D001 Pass

Smoke Detector FIRE DOORS CORRIDOR 660 1 L07 D002 Pass

Smoke Detector FIRE DOORS CORRIDOR 660 1 L07 D003 Pass

Smoke Detector CAFETERIA ENTRANCE 1 L07 D004 Pass

Smoke Detector CAFETERIA ROOM 682 1 L07 D005 Pass

Smoke Detector CAFETERIA ROOM 682 1 L07 D006 Pass

Smoke Detector CAFETERIA ROOM 682 1 L07 D007 Pass

Smoke Detector CAFETERIA ROOM 682 1 L07 D008 Pass

Smoke Detector CAFETERIA ROOM 682 1 L07 D009 Pass

Smoke Detector CAFETERIA ROOM 682 1 L07 D010 Pass

Duct Detector SERVING LINE CAFETERIA 1 L07 D011 Visual

Duct Detector SERVING LINE CAFETERIA 1 L07 D012 Visual

Heat Detector SERVING LINE CAFETERIA 1 L07 D013 Pass

Duct Detector SERVING LINE CAFETERIA 1 L07 D014 Visual

Duct Detector SERVING LINE CAFETERIA 1 L07 D015 Visual

Duct Detector SERVING LINE CAFETERIA 1 L07 D016 Visual

Heat Detector SERVING LINE CAFETERIA 1 L07 D017 Pass

Duct Detector SERVING LINE CAFETERIA 1 L07 D018 Visual

Heat Detector SERVING KITCHEN 1 L07 D019 Pass

Heat Detector SERVING KITCHEN 1 L07 D020 PassHeat Detector DISH WASHING ROOM 685 1 L07 D021 Pass

Pull Station CAFETERIA ENTRANCE 1 L07 M001 Pass

Pull Station CAFETERIA ENTRANCE 680 1 L07 M009 Pass

Monitor KITCHEN HOOD MAIN BLDG 1 L07 M010 Pass

Pull Station CAFETERIA EXIT 1 L07 M022 Pass

Waterflow Switch GYMNASIUM RM 572 1 L07 M023 Pass

Pull Station LOBBY GYM 1 L07 M025 Pass

Pull Station GYM ROOM 522 1 L07 M027 Pass

Pull Station GYM ROOM 530 1 L07 M028 Pass

Pull Station GYM ROOM 536 1 L07 M029 Pass

Pull Station GYM ROOM 544 1 L07 M030 Pass

Pull Station GYM ROOM 550 1 L07 M031 Pass

Pull Station GYM ROOM 545 1 L07 M032 Pass

Pull Station GYM ROOM 543 1 L07 M033 Pass

Pull Station GYM ROOM 535 1 L07 M034 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 156: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station GYM ROOM 539 1 L07 M035 Pass

Pull Station GYM ROOM 521 1 L07 M036 Pass

Pull Station GYM ROOM 561 1 L07 M037 Pass

Pull Station TOP DOOR ROOF GYM 1 L07 M038 Pass

Heat Detector MECHANICAL ROOM 804 1 L08 D001 Pass

Heat Detector STORAGE ROOM 801 1 L08 D002 Pass

Heat Detector HALL 821 O/S LAUNDRY 1 L08 D003 Pass

Heat Detector BOYS LOCKER ROOM 805 1 L08 D004 Pass

Heat Detector HALL 821 O/S ROOM 809 1 L08 D005 Pass

Heat Detector TRAINER ROOM 811 1 L08 D006 Pass

Heat Detector STORAGE ROOM 816 1 L08 D007 Pass

Heat Detector GIRLS LOCKER ROOM 815 1 L08 D008 Pass

Heat Detector MECHANICAL ROOM 819 1 L08 D009 Pass

Smoke Detector ELEVATOR LOBBY 1ST FL 1 L08 D010 Pass

Heat Detector ELEVATOR PIT 1 L08 D011 Pass

Smoke Detector ELEVATOR PIT 1 L08 D012 Pass

Heat Detector ELEVATOR MACHINE ROOM 822 1 L08 D013 Pass

Smoke Detector ELEVATOR MACHINE ROOM 822 1 L08 D014 Pass

Heat Detector GIRLS LOCKER 826 1 L08 D015 Pass

Heat Detector MECHANICAL ROOM 828 1 L08 D016 Pass

Heat Detector GIRLS LOCKER 830 1 L08 D017 Pass

Heat Detector GIRLS LOCKER 834 1 L08 D018 Pass

Heat Detector CUSTODIAL ROOM 838 1 L08 D019 Pass

Heat Detector HALL 839 @ SE EXIT 1 L08 D020 Pass

Heat Detector HALL 839 @ SW EXIT 1 L08 D021 Pass

Heat Detector ELECTRICAL ROOM 837 1 L08 D022 Pass

Heat Detector BOYS LOCKER ROOM 833 1 L08 D023 Pass

Heat Detector BOYS LOCKER 829 1 L08 D024 Pass

Heat Detector MECHANICAL ROOM 827 1 L08 D025 Pass

Heat Detector BOYS LOCKER ROOM 825 1 L08 D026 Pass

Heat Detector LAUNDRY ROOM 802 1 L08 D027 Pass

Smoke Detector DATA ROOM 863 1 L08 D028 Pass

Heat Detector BLEACHERS SEATING 1 L08 D029 Pass

Heat Detector BLEACHERS SEATING 1 L08 D030 Pass

Heat Detector BLEACHERS SEATING 1 L08 D031 Pass

Heat Detector BLEACHERS SEATING 1 L08 D032 Pass

Heat Detector BLEACHERS SEATING 1 L08 D033 Pass

Heat Detector BLEACHERS SEATING 1 L08 D034 Pass

Smoke Detector ELEVATOR SHAFT 1 L08 D035 Pass

Heat Detector ELEVATOR SHAFT 1 L08 D036 Pass

Smoke Detector ELEVATOR LOBBY 1 L08 D037 Pass

Heat Detector CUSTODIAL ROOM 856 1 L08 D038 Pass

Heat Detector GYM LOBBY 850 1 L08 D039 Pass

Heat Detector STORAGE ROOM 857 1 L08 D040 Pass

Heat Detector CONCESSIONS 858 1 L08 D041 Pass

Heat Detector CONCESSIONS 858 1 L08 D042 Pass

Heat Detector STORAGE ROOM 855 1 L08 D043 Pass

Duct Detector LOBBY ROOM 850 1 L08 D044 Pass

Duct Detector CONCESSIONS 858 1 L08 D045 Pass

Duct Detector CONCESSIONS 858 1 L08 D046 Pass

Duct Detector CONCESSIONS 858 1 L08 D047 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 157: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector CONCESSIONS 858 1 L08 D048 Pass

Duct Detector WOMANS RESTROOM 854 1 L08 D049 Pass

Duct Detector WOMANS RESTROOM 853 1 L08 D050 Pass

Pull Station NW FORYER O/S ROOM 801 1 L08 M001 Pass

Pull Station NE EXIT @ ELEVATOR 1 L08 M002 Pass

Waterflow Switch ARENA CUST RM 838 1 L08 M007 Pass

Tamper Switch ARENA CUST RM 838 1 L08 M008 Pass

Pull Station SOUTH EXIT GYM 1 L08 M009 Pass

Pull Station SOUTH EXIT GYM 1 L08 M010 Pass

Pull Station ELECTRICAL ROOM 838 1 L08 M013 Pass

Pull Station GYM LOBBY 1 L08 M015 Pass

Pull Station GYM LOBBY 1 L08 M016 Pass

Pull Station GYM LOBBY 1 L08 M017 Pass

Pull Station GYM LOBBY 1 L08 M018 Pass

Pull Station GYM LOBBY 1 L08 M019 Pass

Pull Station GYM LOBBY 1 L08 M020 Pass

Smoke Detector HALL 1170 ENTRY FIRE DOORS 1 L09 D001 Pass

Smoke Detector HALL 1170 ENTRY FIRE DOORS 1 L09 D002 Pass

Heat Detector CUSTODIAL CLOSET 1144 1 L09 D003 Pass

Smoke Detector CORRIDOR 1140 FIRE DOORS 1 L09 D004 Pass

Smoke Detector CORRIDOR 1140 FIRE DOORS 1 L09 D005 Pass

Smoke Detector ELECTRICAL ROOM 1196 1 L09 D006 Pass

Smoke Detector HALL 1250 ENTRY FIRE DOORS 1 L09 D007 Pass

Smoke Detector HALL 1250 ENTRY FIRE DOORS 1 L09 D008 Pass

Pull Station HALL 900 VESTIBULE 1 L09 M001 Pass

Pull Station CORRIDOR 1140 EXIT 1 L09 M004 Pass

Pull Station LOADING DOCK 1 L09 M048 Pass

Duct Detector FCU-101 1500 BLDG N.MECH ROOM EAST 1200-1600 1 L10 D002 Pass

Duct Detector FCU-105 1500 BLDG S.MECH ROOM EAST 1200-1600 1 L10 D003 Pass

Pull Station RECEPTION 1 L10 M001 Pass

Pull Station LOBBY 1 L10 M002 Pass

Pull Station MEDIA CENTER 1 L10 M003 Pass

Pull Station 1200 HALLWAY 1 L10 M004 Pass

Pull Station 1210 HALLWAY @ 1211 1 L10 M005 Pass

Pull Station 1200 HALLWAY @ 1218 1 L10 M006 Pass

Pull Station 1300 HALLWAY @1328 1 L10 M008 Pass

Pull Station @ 1228 1 L10 M009 Pass

Pull Station 1400 HALLWAY 1 L10 M012 Pass

Pull Station @ 1411 1 L10 M016 Pass

Pull Station ART ROOM 1512 1 L10 M018 Pass

Pull Station ART ROOM 1512 1 L10 M019 Pass

Pull Station HALLWAY 1419 @ 1428 1 L10 M043 Pass

Pull Station HALLWAY 1419 @ 1418 1 L10 M044 Pass

Pull Station HALLWAY 1400 @ 1591 1 L10 M045 Pass

Pull Station 1300 HALLWAY @ 1311 1 L10 M047 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 158: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

No visual or audible notification activated on any strobes and/or speaker strobes in 720, 730, 731, 733

auditorium or backstage rooms during sound testing. No bypass was active on panel and additional pull

stations in area were activated in attempt to cause area to successfuly trip.

Deficiencies

(1) tamper switch in Production Room 189 failed to report to FACP.

(1) tamper switch in Kitchen Lockers 696 failed to report to FACP.

(1) tamper switch in Mechanical Room 451 failed to report to FACP.

(3) troubles on FACP on arrival: (1) Software Mismatch (2) Remote Display 3 troubles (Trouble&No Answer)

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 159: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 160: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Voice Evac 1 0

4 0

6 0

8 0

2 0

Inspector Name : Signature:

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

8/11/2020

EI1273

Innovair

Other

Batteries

Pullstations

NotifierSmoke Detectors FSP851

Duct Detectors System Sensor

Pass

3635 Coal Mountain Drive

North Forsyth High School Performing Arts

Ground Fault

171621

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredLobby

Model Name AFP-200Notifier

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC

All-Star Fire, LLC

PowerPatrol

Notifier NBG12LX

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

AFP-200

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Notifier

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

Pass

Silent Knight SKE-450

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 161: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.2 Pass

Good (2019) 13.2 Pass

Good (2019) 13 Pass

Good (2019) 13.1 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Voice Evac (right)

Voice Evac (left)

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 162: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initiating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station Rear Side Exit 1 M05 Pass

Pull Station Front Side Exit 1 M06 Pass

Pull Station Side Exit 1 M10 Pass

Pull Station Lobby 1 M07 Pass

Pull Station Side Exit 1 M08 Pass

Pull Station Side Exit 1 M09 Pass

Duct Detector RTU-3 1 D03 Visual

Duct Detector RTU-3 1 D04 Visual

Duct Detector RTU-1 1 D05 Visual

Duct Detector RTU-1 1 D06 Visual

Duct Detector RTU-2 1 D07 Visual

Duct Detector RTU-2 1 D08 Visual

Duct Detector RTU-4 1 D09 Visual

Duct Detector RTU-4 1 D10 Visual

Smoke Detector Roll up Door Stage 1 D02 Visual

Smoke Detector Roll up Door Workshop 1 D01 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 163: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 164: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 165: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

2 0

11 0

8 0

21 0

11 0

Inspector Name : Signature:

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

8/11/2020

EI1273 / WO #155454

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

North Forsyth High School - New Gym addition

UL Mech rm

Who Was Notified Prior to the Start of Testing

YesIs the Panel Monitored4100 ES

Model Name 4100ESSimplex

GA

Monitoring Company

30040

All-Star Fire, LLC

Power Patrol

Simplex 4099-9006

TBD

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4100 ES

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Cumming

Are Lamps and Displays Operating Properly

Pass

3635 Coal Mountain Drive

EMC Security

Pass

Pass

Pass

D K Womack

Ground Faults Detected by Control Panel

EMC

4098-9685

Ken Womack

SimplexHeat Detector 4098-9403

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Other

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment Pass

Ground Fault

Control Panel

Device

Pass

Pass

Device Summary

Manufacturer

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 166: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13 Pass

Good (2019) 13 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FACP (left)

12v 50ahFACP (right)

12v 50ah

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Interface Equipment

Generator In Auto

Generator Trouble Generator Trouble Reports to Panel

Correct Switching and Operation Verified

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel Fire Pump Running

Fire Pump Power Loss

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 167: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initiating Device Testing

Device Type Location Floor Address/Zone Results

Heat Detector Gym Elect rm G213 UL M1-01 Visual

Heat Detector Gym Elect rm G213 UL M1-02 Visual

Pull Station Gym @ Stair S202 UL M1-03 Pass

Pull Station Gym @ Stair S201 UL M1-04 Pass

Duct Detector Gym Storage rm G135A UL M1-05 Visual

Smoke Detector Gym Storage rm G207 UL M1-06 Visual

Smoke Detector Gym IDF rm zG205 UL M1-07 Pass

Duct Detector Gym Elect rm UL M1-08 Pass

Smoke Detector Gym Storage rm G215 UL M1-09 Visual

Duct Detector Gym Vestibule RTU G6 UL M1-10 Visual

Duct Detector Gym Handicap Ramp UL M1-11 Visual

Smoke Detector Gym Elev Lobby UL M1-12 Visual

Duct Detector Gym Men's RR RTU - G5 UL M1-15 Visual

Duct Detector Gym Men's RR RTU - G4 UL M1-16 Visual

Smoke Detector Gym Hall 600 UL M1-17 Not found

Smoke Detector Gym Hall 600 UL M1-18 Pass

Heat Detector Gym Concession UL M1-19 Visual

Heat Detector Gym Concession UL M1-20 Visual

Duct Detector Gym Women's RR RTU - G3 UL M1-21 Pass

Duct Detector Gym Vestibule UL M1-22 Visual

Smoke Detector Gym Storage rm G216 UL M1-23 Pass

Pull Station Gym Vestibule UL M1-24 Visual

Smoke Detector Gym Storage rm G212 UL M1-25 Visual

Pull Station Gym Stair UL M1-26 Not found

Pull Station Gym @ Stair S2 LL M1-61 Pass

Pull Station Gym ROTC/Range rm G124 LL M1-62 Pass

Pull Station Gym ROTC Hall G139 LL M1-63 Pass

Smoke Detector Gym ROTC Storage rm G123 LL M1-64 Pass

Smoke Detector Gym ROTC Storage rm G122 LL M1-65 Pass

Heat Detector Gym Janitor rm G118 LL M1-66 Visual

Smoke Detector Gym Coaches Office Storage LL M1-67 Pass

Pull Station Gym Coaches Office Hall LL M1-68 Pass

Pull Station Gym @ Stair S1 LL M1-69 Pass

Pull Station Gym ROTC/Range rm G216 LL M1-70 Pass

Heat Detector Gym Elect rm G104 LL M1-71 Visual

Heat Detector Gym Elev Mach rm G103 LL M1-72 Visual

Smoke Detector Gym Elev Mach rm G103 LL M1-73 Pass

Smoke Detector Gym Locker rm Hall LL M1-79 Pass

Smoke Detector Gym Locker rm Hall LL M1-80 Pass

Smoke Detector Gym Locker rm Hall LL M1-81 Pass

Smoke Detector Gym Locker rm Hall LL M1-82 Pass

Pull Station Gym Lobby G101 LL M1-83 Pass

Smoke Detector Gym Elev Lobby LL M1-84 Visual

Heat Detector Gym Elect/ Mech rm G102 LL M1-85 Visual

Smoke Detector Gym Handicap Ramp LL M1-86 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 168: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Gym 600 Hall LL M1-87 Not found

Heat Detector Gym Trophy Case Storage LL M1-88 Visual

Heat Detector Gym Storage rm G112A LL M1-89 Visual

Smoke Detector Gym Hall G135 LL M1-90 Not found

Smoke Detector Gym Stair G102 LL M1-91 Not found

Heat Detector Gym Storage rm G135A LL M1-92 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 169: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

NOTE:

Could not test elevator recall as smoke detectors are too high.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 170: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 171: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 7 0

16 4

47 1

54 1

69 0

15 0

Inspector Name : Signature:

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

SimplexHeat Detector 4098-9733

All-Star Fire, LLC

Power Patrol

Simplex 4099-9003

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4100 ES

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

3635 Cold Mountain Drive

North Forsyth High School

Ground Fault

171623

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredRiser rm 246

Model Name 4100ESSimplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC

4098-9686

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

8/12/2020

EI1273

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 172: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Fail

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13 Pass

Good (2019) 13.1 Pass

Good (2019) 13 Pass

Good (2019) 13 Pass

Good (2019) 13.1 Pass

Good (2019) 13.1 Pass

Good (2019) 13.1 Pass

Good (2019) 13 Pass

Fair (2019) 12.9 Fail

Fair (2019) 13 Fail

Good (2019) 13.2 Pass

Good (2019) 13.1 Pass

Fair (2019) 12.8 Fail

Fair (2019) 12.9 Fail

Good (2019) 13.1 Pass

Good (2019) 13 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Pass

N/A

N/A

Pass

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #5 rm 158

FCPS (left) #4 rm 229

FCPS (left) #5 rm 158

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 345

FCPS (right) #2 rm 345

FCPS (left) #3 rm 246

FCPS (right) #3 rm 246

12v 7ah

12v 7ah

12v 7ah

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FACP (left) rm 246

12v 50ahFACP (right) rm 246

12v 50ah

12v 7ah

FCPS (right) #1 rm 133

FCPS (left) #1 rm 133

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FCPS (right) #4 rm 229

FCPS (left) #6 rm 802

FCPS (right) #6 rm 802

FCPS (left) #7 rm 852

FCPS (right) #7 rm 852

12v 7ah

12v 7ah

12v 7ah

12v 7ah

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 173: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

N/AFM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 174: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Duct Detector Media Ctr Corr Exit 1 M1-65 Pass

Duct Detector 9th Grade Corr @ Rear Elect rm 1 M1-66 Not Found

Duct Detector 9th Grade Corr @ Front Elect rm 1 M1-67 Not Found

Duct Detector 9th Grade rm 248 1 M1-68 Pass

Duct Detector 9th Grade Corr @ Janitor 1 M1-69 Pass

Duct Detector 9th Grade Corr @ Science Lab 1 M1-70 Pass

Duct Detector Stage Area 1 M1-73 Not Found

Duct Detector Classroom A-54 1 M1-74 Not Found

Duct Detector Boiler Area Mech rm 1 M1-75 No Access

Duct Detector Classroom 143 1 M1-76 Not Found

Duct Detector Classroom B-53 1 M1-77 Not Found

Duct Detector Classroom B-47 1 M1-78 Not Found

Duct Detector Conf. rm 1 M1-79 Not Found

Duct Detector Classroom A-74 1 M1-80 Not Found

Duct Detector A Sec Spec Ed 1 M1-81 Not Found

Duct Detector Classroom B-39 1 M1-82 Not Found

Duct Detector North/South Corr @ Band 1 M1-83 Pass

Duct Detector North/South Corr @ Science 1 M1-84 Pass

Duct Detector Band Room 1 M1-220 Not Found

Duct Detector ERU-2 rm 856 2 M1-236 Not Found

Duct Detector ERU-1 Girls RR 2 M1-237 Not Found

Duct Detector Mech rm 328 1 M1-247 Pass

Duct Detector Mech rm 328 1 M1-248 Not Found

Pull Station D Wing North Exit 1 M1-01 Pass

Pull Station D Wing Exit to Covered Walk 1 M1-02 Pass

Pull Station D Wing Exit to Parking Lot 1 M1-03 Pass

Pull Station D Wing Exit South 1 M1-04 Pass

Pull Station 400-500 Core Back Exit 1 M1-06 Pass

Pull Station C Wing Exit to Covered Walk 1 M1-07 Fail

Pull Station C Wing Main Entrance 1 M1-08 Pass

Pull Station Boiler Room Exit 1 M1-09 Pass

Pull Station C Wing South Exit 1 M1-10 Pass

Pull Station Tech Lab Exit South 1 M1-11 Pass

Pull Station Main Corr Coke Hall North 1 M1-12 Pass

Pull Station A Wing South Exit 1 M1-17 Pass

Pull Station Science Lab Exit 1 M1-18 Pass

Pull Station Band Rehearsal Rm 1 M1-19 Pass

Pull Station A Corr South Exit 1 M1-20 Pass

Pull Station NE Corr Exit @ rm B-53 1 M1-22 Pass

Pull Station Corr Exit @ Science rm 1 M1-23 Pass

Pull Station S Corr Exit @ Girls Locker 1 M1-24 Pass

Pull Station Art Room North Exit 1 M1-25 Pass

Pull Station Art Room South Exit 1 M1-26 Pass

Pull Station Cafe Exit to Biway 1 M1-27 Pass

Pull Station Media Ctr Corr Exit 1 M1-53 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 175: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station 9th Grade Corr Exit @ Rear 1 M1-54 Pass

Pull Station 9th Grade Corr Exit @ Science 1 M1-57 Pass

Pull Station 9th Grade Mech rm 1 M1-58 Pass

Pull Station Corr 800 Exit 1 M1-201 Pass

Pull Station Corr 800 Exit 1 M1-202 Pass

Pull Station Add Stair #1 Exit 1 M1-206 Pass

Pull Station Add Exit @ rm 840 1 M1-209 Pass

Pull Station Add Mech rm 1 M1-212 Pass

Pull Station Add Stair #1 Exit 1 M1-215 Pass

Pull Station Add Stair #1 Exit 1 M1-216 Pass

Pull Station Add Corr @ Stair 1 2 M1-231 Pass

Pull Station Add Corr @ Stair 2 2 M1-239 Pass

Smoke Detector Corr @ rm 132 1 M1-39 Pass

Smoke Detector AGR Science Corr 1 M1-40 Pass

Smoke Detector AGR Science Corr 1 M1-41 Pass

Smoke Detector Main Corr @ rm A-59 1 M1-42 Pass

Smoke Detector Gym Corr @ Concession Stand 1 M1-43 Pass

Smoke Detector North/West Corr @ Concession 1 M1-44 Pass

Smoke Detector Girls Locker Corr @ Gym 1 M1-45 Pass

Smoke Detector SW Corr @ Mech rm 1 M1-46 Pass

Smoke Detector Media Ctr Corr @ Media Prod 1 M1-60 Pass

Smoke Detector Media Ctr Corr Exit South 1 M1-61 Pass

Smoke Detector Media Ctr Corr Exit North 1 M1-62 Pass

Smoke Detector Media Ctr Corr to 9th Grade 1 M1-63 Pass

Smoke Detector Conn Corr 800 Smoke drs 1 M1-203 Pass

Smoke Detector Add Corr 801 Smoke drs 1 M1-204 Pass

Smoke Detector Add Elect rm 802 1 M1-205 Pass

Smoke Detector Add Stair #1 Smoke 1 M1-207 Pass

Smoke Detector Add Corr @ Stair 1 1 M1-208 Pass

Smoke Detector Add Corr @ Stair 2 1 M1-213 Pass

Smoke Detector Add Stair #2 Smoke 1 M1-214 Pass

Smoke Detector Add Elev Equip rm 1 M1-217 Pass

Smoke Detector Add Elev Lobby 1 M1-218 Pass

Smoke Detector Add Elect rm 852 2 M1-230 Pass

Smoke Detector Add Stair @ Smoke 2 M1-232 Pass

Smoke Detector Add Corr @ Stair 1 2 M1-233 Pass

Smoke Detector Add Elev Top of Shaft 2 M1-234 Pass

Smoke Detector Add Elev Lobby 2 M1-235 Pass

Smoke Detector Add Corr @ Stair 2 2 M1-238 Pass

Smoke Detector Add Stair 2 @ Smoke 2 M1-240 Pass

Smoke Detector Sprinkler Closet 245 @ FACP 1 M2-1 Pass

Smoke Detector 800 Hall to 300 Hall dr 1 M1-198 Pass

Pull Station Cafeteria @ 130 Hall 1 M2-108 Pass

Duct Detector Gym 1 H5 RTU-5 1 M2-107 No Access

Duct Detector Gym 1 H5 RTU-4 1 M2-106 No Access

Duct Detector Gym 1 H5 RTU-3 1 M2-105 No Access

Duct Detector Gym 1 H5 RTU-2 1 M2-104 No Access

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 176: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Gym 1 H5 RTU-1 1 M2-103 No Access

Duct Detector Cafeteria 130 RTU-3 1 M2-102 Visual

Duct Detector Cafeteria 130 RTU-4 1 M2-101 Visual

Duct Detector Classroom 371 Hall Mech rm 369 1 M2-94 Pass

Duct Detector Classroom 342 Hall Mech rm 344 1 M2-93 Pass

Duct Detector Classroom 336 Hall Mech rm 338 1 M2-92 Pass

Duct Detector Classroom 330 Hall Mech rm 332 1 M2-91 Pass

Duct Detector Main Office Clinic Stor rm 104 1 M2-90 Pass

Duct Detector Main Office Clinic Stor rm 104 1 M2-89 Pass

Heat Detector Science Hall Mech rm 152 1 M2-87 Visual

Pull Station Main Hall C104 @ Science Exit 1 M2-86 Pass

Smoke Detector Main Hall C104 @ Science 1 M2-85 Pass

Smoke Detector Main Hall C104 @ Science 1 M2-84 Pass

Smoke Detector Main Hall C104 @ Science 1 M2-83 Pass

Smoke Detector Main Hall C104 @ Science 1 M2-82 Pass

Duct Detector Health Classroom 142 RTU-A6 1 M2-81 Not Found

Smoke Detector New Public Health Lab Storage 1 M2-80 Pass

Pull Station New Public Health Lab 147 1 M2-79 Pass

Duct Detector New Public Health Lab 147 RTU-A5 1 M2-78 Visual

Smoke Detector Sports Medicine Lab Storage rm 144 1 M2-77 Pass

Duct Detector New Public Health Lab RTU A4 1 M2-76 Visual

Smoke Detector Band rm Hall C106 1 M2-75 Pass

Smoke Detector Band rm Hall C104 1 M2-74 Pass

Smoke Detector Band rm Inst Storage 133 1 M2-71 Pass

Pull Station Band rm Hall 105 Exit 1 M2-70 Pass

Smoke Detector Band rm Percussion Storage 132 1 M2-68 Pass

Smoke Detector Band rm Uniform Storage 141 1 M2-67 Pass

Smoke Detector Band rm Uniform Storage 141 1 M2-66 Pass

Heat Detector Main Hall Mech rm 170 1 M2-65 Visual

Smoke Detector 300 Hall to 800 Hall dr 1 M2-62 Pass

Pull Station Science Hall Exit to Loading Dock 1 M2-61 Pass

Duct Detector Custodial Closet 372 RTU-A7 1 M2-60 Visual

Heat Detector Classroom 371 Hall Mech rm 369 1 M2-59 Visual

Heat Detector Custodial Closet 372 1 M2-58 Visual

Smoke Detector Classroom Hall to Science Hall 1 M2-57 Pass

Smoke Detector Classroom Hall to Science Hall 1 M2-56 Pass

Pull Station Classroom Hall to Loading Dock Exit 1 M2-55 Pass

Heat Detector Loading Dock Mech rm 1 M2-54 Visual

Pull Station Loading Dock Mech rm 1 M2-53 Pass

Pull Station Loading Dock Mech rm 1 M2-52 Pass

Pull Station Loading Dock Main Elect rm 345 1 M2-51 Pass

Heat Detector Loading Dock Main Elect rm 345 1 M2-50 Visual

Duct Detector Classroom Hall @ rm 344 DOAS A1 1 M2-49 Not Found

Heat Detector Classroom 342 Hall Mech rm 344 1 M2-48 Visual

Heat Detector Classroom 344 Hall Mech rm 341 1 M2-47 Visual

Heat Detector Classroom 336 Hall Mech rm 338 1 M2-46 Visual

Heat Detector Classroom 330 Hall Mech rm 332 1 M2-45 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 177: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector Classroom 337 Hall Mech rm 335 1 M2-44 Visual

Smoke Detector Cafeteria Storage rm 325 1 M2-43 Pass

Heat Detector Cafeteria IDF rm 323 1 M2-42 Visual

Heat Detector Cafeteria Mech rm 322 1 M2-41 Visual

Smoke Detector Hall of Fame to Cafe 1 M2-40 Pass

Smoke Detector Rest Rooms to Cafe 1 M2-39 Pass

Smoke Detector Cafe 130 to Rest Rooms 1 M2-38 Pass

Smoke Detector Cafe to Hall of Fame 1 M2-37 Pass

Duct Detector Cafe 130 to RTU-C3 1 M2-36 Visual

Duct Detector Cafe 130 to RTU-C4 1 M2-35 Visual

Smoke Detector Band rm Hall to Cafe 130 1 M2-34 Pass

Smoke Detector Cafeteria 130 to Band rm Hall 1 M2-33 Pass

Smoke Detector Media Ctr Hall to Cafe 1 M2-32 Pass

Smoke Detector Cafe to Media Ctr Hall 1 M2-31 Pass

Heat Detector Kitchen Laundry 139 1 M2-30 Visual

Duct Detector Kitchen Walk in Cooler RTU C5 1 M2-29 Not Found

Smoke Detector Kitchen Dry Storage 135 1 M2-28 Pass

Pull Station Kitchen 132 Exit 1 M2-27 Pass

Duct Detector Kitchen 132 MAU1 1 M2-26 Pass

Duct Detector Kitchen 132 MAU2 1 M2-25 Pass

Heat Detector Kitchen Custodial Closet 1 M2-23 Visual

Pull Station Cafe to Auditorium Hall Exit 1 M2-19 Pass

Smoke Detector Principals Office Closet 1 M2-18 Pass

Pull Station Cafe to Auditorium Hall 1 M2-17 Pass

Smoke Detector Main Office Vault 111 1 M2-16 Pass

Duct Detector Asst Principal Office 108 1 M2-15 Pass

Smoke Detector Main Office Stor rm 120 1 M2-14 Pass

Duct Detector Main Office Stor rm 110 1 M2-13 Fail

Smoke Detector Cafe to Auditorium Hall 1 M2-12 Pass

Smoke Detector Cafe to Auditorium Hall 1 M2-11 Pass

Smoke Detector School Store Storage rm 127 1 M2-10 Pass

Smoke Detector Clinic Storage rm 104 1 M2-09 Pass

Pull Station Main Entrance 1 M2-08 Pass

Smoke Detector Councelors Office Hall C101 1 M2-07 Pass

Smoke Detector Councelors Office Hall C102 1 M2-06 Pass

Smoke Detector Councelors Office C101 1 M2-05 Pass

Smoke Detector Councelors Office Hall C102 1 M2-04 Pass

Smoke Detector Aux Office Storage rm 106 1 M2-03 Not Found

Smoke Detector Aux Office Vault 1 M2-02 Not Found

Duct Detector Outside ERU to supply in rm 296 1 M1-250 No Access

Duct Detector Outside ERU2 to return in rm 296 1 M1-249 No Access

Duct Detector Outside ERU3 supply closet@ rm 464 1 M1-246 No Access

Duct Detector Outside ERU3 return @ rm 464 1 M1-245 No Access

Duct Detector Outside ERU4 supply in rm 535 1 M1-244 No Access

Duct Detector Outside ERU4 return on rm 535 1 M1-243 No Access

Smoke Detector Broadcast room inside rm 264 1 M1-59 Not Found

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 178: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

3. Duct Detector M2-13 failed to report to panel.

4. 4 Batteries failed load test.

Deficiencies

1. The following strobes failed to flash: in room 282, outside media Ctr in 200 hall by Exit,

and Hall outside rm 246.

2. Pull Station M1-07 failed to report to panel.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 179: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 180: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 1 0

6 0

17 0

2 0

5 0

1 0

Inspector Name : Signature:

Pass

Firelite FCPS-24 FS6

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

TBDVoice Evac Evac 25/50

All-Star Fire, LLC

PowerSonic

Firelite BG12LX

SLA1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

MS 5024

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Firelite

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

3635 Coal Mountain Drive

North Forsyth High School - Auxillary Gym and Field House

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredExt Mech rm NE corner

Model Name MS-5024Firelite

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

Innovair

Batteries

Pullstations

FireliteSmoke Detectors SD355

Duct Detectors System Sensor

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

8/11/2020

EI1273

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 181: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Fail

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Fair (2019) 13.3 Pass

Fair (2019) 13.2 Pass

Fair (2019) 13 Pass

Fair (2019) 13.1 Pass

Good (2019) 13.3 Pass

Good (2019) 13.1 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

Voice Evac (left)

Voice Evac (right)

12v 7ah

12v 7ah

FCPS (right) #1 rm 672

FCPS (left) #1 rm 672

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 182: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initiating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station Visitor Entrance UL 1M-01 Pass

Pull Station Home Entrance UL 1M-02 Pass

Pull Station Main Entrance 1 1M-03 Pass

Pull Station Home Entrance LL 1M-04 Pass

Pull Station Outside Women's Locker rm LL 1M-05 Pass

Pull Station Team Ladies Lounge LL 1M-06 No Access

Pull Station Laundry Exit LL 1M-07 Pass

Pull Station ROTC rm 650 LL 1M-08 Pass

Pull Station Marine Office LL 1M-09 Not Found

Pull Station Outside Men's Locker rm LL 1M-12 Pass

Pull Station Visitor LL 1M-13 Pass

Duct Detector ROTC Storage Area LL 1M-14 Not Found

Duct Detector Room 660 UL 1M-14 Not Found

Pull Station Field House Main Hall LL 1M-17 Pass

Pull Station Weight rm LL 1M-18 Not Found

Pull Station Weight rm LL 1M-19 Pass

Pull Station Weight rm LL 1M-20 Not Found

Smoke Detector Weight rm LL 1M-21 Not Found

Smoke Detector Weight rm LL 1M-22 Not Found

Smoke Detector Coaches Office LL 1M-23 Not Found

Smoke Detector Boys Locker rm LL 1M-24 Pass

Pull Station Field House Main Hall LL 1M-25 Pass

Smoke Detector Music rm LL 1M-27 Not Found

Pull Station Team Men's Lounge LL 1M-28 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 183: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. Upper gym weight bench side has no flash.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 184: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 185: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 3 0

8 2

22 0

13 0

10 0

Inspector Name : Signature:

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Pass

Pass

D K WomackKen Womack

Pass

Simplex 4009

Control Panel

Device

All-Star Fire, LLC

Power Patrol

Simplex 4099-9004

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Alpharetta

Are Lamps and Displays Operating Properly

Pass

4805 Atlanta Hwy

Midway Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name 4010Simplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ga

Monitoring Company

EMC

4098-9685

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

30004

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/28/2020

EI1273 / WO # 155453

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 186: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Fair (2019) 13.3 Pass

Fair (2019) 13.3 Pass

Fair (2018) 13.3 Pass

Fair (2018) 13.3 Pass

Poor (2017) 12.9 Fail

Poor (2017) 13 Fail

Fair (2018) 13.3 Pass

Fair (2018) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

Pass

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FCPS (left) #2 rm 504

FCPS (right) #2 rm 504

FCPS (left) #3 rm 106

FCPS (right) #3 rm 106

12v 7ah

12v 7ah

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FCPS (right) #1 rm 204

FCPS (left) #1 rm 204

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 187: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Duct Detector Bldg 500 RTU 7 1 M1-5 Visual

Duct Detector RTU 10 1 M1-6 Not Found

Duct Detector Bldg 300 Mech rm 1 M1-11 No Access

Duct Detector Bldg 300 Mech rm 1 M1-12 No Access

Duct Detector Media Ctr rm 304 1 M1-14 Visual

Duct Detector Bldg 200 RTU 11 1 M1-31 Pass

Duct Detector Kitchen RTU 15 1 M1-35 Pass

Duct Detector Foyer RTU 11 1 M1-37 Pass

Duct Detector Foyer RTU 12 1 M1-38 Pass

Duct Detector Cafe RTU 13 1 M1-41 No Access

Duct Detector Cafe RTU 14 1 M1-42 No Access

Duct Detector Office Area 1 M1-44 Pass

Duct Detector Gym 1 M1-60 No Access

Pull Station Bldg 500 West Hall 1 M1-3 Pass

Pull Station Bldg 500 East Hall 1 M1-4 Pass

Pull Station Bldg 300 Corr 1 M1-9 Pass

Pull Station Bldg 300 Art rm 1 M1-10 Pass

Pull Station Bldg 300 Mech rm 1 M1-13 No Access

Pull Station Bldg 300 Media Center 1 M1-15 Pass

Pull Station Gym 1 M1-16 Pass

Pull Station Gym 1 M1-17 Pass

Pull Station Gym 1 M1-18 Pass

Pull Station Bldg 100 Office 1 M1-20 Pass

Pull Station Bldg 100 Corr 1 M1-21 Pass

Pull Station Mech rm 503 behind Kitchen 1 M1-26 Pass

Pull Station Bldg 100 Corr 1 M1-27 Pass

Pull Station Bldg 100 Corr 1 M1-30 Pass

Pull Station Bldg 200 Corr 1 M1-32 Pass

Pull Station Bldg 200 Corr 1 M1-33 Pass

Pull Station Kitchen 1 M1-34 Pass

Pull Station Main Entrance 1 M1-39 Pass

Pull Station Cafe 1 M1-40 Pass

Pull Station Cafe 1 M1-43 Pass

Pull Station Corr 178/300 1 M1-45 Pass

Pull Station Corr 178/300 1 M1-46 Pass

Smoke Detector Bldg 400 @ Fire drs 1 M1-7 Pass

Smoke Detector Bldg 400 @ Fire drs 1 M1-8 Pass

Smoke Detector Cafe Fire drs 1 M1-22 Pass

Smoke Detector Office Corr Fire drs 1 M1-23 Pass

Smoke Detector Bldg 100 @ Fire drs 1 M1-28 Pass

Smoke Detector Bldg 100 @ Fire drs 1 M1-29 Pass

Smoke Detector Fire drs @ rm 178 1 M1-47 Pass

Smoke Detector Fire drs @ rm 178 1 M1-48 Pass

Smoke Detector Fire drs @ rm 301 1 M1-49 Pass

Smoke Detector Fire drs @ rm 301 1 M1-52 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 188: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. 2 Batteries failed load test.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 189: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 190: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

2 0

6 0

2 0

27 0

2 0

Inspector Name : Signature:

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/24/2020

EI1273 / WO #155432

Smoke Detectors FSP 851

Duct Detectors TBD

30040

441 Canton Highway

Maintenance North & Warehouse

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredMech Storage rm 147

Model Name AFP 200 Notifier

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

All-Star Fire, LLC

Power Patrol

Notifier NBG12

FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

AFP 200

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Notifier

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Control Panel

Device

Pass

Pass

D K WomackKen Womack

NotifierHeat Detector FST 851

Other

Batteries

Pullstations

Notifier

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Pass

Pass

EMC Security

Pass

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 191: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.4 Pass

Good (2020) 13.2 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FACP (left)

12v 7ahFACP (right)

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Fire Pump Power Loss

Correct Switching and Operation Verified

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 192: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initiating Device Testing

Device Type Location Floor Address/Zone Results

Smoke Detector Warehouse 1 D1 Pass

Duct Detector Conf rm 103 1 D10 Pass

Duct Detector Conf rm 103 1 D11 Pass

Smoke Detector Filing rm 108 1 D12 Pass

Heat Detector Break rm 106 1 D13 Pass

Heat Detector Plumbing rm 107 1 D14 Pass

Smoke Detector Plumbing rm 107 1 D15 Pass

Smoke Detector Filing rm 108 1 D16 Pass

Smoke Detector Office 112 1 D17 Pass

Smoke Detector Record rm 127 1 D18 Pass

Smoke Detector Record rm 127 1 D19 Pass

Smoke Detector Warehouse 1 D2 Pass

Smoke Detector Corr 117 1 D20 Pass

Smoke Detector Corr 117 1 D21 Pass

Smoke Detector Corr 117 1 D22 Pass

Smoke Detector Meeting 131 1 D23 Pass

Smoke Detector Meeting 131 1 D24 Pass

Smoke Detector Locker rm 144 1 D25 Pass

Smoke Detector Key Storage rm 125 1 D26 Pass

Smoke Detector Carp Storage 146 1 D27 Pass

Smoke Detector Mech Storage rm 147 1 D28 Pass

Smoke Detector Elect rm 143 1 D29 Pass

Smoke Detector Warehouse 1 D3 Pass

Smoke Detector Plumbing rm 141 1 D30 Pass

Smoke Detector Near Rest rooms 1 D31 Pass

Smoke Detector Warehouse 1 D4 Pass

Smoke Detector Office Warehouse 1 D5 Pass

Smoke Detector Corr 105 1 D6 Pass

Smoke Detector Lobby 101 1 D7 Pass

Smoke Detector Lobby 101 1 D8 Pass

Smoke Detector Conf rm 103 1 D9 Pass

Pull Station Warehouse 1 M1 Pass

Pull Station Warehouse 1 M2 Pass

Pull Station Lobby 101 1 M5 Pass

Pull Station HVAC Lead rm 132 1 M6 Pass

Pull Station Van Bay 1 M7 Pass

Pull Station Van Bay 1 M8 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 193: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 194: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 195: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 15 2

38 14

63 0

24 0

264 35

198 0

3 1

Inspector Name : Signature:

Heat Detector Notifier FST-851

30024

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/31/2020

EI1273 / WO# 155448

Innovair

Batteries

Pullstations

NotifierSmoke Detectors FSP-851

Duct Detectors System Sensor

Pass

805 Nichols Road

Lambert High School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name NFS2-3030DNotifier

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

All-Star Fire, LLC

Power Patrol

Notifier NBG-12LX

FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

3030

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Notifier

Manufacturer

Ground Faults Detected by Control Panel

Suwanee

Notifier FCPS-24FS8

Control Panel

Device

EMC

D K WomackKen Womack

NotifierVoice Evac Fire Voice 25/50

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Pass

Pass

Are Lamps and Displays Operating Properly

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 196: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Poor (2019) 13 Fail

Poor (2019) 13.3 Fail

Poor (2017) 12.7 Fail

Poor (2017) 12.9 Fail

Poor (2017) 13 Pass

Poor (2017) 13.2 Pass

Poor (2017) 12.7 Fail

Poor (2017) 12.9 Fail

Poor (2017) 13 Pass

Poor (2017) 13 Pass

Poor (2017) 0 Fail

Poor (2017) 0 Fail

Poor (2017) 13.1 Pass

Poor (2017) 13.1 Pass

Poor (2017) 13 Pass

Poor (2017) 13.2 Pass

Poor (2017) 13.1 Pass

Poor (2017) 13 Pass

Poor (2017) 13.1 Pass

Poor (2017) 13.1 Pass

Poor (2017) 12.9 Fail

Poor (2017) 13 Fail

Fair (2018) 13.5 Pass

Fair (2018) 13.5 Pass

Fair (2017) 13.1 Pass

Fair (2017) 13.1 Pass

Fair (2017) 13.1 Pass

Fair (2017) 13.3 Pass

Poor (2017) 0 Fail

Poor (2017) 0 Fail

Poor (2017) 12.9 Fail

Poor (2017) 12.9 Fail

Fair (2017) 13.3 Pass

12v 7ah

12v 7ah

12v 7ah

FCPS (left) #15 rm 2841

FCPS (right) #15 rm 2841

Voice Evac (left) Auditorium

12v 7ah

12v 7ah

12v 7ah

12v 7ah

FCPS (right) #13 rm 2144

FCPS (left) #14 rm 2153

FCPS (left) #14 rm 2153

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

FCPS (left) #11 rm 2106

FCPS (right) #11 rm 2106

FCPS (left) #12 rm 2245

FCPS (left) #13 rm 2144

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

12v 7ah

FCPS (left) #7 rm 1721

FCPS (right) #7 rm 1721

FCPS (left) #8 rm 1153

FCPS (right) #8 rm 1153

FCPS (left) #9 rm 1153

FCPS (right) #9 rm 1153

FCPS (left) #10 rm 1845

FCPS (right) #10 rm 1845

FCPS (right) #12 rm 2245

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 1404

FCPS (right) #2 rm 1404

FCPS (left) #3 rm 1123

FCPS (right) #3 rm 1123

12v 7ah

12v 7ah

12v 7ah

FCPS (right) #1 rm 1404

FCPS (left) #1 rm 1404

FACP (left)

12v 18ahFACP (right)

12v 18ah

12v 7ah

FCPS (right) #4 rm 1536

Location

Battery Testing

Size

12v 7ah

12v 7ah

FCPS (right) #5 rm 1616

FCPS (left) #4 rm 1536

FCPS (left) #5 rm 1616

FCPS (left) #6 rm 1138

FCPS (right) #6 rm 1138

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 197: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Fair (2017) 13.3 Pass

Fair (2017) 13.3 Pass

Fair (2017) 13.3 Pass

Fair (2017) 13.1 Pass

Fair (2017) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Pass

N/A

N/A

Fail

N/A

N/A

Voice Evac (right) Gym

12v 7ahVoice Evac (right) Auditorium

Voice Evac (left) Gym

Voice Evac (left) Cafe rm 1614

Voice Evac (right) Cafe rm 1614

12v 7ah

12v 7ah

12v 7ah

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Interface Equipment

Generator In Auto Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

Fire Pump Power Loss

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 198: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Duct Detector Construction rm 1425 1 L1D007 Visual

Duct Detector Kitchen 1 L1D012 Visual

Duct Detector Drama Office rm 1411 1 L1D018 No Access

Duct Detector Storage rm 1421 1 L1D022 Visual

Duct Detector Storage rm 1107 1 L1D033 Visual

Duct Detector Vestibule rm 1509 1 L1D048 Visual

Duct Detector Storage rm 1525 1 L1D053 Visual

Heat Detector Construction rm 1425 1 L1D001 Visual

Heat Detector Storage rm 1437 1 L1D003 Visual

Heat Detector Coperssion rm 1436 1 L1D005 Visual

Heat Detector Construction rm 1435 1 L1D006 Visual

Heat Detector Elect rm 1541 1 L1D015 Visual

Heat Detector Elect rm 1419 1 L1D016 Visual

Heat Detector Storage rm 1417 1 L1D017 Visual

Heat Detector Storage rm 1421 1 L1D021 Visual

Heat Detector Cat Walk 1 L1D028 Visual

Heat Detector Elect rm 1408 1 L1D034 Visual

Heat Detector Elev Mach rm 1113 1 L1D038 Visual

Heat Detector Mech rm 1119 1 L1D042 Visual

Heat Detector Custodian rm 1121 1 L1D043 Visual

Heat Detector Elect rm 1123 1 L1D044 Visual

Heat Detector Storage rm 1529 1 L1D049 Visual

Heat Detector IDF rm 1112 1 L1D057 Visual

Heat Detector Elect rm 1114 1 L1D058 Visual

Heat Detector Mech rm 1206 1 L1D067 Visual

Heat Detector Mech rm 1207 1 L1D068 Visual

Heat Detector Mech rm 1214 1 L1D073 Visual

Heat Detector Mech rm 1215 1 L1D074 Visual

Heat Detector Mech rm 1218 1 L1D075 Visual

Heat Detector Mech rm 1131 1 L1D084 Visual

Heat Detector Elect rm 1607 1 L1D090 Visual

Heat Detector Mech rm 1609 1 L1D091 Visual

Heat Detector Elect rm 1530 1 L1D094 Visual

Heat Detector Mech rm 1534 1 L1D096 Visual

Heat Detector Elect rm 1536 1 L1D097 Visual

Heat Detector Mech rm 1 L1D098 Not Found

Heat Detector Professional Food rm 1617 1 L1D099 Visual

Heat Detector Linen Storage rm 1621 1 L1D100 Visual

Heat Detector Custodian rm 1629 1 L1D101 Visual

Heat Detector Mech rm 1623 1 L1D102 Visual

Heat Detector Family Consumer. 1625 1 L1D103 Visual

Heat Detector Pantry rm 1619 1 L1D104 Visual

Heat Detector Family Consumer. 1625 1 L1D105 Visual

Heat Detector Mech rm 1304 1 L1D107 Visual

Heat Detector Mech rm 1305 1 L1D110 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 199: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector Mech rm 1313 1 L1D112 Visual

Heat Detector Mech rm 1317 1 L1D113 Visual

Heat Detector Mech rm 1312 1 L1D116 Visual

Heat Detector Mech rm 1251 1 L1D117 Visual

Heat Detector Mech rm 1254 1 L1D118 Visual

Heat Detector Elect rm 1241 1 L1D124 Visual

Heat Detector IDF rm 1239 1 L1D125 Visual

Heat Detector Custodian rm 1233 1 L1D126 Visual

Heat Detector Mech rm 1244 1 L1D127 Visual

Heat Detector Mech rm 1416 1 L1D128 Visual

Heat Detector Storage rm 1412 1 L1D129 Visual

Heat Detector Kiln 1 L1D130 Visual

Heat Detector No Discription 1 L1D153 Not Found

Heat Detector No Discription 1 L1D151 Not Found

Pull Station Construction rm 1435 1 L1M001 Pass

Pull Station Auditorium Stage 1415 1 L1M010 Pass

Pull Station Auditorium Stage 1415 1 L1M012 Pass

Pull Station Main Entrance 1 L1M016 Pass

Pull Station Main Entrance 1 L1M017 Pass

Pull Station Main Entrance 1 L1M019 Not Found

Pull Station Near Art Lab 1420 1 L1M020 Not Found

Pull Station Near Art Lab 1420 1 L1M021 Pass

Pull Station Art Lab rm 1551 1 L1M022 Pass

Pull Station No Discription 1 L1M031 Pass

Pull Station Corr 1200 1 L1M036 Pass

Pull Station Corr 1300 1 L1M037 Pass

Pull Station Corr 1300 1 L1M038 Pass

Pull Station Corr 1100 1 L1M039 Pass

Pull Station Corr 1100 1 L1M040 Pass

Pull Station Family Consumer. 1625 1 L1M047 Not Found

Pull Station Business Education 1545 1 L1M050 Pass

Pull Station Business Education 1546 1 L1M051 Pass

Pull Station Corr 1500 1 L1M052 Pass

Pull Station No Discription 1 L1M066 Pass

Smoke Detector Construction rm 1435 1 L1D004 Not Found

Smoke Detector Corr 1400 1 L1D008 Pass

Smoke Detector Art Lab rm 1420 1 L1D009 Pass

Smoke Detector Art Lab rm 1551 1 L1D010 Pass

Smoke Detector Corr @ rm 1545 1 L1D011 Pass

Smoke Detector Print rm 1545 1 L1D013 Pass

Smoke Detector IDF rm 1547 1 L1D014 No Access

Smoke Detector Auditorium Stage 1 L1D019 No Access

Smoke Detector Auditorium Stage 1 L1D020 No Access

Smoke Detector Storage rm 1408 1 L1D023 Not Found

Smoke Detector Auditorium 1403 1 L1D024 No Access

Smoke Detector Auditorium 1403 1 L1D025 No Access

Smoke Detector Auditorium 1403 1 L1D026 No Access

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 200: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Auditorium 1403 1 L1D027 Pass

Smoke Detector Control rm 1406 1 L1D029 Not Found

Smoke Detector Smoke drs 1403 1 L1D030 Pass

Smoke Detector Smoke drs 1403 1 L1D031 Fail

Smoke Detector Storage rm 1107 1 L1D032 Not Found

Smoke Detector Smoke drs 1400 1 L1D035 Pass

Smoke Detector Smoke drs 1400 1 L1D036 Pass

Smoke Detector Elev Mach rm 1113 1 L1D037 Pass

Smoke Detector Auditorium 1403 1 L1D039 No Access

Smoke Detector Auditorium 1403 1 L1D040 Pass

Smoke Detector Storage rm 1101 1 L1D041 Not Found

Smoke Detector Smoke drs 1500 1 L1D045 Pass

Smoke Detector Smoke drs 1500 1 L1D046 Pass

Smoke Detector Storage rm 1533 1 L1D047 Pass

Smoke Detector Library 1521 1 L1D050 Pass

Smoke Detector Storage rm 1523 1 L1D051 Not Found

Smoke Detector Storage rm 1525 1 L1D052 Not Found

Smoke Detector Storage rm 1527 1 L1D054 Pass

Smoke Detector Elev Lobby 1 L1D055 Pass

Smoke Detector Print rm 1116 1 L1D056 Pass

Smoke Detector Storage rm 1205 1 L1D059 Pass

Smoke Detector Smoke drs 1200 1 L1D060 Pass

Smoke Detector Smoke drs 1200 1 L1D061 Pass

Smoke Detector Smoke drs 1200 1 L1D062 Pass

Smoke Detector Smoke drs 1200 1 L1D063 Pass

Smoke Detector Science Lab rm 1202 1 L1D065 Pass

Smoke Detector Storage rm 1204 1 L1D066 Pass

Smoke Detector Science Storage rm 1209 1 L1D069 Fail

Smoke Detector Science Lab rm 1203 1 L1D070 Fail

Smoke Detector Science Lab rm 1211 1 L1D071 Fail

Smoke Detector Science Lab rm 1210 1 L1D072 Fail

Smoke Detector Smoke drs 1200 1 L1D076 Pass

Smoke Detector Smoke drs 1200 1 L1D077 Pass

Smoke Detector Custodial rm 1126 1 L1D078 No Access

Smoke Detector Science Lab rm 1302 1 L1D079 Pass

Smoke Detector Smoke drs 1300 1 L1D080 Pass

Smoke Detector Smoke drs 1300 1 L1D081 Pass

Smoke Detector Smoke drs 1300 1 L1D082 Pass

Smoke Detector Smoke drs 1300 1 L1D083 Pass

Smoke Detector Mech rm 1603 1 L1D085 No Access

Smoke Detector Smoke drs 1100F 1 L1D086 Pass

Smoke Detector Smoke drs 1100F 1 L1D087 Pass

Smoke Detector Smoke drs 1140 1 L1D088 Pass

Smoke Detector Smoke drs 1140 1 L1D089 Pass

Smoke Detector Storage rm 1135 1 L1D092 Pass

Smoke Detector Storage PC Tech Elect rm 1530 1 L1D093 Not Found

Smoke Detector Storage rm 1532 1 L1D095 Not Found

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 201: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Science Storage rm 1209 1 L1D106 Not Found

Smoke Detector Science Lab rm 1303 1 L1D108 Pass

Smoke Detector Science Storage rm 1307 1 L1D109 Fail

Smoke Detector Science Lab rm 1309 1 L1D111 Pass

Smoke Detector Science Lab rm 1308 1 L1D114 Pass

Smoke Detector Business Lab rm 1310 1 L1D115 Fail

Smoke Detector Smoke drs 1300 1 L1D119 Pass

Smoke Detector Smoke drs 1300 1 L1D120 Pass

Smoke Detector Print rm 1243 1 L1D121 Pass

Smoke Detector Corr 1230 1 L1D122 Pass

Smoke Detector Storage rm 1245 1 L1D123 Pass

Smoke Detector Storage rm 1555 1 L1D131 Pass

Smoke Detector No Discription 1 L1D134 Pass

Smoke Detector No Discription 1 L1D135 Pass

Smoke Detector No Discription 1 L1D140 Not Found

Smoke Detector No Discription 1 L1D136 Pass

Smoke Detector No Discription 1 L1D133 Pass

Smoke Detector No Discription 1 L1D132 Pass

Smoke Detector No Discription 1 L1D150 Not Found

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 202: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Duct Detector Food Court 1612 1 L2D021 No Access

Duct Detector Food Court 1612 1 L2D022 No Access

Duct Detector Food Court 1612 1 L2D026 No Access

Duct Detector Serving Area 1618 1 L2D029 Pass

Duct Detector Serving Area 1618 1 L2D034 Pass

Duct Detector Kitchen Prep 1620 1 L2D035 Pass

Heat Detector Student Records 1 L2D005 Visual

Heat Detector Stor rm 1084 1 L2D006 Visual

Heat Detector Vault rm 1008 1 L2D011 Visual

Heat Detector Reference rm 1009 1 L2D012 Visual

Heat Detector Elect rm 1138 1 L2D014 Visual

Heat Detector Chair Stor rm 1614 1 L2D019 Visual

Heat Detector Chair Stor rm 1614 1 L2D024 Visual

Heat Detector Serving Area 1618 1 L2D030 Visual

Heat Detector Dishwashing rm 1642 1 L2D031 Visual

Heat Detector Kitchen Prep rm 1620 1 L2D036 Visual

Heat Detector Custodian rm 1624 1 L2D037 Visual

Heat Detector Utility rm 1522 1 L2D038 Visual

Heat Detector Kitchen Prep 1620 1 L2D040 Visual

Heat Detector Dry Stor 1638 1 L2D041 Visual

Heat Detector Can Wash 1644 1 L2D043 Visual

Heat Detector IDF 1124 1 L2D048 Visual

Heat Detector Mech rm 1806 1 L2D052 Visual

Heat Detector Mech rm 1809 1 L2D053 Visual

Heat Detector Mech rm 1812 1 L2D054 Visual

Heat Detector Mech rm 1816 1 L2D055 Visual

Heat Detector Mech rm 1815 1 L2D056 Visual

Heat Detector Mech rm 1832 1 L2D060 Visual

Heat Detector Book Stor rm 1819 1 L2D062 Visual

Heat Detector Mech rm 1836 1 L2D064 Visual

Heat Detector Custodian rm 1837 1 L2D068 Visual

Heat Detector IDF rm 1843 1 L2D073 Visual

Heat Detector Elect rm 1845 1 L2D075 Visual

Heat Detector Mech rm 1850 1 L2D078 Visual

Heat Detector Mech rm 1915 1 L2D080 Visual

Heat Detector Mech rm 1919 1 L2D083 Visual

Heat Detector Mech rm 1913 1 L2D085 Visual

Heat Detector Mech rm 1910 1 L2D086 Visual

Heat Detector Mech rm 1905 1 L2D087 Visual

Heat Detector Mech rm 1904 1 L2D088 Visual

Heat Detector Custodian rm 1168 1 L2D089 Visual

Heat Detector Elect rm 1901 1 L2D092 Visual

Heat Detector Book Stor rm 1172 1 L2D093 Visual

Heat Detector Stor rm 1772 1 L2D094 Visual

Heat Detector Custodian rm 1733 1 L2D095 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 203: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector Elect rm 1153 1 L2D096 Visual

Heat Detector Stor rm 1737 1 L2D097 Visual

Heat Detector Stor rm 1737 1 L2D098 Visual

Heat Detector Stor Health rm 1702 1 L2D100 Visual

Heat Detector Stor Health rm 1706 1 L2D101 Visual

Heat Detector Mech rm 1704 1 L2D102 Visual

Heat Detector Elev Mach rm 1739 1 L2D105 Visual

Heat Detector Custodian rm 1745 1 L2D106 Visual

Heat Detector Mech rm 1747 1 L2D107 Visual

Heat Detector Stor rm 1749 1 L2D108 Visual

Heat Detector Custodian rm 1716 1 L2D109 Visual

Heat Detector Main Elect rm 1721 1 L2D113 Visual

Heat Detector Main Elect rm 1721 1 L2D114 Visual

Heat Detector Main Elect rm 1717 1 L2D115 Visual

Heat Detector Main Elect rm 1717 1 L2D116 Visual

Heat Detector Boys Locker rm 1751 1 L2D117 Visual

Heat Detector Girls Locker rm 1757 1 L2D118 Visual

Heat Detector Elect rm 1725 1 L2D121 Visual

Heat Detector Laundry rm 1766 1 L2D122 Visual

Heat Detector Stor rm 1727 1 L2D123 Visual

Heat Detector Mech rm 1803 1 L2D124 Visual

Heat Detector Serving Area 1618 1 L2D125 Visual

Pull Station Main Lobby 1 L2M001 Pass

Pull Station Main Lobby 1 L2M002 Pass

Pull Station Infor Resources rm 1142 1 L2M005 Pass

Pull Station Corr 1 L2M013 Pass

Pull Station Kitchen 1 L2M016 Pass

Pull Station Corr 1710 1 L2M017 Pass

Pull Station Corr @ Stair 5 1 L2M018 Pass

Pull Station Corr 1800 1 L2M020 Pass

Pull Station Corr 1900 1 L2M023 Pass

Pull Station Corr @ rm 1174 1 L2M024 Pass

Pull Station Aux Gym 1170 1 L2M025 Pass

Pull Station Lobby @ Aux Gym 1 L2M027 Pass

Pull Station Stair 8 1 L2M033 Pass

Pull Station Stair 9 1 L2M034 Pass

Pull Station Stair 9 1 L2M035 Pass

Pull Station Corr 1720 1 L2M036 Pass

Pull Station Corr 1720 1 L2M037 Pass

Pull Station Stair 8 1 L2M038 Pass

Pull Station Main Elect rm 1721 1 L2M040 Pass

Pull Station Main Elect rm 1717 1 L2M041 Pass

Pull Station No Discription 1 L2M003 Pass

Pull Station No Discription 1 L2M070 Pass

Smoke Detector ISS rm 1073 1 L2D001 Pass

Smoke Detector Corr 1054 1 L2D002 Pass

Smoke Detector Stor rm 1067 1 L2D003 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 204: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Corr 1054 1 L2D004 Pass

Smoke Detector Clinic 1082 1 L2D007 Visual

Smoke Detector Corr @ Smoke drs 1050 1 L2D008 Pass

Smoke Detector Corr @ Smoke drs 1050 1 L2D009 Pass

Smoke Detector Over FACP 1 L2D010 Pass

Smoke Detector Stor rm 1007 1 L2D013 Pass

Smoke Detector Corr 1140 1 L2D016 Pass

Smoke Detector Corr @ Smoke drs 1700 1 L2D017 Pass

Smoke Detector Corr @ Smoke drs 1700 1 L2D018 Pass

Smoke Detector Food Court 1612 1 L2D020 No Access

Smoke Detector Food Court 1612 1 L2D023 No Access

Smoke Detector Food Court 1612 1 L2D025 No Access

Smoke Detector Food Court 1612 1 L2D027 No Access

Smoke Detector Food Court 1612 1 L2D028 No Access

Smoke Detector Corr @ Smoke drs 1700 1 L2D032 Pass

Smoke Detector Corr @ Smoke drs 1700 1 L2D033 Pass

Smoke Detector Closet 1628 1 L2D039 Not Found

Smoke Detector Bulk Stor 17 1 L2D042 Pass

Smoke Detector Corr @ Smoke drs 1800 1 L2D044 Pass

Smoke Detector Corr @ Smoke drs 1800 1 L2D045 Pass

Smoke Detector Corr @ Smoke drs 1800 1 L2D046 Pass

Smoke Detector Corr @ Smoke drs 1800 1 L2D047 Pass

Smoke Detector Print Closet rm 1156 1 L2D049 Fail

Smoke Detector Corr @ Smoke drs 1800 1 L2D050 Fail

Smoke Detector Corr @ Smoke drs 1800 1 L2D051 Fail

Smoke Detector Book Stor rm 1820 1 L2D057 Pass

Smoke Detector Corr 1830 1 L2D061 Pass

Smoke Detector Spec Education 01 rm 1834 1 L2D063 Fail

Smoke Detector Closet 1840 1 L2D065 Pass

Smoke Detector Spec Education MT/MO rm 1838 1 L2D066 Pass

Smoke Detector Corr 1830 1 L2D067 Pass

Smoke Detector Corr 1830 1 L2D069 Pass

Smoke Detector Spec Education Living rm 1844 1 L2D070 Pass

Smoke Detector Corr 1830 1 L2D071 Pass

Smoke Detector Print rm 1847 1 L2D072 Pass

Smoke Detector Stor rm 1849 1 L2D074 Pass

Smoke Detector Corr 1830 1 L2D076 Pass

Smoke Detector Book Stor rm 1851 1 L2D077 Pass

Smoke Detector Spec Education S/P rm 1846 1 L2D079 Pass

Smoke Detector Corr 1830 1 L2D081 Pass

Smoke Detector Corr @ Smoke drs 1900 1 L2D082 Pass

Smoke Detector Corr @ Smoke drs 1900 1 L2D084 Fail

Smoke Detector Corr @ Smoke drs 1900 1 L2D090 Pass

Smoke Detector Corr @ Smoke drs 1900 1 L2D091 Pass

Smoke Detector Elev rm 1151 1 L2D099 Pass

Smoke Detector Elev Mach rm 1739 1 L2D103 Pass

Smoke Detector Elect rm 1741 1 L2D104 Fail

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 205: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector IDF rm 1718 1 L2D110 Pass

Smoke Detector Smoke drs @ Stair 8 1 L2D111 Pass

Smoke Detector Smoke drs @ Stair 8 1 L2D112 Pass

Smoke Detector Smoke drs @ Stair 9 1 L2D119 Pass

Smoke Detector Smoke drs @ Stair 9 1 L2D120 Pass

Smoke Detector No Discription 1 L2D140 Not Found

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 206: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating device Testing

Device Type Location Floor Address/Zone Results

Duct Detector Corr 2200 2 L3D021 Pass

Duct Detector Corr 2300 2 L3D035 Visual

Duct Detector Main Gym 2 L3D076 Visual

Duct Detector Main Gym 2 L3D077 Visual

Duct Detector Main Gym 2 L3D079 Visual

Duct Detector Aux Gym 1 L3D083 Visual

Duct Detector Main Gym 2 L3D085 Visual

Duct Detector Main Gym 2 L3D087 Visual

Duct Detector Main Gym 2 L3D089 Visual

Duct Detector Main Gym 2 L3D091 Visual

Duct Detector Aux Gym 1 L3D098 Visual

Heat Detector Elevator Shaft 2 L3D002 Visual

Heat Detector IDF rm 2104 2 L3D006 Visual

Heat Detector Elect rm 2106 2 L3D007 Visual

Heat Detector Mech rm 2207 2 L3D015 Visual

Heat Detector Mech rm 2206 2 L3D019 Visual

Heat Detector Mech rm 2214 2 L3D022 Visual

Heat Detector Mech rm 2215 2 L3D023 Visual

Heat Detector Mech rm 2218 2 L3D024 Visual

Heat Detector Mech rm 2332 2 L3D027 Visual

Heat Detector Mech rm 2304 2 L3D032 Visual

Heat Detector Mech rm 2313 2 L3D038 Visual

Heat Detector Mech rm 2317 2 L3D039 Visual

Heat Detector Book Stor rm 2252 2 L3D042 Visual

Heat Detector Mech rm 2250 2 L3D043 Visual

Heat Detector Mech rm 2320 2 L3D044 Visual

Heat Detector Stor rm 2318 2 L3D045 Not Found

Heat Detector Elect rm 2245 2 L3D047 Visual

Heat Detector IDF rm 2243 2 L3D048 Visual

Heat Detector Custodian 2237 2 L3D051 Visual

Heat Detector MDF rm 2008 2 L3D061 Visual

Heat Detector Elect rm 2144 2 L3D067 Visual

Heat Detector Elect rm 2153 2 L3D071 Visual

Heat Detector Elevator Shaft 2 L3D073 Visual

Heat Detector Main Gym 2 L3D075 Visual

Heat Detector Main Gym 2 L3D078 Visual

Heat Detector Main Gym 2 L3D080 Visual

Heat Detector Aux Gym 1 L3D082 Visual

Heat Detector Aux Gym 1 L3D084 Visual

Heat Detector Main Gym 2 L3D086 Visual

Heat Detector Main Gym 2 L3D088 Visual

Heat Detector Main Gym 2 L3D090 Visual

Heat Detector Roof Access rm 2775 2 L3D094 Visual

Heat Detector Stor rm 2767 2 L3D095 Visual

Heat Detector Mech rm 2769 2 L3D096 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 207: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector Aux Gym 1 L3D097 Visual

Heat Detector Aux Gym 1 L3D099 Visual

Heat Detector Main Gym 2 L3D101 Visual

Heat Detector Main Gym 2 L3D102 Visual

Heat Detector Main Gym 2 L3D104 Visual

Heat Detector Stor rm 2745 2 L3D108 Visual

Heat Detector Smoke drs Corr 2800 2 L3D111 Visual

Heat Detector Mech rm 2803 2 L3D112 Visual

Heat Detector Smoke drs Corr 2800 2 L3D116 Visual

Heat Detector Mech rm 2806 2 L3D117 Visual

Heat Detector Mech rm 2809 2 L3D118 Visual

Heat Detector Mech rm 2812 2 L3D119 Visual

Heat Detector Mech rm 2815 2 L3D120 Visual

Heat Detector Mech rm 2816 2 L3D122 Visual

Heat Detector Concession rm 2163 2 L3D125 Visual

Heat Detector Mech rm 2904 2 L3D128 Visual

Heat Detector Stor rm 2165 2 L3D129 Visual

Heat Detector Elect rm 2901 2 L3D130 Visual

Heat Detector Mech rm 2904 2 L3D131 Visual

Heat Detector Mech rm 2910 2 L3D132 Visual

Heat Detector Mech rm 2913 2 L3D133 Visual

Heat Detector Mech rm 2916 2 L3D135 Visual

Heat Detector Mech rm 2917 2 L3D136 Visual

Heat Detector Mech rm 2844 2 L3D140 Visual

Heat Detector Elect rm 2841 2 L3D143 Visual

Heat Detector IDF rm 2839 2 L3D144 Visual

Heat Detector Custodian 2833 2 L3D145 Visual

Heat Detector Mech rm 2834 2 L3D146 Visual

Heat Detector Mech rm 2307 2 L3D149 Visual

Heat Detector Book Stor rm 2820 2 L3D151 Visual

Pull Station Stair 1 @ rm 2201 2 L3M002 Pass

Pull Station Corr 2200 2 L3M004 Pass

Pull Station Stair 2 @ rm 2221 2 L3M006 Pass

Pull Station Stair 3 @ rm 2301 2 L3M007 Pass

Pull Station Corr 2300 2 L3M008 Pass

Pull Station Stair 4 @ rm 2321 2 L3M010 Pass

Pull Station Stair 5 @ rm 2801 2 L3M014 Pass

Pull Station Stair 6 @ rm 2821 2 L3M016 Pass

Pull Station Stair 7 @ rm 2921 2 L3M018 Pass

Pull Station Corr 2150 2 L3M020 Pass

Pull Station Gym 2 L3M021 Pass

Pull Station Main Gym 1 L3M023 Pass

Pull Station Main Gym 1 L3M024 Pass

Pull Station Stair 9 1f L3M029 Pass

Pull Station Main Gym 1 L3M034 Pass

Pull Station Stair 8 @ rm 2763 2 L3M039 Pass

Pull Station Gym 2 L3M040 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 208: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Elevator Shaft 2 L3D001 Visual

Smoke Detector Elev Lobby 1 L3D003 Pass

Smoke Detector Corr @ Smoke drs 2100 2 L3D004 Pass

Smoke Detector Print rm 2108 2 L3D005 Pass

Smoke Detector Corr @ Smoke drs 2200 2 L3D008 Pass

Smoke Detector Corr @ Smoke drs 2200 2 L3D009 Pass

Smoke Detector Corr @ Smoke drs 2200 2 L3D010 Pass

Smoke Detector Corr @ Asst Principal Office 2 L3D011 Pass

Smoke Detector Corr @ Smoke drs 2200 2 L3D012 Pass

Smoke Detector Physical Science Lab 2203 2 L3D013 Pass

Smoke Detector Science Stor rm 2209 2 L3D014 Pass

Smoke Detector Applied Science Lab 2211 2 L3D016 Pass

Smoke Detector Science Lab 2202 2 L3D017 Pass

Smoke Detector Science Stor rm 2208 2 L3D018 Fail

Smoke Detector Science Lab 2210 2 L3D020 Pass

Smoke Detector Smoke drs @ Stair 2 2 L3D025 Pass

Smoke Detector Smoke drs @ Stair 2 2 L3D026 Pass

Smoke Detector Science Stor rm 2205 2 L3D028 Pass

Smoke Detector Custodian 2118 2 L3D029 Not Found

Smoke Detector Science Lab 2302 2 L3D030 Pass

Smoke Detector Science Lab 2306 2 L3D031 Pass

Smoke Detector Science Lab 2308 2 L3D033 Pass

Smoke Detector Exam rm 2314 2 L3D034 Pass

Smoke Detector Health Lab 2310 2 L3D036 Pass

Smoke Detector Health Lab 2310 2 L3D037 Pass

Smoke Detector Smoke drs @ Stair 4 2 L3D040 Pass

Smoke Detector Smoke drs @ Stair 4 2 L3D041 Pass

Smoke Detector Stor rm 2349 2 L3D046 Not Found

Smoke Detector Print rm 2247 2 L3D049 Pass

Smoke Detector Corr 2230 2 L3D050 Pass

Smoke Detector Corr @ Smoke drs 2300 2 L3D052 Pass

Smoke Detector Corr @ Smoke drs 2300 2 L3D053 Pass

Smoke Detector Corr @ Smoke drs 2300 2 L3D054 Pass

Smoke Detector Corr @ Smoke drs 2300 2 L3D055 Pass

Smoke Detector Corr @ Smoke drs 2140 2 L3D056 Pass

Smoke Detector Corr @ Smoke drs 2140 2 L3D057 Fail

Smoke Detector Corr 2140 2 L3D058 Pass

Smoke Detector Reading rm 2000 2 L3D059 Pass

Smoke Detector A/V Stor rm 2001 2 L3D060 Pass

Smoke Detector Work rm 2004 2 L3D062 Fail

Smoke Detector Reading rm 2000 2 L3D063 Fail

Smoke Detector Lobby Below 2 L3D064 Not Found

Smoke Detector Reading rm 2000 2 L3D065 Pass

Smoke Detector Reading rm 2000 2 L3D066 Pass

Smoke Detector Corr 2140 2 L3D068 Fail

Smoke Detector Corr @ Smoke drs 2140 2 L3D069 Pass

Smoke Detector Corr @ Smoke drs 2140 2 L3D070 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 209: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Elev Lobby 2 L3D072 Pass

Smoke Detector Elevator Shaft 2 L3D074 Visual

Smoke Detector Gym Lobby 2 L3D081 Pass

Smoke Detector Smoke drs @ Stair 9 2 L3D092 Pass

Smoke Detector Smoke drs @ Stair 9 2 L3D093 Pass

Smoke Detector Main Gym 2 L3D100 Visual

Smoke Detector Main Gym 2 L3D103 Visual

Smoke Detector Main Gym 2 L3D105 Visual

Smoke Detector Smoke drs @ Stair 8 2 L3D106 Pass

Smoke Detector Smoke drs @ Stair 8 2 L3D107 Pass

Smoke Detector Smoke drs @ Stair 5 2 L3D109 Pass

Smoke Detector Smoke drs @ Stair 5 2 L3D110 Pass

Smoke Detector Smoke drs 2800 Corr 2 L3D111 Pass

Smoke Detector IDF rm 2154 2 L3D113 Not Found

Smoke Detector Print rm 2156 2 L3D114 Fail

Smoke Detector Corr 2150 2 L3D115 Pass

Smoke Detector Corr 2800 2 L3D121 Fail

Smoke Detector Smoke drs @ Stair 6 2 L3D123 Pass

Smoke Detector Smoke drs @ Stair 6 2 L3D124 Pass

Smoke Detector Corr @ Smoke drs 2900 2 L3D126 Pass

Smoke Detector Corr @ Smoke drs 2900 2 L3D127 Pass

Smoke Detector Corr 2900 2 L3D134 Fail

Smoke Detector Smoke drs @ Stair 7 2 L3D137 Pass

Smoke Detector Smoke drs @ Stair 7 2 L3D138 Pass

Smoke Detector Book Stor rm 2847 2 L3D139 Pass

Smoke Detector Corr 2830 2 L3D141 Pass

Smoke Detector Print rm 2843 2 L3D142 Pass

Smoke Detector Gym Lobby 2 L3D147 Visual

Smoke Detector Science Stor rm 2305 2 L3D148 Pass

Smoke Detector Science Lab 2309 2 L3D150 Pass

Smoke Detector Science Lab 2303 2 L3D152 Pass

Smoke Detector Health Stor 2 L3D156 Pass

Smoke Detector Health OCC Left 2 L3D155 Pass

Smoke Detector Health Kitchen 2 L3D158 Pass

Smoke Detector Health Right 2 L3D159 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 210: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

initating Device Testing

Device Type Location Floor Address/Zone Results

Heat Detector Mech rm 1890 1 L4D019 Visual

Heat Detector Mech rm 1893 1 L4D022 Visual

Heat Detector Lab Storage rm 1895A 1 L4D023 Visual

Heat Detector Room 2882 2 L4D046 Not Found

Heat Detector Corr 2880 2 L4D036 Not Found

Heat Detector Storage rm 1861 1 L4D003 Visual

Heat Detector Storage rm 1861 1 L4D004 Visual

Heat Detector IDF rm 1863B 1 L4D005 Visual

Heat Detector Mech rm 1881 1 L4D008 Visual

Heat Detector Storage 1 L4D010 Not Found

Heat Detector Room 1882 1 L4D015 Not Found

Heat Detector Mech rm 1890 1 L4D019 Visual

Heat Detector Mech rm 1893 1 L4D022 Visual

Heat Detector Lab Storage rm 1895A 1 L4D023 Not Found

Heat Detector Corr 2880 2 L4D036 Not Found

Heat Detector Mech rm 2864 2 L4D038 Visual

Heat Detector Mech rm 2861 2 L4D040 Visual

Heat Detector Computer Lab rm 2881 2 L4D042 Visual

Heat Detector Mech rm 2884 2 L4D045 Visual

Heat Detector IDF rm 2890 2 L4D050 Visual

Heat Detector Mech rm 2891 2 L4D054 Visual

Heat Detector Mech rm 2896 2 L4D058 Visual

Heat Detector No Discription TBD L4D070 Not Found

Heat Detector No Discription TBD L4D096 Not Found

Pull Station Corr 1880 South Exit 1 L4M001 Pass

Pull Station Corr 1880 North Exit 1 L4M002 Pass

Pull Station Stair 10 Exit 1 L4M003 Pass

Pull Station No Discription 1 L4M050 Pass

Smoke Detector Office Corr 1 L4D005 Not Found

Smoke Detector Corr @ rm 2880 2 L4D056 Fail

Smoke Detector Mech rm 2963 2 L4D063 Not Found

Smoke Detector Elect rm 1863A 1 L4D006 Not Found

Smoke Detector Elect rm 1863A 1 L4D007 Not Found

Smoke Detector Corr 1880 1 L4D009 Pass

Smoke Detector Classroom 1862 1 L4D011 Pass

Smoke Detector Classroom 1864 1 L4D012 Fail

Smoke Detector New Wing South Exit 1 L4D013 Fail

Smoke Detector Corr 1880 1 L4D014 Fail

Smoke Detector Classroom 1886 1 L4D016 Pass

Smoke Detector Classroom 1883 1 L4D017 Pass

Smoke Detector Corr 1880 1 L4D018 Pass

Smoke Detector Test Supply rm 1880 1 L4D020 Not Found

Smoke Detector Mech rm 1894 1 L4D024 Not Found

Smoke Detector Classroom 1892 1 L4D025 Fail

Smoke Detector Classroom 1896 1 L4D026 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 211: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Corr 1880 1 L4D027 Fail

Smoke Detector Science Lab 1895 1 L4D028 Pass

Smoke Detector Corr 1880 North Exit 1 L4D029 Fail

Smoke Detector Mech rm 1962 1 L4D030 Not Found

Smoke Detector Storage rm 1963 1 L4D031 Not Found

Smoke Detector Storage rm 1963 1 L4D032 Not Found

Smoke Detector Classroom 1961 1 L4D033 Fail

Smoke Detector Smoke drs 1 L4D034 Pass

Smoke Detector Classroom 2862 2 L4D037 Fail

Smoke Detector Classroom 2866 2 L4D039 Fail

Smoke Detector Corr 2880 2 L4D043 Pass

Smoke Detector Corr 2880 South Exit 2 L4D044 Fail

Smoke Detector Classroom 2886 2 L4D047 Pass

Smoke Detector Corr 2880 2 L4D048 Pass

Smoke Detector Corr 2880 2 L4D049 Pass

Smoke Detector M/E rm 2892 2 L4D051 Visual

Smoke Detector M/E rm 2892 2 L4D052 Pass

Smoke Detector Teacher Break rm 2888 2 L4D053 Pass

Smoke Detector Lab Storage rm 2893A 2 L4D055 Pass

Smoke Detector Corr 2880 2 L4D056 Pass

Smoke Detector Science Lab 2893 2 L4D057 Fail

Smoke Detector Classroom 2884 2 L4D059 Not Found

Smoke Detector Corr 2880 2 L4D061 Fail

Smoke Detector Corr 2880 North Exit 2 L4D062 Fail

Smoke Detector Mech rm 2963 2 L4D063 Not Found

Smoke Detector Storage rm 2965 2 L4D064 Pass

Smoke Detector Storage rm 2965 2 L4D065 Pass

Smoke Detector Classroom 2961 2 L4M066 Pass

Smoke Detector Corr 2880 2 L4M067 Not Found

Smoke Detector No Discription 2 L4D086 Not Found

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 212: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. Door holder near 1600/3000 hall does not work.

2. No voice Evac in Cafeteria.

3. Doors holders on 2nd floor at Gym end of building do not hold doors.

L1D109, L1D115, L2D049, L2D050, L2D051, L2D063, L2D084, L2D104, L3D018, L3D057, L3D062, L3D063,

L3D068, L3D114, L3D121, L3D134, L4D056, L4D012, L4D013, L4D014, L4D025, L4D027, L4D029, L4D033,

L4D037, L4D039, L4D044, L4D057, L4D061, & L4D062.

4. 2 Power supplies fail to charge batteries.

5. The following smoke detectors failed to report to the panel: L1D031, L1D069, L1D070, L1D071, L1D072

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 213: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 214: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 10 0

24 8

28 1

19 13

89 2

1 0

2 0

Inspector Name : Signature:

30024

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/23/2020

EI1273 / WO # 155446

SD 505Duct

Waterflow Potter VSR-F

Batteries

Pullstations

Silent KnightSmoke Detectors Sd505-APS

Duct Detectors Silent Knight

Pass

6205 Old Atlanta Road

John's Creek Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name 5820XLSilent Knight

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC

All-Star Fire, LLC

Power Patrol

Silent Knight Sd500Ps

FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

5820XL

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Silent Knight

Manufacturer

Ground Faults Detected by Control Panel

Suwanee

Are Lamps and Displays Operating Properly

D K WomackKen Womack

Silent KnightVoice Evac SKE 450

Pass

Silent Knight 5495

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 215: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Fail

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Poor (2020) 13.6 Fail

Poor (2020) 13 Fail

Good (2018) 13 Pass

Good (2018) 13.3 Pass

Good (2018) 13.3 Pass

Good (2018) 13 Pass

Good (2020) 13.3 Pass

Good (2020) 13.3 Pass

Good (2018) 13.3 Pass

Good (2018) 13.4 Pass

Good (2018) 13.3 Pass

Good (2018) 13.3 Pass

Good (2018) 13.3 Pass

Good (2018) 13.3 Pass

Poor (2020) 12.9 Fail

Poor (2020) 12.9 Fail

Poor (2020) 12.7 Fail

Poor (2020) 12.9 Fail

Poor (2020) 12.6 Fail

Poor (2020) 12.8 Fail

Good (2020) 13 Pass

Good (2020) 13 Pass

Good (2020) 13.1 Pass

Good (2020) 13.1 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

FCPS (right) #1 rm 1034

FCPS (left) #1 rm 1034

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FCPS (right) #4 rm 1403

FCPS (left) #6 rm 1403

FCPS (right) #6 rm 1403

FCPS (left) #7 rm 2009

FCPS (right) #7 rm 2009

FCPS (left) #8 rm 2009

FCPS (right) #8 rm 2009

FCPS (left) #9 rm 2203

FCPS (right) #9 rm 2203

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 1034

FCPS (right) #2 rm 1034

FCPS (left) #3 rm 1034

FCPS (right) #3 rm 1034

12v 7ah

12v 7ah

12v 7ah

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

FCPS (right) #5 rm 1403

FCPS (left) #4 rm 1403

FCPS (left) #5 rm 1403

Fire Pump Running

FCPS (left) #10 rm 2203

FCPS (right) #10 rm 2203

Voice Evac

Voice Evac

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

12v 7ah

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 216: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Fail

N/A

N/A

Pass

N/A

N/AFM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Interface Equipment

Generator Trouble Generator Trouble Reports to Panel

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 217: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Loop 1 M33

Pull Station Corr 1030 Stair Exit 1 P001 Pass

Pull Station Lobby 1000 Exit 1 P002 Pass

Pull Station Lobby 1000 Exit 1 P003 Pass

Pull Station Corr 1507 Stair Exit 1 P004 Pass

Pull Station Gym 1500 Exit 1 P005 Pass

Pull Station Lunchroom 1400 Exit 1 P006 Pass

Pull Station Storage 1550 Exit 1 P007 Pass

Pull Station Elect rm 1421 Exit 1 P008 Fail

Pull Station Mech rm 1420 Exit 1 P009 Pass

Pull Station Kitchen Exit 1 P010 Pass

Pull Station Boiler rm 1425 Exit 1 P011 Pass

Pull Station Corr 1314 Stair Exit 1 P012 Pass

Pull Station Corr 1314 Lobby Exit 1 P013 Pass

Pull Station Lobby 1300 Exit 1 P014 Pass

Pull Station Lobby 1300 Exit 1 P015 Pass

Pull Station Corr 1204 Lobby Exit 1 P016 Pass

Pull Station Corr 1204 Stair Exit 1 P017 Pass

Pull Station Multi rm 1200 Exit 1 P018 Pass

Pull Station Art Class 1105 Exit 1 P019 Pass

Pull Station Music rm 1103 Exit 1 P020 Pass

Smoke Detector Corr 1030 Stair 1 P021 Pass

Smoke Detector Corr 1030 @ Stair 1 P022 Pass

Smoke Detector Hall @ Principals Office 1 P023 Pass

Smoke Detector Main Office Hall 1 P024 Pass

Smoke Detector Middle of Corr 1030 1 P025 Pass

Smoke Detector Middle of Corr 1030 1 P026 Pass

Duct Detector IHP AD2 above 1020 1 P027 Not Found

Smoke Detector Corr 1030 @ Lobby 1 P028 Pass

Smoke Detector Lobby 1000 1 P029 Pass

Smoke Detector Lobby 1000 1 P030 Pass

Smoke Detector Corr 1100 1 P031 Pass

Smoke Detector Corr 1100 1 P032 Pass

Smoke Detector Lobby 1000 1 P033 Pass

Smoke Detector Lobby 1000 1 P034 Pass

Smoke Detector Lobby 1000 1 P035 Pass

Smoke Detector Lobby 1000 1 P036 Pass

Smoke Detector Corr 1507 @ Lobby 1 P037 Pass

Smoke Detector Elevator #1 Lobby 1 P038 Pass

Smoke Detector Elevator #1 Pit 1 P039 Visual

Heat Detector Elevator #1 Pit 1 P040 Visual

Smoke Detector Elevator #1 Mach rm 1 P041 Pass

Smoke Detector Janitor Closet 1522 1 P042 Pass

Smoke Detector Elect rm 1526 1 P043 Pass

Smoke Detector Corr 1507 @ Stair 1 P044 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 218: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Corr 1507 Stair 1 P045 Pass

Smoke Detector Elect rm 1421 1 P046 Pass

Tamper Switch Riser #1 1 P047 Fail

Flow Switch Riser #1 1 P048 Pass

Duct Detector RTU K1 in Kit supply 1 P049 Fail

Duct Detector RTU K1 in Kit return 1 P050 Fail

Ansul Kitchen Hood 1 P051 Visual

Smoke Detector Corr 1314 Stair 1 P052 Pass

Smoke Detector Corr 1314 @ Stair 1 P053 Pass

Smoke Detector Elect rm 1403 1 P054 Fail

Duct Detector RTU U2 return 1 P055 No Access

Duct Detector RTU U2 supply 1 P056 No Access

Duct Detector RTU U3 supply 1 P057 No Access

Duct Detector RTU U3 return 1 P058 No Access

Smoke Detector Lunch rm Corr Exit 1 P059 No Access

Smoke Detector Elect rm 1034 1 P060 Pass

Smoke Detector Corr 1100 Middle 1 P061 Pass

Smoke Detector Corr 1100 Middle 1 P062 Pass

Smoke Detector Lunch rm Lobby Exit 1 P063 Pass

Smoke Detector Lunch rm Lobby Exit 1 P064 Pass

Smoke Detector Corr 1314 @ Lobby 1 P065 Pass

Smoke Detector Lobby 1300 1 P066 Pass

Smoke Detector Lobby 1300 1 P067 Pass

Smoke Detector Lobby 1300 1 P068 Pass

Smoke Detector Lobby 1300 1 P069 Pass

Smoke Detector Lobby 1300 1 P070 Pass

Smoke Detector Lobby 1300 1 P071 Pass

Smoke Detector Lobby 1300 1 P072 Pass

Smoke Detector Corr 1100 1 P073 Pass

Smoke Detector Corr 1100 1 P074 Pass

Smoke Detector Multi rm Lobby Exit 1 P075 Pass

Duct Detector WSHP AD4 rm 1205 1 P076 Fail

Smoke Detector Corr 1204 @ Lobby 1 P077 Pass

Heat Detector Elevator #2 Pit 1 PO78 Visual

Smoke Detector Elevator #2 Pit 1 P079 Visual

Smoke Detector Elevator #2 Lobby 1 P080 Pass

Smoke Detector Elevator #2 Mach rm 1 P081 Pass

Smoke Detector Corr 1204 @ Stair 1 P082 Pass

Smoke Detector Corr 1204 Stair 1 P083 Pass

Smoke Detector Print rm 1326 1 P084 Fail

Tamper Switch Riser #2 1 P085 Fail

Flow Switch Riser #2 1 P086 Pass

Smoke Detector Above FACP 1 P108 Pass

Tamper Switch Elevator #1 1 P109 Not Found

Tamper Switch Elevator #2 1 P110 Not Found

Heat Detector Elevator #1 Mach rm 1 P111 Visual

Heat Detector Elevator #1 Mach rm 1 P112 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 219: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector Elevator #2 Mach rm 1 P113 Visual

Smoke Detector Corr 1200 Smoke drs 1 P114 Pass

Smoke Detector Corr 1200 Smoke drs 1 P115 Pass

Loop 2 M01

Smoke Detector Gym Corr Exit 1 P001 No Access

Duct Detector RTU G2 above Gym 1 P002 No Access

Duct Detector RTU G1 above Gym 1 P003 No Access

Smoke Detector Gym Lobby Exit 2 P004 No Access

Smoke Detector Gym Lobby Exit 2 P005 No Access

Smoke Detector Corr 2500 Stair 2 P006 Pass

Smoke Detector Corr 2500 @ Stair 2 P007 Pass

Smoke Detector Elect rm 2504 2 P008 Pass

Smoke Detector Elevator #1 Top of Shaft 2 P009 Visual

Heat Detector Elevator #1 Top of Shaft 2 P010 Visual

Smoke Detector Elevator #1 Lobby 2 P011 Pass

Pull Station Lobby 2000 2 P013 Pass

Smoke Detector Elect rm 2003 2 P014 Not Found

Smoke Detector Corr 2040 Middle 2 P015 Pass

Smoke Detector Corr 2040 Middle 2 P016 Pass

Smoke Detector Corr 2040 @ Stair 2 P017 Pass

Smoke Detector Corr 2040 Stair 2 P018 Pass

Duct Detector RTU MC1 in Library 2 P019 Fail

Smoke Detector Corr 2207 Stair 2 P020 Pass

Smoke Detector Corr 2207 @ Stair 2 P021 Pass

Smoke Detector Elect rm 2203 2 P022 Pass

Smoke Detector Video Head End 2 P023 Pass

Heat Detector Elevator #2 Top of Shaft 2 P024 Visual

Smoke Detector Elevator #2 Top of Shaft 2 P025 Visual

Smoke Detector Elevator #2 Lobby 2 P026 Pass

Pull Station Lobby 2300 2 P027 Pass

Pull Station Lobby 2300 2 P028 Pass

Pull Station Lobby 2300 2 P029 Pass

Smoke Detector Closet 2312 2 P030 Pass

Smoke Detector Closet 2320 2 P031 Pass

Smoke Detector Print rm 2324 2 P032 Pass

Smoke Detector Corr 2318 @ Stair 2 P033 Pass

Smoke Detector Corr 2318 Stair 2 P034 Pass

Duct Detector RTU supply rm 2011 2 P035 Fail

Duct Detector RTU return rm 2011 2 P036 Fail

Duct Detector RTU supply rm 2004 2 P037 Fail

Duct Detector RTU supply rm 2004 2 P038 Fail

Smoke Detector Corr 2500 @ Lobby 2 P039 Pass

Smoke Detector Lobby 2000 2 P040 Pass

Smoke Detector Corr 2040 @ Lobby 2 P041 Pass

Smoke Detector Lobby 2000 2 P042 Pass

Smoke Detector Corr 2207 Middle 2 P043 Pass

Smoke Detector Corr 2207 Middle 2 P044 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 220: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Corr 2207 @ Lobby 2 P045 Pass

Smoke Detector Lobby 2300 2 P046 Pass

Smoke Detector Corr 2318 @ Lobby 2 P047 Pass

Smoke Detector Lobby 2300 2 P048 Pass

Pull Station Corr 2318 @ Stair Exit 2 P049 Pass

Pull Station Corr 2207 Stair Exit 2 P050 Pass

Pull Station Corr 2040 Stair Exit 2 P051 Pass

Pull Station Corr 2500 Stair Exit 2 P052 Pass

Duct Detector RTU supply rm 2301 2 P053 Fail

Duct Detector RTU return rm 2301 2 P054 Fail

Duct Detector RTU supply rm 2304 2 P055 Fail

Duct Detector RTU return rm 2304 2 P056 Fail

Duct Detector RTU Lobby 2300 2 P057 Fail

Ansul Hood System 2 P059 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 221: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 222: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 223: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 224: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 225: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

M01P019, M01P035, M01P036, M01P037, M01P038, M01P053, M01P054, M01P055, M01 P056, M01 P057.

4. Riser tampers on #1 & #2, M33P047 & M33P085 failed to report to panel.

5. The following smoke detectors failed to report to the panel: M33P054 & M33P084

Deficiencies

1. Strobe at Exit near Room 1532 - does not flash.

2. 8 Batteries failed load test.

3. Pull station M33P008 failed to report to panel.

6. The following duct detectors failed to report to the panel: M33P049, M33P050, M33P076,

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 226: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 227: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

4 0

9 0

6 0

5 0

1 0

1 0

Inspector Name : Signature:

Control Panel

Device

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment Pass

EMC Security

Pass

Pass

Pass

D K WomackKen Womack

SimplexVoice Evac 4003

All-Star Fire, LLC

Casil

Simplex 4099-9006

CA12330

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4020

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

520 Tribble Gap Road

Forsyth Central High School Gym

Ground Fault

171610

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFoyer

Model Name 4020Simplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC

4098-9685

Heat detectors Simplex 4098-9734

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

8/7/2020

EI1273

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 228: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 4 0

10 0

23 0

27 10

13 1

3 0

Inspector Name : Signature:

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

8/6/2020

EI1273 / WO#155484

4098-9685

Other

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

Pass

520 Tribble Gap Rd

Forsyth Central High School - West Campus

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredBldg DRM 1536

Model Name 4010Simplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ga

Monitoring Company

EMC

All-Star Fire, LLC

Power Sonic

Simplex 4099-9004

FAS1275

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

SimplexHeat Detector 4098-9734

Pass

Simplex 4009

EMC Security

Fail

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 229: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Poor (2017) 12.9 Pass

Poor (2017) 12.9 Pass

Poor (2017) 13 Pass

Poor (2017) 13 Pass

Poor (2017) 12.9 Pass

Poor (2017) 12.9 Pass

Poor (2017) 12.9 Pass

Poor (2017) 12.9 Pass

Poor (2017) 12.8 Pass

Poor (2017) 12.9 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

Pass

N/A

N/A

FCPS (right) #4 rm 1242

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

12v 7ah

FCPS (left) #2 rm 1408

FCPS (right) #2 rm 1408

FCPS (left) #3 rm 1242

FCPS (right) #3 rm 1242

12v 7ah

12v 7ah

12v 7ah

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FCPS (right) #1 rm 1536

FCPS (left) #1 rm 1536

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

FCPS (left) #4 rm 1242

Fire Pump Running

Fire Pump Power Loss

12v 7ah

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 230: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initiating Device Testing

East Building

Device Type Location Floor Address/Zone Result

Pull Station D bldg Corr 1 1M003 Pass

Smoke Detector D bldg Corr 1 1M004 Pass

Smoke Detector Bridge way for C & D 1 1M005 Pass

Pull Station Bridge way for C & D 1 1M006 Pass

Smoke Detector Bridge way for C & D 1 1M007 Pass

Smoke Detector Bridge way for C & D 1 1M008 Pass

Duct Detector C Wing rm 1557 1 1M009 Not Found

Duct Detector C Wing rm 1554 1 1M010 Pass

Pull Station C Wing Exit 1 1M011 Pass

Pull Station C Wing Exit 1 1M012 Pass

Duct Detector B Wing Science Lab 1406 1 1M013 Pass

Pull Station B Wing Exit 1 1M014 Pass

Pull Station A Wing Exit 1 1M015 Pass

Smoke Detector A Wing Elect rm 1329 1 1M016 Fail

Duct Detector A Wing Commons 1 1M017 Pass

Pull Station Display Area 1100A 1 1M020 Pass

Duct Detector Display Area 1100A 1 1M023 Pass

Duct Detector Main Entrance Corr 1 1M024 Pass

Duct Detector Teacher Resource rm 1140 1 1M025 Pass

Pull Station Main Entrance 1 1M026 Pass

Smoke Detector Office Corr 1 1M027 Pass

Duct Detector Office Test rm 1106 1 1M028 Pass

Smoke Detector Office Testing Elect rm 1 1M029 Pass

Smoke Detector Office Corr 1 1M030 Pass

Smoke Detector Office Corr 1 1M031 Pass

Smoke Detector Office Corr Storage 1 1M032 Pass

Smoke Detector Office Corr Cust Closet 1 1M033 Pass

Duct Detector Spec Ed rm 1168 1 1M034 Pass

Duct Detector Spec Ed rm 1171 1 1M035 Pass

Pull Station Spec Ed Corr Exit 1 1M037 Pass

Duct Detector Tech Lab rm 1160 1 1M038 Pass

Duct Detector Classroom 1187 1 1M039 Pass

Pull Station Mech rm 1242 1 1M041 Pass

Pull Station Tech Lab rm 1160 Exit 1 1M042 Pass

Pull Station Gym 1240 1 1M049 Pass

Duct Detector Gym 1240 1 1M050 Visual

Duct Detector Gym 1240 1 1M051 Visual

Duct Detector Gym 1240 1 1M054 Visual

Duct Detector Gym 1240 1 1M055 Visual

Pull Station Gym 1240 1 1M056 Pass

Pull Station Gym 1240 1 1M057 Pass

Pull Station Business Lab Corr Exit 1 1M058 Pass

Pull Station A Wing Exit 1 1M059 Pass

Pull Station Gym 1240 1 1M060 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 231: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Outside ERU-1 ret 1 1M062 Fail

Duct Detector Outside ERU-2 sup 1 1M063 Fail

Duct Detector Outside ERU-2 ret 1 1M064 Fail

Duct Detector Outside ERU-3 sup 1 1M065 Fail

Duct Detector Outside ERU-3 ret 1 1M066 Fail

Duct Detector Outside ERU-4 sup 1 1M067 Fail

Duct Detector Outside ERU-4 ret 1 1M068 Fail

Duct Detector Outside ERU-5 sup 1 1M069 Fail

Duct Detector Outside ERU-5 ret 1 1M070 Fail

Duct Detector Outside ERU-1 sup 1 1M071 Fail

Pull Station Corr 1200 Exit 1 1M 075 Pass

Smoke Detector Corr 1200 Smoke drs 1 1M076 Pass

Smoke Detector Corr 1221 Smoke drs 1 1M077 Pass

Heat Detector Break rm 1210 1 1M078 Visual

Duct Detector Corr 1215 1 1M081 Pass

Pull Station Corr 1240 Exit 1 1M082 Pass

Heat Detector Server and Profound rm 1244 1 1M083 Visual

Pull Station Corr 1240 Exit by 1244 1 1M084 Pass

Heat Detector Kitchen 1224 1 1M086 Visual

Pull Station Corr 1221 Exit 1 1M087 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 232: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Trouble on panel on arrival, water flow 1M049 invrep.

Deficiencies

1. Smoke detector 1M016 failed to report to panel.

2. All ERU's duct detectors failed to flash or report to the panel, 1M061, 1M062, 1M063,

1M064, 1M065, 1M066, 1M067, 1M068, 1M069, 1M070 & 1M071.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 233: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 234: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

4 0

9 0

10 0

2 0

1 0

3 0

Inspector Name : Signature:

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

8/7/2020

EI1273 / WO #155444

Smoke Detectors FSP-851

Duct Detectors System Sensor

30040

Control Panel

Device

Pass

DNR

Batteries

Pullstations

Notifier

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

520 Tribble Gap Road

Forsyth Central High School

Ground Fault

171652

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredElect rm 1262

Model Name NFS2-640Notifier

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Secutity

Pass

All-Star Fire, LLC

PowerSonic

Notifier NBG-12LX

FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

NFS2 -640

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Notifier

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

NotifierVoice Evac NFC-50/100

Heat Detectors Notifier FST-851

Interface Equipment

Pass

Pass

EMC Security

Pass

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 235: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (no date) 13.2 Pass

Good (no date) 13.2 Pass

Good (no date) 13.2 Pass

Good (no date) 13.2 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Supervisory Signals

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Correct Switching and Operation Verified

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

12v 18ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FACP (left)

12v 18ahFACP (right)

12v 18ah

12v 18ah

Voice Evac (right)

Voice Evac (left)

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

Fire Pump Power Loss

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 236: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initaging Device Testing

Device Type Location Floor Address/Zone Results

Smoke Detector Main Elect rm Above FACP L1D001 Pass

Heat Detector Mech rm by Kitchen L1D002 Visual

Duct Detector Dry Storage L1D005 Visual

Duct Detector Cafe a Serving Line L1D006 Not Found

Duct Detector Cafe a Serving Line L1D007 Not Found

Duct Detector Cafe a Serving Line L1D008 Not Found

Duct Detector Cafe a Serving Line L1D009 Not Found

Pull Station Kitchen Rear Exit L1M001 Pass

Pull Station Cafe Exit L1M002 Pass

Pull Station Hall Exit by Cafe L1M003 Pass

Heat Detector Cafe L2D001 Visual

Smoke Detector Clinic Storage L2D002 Pass

Heat Detector Mail /Break rm L2D003 Visual

Duct Detector School Store L2D007 Visual

Duct Detector Marketing rm L2D008 Visual

Duct Detector Media Production L2D009 Pass

Duct Detector Media A/V Storage L2D010 Pass

Duct Detector Computer Lab L2D012 Visual

Pull Station Hall by School Store L2M001 Pass

Pull Station Marketing rm L2M002 Pass

Pull Station Band Storage L2M003 Pass

Pull Station Band Storage L2M004 Pass

Pull Station Corr by Counselor L2M005 Pass

Pull Station Waiting rm/Lobby L2M006 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 237: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 238: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 239: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

4 4

3 0

1 0

2 1

1 0

2 0

Inspector Name : Signature:

Interface Equipment

Pass

Pass

EMC Security

Fail

Pass

Pass

D K WomackKen Womack

NotifierVoice Evac NFC-50/100

Heat Detectors Notifier FST-851

All-Star Fire, LLC

Power Sonic

Notifier NBG12LX

FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

NFS 320

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Notifier

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

520 Tribble Gap Road

Forsyth Central High School Field House

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredMain Lobby

Model Name NFS-320Notifier

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC

Pass

Smoke Detectors FSP-851

Duct Detectors TBD

30040

Control Panel

Device

Pass

TBD

Batteries

Pullstations

Notifier

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

8/7/2020

EI1273 / WO #155444

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 240: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Poor (2016) 12.8 Fail

Poor (2016) 12.9 Fail

Poor (2016) 13 Fail

Poor (2016) 13 Fail

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

Fire Pump Power Loss

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

12v 18ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FACP (left)

12v 18ahFACP (right)

12v 18ah

12v 18ah

Voice Evac (right)

Voice Evac (left)

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Supervisory Signals

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Correct Switching and Operation Verified

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 241: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Smoke Detector Lobby above FACP 1 1D001 Fail

Heat Detector Mech rm 1 1D002 Visual

Smoke Detector Elect rm 1 1D003 Pass

Heat Detector Mech rm 1 1D004 Visual

Duct Detector Freshman Restroom 1 1D006 Not Found

Pull Station Varsity Entry 1 1M001 Pass

Pull Station Lobby Entrance 1 1M002 Pass

Pull Station Freshman Entry 1 1M003 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 242: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

3. Failed water flow switch.

Trouble on panel on arrival, waterflow 1M049 INVREP.

Deficiencies

1. 4 Batteries failed load test.

2. Smoke detector 1D001 failed to go into alarm, failed to report to panel.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 243: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 244: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

3 0

10 0

28 0

25 0

2 0

14 0

3 0

3 0

Inspector Name : Signature:

Duct Detectors Simplex 4098-9756

Voice Control Panel Simplex 4003

Heat Detectors Simplex 4090-9733

David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Power Patrol

4010Control Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Simplex

Simplex

2099-9101

Who Was Notified Prior to the Start of Testing Monitoring Company & Staff

Batteries FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Simplex 4009

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC Security (888-745-4733)Monitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Yes

Are Lamps and Displays Operating Properly

(678) 691-0011

7465 Wallace Tatumn Road

30028

Simplex

Front Office

Model Name

Cumming GA

Is the Panel Monitored Yes

4010

EI1273 / WO #155449

Liberty Middle School

6/8/2020

Tamper Switches Potter OS&Y-SU2

Waterflow Switches Potter VSR-F

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 245: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.6 Pass

Good (2020) 13.6 Pass

Good (2020) 13.6 Pass

Good (2020) 13.5 Pass

Good (2020) 13.6 Pass

Good (2020) 13.5 Pass

Good (2020) 13.6 Pass

Good (2020) 13.4 Pass

Good (2020) 13.6 Pass

Good (2020) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

Pass

Pass

N/A

Fire Pump Phase Reversal

BPS Rm 141 (Left)

Voice Control Panel (Left) 12V 7AH

Voice Control Panel (Right) 12V 7AH

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

Fire Alarm Control Panel (Right) 12V 7AH

Kitchen Hoods

Location Size

Magnetic Door Holders

BPS Rm 425 (Right) 12V 7AH

BPS 531 (Left) 12V 7AH

BPS 531 (Right) 12V 7AH

12V 7AH

BPS Rm 141 (Right) 12V 7AH

Fire Pump Trouble

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

12V 7AH

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

Fire Alarm Control Panel (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

BPS Rm 425 (Left)

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 246: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Smoke Detector CLERICAL A103 1 M1 1 Pass

Smoke Detector A101 1 M1 2 Pass

Smoke Detector LUNCH RM A127 1 M1 3 Pass

Pull Station CORRIDOR A101 MAIN ENTRANCE 1 M1 4 Pass

Pull Station DINING AREA A128 1 M1 5 Pass

Pull Station PASSAGE A112 1 M1 6 Pass

Duct Detector MECHANICAL RM A116 1 M1 7 Pass

Duct Detector MECHANICAL RM A116 1 M1 8 Pass

Pull Station MECHANICAL RM A116 1 M1 9 Pass

Smoke Detector CORRIDOR A101 1 M1 10 Pass

Smoke Detector LUNCH RM A127 1 M1 11 Pass

Smoke Detector LUNCH RM A127 1 M1 12 Pass

Smoke Detector FOOD COURT A129 1 M1 13 Pass

Smoke Detector FOOD COURT A129 1 M1 14 Pass

Smoke Detector LUNCH RM A127 1 M1 15 Pass

Smoke Detector LUNCH RM A127 1 M1 16 Pass

Duct Detector KITCHEN A130 1 M1 17 Pass

Duct Detector KITCHEN A130 1 M1 18 Pass

Monitor KITCHEN HOOD 1 M1 19 Pass

Heat Detector KITCHEN A130 1 M1 20 Visual

Pull Station LUNCH RM A127 1 M1 21 Pass

Waterflow Switch MECHANICAL RM A134 1 M1 23 Pass

Tamper Switch MECHANICAL RM A134 1 M1 23 Pass

Pull Station MECHANICAL RM A134 1 M1 24 Pass

Pull Station CORRIDOR TO PATIO A101 1 M1 25 Pass

Smoke Detector CORRIDOR TO CENTRAL CROSSING 1 M1 26 Pass

Smoke Detector CENTRAL CROSSING A147 1 M1 27 Pass

Smoke Detector CENTRAL CROSSING A147 1 M1 28 Pass

Smoke Detector FOOD COURT A129 1 M1 29 Pass

Pull Station CORRIDOR B148 1 M1 30 Pass

Pull Station RECEIVING A138 1 M1 31 Pass

Smoke Detector CORRIDOR A146 1 M1 32 Pass

Smoke Detector 8TH GRADE CORRIDOR 1 M1 33 Pass

Waterflow Switch MECHANICAL RM A134 1 M1 34 Pass

Tamper Switch MECHANICAL RM A134 1 M1 34 Pass

Duct Detector 8TH GRADE RM 448 1 M1 35 Pass

Monitor KITCHEN HOOD RM #315 1 M1 36 Pass

Pull Station 8TH GRADE CORRIDOR EXIT 1 M1 37 Pass

Heat Detector KITCHEN B142 1 M1 38 Visual

Smoke Detector CORRIDOR B101 1 M1 39 Pass

Smoke Detector 7TH GRADE CORRIDOR 1 M1 40 Pass

Smoke Detector STORAGE PREP 7TH GRADE SCIENCE 1 M1 41 Pass

Pull Station MAIN OFFICE EXIT DR 1 M1 42 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 247: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector 7TH GRADE CORRIDOR 1 M1 43 Pass

Pull Station 7TH GRADE CORRIDOR EXIT 1 M1 45 Pass

Pull Station MECHANICAL RM B107 1 M1 46 Pass

Pull Station CORRIDOR B148 BY SPECIAL ED 1 M1 47 Pass

Pull Station CORRIDOR BETWEEN 6TH & 7TH 1 M1 48 Pass

Smoke Detector CORRIDOR B100 1 M1 49 Pass

Smoke Detector 6TH GRADE CORRIDOR 1 M1 50 Pass

Duct Detector 6TH GRADE CORRIDOR 1 M1 52 Pass

Pull Station 6TH GRADE CORRIDOR EXIT 1 M1 54 Pass

Duct Detector BUSINESS EDUCATION B104 1 M1 55 Pass

Duct Detector MECHANICAL RM A159 1 M1 56 Pass

Duct Detector MECHANICAL RM A159 1 M1 57 Pass

Pull Station READING AREA A151 1 M1 58 Pass

Pull Station CORRIDOR EXIT TO READING AREA 1 M1 59 Pass

Smoke Detector CORRIDOR A148 1 M1 60 Pass

Smoke Detector CORRIDOR AREA F 1 M1 61 Pass

Pull Station CHORUS F101 1 M1 62 Pass

Pull Station TECHNOLOGY LAB 103 1 M1 63 Pass

Pull Station ART LAB SUITE F117 1 M1 64 Pass

Smoke Detector CORRIDOR AREA F 1 M1 65 Pass

Pull Station MECHANICAL RM F120 1 M1 66 Pass

Pull Station MECHANICAL RM 606 1 M1 67 Pass

Pull Station CORRIDOR AREA F 1 M1 68 Pass

Smoke Detector CORRIDOR AREA F NEAR ART LAB 1 M1 69 Pass

Pull Station CORRIDOR AREA F GYM ENTRANCE 1 M1 70 Pass

Pull Station BAND RM F129 1 M1 71 Pass

Duct Detector MECHANICAL RM G109 1 M1 72 Pass

Waterflow Switch MECHANICAL RM A134 1 M1 73 Pass

Tamper Switch MECHANICAL RM A134 1 M1 73 Pass

Pull Station MECHANICAL RM G109 1 M1 75 Pass

Pull Station CORRIDOR EXIT NEAR LAUNDRY 1 M1 76 Pass

Monitor 4003 MANUAL EVAC TRBL 1 M1 80 Pass

Duct Detector GYM NEW RTU 1 1 M1 84 Pass

Duct Detector GYM NEW RTU 2 1 M1 85 Pass

Duct Detector KITCHEN RTU 1 M1 86 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 248: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 249: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 250: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

4 0

12 0

58 0

2 0

13 0

4 0

4 0

Inspector Name : Signature: David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Interstate

4010Control Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Simplex

Simplex

4099-9001

Who Was Notified Prior to the Start of Testing Monitoring Company & Reception

Batteries SLA1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Simplex 4009

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Pass

Are Lamps and Displays Operating Properly

(678) 691-0011

1120 Dahlonega Highway

30040

Simplex

Outdoor Elec. Service Rm

Model Name

Cumming GA

Is the Panel Monitored Yes

4010

EI1273 / WO # 1554736

Board of Education & Professional Development Center

7/10/2020

Waterflow Switches Potter VSR

Tamper Switches Global Safety Products BG-V

Heat Detectors Simplex 4098-9733

Duct Detectors Simplex 4098-9756

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 251: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Fail

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.8 Pass

Good (2019) 13.9 Pass

Good (2019) 13.6 Pass

Good (2019) 13.7 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Pass

N/A

N/A

N/A

Pass

Pass

FACP (Left)

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

BPS #1 2nd Fl Elec. Rm (Left)

Generator Trouble Reports to Panel

12V 7AH

12V 7AH

12V 7AH

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

Fire Pump Trouble

Fire Pump Phase Reversal

BPS #1 2nd Fl Elec. Rm (Right)

FACP (Right)

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 252: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Pull Station REAR EXIT WEST 1 M1 1 Pass

Pull Station SIDE EXIT SOUTH 1 M1 2 Pass

Pull Station FRONT EXIT BOARD RM EAST 1 M1 3 Pass

Pull Station MAIN LOBBY EAST 1 M1 4 Pass

Pull Station NORTH STAIR 1 M1 5 Pass

Pull Station SOUTH STAIR 1 M1 6 Pass

Smoke Detector 1ST FLOOR CORR 108 1 M1 9 Pass

Smoke Detector 1ST FLOOR CORR 108 1 M1 10 Pass

Smoke Detector CORR 108 1 M1 11 Pass

Smoke Detector 1ST FLOOR AUX 104 1 M1 12 Pass

Smoke Detector 1ST FLOOR AUDIO 103 1 M1 13 Pass

Smoke Detector FIRST FLR RM 102 1 M1 14 Pass

Smoke Detector FIRST FLR LOBBY 100 1 M1 15 Pass

Smoke Detector FIRST FLR LOBBY 100 1 M1 16 Pass

Smoke Detector FIRST FLR LOBBY 100 1 M1 17 Pass

Smoke Detector FIRST FLR LOBBY 100 1 M1 18 Pass

Smoke Detector 1ST FLOOR CORR 123 1 M1 19 Pass

Smoke Detector FIRST FLR LOBBY 100 1 M1 20 Pass

Smoke Detector FIRST FLOOR CORR 151 1 M1 21 Pass

Smoke Detector FIRST FLOOR CORR 151 1 M1 22 Pass

Smoke Detector MICRO STOR RM 1 M1 23 Pass

Smoke Detector 1ST. FL. OFFICE 132 1 M1 24 Pass

Smoke Detector CORR 151 1 M1 25 Pass

Smoke Detector CORR 151 1 M1 26 Pass

Smoke Detector ELECTRIC RM 213 2 M1 27 Pass

Smoke Detector VAULT 150 1 M1 28 Pass

Smoke Detector SPRINKLER 141 1 M1 29 Pass

Smoke Detector MAIN ELECTRIC RM 131 1 M1 30 Pass

Smoke Detector COMMON RM 1 M1 31 Pass

Smoke Detector TEL RM 138 1 M1 32 Pass

Smoke Detector CUST RM 158 1 M1 33 Pass

Smoke Detector STOR RM 232 2 M1 34 Pass

Heat Detector ELEVATOR MECH RM 157 1 M1 35 Visual

Tamper Switch MAIN SPRINKLER RISER 1 M1 40 Pass

Waterflow Switch MAIN SPRINKLER RISER 1 M1 40 Pass

Tamper Switch NORTH STAIR 1 M1 42 Pass

Waterflow Switch NORTH STAIR 1 M1 42 Pass

Smoke Detector ELEVATOR MECH RM 157 1 M1 44 Pass

Pull Station MAIN STAIR 2 M1 55 Pass

Pull Station SOUTH STAIR 2 M1 56 Pass

Smoke Detector ELEVATOR LOBBY 2 M1 60 Pass

Smoke Detector LOBBY BRIDGE 2 M1 61 Pass

Smoke Detector CORR 229 2 M1 62 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 253: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector ELECTRIC RM 26 2 M1 63 Pass

Smoke Detector HOR 204 2 M1 64 Pass

Smoke Detector BREAK RM 2 M1 65 Pass

Smoke Detector CUSTODIAN RM 251 2 M1 66 Pass

Smoke Detector STORAGE RM 232 2 M1 67 Pass

Smoke Detector ELECTRIC RM 248 2 M1 68 Pass

Tamper Switch NORTH STAIR 2 M1 70 Pass

Waterflow Switch NORTH STAIR 2 M1 70 Pass

Monitor KITCHEN HOOD 2 M1 71 Pass

Monitor SERVER RM HALON SYS. NOTIFIER 2 M1 72 Pass

Pull Station 3RD FL PUBLIC INFO REAR 3 M1 73 Pass

Pull Station 3RD FL PUBLIC INFO FRONT 3 M1 74 Pass

Pull Station SOUTH STAIR 3 M1 75 Pass

Pull Station NORTH STAIR 3 M1 76 Pass

Smoke Detector CORR 331 3 M1 80 Pass

Smoke Detector LOBBY AT BRIDGE 3 M1 81 Pass

Smoke Detector LOBBY AT BRIDGE 3 M1 82 Pass

Smoke Detector LOBBY AT BRIDGE 3 M1 83 Pass

Smoke Detector CORR BALCONY 301 3 M1 84 Pass

Smoke Detector BRIDGE 3 M1 85 Pass

Smoke Detector ELEVATOR LOBBY 3 M1 86 Pass

Smoke Detector LOBBY AT BRIDGE 3 M1 87 Pass

Smoke Detector NORTH STAIR 3 M1 88 Pass

Smoke Detector TOP OF SHAFT 3 M1 89 Pass

Smoke Detector STORAGE RM 330 3 M1 90 Pass

Smoke Detector CONF RM 349 3 M1 91 Pass

Smoke Detector STORAGE RM 317 3 M1 92 Pass

Smoke Detector STORAGE RM 303 3 M1 93 Pass

Smoke Detector RM 300 3 M1 94 Pass

Smoke Detector STOR RM 335 3 M1 96 Pass

Smoke Detector STOR RM 335 3 M1 97 Pass

Smoke Detector STOR RM 335 3 M1 98 Pass

Smoke Detector CUST RM 3 M1 99 Pass

Smoke Detector ELECTRICAL RM 339 3 M1 100 Pass

Smoke Detector SOUTH STAIR 3 M1 101 Pass

Smoke Detector CORR BALCONY 334 3 M1 103 Pass

Heat Detector TOP OF ELEVATOR SHAFT 3 M1 105 Visual

Tamper Switch NORTH STAIR 3 M1 110 Pass

Waterflow Switch NORTH STAIR 3 M1 110 Pass

Duct Detector RTU-4 1 M1 115 Pass

Duct Detector RTU-8 2 M1 116 Pass

Duct Detector RTU-5 2 M1 117 Pass

Duct Detector RTU-1 1 M1 118 Pass

Duct Detector RTU-13 3 M1 119 Pass

Duct Detector RTU-9 3 M1 120 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 254: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector RTU-6 2 M1 121 Pass

Duct Detector RTU-2 1 M1 122 Pass

Duct Detector RTU-10 3 M1 123 Pass

Duct Detector RTU-12 3 M1 124 Pass

Duct Detector RTU-7 2 M1 125 Pass

Duct Detector RTU-3 1 M1 126 Pass

Duct Detector RTU-11 3 M1 127 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 255: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

(1) Simplex 4904-9137 red wall mounted strobe on 2nd fl by room 255 failed to activate during alarm.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 256: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 257: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 4 0

16 2

37 0

22 0

81 0

3 0

Inspector Name : Signature:

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

SimplexVoice Evac 4003

All-Star Fire, LLC

Power Sonic

Simplex 2099-9756

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4100

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Alpharetta

Are Lamps and Displays Operating Properly

Pass

625 James Road

DeSana Middle School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name 4100 ESSimplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

4098-9688

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

30004

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

8/3/2020

EI1273

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 258: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.4 Pass

Good (2020) 13.6 Pass

Good (2020) 13.1 Pass

Good (2020) 13.1 Pass

Good (2020) 13 Pass

Good (2020) 13.3 Pass

Not Found

Not Found

Not Found

Not Found

Good (2020) 13.3 PassGood (2020) 13.2 Pass

Good (2020) 13.3 Fail

Good (2020) 13.1 Fail

Good (2020) 13.4 Pass

Good (2020) 13.4 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Pass

N/A

N/A

Pass

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Voice Evac (right) Cafe

FCPS (left) #4 Corr @ rm 2228

Voice Evac (left) Cafe

Voice Evac (left) Media

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Voice Evac (right) Media

Voice Evac (left) Gym

Voice Evac (right) Gym

12v 7ah

12v 7ah

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 1581

FCPS (right) #2 rm 1581

FCPS (left) #3 Corr @ rm 1238

FCPS (right) #3 Corr @ rm 1238

12v 7ah

12v 7ah

12v 7ah

FCPS (right) #4 Corr @ rm 2228

Maglock Release

Stairwell Pressurization

FACP (left)

12v 18ah FACP (right)

12v 18ah

12v 7ah

FCPS (right) #1 rm1278

FCPS (left) #1 rm 1278

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 259: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

N/AFM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 260: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Smoke Detector Parent Reception rm 1500 LL M1-1 Pass

Smoke Detector Corr 1570 LL M1-2 Visual

Smoke Detector Lunch rm 1540 LL M1-3 Visual

Pull Station Lunch rm 1540 LL M1-4 Pass

Smoke Detector Lunch rm 1540 LL M1-5 Visual

Smoke Detector Lunch rm 1540 LL M1-6 Visual

Smoke Detector Lunch rm 1540 LL M1-7 Visual

Pull Station Elect rm 1310 LL M1-8 Pass

Pull Station Lunch rm 1540 LL M1-10 Pass

Smoke Detector Corr 1570 LL M1-11 Visual

Pull Station Vestibule 1501 LL M1-12 Pass

Pull Station Parent Reception rm 1500 LL M1-15 Pass

Smoke Detector Vault rm 1508 LL M1-18 No Access

Smoke Detector Elect rm 1522 LL M1-20 Pass

Pull Station Passage 1521 LL M1-21 Pass

Smoke Detector Mech rm 1304 LL M1-22 Pass

Pull Station Mech rm 1304 LL M1-23 Pass

Pull Station Media Ctr 1580 LL M1-28 Pass

Duct Detector Media Ctr 1580 LL M1-29 Pass

Duct Detector Media Ctr 1580 LL M1-30 Pass

Duct Detector Media Ctr 1580 LL M1-31 Pass

Smoke Detector Media Ctr 1580 LL M1-32 Pass

Smoke Detector Lobby 1571 LL M1-33 Pass

Smoke Detector Lobby 1571 LL M1-35 Visual

Smoke Detector Food Court 1550 LL M1-63 Pass

Pull Station Elect rm 1320 LL M1-36 Pass

Smoke Detector Food Court 1550 LL M1-42 Pass

Duct Detector Food Court 1550 RTU cafe2 LL M1-43 Not Found

Smoke Detector Food Court 1550 LL M1-44 Pass

Duct Detector Kitchen 1566 OAU-1 LL M1-45 Pass

Duct Detector Kitchen 1566 RTU kit-1 LL M1-47 Pass

Pull Station Kitchen 1566 RTU kit-1 LL M1-48 Pass

Smoke Detector Lobby 1577 LL M1-49 Pass

Smoke Detector Store 1577 LL M1-51 Pass

Pull Station Lobby 1577 LL M1-52 Pass

Smoke Detector Lobby 1577 LL M1-53 Pass

Smoke Detector Lobby 1577 LL M1-54 Pass

Pull Station Lobby 1577 LL M1-55 Pass

Smoke Detector Corr 1100 LL M1-60 Pass

Pull Station Corr 1100 LL M1-69 Pass

Smoke Detector Elect rm 1119 LL M1-70 Pass

Smoke Detector Data rm 1120 LL M1-71 Pass

Duct Detector Girls RR 1123 ERU-1 LL M1-72 Pass

Smoke Detector Corr 1100 LL M1-82 Pass

Pull Station Corr 1100 LL M1-83 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 261: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Stair 1150 LL M1-84 Pass

Pull Station Stair 1150 LL M1-85 Pass

Smoke Detector Commons LL M1-86 Pass

Smoke Detector Elev #1 Lobby 1010 LL M1-90 Pass

Smoke Detector Commons Area 1010 LL M1-91 Pass

Smoke Detector Commons Area 1010 LL M1-92 Pass

Heat Detector Elev #1 Equip rm 1008 LL M1-93 Visual

Smoke Detector Commons Area 1000 LL M1-100 Pass

Pull Station Commons Area 1000 LL M1-101 Pass

Smoke Detector Commons Area 1000 LL M1-102 Pass

Smoke Detector Commons Area 1000 LL M1-103 Pass

Smoke Detector Commons Area 1000 LL M1-104 Pass

Smoke Detector Commons Area 1000 LL M1-105 Pass

Pull Station Commons Area 1000 LL M1-106 Pass

Smoke Detector Stair 1015 LL M1-107 Pass

Smoke Detector Stair 1015 LL M1-108 Pass

Smoke Detector Stair 1015 LL M1-109 Pass

Smoke Detector Stair 1015 LL M1-110 Pass

Smoke Detector Vestibule 1015 LL M1-111 Pass

Pull Station Vestibule 1015 LL M1-112 Pass

Pull Station Vestibule 1015 LL M1-113 Pass

Smoke Detector Test Prep rm 1206 LL M1-114 No Access

Pull Station Mech rm 1230 LL M1-125 Pass

Duct Detector Mech rm 1230 eru 2 LL M1-126 Not Found

Pull Station Corr 1200 LL M1-127 Pass

Pull Station Art Lab rm 1240 LL M1-129 Pass

Smoke Detector Elect rm 1243 LL M1-130 Pass

Smoke Detector Data rm 1245 LL M1-131 Pass

Smoke Detector Corr 1250 LL M1-132 Pass

Smoke Detector Corr 1250 LL M1-133 Pass

Smoke Detector Elev #2 Lobby 1251 LL M1-135 Pass

Smoke Detector Corr 1250 LL M1-136 Pass

Smoke Detector Corr 1250 LL M1-137 Pass

Smoke Detector Stair 1257 LL M1-138 Pass

Pull Station Stair 1257 LL M1-139 Pass

Smoke Detector Corr 1260 LL M1-140 Pass

Smoke Detector Corr 1260 LL M1-141 Visual

Smoke Detector Concession rm 1271 LL M1-142 Pass

Smoke Detector Vestibule 1270 LL M1-143 Pass

Pull Station Choral rm 1261 LL M1-144 Pass

Smoke Detector Corr 1260 LL M1-145 Visual

Pull Station Band rm 1263 LL M1-146 Pass

Pull Station Corr 1260 LL M1-147 Pass

Smoke Detector Vestibule 1270 LL M1-149 Pass

Smoke Detector Elect rm 1275 LL M1-151 Visual

Duct Detector Corr 1277 RTU-health LL M1-152 Pass

Pull Station Corr 1277 RTU-health LL M1-154 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 262: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Boys Locker rm RTU-locker1 LL M1-156 Pass

Duct Detector Health rm 1280 RTU-gym1 LL M1-157 Pass

Duct Detector Health rm 1280 RTU-gym2 LL M1-158 Pass

Pull Station Mech rm 1291 LL M1-162 Pass

Pull Station Corr 1290 LL M1-163 Pass

Duct Detector Vestibule 1290 RTU-Locker 2 LL M1-165 Pass

Pull Station Corr 1250 LL M1-167 Pass

Heat Detector Elev #2 Equip rm 1255 LL M1-168 Visual

Smoke Detector Elev #2 Equip rm 1255 LL M1-169 Pass

Smoke Detector Stair 2150 UL M1-176 Pass

Smoke Detector Corr 2100 UL M1-177 Pass

Pull Station Corr 2100 UL M1-178 Pass

Pull Station Corr 2100 UL M1-183 Pass

Smoke Detector Elect rm 2120 UL M1-184 Not Found

Smoke Detector Corr 2100 UL M1-189 Pass

Smoke Detector Corr 2100 UL M1-190 Pass

Pull Station Corr 2100 UL M1-191 Pass

Smoke Detector Commons 2000 UL M1-192 Pass

Smoke Detector Elev #1 Lobby 2014 UL M1-195 Pass

Smoke Detector Elev #1 Top of Shaft UL M1-196 Visual

Heat Detector Elev #1 Top of Shaft UL M1-197 Visual

Smoke Detector Commons 2000 UL M1-198 Visual

Smoke Detector Stair 2001 UL M1-199 Visual

Smoke Detector Stair 2001 UL M1-200 Visual

Smoke Detector Stair 2001 UL M1-201 Visual

Smoke Detector Stair 2001 UL M1-202 Visual

Smoke Detector Stair 2001 UL M1-203 Visual

Pull Station Commons Area 2000 UL M1-204 Pass

Smoke Detector Commons Area 2000 UL M1-205 Visual

Smoke Detector Commons Area 2000 UL M1-206 Visual

Smoke Detector Commons Area 2000 UL M1-207 Visual

Pull Station Commons Area 2000 UL M1-208 Pass

Smoke Detector Commons Area 2000 UL M1-209 Visual

Pull Station Corr 2200 UL M1-218 Pass

Smoke Detector Elev #2 Lobby 2251 UL M1-223 Pass

Heat Detector Elev #2 Top of Shaft UL M1-224 Visual

Smoke Detector Elev #2 Top of Shaft UL M1-225 Visual

Pull Station Corr 2200 UL M1-226 Pass

Smoke Detector Corr 2200 UL M1-227 Pass

Smoke Detector Stair 2250 UL M1-228 Pass

Duct Detector Mezzanine hp-d73 UL M1-229 Pass

Duct Detector Mezzanine hp-d74 UL M1-230 Pass

Smoke Detector Mezzanine UL M1-231 Not Found

Duct Detector Mezzanine FCU-d100 UL M1-232 Not Found

Duct Detector Mezzanine AHU-gym1 UL M1-233 Pass

Duct Detector Gym Mezzanine UL M1-240 Not Found

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 263: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Gym Mezzanine UL M1-241 Pass

Duct Detector Commons UL M1-236 Not Found

Duct Detector Commons Office UL M1-239 Not Found

Smoke Detector Stair 2250 UL M1-228 Pass

Smoke Detector Corr 2200 UL M1-227 Pass

Duct Detector HP-B6 HVAC rm 1114 LL M1-237 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 264: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. 2 Batteries failed load test.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 265: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 266: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

4 0

14 0

38 0

70 0

168 1

41 0

46 0

11 0

14 0

Inspector Name : Signature:

Voice Evacuation Panel Silent Knight ECS

Heat Detectors Silent Knight IDP-HEAT

RPS-1000

Duct Detectors System Sensor DNR

Waterflow Switches Potter VSR

Tamper Switches Tyco BFV-300

(678) 691-0011

645 Mullinax Road

30004

Silent Knight

Elec. Rm 1316A

Model Name

Alpharetta GA

Is the Panel Monitored Yes

IFP-2000

EI1273 / WO #156056

Denmark High School Main Building

8/6/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Yes

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing Monitoring Company & Office Staff

Batteries FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Silent Knight

David Piorkowski

Pass

Pullstations

Smoke Detectors IDP-PHOTO

Power Patrol

IFP-2000Control Panel

Pass

Device

Silent Knight

Interface Equipment

David Piorkowski

Silent Knight

Silent Knight

IDP-PULL-DA

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 267: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.6 Pass

Good (2020) 13.5 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Pass

N/A

Pass

Pass

Pass

N/A

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 18AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Continued on Page 3 - Battery Testing

FACP (Right) 12V 18AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 268: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Floor Condition Voltage Load Test

1 Good (2020) 13.3 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.3 Pass

1 Good (2020) 13.5 Pass

1 Good (2016) 13.5 Pass

1 Good (2016) 13.6 Pass

1 Good (2016) 13.6 Pass

1 Good (2016) 13.7 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.5 Pass

1 Good (2020) 13.5 Pass

1 Good (2020) 13.6 Pass

1 Good (2016) 13.6 Pass

1 Good (2016) 13.6 Pass

1 Good (2016) 13.6 Pass

1 Good (2016) 13.6 Pass

1 Good (2016) 13.6 Pass

1 Good (2016) 13.6 Pass

1 Good (2016) 13.6 Pass

1 Good (2016) 13.6 Pass

1 Good (2016) 13.6 Pass

1 Good (2016) 13.5 Pass

G Good (2016) 13.5 Pass

G Good (2016) 13.5 Pass

2 Good (2020) 13.6 Pass

2 Good (2020) 13.5 Pass

2 Good (2020) 13.5 Pass

2 Good (2020) 13.5 Pass

2 Good (2020) 13.6 Pass

2 Good (2020) 13.5 Pass

2 Good (2020) 13.6 Pass

2 Good (2020) 13.5 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.4 Pass

RPS-1000 in Elec Rm 2619 (Right) 12V 7AH

SK5495 in Elec Rm 2619 (Left) 12V 7AH

SK5495 in Elec Rm 2619 (Right) 12V 7AH

RPS-1000 in Elec Rm 2619 (Left) 12V 7AH

SK5495 in IDF Rm 1537 (Left) 12V 7AH

SK5495 in IDF Rm 1537 (Right) 12V 7AH

RPS-1000 in Elec Rm 1619 (Right) 12V 7AH

ECS-125W in Elec Rm 2026 (Left) 12V 7AH

ECS-125W in Elec Rm 2026 (Right) 12V 7AH

SK5495 in Elec Rm 0143 (Left) 12V 7AH

SK5495 in Elec Rm 0143 (Right) 12V 7AH

SK5495 in Elec Rm 2026 (Left) 12V 7AH

SK5495 in Elec Rm 2026 (Right) 12V 7AH

SK5495 in Elec Rm 1619 (Left) 12V 7AH

SK5495 in Elec Rm 1619 (Right) 12V 7AH

RPS-1000 in Elec Rm 1619 (Left) 12V 7AH

SK5495 in Elec Rm 1051 R-Side (Right) 12V 8AH

SK5495 in IDF Rm 1729 (Left) 12V 7AH

SK5495 in IDF 1729 (Right) 12V 7AH

SK5495 in Elec Rm 1051 L-Side (Left) 12V 8AH

SK5495 in Elec Rm 1051 L-Side (Right) 12V 8AH

SK5495 in Elec Rm 1051 R-Side (Left) 12V 8AH

ECS-125W in IDF Rm 1215 (Right) 12V 7AH

RPS-1000 in IDF Rm 1215 (Left) 12V 7AH

RPS-1000 in IDF Rm 1215 (Right) 12V 7AH

SK5495 in IDF Rm 1215 (Left) 12V 7AH

SK5495 in IDF Rm 1215 (Right) 12V 7AH

ECS-125W in IDF Rm 1215 (Left) 12V 7AH

Battery Testing (cont.)

Location Size

SK5495 in Mech Rm 1141 (Left) 12V 7AH

ECS-125W in Elec Rm 1316A (Left) 12V 7AH

ECS-125W in Elec Rm 1316A (Right) 12V 7AH

SK5495 in Mech Rm 1141 (Right) 12V 7AH

SK5495 in Elec Rm 1343 (Right) 12V 8AH

ECS-125W in Elec Rm 1343 (Left) 12V 8AH

ECS-125W in Elec Rm 1343 (Right) 12V 8AH

SK5495 in Elec Rm 1343 (Left) 12V 8AH

Page 269: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Pull Station STAIR 13 1133 1 M09 M002 Pass

Pull Station GYM EXIT TO LOBBY 1 M09 M003 Pass

Pull Station STAIR 12 1155 1 M09 M004 Pass

Pull Station LOBBY 1000D 1 M09 M005 Pass

Pull Station LOBBY 1000D 1 M09 M006 Pass

Pull Station GYM EXIT TO LOBBY 1000D 1 M09 M007 Pass

Pull Station CORRIDOR 0130 AT AUX GYM G M09 M008 Pass

Smoke Detector WEIGHT ROOM 0140 G M09 M009 Pass

Pull Station WEIGHT ROOM 0140 G M09 M010 Pass

Pull Station STAIR 13 0133 G M09 M011 Pass

Pull Station STAIR 13 0133 G M09 M012 Pass

Pull Station CORRIDOR 0130 G M09 M013 Pass

Pull Station CORRIDOR 0130 G M09 M014 Pass

Waterflow Switch STORAGE 0123 G M09 M015 Pass

Low Air STORAGE 0123 G M09 M016 Pass

Tamper Switch STORAGE 0123 G M09 M017 Pass

Pull Station STAIR 11 0153 G M09 M020 Pass

Pull Station STAIR 12 0155 G M09 M021 Pass

Pull Station CORRIDOR 1000B 1 M09 M022 Pass

Pull Station CORRIDOR 1000B 1 M09 M023 Pass

Pull Station STAIR 6 1484 1 M09 M026 Pass

Pull Station STAIR 5 1486 1 M09 M027 Pass

Pull Station LOBBY 1402 1 M09 M028 Pass

Waterflow Switch LEVEL 2 RISER ROOM 2 M09 M035 Pass

Low Air LEVEL 2 RISER ROOM 2 M09 M036 Pass

Tamper Switch LEVEL 2 RISER ROOM 2 M09 M037 Pass

Tamper Switch STAIR 5 2436 2 M09 M038 Pass

Pull Station STAIR 6 2435 2 M09 M039 Pass

Pull Station MECHANICAL PENTHOUSE PH M09 M046 Pass

Pull Station CORRIDOR 1100 1 M09 M047 Pass

Smoke Detector MAIN MECHANICAL ROOM 1145 1 M09 S001 Pass

Smoke Detector CORRIDOR 1100 1 M09 S002 Pass

Smoke Detector CORRIDOR 1100 1 M09 S003 Pass

Smoke Detector BULK STORAGE 1142 1 M09 S004 Pass

Smoke Detector CORRIDOR 1300 1 M09 S005 Pass

Smoke Detector CORRIDOR 1300 1 M09 S006 Pass

Smoke Detector CORRIDOR 1300 1 M09 S013 Pass

Smoke Detector CORRIDOR 1300 1 M09 S014 Pass

Smoke Detector CORRIDOR 1000B 1 M09 S015 Pass

Smoke Detector CORRIDOR 1000B 1 M09 S016 Pass

Smoke Detector CORRIDOR 1000B 1 M09 S017 Pass

Smoke Detector CORRIDOR 1000B 1 M09 S018 Pass

Smoke Detector STORAGE 1496A 1 M09 S019 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 270: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector DATA CENTER 1497 1 M09 S020 Pass

Heat Detector DATA CENTER 1497 1 M09 S025 Pass

Heat Detector MECHANICAL ROOM 1487 1 M09 S026 Pass

Smoke Detector STORAGE 1491 1 M09 S027 Pass

Heat Detector MECHANICAL ROOM 1488 1 M09 S028 Pass

Smoke Detector STORAGE 1483 1 M09 S029 Pass

Smoke Detector ELECTRICAL ROOM 1428 1 M09 S030 Pass

Smoke Detector STORAGE 1418 1 M09 S031 Pass

Smoke Detector LOBBY 1402 1 M09 S032 Pass

Smoke Detector LOBBY 1402 1 M09 S033 Pass

Smoke Detector VAULT 1453 1 M09 S034 Pass

Smoke Detector AD STORAGE 1472 1 M09 S035 Pass

Smoke Detector IDF 1537 1 M09 S036 Pass

Smoke Detector ELECTRICAL ROOM 1474 1 M09 S037 Pass

Heat Detector BREAK ROOM 1469 1 M09 S038 Pass

Heat Detector MECHANICAL ROOM 2025 G M09 S039 Pass

Smoke Detector ELEC. ROOM 2026 2 M09 S040 Pass

Smoke Detector CORRIDOR 2400 2 M09 S041 Pass

Smoke Detector CORRIDOR 2400 2 M09 S042 Pass

Smoke Detector MDF 2023 2 M09 S043 Pass

Smoke Detector MECHANICAL ROOM 2020 2 M09 S044 Pass

Heat Detector CUSTODIAN 1058 1 M09 S045 Pass

Smoke Detector IDF 1534 B 1 M09 S046 Pass

Smoke Detector CHAIR STORAGE 1144 1 M09 S047 Pass

Duct Detector AUX GYM 0150 G M09 S048 Pass

Duct Detector AUX GYM 0150 G M09 S049 Pass

Duct Detector CORRIDOR 2400 2 M09 S050 Pass

Duct Detector CORRIDOR 2400 2 M09 S051 Pass

Duct Detector CORRIDOR 2400 2 M09 S052 Pass

Heat Detector MECHANICAL ROOM 1141 1 M09 S056 Pass

Duct Detector GYM TRACK 1 M09 S057 Pass

Duct Detector GYM TRACK 1 M09 S058 Pass

Duct Detector GYM TRACK 1 M09 S059 Pass

Duct Detector GYM TRACK 1 M09 S060 Pass

Duct Detector GYM TRACK 1 M09 S061 Pass

Duct Detector GYM TRACK 1 M09 S062 Pass

Duct Detector GYM TRACK 1 M09 S063 Pass

Duct Detector GYM TRACK 1 M09 S064 Pass

Smoke Detector IN STORAGE 1136 1 M09 S065 Pass

Heat Detector IN CONCESSIONS 1135 1 M09 S066 Pass

Duct Detector GYM MAIN LVL TRACK 1 M09 S069 Pass

Smoke Detector MECH ROOM 1141 1 M09 S070 Pass

Smoke Detector STORAGE 1134 1 M09 S071 Pass

Duct Detector MECH ROOM 1141 1 M09 S072 Pass

Smoke Detector STORAGE 0105 G M09 S075 Pass

Smoke Detector IDF 0103 G M09 S076 Pass

Smoke Detector MECHANICAL ROOM 0104 G M09 S077 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 271: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector CUSTODIAN 0144 G M09 S078 Pass

Smoke Detector STORAGE 0105 G M09 S079 Pass

Smoke Detector STORAGE 0102 G M09 S080 Pass

Heat Detector LAUNDRY 0124 G M09 S081 Pass

Smoke Detector CUSTODIAN 0131 G M09 S082 Pass

Smoke Detector ELECTRICAL ROOM 0142 G M09 S083 Pass

Smoke Detector STORAGE 0123 G M09 S084 Pass

Duct Detector CORR. 1100 1 M09 S085 Pass

Smoke Detector STORAGE 0122 G M09 S086 Pass

Smoke Detector ELEVATOR 2 LOBBY G M09 S087 Pass

Smoke Detector ELEVATOR MECHANICAL ROOM PH M09 S088 Pass

Heat Detector ELEVATOR 2 PIT G M09 S090 Pass

Duct Detector CORRIDOR 2400 2 M09 S091 Pass

Duct Detector MECH PENTHOUSE PH M09 S104 Pass

Duct Detector WEIGHT ROOM G M09 S150 Pass

Duct Detector WEIGHT ROOM G M09 S151 Pass

Pull Station STAIR 08 1216 1 M10 M002 Pass

Pull Station CORR 1200 AT STAIR 8 1216 1 M10 M003 Pass

Pull Station CORRIDOR 1200 1 M10 M004 Pass

Pull Station CORRIDOR 1250 1 M10 M005 Pass

Pull Station CORR 1250 AT STAIR 7 1275 1 M10 M006 Pass

Pull Station STAIR 7 1275 1 M10 M007 Pass

Pull Station STAIR 09 1257 1 M10 M009 Pass

Pull Station STAIR 11 1259 1 M10 M010 Pass

Pull Station CORRIDOR 1000 1 M10 M011 Pass

Pull Station STAIR 10 1204 1 M10 M012 Pass

Pull Station STAIR 7 2275 2 M10 M013 Pass

Pull Station STAIR 9 2257 2 M10 M014 Pass

Pull Station STAIR 10 2204 2 M10 M015 Pass

Pull Station STAIR 8 2216 2 M10 M016 Pass

Pull Station MECHANICAL PENTHOUSE PH M10 M028 Pass

Pull Station MECHANICAL PENTHOUSE PH M10 M029 Pass

Waterflow Switch MECHANICAL CORRIDOR 2240 2 M10 M030 Pass

Low Air MECHANICAL CORRIDOR 2240 2 M10 M031 Pass

Tamper Switch MECHANICAL CORRIDOR 2240 2 M10 M032 Pass

Smoke Detector ELECTRICAL 1217 1 M10 S001 Pass

Smoke Detector IDF 1215 * 1 M10 S002 Pass

Heat Detector CUSTODIAN 1213 1 M10 S003 Pass

Smoke Detector BOOK STORAGE 1218 1 M10 S004 Fail

Smoke Detector FIRE DOORS STAIR 8 1216 1 M10 S005 Pass

Smoke Detector FIRE DOORS STAIR 8 1216 1 M10 S006 Pass

Smoke Detector STORAGE 1228 1 M10 S007 Pass

Smoke Detector FIRE DOORS STAIR 7 1275 1 M10 S008 Pass

Smoke Detector FIRE DOORS STAIR 7 1275 1 M10 S009 Pass

Heat Detector LIFE SKILLS 1267 1 M10 S010 Pass

Smoke Detector FIRE DOORS STAIR 9 1257 1 M10 S011 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 272: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector FIRE DOORS STAIR 9 1257 1 M10 S012 Pass

Smoke Detector FIRE DOORS CORRIDOR 1250 1 M10 S013 Pass

Heat Detector TEACHER BREAK ROOM 1252 1 M10 S014 Pass

Smoke Detector FIRE DOORS CORRIDOR 1250 1 M10 S015 Pass

Smoke Detector STORAGE 1005 1 M10 S016 Pass

Smoke Detector BOOK STORAGE 1011 1 M10 S017 Pass

Smoke Detector ELEVATOR 2 LOBBY 1103 1 M10 S018 Pass

Smoke Detector FIRE DOORS CORRIDOR 1200 1 M10 S019 Pass

Smoke Detector FIRE DOORS CORRIDOR 1200 1 M10 S020 Pass

Smoke Detector FIRE DOORS STAIR 10 1204 1 M10 S021 Pass

Smoke Detector FIRE DOORS STAIR 10 1204 1 M10 S022 Pass

Smoke Detector FIRE DOORS STAIR 10 2204 2 M10 S023 Pass

Smoke Detector FIRE DOORS STAIR 10 2204 2 M10 S024 Pass

Smoke Detector FIRE DOORS CORRIDOR 2200 2 M10 S025 Pass

Smoke Detector FIRE DOORS CORRIDOR 2200 2 M10 S026 Pass

Smoke Detector IDF 2215 RPS 3 NAC 11 2 M10 S027 Pass

Smoke Detector ELECTRICAL 2213 2 M10 S028 Pass

Heat Detector CUSTODIAN 2217 2 M10 S029 Pass

Heat Detector BOOK STORAGE 2223 2 M10 S030 Pass

Smoke Detector FIRE DOORS STAIR 8 2216 2 M10 S031 Pass

Smoke Detector FIRE DOORS STAIR 8 2216 2 M10 S032 Pass

Smoke Detector STORAGE 2228 2 M10 S033 Pass

Smoke Detector FIRE DOORS STAIR 9 2257 2 M10 S034 Pass

Smoke Detector FIRE DOORS STAIR 9 2257 2 M10 S035 Pass

Heat Detector ELEVATOR 2 LOBBY 1103 1 M10 S036 Pass

Smoke Detector FIRE DOORS CORRIDOR 2500 2 M10 S037 Pass

Smoke Detector FIRE DOORS CORRIDOR 2500 2 M10 S038 Pass

Smoke Detector FIRE DOORS STAIR 7 2275 2 M10 S039 Pass

Smoke Detector FIRE DOORS STAIR 7 2275 2 M10 S040 Pass

Smoke Detector ELEVATOR 2 LVL2 LOBBY 2 M10 S041 Pass

Smoke Detector STORAGE 1512 1 M10 S042 Pass

Smoke Detector CHORAL STORAGE 1712 1 M10 S043 Pass

Smoke Detector LINEN STORAGE 1507 1 M10 S044 Pass

Heat Detector PROFESSIONAL FOODS 1502 1 M10 S045 Pass

Heat Detector PROFESSIONAL FOODS 1502 1 M10 S046 Pass

Smoke Detector FIRE DOORS PERFORMANCE CORR 1 M10 S047 Pass

Smoke Detector FIRE DOORS PERFORMANCE CORR 1 M10 S048 Pass

Smoke Detector MECHANICAL ROOM 1059 1 M10 S050 Pass

Pull Station MAIN ELECTRICAL RM 1143 1 M97 M001 Pass

Pull Station MAIN ELECTRICAL RM 1145 1 M97 M002 Pass

Pull Station CORRIDOR AT MAIN MECH 1145 1 M97 M003 Pass

Pull Station FOOD COURT 1320 1 M97 M004 Pass

Pull Station FOOD COURT 1320 1 M97 M005 Pass

Waterflow Switch FOOD PREP-1330 RISER ROOM 1 M97 M015 Pass

Low Air FOOD PREP-1330 RISER ROOM 1 M97 M016 Pass

Tamper Switch FOOD PREP-1330 RISER ROOM 1 M97 M017 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 273: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Monitor FOOD PREP-1330 KH 1 M97 M019

Pull Station FOOD PREP-1330 1 M97 M021 Pass

Pull Station BAND 1731 1 M97 M022 Pass

Pull Station DRAMA 1726 1 M97 M023 Pass

Pull Station THEATER 1050 AT STAIR 18 1 M97 M024 Pass

Pull Station THEATER 1050 AT STAIR 17 1 M97 M025 Pass

Pull Station THEATER 1050 AT CONTROL 1052 1 M97 M028 Pass

Pull Station THEATER 1050 AT CONTROL 1052 1 M97 M029 Pass

Pull Station THEATER 1050 ENTRANCE 1 M97 M032 Pass

Pull Station EXIT AT STAIR 20 1 M97 M033 Pass

Pull Station EXIT AT STAIR 20 2 M97 M036 Pass

Pull Station CORRIDOR 1000 1 M97 M039 Pass

Pull Station STAIR 4 1604 1 M97 M040 Pass

Pull Station CORRIDOR AT STAIR 2 1632 1 M97 M041 Pass

Pull Station STAIR 2 1632 1 M97 M042 Pass

Pull Station CORRIDOR AT STAIR 1 1669 1 M97 M043 Pass

Pull Station STAIR 1 1669 1 M97 M044 Pass

Pull Station STAIR 3 1653 1 M97 M045 Pass

Pull Station STAIR 3 2653 2 M97 M046 Pass

Pull Station STAIR 4 2604 2 M97 M047 Pass

Pull Station STAIR 2 2632 2 M97 M048 Pass

Pull Station STAIR 1 2669 2 M97 M049 Pass

Pull Station DRY STORAGE 1333 1 M97 M050 Pass

Pull Station STAIR 14 0114 G M97 M061 Pass

Pull Station MECHANICAL PENTHOUSE PH M97 M068 Pass

Pull Station MECHANICAL PENTHOUSE PH M97 M069 Pass

Tamper Switch PIV M97 M070 Pass

Waterflow Switch MAIN MECH. 1145 1 M97 M071 Pass

Tamper Switch MAIN MECH. 1145 1 M97 M072 Pass

Waterflow Switch MAIN MECH. 1145 1 M97 M073 Pass

Tamper Switch MAIN MECH. 1145 1 M97 M074 Pass

Waterflow Switch MAIN MECH. 1145 1 M97 M075 Pass

Tamper Switch MAIN MECH. 1145 1 M97 M076 Pass

Waterflow Switch MAIN MECH. 1145 1 M97 M077 Pass

Tamper Switch MAIN MECH. 1145 1 M97 M078 Pass

Waterflow Switch MAIN MECH. 1145 1 M97 M079 Pass

Tamper Switch MAIN MECH. 1145 1 M97 M080 Pass

Waterflow Switch MAIN MECH. 1145 1 M97 M081 Pass

Tamper Switch MAIN MECH. 1145 1 M97 M082 Pass

Tamper Switch MAIN MECH. 1145 1 M97 M083 PassWaterflow Switch MECH. CORRIDOR 2640 2 M97 M084 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 274: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Low Air MECH. CORR. 2640 2 M97 M085 Pass

Tamper Switch MECH. CORRIDOR 2640 2 M97 M086 Pass

Pull Station ENGINEERING LAB 1531 1 M97 M101 Pass

Pull Station CORRIDOR 1728 1 M97 M102 Pass

Smoke Detector ABOVE FACP 1 M97 S001 Pass

Smoke Detector MAIN. ELECTRICAL 1143 1 M97 S002 Pass

Smoke Detector MAIN MECHANICAL ROOM 1145 1 M97 S003 Pass

Heat Detector CUSTODIAN 1336 1 M97 S004 Pass

Heat Detector UTILITY 1337 1 M97 S005 Pass

Smoke Detector LOCKER 1339 1 M97 S006 Pass

Duct Detector FOOD COURT 1320 1 M97 S008 Pass

Duct Detector FOOD COURT 1320 1 M97 S009 Visual

Duct Detector FOOD COURT 1320 1 M97 S010 Pass

Duct Detector FOOD PREP 1330 1 M97 S011 Pass

Duct Detector FOOD PREP 1330 1 M97 S012 Pass

Duct Detector FOOD PREP 1330 1 M97 S013 Pass

Duct Detector FOOD PREP 1330 1 M97 S014 Pass

Smoke Detector ELECTRICAL ROOM 1343 1 M97 S015 Pass

Smoke Detector BULK STORAGE 1342 1 M97 S016 Pass

Smoke Detector DRY STORAGE 1333 1 M97 S017 Pass

Smoke Detector DRY STORAGE 1333 1 M97 S018 Pass

Smoke Detector FIRE DOORS FOOD PREP 1 M97 S019 Pass

Smoke Detector FIRE DOORS FOOD PREP 1 M97 S020 Pass

Heat Detector CUSTODIAN 1525 1 M97 S021 Pass

Heat Detector CUSTODIAN 1530 1 M97 S022 Pass

Smoke Detector CORRIDOR 1500 1 M97 S023 Pass

Smoke Detector CORRIDOR 1500 1 M97 S024 Pass

Smoke Detector ELECTRICAL ROOM 1 M97 S025 Pass

Smoke Detector IDF 1729 1 M97 S026 Pass

Heat Detector COMPRESSOR 1534A 1 M97 S027 Pass

Smoke Detector UNIFORM STORAGE 1732 1 M97 S028 Pass

Smoke Detector INSTRUMENT STORAGE 1733 1 M97 S029 Pass

Duct Detector STAGE 1060 1 M97 S030 Pass

Duct Detector STAGE 1060 1 M97 S031 Pass

Heat Detector PROP STORAGE 1720 1 M97 S032 Pass

Heat Detector PROP STORAGE 1720 1 M97 S033 Pass

Duct Detector STAGE 1060 1 M97 S034 Pass

Duct Detector PROP STORAGE 1720 1 M97 S035 Pass

Smoke Detector STORAGE 1731 1 M97 S036 Pass

Duct Detector UNIFORM STORAGE 1732 1 M97 S037 Pass

Duct Detector BAND 1731 1 M97 S038 Visual

Smoke Detector STAGE 1060 CLOSET 1 M97 S039 Pass

Heat Detector STAGE 1060 1 M97 S040 Pass

Smoke Detector STORAGE 1512 1 M97 S042 Pass

Smoke Detector CHORAL STORAGE 1712 1 M97 S043 Pass

Heat Detector PROFESSIONAL FOODS 1502 1 M97 S045 Pass

Heat Detector PROFESSIONAL FOODS 1502 1 M97 S046 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 275: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector PERFORMANCE CORR. 1 M97 S047 Pass

Smoke Detector PERFORMANCE CORR. 1 M97 S048 Pass

Smoke Detector MECHANICAL ROOM 1059 1 M97 S050 Pass

Smoke Detector ELECTRICAL ROOM 1051 1 M97 S051 Pass

Smoke Detector ELEVATOR 1 LOBBY 1 M97 S052 Pass

Duct Detector BAND 1731 1 M97 S053 Pass

Smoke Detector ELECTRICAL RM. 1529 1 M97 S054 Pass

Smoke Detector STORAGE 1053 1 M97 S055 Pass

Smoke Detector CONTROL 1052 1 M97 S056 Pass

Smoke Detector IDF 1523 1 M97 S057 Pass

Smoke Detector STORAGE 1520 1 M97 S058 Pass

Smoke Detector STORAGE 1516 1 M97 S059 Pass

Heat Detector KILN 1517 1 M97 S060 Pass

Smoke Detector DISPLAY 1030 1 M97 S061 Pass

Heat Detector STORAGE 1509 1 M97 S062 Pass

Smoke Detector CORR. 1500 1 M97 S063 Pass

Smoke Detector CORR. 1500 1 M97 S064 Pass

Smoke Detector CORR. 1600 1 M97 S065 Pass

Smoke Detector CORR. 1000B 1 M97 S066 Pass

Smoke Detector CORR. 1000B 1 M97 S067 Pass

Smoke Detector CORR. 1600 1 M97 S068 Pass

Smoke Detector STAIR 4 1604 1 M97 S069 Pass

Smoke Detector STAIR 4 1604 1 M97 S070 Pass

Smoke Detector SCIENCE PREP 1607 1 M97 S071 Pass

Smoke Detector IDF 1612 1 M97 S072 Pass

Smoke Detector SCIENCE PREP 1610 1 M97 S073 Pass

Smoke Detector ELECTRICAL RM. 1662 1 M97 S074 Pass

Smoke Detector SCIENCE PREP 1617 1 M97 S075 Pass

Smoke Detector STAIR 2 1632 1 M97 S076 Pass

Smoke Detector STAIR 2 1632 1 M97 S077 Pass

Smoke Detector STAIR 1 1669 1 M97 S078 Pass

Smoke Detector STAIR 1 1669 1 M97 S079 Pass

Smoke Detector IDF 1664 1 M97 S080 Pass

Smoke Detector SCIENCE PREP 1662 1 M97 S081 Pass

Smoke Detector SCIENCE PREP 1654 1 M97 S082 Pass

Smoke Detector STAIR 3 1653 1 M97 S083 Pass

Smoke Detector STAIR 3 1653 1 M97 S084 Pass

Smoke Detector AT CORRIDOR 1650 1 M97 S085 Pass

Smoke Detector AT CORRIDOR 1650 1 M97 S086 Pass

Smoke Detector AT STAIR 3 2653 2 M97 S087 Pass

Smoke Detector STAIR 3 2653 2 M97 S088 Pass

Smoke Detector AT CORRIDOR 2650 2 M97 S089 Pass

Smoke Detector CORRIDOR 2650 2 M97 S090 Pass

Heat Detector TEACHER WORK RM 2700 2 M97 S091 Pass

Heat Detector TEACHER BREAK ROOM 2702 2 M97 S092 Pass

Smoke Detector AT STAIR 14 1 M97 S093 Pass

Smoke Detector AT STAIR 14 2 M97 S094 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 276: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector STORAGE 2046 2 M97 S095 Pass

Smoke Detector ELEVATOR 1 LOBBY 2045 2 M97 S096 Pass

Smoke Detector ELEVATOR 1 SHAFT 2 M97 S097 Pass

Heat Detector ELEVATOR 1 LOBBY 1 M97 S098 Pass

Smoke Detector STORAGE 2047 2 M97 S099 Pass

Smoke Detector CORRIDOR 2600 2 M97 S100 Pass

Smoke Detector CORRIDOR 2600 2 M97 S101 Pass

Smoke Detector STAIR 4 2604 2 M97 S102 Pass

Smoke Detector STAIR 4 2604 2 M97 S103 Pass

Heat Detector SCIENCE PREP 2607 2 M97 S104 Pass

Smoke Detector IDF 2612 2 M97 S105 Pass

Heat Detector SCIENCE PREP 2610 2 M97 S106 Pass

Heat Detector CENTRAL PREP 2616 2 M97 S107 Pass

Smoke Detector ELECTRICAL 2619 2 M97 S108 Pass

Heat Detector SCIENCE PREP 2617 2 M97 S109 Pass

Smoke Detector STAIR 2 2632 2 M97 S110 Pass

Smoke Detector STAIR 2 2632 2 M97 S111 Pass

Smoke Detector STAIR 1 2669 2 M97 S112 Pass

Smoke Detector STAIR 1 2669 2 M97 S113 Pass

Smoke Detector IDF 2664 2 M97 S114 Pass

Heat Detector SCIENCE PREP 2662 2 M97 S115 Pass

Heat Detector ELECTRICAL ROOM 2656 2 M97 S116 Pass

Heat Detector SCIENCE PREP 2654 2 M97 S117 Pass

Duct Detector LINEN STORAGE 1507 1 M97 S118 Pass

Duct Detector CULINARY CLASSROOM 1505 1 M97 S119 Pass

Duct Detector CORRIDOR 1500 1 M97 S120 Pass

Duct Detector CORRIDOR 1500 1 M97 S121 Pass

Duct Detector CORRIDOR 1500 1 M97 S122 Pass

Duct Detector CORRIDOR 1500 1 M97 S123 Pass

Smoke Detector ELECTRICAL 1656 1 M97 S124 Pass

Duct Detector MECH PENTHOUSE ERU PH M97 S125 Pass

Duct Detector MECH PENTHOUSE ERU PH M97 S126 Pass

Duct Detector MECH PENTHOUSE ERU PH M97 S127 Pass

Duct Detector MECH PENTHOUSE ERU PH M97 S128 Pass

Duct Detector MECH PENTHOUSE ERU PH M97 S129 Pass

Duct Detector RTU-70 AG TECH CLASSRM 1511 1 M97 S130 Pass

Smoke Detector ELEVATOR (ROOF) LOBBY PH M97 S131 Pass

Smoke Detector PROP STORAGE 1720 1 M97 S132 Pass

Heat Detector ELEVATOR 1 PIT 1 M97 S136 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 277: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

testing.

(1) Smoke detector (M10:S004) on 1st Floor in Book Storage Room 1218 fails to activate from smoke

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 278: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 279: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

3 0

3 0

5 0

2 0

Inspector Name : Signature:

(678) 691-0011

645 Mullinax Road

30004

Silent Knight

Elec. Rm 4147

Model Name

Alpharetta GA

Is the Panel Monitored Yes

IFP-2000

EI1273 / WO# 156056

Panel Power Loss

VISTA-128FBP

Heat Detectors Silent Knight IDP-HEAT

DACT

Denmark High School ( Animal ) - Science Building

7/31/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Silent Knight

Yes

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing Monitoring Company & Office Staff

Batteries SLA1116

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

IDP-PULL-DA

Honeywell

David Piorkowski

Pass

Pullstations

Smoke Detectors IDP-PHOTO

Imterstate Batteries

IFP-2000Control Panel

Pass

Device

Silent Knight

Interface Equipment

David Piorkowski

Silent Knight

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 280: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.4 Pass

Good (2019) 13.5 Pass

Good (2019) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 20AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

12V 20AH

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

DACT

FACP (Right) 12V 20AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 281: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Smoke Detector MECH / ELEC 4127 1 M97 S001 Pass

Smoke Detector STORAGE 4122 1 M97 S002 Pass

Smoke Detector EXAM / TREATMENT 4120 1 M97 S003 Pass

Smoke Detector EXAM / TREATMENT 4120 1 M97 S004 Pass

Heat Detector GROOMING 4123 1 M97 S005 Pass

Heat Detector AGRICULTURAL MECHANICS 4126 1 M97 S006 Pass

Smoke Detector EXAM / TREATMENT CLOSET 1 M97 S007 Pass

Pull Station AGRICULTURAL MECHANICS 4126 1 M97 M001 Pass

Pull Station EXIT AT RESTROOMS 1 M97 M002 Pass

Pull Station EXAM / TREATMENT 4120 1 M97 M003 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 282: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 283: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 284: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 285: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 286: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 287: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 288: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 289: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

3 0

12 0

5 0

1 0

Inspector Name : Signature: David Piorkowski

Pass

Pullstations

Smoke Detectors IDP-PHOTO

Power Sonic

IFP-2000Control Panel

Pass

Device

Silent Knight

Interface Equipment

David Piorkowski

Silent Knight

Monitoring Company & Office Staff

Batteries PS-12180

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Honeywell

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Yes

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing

Panel Power Loss

VISTA-128FBP

Heat Detectors Silent Knight IDP-HEAT

DACT

Silent Knight

IDP-PULL-DA

(678) 691-0011

645 Mullinax Road

30004

Silent Knight

Elec. Rm 4046

Model Name

Alpharetta GA

Is the Panel Monitored Yes

IFP-2000

EI1273 / WO #156056

Forsyth County School - Denmark High School Field House

7/31/2020

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 290: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2018) 13.4 Pass

Good (2018) 13.5 Pass

Good (2017) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

12V 20AH

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

DACT

FACP (Right) 12V 18AH

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Magnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 18AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 291: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Smoke Detector VISITOR - ELEC 4046 ABOVE FACP 1 M97 S001 Pass

Smoke Detector VISITOR - UTILITY 4045 1 M97 S002 Pass

Smoke Detector VISITOR - STORAGE 4047 1 M97 S003 Pass

Smoke Detector VISITOR - STORAGE 4048 1 M97 S004 Pass

Smoke Detector TICKET BOOTH 4001 1 M97 S005 Pass

Heat Detector CONCESSIONS 4000 1 M97 S006 Pass

Pull Station ELECTRICAL 4046 1 M97 M007 Pass

Pull Station VISITOR - TEAM LOCKER 1 M97 M008 Pass

Pull Station VISITOR - STORAGE 4048 1 M97 M009 Pass

Pull Station VISITOR - GIRLS LOCKER 4020 1 M97 M010 Pass

Pull Station VISITOR - BOYS LOCKER 4022 1 M97 M011 Pass

Pull Station VISITOR - MEN 4024 1 M97 M012 Pass

Pull Station TICKET BOOTH 4001 1 M97 M013 Pass

Pull Station TICKET BOOTH 4000 1 M97 M014 Pass

Pull Station CONCESSIONS 4000 1 M97 M015 Pass

Pull Station HOME - VEST 4000 1 M97 M016 Pass

Pull Station HOME - TRAINING 4016 1 M97 M017 Pass

Pull Station HOME - COACH'S OFFICE 4010 1 M97 M018 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 292: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 293: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 294: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 295: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 296: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 297: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 298: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 299: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 2 0

6 6

36 0

11 0

11 0

3 0

3 0

Inspector Name : Signature:

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

PotterWaterflow VSR -F

All-Star Fire, LLC

Ultra Power

Simplex 4099-9006

UL12180

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

1994 Peachtree Parkway

Big Creek Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredElect rm 177

Model Name 4010Simplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

4098-9685

Tamper Kennedy TBD

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

30041

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

6/26/2020

EI1273 / WO #155437

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 300: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Poor (2017) 13 Fail

Poor (2017) 13 Fail

Poor (2019) 13 Fail

Poor (2019) 12.9 Fail

Poor (2019) 12.8 Fail

Poor (2019) 12.8 Fail

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

N/A

Pass

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

Fire Pump Power Loss

FCPS (left) #2

FCPS (right) #2

12v 7ah

12v 7ah

Correct Switching and Operation Verified

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FACP (left)

12v 18ahFACP (right)

12v 18ah

12v 7ah

FCPS (right) #1

FCPS (left) #1

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 301: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station 400 Hall Exit @ rm 456 1 M1-8 Pass

Duct Detector Rm 142 ERU supply 1 M1-32 Not Found

Duct Detector Rm 142 ERU return 1 M1-33 Not Found

Duct Detector Rm 262 ERU supply 1 M1-40 Pass

Duct Detector Rm 262 ERU return 1 M1-41 Pass

Duct Detector Rm 450 ERU supply 1 M1-42 Pass

Duct Detector Rm 450 ERU return 1 M1-43 Pass

Duct Detector Rm 505 ERU supply 1 M1-49 Pass

Duct Detector Rm 505 ERU return 1 M1-50 Pass

Duct Detector Crawl Space AHU bldg 500 1 M1-55 Visual

Duct Detector Kitchen Dry Storage 1 M1-59 Pass

Duct Detector Gym AHU 1 M1-60 Visual

Smoke Detector 400 Hall Smoke dr @ rm 427 1 M1-101 Pass

Smoke Detector 400 Hall Smoke dr @ rm 427 1 M1-102 Pass

Smoke Detector 100 Hall Smoke dr @ rm 104 1 M1-103 Pass

Smoke Detector 100 Hall Smoke dr @ rm 143 1 M1-104 Pass

Smoke Detector 100 Hall Smoke dr @ rm 152 1 M1-105 Pass

Smoke Detector 100 Hall Smoke dr @ rm 154 1 M1-106 Pass

Smoke Detector Elect rm 177 @ FACP 1 M1-107 Pass

Smoke Detector Outside Boiler rm 165 1 M1-108 Pass

Smoke Detector 400 Hall @ rm 448 1 M1-109 Pass

Smoke Detector 400 Hall @ rm 456 1 M1-110 Pass

Smoke Detector 400 Hall @ rm 462 1 M1-111 Pass

Pull Station 100 Main Lobby Exit 1 M1-1 Pass

Pull Station 100 Hall Exit @ rm 121 1 M1-2 Pass

Pull Station 400 Hall Exit @ rm 401 1 M1-3 Pass

Pull Station 400 Hall Exit @ rm 415 1 M1-4 Pass

Pull Station 400 Hall Exit @ rm 427 1 M1-5 Pass

Pull Station 400 Hall Exit @ rm 434 1 M1-6 Pass

Pull Station 400 Hall Exit @ rm 466 1 M1-7 Pass

Pull Station 400 Hall Exit @ rm 456 1 M1-8 Pass

Pull Station 100 Hall Exit @ Cafe 154 1 M1-9 Pass

Pull Station 300 Gym Exit @ rm 301 1 M1-10 Pass

Pull Station 300 Gym West Side Exit 1 M1-11 Pass

Pull Station 300 Gym East Side Exit 1 M1-12 Pass

Pull Station 100 Kitchen Exit 156 1 M1-13 Pass

Pull Station 100 Cafeteria Exit 154 1 M1-14 Pass

Pull Station 100 Hall Exit @ rm 153 1 M1-15 Pass

Pull Station 100 Main Office Exit 120 1 M1-16 Pass

Pull Station 200 Media Center Exit 210 1 M 1-17 Pass

Pull Station 200 Hall Exit @ rm 228 1 M1-18 Pass

Pull Station 200 Hall Exit @ rm 201 1 M1-19 Pass

Pull Station Hall Exit between 100 & 200 1 M1-20 Pass

Pull Station 100 Hall Exit @ rm 178 1 M1-21 Pass

Ansul Kitchen Hood 1 M1-22 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 302: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station 100 Main Off 120 @ Counter 1 M1-24 Pass

Pull Station 200 Hall Exit to Playground 1 M1-25 Pass

Pull Station 200 Hall Exit @ rm 231 1 M1-26 Pass

Pull Station 200 Hall Exit @ rm 248 1 M1-27 Pass

Pull Station 200 Hall Exit @ rm 238 1 M1-28 Pass

Pull Station 200 Hall Exit @ rm 275 1 M1-29 Pass

Pull Station 200 N/E Hall Exit @ rm 290 1 M1-30 Pass

Pull Station 200 N/W Hall Exit @ rm 290 1 M1-31 Pass

Pull Station Multipurpose rm 290 @ Stor rm 292 1 M 1-34 Pass

Pull Station Multipurpose rm 290 @ Stor rm 291 1 M1-35 Pass

Flow Switch 100 Boiler rm 165 1 M1-36 Pass

Flow Switch 100 Boiler rm 165 1 M1-37 Pass

Tamper Switch 100 Boiler rm 165 1 M1-38 Pass

Tamper Switch 100 Boiler rm 165 1 M1-39 Pass

Pull Station 500 Auditorium Exit 502 1 M1-51 Pass

Pull Station 500 Auditorium Exit 502 1 M1-52 Pass

Pull Station 500 Hall Exit @ rm 503 1 M1-53 Pass

Pull Station 500 Side Hall Exit @ rm 506 1 M 1-54 Pass

Flow Switch 500 Auditorium Storage rm 1 M1-56 Pass

Tamper Switch 500 Auditorium Storage rm 1 M1-57 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 303: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. 6 Batteries failed load test.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 304: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 305: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 1 0

4 0

23 0

10 0

8 0

2 0

2 0

Inspector Name : Signature:

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

PotterWaterflow VSR-F

All-Star Fire, LLC

Interstate

Simplex 4099-9006

SLA1115

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010 ES

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

3740 Melody Mizer Lane

Daves Creek Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name 4010ESSimplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

4098-9685

Tamper Kennedy TBD

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

30041

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

6/26/2020

EI1273 / WO # 155443

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 306: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.1 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

See note

N/A

N/A

Pass

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

Fire Pump Power Loss

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FACP (left)

12v 18ahFACP (right)

12v 18ah

12v 7ah

FCPS (right) rm 407

FCPS (left) rm 407

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Supervisory Signals

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Correct Switching and Operation Verified

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 307: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station Main Entry 1 M2-1 Pass

Duct Detector Riser rm 101 1 M2-2 Pass

Pull Station Media Center 120 1 M2-3 Pass

Pull Station 400 Hall @ Girls RR 408 1 M2-4 Pass

Pull Station 400 Hall Exit @ rm 401 1 M2-5 Pass

Pull Station 400 Hall Exit @ Vestibule 421 1 M2-6 Pass

Smoke Detector 400 Hall @ rm 434 1 M2-7 Pass

Smoke Detector 400 Hall @ rm 436 1 M2-8 Pass

Pull Station 400 Hall Exit @ Art rm 1 M2-9 Pass

Pull Station 400 Hall Exit @ Music rm 1 M2-10 Pass

Smoke Detector 400 Hall @ Smoke Doors By Cafe 1 M2-11 Pass

Smoke Detector 400 Hall Cafe Smoke Doors 1 M2-12 Pass

Pull Station Cafe Exit 1 M2-13 Pass

Pull Station Kitchen Exit 1 M2-14 Pass

Pull Station 300 Hall @ Conference Rm 343 1 M2-15 Pass

Pull Station 300 Hall @ Teachers Lounge 1 M2-16 Pass

Pull Station 300 Hall @ rm 301 1 M2-17 Pass

Smoke Detector Cafe Smoke Doors @ Restrooms 1 M2-18 Pass

Smoke Detector Smoke Doors @ rm 158 1 M2-19 Pass

Pull Station Gym @ 200 Hall 1 M2-20 Pass

Pull Station Gym Exit 1 M2-21 Pass

Pull Station Rear Gym Exit 1 M2-22 Pass

Pull Station Gym Elect rm 1 M2-23 Pass

Pull Station 200 Hall Exit @ rm 241 1 M2-24 Pass

Pull Station Faculty Lounge @ rm 133 1 M2-25 Pass

Smoke Detector Smoke Doors @ Work rm 1 M2-26 Pass

Smoke Detector 200 Hall Smoke Doors @ Work rm 1 M2-27 Pass

Pull Station 200 Hall Exit @ rm 213 1 M2-28 Pass

Pull Station 200 Hall Exit @ rm 201 1 M2-29 Pass

Pull Station 200 Hall Exit to 300 Hall 1 M2-30 Pass

Pull Station Gym @ 400 Hall 1 M2-31 Pass

Pull Station Gym Exit @ rm 164 1 M2-32 Pass

Duct Detector Hall 150 @ rm 158 1 M2-33 Pass

Ansul Kitchen Hood 1 M2-34 Visual

Duct Detector Gym Restroom 1 M2-35 Pass

Duct Detector 300 Hall in rm 314 ERU 1 1 M2-36 Pass

Duct Detector 200 Hall in rm 224 ERU 2 1 M2-37 Not Found

Duct Detector Cafe @ Kitchen 1 M2-38 Visual

Duct Detector 200 Hall in rm 224 ERU 2 1 M2-39 Not Found

Tamper Riser 1 1 M2-40 Pass

Tamper Riser 2 1 M2-41 Pass

Duct Detector 300 Hall in rm 314 ERU 1 1 M2-42 Pass

Duct Detector 400 Hall in rm 403 ERU 4 1 M2-43 Visual

Duct Detector 400 Hall in rm 403 ERU 4 1 M2-44 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 308: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Could not test HVAC shutdown as air handlers are turned off.

Deficiencies

None.

Note:

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 309: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 310: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 5 0

14 0

27 0

28 0

92 0

1 0

Inspector Name : Signature:

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/13/2020

EI1273 / WO #155442

4098-9685

Other

Batteries

Pullstations

SimplexSmoke Detectors 4098-9757

Duct Detectors Simplex

Pass

540 Dahlonega Street

Cumming Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office Hall

Model Name 4010Simplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

All-Star Fire, LLC

Power Patrol

Simplex 4099-9004

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

SimplexVoice Evac 4003

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 311: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13 Pass

Good (2020) 13 Pass

Good (2020) 13.2 Pass

Good (2020) 13.2 Pass

Good (2020) 13.1 Pass

Good (2020) 13.1 Pass

Good (2020) 13.1 Pass

Good (2020) 13.1 Pass

Good (2020) 13.4 Pass

Good (2020) 13.3 Pass

Good (2020) 12.9 Pass

Good (2020) 13.1 Pass

Good (2020) 13 Pass

Good (2020) 13.1 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

N/A

Pass

N/A

N/A

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FCPS (right) #1 rm 581

FCPS (left) #1 rm 581

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 435

FCPS (right) #2 rm 435

FCPS (left) #3 rm 676

FCPS (right) #3 rm 676

12v 7ah

12v 7ah

12v 7ah

FCPS (right) #4 rm 672

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

12v 7ah

Voice Evac rm 552 12v 7ah

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #5 rm 455

FCPS (left) #4 rm 672

FCPS (left) #5 rm 455

Voice Evac rm 552

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 312: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Smoke Detector 2nd Grade Corr 1 M1-2 Pass

Smoke Detector 2nd Grade Corr 1 M1-3 Pass

Duct Detector 2nd Grade Corr 1 M1-4 Pass

Duct Detector 2nd Grade Corr 1 M1-5 Pass

Smoke Detector 2nd Grade Corr 1 M1-6 Pass

Smoke Detector Communication rm 455 1 M1-7 Pass

Smoke Detector Elect rm 457 1 M1-8 Pass

Smoke Detector 2nd Grade Corr 1 M1-9 Pass

Smoke Detector Book rm 302 1 M1-10 Pass

Smoke Detector Storage rm 470 1 M1-12 Pass

Smoke Detector Left Hub 1 M1-13 Visual

Duct Detector Music rm 462 1 M1-14 Pass

Smoke Detector Left Hub 1 M1-15 Pass

Smoke Detector Left Hub 1 M1-16 Pass

Smoke Detector Media Prod rm 531 1 M1-17 Pass

Smoke Detector Computer Network rm 535 1 M1-18 Pass

Smoke Detector Audio/visual Stor rm 536 1 M1-19 Pass

Duct Detector Foyer 1 M1-21 Not found

Duct Detector Foyer 1 M1-22 Not found

Duct Detector Foyer 1 M1-24 Pass

Duct Detector Foyer 1 M1-25 Pass

Smoke Detector Left Hub 1 M1-27 Visual

Smoke Detector Left Hub 1 M1-28 Visual

Smoke Detector Storage rm 256 1 M1-29 Pass

Smoke Detector Storage rm 253 1 M1-30 Pass

Smoke Detector Storage rm 1 M1-31 Pass

Smoke Detector 1st Grade Corr 1 M1-33 Pass

Smoke Detector 1st Grade Corr 1 M1-35 Pass

Smoke Detector 1st Grade Corr 1 M1-36 Pass

Smoke Detector 1st Grade Corr 1 M1-37 Pass

Duct Detector 1st Grade Corr 1 M1-38 Not found

Duct Detector 1st Grade Corr 1 M1-39 Not found

Smoke Detector 1st Grade Corr 1 M1-40 Pass

Smoke Detector Kindergarten Corr 1 M1-44 Pass

Smoke Detector Kindergarten Corr 1 M1-46 Pass

Smoke Detector Book rm 101 1 M1-48 Pass

Smoke Detector Kindergarten Corr 1 M1-49 Pass

Duct Detector Kindergarten Corr 1 M1-50 Pass

Duct Detector Kindergarten Corr 1 M1-51 Pass

Smoke Detector Elect rm 433 1 M1-52 Pass

Smoke Detector Communication rm 435 1 M1-53 Pass

Smoke Detector Kindergarten Corr 1 M1-54 Pass

Smoke Detector 1st Grade Corr 1 M1-55 Pass

Smoke Detector Kindergarten Corr 1 M1-56 Pass

Smoke Detector Gym Vestibule 1 M1-60 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 313: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Gym rm 580 1 M1-61 Pass

Smoke Detector Elect rm 581 1 M1-63 Pass

Smoke Detector Right Hub 1 M1-65 Pass

Smoke Detector Right Hub 1 M1-66 Visual

Smoke Detector Right Hub 1 M1-67 Visual

Smoke Detector Communication rm 676 1 M1-68 Pass

Smoke Detector Elect rm 677 1 M1-69 Pass

Smoke Detector Storage rm 679 1 M1-70 Pass

Smoke Detector Storage rm 668 1 M1-71 Pass

Smoke Detector Book rm 902 1 M1-73 Pass

Smoke Detector 3rd Grade Corr 1 M1-74 Pass

Smoke Detector 3rd Grade Corr 1 M1-75 Pass

Smoke Detector 3rd Grade Corr 1 M1-76 Pass

Smoke Detector 3rd Grade Corr 1 M1-77 Pass

Smoke Detector 3rd Grade Corr 1 M1-78 Pass

Smoke Detector 4th Grade Corr 1 M1-80 Pass

Smoke Detector 4th Grade Corr 1 M1-81 Pass

Smoke Detector 4th Grade Corr 1 M1-82 Pass

Smoke Detector 5th Grade Corr 1 M1-84 Pass

Smoke Detector 5th Grade Corr 1 M1-85 Pass

Smoke Detector Book rm 701 1 M1-87 Pass

Smoke Detector 5th Grade Corr 1 M1-88 Pass

Smoke Detector 5th Grade Corr 1 M1-89 Pass

Duct Detector 5th Grade Corr 1 M1-90 Not found

Duct Detector 5th Grade Corr 1 M1-91 Not found

Smoke Detector 5th Grade Corr 1 M1-92 Pass

Smoke Detector Elect rm 671 1 M1-93 Pass

Smoke Detector Communication rm 672 1 M1-94 Pass

Smoke Detector Communication rm 673 1 M1-95 Pass

Smoke Detector Elect rm 674 1 M1-96 Pass

Duct Detector 4th Grade Corr 1 M1-97 Pass

Smoke Detector 4th Grade Corr 1 M1-98 Pass

Duct Detector 4th Grade Corr 1 M1-99 Pass

Smoke Detector Storage rm 629 1 M1-103 No Access

Smoke Detector Right Hub 1 M1-104 Visual

Smoke Detector Right Hub 1 M1-105 Pass

Smoke Detector Right Hub 1 M1-106 Pass

Smoke Detector Storage rm 623 1 M1-107 Pass

Smoke Detector Storage rm 552 1 M1-108 Pass

Smoke Detector Gym Corr 1 M1-109 Pass

Smoke Detector Gym Corr 1 M1-110 Pass

Smoke Detector Main Elect rm 572 1 M1-111 Pass

Smoke Detector Gym Corr 1 M1-114 Pass

Smoke Detector Gym 1 M1-115 Pass

Smoke Detector 2nd Grade Corr 1 M1-116 Pass

Duct Detector 3rd Grade Corr 1 M1-117 Pass

Duct Detector 3rd Grade Corr 1 M1-118 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 314: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Right Hub 1 M1-119 Visual

Smoke Detector Elect rm 451 1 M1-122 Pass

Smoke Detector Outside Storage rm 1 M1-123 No Access

Smoke Detector Communication rm 453 1 M1-125 Pass

Duct Detector Kitchen 1 M1-127 Not found

Duct Detector Kitchen 1 M1-128 Not found

Smoke Detector Chem Wash rm 566 1 M1-129 Pass

Smoke Detector Cust rm 565 1 M1-130 Pass

Smoke Detector Office Left Smoke drs 1 M1-156 Pass

Smoke Detector Office Left Smoke drs 1 M1-157 Pass

Smoke Detector Cafe Left Smoke drs 1 M1-158 Pass

Smoke Detector Cafe Left Smoke drs 1 M1-159 Pass

Smoke Detector Cafe Left Smoke drs 1 M1-160 Pass

Smoke Detector Cafe Left Smoke drs 1 M1-161 Pass

Smoke Detector Office Right Smoke drs 1 M1-162 Pass

Smoke Detector Office Right Smoke drs 1 M1-163 Pass

Smoke Detector Cafe Right Smoke drs 1 M1-164 Pass

Smoke Detector Cafe Right Smoke drs 1 M1-165 Pass

Smoke Detector Cafe Right Smoke drs 1 M1-166 Pass

Smoke Detector Cafe Right Smoke drs 1 M1-167 Pass

Duct Detector Kitchen 1 M1-220 Not found

Duct Detector Gym 1 M1-221 Not found

Pull Station 2nd Grade Corr Exit 1 M1-1 Pass

Pull Station Left Hub Exit 1 M1-11 Pass

Pull Station Foyer Right Exit 1 M1-20 Pass

Pull Station Foyer Exit 1 M1-23 Pass

Pull Station Foyer Left Exit 1 M1-26 Pass

Pull Station 1st Grade Corr 1 M1-32 Pass

Pull Station 1st Grade Corr 1 M1-34 Pass

Pull Station Kindergarten Corr 1 M1-45 Pass

Pull Station Left Hub 1 M1-47 Pass

Pull Station 4th Grade Corr 1 M1-57 Pass

Pull Station Can wash room 466 1 M1-58 Pass

Suppression Press Main kitchen hood 1 M1-59 Visual

Pull Station Gym Vestibule 1 M1-62 Pass

Suppression Press Right Hub Kitchen Room 644 1 M1-64 Visual

Pull Station Right Hub 1 M1-72 Pass

Pull Station 3rd Grade Corr Exit 1 M1-79 Pass

Pull Station 5th Grade Corr 1 M1-83 Pass

Pull Station Right Hub 1 M1-86 Pass

Pull Station Main Elect rm 572 1 M1-112 Pass

Pull Station Gym Corr 1 M1-113 Pass

Pull Station Main Elec rm 572 1 M1-120 Pass

Sprinkler Monitor Main Elec rm 572 1 M1-121 Not found

Pull Station Outside Storage rm 1 M1-124 No Access

Pull Station Gym Room 580 1 M1-126 Pass

Pull Station Kitchen Recieving door 1 M1-131 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 315: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station Cafeteria side exit 1 M1-132 Pass

Pull Station Multi-Purpose Room 587 1 M1-133 Pass

Pull Station Multi-Purpose Room 587 1 M1-134 Pass

Pull Station Gym Room 580 1 M1-135 Pass

Pull Station Cafeteria exit 1 M1-136 Pass

Tamper Switch Outside P.I.V. 1 M1-137 Not found

Fire Monitor Zone Storage rm 552 (4003) 1 M1-138 Not found

Duct Detector ERU 1 Mech rm 201 1 M1-141 Pass

Duct Detector ERU 2 Mech rm 216 1 M1-143 Not found

Duct Detector ERU 3 Mech rm 317 1 M1-145 Not found

Duct Detector ERU 4 Mech rm 713 1 M1-147 Not found

Duct Detector ERU 5 Mech rm 813 1 M1-149 Not found

Duct Detector ERU 6 Mech rm 913 1 M1-169 Not found

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 316: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 317: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 318: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

4 0

18 0

10 0

23 0

2 0

2 0

Inspector Name : Signature:

EI1273 / WO # 155441

6/10/2020

Coal Mountain Elementary Schools

Pass

Monitoring Company & Office Staff

3455 Coal Mountain Drive

30028

Simplex

Office Hallway outside room 115

Model Name

Cumming GA

Is the Panel Monitored Yes

System Sensor OSY2

Waterflow Switches System Sensor WFD40

Loss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Duct Detectors Simplex 4098-9753

Simplex

Simplex

2099-9101

Batteries FAS1075

All- Star Fire LLC

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Pass

Panel Power Loss

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing

(678) 691-0011

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

4010

Pass

Pass

Panel Secondary power loss

Open Circuit Detection

Power Supplies

Open Circuits are Detected by Fire Alarm Control Panel

Model

Device Summary

Manufacturer

Interfaced Equipment Tested for Circuit Supervision Pass

4009

David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Power Patrol

4010Control Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Simplex

Ground fault

Tamper Switches

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 319: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.6 Pass

Good (2019) 13.5 Pass

Good (2019) 13.6 Pass

Good (2019) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

Pass

N/A

N/AFM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7A

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

12V 7A

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

FACP (Right)

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Kitchen Hoods

Location Size

Magnetic Door Holders

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

BPS #1 Rm 131 (Left) 12V 7A

12V 7A

Fire Pump Trouble

Fire Pump Phase Reversal

BPS #1 Rm 131 (Right)

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 320: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Tamper Switch SPRINKLER RISER 1 MAIN MECH RM 131 1 M1 1 Pass

Waterflow Switch SPRINKLER RISER 1 MAIN MECH RM 131 1 M1 2 Pass

Tamper Switch SPRINKLER RISER 2 MAIN MECH RM 131 1 M1 3 Pass

Waterflow Switch SPRINKLER RISER 2 MAIN MECH RM 131 1 M1 3 Pass

Pull Station KITCHEN 1 M1 4 Pass

Duct Detector CAFÉ 1 M1 6 Pass

Pull Station MAIN HALL 1 M1 7 Pass

Pull Station MAIN HALL 1 M1 8 Pass

Duct Detector MAIN HALL 1 M1 9 Pass

Duct Detector MAIN HALL 1 M1 10 Pass

Smoke Detector MAIN HALL 1 M1 11 Pass

Smoke Detector MAIN HALL 1 M1 12 Pass

Duct Detector MAIN HALL 1 M1 13 Pass

Smoke Detector MAIN HALL 1 M1 14 Pass

Pull Station MAIN HALL 1 M1 15 Pass

Smoke Detector MAIN HALL 1 M1 16 Pass

Duct Detector CORRIDOR 126 1 M1 20 Pass

Pull Station CORRIDOR 133 EXIT 1 M1 21 Pass

Duct Detector CORRIDOR 133 1 M1 22 Pass

Pull Station CORR 133 @ COURTYARD 1 M1 23 Pass

Duct Detector 5TH GRADE HALL 1 M1 26 Pass

Pull Station CORR 126 1 M1 27 Pass

Duct Detector REAR ELECTRICAL RM 1 M1 28 Pass

Pull Station 5TH GRADE HALL 1 M1 29 Pass

Duct Detector 5TH GRADE HALL 1 M1 30 Pass

Pull Station ENTRANCE CORR 118 1 M1 33 Pass

Duct Detector ENTRANCE CORR 118 1 M1 34 Pass

Pull Station ENTRANCE CORR 118 1 M1 35 Pass

Pull Station LIBRARY 1 M1 36 Pass

Pull Station LIBRARY 1 M1 37 Pass

Duct Detector ADMIN OFFICE HALL 1 M1 38 Pass

Pull Station ADMIN OFFICE ENTRANCE 1 M1 39 Pass

Pull Station ADMIN OFFICE ENTRANCE 1 M1 40 Pass

Duct Detector MAIN HALL 1 M1 41 Pass

Duct Detector MAIN HALL 1 M1 42 Pass

Duct Detector CAFÉ 1 M1 43 Pass

Duct Detector CAFÉ 1 M1 44 Pass

Smoke Detector MAIN HALL 1 M1 45 Pass

Smoke Detector MAIN HALL 1 M1 46 Pass

Duct Detector MAIN HALL 1 M1 47 Pass

Pull Station 5TH GRADE HALL 1 M1 48 Pass

Smoke Detector 5TH GRADE HALL 1 M1 49 Pass

Smoke Detector 5TH GRADE HALL 1 M1 50 Pass

Pull Station 5TH GRADE HALL 1 M1 51 Pass

Pull Station CAR LOADING AREA 1 M1 52 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 321: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector CAR LOADING AREA 1 M1 53 Pass

Smoke Detector MAIN HALL 1 M1 54 Pass

Smoke Detector MAIN HALL 1 M1 55 Pass

Duct Detector MAIN HALL 1 M1 56 Pass

Pull Station GYM 1 M1 57 Pass

Duct Detector ERU 2 RETURN RM 184 1 M1 67 Pass

Duct Detector ERU SUPPLY RM 186 1 M1 66 Pass

Duct Detector ERU 3 SUPPLY RM 209 1 M1 68 Pass

Duct Detector ERU 1 RETURN RM 453 1 M1 64 Pass

Duct Detector ERU 1 RETURN RM 455 1 M1 65 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 322: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 323: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

Recommend adding visual notification to staff bathrooms by Gym and by workroom lounge - (4) total.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 324: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

2 0

6 0

22 0

8 2

47 0

3 1

3 0

Inspector Name : Signature:

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Pass

Are Lamps and Displays Operating Properly

Power Supplies Simplex 4009

Ground fault

VSR-F

Tamper Switches Potter OSYSU-2

Simplex

Simplex

2099-9101

(678) 691-0011

6945 Keith Bridge Road

30506

Simplex

Office Rm 101

Model Name

Gainesville GA

Is the Panel Monitored Yes

4010

EI1273 / WO #155440

Chestatee Elementary School

6/15/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Who Was Notified Prior to the Start of Testing Monitoring Company & Office Staff

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Panel Secondary power loss

Open Circuit Detection

Panel Power Loss

Duct Detectors Simplex

Batteries

4098-9756

David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Power Patrol

4010Control Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Waterflow Switches Potter

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 325: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Fail

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2017) 13.4 Pass

Good (2017) 13.4 Pass

Good (2020) 13.5 Pass

Good (2020) 13.5 Pass

Good (2017) 13.3 Pass

Good (2017) 13.4 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

Pass

N/A

N/AFM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7A

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

BPS #1 Rm 261 (Right)

FACP (Right) 12V 7A

Speakers/Horns

BPS #2 Rm 427 (Right) 12V 7A

BPS #1 Rm 261 (Left) 12V 7A

12V 7A

BPS #2 Rm 427 (Left) 12V 7A

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 326: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Pull Station EXIT @ 470 1 M1 1 Pass

Pull Station EXIT @ 459 1 M1 2 Pass

Pull Station EXIT @ 413 1 M1 3 Pass

Pull Station EXIT @ 401 1 M1 4 Pass

Pull Station MAIN LOBBY @ 101 1 M1 5 Pass

Pull Station EXIT @ 427 1 M1 6 Pass

Pull Station MECHANICAL RM 429 1 M1 7 Pass

Pull Station AT RM 450 1 M1 8 Pass

Pull Station GYM REAR EXIT 1 M1 9 Pass

Pull Station CORRIDOR @ 358 1 M1 10 Pass

Pull Station MEDIA CENTER @ 118 1 M1 11 Pass

Pull Station AT 148 1 M1 12 Pass

Pull Station AT 238 1 M1 13 Pass

Pull Station AT 225 1 M1 14 Pass

Pull Station CORRIDOR EXIT @ 261 1 M1 15 Pass

Pull Station AT 292 1 M1 16 Pass

Pull Station AT 291 1 M1 17 Pass

Pull Station KITCHEN EXIT 1 M1 18 Pass

Pull Station CAFETERIA WEST EXIT 1 M1 19 Pass

Duct Detector CORRIDOR @ 469 1 M1 20 Pass

Duct Detector CORRIDOR @ 459 1 M1 21 Pass

Duct Detector CORRIDOR @ 462 1 M1 22 Pass

Duct Detector CORRIDOR @ 459 1 M1 23 Pass

Duct Detector CORRIDOR @ 455 1 M1 24 Pass

Duct Detector IN RM 454 1 M1 25 Pass

Duct Detector CORRIDOR @ 442 1 M1 26 Pass

Duct Detector CORRIDOR @ 446 1 M1 27 Pass

Duct Detector CORRIDOR @ 449 1 M1 28 Pass

Duct Detector CORRIDOR @ 431 1 M1 29 Pass

Duct Detector CORRIDOR @ 430 1 M1 30 Pass

Duct Detector CORRIDOR @ 415 1 M1 31 Pass

Duct Detector CORRIDOR @ 423 1 M1 32 Pass

Duct Detector CORRIDOR @ 401 1 M1 33 Pass

Duct Detector CORRIDOR @ 340 1 M1 34 Pass

Duct Detector CORRIDOR @ 343 1 M1 35 Pass

Duct Detector IN RM 356 1 M1 36 Pass

Duct Detector CORRIDOR @ 336 1 M1 37 Pass

Duct Detector CORRIDOR @ 310 1 M1 38 Pass

Duct Detector MAIN CORRIDOR @ 302 1 M1 39 Pass

Duct Detector MAIN CORRIDOR @ 117 1 M1 40 Pass

Duct Detector MEDIA CENTER 1 M1 41 Pass

Pull Station MEDIA CENTER WEST EXIT 1 M1 42 Pass

Duct Detector IN HALL @ 241 1 M1 43 Pass

Duct Detector MULTIPURPOSE RM 170 1 M1 44 Pass

Duct Detector IN HALL @ 241 1 M1 45 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 327: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector MULTIPURPOSE RM 170 1 M1 46 Pass

Duct Detector IN HALL @ 241 1 M1 47 Pass

Duct Detector IN RM 254 1 M1 48 Pass

Duct Detector KITCHEN OFFICE 134 1 M1 49 Pass

Duct Detector CAFETERIA @ OFFICE 1 M1 50 Pass

Duct Detector CAFETERIA @ NW CORNER 1 M1 51 Pass

Duct Detector CAFETERIA @ SW CORNER 1 M1 52 Pass

Duct Detector CAFETERIA @ STORAGE 122 1 M1 53 Pass

Duct Detector HALL @ 264 1 M1 54 Pass

Duct Detector HALL @ 265 1 M1 55 Pass

Duct Detector HALL @ 267 1 M1 56 Pass

Duct Detector HALL @ 291 1 M1 57 Pass

Duct Detector HALL @ 292 1 M1 58 Pass

Duct Detector HALL @ WORK RM 166 RTU-8 1 M1 59 Pass

Duct Detector HALL @ WORK RM 166 RTU-9 1 M1 60 Pass

Duct Detector HALL @ 201 1 M1 61 Pass

Duct Detector HALL @ 201 1 M1 62 Pass

Duct Detector HALL @ 201 1 M1 63 Pass

Duct Detector HALL @ 205 1 M1 64 Pass

Duct Detector HALL @ 232 1 M1 65 Pass

Duct Detector HALL @ 239 1 M1 66 Pass

Duct Detector HALL @ 238 1 M1 67 Pass

Smoke Detector HALL @ FIRE DOORS 152 1 M1 68 Fail

Smoke Detector HALL @ FIRE DOORS 152 1 M1 69 Fail

Smoke Detector HALL @ 141 1 M1 70 Pass

Smoke Detector HALL @ 141 1 M1 71 Pass

Smoke Detector MAIN CORRIDOR SMOKE DOORS @ 340 1 M1 72 Pass

Smoke Detector MAIN CORRIDOR SMOKE DOORS @ 340 1 M1 73 Pass

Smoke Detector SMOKE DOORS @ 435 1 M1 74 Pass

Smoke Detector SMOKE DOORS @ 435 1 M1 75 Pass

Pull Station MECHANICAL RM 263 1 M1 77 Pass

Waterflow Switch MECHANICAL RM 263 RISER 2 1 M1 80 Pass

Waterflow Switch MECHANICAL RM 263 RISER 3 1 M1 80 Pass

Tamper Switch MECHANICAL RM 263 RISER 2 1 M1 80 Pass

Tamper Switch MECHANICAL RM 263 RISER 3 1 M1 80 Pass

Waterflow Switch MECHANICAL RM 429 RISER 1 1 M1 84 Fail

Tamper Switch MECHANICAL RM 429 RISER 1 1 M1 84 Pass

Pull Station CAFETERIA NORTH EXIT 1 M1 127 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 328: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

(1) Potter VSR-F waterflow switch in Mechanical Room #429 - failed to report to FACP.

Deficiencies

(1) Strobe only in room 150 next to clinic has a non-functional red simplex wall mounted strobe that needs repair.

(2) Smoke detectors in Hallway @ fire doors by Room 152 are covered in plastic hanging from electrical boxes.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 329: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

(2) Bathrooms #402 & #404 have no visual notification.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 330: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

4 0

10 0

27 0

3 0

16 0

3 0

3 0

Inspector Name : Signature: David Piorkowski

Pass

Pullstations

Smoke Detectors SD350

Power Patrol

MS-9200UDLSControl Panel

Pass

Device

Fire-Lite

Interface Equipment

David Piorkowski

Fire-Lite

Fire-Lite

BG-12LX

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing Monitoring Company & Office Staff

Batteries FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Silent Knight

6/11/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Pass

Tamper Switches System Sensor OSY2

(678) 691-0011

2800 Holtzclaw Road

30041

Fire-Lite

TBD

Model Name

Cumming GA

Is the Panel Monitored Yes

9200UDLS

EI1273

Chattahoochee Elementary School

5495

WFD40System SensorWaterflow Switches

Duct Detectors System Sensor DH100ACDCP

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 331: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.6 Pass

Good (2019) 13.5 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

Pass

Pass

N/A

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Continued on Page 3 - Battery Testing

FACP 12V 7A

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Magnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7A

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 332: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Floor Condition Voltage Load Test

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.6 Pass

BPS #4 Rm 422 (Left) 12V 7AH

BPS #3 Rm 422 (Left) 12V 7AH

BPS #3 Rm 422 (Right) 12V 7AH

BPS #2 Rm 318 (Left) 12V 7AH

BPS #2 Rm 318 (Right) 12V 7AH

BPS #1 Rm 213 (Right) 12V 7AH

Battery Testing (cont.)

Location Size

BPS #1 Rm 213 (Left) 12V 7AH

BPS #4 Rm 422 (Right) 12V 7AH

Page 333: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Smoke Detector SMOKE ABOVE PANEL 1 D 1 Pass

Duct Detector ERU 1 SUPPLY - ROOM 216 1 D 2 Pass

Duct Detector ERU 1 RETURN - ROOM 216 1 D 3 Pass

Duct Detector ERU 2 SUPPLY - ROOM 217 1 D 4 Pass

Duct Detector ERU 2 RETURN - ROOM 217 1 D 5 Pass

Duct Detector ERU 3 SUPPLY - ROOM 330 1 D 6 Pass

Duct Detector ERU 3 RETURN - ROOM 330 1 D 7 Pass

Duct Detector ERU 4 SUPPLY - ROOM 216 1 D 8 Pass

Duct Detector ERU 4 RETURN - ROOM 216 1 D 9 Pass

Duct Detector ERU 5 SUPPLY - IN ROOM 444 1 D 10 Pass

Duct Detector ERU 5 RETURN - IN ROOM 444 1 D 11 Pass

Smoke Detector HALL 300 1 D 15 Pass

Smoke Detector HALL 400 1 D 16 Pass

Pull Station MECH RM 101 1 M 3 Pass

Pull Station MAIN ENTRANCE 1 M 4 Pass

Pull Station MECH RM 102 1 M 5 Pass

Pull Station MEDIA CENTER RM 130 1 M 6 Pass

Pull Station MEDIA CENTER RM 130 1 M 7 Pass

Pull Station MEDIA CENTER RM 130 1 M 8 Pass

Pull Station MAIN CORRIDOR 1 M 9 Pass

Pull Station MAIN CORRIDOR 1 M 10 Pass

Pull Station 1ST HALLWAY 1 M 11 Pass

Pull Station BUS EXIT HALL 200 1 M 12 Pass

Pull Station HALL 200 FIRST 1 M 13 Pass

Pull Station CAFÉ EXIT 142 1 M 14 Pass

Pull Station 142 CAFÉ EXIT 1 M 15 Pass

Pull Station 169 MUSIC CORRIDOR 1 M 16 Pass

Pull Station 170 GYM EXIT 1 M 17 Pass

Pull Station 180 GYM EXIT 1 M 18 Pass

Pull Station 180 MULTI-PURPOSE 1 M 19 Pass

Pull Station 180 MULTI-PURPOSE 1 M 20 Pass

Pull Station HALL 300 CORRIDOR 1 M 21 Pass

Pull Station 300 HALL CORRIDOR 1 M 22 Pass

Pull Station 300 HALL 3RD CORRIDOR 1 M 23 Pass

Pull Station 300 HALL 3RD CORRIDOR 1 M 24 Pass

Pull Station 400 HALL EXIT BY CLINIC 1 M 25 Pass

Pull Station 400 HALL 4TH CORRIDOR 1 M 26 Pass

Pull Station 400 HALL 4TH CORRIDOR 1 M 27 Pass

Pull Station 400 HALL 4TH CORRIDOR 1 M 28 Pass

Waterflow Switch RM 172 RISER 1 M 29 Pass

Tamper Switch RM 172 RISER 1 M 30 Pass

Tamper Switch RM 170 PIV #1 1 M 31 Locked

Duct Detector RM 101 1 M 32 Pass

Duct Detector RM 102 1 M 33 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 334: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector CAFÉ RM 142 1 M 40 Pass

Duct Detector RM 137 1 M 49 Pass

Monitor KITCHEN HOOD ANSUL 1 M 50 Pass

Waterflow Switch RM 429 RISER 1 M 51 Pass

Tamper Switch RM 429 RISER 1 M 52 Pass

Pull Station KITCHEN EXIT 1 M 53 Pass

Tamper Switch RM 429 PIV #2 1 M 54 Locked

Waterflow Switch RM 172 RISER 1 M 55 Pass

Tamper Switch RM 172 RISER 1 M 56 Pass

Duct Detector RM 142 KITCHEN 1 M 59 Pass

Duct Detector RM 142 KITCHEN 1 M 60 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 335: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 336: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 337: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

2 0

9 0

11 1

18 0

2 0

Inspector Name : Signature:

FSP-851

30024

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/16/2020

EI1273

3591 Old Atlanta Rd

Bus Shop South

Ground Fault

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredIDF rm 9

Model Name NFS-320Notifier

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ga

Monitoring Company

EMC

EMC Security

Fail

All-Star Fire, LLC

Power Patrol

Notifier NBG-12LX

FAS 1270

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

NFS-320

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Notifier

Manufacturer

Ground Faults Detected by Control Panel

Suwanee

Are Lamps and Displays Operating Properly

Control Panel

Device

Pass

Pass

D K WomackKen Womack

NotifierHeat Detectors FST-851

Duct Detector System Sensor TBD

Batteries

Pullstations

NotifierSmoke Detectors

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 338: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2018) 13.1 Pass

Good (2018) 13.1 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Building Temp

Supervisory Signals

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When Activated

Correct Switching and Operation Verified

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble

FACP (left)

12v 7ahFACP (right)

Generator Trouble Reports to Panel

Fire Pump Running

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Fire Pump Power Loss

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 339: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station Office Corridor Exit 1 M001 Pass

Pull Station Conference rm 1 M002 Pass

Pull Station Drivers Lounge 1 M003 Pass

Pull Station Garage rm Front 1 M004 Pass

Pull Station Bus Wash 1 M005 Pass

Pull Station Bus Wash 1 M006 Pass

Pull Station Garage rm Back 1 M007 Pass

Pull Station Garage Front 1 M008 Pass

Pull Station Parts Rm 1 M009 Pass

Duct Detector MAV22 Shop Bay 4 rear 1 M010 Visual

Duct Detector MAV21 Shop Bay 4 front 1 M012 Pass

Smoke Detector IDF rm 9 1 D001 Pass

Smoke Detector Office 10 1 D002 Pass

Smoke Detector Office 11 1 D003 Pass

Smoke Detector Office 12 1 D004 Pass

Smoke Detector Office Corridor 1 D005 Pass

Smoke Detector Office 13 1 D006 Fail

Heat Detector File rm 14 1 D007 Visual

Heat Detector Water Heater rm 15A 1 D008 Visual

Smoke Detector Conference rm 21 1 D009 Pass

Heat Detector Custodial rm 8 1 D010 Visual

Heat Detector Tool Storage 6 1 D011 Visual

Heat Detector Shop Bay 1 Center 1 D012 Visual

Heat Detector Shop Bay 1 Front 1 D013 Visual

Heat Detector Shop Bay 1 Rear 1 D014 Visual

Heat Detector Shop Bay 2&3 Center 1 D015 Visual

Heat Detector Shop Bay 2&3 Rear 1 D016 Visual

Heat Detector Shop Bay 2&3 Front 1 D017 Visual

Heat Detector Shop Bay 4 Center 1 D018 Visual

Heat Detector Shop Bay 4 Rear 1 D019 Visual

Heat Detector Shop Bay 4 Front 1 D020 Visual

Smoke Detector Office Corridor 1 D021 Pass

Heat Detector Break rm 7 1 D022 Visual

Smoke Detector Shop Supervisor rm 9 1 D023 Pass

Smoke Detector Service Desk rm 17 1 D024 Pass

Smoke Detector Drivers Lounge 1 D025 Pass

Heat Detector Parts rm 4 1 D026 Visual

Heat Detector Tire Storage rm 5 1 D027 Visual

Heat Detector Mezz 1 D028 Visual

Heat Detector Mezz 1 D029 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 340: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Note:

Upon arrival panel shows trbl, Smoke Office 13 Invrep

Deficiencies

1. Detector D006 fails to report to panel

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 341: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 342: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

2 0

4 0

3 0

1 0

2 0

Inspector Name : Signature:

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Pass

Pass

Control Panel

Device

Pass

Pass

D K WomackKen Womack

PotterTamper PS10-2A

Other Potter OSYSU-2

Batteries

Pullstations

System SensorSmoke Detectors

All-Star Fire, LLC

Power Patrol

Firelite BG8

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

MS10 UD

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Firelite

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

MS10UDFirelite

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

EMC Security

Pass

2451

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/16/2020

EI1273 / WO # 155474

3710 Matt Highway

Bus Shop N / North Transportation

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Door

Model Name

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 343: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019 13 Pass

Good (2019 13 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Generator Trouble Reports to Panel

Fire Pump Running

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Fire Pump Power Loss

Correct Switching and Operation Verified

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble

FACP (left)

12v 7ahFACP (right)

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 344: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station Front Exit 1 Z 1 Pass

Pull Station Left Rear Exit 1 Z 1 Pass

Pull Station Right Rear Exit 1 Z 1 Pass

Tamper Riser room 1 Z 6 Pass

Low pressure Riser room 1 Z 6 Pass

High Pressure Riser room 1 Z 5 Pass

Heat Detector Riser room 1 Z 3 Visual

Smoke Detector Riser room 1 Z 2 Pass

Pull Station Conference Exit room 101 1 Z 1 Pass

Smoke Detector Tele Closet 1 Z 2 Pass

Smoke Detector Storage room 102 1 Z 2 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 345: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 346: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

Programming to reflect what is on panel. All zones read pull Station.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 347: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 5 0

12 0

18 0

34 0

8 0

3 0

4 1

Inspector Name : Signature:

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

System SensorWater flow WFD40N

All-Star Fire, LLC

Interstate

Simplex 2099-9754

SLA1116

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4100 ES

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Alpharetta

Are Lamps and Displays Operating Properly

Pass

175 Martin Drive

Brandywine Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office Hall

Model Name 4100ESSimplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

4098-9688

Tamper Globe GLR300G

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

30004

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

6/29/2020

EI1273

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 348: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.4 Pass

Good (2019) 13.1 Pass

Good (2019) 13.3 Pass

Good (2019) 13.2 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.2 Pass

Good (2019) 13.1 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #5 rm 422

FCPS (left) #4 rm

FCPS (left) #5 rm 422

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 207

FCPS (right) #2 rm 207

FCPS (left) #3 rm 207

FCPS (right) #3 rm 207

12v 7ah

12v 7ah

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FACP (left)

12v 18ahFACP (right)

12v 18ah

12v 7ah

FCPS (right) #1 rm 156

FCPS (left) #1 rm 156

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FCPS (right) #4 rm

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 349: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Smoke Detector Above FACP 1 M1-1 Pass

Duct Detector Corr 109 1 M1-2 Pass

Pull Station Cafeteria Entrance 1 M1-3 Pass

Duct Detector Serving Line 160 1 M1-4 Pass

Ansul Kitchen Hood 1 M1-5 Visual

Duct Detector Corr by rm 171 1 M1-6 Pass

Pull Station Office 164 1 M1-7 Pass

Duct Detector Cafeteria 1 M1-8 Pass

Smoke Detector Elect rm 156 1 M1-9 Pass

Flow Switch Mech rm 158 1 M1-10 Pass

Tamper Switch Mech rm 158 1 M1-11 Pass

Flow Switch Mech rm 158 1 M1-12 Pass

Tamper Switch Mech rm 158 1 M1-13 Pass

Flow Switch Mech rm 158 1 M1-14 Pass

Tamper Switch Mech rm 158 1 M1-15 Pass

Tamper Switch Outside PIV 1 M1-16 Fail

Smoke Detector Mech rm 158 1 M1-17 Pass

Pull Station Mech rm 158 1 M1-18 Pass

Pull Station Gym Entry/Exit Hall dr SE 1 M1-19 Pass

Pull Station Gym Entry/Exit Hall dr NE 1 M1-20 Pass

Pull Station Gym Entry/Exit Hall dr NW 1 M1-21 Not Found

Duct Detector Gym Mech rm 241 1 M1-22 Pass

Pull Station Gym Exit SW 1 M1-23 Pass

Smoke Detector Elect rm 110 1 M1-24 Pass

Duct Detector Corr 111 1 M1-25 Pass

Ansul Spec Ed Kitchen Hood 1 M1-26 Visual

Smoke Detector Elect rm 207 1 M1-27 Pass

Pull Station Vestibule 101 1 M1-28 Pass

Pull Station Vestibule 101 1 M1-29 Pass

Duct Detector Corr 407 1 M1-30 Pass

Duct Detector Mech rm 254 1 M1-31 Pass

Duct Detector Mech rm 259 1 M1-32 Pass

Pull Station Corr by rm 260 1 M1-33 Pass

Duct Detector Mech rm 267 1 M1-34 Pass

Duct Detector Room 274 1 M1-35 Pass

Duct Detector Mech rm 278 1 M1-36 Pass

Duct Detector Mech rm 277 1 M1-37 Pass

Pull Station Corr 281 1 M1-38 Pass

Duct Detector Mech rm 288 1 M1-39 Pass

Duct Detector Mech rm 289 1 M1-40 Pass

Duct Detector Kindergarten rm 292 1 M1-41 Pass

Duct Detector Mech rm 299 1 M1-42 Pass

Duct Detector Mech rm 298 1 M1-43 Pass

Duct Detector Mech rm 298 1 M1-44 Pass

Smoke Detector Elect rm 319 1 M1-45 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 350: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station Corr 310 by IRR rm 1 M1-46 Pass

Smoke Detector Elect rm 422 1 M1-47 Pass

Duct Detector Corr 420 by Conf rm 405 1 M1-48 Pass

Duct Detector Corr 420 by Reception rm 428 1 M1-49 Pass

Pull Station Corr 420 by Reception rm 428 1 M1-50 Pass

Duct Detector Mech rm 434 1 M1-51 Pass

Duct Detector Mech rm 440 1 M1-52 Pass

Pull Station Corr 430 by rm 422 1 M1-53 Pass

Duct Detector Mech rm 465 1 M1-54 Pass

Duct Detector Mech rm 473 1 M1-55 Pass

Pull Station Corr 460 by rm 475 1 M1-56 Pass

Duct Detector Mech rm 484 1 M1-57 Pass

Duct Detector Mech rm 490 1 M1-58 Pass

Pull Station Corr 480 by rm 492 1 M1-59 Pass

Duct Detector Mech rm 504 1 M1-60 Pass

Duct Detector Room 505 1 M1-61 Pass

Duct Detector Mech rm 510 1 M1-62 Pass

Duct Detector Corr 500 by rm 512 1 M1-63 Pass

Pull Station Corr 200 by rm 522 1 M1-64 Pass

Smoke Detector Elect rm 527A 1 M1-65 Pass

Duct Detector Room 530 1 M1-66 Pass

Duct Detector Mech rm 533 1 M1-67 Pass

Duct Detector Mech rm 533 1 M1-68 Pass

Pull Station Corr 520 by rm 534 1 M1-69 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 351: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

PIV did not report to panel.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 352: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 353: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 2 0

6 6

36 0

11 0

11 0

3 0

3 0

Inspector Name : Signature:

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

PotterWaterflow VSR -F

All-Star Fire, LLC

Ultra Power

Simplex 4099-9006

UL12180

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

1994 Peachtree Parkway

Big Creek Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredElect rm 177

Model Name 4010Simplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

4098-9685

Tamper Kennedy TBD

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

30041

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

6/26/2020

EI1273 / WO #155437

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 354: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Poor (2017) 13 Fail

Poor (2017) 13 Fail

Poor (2019) 13 Fail

Poor (2019) 12.9 Fail

Poor (2019) 12.8 Fail

Poor (2019) 12.8 Fail

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

N/A

Pass

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

Fire Pump Power Loss

FCPS (left) #2

FCPS (right) #2

12v 7ah

12v 7ah

Correct Switching and Operation Verified

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FACP (left)

12v 18ahFACP (right)

12v 18ah

12v 7ah

FCPS (right) #1

FCPS (left) #1

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 355: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station 400 Hall Exit @ rm 456 1 M1-8 Pass

Duct Detector Rm 142 ERU supply 1 M1-32 Not Found

Duct Detector Rm 142 ERU return 1 M1-33 Not Found

Duct Detector Rm 262 ERU supply 1 M1-40 Pass

Duct Detector Rm 262 ERU return 1 M1-41 Pass

Duct Detector Rm 450 ERU supply 1 M1-42 Pass

Duct Detector Rm 450 ERU return 1 M1-43 Pass

Duct Detector Rm 505 ERU supply 1 M1-49 Pass

Duct Detector Rm 505 ERU return 1 M1-50 Pass

Duct Detector Crawl Space AHU bldg 500 1 M1-55 Visual

Duct Detector Kitchen Dry Storage 1 M1-59 Pass

Duct Detector Gym AHU 1 M1-60 Visual

Smoke Detector 400 Hall Smoke dr @ rm 427 1 M1-101 Pass

Smoke Detector 400 Hall Smoke dr @ rm 427 1 M1-102 Pass

Smoke Detector 100 Hall Smoke dr @ rm 104 1 M1-103 Pass

Smoke Detector 100 Hall Smoke dr @ rm 143 1 M1-104 Pass

Smoke Detector 100 Hall Smoke dr @ rm 152 1 M1-105 Pass

Smoke Detector 100 Hall Smoke dr @ rm 154 1 M1-106 Pass

Smoke Detector Elect rm 177 @ FACP 1 M1-107 Pass

Smoke Detector Outside Boiler rm 165 1 M1-108 Pass

Smoke Detector 400 Hall @ rm 448 1 M1-109 Pass

Smoke Detector 400 Hall @ rm 456 1 M1-110 Pass

Smoke Detector 400 Hall @ rm 462 1 M1-111 Pass

Pull Station 100 Main Lobby Exit 1 M1-1 Pass

Pull Station 100 Hall Exit @ rm 121 1 M1-2 Pass

Pull Station 400 Hall Exit @ rm 401 1 M1-3 Pass

Pull Station 400 Hall Exit @ rm 415 1 M1-4 Pass

Pull Station 400 Hall Exit @ rm 427 1 M1-5 Pass

Pull Station 400 Hall Exit @ rm 434 1 M1-6 Pass

Pull Station 400 Hall Exit @ rm 466 1 M1-7 Pass

Pull Station 400 Hall Exit @ rm 456 1 M1-8 Pass

Pull Station 100 Hall Exit @ Cafe 154 1 M1-9 Pass

Pull Station 300 Gym Exit @ rm 301 1 M1-10 Pass

Pull Station 300 Gym West Side Exit 1 M1-11 Pass

Pull Station 300 Gym East Side Exit 1 M1-12 Pass

Pull Station 100 Kitchen Exit 156 1 M1-13 Pass

Pull Station 100 Cafeteria Exit 154 1 M1-14 Pass

Pull Station 100 Hall Exit @ rm 153 1 M1-15 Pass

Pull Station 100 Main Office Exit 120 1 M1-16 Pass

Pull Station 200 Media Center Exit 210 1 M 1-17 Pass

Pull Station 200 Hall Exit @ rm 228 1 M1-18 Pass

Pull Station 200 Hall Exit @ rm 201 1 M1-19 Pass

Pull Station Hall Exit between 100 & 200 1 M1-20 Pass

Pull Station 100 Hall Exit @ rm 178 1 M1-21 Pass

Ansul Kitchen Hood 1 M1-22 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 356: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station 100 Main Off 120 @ Counter 1 M1-24 Pass

Pull Station 200 Hall Exit to Playground 1 M1-25 Pass

Pull Station 200 Hall Exit @ rm 231 1 M1-26 Pass

Pull Station 200 Hall Exit @ rm 248 1 M1-27 Pass

Pull Station 200 Hall Exit @ rm 238 1 M1-28 Pass

Pull Station 200 Hall Exit @ rm 275 1 M1-29 Pass

Pull Station 200 N/E Hall Exit @ rm 290 1 M1-30 Pass

Pull Station 200 N/W Hall Exit @ rm 290 1 M1-31 Pass

Pull Station Multipurpose rm 290 @ Stor rm 292 1 M 1-34 Pass

Pull Station Multipurpose rm 290 @ Stor rm 291 1 M1-35 Pass

Flow Switch 100 Boiler rm 165 1 M1-36 Pass

Flow Switch 100 Boiler rm 165 1 M1-37 Pass

Tamper Switch 100 Boiler rm 165 1 M1-38 Pass

Tamper Switch 100 Boiler rm 165 1 M1-39 Pass

Pull Station 500 Auditorium Exit 502 1 M1-51 Pass

Pull Station 500 Auditorium Exit 502 1 M1-52 Pass

Pull Station 500 Hall Exit @ rm 503 1 M1-53 Pass

Pull Station 500 Side Hall Exit @ rm 506 1 M 1-54 Pass

Flow Switch 500 Auditorium Storage rm 1 M1-56 Pass

Tamper Switch 500 Auditorium Storage rm 1 M1-57 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 357: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. 6 Batteries failed load test.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 358: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 359: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

4 0

3 0

4 0

3 0

Inspector Name : Signature: David Piorkowski

Pass

Pullstations

Smoke Detectors FSP-851

Yuasa

NFW-50XControl Panel

Pass

Device

Notifier

Interface Equipment

David Piorkowski

Notifier

Ground fault

Panel Secondary power loss

Open Circuit Detection

Sub Panel (DACT only)

NBG-12LX

VISTA-128FBP

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing

(678) 691-0011

1100 Lanier 400 Parkway

30040

Notifier

Data Room 1st Fl

Model Name

Cumming GA

Is the Panel Monitored Yes

NFW-50X

EI1273

7/2/2020

Forsyth County School - Alliance Academy for Innovation of Cumming - Parking Deck

Pass

Heat Detectors Notifier FSH-851R

Honeywell

Notifier

Monitoring Company & Maintenance Staff

Batteries NP7-12

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 360: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.6 Pass

Good (2019) 13.7 Pass

Good (2019) 13.6 Pass

Good (2019) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

N/A

N/A

N/A

N/A

N/A

N/A

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Kitchen Hoods

Location Size

Magnetic Door Holders

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

Sub Panel for DACT (Left) 12V 7AH

12V 7AH

Fire Pump Trouble

Fire Pump Phase Reversal

Sub Panel for DACT (Right)

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

FACP (Right)

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

12V 7AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 361: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Location Floor Type Point Results

Smoke Detector Above Panel 1 D 4 Pass

Smoke Detector Electrical Room 1 D 5 Pass

Smoke Detector Elevator Room 1 D 6 Pass

Heat Detector Elevator Lobby 1 D 7 Pass

Heat Detector Elevator Lobby 2 D 8 Pass

Heat Detector Elevator Lobby 3 D 9 Pass

Smoke Detector Elevator Shaft 3 D 10 Pass

Pull Station Data Room 1 M 1 Pass

Pull Station Electrical Room 1 M 2 Pass

Pull Station Elevator Roon 1 M 3 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 362: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 363: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 364: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Job #Date

NameAddressCity State Zip

Fire Control Panel InspectionManufacturerPanel LocationAccount #

Total Devices

Number of Devices Failed

1 013 02 0

30 040 059 0

109 052 09 0

10 0

Inspector Name : Signature:

Panel Power Loss

FailAre Lamps and Displays Operating Properly

Heat Detectors Notifier FSH-851R

Pass

NotifierNotifier

NBG-12LX

Duct Detectors System Sensor DNRWaterflow Switches Potter VSR

(678) 691-0011

1100 Lanier 400 Parkway30040

NotifierOutside Elec. Rm 2902

Model Name

Cumming GA

Is the Panel Monitored YesNFS2-640

EI1273

Alliance Academy for Innovation 7/2/2020

Power Supplies Notifier FCPS-24S8

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Who Was Notified Prior to the Start of Testing Monitoring Company & Maintenance Staff

Batteries FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power lossOpen Circuit Detection

Digital Audio Amplifiers Notifier DAA-2

David Piorkowski

Pass

PullstationsSmoke Detectors FSP-851

Power Patrol

NFS2-640Control Panel

Pass

Device

Notifier

Interface Equipment

David Piorkowski

Tamper Switches Victaulic Butterfly

Page 365: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

PassPass

YFailPass

N/AN/AN/A

Condition Voltage Load TestGood (2020) 13.6 PassGood (2020) 13.6 PassGood (2017) 13.5 PassGood (2017) 13.6 Pass

N/AN/AN/AN/A

Fire Pump Controller Troubles Report to Panel N/APhase Reversal on Pump Controller Reports to Panel N/A

N/AN/A

PassPassN/APassPassPassN/A

Digital Audio Amplifier @ FACP (Top) 12V 12AHDigital Audio Amplifier @ FACP (Bottom) 12V 12AH

Speakers/Horns

FM-200 / Preaction SystemsKitchen Hood Suppression System Report CorrectlyFM-200/Preaction Systems Report Correctly

12V 20AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When ActivatedWater Level/Water Temp Sensors Report CorrectlyPower Loss on Fire Pump Reports to PanelFire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In AutoGenerator Trouble

Interface EquipmentFire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire AlarmFire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Emergency Communications EquipmentPhone SetsPhone JacksAmplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator RecallHVAC ShutdownStairwell Pressurization

Fire Pump RunningFire Pump TroubleFire Pump Phase Reversal

Notification DevicesVoice Evacuation Does the Voice Evacuation Work Properly and is it IntelligibleNAC Circuits Are the Notification Appliance Circuits Monitored for IntegrityCircuit StyleStrobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Continued on Page 3 - Battery Testing

FACP (Right) 12V 20AH

Page 366: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Location Floor Size Condition Voltage Load TestBPS #1 next to FACP (Left) 2 12V 7AH Good (2020) 13.6 Pass

BPS #1 next to FACP (Right) 2 12V 7AH Good (2020) 13.6 PassBPS #2 in MDF Rm 1609 (Left) 1 12V 7AH Good (2020) 13.7 Pass

BPS #2 in MDF Rm 1609 (Right) 1 12V 7AH Good (2020) 13.7 PassBPS #3 in MDF Rm 1609 (Left) 1 12V 7AH Good (2020) 13.7 Pass

BPS #3 in MDF Rm 1609 (Right) 1 12V 7AH Good (2020) 13.7 PassBPS #4 in MDF Rm 1609 (Left) 1 12V 7AH Good (2020) 13.6 Pass

BPS #4 in MDF Rm 1609 (Right) 1 12V 7AH Good (2020) 13.6 PassBPS #5 in IDF Rm 2609 (Left) 2 12V 7AH Good (2020) 13.7 Pass

BPS #5 in IDF Rm 2609 (Right) 2 12V 7AH Good (2020) 13.7 PassBPS #6 in IDF Rm 3609 (Left) 3 12V 7AH Good (2020) 13.7 Pass

BPS #6 in IDF Rm 3609 (Right) 3 12V 7AH Good (2020) 13.7 PassBPS #7 in IDF Rm 3609 (Left) 3 12V 7AH Good (2020) 13.7 Pass

BPS #7 in IDF Rm 3609 (Right) 3 12V 7AH Good (2020) 13.7 PassBPS #8 in IDF Rm 3609 (Left) 3 12V 7AH Good (2020) 13.7 Pass

BPS #8 in IDF Rm 3609 (Right) 3 12V 7AH Good (2020) 13.7 PassBPS #9 in Elec Rm 5100 (Left) 2 12V 7AH Good (2020) 13.7 Pass

BPS #9 in Elec Rm 5100 (Right) 2 12V 7AH Good (2020) 13.7 PassBPS #10 in Elec Rm 5100 (Left) 2 12V 7AH Good (2020) 13.6 Pass

BPS #10 in Elec Rm 5100 (Right) 2 12V 7AH Good (2020) 13.6 PassBPS #11 in Mech Rm 1111 (Left) 1 12V 7AH Good (2020) 13.6 Pass

BPS #11 in Mech Rm 1111 (Right) 1 12V 7AH Good (2020) 13.6 PassBPS #12 in Mech Rm 1111 (Left) 1 12V 7AH Good (2020) 13.7 Pass

BPS #12 in Mech Rm 1111 (Right) 1 12V 7AH Good (2020) 13.7 PassBPS #13 in Mech Rm 2306 (Left) 2 12V 7AH Good (2017) 13.5 Pass

BPS #13 in Mech Rm 2306 (Right) 2 12V 7AH Good (2017) 13.6 Pass

Battery Testing (cont.)

Page 367: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Device Type Location Floor Loop Address ResultsSmoke Detector FIRE DOORS BY 1519 1 L01 D001 PassSmoke Detector FIRE DOORS BY 1519 1 L01 D002 PassSmoke Detector FIRE DOORS BY 1519 1 L01 D003 PassSmoke Detector FIRE DOORS BY 1519 1 L01 D004 PassSmoke Detector FIRE DOORS BY 1329 1 L01 D005 PassSmoke Detector FIRE DOORS BY 1329 1 L01 D006 PassSmoke Detector FIRE DOORS STAIR 4 1 L01 D007 PassSmoke Detector FIRE DOORS STAIR 4 1 L01 D008 PassSmoke Detector ELEVATOR LOBBY 1ST FL. 1 L01 D009 PassSmoke Detector FIRE DOORS STAIR 2 1ST FL. 1 L01 D010 PassSmoke Detector FIRE DOORS STAIR 2 1ST FL. 1 L01 D011 PassSmoke Detector FIRE DOORS BY 1501 1 L01 D012 PassSmoke Detector FIRE DOORS BY 1501 1 L01 D013 PassHeat Detector MECHANICAL ROOM 1517 1 L01 D014 PassHeat Detector EQUIP WORKROOM 1511 1 L01 D015 Pass

Smoke Detector MDF 1609 1ST. FL. 1 L01 D016 PassSmoke Detector CUSTODIAN 1608 1ST. FL. 1 L01 D017 PassHeat Detector BUILDING SERV. 1406 1ST. FL. 1 L01 D018 PassHeat Detector BUILDING SERV. 1406 1ST. FL. 1 L01 D019 PassHeat Detector BUILDING SERV. 1406 1ST. FL. 1 L01 D020 Pass

Smoke Detector STORAGE ROOM 1318- B 1 L01 D021 PassSmoke Detector STORAGE ROOM 1320 1ST. FL. 1 L01 D022 PassHeat Detector ELEVATOR EQUIPMENT 1ST. FL. 1 L01 D023 Pass

Smoke Detector MEDIA PRODUCTION 1ST. FL. 1 L01 D024 PassHeat Detector A/V STORAGE 1ST. FL. 1 L01 D025 PassHeat Detector EQUIP/WORKROOM 1329 1ST FL. 1 L01 D026 PassHeat Detector EQUIP/WORKROOM 1329 1ST. FL. 1 L01 D027 PassHeat Detector STORAGE ROOM 1332 1ST. FL. 1 L01 D028 PassHeat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D029 PassHeat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D030 PassHeat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D031 PassHeat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D032 PassHeat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D033 PassHeat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D034 PassHeat Detector EQUIP/WORKROOM 1325 1ST. FL. 1 L01 D035 PassHeat Detector EQUIP/WORKROOM 1325 1ST. FL. 1 L01 D036 PassHeat Detector STORAGE ROOM 1328 1ST. FL. 1 L01 D037 PassHeat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D038 PassHeat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D039 PassHeat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D040 PassHeat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D041 PassHeat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D042 PassHeat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D043 PassHeat Detector EQUIP/WORKROOM 1321 1ST. FL. 1 L01 D044 PassHeat Detector EQUIP/WORKROOM 1321 1ST. FL. 1 L01 D045 Pass

Initiating Device Testing

Page 368: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Heat Detector STORAGE ROOM 1324 1ST. FL. 1 L01 D046 PassHeat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D047 PassHeat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D048 PassHeat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D049 PassHeat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D050 PassHeat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D051 PassHeat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D052 PassHeat Detector EQUIP/WORKROOM 1315 1ST. FL. 1 L01 D053 PassHeat Detector STORAGE ROOM 1317 1ST. FL. 1 L01 D054 PassHeat Detector EQUIP/WORKROOM 1315 1ST. FL. 1 L01 D055 PassHeat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D056 PassHeat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D057 PassHeat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D058 PassHeat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D059 PassHeat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D060 PassHeat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D061 Pass

Smoke Detector BOYS GYM COACH 1ST. FL. 1 L01 D062 PassSmoke Detector GIRLS GYM COACH 1ST. FL. 1 L01 D063 PassHeat Detector PUBLIC SAFE 1204 STO. 1ST. FL. 1 L01 D064 PassHeat Detector STORAGE ROOM 1207 1ST. FL. 1 L01 D065 PassHeat Detector STORAGE ROOM 1301-B 1ST. FL. 1 L01 D066 PassHeat Detector CUSTODIAN 1403 1ST. FL. 1 L01 D067 PassHeat Detector BUILDING SERV. 1206 1ST. FL. 1 L01 D068 PassHeat Detector BUILDING SERV. 1206 1ST. FL. 1 L01 D069 PassHeat Detector BUILDING SERV. 1206 1ST. FL. 1 L01 D070 Pass

Smoke Detector BUILDING SERV. 1206 1ST. FL. 1 L01 D071 PassHeat Detector ADMIN. VAULT 1ST. FL. 1 L01 D072 PassHeat Detector STORAGE ROOM 1108 1ST. FL. 1 L01 D073 PassHeat Detector MECHANICAL ROOM 1111 1ST. FL. 1 L01 D074 PassHeat Detector STORAGE ROOM 1509 1ST. FL. 1 L01 D075 PassHeat Detector ROOM 1406 1ST. FL. 1 L01 D076 PassDuct Detector BOYS LOCKER 1ST. FL. 1 L01 D077 PassDuct Detector BOYS LOCKER 1ST. FL. 1 L01 D078 PassDuct Detector GYM AT LOCKER ROOMS 1ST. FL. 1 L01 D079 PassDuct Detector GIRLS LOCKER 1ST. FL. 1 L01 D080 PassDuct Detector GIRLS LOCKER 1ST. FL. 1 L01 D081 PassDuct Detector GYM CEILING 1ST. FL. 1 L01 D090 VisualDuct Detector GYM CEILING 1ST. FL. 1 L01 D091 VisualDuct Detector GYM CEILING 1ST. FL 1 L01 D092 VisualDuct Detector GYM CEILING 1ST. FL 1 L01 D093 VisualDuct Detector GYM CEILING 1ST. FL 1 L01 D094 VisualDuct Detector GYM CEILING 1ST. FL 1 L01 D095 VisualDuct Detector GYM CEILING 1ST. FL 1 L01 D096 VisualDuct Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D097 PassDuct Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D098 PassDuct Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D099 PassDuct Detector MECHATRONICS 1326 1ST. FL. 1 L01 D100 Pass

Page 369: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Duct Detector MECHATRONICS 1326 1ST. FL. 1 L01 D101 PassDuct Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D102 Pass

Smoke Detector ELEVATOR EQUIPMENT 1ST. FL. 1 L01 D149 PassDuct Detector GYM OFFICE 1ST. FL. 1 L01 D150 PassDuct Detector GYM OFFICE 1ST. FL. 1 L01 D151 PassDuct Detector GYM OFFICE 1ST. FL. 1 L01 D152 Pass

Pull Station STAIR WELL 3 1ST. FL 1 L01 M001 PassPull Station STAIR 3 VESTIBULE 1ST. FL 1 L01 M002 PassPull Station VESTIBULE BY MEDIA 1ST. FL 1 L01 M003 PassPull Station VESTIBULE BY 1329 1ST. FL. 1 L01 M004 PassPull Station VESTIBULE BY 1309 1ST. FL. 1 L01 M005 PassPull Station STAIR WELL 41ST. FL 1 L01 M006 PassPull Station ENG. TECH LAB. 1ST. FL. 1 L01 M007 PassPull Station MECHATRONICS LAB 1ST. FL. 1 L01 M008 PassPull Station ENG. TECH LAB. 1322 1ST. FL. 1 L01 M009 PassPull Station FLIGHT OP. LAB. 1ST. FL. 1 L01 M010 PassPull Station GYM VESTIBULE 1ST. FL. 1 L01 M012 PassPull Station GYM VESTIBULE 1 L01 M013 PassPull Station STAIR WELL 2 1ST. FL. 1 L01 M014 PassPull Station ENTRY LOBBY BY ADMIN 1ST. FL. 1 L01 M015 PassPull Station ENTRY LOBBY BY ADMIN 1ST. FL. 1 L01 M016 PassPull Station ENTRY VEST. TO ADMIN 1ST. FL 1 L01 M017 PassPull Station EXIT AT STAIR 2 1ST. FL 1 L01 M018 PassPull Station STAIR 1 1ST FL 1 L01 M019 PassPull Station STAIR 1 1ST FL. 1 L01 M020 PassPull Station ELEVATOR LOBBY 1ST. FL. 1 L01 M021 Pass

Tamper Switch STAIR 3 1ST FL. 1 L01 M022 Pass

Waterflow Switch STAIR WELL 3 1ST. FL. 1 L01 M023 PassTamper Switch STAIR 1 1ST. FL 1 L01 M024 Pass

Waterflow Switch STAIR 1 1ST. FL. 1 L01 M025 PassHeat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D001 PassHeat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D002 PassHeat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D003 PassHeat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D004 PassHeat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D005 PassHeat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D006 PassHeat Detector KITCHEN DRY STORAGE 2ND. FL. 2 L02 D007 PassHeat Detector KITCHEN DRY STORAGE 2ND. FL. 2 L02 D008 PassHeat Detector KITCHEN LOCKER ROOM 2ND. FL. 2 L02 D009 PassHeat Detector KITCHEN LAUNDRY ROOM 2ND. FL. 2 L02 D010 PassHeat Detector KITCHEN CUSTODIAN 2ND. FL. 2 L02 D011 PassHeat Detector KITCHEN 2ND. FL. 2 L02 D012 PassHeat Detector KITCHEN 2ND. FL. 2 L02 D013 PassDuct Detector KITCHEN 2ND. FL. 2 L02 D014 PassHeat Detector SERVING LINE 2ND. FL. 2 L02 D015 Pass

Page 370: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Heat Detector SERVING LINE 2ND. FL. 2 L02 D016 PassHeat Detector DISH WASH 2ND. FL. 2 L02 D017 PassDuct Detector DUCT DET. RM 2311 2 L02 D018 PassHeat Detector BREAK ROOM BY GUEST JAA 2 L02 D019 PassHeat Detector IDF 2609 2ND. FL. 2 L02 D021 PassHeat Detector BUILDING SERV. 2406 2ND. FL. 2 L02 D023 PassHeat Detector BUILDING SERV. 2406 2ND. FL. 2 L02 D024 Pass

Smoke Detector STORAGE ROOM 2404-A 2ND. FL. 2 L02 D025 PassHeat Detector BUILDING SERV. 2406 2ND. FL. 2 L02 D026 PassHeat Detector CUSTODIAN 2603 2ND. FL. 2 L02 D027 PassHeat Detector STORAGE ROOM 2315 2ND. FL. 2 L02 D028 PassHeat Detector STORAGE ROOM 2314 2ND. FL. 2 L02 D029 PassHeat Detector PUBLIC SAFETY LAB. 2ND. FL. 2 L02 D030 PassHeat Detector SCHOOL STORE 2ND. FL. 2 L02 D031 PassHeat Detector STORAGE ROOM 2402-A 2ND. FL. 2 L02 D032 PassHeat Detector CUSTODIAN 2407 2ND. FL. 2 L02 D033 PassHeat Detector BUILDING SERV. 2206 2ND. FL. 2 L02 D034 PassHeat Detector BUILDING SERV. 2206 2ND. FL. 2 L02 D036 PassHeat Detector BUILDING SERV. 2206 2ND. FL. 2 L02 D037 Pass

Smoke Detector MECHANICAL ROOM 2306 2ND. FL. 2 L02 D038 PassHeat Detector STUDENT RECORDS 2ND. FL. 2 L02 D039 Pass

Smoke Detector STORAGE 2110 2ND. FL. 2 L02 D040 PassHeat Detector CLINIC 2ND. FL. 2 L02 D041 PassHeat Detector STORAGE ROOM 2509 2ND. FL. 2 L02 D042 Pass

Smoke Detector FIRE DOOR AT KITCHEN 2ND. FL. 2 L02 D044 PassSmoke Detector FIRE DOOR AT KITCHEN 2ND. FL. 2 L02 D045 PassSmoke Detector FIRE DOORS STAIR 3 2ND. FL. 2 L02 D046 PassSmoke Detector FIRE DOORS STAIR 3 2ND. FL. 2 L02 D047 PassSmoke Detector FIRE DOORS BY 2507 2ND. FL. 2 L02 D048 PassSmoke Detector FIRE DOORS BY 2507 2ND. FL. 2 L02 D049 PassSmoke Detector STAIR 4 FIRE DOORS 2ND. FL. 2 L02 D050 PassSmoke Detector STAIR 4 FIRE DOORS 2ND. FL. 2 L02 D051 PassSmoke Detector FIRE DOORS BY DINING 2ND. FL. 2 L02 D052 PassSmoke Detector FIRE DOORS BY DINING 2ND. FL. 2 L02 D053 PassSmoke Detector ELEVATOR LOBBY 2ND. FL. 2 L02 D054 PassSmoke Detector SPECIAL ED. ROOM 2403 2ND. FL. 2 L02 D055 PassSmoke Detector SPECIAL ED. ROOM 2401 2ND. FL. 2 L02 D056 PassSmoke Detector FIRE DOOR STAIR 2 2ND. FL. 2 L02 D057 PassSmoke Detector FIRE DOOR STAIR 2 2ND. FL. 2 L02 D058 PassSmoke Detector FIRE DOOR AT STAIR 1 2ND. FL. 2 L02 D059 PassSmoke Detector FIRE DOOR AT STAIR 1 2ND. FL. 2 L02 D060 PassDuct Detector KITCHEN 2ND. FL. 2 L02 D063 PassDuct Detector SERVING LINE 2ND. FL. 2 L02 D064 PassDuct Detector SERVING LINE 2ND. FL. 2 L02 D065 PassDuct Detector SERVING LINE 2ND. FL. 2 L02 D066 PassDuct Detector SERVING LINE 2ND. FL. 2 L02 D067 PassDuct Detector FOYER TO STAIR 3 2 L02 D068 Pass

Page 371: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Duct Detector BATHROOM 2607 2ND. FL. 2 L02 D069 PassDuct Detector BUILDING SERV. 2406 2ND. FL. 2 L02 D072 PassHeat Detector ROOM 2206 2 L02 D074 PassHeat Detector ROOM 2406 2 L02 D075 PassHeat Detector ROOM 2406 2 L02 D076 PassDuct Detector HALL BY 2316 2ND. FL. 2 L02 D079 PassDuct Detector HALL BY 2311 2ND. FL. 2 L02 D080 PassDuct Detector HALL BY 2311 2ND. FL. 2 L02 D081 PassHeat Detector KITCHEN 2ND. FL. 2 L02 D086 PassDuct Detector FIRE DOORS AT KITCHEN 2ND. FL. 2 L02 D088 PassHeat Detector PREP ROOM 3512 3RD. FL. 3 L02 D090 Pass

Smoke Detector IDF ROOM 3609 3RD. FL. 3 L02 D091 PassHeat Detector BUILDING SERV. 3406 3RD. FL. 3 L02 D092 PassHeat Detector BUILDING SERV. 3406 3RD. FL. 3 L02 D094 PassHeat Detector BUILDING SERV. 3406 3RD. FL. 3 L02 D095 PassHeat Detector BUILDING SERV. 3406 3RD. FL. 3 L02 D096 PassDuct Detector BUILDING SERV. 3406 3RD. FL. 3 L02 D097 PassHeat Detector PREP ROOM 3312 3RD. FL. 3 L02 D098 Pass

Smoke Detector PREP ROOM 3307 3RD. FL. 3 L02 D100 PassHeat Detector ELEVATOR SHAFT 3 L02 D101 PassHeat Detector PENTHOUSE 4 L02 D102 PassHeat Detector ELEVATOR SHAFT PENTHOUSE 4 L02 D103 Pass

Smoke Detector CUSTODIAN 3403 3RD. FL. 3 L02 D104 PassHeat Detector BUILDING SERV. 3204 3RD. FL. 3 L02 D105 PassHeat Detector BUILDING SERV. 3204 3RD. FL. 3 L02 D106 PassHeat Detector BUILDING SERV. 3204 3RD. FL. 3 L02 D107 PassHeat Detector BUILDING SERV. 3204 3RD. FL. 3 L02 D108 PassHeat Detector LAUNDRY STOR. 3205 3RD. FL. 3 L02 D109 PassHeat Detector EQUIP. STORAGE 3207 3RD. FL. 3 L02 D110 Pass

Smoke Detector FIRE DOOR STAIR 3 3RD. FL. 3 L02 D112 PassSmoke Detector FIRE DOOR STAIR 3 3RD. FL. 3 L02 D113 PassSmoke Detector FIRE DOOR STAIR 4 3RD. FL. 3 L02 D114 PassSmoke Detector FIRE DOOR STAIR 4 3RD. FL. 3 L02 D115 PassSmoke Detector ELEVATOR SHAFT 3 L02 D116 PassSmoke Detector ELEVATOR SHAFT PENTHOUSE 4 L02 D117 PassSmoke Detector ELEVATOR LOBBY PENTHOUSE 4 L02 D118 PassSmoke Detector ELEVATOR LOBBY 3RD. FL. 3 L02 D119 PassSmoke Detector FIRE DOORS STAIR 2 3RD. FL. 3 L02 D120 PassSmoke Detector FIRE DOORS STAIR 2 3RD. FL. 3 L02 D121 PassSmoke Detector FIRE DOOR STAIR 1 3RD. FL. 3 L02 D122 PassSmoke Detector FIRE DOOR STAIR 1 3RD. FL. 3 L02 D123 PassDuct Detector ROOM 3404 3RD. FL. 3 L02 D129 PassDuct Detector HALL BY 3309 3RD. FL. 3 L02 D130 PassDuct Detector ROOM 3204 3RD. FL. 3 L02 D131 PassDuct Detector HALL BY 3404 3RD. FL 3 L02 D132 PassDuct Detector HALL BY 3311 3RD. FL 3 L02 D134 PassDuct Detector CORRIDOR BY 3603 3RD. FL 3 L02 D136 Pass

Page 372: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Duct Detector CAFETERIA CEILING 3RD. FL. 3 L02 D137 PassDuct Detector CAFETERIA CEILING 3RD. FL. 3 L02 D138 PassDuct Detector CAFETERIA CEILING 3RD. FL. 3 L02 D139 PassDuct Detector JA DISCOVERY CEILING 2 L02 D140 VisualDuct Detector JA DISCOVERY CEILING 2 L02 D141 VisualDuct Detector JA DISCOVERY CEILING 2 L02 D142 VisualDuct Detector JA DISCOVERY CEILING 2 L02 D144 VisualDuct Detector HALL BY 3314 3RD FL. 3 L02 D145 PassDuct Detector HALL BY 3310 3RD. FL 3 L02 D146 Pass

Smoke Detector HALL BY 3306 3RD. FL 3 L02 D147 PassSmoke Detector HALL BY 3308 3RD. FL 3 L02 D148 PassDuct Detector ABOVE FREEZER 2ND. FL. 2 L02 D150 PassHeat Detector STAFF BREAK ROOM JA DISCOVERY 2 L02 D151 Pass

Pull Station STAIR 3 EXIT 2ND FL. 2 L02 M001 PassPull Station EXIT BY MECH. ROOM 2901 2ND. FL. 2 L02 M002 PassPull Station MAIN MECHANICAL ROOM 2ND. FL 2 L02 M003 PassPull Station MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 M004 PassPull Station MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 M005 PassPull Station KITCHEN EXIT 2 L02 M006 PassPull Station STAIR 3 EXIT 2ND. FL. 2 L02 M007 PassPull Station STAIR 4 2ND FL 2 L02 M008 PassPull Station STAIR 3 EXIT 3RD. FL. 3 L02 M009 PassPull Station EXIT AT STAIR 2 2ND FL 2 L02 M010 PassPull Station AT STAIR 1 2ND. FL 2 L02 M011 Pass

Tamper Switch REAR ELECT. 2 L02 M012 PassPull Station GUEST BAR EXIT 2 L02 M013 PassPull Station PRE- FUNCTION EXIT 2 L02 M015 Pass

Tamper Switch MAIN MECHANICAL ROOM 2ND FL 2 L02 M016 Pass

Waterflow Switch MAIN MECHANICAL ROOM 2ND FL. 2 L02 M017 PassTamper Switch MAIN MECHANICAL ROOM 2ND FL. 2 L02 M018 Pass

Waterflow Switch MAIN MECHANICAL ROOM 2ND FL. 2 L02 M019 PassTamper Switch MAIN MECHANICAL ROOM 2ND FL. 2 L02 M020 Pass

Waterflow Switch MAIN MECHANICAL ROOM 2ND FL. 2 L02 M021 PassTamper Switch STAIR WELL 3 2ND FL 2 L02 M024 Pass

Waterflow Switch STAIR WELL 3 2ND FL 2 L02 M025 PassTamper Switch STAIR 1 2ND FL 2 L02 M026 Pass

Waterflow Switch STAIR 1 2ND FL 2 L02 M027 PassMonitor MAIN KITCHEN 2ND FL 2 L02 M030 Pass

Pull Station EXIT AT STAIR 4 3RD FL 3 L02 M034 PassPull Station PENTHOUSE 4 L02 M035 PassPull Station ELEVATOR LOBBY 4 L02 M036 PassPull Station STAIR 2 EXIT 3RD FL. 3 L02 M037 Pass

Page 373: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Pull Station EXIT AT STAIR 1 3RD FL 3 L02 M038 PassPull Station PRE- FUNCTION EXIT JA DISCOVERY 2 L02 M039 Pass

Tamper Switch STAIR 3 3RD FL. 3 L02 M042 Pass

Waterflow Switch STAIR 3 3RD FL. 3 L02 M043 PassTamper Switch STAIR 1 3RD. FL 3 L02 M044 Pass

Waterflow Switch STAIR 1 3RD. FL 3 L02 M045 PassPull Station COMPUTER LAB 2318 2ND. FL 2 L02 M120 Pass

Page 374: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

(1) Strobe not functional in JA Discovery Area inside ADP booth.

Deficiencies 1. (1) NAC 3 trouble on BPS #9 in Elecrical Room 5100 for JA Discovery Area reporting to FACP on arrival.2. (3) White system sensor wall mounted speaker strobes did not provide visual notification in JA Discovery Area:

(1) Outside Philanthropy booth.

3. (7) White system sensor wall mounted strobes not functional in JA Discovery Area:(1) Inside Zaxby's booth.(1) Inside Publix booth.(1) Inside Associated Credit Union booth.

(1) Outside Zaxby's booth.

(1) Inside #5105 Classroom.

(1) Inside Bagwell Insurance Group booth.(1) Inside Philanthropy booth.(1) Strobe not functional in JA Discovery Area inside Delta booth.

Page 375: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

All-Star Fire, LLC3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

RecommendationsHeat detector labeled Public Safe 1204 STO - 1st Floor is actually located in Room #1203 - fix description in program.

Page 376: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

13 0

2 0

30 0

40 0

59 0

109 0

52 0

9 0

10 0

Inspector Name : Signature:

Panel Power Loss

Fail

Are Lamps and Displays Operating Properly

Heat Detectors Notifier FSH-851R

Pass

Notifier

Notifier

NBG-12LX

Duct Detectors System Sensor DNR

Waterflow Switches Potter VSR

(678) 691-0011

1100 Lanier 400 Parkway

30040

Notifier

Outside Elec. Rm 2902

Model Name

Cumming GA

Is the Panel Monitored Yes

NFS2-640

EI1273 / WO# 156057

Alliance Academy for Innovation

7/2/2020

Power Supplies Notifier FCPS-24S8

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Who Was Notified Prior to the Start of Testing Monitoring Company & Maintenance Staff

Batteries FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Digital Audio Amplifiers Notifier DAA-2

David Piorkowski

Pass

Pullstations

Smoke Detectors FSP-851

Power Patrol

NFS2-640Control Panel

Pass

Device

Notifier

Interface Equipment

David Piorkowski

Tamper Switches Victaulic Butterfly

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 377: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Fail

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.6 Pass

Good (2020) 13.6 Pass

Good (2017) 13.5 Pass

Good (2017) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Pass

N/A

Pass

Pass

Pass

N/A

Digital Audio Amplifier @ FACP (Top) 12V 12AH

Digital Audio Amplifier @ FACP (Bottom) 12V 12AH

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 20AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Continued on Page 3 - Battery Testing

FACP (Right) 12V 20AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 378: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Location Floor Size Condition Voltage Load Test

BPS #1 next to FACP (Left) 2 12V 7AH Good (2020) 13.6 Pass

BPS #1 next to FACP (Right) 2 12V 7AH Good (2020) 13.6 Pass

BPS #2 in MDF Rm 1609 (Left) 1 12V 7AH Good (2020) 13.7 Pass

BPS #2 in MDF Rm 1609 (Right) 1 12V 7AH Good (2020) 13.7 Pass

BPS #3 in MDF Rm 1609 (Left) 1 12V 7AH Good (2020) 13.7 Pass

BPS #3 in MDF Rm 1609 (Right) 1 12V 7AH Good (2020) 13.7 Pass

BPS #4 in MDF Rm 1609 (Left) 1 12V 7AH Good (2020) 13.6 Pass

BPS #4 in MDF Rm 1609 (Right) 1 12V 7AH Good (2020) 13.6 Pass

BPS #5 in IDF Rm 2609 (Left) 2 12V 7AH Good (2020) 13.7 Pass

BPS #5 in IDF Rm 2609 (Right) 2 12V 7AH Good (2020) 13.7 Pass

BPS #6 in IDF Rm 3609 (Left) 3 12V 7AH Good (2020) 13.7 Pass

BPS #6 in IDF Rm 3609 (Right) 3 12V 7AH Good (2020) 13.7 Pass

BPS #7 in IDF Rm 3609 (Left) 3 12V 7AH Good (2020) 13.7 Pass

BPS #7 in IDF Rm 3609 (Right) 3 12V 7AH Good (2020) 13.7 Pass

BPS #8 in IDF Rm 3609 (Left) 3 12V 7AH Good (2020) 13.7 Pass

BPS #8 in IDF Rm 3609 (Right) 3 12V 7AH Good (2020) 13.7 Pass

BPS #9 in Elec Rm 5100 (Left) 2 12V 7AH Good (2020) 13.7 Pass

BPS #9 in Elec Rm 5100 (Right) 2 12V 7AH Good (2020) 13.7 Pass

BPS #10 in Elec Rm 5100 (Left) 2 12V 7AH Good (2020) 13.6 Pass

BPS #10 in Elec Rm 5100 (Right) 2 12V 7AH Good (2020) 13.6 Pass

BPS #11 in Mech Rm 1111 (Left) 1 12V 7AH Good (2020) 13.6 Pass

BPS #11 in Mech Rm 1111 (Right) 1 12V 7AH Good (2020) 13.6 Pass

BPS #12 in Mech Rm 1111 (Left) 1 12V 7AH Good (2020) 13.7 Pass

BPS #12 in Mech Rm 1111 (Right) 1 12V 7AH Good (2020) 13.7 Pass

BPS #13 in Mech Rm 2306 (Left) 2 12V 7AH Good (2017) 13.5 Pass

BPS #13 in Mech Rm 2306 (Right) 2 12V 7AH Good (2017) 13.6 Pass

Battery Testing (cont.)

Page 379: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Smoke Detector FIRE DOORS BY 1519 1 L01 D001 Pass

Smoke Detector FIRE DOORS BY 1519 1 L01 D002 Pass

Smoke Detector FIRE DOORS BY 1519 1 L01 D003 Pass

Smoke Detector FIRE DOORS BY 1519 1 L01 D004 Pass

Smoke Detector FIRE DOORS BY 1329 1 L01 D005 Pass

Smoke Detector FIRE DOORS BY 1329 1 L01 D006 Pass

Smoke Detector FIRE DOORS STAIR 4 1 L01 D007 Pass

Smoke Detector FIRE DOORS STAIR 4 1 L01 D008 Pass

Smoke Detector ELEVATOR LOBBY 1ST FL. 1 L01 D009 Pass

Smoke Detector FIRE DOORS STAIR 2 1ST FL. 1 L01 D010 Pass

Smoke Detector FIRE DOORS STAIR 2 1ST FL. 1 L01 D011 Pass

Smoke Detector FIRE DOORS BY 1501 1 L01 D012 Pass

Smoke Detector FIRE DOORS BY 1501 1 L01 D013 Pass

Heat Detector MECHANICAL ROOM 1517 1 L01 D014 Pass

Heat Detector EQUIP WORKROOM 1511 1 L01 D015 Pass

Smoke Detector MDF 1609 1ST. FL. 1 L01 D016 Pass

Smoke Detector CUSTODIAN 1608 1ST. FL. 1 L01 D017 Pass

Heat Detector BUILDING SERV. 1406 1ST. FL. 1 L01 D018 Pass

Heat Detector BUILDING SERV. 1406 1ST. FL. 1 L01 D019 Pass

Heat Detector BUILDING SERV. 1406 1ST. FL. 1 L01 D020 Pass

Smoke Detector STORAGE ROOM 1318- B 1 L01 D021 Pass

Smoke Detector STORAGE ROOM 1320 1ST. FL. 1 L01 D022 Pass

Heat Detector ELEVATOR EQUIPMENT 1ST. FL. 1 L01 D023 Pass

Smoke Detector MEDIA PRODUCTION 1ST. FL. 1 L01 D024 Pass

Heat Detector A/V STORAGE 1ST. FL. 1 L01 D025 Pass

Heat Detector EQUIP/WORKROOM 1329 1ST FL. 1 L01 D026 Pass

Heat Detector EQUIP/WORKROOM 1329 1ST. FL. 1 L01 D027 Pass

Heat Detector STORAGE ROOM 1332 1ST. FL. 1 L01 D028 Pass

Heat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D029 Pass

Heat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D030 Pass

Heat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D031 Pass

Heat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D032 Pass

Heat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D033 Pass

Heat Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D034 Pass

Heat Detector EQUIP/WORKROOM 1325 1ST. FL. 1 L01 D035 Pass

Heat Detector EQUIP/WORKROOM 1325 1ST. FL. 1 L01 D036 Pass

Heat Detector STORAGE ROOM 1328 1ST. FL. 1 L01 D037 Pass

Heat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D038 Pass

Heat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D039 Pass

Heat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D040 Pass

Heat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D041 Pass

Heat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D042 Pass

Heat Detector MECHATRONICS. LAB. 1ST. FL. 1 L01 D043 Pass

Heat Detector EQUIP/WORKROOM 1321 1ST. FL. 1 L01 D044 Pass

Heat Detector EQUIP/WORKROOM 1321 1ST. FL. 1 L01 D045 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 380: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector STORAGE ROOM 1324 1ST. FL. 1 L01 D046 Pass

Heat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D047 Pass

Heat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D048 Pass

Heat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D049 Pass

Heat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D050 Pass

Heat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D051 Pass

Heat Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D052 Pass

Heat Detector EQUIP/WORKROOM 1315 1ST. FL. 1 L01 D053 Pass

Heat Detector STORAGE ROOM 1317 1ST. FL. 1 L01 D054 Pass

Heat Detector EQUIP/WORKROOM 1315 1ST. FL. 1 L01 D055 Pass

Heat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D056 Pass

Heat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D057 Pass

Heat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D058 Pass

Heat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D059 Pass

Heat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D060 Pass

Heat Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D061 Pass

Smoke Detector BOYS GYM COACH 1ST. FL. 1 L01 D062 Pass

Smoke Detector GIRLS GYM COACH 1ST. FL. 1 L01 D063 Pass

Heat Detector PUBLIC SAFE 1204 STO. 1ST. FL. 1 L01 D064 Pass

Heat Detector STORAGE ROOM 1207 1ST. FL. 1 L01 D065 Pass

Heat Detector STORAGE ROOM 1301-B 1ST. FL. 1 L01 D066 Pass

Heat Detector CUSTODIAN 1403 1ST. FL. 1 L01 D067 Pass

Heat Detector BUILDING SERV. 1206 1ST. FL. 1 L01 D068 Pass

Heat Detector BUILDING SERV. 1206 1ST. FL. 1 L01 D069 Pass

Heat Detector BUILDING SERV. 1206 1ST. FL. 1 L01 D070 Pass

Smoke Detector BUILDING SERV. 1206 1ST. FL. 1 L01 D071 Pass

Heat Detector ADMIN. VAULT 1ST. FL. 1 L01 D072 Pass

Heat Detector STORAGE ROOM 1108 1ST. FL. 1 L01 D073 Pass

Heat Detector MECHANICAL ROOM 1111 1ST. FL. 1 L01 D074 Pass

Heat Detector STORAGE ROOM 1509 1ST. FL. 1 L01 D075 Pass

Heat Detector ROOM 1406 1ST. FL. 1 L01 D076 Pass

Duct Detector BOYS LOCKER 1ST. FL. 1 L01 D077 Pass

Duct Detector BOYS LOCKER 1ST. FL. 1 L01 D078 Pass

Duct Detector GYM AT LOCKER ROOMS 1ST. FL. 1 L01 D079 Pass

Duct Detector GIRLS LOCKER 1ST. FL. 1 L01 D080 Pass

Duct Detector GIRLS LOCKER 1ST. FL. 1 L01 D081 Pass

Duct Detector GYM CEILING 1ST. FL. 1 L01 D090 Visual

Duct Detector GYM CEILING 1ST. FL. 1 L01 D091 Visual

Duct Detector GYM CEILING 1ST. FL 1 L01 D092 Visual

Duct Detector GYM CEILING 1ST. FL 1 L01 D093 Visual

Duct Detector GYM CEILING 1ST. FL 1 L01 D094 Visual

Duct Detector GYM CEILING 1ST. FL 1 L01 D095 Visual

Duct Detector GYM CEILING 1ST. FL 1 L01 D096 Visual

Duct Detector FLIGHT OP. LAB. 1312 1ST. FL. 1 L01 D097 Pass

Duct Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D098 Pass

Duct Detector ENG. TECH LAB. 1322 1ST. FL. 1 L01 D099 Pass

Duct Detector MECHATRONICS 1326 1ST. FL. 1 L01 D100 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 381: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector MECHATRONICS 1326 1ST. FL. 1 L01 D101 Pass

Duct Detector ENG. TECH LAB. 1330 1ST. FL. 1 L01 D102 Pass

Smoke Detector ELEVATOR EQUIPMENT 1ST. FL. 1 L01 D149 Pass

Duct Detector GYM OFFICE 1ST. FL. 1 L01 D150 Pass

Duct Detector GYM OFFICE 1ST. FL. 1 L01 D151 Pass

Duct Detector GYM OFFICE 1ST. FL. 1 L01 D152 Pass

Pull Station STAIR WELL 3 1ST. FL 1 L01 M001 Pass

Pull Station STAIR 3 VESTIBULE 1ST. FL 1 L01 M002 Pass

Pull Station VESTIBULE BY MEDIA 1ST. FL 1 L01 M003 Pass

Pull Station VESTIBULE BY 1329 1ST. FL. 1 L01 M004 Pass

Pull Station VESTIBULE BY 1309 1ST. FL. 1 L01 M005 Pass

Pull Station STAIR WELL 41ST. FL 1 L01 M006 Pass

Pull Station ENG. TECH LAB. 1ST. FL. 1 L01 M007 Pass

Pull Station MECHATRONICS LAB 1ST. FL. 1 L01 M008 Pass

Pull Station ENG. TECH LAB. 1322 1ST. FL. 1 L01 M009 Pass

Pull Station FLIGHT OP. LAB. 1ST. FL. 1 L01 M010 Pass

Pull Station GYM VESTIBULE 1ST. FL. 1 L01 M012 Pass

Pull Station GYM VESTIBULE 1 L01 M013 Pass

Pull Station STAIR WELL 2 1ST. FL. 1 L01 M014 Pass

Pull Station ENTRY LOBBY BY ADMIN 1ST. FL. 1 L01 M015 Pass

Pull Station ENTRY LOBBY BY ADMIN 1ST. FL. 1 L01 M016 Pass

Pull Station ENTRY VEST. TO ADMIN 1ST. FL 1 L01 M017 Pass

Pull Station EXIT AT STAIR 2 1ST. FL 1 L01 M018 Pass

Pull Station STAIR 1 1ST FL 1 L01 M019 Pass

Pull Station STAIR 1 1ST FL. 1 L01 M020 Pass

Pull Station ELEVATOR LOBBY 1ST. FL. 1 L01 M021 Pass

Tamper Switch STAIR 3 1ST FL. 1 L01 M022 Pass

Waterflow Switch STAIR WELL 3 1ST. FL. 1 L01 M023 Pass

Tamper Switch STAIR 1 1ST. FL 1 L01 M024 Pass

Waterflow Switch STAIR 1 1ST. FL. 1 L01 M025 Pass

Heat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D001 Pass

Heat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D002 Pass

Heat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D003 Pass

Heat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D004 Pass

Heat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D005 Pass

Heat Detector MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 D006 Pass

Heat Detector KITCHEN DRY STORAGE 2ND. FL. 2 L02 D007 Pass

Heat Detector KITCHEN DRY STORAGE 2ND. FL. 2 L02 D008 Pass

Heat Detector KITCHEN LOCKER ROOM 2ND. FL. 2 L02 D009 Pass

Heat Detector KITCHEN LAUNDRY ROOM 2ND. FL. 2 L02 D010 Pass

Heat Detector KITCHEN CUSTODIAN 2ND. FL. 2 L02 D011 Pass

Heat Detector KITCHEN 2ND. FL. 2 L02 D012 Pass

Heat Detector KITCHEN 2ND. FL. 2 L02 D013 Pass

Duct Detector KITCHEN 2ND. FL. 2 L02 D014 Pass

Heat Detector SERVING LINE 2ND. FL. 2 L02 D015 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 382: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector SERVING LINE 2ND. FL. 2 L02 D016 Pass

Heat Detector DISH WASH 2ND. FL. 2 L02 D017 Pass

Duct Detector DUCT DET. RM 2311 2 L02 D018 Pass

Heat Detector BREAK ROOM BY GUEST JAA 2 L02 D019 Pass

Heat Detector IDF 2609 2ND. FL. 2 L02 D021 Pass

Heat Detector BUILDING SERV. 2406 2ND. FL. 2 L02 D023 Pass

Heat Detector BUILDING SERV. 2406 2ND. FL. 2 L02 D024 Pass

Smoke Detector STORAGE ROOM 2404-A 2ND. FL. 2 L02 D025 Pass

Heat Detector BUILDING SERV. 2406 2ND. FL. 2 L02 D026 Pass

Heat Detector CUSTODIAN 2603 2ND. FL. 2 L02 D027 Pass

Heat Detector STORAGE ROOM 2315 2ND. FL. 2 L02 D028 Pass

Heat Detector STORAGE ROOM 2314 2ND. FL. 2 L02 D029 Pass

Heat Detector PUBLIC SAFETY LAB. 2ND. FL. 2 L02 D030 Pass

Heat Detector SCHOOL STORE 2ND. FL. 2 L02 D031 Pass

Heat Detector STORAGE ROOM 2402-A 2ND. FL. 2 L02 D032 Pass

Heat Detector CUSTODIAN 2407 2ND. FL. 2 L02 D033 Pass

Heat Detector BUILDING SERV. 2206 2ND. FL. 2 L02 D034 Pass

Heat Detector BUILDING SERV. 2206 2ND. FL. 2 L02 D036 Pass

Heat Detector BUILDING SERV. 2206 2ND. FL. 2 L02 D037 Pass

Smoke Detector MECHANICAL ROOM 2306 2ND. FL. 2 L02 D038 Pass

Heat Detector STUDENT RECORDS 2ND. FL. 2 L02 D039 Pass

Smoke Detector STORAGE 2110 2ND. FL. 2 L02 D040 Pass

Heat Detector CLINIC 2ND. FL. 2 L02 D041 Pass

Heat Detector STORAGE ROOM 2509 2ND. FL. 2 L02 D042 Pass

Smoke Detector FIRE DOOR AT KITCHEN 2ND. FL. 2 L02 D044 Pass

Smoke Detector FIRE DOOR AT KITCHEN 2ND. FL. 2 L02 D045 Pass

Smoke Detector FIRE DOORS STAIR 3 2ND. FL. 2 L02 D046 Pass

Smoke Detector FIRE DOORS STAIR 3 2ND. FL. 2 L02 D047 Pass

Smoke Detector FIRE DOORS BY 2507 2ND. FL. 2 L02 D048 Pass

Smoke Detector FIRE DOORS BY 2507 2ND. FL. 2 L02 D049 Pass

Smoke Detector STAIR 4 FIRE DOORS 2ND. FL. 2 L02 D050 Pass

Smoke Detector STAIR 4 FIRE DOORS 2ND. FL. 2 L02 D051 Pass

Smoke Detector FIRE DOORS BY DINING 2ND. FL. 2 L02 D052 Pass

Smoke Detector FIRE DOORS BY DINING 2ND. FL. 2 L02 D053 Pass

Smoke Detector ELEVATOR LOBBY 2ND. FL. 2 L02 D054 Pass

Smoke Detector SPECIAL ED. ROOM 2403 2ND. FL. 2 L02 D055 Pass

Smoke Detector SPECIAL ED. ROOM 2401 2ND. FL. 2 L02 D056 Pass

Smoke Detector FIRE DOOR STAIR 2 2ND. FL. 2 L02 D057 Pass

Smoke Detector FIRE DOOR STAIR 2 2ND. FL. 2 L02 D058 Pass

Smoke Detector FIRE DOOR AT STAIR 1 2ND. FL. 2 L02 D059 Pass

Smoke Detector FIRE DOOR AT STAIR 1 2ND. FL. 2 L02 D060 Pass

Duct Detector KITCHEN 2ND. FL. 2 L02 D063 Pass

Duct Detector SERVING LINE 2ND. FL. 2 L02 D064 Pass

Duct Detector SERVING LINE 2ND. FL. 2 L02 D065 Pass

Duct Detector SERVING LINE 2ND. FL. 2 L02 D066 Pass

Duct Detector SERVING LINE 2ND. FL. 2 L02 D067 Pass

Duct Detector FOYER TO STAIR 3 2 L02 D068 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 383: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector BATHROOM 2607 2ND. FL. 2 L02 D069 Pass

Duct Detector BUILDING SERV. 2406 2ND. FL. 2 L02 D072 Pass

Heat Detector ROOM 2206 2 L02 D074 Pass

Heat Detector ROOM 2406 2 L02 D075 Pass

Heat Detector ROOM 2406 2 L02 D076 Pass

Duct Detector HALL BY 2316 2ND. FL. 2 L02 D079 Pass

Duct Detector HALL BY 2311 2ND. FL. 2 L02 D080 Pass

Duct Detector HALL BY 2311 2ND. FL. 2 L02 D081 Pass

Heat Detector KITCHEN 2ND. FL. 2 L02 D086 Pass

Duct Detector FIRE DOORS AT KITCHEN 2ND. FL. 2 L02 D088 Pass

Heat Detector PREP ROOM 3512 3RD. FL. 3 L02 D090 Pass

Smoke Detector IDF ROOM 3609 3RD. FL. 3 L02 D091 Pass

Heat Detector BUILDING SERV. 3406 3RD. FL. 3 L02 D092 Pass

Heat Detector BUILDING SERV. 3406 3RD. FL. 3 L02 D094 Pass

Heat Detector BUILDING SERV. 3406 3RD. FL. 3 L02 D095 Pass

Heat Detector BUILDING SERV. 3406 3RD. FL. 3 L02 D096 Pass

Duct Detector BUILDING SERV. 3406 3RD. FL. 3 L02 D097 Pass

Heat Detector PREP ROOM 3312 3RD. FL. 3 L02 D098 Pass

Smoke Detector PREP ROOM 3307 3RD. FL. 3 L02 D100 Pass

Heat Detector ELEVATOR SHAFT 3 L02 D101 Pass

Heat Detector PENTHOUSE 4 L02 D102 Pass

Heat Detector ELEVATOR SHAFT PENTHOUSE 4 L02 D103 Pass

Smoke Detector CUSTODIAN 3403 3RD. FL. 3 L02 D104 Pass

Heat Detector BUILDING SERV. 3204 3RD. FL. 3 L02 D105 Pass

Heat Detector BUILDING SERV. 3204 3RD. FL. 3 L02 D106 Pass

Heat Detector BUILDING SERV. 3204 3RD. FL. 3 L02 D107 Pass

Heat Detector BUILDING SERV. 3204 3RD. FL. 3 L02 D108 Pass

Heat Detector LAUNDRY STOR. 3205 3RD. FL. 3 L02 D109 Pass

Heat Detector EQUIP. STORAGE 3207 3RD. FL. 3 L02 D110 Pass

Smoke Detector FIRE DOOR STAIR 3 3RD. FL. 3 L02 D112 Pass

Smoke Detector FIRE DOOR STAIR 3 3RD. FL. 3 L02 D113 Pass

Smoke Detector FIRE DOOR STAIR 4 3RD. FL. 3 L02 D114 Pass

Smoke Detector FIRE DOOR STAIR 4 3RD. FL. 3 L02 D115 Pass

Smoke Detector ELEVATOR SHAFT 3 L02 D116 Pass

Smoke Detector ELEVATOR SHAFT PENTHOUSE 4 L02 D117 Pass

Smoke Detector ELEVATOR LOBBY PENTHOUSE 4 L02 D118 Pass

Smoke Detector ELEVATOR LOBBY 3RD. FL. 3 L02 D119 Pass

Smoke Detector FIRE DOORS STAIR 2 3RD. FL. 3 L02 D120 Pass

Smoke Detector FIRE DOORS STAIR 2 3RD. FL. 3 L02 D121 Pass

Smoke Detector FIRE DOOR STAIR 1 3RD. FL. 3 L02 D122 Pass

Smoke Detector FIRE DOOR STAIR 1 3RD. FL. 3 L02 D123 Pass

Duct Detector ROOM 3404 3RD. FL. 3 L02 D129 Pass

Duct Detector HALL BY 3309 3RD. FL. 3 L02 D130 Pass

Duct Detector ROOM 3204 3RD. FL. 3 L02 D131 Pass

Duct Detector HALL BY 3404 3RD. FL 3 L02 D132 Pass

Duct Detector HALL BY 3311 3RD. FL 3 L02 D134 Pass

Duct Detector CORRIDOR BY 3603 3RD. FL 3 L02 D136 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 384: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector CAFETERIA CEILING 3RD. FL. 3 L02 D137 Pass

Duct Detector CAFETERIA CEILING 3RD. FL. 3 L02 D138 Pass

Duct Detector CAFETERIA CEILING 3RD. FL. 3 L02 D139 Pass

Duct Detector JA DISCOVERY CEILING 2 L02 D140 Visual

Duct Detector JA DISCOVERY CEILING 2 L02 D141 Visual

Duct Detector JA DISCOVERY CEILING 2 L02 D142 Visual

Duct Detector JA DISCOVERY CEILING 2 L02 D144 Visual

Duct Detector HALL BY 3314 3RD FL. 3 L02 D145 Pass

Duct Detector HALL BY 3310 3RD. FL 3 L02 D146 Pass

Smoke Detector HALL BY 3306 3RD. FL 3 L02 D147 Pass

Smoke Detector HALL BY 3308 3RD. FL 3 L02 D148 Pass

Duct Detector ABOVE FREEZER 2ND. FL. 2 L02 D150 Pass

Heat Detector STAFF BREAK ROOM JA DISCOVERY 2 L02 D151 Pass

Pull Station STAIR 3 EXIT 2ND FL. 2 L02 M001 Pass

Pull Station EXIT BY MECH. ROOM 2901 2ND. FL. 2 L02 M002 Pass

Pull Station MAIN MECHANICAL ROOM 2ND. FL 2 L02 M003 Pass

Pull Station MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 M004 Pass

Pull Station MAIN ELECTRICAL ROOM 2ND. FL. 2 L02 M005 Pass

Pull Station KITCHEN EXIT 2 L02 M006 Pass

Pull Station STAIR 3 EXIT 2ND. FL. 2 L02 M007 Pass

Pull Station STAIR 4 2ND FL 2 L02 M008 Pass

Pull Station STAIR 3 EXIT 3RD. FL. 3 L02 M009 Pass

Pull Station EXIT AT STAIR 2 2ND FL 2 L02 M010 Pass

Pull Station AT STAIR 1 2ND. FL 2 L02 M011 Pass

Tamper Switch REAR ELECT. 2 L02 M012 Pass

Pull Station GUEST BAR EXIT 2 L02 M013 Pass

Pull Station PRE- FUNCTION EXIT 2 L02 M015 Pass

Tamper Switch MAIN MECHANICAL ROOM 2ND FL 2 L02 M016 Pass

Waterflow Switch MAIN MECHANICAL ROOM 2ND FL. 2 L02 M017 Pass

Tamper Switch MAIN MECHANICAL ROOM 2ND FL. 2 L02 M018 Pass

Waterflow Switch MAIN MECHANICAL ROOM 2ND FL. 2 L02 M019 Pass

Tamper Switch MAIN MECHANICAL ROOM 2ND FL. 2 L02 M020 Pass

Waterflow Switch MAIN MECHANICAL ROOM 2ND FL. 2 L02 M021 Pass

Tamper Switch STAIR WELL 3 2ND FL 2 L02 M024 Pass

Waterflow Switch STAIR WELL 3 2ND FL 2 L02 M025 Pass

Tamper Switch STAIR 1 2ND FL 2 L02 M026 Pass

Waterflow Switch STAIR 1 2ND FL 2 L02 M027 Pass

Monitor MAIN KITCHEN 2ND FL 2 L02 M030 Pass

Pull Station EXIT AT STAIR 4 3RD FL 3 L02 M034 Pass

Pull Station PENTHOUSE 4 L02 M035 Pass

Pull Station ELEVATOR LOBBY 4 L02 M036 Pass

Pull Station STAIR 2 EXIT 3RD FL. 3 L02 M037 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 385: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station EXIT AT STAIR 1 3RD FL 3 L02 M038 Pass

Pull Station PRE- FUNCTION EXIT JA DISCOVERY 2 L02 M039 Pass

Tamper Switch STAIR 3 3RD FL. 3 L02 M042 Pass

Waterflow Switch STAIR 3 3RD FL. 3 L02 M043 Pass

Tamper Switch STAIR 1 3RD. FL 3 L02 M044 Pass

Waterflow Switch STAIR 1 3RD. FL 3 L02 M045 Pass

Pull Station COMPUTER LAB 2318 2ND. FL 2 L02 M120 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 386: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

(1) Strobe not functional in JA Discovery Area inside ADP booth.

Deficiencies

1. (1) NAC 3 trouble on BPS #9 in Elecrical Room 5100 for JA Discovery Area reporting to FACP on arrival.

2. (3) White system sensor wall mounted speaker strobes did not provide visual notification in JA Discovery Area:

(1) Outside Philanthropy booth.

3. (7) White system sensor wall mounted strobes not functional in JA Discovery Area:

(1) Inside Zaxby's booth.

(1) Inside Publix booth.

(1) Inside Associated Credit Union booth.

(1) Outside Zaxby's booth.

(1) Inside #5105 Classroom.

(1) Inside Bagwell Insurance Group booth.

(1) Inside Philanthropy booth.

(1) Strobe not functional in JA Discovery Area inside Delta booth.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 387: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

Heat detector labeled Public Safe 1204 STO - 1st Floor is actually located in Room #1203 -

fix description in program.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 388: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 5 0

12 0

20 0

34 0

6 0

3 0

3 0

Inspector Name : Signature:

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

6/24/2020

EI1273 / WO #155470

4098-9685

Tamper Kennedy TBD

Batteries

Pullstations

Simplex Smoke Detectors 4098-9714

Duct Detectors Simplex

Pass

3655 Castleberry Road

George W Whitlow Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office Hall

Model Name 4010Simplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

All-Star Fire, LLC

Power Patrol

Simplex 4099-9006

FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

PotterWaterflow VSR-F

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 389: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.4 Pass

Good (2019) 13.1 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

Good (2019) 13.4 Pass

Good (2019) 13.3 Pass

Good (2019) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

12v 7ah

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FCPS (right) #1 rm 257

FCPS (left) #1 rm 257

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #4 rm 157

FCPS (right) #4 rm 157

FCPS (left) #5 rm 157

FCPS (right) #5 rm 157

12v 7ah

12v 7ah

12v 7ah

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #3 rm 388

FCPS (left) #2 rm 257

FCPS (left) #3 rm 388

FCPS (right) #2 rm 257

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 390: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Smoke Detector Reception Sec Hall 1 M1-1 Pass

Smoke Detector Elect rm 133 1 M1-2 Pass

Duct Detector Lobby Corr 201 1 M1-3 Pass

Duct Detector Mech rm 344 1 M1-6 Pass

Duct Detector Corr 356 1 M1-7 Pass

Duct Detector Mech rm 352 1 M1-8 Pass

Duct Detector Corr 337 1 M1-10 Pass

Duct Detector Corr 337 1 M1-11 Pass

Duct Detector Corr 337 1 M1-12 Pass

Duct Detector Corr 337 1 M1-13 Pass

Duct Detector Corr 334 1 M1-14 Pass

Duct Detector Corr 229 1 M1-16 Pass

Duct Detector Corr 208 1 M1-17 Pass

Smoke Detector Elect rm 257A 1 M1-18 Pass

Duct Detector Mech rm 304 1 M1-20 Pass

Smoke Detector Elect rm 309 1 M1-21 Pass

Duct Detector Mech rm 314 1 M1-22 Pass

Duct Detector Corr 287 1 M1-25 Pass

Duct Detector Mech rm 286 1 M1-26 Pass

Duct Detector Mech rm 296 1 M1-27 Pass

Duct Detector Mech rm 267A 1 M1-29 Pass

Duct Detector Mech rm 277 1 M1-30 Pass

Duct Detector Corr 376 1 M1-32 Pass

Duct Detector Mech rm 366 1 M1-33 Pass

Duct Detector Mech rm 372 1 M1-34 Pass

Duct Detector Mech rm 384 1 M1-36 Pass

Smoke Detector Elect rm 388 1 M1-37 Pass

Duct Detector Mech rm 392 1 M1-38 Pass

Duct Detector Corr 138 1 M1-40 Pass

Duct Detector Corr 400 1 M1-41 Pass

Duct Detector Corr 400 1 M1-42 Pass

Duct Detector Corr 400 1 M1-43 Pass

Duct Detector Corr 400 1 M1-44 Pass

Duct Detector Mech rm 414 1 M1-45 Pass

Smoke Detector Elect rm 157 1 M1-47 Visual

Duct Detector Receiving Hall 162A 1 M1-48 Pass

Duct Detector Serving Line 160 1 M1-49 Pass

Duct Detector Cafeteria 1 M1-51 Pass

Duct Detector Corr 159 to Cafe 1 M1-52 Pass

Duct Detector Mech rm 421 1 M1-57 Pass

Pull Station Main Entrance 1 M1-4 Pass

Pull Station Main Entrance 1 M1-5 Pass

Pull Station Corr 356 South Exit 1 M1-9 Pass

Pull Station Corr 337 South Exit 1 M1-15 Pass

Pull Station Lobby 240 North Exit 1 M1-19 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 391: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station Corr 317 South Exit 1 M1-23 Pass

Pull Station Corr 257 East Exit 1 M1-24 Pass

Pull Station Corr 287 South Exit 1 M1-28 Pass

Pull Station Corr 267 North Exit 1 M1-31 Pass

Pull Station Corr 376 South Exit 1 M1-35 Pass

Pull Station Corr 395 South Exit 1 M1-39 Pass

Pull Station Corr 400 South Exit 1 M1-46 Pass

Pull Station Receiving Hall 162A 1 M1-50 Pass

Pull Station Corr 159 to Cafe 1 M1-53 Pass

Pull Station Cafeteria 1 M1-54 Pass

Pull Station Corr 257 West Exit 1 M1-55 Pass

Pull Station Mech rm 158 1 M1-56 Pass

Pull Station Gym 1 M1-58 Pass

Pull Station Gym 1 M1-59 Pass

Pull Station Gym 1 M1-60 Pass

Flow Switch Riser #1 1 M1-61 Pass

Flow Switch Riser #3 1 M1-62 Pass

Flow Switch Riser #2 1 M1-63 Pass

Ansul Kitchen Hood 1 M1-64 Visual

Ansul Sp Ed Kitchen 1 M1-65 Visual

Tamper Switch Riser #1 1 M1-61 Pass

Tamper Switch Riser #2 1 M1-63 Pass

Tamper Switch Riser #3 1 M1-62 Pass

Tamper Switch Main 1 M1-61 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 392: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 393: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 394: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

2 0

Power Supplies 2 0

8 0

4 0

27 0

Inspector Name : Signature:

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

6/24/2020

EI1273 / WO #155470

3655 Castleberry Road

George W. Whitlow Elementary School Trailers

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredRouter Cabinet

Model Name Vista 28Honeywell

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

30040

All-Star Fire, LLC

Power Patrol

Firelite BG-12

FAS1275

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

Vista 28

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Honeywell

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

Pass

SilentKnight 5495

Control Panel

Device

Batteries

Pullstations

System SensorSmoke Detectors 2WT-B

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Pass

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 395: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.2 Pass

Good (2019) 13.3 Pass

Good (2019) 13.1 Pass

Good (2019) 13.2 Pass

Good (2019) 13.3 Pass

Good (2019) 13.2 Pass

Good (2019) 13 Pass

Good (2019) 13 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

FACP (left) #1

12v 7ahFACP (right) #1

12v 7ah

12v 7ah

FCPS (right) #1

FCPS (left) #1

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #2

FACP (left) #2

FCPS (left) #2

FACP (right) #2

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 396: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Smoke Detector 510 1 15 Pass

Smoke Detector 511 1 24 Pass

Smoke Detector 512 1 17 Pass

Smoke Detector 513 1 16 Pass

Smoke Detector 514 1 20 Pass

Pull Station Entry 1 10 Pass

Smoke Detector 515 1 21 Pass

Smoke Detector 516 1 22 Pass

Pull Station Entry 1 11 Pass

Smoke Detector 517 1 23 Pass

Smoke Detector Hall 1 18 Pass

Smoke Detector 519 1 25 Pass

Smoke Detector 518 1 19 Pass

Smoke Detector 521 1 27 Pass

Smoke Detector 520 1 26 Pass

Smoke Detector Hall 1 12 Pass

Smoke Detector Hall 1 13 Pass

Smoke Detector Hall 1 14 Pass

Smoke Detector 501 1 14 Pass

Smoke Detector 502 1 15 Pass

Smoke Detector 503 1 16 Pass

Smoke Detector 504 1 17 Pass

Smoke Detector 505 1 18 Pass

Smoke Detector 506 1 19 Pass

Smoke Detector 507 1 20 Pass

Smoke Detector 508 1 21 Pass

Pull Station Entry 1 10 Pass

Pull Station Entry 1 12 Pass

Smoke Detector Hall 1 11 Pass

Smoke Detector Hall 1 13 Pass

Smoke Detector Hall 1 12 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 397: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 398: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 399: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

6 0

14 0

20 0

7 0

34 0

3 0

4 0

Inspector Name : Signature:

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Pass

Are Lamps and Displays Operating Properly

Power Supplies Simplex 4009

Ground fault

GD-4765-8N

Waterflow Switches System Sensor VSR

Simplex

Simplex

2099-9101

(678) 691-0011

6200 Dahlonega Highway

30028

Simplex

Front Office by Reception

Model Name

Cumming GA

Is the Panel Monitored Yes

4010

EI1273 / WO # 155464

Silver City Elementary

6/9/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC Security (888-745-4733)Monitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Who Was Notified Prior to the Start of Testing Monitoring Company & Staff

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Panel Secondary power loss

Open Circuit Detection

Panel Power Loss

Duct Detectors Simplex

Batteries

4098-9756

David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Power Patrol

4010Control Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Tamper Switches Nibco

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 400: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2016) 13.5 Pass

Good (2016) 13.6 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.8 Pass

Good (2019) 13.8 Pass

Good (2019) 13.7 Pass

Good (2019) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

N/A

Pass

N/AFM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

Fire Alarm Control Panel (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

BPS #3 RM 388 (Left)

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

12V 7AH

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Fire Alarm Control Panel (Right) 12V 7AH

Kitchen Hoods

Location Size

Magnetic Door Holders

BPS #3 RM 388 (Right) 12V 7AH

BPS #4 RM 349 (Left) 12V 7AH

BPS #4 RM 349 (Right) 12V 7AH

BPS #1 RM 133 (Left) 12V 7AH

BPS #1 RM 133 (Right) 12V 7AH

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

12V 7AH

BPS #2 RM 157 (Right) 12V 7AH

Fire Pump Trouble

Fire Pump Phase Reversal

BPS #2 RM 157 (Left)

BPS #5 RM 309 (Left) 12V 7AH

BPS #5 RM 309 (Right) 12V 7AH

BPS #6 RM 229 (Left) 12V 7AH

BPS #6 RM 229 (Right) 12V 7AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 401: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Smoke Detector RECEPTION RM 1.101 1 M1 1 Pass

Pull Station MAIN LOBBY 1.100 1 M1 2 Pass

Pull Station MAIN LOBBY 1.100 1 M1 3 Pass

Duct Detector CORR 1.340 1 M1 4 Pass

Smoke Detector ELEC/STORAGE RM 1.118 1 M1 5 Pass

Duct Detector CORR 1.120 @ MUSIC RM 1 M1 6 Pass

Duct Detector CORR 1.115 @ FAC WORKRM 1 M1 7 Pass

Pull Station CORR 1.115 @ FAC WORKRM 1 M1 8 Pass

Pull Station CAFÉ FRONT EXIT 1 M1 9 Pass

Duct Detector CAFÉ SERVICING LINE 1 M1 10 Pass

Duct Detector KITCHEN 1.135 1 M1 11 Pass

Pull Station KITCHEN EXIT 1.135 1 M1 12 Pass

Monitor KITCHEN HOOD 1 M1 13 Pass

Smoke Detector ELEC RM 1.146 1 M1 14 Pass

Duct Detector CAFÉ @ ELEC RM 1.146 1 M1 15 Pass

Pull Station MECHANICAL RM 1.147 1 M1 16 Pass

Tamper Switch SPRINKLER RM 1.147 MAIN CV 1 M1 17 Pass

Tamper Switch SPRINKLER RM 1.147 RISER 1 1 M1 18 Pass

Pull Station CORR 1.155 @ SIDE EXIT 1 M1 19 Pass

Duct Detector MECH RM 1.150 AT ACTIVITY COURT 1 M1 20 Pass

Pull Station ACTIVITY COURT EXIT @ EQUIP 1 M1 21 Pass

Pull Station ACTIVITY COURT EXIT 1 M1 22 Pass

Duct Detector CORR 1.165 @ 5 GRD CLAS RM 1 M1 23 Pass

Duct Detector CORR 1.165 @ 5 GRD CLAS RM 1 M1 24 Pass

Duct Detector CORR 1.165 @ 5 GRD CLAS RM 1 M1 25 Pass

Duct Detector CORR 1.165 @ 5 GRD CLAS RM 1 M1 26 Pass

Duct Detector MECH RM 414 1 M1 27 Pass

Pull Station CORR 1.165 EXIT 1 M1 28 Pass

Pull Station ACTIVITY COURT BACK EXIT 1 M1 29 Pass

Pull Station CORT 1.175 BACK EXIT 1 M1 30 Pass

Duct Detector MECH RM 372 1 M1 31 Pass

Smoke Detector STORAGE / ELEC RM 1.176 1 M1 32 Pass

Duct Detector MECH RM 392 1 M1 33 Pass

Duct Detector MECH RM 366 1 M1 34 Pass

Duct Detector MECH RM 352 1 M1 35 Pass

Pull Station CORR 1.190 @ BACK EXIT 1 M1 36 Not Found

Duct Detector CORR 1.190 @ 3 & 4 GRD CLASS 1 M1 37 Pass

Duct Detector MECH RM 344 1 M1 38 Pass

Duct Detector CORR 1.220 @ 2 & 3 CLASS 1 M1 39 Not Found

Smoke Detector STORAGE / ELEC RM 1.211 1 M1 40 Pass

Duct Detector MECH RM 1.206 1 M1 41 Pass

Pull Station CORR 1.200 @ BACK EXIT 1 M1 42 Pass

Pull Station CORR 1.200 @ BACK EXIT 1 M1 43 Pass

Duct Detector MECH RM 1.226 1 M1 44 Pass

Duct Detector CORR 1.220 @ 2 & 3 CLASS 1 M1 45 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 402: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector CORR 1.220 @ 2 & 3 CLASS 1 M1 46 Pass

Duct Detector MECH RM 304 1 M1 47 Pass

Duct Detector CORR 1.220 @ 2 & 3 CLASS 1 M1 48 Not Found

Duct Detector CORR 1.220 @ 2 & 3 CLASS 1 M1 49 Pass

Smoke Detector ELEC RM 1.244 @ 1 & 2 CLASS 1 M1 50 Pass

Duct Detector MECH RM 1.238 1 M1 51 Pass

Pull Station CORR 1.240 BACK EXIT 1 M1 52 Pass

Pull Station CORR 1.240 BACK EXIT 1 M1 53 Pass

Duct Detector MECH RM 1.259 1 M1 54 Pass

Duct Detector MECH RM 1.285 1 M1 55 Pass

Duct Detector CORR 1.250 @ FIRST GRADE 1 M1 56 Pass

Pull Station CORR 1.155 EXIT @ FIRST & KID 1 M1 57 Pass

Duct Detector MECH RM 267A 1 M1 58 Pass

Duct Detector MECH RM 1.285 1 M1 59 Pass

Pull Station CORR 1.280 @ FRONT EXIT 1 M1 60 Pass

Pull Station LOBBY 1.300 @ FRONT EXIT 1 M1 61 Pass

Duct Detector CORR 1.315 SPECIAL NEEDS 1 M1 62 Pass

Duct Detector CORR 1.310 1 M1 63 Pass

Smoke Detector ELEC RM 1.308 @ ART CLASS 1 M1 64 Not Found

Waterflow Switch MECHANICAL RM 1.147 RISER 1 1 M1 65 Pass

Waterflow Switch MECHANICAL RM 1.147 RISER 2 1 M1 65 Pass

Tamper Switch MECHANICAL RM 1.147 RISER 2 1 M1 65 PassWaterflow Switch MECHANICAL RM 1.147 RISER 3 1 M1 66 Pass

Tamper Switch MECHANICAL RM 1.147 RISER 3 1 M1 66 Pass

Monitor SPECIAL NEEDS KITCHEN 217 ANSUL SYS 1 M1 110 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 403: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 404: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 405: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

6 0

14 0

20 0

7 0

34 0

3 0

4 0

Inspector Name : Signature:

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Pass

Are Lamps and Displays Operating Properly

Power Supplies Simplex 4009

Ground fault

GD-4765-8N

Waterflow Switches System Sensor VSR

Simplex

Simplex

2099-9101

(678) 691-0011

6200 Dahlonega Highway

30028

Simplex

Front Office by Reception

Model Name

Cumming GA

Is the Panel Monitored Yes

4010

EI1273 / WO # 155464

Silver City Elementary

6/9/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC Security (888-745-4733)Monitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Who Was Notified Prior to the Start of Testing Monitoring Company & Staff

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Panel Secondary power loss

Open Circuit Detection

Panel Power Loss

Duct Detectors Simplex

Batteries

4098-9756

David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Power Patrol

4010Control Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Tamper Switches Nibco

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 406: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2016) 13.5 Pass

Good (2016) 13.6 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

Good (2019) 13.8 Pass

Good (2019) 13.8 Pass

Good (2019) 13.7 Pass

Good (2019) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

N/A

Pass

N/AFM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

Fire Alarm Control Panel (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

BPS #3 RM 388 (Left)

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

12V 7AH

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Fire Alarm Control Panel (Right) 12V 7AH

Kitchen Hoods

Location Size

Magnetic Door Holders

BPS #3 RM 388 (Right) 12V 7AH

BPS #4 RM 349 (Left) 12V 7AH

BPS #4 RM 349 (Right) 12V 7AH

BPS #1 RM 133 (Left) 12V 7AH

BPS #1 RM 133 (Right) 12V 7AH

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

12V 7AH

BPS #2 RM 157 (Right) 12V 7AH

Fire Pump Trouble

Fire Pump Phase Reversal

BPS #2 RM 157 (Left)

BPS #5 RM 309 (Left) 12V 7AH

BPS #5 RM 309 (Right) 12V 7AH

BPS #6 RM 229 (Left) 12V 7AH

BPS #6 RM 229 (Right) 12V 7AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 407: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Smoke Detector RECEPTION RM 1.101 1 M1 1 Pass

Pull Station MAIN LOBBY 1.100 1 M1 2 Pass

Pull Station MAIN LOBBY 1.100 1 M1 3 Pass

Duct Detector CORR 1.340 1 M1 4 Pass

Smoke Detector ELEC/STORAGE RM 1.118 1 M1 5 Pass

Duct Detector CORR 1.120 @ MUSIC RM 1 M1 6 Pass

Duct Detector CORR 1.115 @ FAC WORKRM 1 M1 7 Pass

Pull Station CORR 1.115 @ FAC WORKRM 1 M1 8 Pass

Pull Station CAFÉ FRONT EXIT 1 M1 9 Pass

Duct Detector CAFÉ SERVICING LINE 1 M1 10 Pass

Duct Detector KITCHEN 1.135 1 M1 11 Pass

Pull Station KITCHEN EXIT 1.135 1 M1 12 Pass

Monitor KITCHEN HOOD 1 M1 13 Pass

Smoke Detector ELEC RM 1.146 1 M1 14 Pass

Duct Detector CAFÉ @ ELEC RM 1.146 1 M1 15 Pass

Pull Station MECHANICAL RM 1.147 1 M1 16 Pass

Tamper Switch SPRINKLER RM 1.147 MAIN CV 1 M1 17 Pass

Tamper Switch SPRINKLER RM 1.147 RISER 1 1 M1 18 Pass

Pull Station CORR 1.155 @ SIDE EXIT 1 M1 19 Pass

Duct Detector MECH RM 1.150 AT ACTIVITY COURT 1 M1 20 Pass

Pull Station ACTIVITY COURT EXIT @ EQUIP 1 M1 21 Pass

Pull Station ACTIVITY COURT EXIT 1 M1 22 Pass

Duct Detector CORR 1.165 @ 5 GRD CLAS RM 1 M1 23 Pass

Duct Detector CORR 1.165 @ 5 GRD CLAS RM 1 M1 24 Pass

Duct Detector CORR 1.165 @ 5 GRD CLAS RM 1 M1 25 Pass

Duct Detector CORR 1.165 @ 5 GRD CLAS RM 1 M1 26 Pass

Duct Detector MECH RM 414 1 M1 27 Pass

Pull Station CORR 1.165 EXIT 1 M1 28 Pass

Pull Station ACTIVITY COURT BACK EXIT 1 M1 29 Pass

Pull Station CORT 1.175 BACK EXIT 1 M1 30 Pass

Duct Detector MECH RM 372 1 M1 31 Pass

Smoke Detector STORAGE / ELEC RM 1.176 1 M1 32 Pass

Duct Detector MECH RM 392 1 M1 33 Pass

Duct Detector MECH RM 366 1 M1 34 Pass

Duct Detector MECH RM 352 1 M1 35 Pass

Pull Station CORR 1.190 @ BACK EXIT 1 M1 36 Not Found

Duct Detector CORR 1.190 @ 3 & 4 GRD CLASS 1 M1 37 Pass

Duct Detector MECH RM 344 1 M1 38 Pass

Duct Detector CORR 1.220 @ 2 & 3 CLASS 1 M1 39 Not Found

Smoke Detector STORAGE / ELEC RM 1.211 1 M1 40 Pass

Duct Detector MECH RM 1.206 1 M1 41 Pass

Pull Station CORR 1.200 @ BACK EXIT 1 M1 42 Pass

Pull Station CORR 1.200 @ BACK EXIT 1 M1 43 Pass

Duct Detector MECH RM 1.226 1 M1 44 Pass

Duct Detector CORR 1.220 @ 2 & 3 CLASS 1 M1 45 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 408: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector CORR 1.220 @ 2 & 3 CLASS 1 M1 46 Pass

Duct Detector MECH RM 304 1 M1 47 Pass

Duct Detector CORR 1.220 @ 2 & 3 CLASS 1 M1 48 Not Found

Duct Detector CORR 1.220 @ 2 & 3 CLASS 1 M1 49 Pass

Smoke Detector ELEC RM 1.244 @ 1 & 2 CLASS 1 M1 50 Pass

Duct Detector MECH RM 1.238 1 M1 51 Pass

Pull Station CORR 1.240 BACK EXIT 1 M1 52 Pass

Pull Station CORR 1.240 BACK EXIT 1 M1 53 Pass

Duct Detector MECH RM 1.259 1 M1 54 Pass

Duct Detector MECH RM 1.285 1 M1 55 Pass

Duct Detector CORR 1.250 @ FIRST GRADE 1 M1 56 Pass

Pull Station CORR 1.155 EXIT @ FIRST & KID 1 M1 57 Pass

Duct Detector MECH RM 267A 1 M1 58 Pass

Duct Detector MECH RM 1.285 1 M1 59 Pass

Pull Station CORR 1.280 @ FRONT EXIT 1 M1 60 Pass

Pull Station LOBBY 1.300 @ FRONT EXIT 1 M1 61 Pass

Duct Detector CORR 1.315 SPECIAL NEEDS 1 M1 62 Pass

Duct Detector CORR 1.310 1 M1 63 Pass

Smoke Detector ELEC RM 1.308 @ ART CLASS 1 M1 64 Not Found

Waterflow Switch MECHANICAL RM 1.147 RISER 1 1 M1 65 Pass

Waterflow Switch MECHANICAL RM 1.147 RISER 2 1 M1 65 Pass

Tamper Switch MECHANICAL RM 1.147 RISER 2 1 M1 65 PassWaterflow Switch MECHANICAL RM 1.147 RISER 3 1 M1 66 Pass

Tamper Switch MECHANICAL RM 1.147 RISER 3 1 M1 66 Pass

Monitor SPECIAL NEEDS KITCHEN 217 ANSUL SYS 1 M1 110 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 409: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 410: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 411: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

3 0

2 0

18 0

Inspector Name : Signature: David Piorkowski

Pass

Pullstations

Smoke Detectors 5193SD

Power Patrol

VISTA-128FBPControl Panel

Pass

Device

Honeywell

Interface Equipment

David Piorkowski

Fire-Lite

Honeywell

BG-12

Monitoring Company & Office Staff

Batteries FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Fire-Lite FCPS-24FS8

Who Was Notified Prior to the Start of Testing

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Pass

Are Lamps and Displays Operating Properly

(678) 691-0011

8145 Majors Road

30041

Honeywell

Server Rack in Rm 2701

Model Name

Cumming GA

Is the Panel Monitored Yes

VISTA-128FBP

EI1273 / WO # 155463

Shiloh Point Elementary School - Mobile Classroom

7/8/2020

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 412: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.7 Pass

Good (2020) 13.6 Pass

Good (2020) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

FCPS (Left) 12V 7AH

FCPS (Right) 12V 7AH

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Magnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 20AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 413: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Zone Results

Pull Station Front Entrance 1 10 Pass

Pull Station Rear Exit 1 11 Pass

Smoke Detector Hall Entrance 1 12 Pass

Smoke Detector Hall Center 1 13 Pass

Smoke Detector Hall Exit 1 14 Pass

Smoke Detector Panel Room 2701 1 15 Pass

Smoke Detector Room 2701 1 16 Pass

Smoke Detector Room 2702 1 17 Pass

Smoke Detector Room 2703 1 18 Pass

Smoke Detector Room 2704 1 19 Pass

Smoke Detector Room 2705 1 20 Pass

Smoke Detector Room 2706 1 21 Pass

Smoke Detector Room 2707 1 22 Pass

Smoke Detector Room 2708 1 23 Pass

Smoke Detector Room 2709 1 24 Pass

Smoke Detector Room 2710 1 25 Pass

Smoke Detector Hall Middle 1 26 Pass

Smoke Detector Hall Middle 1 27 Pass

Smoke Detector Room 2711 1 28 Pass

Smoke Detector Room 2712 1 29 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 414: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 415: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 416: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

5 0

14 0

27 0

67 0

6 0

19 0

2 0

2 0

Inspector Name : Signature:

Voice Evacuation Panel Simplex 4003

Heat Detectors Simplex 4098-9733

4009

Duct Detectors Simplex 4098-9756

Waterflow Switches Potter VSR-F

Tamper Switches Kennedy Butterfly

(678) 691-0011

8145 Majors Road

30041

Simplex

Admin Area Work Area Rm 1001

Model Name

Cumming GA

Is the Panel Monitored Yes

4010

EI1273 / WO # 155463

Shiloh Point Elementary School

7/8/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Pass

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing Monitoring Company & Office Staff

Batteries FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Simplex

David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Power Patrol

4010Control Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Simplex

Simplex

4099-9001

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 417: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Fail

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.7 Pass

Good (2020) 13.8 Pass

Good (2020) 13.7 Pass

Good (2020) 13.7 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Pass

N/A

Pass

Pass

N/A

N/A

Voice Evac Rm 1401 (Left) 12V 7AH

Voice Evac Rm 1401 (Right) 12V 7AH

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Continued on Page 3 - Battery Testing

FACP (Right) 12V 7AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 418: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Floor Condition Voltage Load Test

1 Good (2020) 13.9 Pass

1 Good (2020) 13.9 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.8 Pass

1 Good (2020) 13.8 Pass

BPS #5 Rm 2009 (Left) 12V 7AH

BPS #5 Rm 2009 (Right) 12V 7AH

Battery Testing (cont.)

Location Size

BPS #1 Rm 1034 (Left) 12V 7AH

BPS #2 Rm 1207 (Left) 12V 7AH

BPS #2 Rm 1207 (Right) 12V 7AH

BPS #1 Rm 1034 (Right) 12V 7AH

BPS #4 Rm 2203 (Right) 12V 7AH

BPS #3 Rm 1403 (Left) 12V 7AH

BPS #3 Rm 1403 (Right) 12V 7AH

BPS #4 Rm 2203 (Left) 12V 7AH

Page 419: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Pull Station SECOND GRADE CORRIDOR EXIT 2 M1 1 Pass

Smoke Detector FIRST FLOOR RM 1070 SMOKE DOOR 1 M1 2 Pass

Smoke Detector FIRST FLOOR SECOND GRADE CORRIDOR 1 M1 3 Pass

Smoke Detector FIRST FLOOR ELECTRIC RM 1034 1 M1 4 Pass

Smoke Detector ADMIN AREA 1001B 1 M1 5 Pass

Pull Station LOBBY 1000 EXIT 1 M1 6 Pass

Smoke Detector PRINTER ROOM 1209 1 M1 7 Pass

Pull Station LOBBY 1000 EXIT 1 M1 8 Pass

Smoke Detector FIRST FLOOR ELEVATOR LOBBY 1505 1 M1 13 Pass

Heat Detector ELEVATOR 1506 BOTTOM OF SHAFT 1 M1 14 Pass

Smoke Detector ELEVATOR 1506 BOTTOM OF SHAFT 1 M1 15 Pass

Smoke Detector JANITOR 1522 1 M1 16 Pass

Smoke Detector ELECTRIC RM 1528 1 M1 17 Pass

Pull Station PLAYCOURT 1500 EXIT 1 M1 19 Pass

Pull Station LUNCHROOM 1400 1 M1 20 Pass

Smoke Detector FIRST GRADE HALL SMOKE DOOR 1 M1 21 Pass

Smoke Detector FIRST GRADE STAIR 1540 SMOKE DOOR 1 M1 22 Pass

Pull Station STAIR 1540 EXIT 1 M1 23 Pass

Smoke Detector SMOKE DOOR AT PLAYCOURT 1 M1 24 Pass

Smoke Detector PRINTER ROOM 2204 2 M1 25 Pass

Smoke Detector LOBBY SMOKE DOOR AT CORRIDOR 1100 1 M1 26 Pass

Smoke Detector LOBBY SMOKE DOOR AT CORRIDOR 1100 1 M1 27 Pass

Smoke Detector PLAYCOURT SMOKE DOOR AT LOBBY 1 M1 28 Pass

Smoke Detector PRINTER RM 2018 2 M1 29 Pass

Smoke Detector CORRIDOR 1100 SMOKE DOOR AT LOBBY 1 M1 30 Pass

Smoke Detector CORRIDOR 1100 SMOKE DOOR AT LOBBY 1 M1 31 Pass

Duct Detector HVAC RM 1101 1 M1 32 Pass

Duct Detector HVAC RM 1101 1 M1 33 Pass

Smoke Detector PRINTER RM 2521 2 M1 34 Pass

Pull Station MUSIC CLASSROOM 1103 EXIT 1 M1 35 Pass

Pull Station ART CLASSROOM 1105 EXIT 1 M1 36 Pass

Smoke Detector ELECTRIC RM 1108 1 M1 37 Pass

Duct Detector LUNCHROOM 1400 1 M1 38 Pass

Duct Detector LUNCHROOM 1400 1 M1 39 Pass

Smoke Detector SMOKE DOOR AT LOBBY 1300 1 M1 40 Pass

Smoke Detector SMOKE DOOR AT LOBBY 1300 1 M1 41 Pass

Smoke Detector PRINTER RM 1527 1 M1 42 Pass

Smoke Detector LUNCHROOM SMOKE DOOR AT LOBBY 1 M1 43 Pass

Smoke Detector FIRST FLOOR PRINTER RM 1 M1 44 Pass

Smoke Detector LOBBY 1300 SMOKE DOOR AT LUNCHRM 1 M1 45 Pass

Smoke Detector LOBBY 1300 SMOKE DOOR AT 1100 1 M1 46 Pass

Smoke Detector LOBBY 1300 SMOKE DOOR AT 1100 1 M1 47 Pass

Duct Detector HVAC RM 1205 1 M1 48 Pass

Duct Detector HVAC RM 1205 1 M1 49 Pass

Duct Detector HVAC RM 1205 1 M1 50 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 420: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station KINDERGARDEN HALL EXIT 1 M1 51 Pass

Smoke Detector KINDERGARTEN SMOKE DOOR AT STAIR 1242 1 M1 52 Pass

Smoke Detector KINDERGARTEN SMOKE DOOR AT STAIR 1242 1 M1 53 Pass

Pull Station STAIR 1242 EXIT 1 M1 54 Pass

Smoke Detector ELEVATOR 1300B BOTTOM OF SHAFT 1 M1 55 Pass

Heat Detector ELEVATOR 1300B BOTTOM OF SHAFT 1 M1 56 Pass

Smoke Detector ELEVATOR 1300A LOBBY 1 M1 57 Pass

Smoke Detector ELEVATOR EQUIPMENT RM 1306 1 M1 58 Pass

Pull Station MAIN LOBBY 1300 EXIT 1 M1 63 Pass

Pull Station MAIN LOBBY 1300 EXIT 1 M1 64 Pass

Pull Station MAIN LOBBY 1300 EXIT 1 M1 65 Pass

Smoke Detector CAFE ELECTRIC RM 1403 1 M1 66 Pass

Smoke Detector CORRIDOR 1314 SMOKE DOOR 1 M1 67 Pass

Smoke Detector STAIR 1430 SMOKE DOOR 1 M1 68 Pass

Pull Station STAIR 1340 EXIT 1 M1 69 Pass

Pull Station BOILER ROOM 1425 EXIT 1 M1 70 Pass

Smoke Detector PRINT RM 1326 1 M1 71 Pass

Pull Station KITCHEN RECEIVING EXIT 1 M1 72 Pass

Pull Station MECHANICAL ROOM 1420 1 M1 73 Pass

Waterflow Switch MECHANICAL ROOM 1420 1 M1 74 Pass

Smoke Detector ELECTRIC RM 1421 1 M1 75 Pass

Pull Station ELECTRICAL ROOM 1421 EXIT 1 M1 76 Pass

Duct Detector KITCHEN 1412 AHU 1 M1 77 Pass

Smoke Detector STAIR 2070 SMOKE DOOR 2 M1 80 Pass

Smoke Detector FOURTH GRADE HALL SMOKE DOOR 2 M1 81 Pass

Pull Station STAIR 2070 EXIT 2 M1 82 Pass

Smoke Detector SMOKE DOOR AT LOBBY 1000 1 M1 83 Pass

Smoke Detector SMOKE DOOR AT LOBBY 1000 1 M1 84 Pass

Pull Station LOBBY 2000 EXIT 2 M1 85 Pass

Smoke Detector ELECTRICAL RM 2009 2 M1 86 Pass

Duct Detector HVAC RM 2003 AHU 2 M1 87 Pass

Smoke Detector ELEVATOR LOBBY 2501 2 M1 88 Pass

Smoke Detector ELEVATOR TOP OF SHAFT 2 M1 89 Pass

Heat Detector ELEVATOR TOP OF SHAFT 2 M1 90 Visual

Smoke Detector SMOKE DOOR AT LOBBY 1000 1 M1 91 Pass

Smoke Detector SMOKE DOOR AT LOBBY 1000 1 M1 92 Pass

Smoke Detector ELECTRIC RM 2504 2 M1 93 Pass

Smoke Detector FIFTH GRADE SMOKE DOOR AT STAIR 2 M1 95 Pass

Smoke Detector FIFTH GRADE SMOKE DOOR AT STAIR 2 M1 96 Pass

Pull Station STAIR 2540 EXIT 2 M1 97 Pass

Duct Detector MEDIA CENTER 2100 AHU 2 M1 98 Pass

Smoke Detector STAIR 2240 SMOKE DOOR 2 M1 99 Pass

Smoke Detector STAIR 2240 SMOKE DOOR 2 M1 100 Pass

Pull Station STAIR 2240 EXIT 2 M1 101 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 421: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector ELECTRICAL RM 2203 2 M1 102 Pass

Smoke Detector VIDEO HEAD END RM 2109 2 M1 103 Pass

Smoke Detector SMOKE DOOR AT LOBBY 1300 1 M1 104 Pass

Smoke Detector SMOKE DOOR AT LOBBY 1300 1 M1 105 Pass

Smoke Detector ELEVATOR TOP OF SHAFT 2 M1 106 Pass

Smoke Detector ELEVATOR LOBBY 2202 2 M1 107 Pass

Heat Detector ELEVATOR TOP OF SHAFT 2 M1 108 Visual

Pull Station MAIN LOBBY 2300 EXIT 2 M1 109 Pass

Pull Station MAIN LOBBY 2300 EXIT 2 M1 110 Pass

Pull Station MAIN LOBBY 2300 EXIT 2 M1 111 Pass

Smoke Detector FIRST GRADE SMOKE DOOR LOBBY 1 M1 112 Pass

Smoke Detector FIRST GRADE SMOKE DOOR LOBBY 1 M1 113 Pass

Smoke Detector IDF RM 2312 2 M1 114 Pass

Smoke Detector ELECTRICAL RM 2320 2 M1 115 Pass

Smoke Detector PRINT RM 2324 2 M1 116 Pass

Smoke Detector THIRD/FIFTH GRADE SMOKE DOOR AT STAIR 2 M1 117 Pass

Smoke Detector THIRD/FIFTH GRADE SMOKE DOOR AT STAIR 2 M1 118 Pass

Pull Station STAIR 2340 EXIT 2 M1 119 Pass

Duct Detector MEZZANINE LEVEL AHU PH M1 120 Pass

Duct Detector MEZZANINE LEVEL AHU PH M1 121 Pass

Duct Detector LOBBY MECHANICAL RM AHU 1 M1 122 Pass

Duct Detector LOBBY MECHANICAL RM AHU 1 M1 123 Pass

Duct Detector LOBBY MECHANICAL RM AHU 1 M1 124 Pass

Duct Detector LOBBY MECHANICAL RM AHU 1 M1 125 Pass

Duct Detector MEZZANINE LEVEL AHU 2 M1 126 Pass

Smoke Detector ELEVATOR EQUIPMENT RM 1008 1 M1 128 Pass

Waterflow Switch MECHANICAL ROOM 1420 1 M1 131 Pass

Tamper Switch MECHANICAL ROOM 1420 1 M1 132 Pass

Tamper Switch MECHANICAL ROOM 1420 1 M1 133 Pass

Duct Detector MEZZANINE LEVEL AHU 2 M1 134 Pass

Heat Detector ELEVATOR #1 MACHINE RM 1 M1 140 Pass

Heat Detector ELEVATOR #2 MACHINE RM 1 M1 141 Pass

Pull Station MULTI PURPOSE ROOM 1200 1 M1 142 Pass

Duct Detector GYM AHU PH M1 220 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 422: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. (1) Red wall mounted Simplex TrueAlert strobe in Unisex Bathroom 1028 - fails to activate.

2. (1) Red wall mounted Wheelock horn strobe strobe in Kitchen next to Room #1413 fails to provide visual notification.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 423: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 424: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 4 0

12 2

21 0

10 0

95 0

1 0

4 0

Inspector Name : Signature:

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

SimplexVoice Evac 4003

All-Star Fire, LLC

Power Patrol

Simplex 4099-9004

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Suwanee

Are Lamps and Displays Operating Properly

Pass

600 James Burgess Road

Settles Bridge Elementary School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredMain Office

Model Name 4010Simplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC security

4098-9686

Heat Detectors Simplex 4098-9734

Batteries

Pullstations

SimplexSmoke Detectors 4098-9605

Duct Detectors Simplex

30024

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/20/2020

EI1273 / WO #155461

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 425: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.3 Pass

Good (2020) 13.3 Pass

Fair (2019) 12.9 Fail

Fair (2019) 12.9 Fail

Good (2020) 13 Pass

Good (2020) 13.2 Pass

Good (2020) 13.1 Pass

Good (2020) 13.1 Pass

Good (2019) 13 Pass

Good (2019) 13.1 Pass

Good (2020) 13.3 Pass

Good (2020) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

N/A

Pass

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Voice evac

FCPS (left) #4 rm 271

Voice evac

Fire Pump Running

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 437

FCPS (right) #2 rm 437

FCPS (left) #3 rm 237

FCPS (right) #3 rm 237

12v 7ah

12v 7ah

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FCPS (right) #1 rm 510

FCPS (left) #1 rm 510

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FCPS (right) #4 rm 271

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 426: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initaiting Device Testing

Device Type Location Floor Address/Zone Results

Smoke Detector Main Elect rm 1 M1-32 No Access

Pull Station Office 1 M1-1 Pass

Duct Detector Boys RR 229 ERU-sb2 1 M1-10 Not Found

Smoke Detector E Wing Corr 1 M1-102 Pass

Smoke Detector E Wing Corr 1 M1-103 Pass

Pull Station E Wing Corr 1 M1-104 Pass

Smoke Detector E Wing Corr @ Smoke dr 1 M1-105 Pass

Smoke Detector E Wing Corr @ Smoke dr 1 M1-106 Pass

Smoke Detector E Wing rm 401 1 M1-108 Pass

Smoke Detector E Wing rm 401 1 M1-109 Pass

Duct Detector Classroom 301 1 M1-11 Pass

Pull Station E Wing Exit @ rm 401 1 M1-112 Pass

Smoke Detector E Wing Corr 1 M1-113 Pass

Smoke Detector E Wing Corr 1 M1-114 Pass

Smoke Detector E Wing rm 411 1 M1-115 Pass

Smoke Detector E Wing rm 419 1 M1-116 Pass

Smoke Detector E Wing @ rm 423 1 M1-117 Pass

Duct Detector Kitchen 1 M1-12 Pass

Heat Detector E Wing Elect rm 433 1 M1-120 Visual

Smoke Detector E Wing Tele rm 437 1 M1-121 Pass

Pull Station E Wing Corr 1 M1-122 Pass

Tamper Switch E Wing rm 437 1 M1-123 Pass

Smoke Detector E Wing @ rm 439 1 M1-124 Pass

Smoke Detector E Wing @ rm 447 1 M1-127 Pass

Smoke Detector E Wing Corr 1 M1-129 Pass

Ansul Kitchen Hood 1 M1-13 Visual

Smoke Detector E Wing Corr 1 M1-130 Pass

Smoke Detector E Wing Corr 1 M1-131 Pass

Smoke Detector E Wing Corr 1 M1-132 Pass

Smoke Detector E Wing Corr 1 M1-133 Pass

Smoke Detector E Wing Corr 1 M1-135 Pass

Pull Station E Wing Corr 1 M1-136 Pass

Smoke Detector E Wing rm 412 1 M1-137 Pass

Duct Detector Computer rm 1 M1-14 Pass

Smoke Detector E Wing rm 420 1 M1-140 Pass

Smoke Detector E Wing rm 424 1 M1-141 Pass

Heat Detector E Wing Janitor rm 1 M1-143 Visual

Smoke Detector E Wing Stor rm 438 1 M1-144 Pass

Smoke Detector E Wing rm 440 1 M1-145 Pass

Smoke Detector E Wing rm 448 1 M1-148 Pass

Smoke Detector Conference rm Closet 1 M1-15 Not Found

Smoke Detector E Wing Corr 1 M1-152 Pass

Pull Station F Wing Corr 1 M1-153 Pass

Smoke Detector E Wing Corr 1 M1-154 Pass

Smoke Detector F Wing @ rm 237 1 M1-155 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 427: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Tamper Switch F Wing @ rm 237 1 M1-156 Pass

Pull Station E Wing Corr 1 M1-157 Pass

Heat Detector F Wing Elect rm 223 1 M1-158 Visual

Heat Detector F Wing Janitor rm 244 1 M1-159 Visual

Smoke Detector Main Office Closet 1 M1-16 Pass

Smoke Detector F Wing Corr 1 M1-161 Pass

Smoke Detector F Wing @ rm 234 1 M1-162 Pass

Smoke Detector F Wing Corr 1 M1-163 Pass

Smoke Detector F Wing Corr 1 M1-164 Pass

Smoke Detector F Wing Corr 1 M1-166 Pass

Pull Station E Wing Corr 1 M1-167 Pass

Smoke Detector F Wing @ rm 262 1 M1-168 Pass

Smoke Detector F Wing @ rm 263 1 M1-169 Pass

Smoke Detector Main Office Closet 1 M1-17 Pass

Smoke Detector F Wing Corr 1 M1-171 Pass

Duct Detector Rest room 259 1 M1-175 Pass

Duct Detector Multi Purpose rm 401 ERU-SB-4 1 M1-176 Not Found

Smoke Detector Main Office Closet 1 M1-18 Pass

Pull Station Gym 1 M1-2 Pass

Smoke Detector Copy rm 1 M1-20 Pass

Smoke Detector Vault 1 M1-21 Pass

Smoke Detector Riser room 1 M1-22 Pass

Duct Detector Kitchen 1 M1-220 Pass

Duct Detector Gym 1 M1-221 No Access

Smoke Detector Gym Storage 1 M1-23 Pass

Smoke Detector Gym Storage 1 M1-24 Pass

Smoke Detector Gym Storage 1 M1-25 No Access

Smoke Detector Media Production rm 1 M1-26 Pass

Smoke Detector Media Tech Dist 1 M1-27 Pass

Smoke Detector A/V Storage 1 M1-28 Pass

Smoke Detector Music Storage 1 M1-29 Pass

Pull Station Gym 1 M1-3 Pass

Smoke Detector Mech rm 1 M1-30 Pass

Smoke Detector Music Storage 1 M1-31 Pass

Smoke Detector Kitchen Elect rm 1 M1-34 Pass

Smoke Detector Outside Mech rm 1 M1-35 No Access

Smoke Detector Kitchen Storage 1 M1-36 No Access

Smoke Detector Kitchen Storage 1 M1-37 No Access

Smoke Detector Employee Lounge 1 M1-38 Pass

Smoke Detector 1st Grade Corr Smoke dr 1 M1-39 Pass

Pull Station Gym 1 M1-4 Pass

Smoke Detector 1st Grade Corr 1 M1-40 Pass

Smoke Detector 1st Grade Art Storage 1 M1-41 Pass

Smoke Detector 1st Grade Art Rm Closet 1 M1-42 Pass

Smoke Detector 1st Grade Corr Storage Closet 1 M1-43 Pass

Smoke Detector 1st Grade Corr Storage Closet 1 M1-44 Pass

Smoke Detector 1st Grade Corr Storage Closet 1 M1-45 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 428: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector 2nd Grade Corr Storage 1 M1-46 Pass

Smoke Detector 2nd Grade Corr Storage 1 M1-47 Pass

Smoke Detector 2nd Grade Corr Storage 1 M1-48 Pass

Smoke Detector 2nd Grade Corr Storage 1 M1-49 Pass

Pull Station Gym 1 M1-5 Pass

Smoke Detector 1st Grade Corr Mop Closet 1 M1-50 Pass

Smoke Detector Outside Elect rm Wing 2 1 M1-51 Pass

Smoke Detector Kindergarten Storage 1 M1-52 Pass

Smoke Detector Kindergarten Storage 1 M1-53 Pass

Smoke Detector Kindergarten Storage 1 M1-54 Pass

Smoke Detector Kindergarten Storage 1 M1-55 Pass

Smoke Detector Kindergarten Storage 1 M1-56 Pass

Smoke Detector Kindergarten Storage 1 M1-57 Pass

Smoke Detector Kindergarten Storage 1 M1-58 Pass

Smoke Detector Kindergarten Storage 1 M1-59 Pass

Pull Station Cafeteria 1 M1-6 Pass

Smoke Detector 4th Grade Corr Smoke drs 1 M1-60 Pass

Smoke Detector 4th Grade Corr 1 M1-61 Pass

Smoke Detector 4th Grade Corr Storage 1 M1-62 Pass

Smoke Detector 4th gd Storage rm 1 M1-63 Pass

Smoke Detector 4th gd Storage rm 1 M1-64 Pass

Smoke Detector 4th gd Hall Elect rm 1 M1-66 Pass

Smoke Detector 4th gd Storage rm 1 M1-67 Pass

Smoke Detector 2nd Grade Corr Storage 1 M1-68 Pass

Smoke Detector 2nd Grade Corr Storage 1 M1-69 Pass

Pull Station Cafeteria 1 M1-7 Pass

Smoke Detector 2nd Grade Corr Storage 1 M1-70 Pass

Smoke Detector 2nd Grade Corr Storage 1 M1-71 Pass

Smoke Detector 5th gd Janitor Closet 1 M1-72 Pass

Smoke Detector Main Corr Women's RR 1 M1-73 Not Found

Tamper Switch Outside Mech rm @ Kitchen 1 M1-78 No Access

Pull Station Cafeteria 1 M1-8 Pass

Pull Station K, 1st & 2nd North Corr 1 M1-80 Pass

Pull Station K, 1st & 2nd West Corr 1 M1-81 Pass

Pull Station 3 1 M1-83 Pass

Pull Station 3 1 M1-84 Pass

Pull Station 3 1 M1-85 Pass

Pull Station Kitchen 1 M1-9 Pass

Duct Detector Girls RR 231 ERU-SB-2 1 M1-96 Pass

Duct Detector Classroom 309 ERU-SB-1 1 M1-97 Not Found

Smoke Detector 4th gd Storage rm 1 M1-65 Pass

Smoke Detector Main Elect rm 1 M1-32 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 429: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. 2 Batteries failed load test.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 430: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

Recommend all rest rooms have strobe.

Recommend all strobes sync.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 431: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

3 0

3 0

4 0

Inspector Name : Signature:

(678) 691-0011

1655 Spot Rd Connector

30040

Honeywell

Room 2502

Model Name

Cumming GA

Is the Panel Monitored Yes

VISTA-128FBP

EI1273 / WO# 155459

Sawnee Primary School Trailer

6/8/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC Security (888-745-4733)Monitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Pass

Are Lamps and Displays Operating Properly

BG-12

Who Was Notified Prior to the Start of Testing Monitoring Company & Staff

Batteries

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Fire-Lite FSPS-24FS8

Interstate SLA1116

David Piorkowski

Pass

Pullstations

Smoke Detectors 5193SD

VISTA-128FBPControl Panel

Pass

Device

Honeywell

Interface Equipment

David Piorkowski

Fire-Lite

System Sensor

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 432: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.5 Pass

Good (2019) 13.7 Pass

Good (2019) 13.7 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/AFM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 18AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

Fire Alarm Control Panel

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

12V 7AH

Voice Control Panel (Right) 12V 7AH

Fire Pump Trouble

Fire Pump Phase Reversal

Voice Control Panel (Left)

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 433: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Zone Results

Smoke Detector Room 2502 Above FACP 1 10 Pass

Smoke Detector Room 2502 1 11 Pass

Pull Station Room 2502 1 12 Pass

Smoke Detector Room 2501 1 13 Pass

Pull Station Room 2501 1 14 Pass

Smoke Detector Room 2503 1 15 Pass

Pull Station Room 2503 1 16 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 434: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 435: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 436: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

1 0

4 0

6 0

14 0

11 0

8 0

2 0

2 0

Inspector Name : Signature:

Voice Control Panel Simplex 4003

Duct Detectors Air Products RWJ-N

Heat Detectors System Sensor 4098-9733

David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Interstate

4100UControl Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Simplex

Simplex

2099-9101

Who Was Notified Prior to the Start of Testing Monitoring Company & Staff

Batteries SLA1116

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Expansion Power Supply Simplex 566-047

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC Security (888-745-4733)Monitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Pass

Are Lamps and Displays Operating Properly

(678) 691-0011

1655 Spot Road Connector

30040

Simplex

Reception Rm 2102

Model Name

Cumming GA

Is the Panel Monitored Yes

4100U

EI1273

Sawnee Primary School Building

6/8/2020

Tamper Switches Potter OS&Y-SU2

Waterflow Switches Potter VSR

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 437: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.6 Pass

Good (2019) 13.6 Pass

Good (2019) 13.5 Pass

Good (2019) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

Pass

Pass

N/A

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Kitchen Hoods

Location Size

Magnetic Door Holders

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

12V 7AH

Voice Control Panel (Right) 12V 7AH

Fire Pump Trouble

Fire Pump Phase Reversal

Voice Control Panel (Left)

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Fire Alarm Control Panel (Right)

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 18AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

Fire Alarm Control Panel (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

12V 18AH

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 438: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Pull Station Reception Area 1 M2 1 Pass

Pull Station Café 1 M2 2 Pass

Pull Station Café 1 M2 3 Pass

Pull Station Kitchen 1 M2 4 Pass

Pull Station Front Gym Entrance 1 M2 5 Pass

Pull Station Gym Side Exit 1 M2 6 Pass

Smoke Detector B Wing Electrical Rm 1 M2 7 Pass

Smoke Detector B Wing Computer Lab 1 M2 8 Pass

Smoke Detector B Wing Wing Corr @ Fire Door 1 M2 9 Pass

Smoke Detector Center Corr @ B Wing Fire 1 M2 10 Pass

Smoke Detector Center Corr @ C Wing Fire 1 M2 11 Pass

Smoke Detector C Wing Corr Fire Door 1 M2 12 Pass

Smoke Detector Kitchen Telephone Closet 1 M2 13 Pass

Smoke Detector Center Corr @ D Wing Fire 1 M2 14 Pass

Smoke Detector D Wing Corr @ Fire Door 1 M2 15 Pass

Smoke Detector D Wing Telephone Closet 1 M2 16 Pass

Smoke Detector Center Corr @ A Wing Fire 1 M2 17 Pass

Smoke Detector A Wing Corr @ Fire Door 1 M2 18 Pass

Smoke Detector Media Prod Room 105 1 M2 19 Pass

Smoke Detector Media Communications 1 M2 20 Pass

Heat Detector A Wing Mech Room 107 1 M2 21 Pass

Heat Detector A Wing Janitors Closet 108 1 M2 22 Pass

Heat Detector A Wing Main Elect Room 1 M2 23 Pass

Heat Detector A Wing Storage Room 111 1 M2 24 Pass

Heat Detector A Wing Kiln Room 110 1 M2 25 Pass

Heat Detector B Wing Book Storage 1 M2 26 Pass

Heat Detector B Wing Janitor Closet 234 1 M2 27 Pass

Heat Detector B Wing Storage Room 233 1 M2 28 Pass

Heat Detector B Wing Book Storage 236 1 M2 29 Pass

Heat Detector D Wing Book Storage 236 1 M2 30 Pass

Heat Detector D Wing Janitor Closet 445 1 M2 31 Pass

Tamper Switch C-Wing Mechanical Rm 309 1 M2 33 PassWaterflow Switch C-Wing Mechanical Rm 309 1 M2 34 Pass

Monitor Kitchen Hood 1 M2 35 Pass

Duct Detector Dishwasher Room 1 M2 36 Pass

Duct Detector A Wing Mech Room AHU 1 1 M2 37 Pass

Tamper Switch Riser Room 507 Riser 2 1 M2 42 Pass

Waterflow Switch Riser Room 507 Riser 2 1 M2 43 Pass

Duct Detector Kitchen Rear AHU 1 M2 44 Not Found

Duct Detector Gym 1 M2 45 Visual

Duct Detector ERU-SP-2 Classroom 2267 Supply 1 M2 64 Pass

Duct Detector ERU-SP-1 Classroom 2327 Supply 1 M2 65 Pass

Duct Detector ERU-SP-2 Classroom 2275 Return 1 M2 66 Pass

Duct Detector ERU-SP-1 Classroom 2335 Return 1 M2 67 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 439: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 440: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

A/V Bypass button does not bypass all notification in building.

No visual notification in (2) conference rms near front entrance

No visual notification in the (4) bathrooms at the intersecting wings in center of building.

No visual notification in classrooms.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 441: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

3 0

8 0

17 0

12 0

28 0

2 0

2 0

Inspector Name : Signature:

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Pass

Are Lamps and Displays Operating Properly

Power Supplies Simplex 4009

Ground fault

Panel Secondary power loss

Open Circuit Detection

Panel Power Loss

OS&Y-SU2

Waterflow Switches Potter VSR

Simplex

Simplex

2099-9101

Duct Detectors Simplex

Potter

(678) 691-0011

1616 Canton Highway

30040

Simplex

Front Office

Model Name

Cumming GA

Is the Panel Monitored Yes

4010

EI1273

Sawnee Elementary School

6/8/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC Security (888-745-4733)Monitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Who Was Notified Prior to the Start of Testing Monitoring Company & Staff

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Batteries

4098-9756

David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Power Patrol

4010Control Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Tamper Switches

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 442: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.6 Pass

Good (2020) 13.6 Pass

Good (2020) 13.8 Pass

Good (2020) 13.9 Pass

Good (2016) 13.5 Pass

Good (2016) 13.6 Pass

Good (2020) 12.9 Pass

Good (2020) 12.9 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

Pass

N/A

N/AFM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

Fire Pump Running Reports to Panel

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

12V 7AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Supervisory Signals

Site Water Level /Temp

Fire Alarm Control Panel (Left)

Fire Alarm Control Panel (Right) 12V 7AH

BPS Rm 225 (Left) 12V 7AH

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Magnetic Door Holders

BPS Rm 225 (Right) 12V 7AH

BPS Gym (Left) 12V 7AH

BPS Gym (Right) 12V 7AH

12V 7AH

BPS Rm 260 (Right) 12V 7AH

Fire Pump Trouble

Fire Pump Phase Reversal

BPS Rm 260 (Left)

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Emergency Communications Equipment

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

Battery Testing

Each Phone Set Activated and Operation VerifiedPhone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 443: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Pull Station MAIN ENTRANCE 1 M1 1 Pass

Pull Station MAIN ENTRANCE 1 M1 2 Pass

Pull Station MAIN LOBBY 1 M1 3 Pass

Duct Detector CORRIDOR 100 1 M1 4 Pass

Smoke Detector CORRIDOR 130 1 M1 5 Pass

Duct Detector CORRIDOR 100 1 M1 6 Pass

Duct Detector CORRIDOR 100 1 M1 7 Pass

Duct Detector MEDIA STORAGE RM 121 1 M1 8 Pass

Pull Station CORRIDOR 130 1 M1 9 Pass

Duct Detector CORRIDOR 130 1 M1 10 Pass

Smoke Detector CORRIDOR 159 FIRE DOORS 1 M1 11 Pass

Smoke Detector CORRIDOR 200 FIRE DOORS 1 M1 12 Pass

Pull Station CORRIDOR 200 1 M1 13 Pass

Smoke Detector CORRIDOR 200 FIRE DOORS 1 M1 14 Pass

Duct Detector CORRIDOR 289 1 M1 15 Pass

Smoke Detector CORRIDOR 289 FIRE DOORS 1 M1 16 Pass

Duct Detector CORRIDOR 289 1 M1 17 Pass

Duct Detector CORRIDOR 289 1 M1 18 Pass

Pull Station CORRIDOR 289 1 M1 19 Pass

Pull Station CORRIDOR 279 1 M1 20 Pass

Duct Detector CORRIDOR 279 1 M1 21 Pass

Duct Detector GIRLS RR 268 1 M1 22 Pass

Smoke Detector CORRIDOR 279 1 M1 23 Pass

Duct Detector CORRIDOR 279 1 M1 24 Pass

Duct Detector CORRIDOR 279 1 M1 25 Pass

Smoke Detector CORRIDOR 256 FIRE DOORS 1 M1 26 Pass

Smoke Detector CORRIDOR 256 FIRE DOORS 1 M1 27 Pass

Duct Detector CORRIDOR 256 1 M1 28 Pass

Pull Station CORRIDOR 256 1 M1 29 Pass

Pull Station CORRIDOR 238 1 M1 30 Pass

Duct Detector CORRIDOR 238 1 M1 31 Pass

Duct Detector CORRIDOR 238 1 M1 32 Pass

Smoke Detector CORRIDOR 238 1 M1 33 Pass

Duct Detector CORRIDOR 238 1 M1 34 Pass

Duct Detector CLASSRM 202 1 M1 35 Pass

Pull Station CORRIDOR 218 1 M1 36 Pass

Duct Detector CORRIDOR 218 1 M1 37 Pass

Smoke Detector CORRIDOR 218 FIRE DOORS 1 M1 38 Pass

Smoke Detector CORRIDOR 218 FIRE DOORS 1 M1 39 Pass

Pull Station CORRIDOR 200 1 M1 40 Pass

Duct Detector STORAGE RM 196 1 M1 41 Pass

Pull Station MECHANICAL RM 195 1 M1 42 Pass

Duct Detector KITCHEN 185 1 M1 43 Pass

Duct Detector KITCHEN 185 1 M1 44 Pass

Duct Detector KITCHEN 185 1 M1 45 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 444: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station CAFETERIA 180 1 M1 46 Pass

Pull Station CORRIDOR 161 1 M1 47 Pass

Duct Detector CORRIDOR 161 1 M1 48 Pass

Duct Detector CORRIDOR 169 1 M1 49 Pass

Duct Detector CORRIDOR 169 1 M1 50 Pass

Pull Station GYM 1 M1 51 Pass

Pull Station GYM 1 M1 52 Pass

Pull Station GYM 1 M1 53 Pass

Waterflow Switch MECH RM 195 SPRINKLER RISER 1 1 M1 54 Pass

Tamper Switch MECH RM 195 SPRINKLER RISER 1 1 M1 54 Pass

Waterflow Switch MECH RM 195 SPRINKLER RISER 2 1 M1 55 Pass

Tamper Switch MECH RM 195 SPRINKLER RISER 2 1 M1 55 Pass

Duct Detector CORRIDOR 238 1 M1 58 Pass

Smoke Detector CORRIDOR 279 1 M1 59 Pass

Duct Detector STORAGE RM 184 1 M1 60 Pass

Duct Detector GYMNASIUM AH2 1 M1 70 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 445: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 446: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

Note:

NAC panel in Gym.

Gym SLC Transient Protection located in Rm 1253 Above Ceiling on outside wall and at

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 447: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

9 0

20 0

27 0

44 0

24 0

5 0

5 0

Inspector Name : Signature:

Duct Detectors System Sensor DNR

Waterflow Switches Potter VSR-F

David Piorkowski David Piorkowski

Tamper Switches Victaulic Butterfly

Pass

Device

Notifier

Interface Equipment

NotifierPower Supplies FCPS-24S8

Smoke Detectors FSP-851

Power Patrol

AFP-400Control Panel

Notifier NBG-12LX

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Are Lamps and Displays Operating Properly

Loss of AC is Detected by the Fire Alarm Control Panel

(678) 691-0011

610 Burgess Road

30024

Notifier

Admin Area Rm 101

Model Name

Suwanee GA

Is the Panel Monitored Yes

AFP-400

EI1273

Riverwatch Middle School

6/23/2020

Pass

Notifier

Who Was Notified Prior to the Start of Testing Monitoring Company & Office Staff

Batteries FAS 1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

Pass

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection Pass

Pullstations

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 448: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Condition Voltage

Good (2020) 13.5

Good (2020) 13.4

Fire Pump Controller Troubles Report to Panel

Phase Reversal on Pump Controller Reports to Panel

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Continued on Page 3 - Battery Testing

FACP 12V 7A

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Magnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7A

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 449: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Fail

Fail

N/A

N/A

N/A

Load Test

Pass

Pass

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Pass

N/A

Pass

Pass

Pass

N/A

Notification Devices

Emergency Communications Equipment

Battery Testing

Interface Equipment

Supervisory Signals

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 450: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Floor Condition Voltage

1 Good (2020) 13.6

1 Good (2020) 13.6

1 Good (2020) 13.5

1 Good (2020) 13.7

1 Good (2020) 13.7

1 Good (2020) 13.8

1 Good (2020) 13.5

1 Good (2020) 13.5

1 Good (2020) 13.7

1 Good (2020) 13.8

1 Good (2020) 13.6

1 Good (2020) 13.8

1 Good (2020) 13.8

1 Good (2020) 13.8

1 Good (2020) 13.7

1 Good (2020) 13.7

1 Good (2020) 13.7

1 Good (2020) 13.7

BPS #4 Rm 140 (Right) 12V 7AH

BPS #3 Rm 530 (Left) 12V 7AH

BPS #3 Rm 530 (Right) 12V 7AH

BPS #4 Rm 140 (Left) 12V 7AH

BPS #2 Rm 418 (Left) 12V 7AH

BPS #2 Rm 418 (Right) 12V 7AH

BPS #1 Rm 606 (Right) 12V 7AH

Battery Testing (cont.)

Location Size

BPS #1 Rm 606 (Left) 12V 7AH

BPS #5 Rm 328 (Left) 12V 7AH

BPS #5 Rm 328 (Right) 12V 7AH

BPS #6 Rm 358 (Left) 12V 7AH

BPS #6 Rm 358 (Right) 12V 7AH

BPS #7 Rm 358 (Left) 12V 7AH

BPS #7 Rm 358 (Right) 12V 7AH

BPS #8 Rm 393 (Left) 12V 7AH

BPS #8 Rm 393 (Right) 12V 7AH

BPS #9 Rm 393 (Left) 12V 7AH

BPS #9 Rm 393 (Right) 12V 7AH

Page 451: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Load Test

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Battery Testing (cont.)

Page 452: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address

Smoke Detector LUNCH RM DOORS 1 D 101

Smoke Detector LUNCH RM DOORS 1 D 102

Smoke Detector LUNCH RM DOORS 1 D 103

Smoke Detector LUNCH RM DOORS 1 D 104

Smoke Detector LUNCH RM 1 D 105

Smoke Detector LUNCH RM 1 D 106

Smoke Detector LUNCH RM 1 D 107

Duct Detector KITCHEN RTU A-2 1 D 108

Duct Detector MECH RM RTU A-1 1 D 109

Duct Detector MECHANICAL A116 1 D 110

Duct Detector MECHANICAL A116 1 D 111

Duct Detector MECHANICAL A159 1 D 112

Duct Detector MECHANICAL A159 1 D 113

Smoke Detector MAIN CORRIDOR A101 1 D 114

Smoke Detector MAIN CORRIDOR A101 1 D 115

Smoke Detector BAND RM STORAGE 1 D 116

Smoke Detector TIME OUT SPECIAL ED B118 1 D 117

Smoke Detector BOOK STORAGE B 108 1 D 118

Duct Detector CORRIDOR A148 ERU B1 1 D 122

Smoke Detector GYM LOBBY 1 D 123

Smoke Detector NEAR GYM LOBBY 1 D 125

Smoke Detector NEAR GYM LOBBY 1 D 126

Duct Detector RM 481 RETURN 1 D 128

Smoke Detector NEAR OFFICE A 140 1 D 129

Smoke Detector NEAR MATH RM C 134 1 D 130

Duct Detector CORRIDOR C 100 1 D 131

Duct Detector CORRIDOR C 100 1 D 132

Smoke Detector NEAR BOOK RM 134 1 D 133

Smoke Detector NEAR MATH RM D134 1 D 134

Duct Detector NEAR B120 1 D 135

Duct Detector NEAR MATH RM E134 1 D 136

Smoke Detector NEAR B120 1 D 137

Smoke Detector NEAR MATH RM E134 1 D 138

Duct Detector CORRIDOR E100 1 D 139

Duct Detector CORRIDOR E100 1 D 140

Duct Detector RM 481 SUPPLY 1 D 141

Smoke Detector DATA RM 394 1 D 142

Smoke Detector ELECTRICAL RM 393 1 D 143

Duct Detector RM 398 SUPPLY 1 D 144

Duct Detector RM 398 RETURN 1 D 145

Smoke Detector 384 CORRIDOR F/DRS 1 D 146

Smoke Detector 467 CORRIDOR F/DRS 1 D 147

Smoke Detector 467 E CORRIDOR F/DRS 1 D 148

Smoke Detector BOOK STORAGE RM 461 1 D 149

Smoke Detector 462 CORRIDOR F/DRS 1 D 150

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 453: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector 460 CORRIDOR F/DRS 1 D 152

Smoke Detector 346E CORRIDOR F/DRS 1 D 153

Smoke Detector 346 CORRIDOR F/DRS 1 D 154

Smoke Detector STORAGE RM 370 1 D 155

Smoke Detector DATA RM 359 1 D 156

Smoke Detector ELECTRICAL 358 1 D 157

Duct Detector RM 377 SUPPLY 1 D 158

Duct Detector RM 377 RETURN 1 D 159

Smoke Detector 258 CORRIDOR F/DRS 1 D 160

Smoke Detector BOOK RM 252 1 D 161

Smoke Detector 251 CORRIDOR F/DRS 1 D 162

Smoke Detector 250 CORRIDOR F/DRS 1 D 163

Smoke Detector 258E CORRIDOR F/DRS 1 D 164

Duct Detector RM 270 SUPPLY 1 D 165

Smoke Detector 384 CORRIDOR F/DRS 1 D 169

Smoke Detector 467 CORRIDOR F/DRS 1 D 170

Smoke Detector 346 CORRIDOR F/DRS 1 D 171

Smoke Detector 258 CORRIDOR F/DRS 1 D 172

Duct Detector ERU 1 SUPPLY 1 D 173

Duct Detector ERU 1 RETURN 1 D 174

Duct Detector RM 504 RETURN 1 D 175

Duct Detector RM 504 SUPPLY 1 D 176

Smoke Detector KITCHEN RM 133 1 D 180

Pull Station MAIN ENTRANCE 1 M 101

Pull Station LUNCH RM EXIT 1 M 102

Pull Station LUNCH RM EXIT 1 M 103

Pull Station MAIN OFFICE FRONT EXIT 1 M 105

Pull Station RM 528 EXIT 1 M 106

Pull Station 149 CORRIDOR EXIT 1 M 110

Pull Station MAIN OFFICE EXIT 1 M 112

Pull Station CORRIDOR A101 1 M 113

Pull Station MEDIA CENTER 1 M 114

Pull Station NEAR COMP NET RM 1 M 117

Pull Station KITCHEN 1 M 118

Pull Station NEAR BOOK RM B119 1 M 122

Pull Station GYM LOBBY 1 M 127

Pull Station BAND EXIT 1 M 128

Pull Station EXIT AT RM 528 1 M 130

Pull Station CHORUS RM 1 M 131

Pull Station ART RM 1 M 132

Pull Station NEAR FOOTBALL LOCKER 1 M 133

Pull Station NEAR WEIGHT RM 1 M 135

Waterflow Switch RISER RM 395 1 M 136

Waterflow Switch RISER RM 395 1 M 137

Pull Station 384 CORRIDOR EXIT 1 M 138

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 454: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station 526 CORRIDOR EXIT 1 M 141

Pull Station CORRIDOR C100 1 M 142

Pull Station CORRIDOR D100 1 M 146

Pull Station 370 CORRIDOR EXIT 1 M 149

Pull Station CORRIDOR E100 1 M 150

Pull Station TECHNOLOGY LAB 1 M 151

Pull Station 251 CORRIDOR EXIT 1 M 156

Tamper Switch RISER RM 395 1 M 166

Waterflow Switch RISER 1 1 M 190

Tamper Switch RISER 1 1 M 191

Waterflow Switch RISER 2 1 M 192

Tamper Switch RISER 2 1 M 193

Waterflow Switch RISER 3 1 M 194

Tamper Switch RISER 3 1 M 195

Monitor KITCHEN HOOD 1 M 196

Tamper Switch OUTDOOR PIV BY RISER RM 395 1 M 198

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 455: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Results

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Visual

Visual

Pass

Pass

Pass

Pass

Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 456: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Pass

Pass

Pass

Pass

Visual

Visual

Pass

Pass

Pass

Pass

Pass

Visual

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 457: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Padlocked

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 458: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

(9) Notification devices failed to activate during sound test:

(1) Red wall mounted Gentex strobe in room 318

(8) Red wall mounted Gentex horn-strobes & strobes between office 581 spanning to weight room 590 including

girls locker room side of gym - from BPS#3 located in Room 530.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 459: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

Program module 128 as pullstation type with band room description.

Program smoke detector 129 description as Corridor near Rm 209

Program smoke detector 130 description as Corridor near Rm 211

Remove 'Duct' from descriptor in program for D123 as it a smoke detector.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 460: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 2 0

6 0

14 0

10 0

25 0

2 0

Inspector Name : Signature:

Pass

Firelite FCPS 24FS8

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

D K WomackKen Womack

System SensorWaterflow WFD40

All-Star Fire, LLC

Yuasa

Firelite BG12-LX

NP7-12

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

MS 9200

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Firelite

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

Pass

1130 Dahlonega Highway

Forsyth Academy/ Forsuth Virtual / Academy of Creative Education - PLC

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredElect Room 152

Model Name MS-9200Firelite

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC

D4120

Other

Batteries

Pullstations

FireliteSmoke Detectors SD300

Duct Detectors System Sensor

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/20/2020

EI1273 / WO # 155436

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 461: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.4 Pass

Good (2019) 13.4 Pass

Good (no date) 13 Pass

Good (no date) 13.2 Pass

Good (2020) 13.2 Pass

Good (2020) 13.1 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Fire Pump Running

Fire Pump Power Loss

FCPS (left) #2 rm 148

FCPS (right) #2 rm 148

12v 7ah

12v 7ah

Correct Switching and Operation Verified

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FCPS (right) #1 rm

FCPS (left) #1 rm

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 462: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Pull Station Lobby 1 M01 Pass

Pull Station Exit 150 Hall 1 M02 Pass

Pull Station N Exit 100 Hall 1 M03 Pass

Pull Station S Exit 100 Hall 1 M04 Pass

Pull Station N Exit rm 130 1 M05 Pass

Pull Station S Exit rm 130 1 M06 Pass

Pull Station Entry rm 130 1 M07 Pass

Flow Switch Mech rm 132 1 M08 Pass

Tamper Switch Mech rm 132 1 M09 Pass

Pull Station F/NS Cafe Exit 1 M23 Pass

Pull Station F/NS Cafe Exit 1 M24 Pass

Pull Station F/NS rm 107 1 M25 Pass

Pull Station F/NS Cafe Exit 1 M26 Pass

Pull Station F/NS Dock Exit 1 M34 Pass

Pull Station F/NS Corr Exit 1 M35 Pass

Flow Switch F/NS rm 102 1 M39 Pass

Tamper Switch F/NS rm 102 1 M40 Pass

Ansul Hood rm 112 1 M41 Visual

Duct Detector F/NS rm 142 1 M45 Not found

Pull Station Exit rm 134 1 M96 Pass

Tamper Switch PIV rm 132 1 M97 Not found

Duct Detector F/NS ITS DD 1 P01 Not found

Duct Detector F/NS ITR DD 1 P02 Not found

Smoke Detector 100 Hall rm 102 1 P08 Pass

Smoke Detector 100 Hall rm 108 1 P09 Pass

Smoke Detector 100 Hall rm 122 1 P10 Pass

Smoke Detector 100 Hall rm 130 1 P11 Pass

Smoke Detector Mech rm 132 1 P12 Pass

Smoke Detector Elect rm 133 1 P14 Pass

Smoke Detector Vault rm 112 1 P15 Pass

Smoke Detector Elect rm 152 1 P16 Pass

Smoke Detector Cust rm 154 1 P17 Pass

Smoke Detector 150 Hall rm 154 1 P18 Pass

Smoke Detector 150 Hall rm 159 1 P19 Pass

Smoke Detector 150 Hall rm 163 1 P20 Pass

Smoke Detector Mech rm 116 1 P21 Pass

Smoke Detector F/NS rm 102 1 P22 Visual

Smoke Detector F/NS rm 110 1 P27 Pass

Smoke Detector F/NS rm 110 1 P28 Pass

Smoke Detector F/NS rm 112 1 P29 Pass

Smoke Detector F/NS rm 112 1 P30 Pass

Smoke Detector F/NS rm 140 1 P31 Pass

Smoke Detector F/NS rm 144 1 P32 Pass

Smoke Detector F/NS rm 120 1 P33 Not found

Smoke Detector F/NS rm 148A 1 P36 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 463: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector F/NS rm 150 1 P37 Visual

Smoke Detector F/NS DD rm 102 1 P42 Visual

Duct Detector F/NS DD rm 100 1 P43 Visual

Duct Detector F/NS DD rm 100 1 P44 Not found

Smoke Detector Rm 114 1 P50 Not found

Duct Detector 100 Hall rm 130 1 P51 Pass

Duct Detector AHU #1 DD rm 130 1 P95 Visual

Duct Detector AHU #2 DD rm 135 1 P96 No Access

Duct Detector EHU #1 DD rm 135 1 P97 No Access

Duct Detector DHU #1 DDrm 130 1 P98 Visual

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 464: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 465: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 466: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 7 0

16 4

30 0

25 0

128 0

4

Inspector Name : Signature:

30041

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/17/2020

EI1273 / WO # 155457

4098-9685

Other

Batteries

Pullstations

SimplexSmoke Detectors 4098-9757

Duct Detectors Simplex

Pass

8135 Majors Road

Piney Grove Middle School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredMain Office

Model Name 4100 USimplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC

All-Star Fire, LLC

Power Patrol

Simplex 4099-9004

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4100 U

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

KennedyTamper TBD

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

,hd

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 467: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Fair (2017) 13 Fail

Fair (2017) 12.9 Fail

Good (2018) 13.3 Pass

Good (2018) 13.4 Pass

Fair (2017) 13.3 Pass

Fair (2017) 13.3 Pass

Good (2018) 13.4 Pass

Good (2018) 13.4 Pass

Good (2018) 13.3 Pass

Good (2018) 13.3 Pass

Fair (2017) 13.3 Pass

Fair (2017) 13.3 Pass

Good (2018) 13 Pass

Good (2018) 13.3 Pass

Poor (2015) 13 Fail

Poor (2015) 13.1 Fail

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

Pass

Pass

N/A

N/A

Pass

FCPS (right) #7 rm 2120

12v 7ah

12v 7ah

12v 7ah

FCPS (right) #1 rm 1592

FCPS (left) #1 rm 1592

FCPS (left) #6 rm 2223

FCPS (right) #6 rm 2223

FCPS (left) #7 rm 2120

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

FCPS (right) #4 rm 1243

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

12v 7ah

Fire Pump Power Loss

Correct Switching and Operation Verified

12v 7ah

12v 7ah

Visually Inspected and Operation VerifiedPhone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 1592

FCPS (right) #2 rm 1592

FCPS (left) #3 rm 1275

FCPS (right) #3 rm 1275

12v 7ah

12v 7ah

12v 7ah

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

FCPS (right) #5 rm 1120

FCPS (left) #4 rm 1243

FCPS (left) #5 rm 1120

Fire Pump Running

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 468: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

N/AFM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 469: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Tamper Switch PIV by Kitchen LL M1-1 Pass

Pull Station Main Entrance E LL M1-2 Pass

Pull Station Main Entrance W LL M1-3 Pass

Smoke Detector Main Office Elect rm 1522 LL M1-4 Pass

Pull Station Main Office Exit W LL M1-5 Pass

Duct Detector Outside Mech rm 1304 LL M1-6 Not found

Pull Station Outside Mech rm 1304 LL M1-7 Pass

Pull Station Corr @ Teacher Workrm 1542 LL M1-8 Pass

Smoke Detector Corr @ Book Store 1530 LL M1-9 Visual

Smoke Detector Corr @ Book Store 1530 LL M1-10 Visual

Smoke Detector Book Store rm 1530 LL M1-11 Pass

Smoke Detector Corr @ Cust Closet 1547 LL M1-12 Visual

Smoke Detector Corr @ Cust Closet 1547 LL M1-13 Visual

Smoke Detector Corr @ Book Store 1530 LL M1-14 Visual

Smoke Detector Cafeteria @ Food Court LL M1-15 Visual

Smoke Detector Cafeteria @ Food Court LL M1-16 Visual

Smoke Detector Cafeteria @ Dish Wash Area LL M1-17 Visual

Smoke Detector Kitchen @ Dish Wash Area LL M1-18 Visual

Smoke Detector Food Court S LL M1-19 Pass

Smoke Detector Food Court S LL M1-20 Pass

Duct Detector Cafe NW RTU1 LL M1-21 Not found

Duct Detector Cafe N/Center RTU2 LL M1-22 Not found

Pull Station Cafe Exit NE LL M1-23 Pass

Tamper Switch Outside Mech rm 1311 LL M1-24 Pass

Pull Station Outside Elect rm 1310 LL M1-25 Pass

Tamper Switch Commons & E Wing Outside Mech rm 1311 LL M1- 26 Pass

Duct Detector Cafeteria NE RTU Cafe 3 LL M1- 27 Not found

Ansul Kitchen Hood LL M1-28 Visual

Duct Detector Food Court N RTU Kit2 LL M1-29 Pass

Smoke Detector Food Court N LL M1-30 Visual

Smoke Detector Corr @ Food Court Entrance LL M1-31 Pass

Smoke Detector Elect rm 1592 LL M1-32 Pass

Duct Detector Kitchen N RTU Kit1 LL M1-33 Pass

Pull Station Kitchen East Exit LL M1-34 Pass

Duct Detector Media Ctr Office 1582 RTU Med1a3 LL M1-35 Pass

Duct Detector Media Ctr Prod 1585 RTU Med 1A2 LL M1-36 Pass

Duct Detector Media Ctr Prod 1585 RTU Med 1A1 LL M1-37 Pass

Pull Station Media Ctr NW Exit LL M1-38 Pass

Smoke Detector Corr @ Elect rm 1592 LL M1-39 Pass

Smoke Detector Corr @ Elect rm 1592 LL M1-40 Pass

Smoke Detector Commons Area South LL M1-41 Pass

Smoke Detector Commons Area South LL M1-42 Pass

Heat Detector Elevator Equip rm 1010 LL M1-43 Visual

Smoke Detector Elevator Equip rm 1010 LL M1-44 Pass

Tamper Switch Gym W Wing Outside Mech rm 1311 LL M1-49 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 470: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Business Cl rm 1224 eru LL M1-50 Pass

Smoke Detector Elevator Lobby LL M1-51 Pass

Smoke Detector Commons Area East LL M1-52 Pass

Smoke Detector Commons Area East LL M1-53 Pass

Smoke Detector Corr @ Rm 1101 LL M1-54 Pass

Smoke Detector Corr @ Rm 1102 LL M1-55 Pass

Smoke Detector Classroom 1102 LL M1-56 Pass

Smoke Detector Classroom 1106 LL M1-57 Pass

Smoke Detector Classroom 1112 LL M1-58 Pass

Smoke Detector Classroom 1116 LL M1-59 Pass

Smoke Detector Classroom 1124 LL M1-60 Pass

Smoke Detector Classroom 1128 LL M1-61 Pass

Smoke Detector Classroom 1134 LL M1-62 Pass

Smoke Detector Classroom 1138 LL M1-63 Pass

Smoke Detector Corr @ Rm 1138 LL M1-64 Pass

Smoke Detector Stairwell East LL M1-65 Pass

Pull Station Stairwell East LL M1-66 Pass

Smoke Detector Classroom 1141 LL M1-67 Pass

Tamper Switch Admin Outside Mech rm 1311 LL M1-68 Pass

Smoke Detector Classroom 1137 LL M1-69 Pass

Smoke Detector Classroom 1133 LL M1-70 Pass

Smoke Detector Classroom 1129 LL M1-71 Pass

Duct Detector Girls RR @ rm 1124 LL M1-72 Not found

Smoke Detector Elect rm 1120 LL M1-73 Pass

Smoke Detector Classroom 1117 LL M1-74 Pass

Smoke Detector Classroom 1113 LL M1-75 Pass

Smoke Detector Classroom 1111 LL M1-76 Pass

Smoke Detector Classroom 1107 LL M1-77 Pass

Smoke Detector Classroom 1101 LL M1-78 Pass

Smoke Detector Commons Area West LL M1-79 Pass

Smoke Detector Commons Area West LL M1-80 Pass

Pull Station Corr @ Book Storage 1202 LL M1-81 Pass

Smoke Detector Corr @ Book Storage 1202 LL M1-82 Pass

Smoke Detector Corr @ Book Storage 1202 LL M1-83 Pass

Pull Station Commons Area NW Exit LL M1-84 Pass

Smoke Detector Classroom 1212 LL M1-85 Pass

Duct Detector Mech rm 1230 eru LL M1-86 Pass

Duct Detector Mech rm 1230 eru LL M1-87 Visual

Pull Station Mech rm 1230 LL M1-88 Pass

Smoke Detector Classroom 1232 LL M1-89 Pass

Duct Detector Mech rm 1533 RTU 128 LL M1-90 Pass

Smoke Detector Classroom 1240 LL M1-91 Pass

Pull Station Classroom 1240 LL M1-92 Pass

Smoke Detector Classroom 1233 LL M1-93 Pass

Smoke Detector Classroom 1237 LL M1-94 Pass

Smoke Detector Corr @ Rm 1245 LL M1-95 Pass

Smoke Detector Corr @ Rm 1245 LL M1-96 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 471: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Boys RR @ W Stairwell LL M1-97 Pass

Pull Station Boys RR @ W Stairwell LL M1-98 Pass

Smoke Detector Elect rm 1243 LL M1-99 Pass

Pull Station Outside Mech rm 1301 LL M1-100 Pass

Smoke Detector Boys RR @ W Stairwell LL M1-101 Pass

Smoke Detector Classroom 1245 LL M1-102 Pass

Smoke Detector TBD LL M1-103 Pass

Ansul Rm 1217 & 1227 LL M1-104 Visual

Smoke Detector Corr @ Stairwell West LL M1-105 Pass

Smoke Detector Girls RR @ Stairwell West LL M1-106 Pass

Smoke Detector Corr @ Stairwell West LL M1-107 Pass

Smoke Detector Girls RR @ Stairwell West LL M1-108 Pass

Smoke Detector Stairwell West LL M1-109 Pass

Smoke Detector Corr @ Choral rm 1261 LL M1-110 Pass

Smoke Detector Corr @ Choral rm 1261 LL M1-111 Pass

Smoke Detector Gym Exit SE LL M1-112 Visual

Smoke Detector Corr @ East Gym Entrance LL M1-113 Visual

Pull Station Choral rm 1261 LL M1-114 Pass

Pull Station Band rm 1263 LL M1-115 Pass

Pull Station Corr @ West Gym Entrance LL M1-116 Pass

Smoke Detector Corr @ West Gym Entrance LL M1-117 Visual

Smoke Detector Gym Exit SW LL M1-118 Visual

Smoke Detector Gym Elect rm 1275 LL M1-119 Pass

Pull Station Gym Exit @ Girls Locker rm 1293 LL M1-120 Pass

Duct Detector Girls Locker rm 1293 RTU F134 LL M1-121 Pass

Duct Detector Girls Locker rm 1293 RTU Gym2 LL M1-122 Not found

Duct Detector Gym Laundry rm 1281 RTU Gym1 LL M1-123 Not found

Duct Detector Boys Locker rm 1284 RTU F135 LL M1-124 Pass

Pull Station Gym @ Boys Locker rm 1284 LL M1-125 Pass

Duct Detector Boys Locker rm 1284 RTU F118 LL M1-126 Pass

Pull Station Outside Mech rm 1302 LL M1-127 Pass

Pull Station Classroom 1233 LL M1-128 Pass

Smoke Detector Classroom 1231 LL M1-129 Pass

Smoke Detector Classroom 1227 LL M1-130 Pass

Smoke Detector Classroom 1217 LL M1-131 Pass

Smoke Detector Classroom 1224 LL M1-132 Pass

Duct Detector Mech rm 2260 FCU F100 UL M1-133 Visual

Duct Detector Mech rm 2260 FCU F102 UL M1-134 Pass

Pull Station Corr @ Book Storage 2257 UL M1-135 Pass

Smoke Detector Corr @ Stairwell West UL M1-136 Pass

Smoke Detector Top of Stairwell West UL M1-137 Pass

Smoke Detector Classroom 2250 UL M1-138 Pass

Smoke Detector Classroom 2246 UL M1-139 Pass

Smoke Detector Classroom 2240 UL M1-140 Pass

Smoke Detector Classroom 2236 UL M1-141 Pass

Smoke Detector Classroom 2220 UL M1-142 Pass

Smoke Detector Classroom 2216 UL M1-143 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 472: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector Classroom 2212 UL M1-144 Pass

Smoke Detector Classroom 2208 UL M1-145 Pass

Smoke Detector Classroom 2204 UL M1-146 Pass

Smoke Detector Commons Area West UL M1-147 Pass

Smoke Detector Commons Area West UL M1-148 Pass

Pull Station Commons Area NW Exit UL M1-149 Pass

Smoke Detector Corr @ Rm 2205 UL M1-150 Pass

Smoke Detector Corr @ Rm 2204 UL M1-151 Pass

Smoke Detector Classroom 2205 UL M1-152 Pass

Smoke Detector Classroom 2207 UL M1-153 Pass

Smoke Detector Classroom 2215 UL M1-154 Pass

Smoke Detector Classroom 2219 UL M1-155 Pass

Smoke Detector Classroom 2227 UL M1-156 Pass

Smoke Detector Classroom 2231 UL M1-157 Pass

Smoke Detector Classroom 2241 UL M1-158 Pass

Smoke Detector Classroom 2245 UL M1-159 Pass

Smoke Detector Commons Area East UL M1-160 Pass

Smoke Detector Commons Area East UL M1-161 Pass

Smoke Detector Elevator Lobby UL M1-162 Pass

Smoke Detector Top of Shaft UL M1-163 Visual

Smoke Detector Classroom 2101 UL M1-164 Pass

Smoke Detector Corr @ Rm 2101 UL M1-165 Pass

Smoke Detector Corr @ Rm 2102 UL M1-166 Pass

Smoke Detector Classroom 2102 UL M1-167 Pass

Smoke Detector Classroom 2206 UL M1-168 Pass

Smoke Detector Classroom 2112 UL M1-169 Pass

Smoke Detector Classroom 2111 UL M1-170 Pass

Smoke Detector Classroom 2107 UL M1-171 Pass

Smoke Detector Classroom 2113 UL M1-172 Pass

Smoke Detector Classroom 2116 UL M1-173 Pass

Smoke Detector Classroom 2117 UL M1-174 Pass

Smoke Detector Elect rm 2120 UL M1-175 Pass

Duct Detector Corr @ Rm 2124 UL M1-176 Not found

Smoke Detector Classroom 2124 UL M1-177 Pass

Smoke Detector Classroom 2128 UL M1-178 Pass

Duct Detector Mech rm 2103 UL M1-179 Pass

Duct Detector Mech rm 2103 UL M1-180 Pass

Smoke Detector Classroom 2129 UL M1-181 Pass

Smoke Detector Classroom 2133 UL M1-182 Pass

Smoke Detector Classroom 2134 UL M1-183 Pass

Smoke Detector Classroom 2137 UL M1-184 Pass

Smoke Detector Classroom 2138 UL M1-185 Pass

Smoke Detector Corr @ Rm 2141 UL M1-186 Pass

Smoke Detector Classroom 2141 UL M1-187 Pass

Smoke Detector Top of Stairwell East UL M1-188 Pass

Pull Station Corr @ Rm 2141 UL M1-189 Pass

Pull Station Stairwell West UL M1-190 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 473: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector Corr @ Rm 1128 LL M1-192 Pass

Pull Station Commons Area NE Exit LL M1-193 Pass

Smoke Detector Elect rm 2223 UL M1-194 Pass

Pull Station Main Office Exit LL M1-195 Pass

Pull Station Corr @ Rm 1141 LL M1-200 Pass

Pull Station Commons Area NE Exit UL M1-201 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 474: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 475: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 476: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

Power Supplies 4 0

12 2

25 0

18 0

104 0

3 0

5 0

Inspector Name : Signature:

30040

3284 Medlock Bridge Rd, Suite 300

Norcross, GA 30092

(678) 691-0011

7/6/2020

EI1273

4098-9685

Tamper Kennedy TBD

Batteries

Pullstations

SimplexSmoke Detectors 4098-9714

Duct Detectors Simplex

Pass

605 Tribble Gap Road

Otwell Middle School

Ground Fault

TBD

Who Was Notified Prior to the Start of Testing

YesIs the Panel MonitoredFront Office

Model Name 4010Sinplex

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

GA

Monitoring Company

EMC Security

All-Star Fire, LLC

Power Patrol

Simplex 4099-9004

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Loss of Secondary Power (Batteries/Generator) is Detected

4010

Interfaced Equipment Tested for Circuit Supervision

Model

Loss of AC is Detected by the Fire Alarm Control Panel

Simplex

Manufacturer

Ground Faults Detected by Control Panel

Cumming

Are Lamps and Displays Operating Properly

D K WomackKen Womack

PotterWater flow VSR

Pass

Simplex 4009

EMC Security

Pass

Pass

Pass

Device Summary

Panel Power Loss

Open Circuit Detection

Panel Secondary Power Loss

Interface Equipment

Control Panel

Device

Pass

Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 477: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.3 Pass

Good (2020) 13.3 Pass

Good (2020) 13.6 Pass

Good (2020) 13.6 Pass

Good (2020) 12.9 Pass

Good (2020) 12.9 Pass

Fair (2019) 12.9 Fail

Fair (2019) 12.9 Fail

Fair (2020) 13.2 Pass

Fair (2020) 13.3 Pass

Good (2020) 13.4 Pass

Good (2020) 13.3 Pass

N/A

N/A

N/A

N/A

Fire Pump Trouble Fire Pump Controller Troubles Report to Panel N/A

Fire Pump Phase Reversal Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

Pass

N/A

N/A

Are the Notification Appliance Circuits Monitored for Integrity

Does the Voice Evacuation Work Properly and is it IntelligibleVoice Evacucation

Notification Devices

Each Phone Set Activated and Operation Verified

Emergency Communications Equipment

Each Strobe Operates ProperlyStrobes

What Style are the Notification Circuits

Each Device Operates Properly

NAC Circuits

Circuit Style

Phone Sets

Horns

FCPS (right) #1 rm 125

FCPS (left) #1 rm 125

Water Level/Water Temp Sensors Report CorrectlySite Water Level /Temp

Temperature Switch Reports to Panel When ActivatedBuilding Temp

Supervisory Signals

FACP (left)

12v 7ahFACP (right)

12v 7ah

12v 7ah

12v 7ah

FM-200 / Preaction Systems FM-200/Preaction Systems Report Correctly

Maglock Release

Stairwell Pressurization

Fire Alarm Properly Recall ElevatorsElevator Recall

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Kitchen Hood Suppression System Report CorrectlyKitchen Hoods

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Release Maglocks

HVAC Shutdown Fire Alarm Properly Shutdown HVAC Units

FCPS (left) #4 rm 530

Voice Evac (right)

Phone Jacks

Amplifiers/Tone Generators

12v 7ah

12v 7ah

FCPS (left) #2 rm 140

FCPS (right) #2 rm 140

FCPS (left) #3 rm 418

FCPS (right) #3 rm 418

12v 7ah

12v 7ah

12v 7ah

FCPS (right) #4 rm 530

Correct Switching and Operation Verified

12v 7ah

Fire Pump Running

Fire Pump Power Loss

12v 7ah

Visually Inspected and Operation Verified

Interface Equipment

Generator In Auto

Location

Battery Testing

Size

12v 7ah

Generator Signals Report to Panel

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Generator Trouble Generator Trouble Reports to Panel

Voice Evac (left)

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 478: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Initating Device Testing

Device Type Location Floor Address/Zone Results

Smoke Detector E Wing Sci Prep rm 121 1 M1-2 Pass

Duct Detector E Wing RTU 1 M1-6 Not Found

Duct Detector E Wing RTU 1 M1-7 Not Found

Smoke Detector E Wing Print rm 125 1 M1-8 Pass

Smoke Detector E Wing Elect rm 26 1 M1-9 Pass

Smoke Detector E Wing Network rm 127 1 M1-10 Pass

Smoke Detector E Wing Sci Prep rm 131 1 M1-11 Pass

Smoke Detector E Wing Smoke Dr 1 M1-12 Pass

Smoke Detector E Wing Smoke Dr 1 M1-13 Pass

Smoke Detector Book Storage rm B119 1 M1-14 Pass

Smoke Detector E Wing Smoke Dr 1 M1-15 Pass

Smoke Detector E Wing Smoke Dr 1 M1-16 Pass

Smoke Detector Storage rm B120 1 M1-17 Pass

Smoke Detector Elect rm B121 1 M1-18 Pass

Smoke Detector Book rm B133 1 M1-21 Pass

Smoke Detector Bulk Stor rm B124 1 M1-22 Pass

Smoke Detector Counselor Office rm B132 1 M1-23 Not Found

Smoke Detector Book Storage rm B108 1 M1-24 Pass

Smoke Detector Food Court Smoke Dr 1 M1-25 Pass

Smoke Detector Food Court Smoke Dr 1 M1-26 Pass

Smoke Detector Food Court Smoke Dr 1 M1-27 Pass

Smoke Detector Food Court Smoke Dr 1 M1-28 Pass

Smoke Detector Corr A101 Smoke Dr 1 M1-30 Pass

Smoke Detector Corr A101 Smoke Dr 1 M1-31 Pass

Duct Detector Main Kitchen A130 1 M1-32 Pass

Smoke Detector Corr A101 Smoke Dr 1 M1-33 Pass

Smoke Detector Food Court/Lunch Rm Smoke Dr 1 M1-35 Pass

Smoke Detector Food Court/Lunch Rm Smoke Dr 1 M1-36 Pass

Smoke Detector Dishwasher rm A132 1 M1-37 Pass

Smoke Detector Food Court/Lunch Rm Smoke Dr 1 M1-38 Pass

Smoke Detector Food Court/Lunch Rm Smoke Dr 1 M1-39 Pass

Smoke Detector Lunch rm Dish Return 1 M1-40 Pass

Smoke Detector Lunch rm Smoke dr East 1 M1-41 Pass

Smoke Detector Lunch rm Smoke dr East 1 M1-42 Pass

Smoke Detector Elect rm A125 1 M1-43 Pass

Smoke Detector Mech rm A116 1 M1-44 Pass

Duct Detector Mech rm A116 1 M1-45 Pass

Duct Detector Mech rm A116 1 M1-46 Pass

Smoke Detector Admin Supply A120 1 M1-48 Pass

Smoke Detector Lunch rm Smoke dr West 1 M1-49 Pass

Smoke Detector Lunch rm Smoke dr West 1 M1-50 Pass

Smoke Detector D Wing Sci Prep rm 121 1 M1-54 Pass

Duct Detector D Wing RTU 1 M1-58 Not Found

Duct Detector D Wing RTU 1 M1-59 Not Found

Smoke Detector D Wing Print rm 125 1 M1-60 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 479: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector D Wing Elect rm 126 1 M1-61 Pass

Smoke Detector D Wing Network rm 127 1 M1-62 Pass

Smoke Detector D Wing Sci Prep rm 131 1 M1-63 Pass

Smoke Detector D Wing Smoke dr 1 M1-64 Pass

Smoke Detector D Wing Smoke dr 1 M1-65 Pass

Smoke Detector D Wing Smoke dr 1 M1-66 Pass

Smoke Detector D Wing Smoke dr 1 M1-67 Pass

Smoke Detector Storage rm B134 1 M1-68 Pass

Smoke Detector Elect rm B135 1 M1-69 Pass

Smoke Detector Book rm B136 1 M1-71 Pass

Smoke Detector C Wing Smoke dr 1 M1-72 Pass

Smoke Detector C Wing Smoke dr 1 M1-73 Pass

Smoke Detector C Wing Smoke dr 1 M1-74 Pass

Smoke Detector C Wing Smoke dr 1 M1-75 Pass

Smoke Detector Dry Food Storage A143 1 M1-76 No Access

Smoke Detector Laundry/Lockers A141 1 M1-77 Pass

Smoke Detector Elect rm A139 1 M1-79 Pass

Smoke Detector C Wing Sci Prep rm 131 1 M1-80 Pass

Duct Detector C Wing RTU 1 M1-84 Not Found

Duct Detector C Wing RTU 1 M1-85 Not Found

Smoke Detector C Wing Print rm 125 1 M1-86 Pass

Smoke Detector C Wing Elect rm 126 1 M1-87 Pass

Smoke Detector C Wing Network rm 127 1 M1-88 Pass

Smoke Detector C Wing Sci Prep rm 121 1 M1-89 Pass

Duct Detector Mech rm A134 1 M1-91 Not Found

Smoke Detector Elect rm A133 1 M1-92 Not Found

Smoke Detector Mech rm A134 1 M1-93 Pass

Smoke Detector Corr A101 Smoke Dr 1 M1-97 Pass

Smoke Detector G Wing Mech rm G109 1 M1-103 Not Found

Duct Detector G Wing Mech rm G109 1 M1-104 Not Found

Smoke Detector G Wing Stor rm G111 1 M1-105 Visual

Smoke Detector G Wing Smoke dr @ Gym NE 1 M1-106 Pass

Smoke Detector G Wing Smoke dr @ Gym NE 1 M1-109 Visual

Smoke Detector G Wing Laundry 1 M1-111 Pass

Smoke Detector G Wing Smoke dr @ Gym SE 1 M1-112 Visual

Smoke Detector G Wing Smoke dr @ Gym SE 1 M1-115 Visual

Smoke Detector G Wing Smoke dr @ Gym NW 1 M1-116 Visual

Smoke Detector G Wing Smoke dr @ Gym NW 1 M1-117 Pass

Smoke Detector F Wing Smoke dr @ Concessions 128 1 M1-120 Pass

Smoke Detector F Wing Smoke dr @ Concessions 128 1 M1-124 Not Found

Smoke Detector G Wing Smoke dr @ Gym SW 1 M1-127 Pass

Smoke Detector G Wing Smoke dr @ Gym SW 1 M1-128 Visual

Smoke Detector F Wing Stor rm 118 1 M1-131 Pass

Smoke Detector F Wing Kitchen rm 119 1 M1-132 Pass

Smoke Detector G Wing Elect rm 105 1 M1-134 Pass

Smoke Detector G/F Wing Smoke dr 1 M1-136 Pass

Smoke Detector G/F Wing Smoke dr 1 M1-137 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 480: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector G/F Wing Smoke dr 1 M1-138 Pass

Smoke Detector G/F Wing Smoke dr 1 M1-139 Pass

Smoke Detector G Wing Stor rm 122 1 M1-140 Pass

Smoke Detector F Wing Exit @ Tech Lab rm 516 1 M1-144 Pass

Smoke Detector F Wing Tech Lab Stor rm 107 1 M1-145 Pass

Smoke Detector A/F Wing Smoke dr 1 M1-149 Pass

Smoke Detector A/F Wing Smoke dr 1 M1-150 Pass

Smoke Detector F Wing Choral rm 101 1 M1-151 Pass

Smoke Detector A/F Wing Smoke dr 1 M1-153 Pass

Smoke Detector A/F Wing Smoke dr 1 M1-154 Pass

Smoke Detector F Wing Home/Family Stor rm 116 1 M1-157 Pass

Smoke Detector F Wing Media Ctr A/V Stor 1 M1-159 Pass

Duct Detector A Wing Mezzanine A148 1 M1-160 Not Found

Smoke Detector A Wing Mech rm 159 1 M1-161 Not Found

Duct Detector A Wing Mech rm 159 1 M1-162 Pass

Duct Detector A Wing Mech rm 159 1 M1-163 Pass

Duct Detector G Wing Engineering bldg 1 M1-171 Not Found

Duct Detector Cafe RTU 1 M1-201 Not Found

Pull Station E Wing Exit 1 M1-1 Pass

Pull Station Main Office Exit 1 M1-5 Pass

Pull Station Corr B148 Exit E/D Wings 1 M1-19 Pass

Pull Station Corr B148 Exit North 1 M1-20 Pass

Ansul Sp Ed Kitchen Hood rm B142 1 M1-29 Visual

Pull Station A Wing Exit to Courtyard 1 M1-34 Pass

Pull Station Admin Exit A112 1 M1-47 Pass

Pull Station Lunch rm Exit to Corr 1 M1-51 Pass

Pull Station Main Entrance Corr 1 M1-52 Pass

Pull Station D Wing Exit 1 M1-53 Pass

Tamper Switch Mech rm A134 1 M1-55 Pass

Tamper Switch Mech rm A134 1 M1-56 Pass

Tamper Switch Mech rm A134 1 M1-57 Pass

Pull Station Corr B148 Exit @ C/D Wings 1 M1-70 Pass

Pull Station Kitchen Receiving rm A148 1 M1-78 Pass

Pull Station C Wing Exit 1 M1-90 Pass

Pull Station Lunch rm Exit South 1 M1-94 Pass

Tamper Switch PIV 1 M1-95 Pass

Ansul Ktchen Hood rm A130 1 M1-96 Visual

Tamper Switch Mech rm A134 1 M1-99 Pass

Pull Station G Wing Rear Exit @ Weight rm 1 M1-101 Pass

Duct Detector Gym 1 M1-107 No Access

Duct Detector Gym 1 M1-108 No Access

Pull Station A Wing Exit @ Laundry 1 M1-110 Pass

Pull Station G Wing Gym Exit to Corr NW 1 M1-113 Pass

Pull Station A Wing Exit to Corr SW 1 M1-114 Pass

Pull Station A Wing Corr G100 Exit North 1 M1-121 Pass

Pull Station F Wing Exit Band rm 129 1 M1-126 Pass

Pull Station F Wing Exit Art Lab rm 117 1 M1-133 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 481: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station G Wing Exit Corr G100 1 M1-135 Pass

Pull Station F Wing Exit Choral rm 101 1 M1-148 Pass

Ansul F Wing Kitchen Hood rm 113 1 M1-152 Visual

Ansul F Wing Kitchen Hood rm 114 1 M1-155 Visual

Pull Station F Wing Corr Exit West 1 M1-156 Pass

Ansul F Wing Kitchen Hood rm 115 1 M1-158 Visual

Pull Station A Wing Exit Reading/Media Ctr 1 M1-164 Pass

Pull Station G Wing Engineering bldg 1 M1-170 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 482: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. (2) Batteries failed load test.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 483: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 484: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

6 0

14 4

20 0

7 0

34 0

3 0

4 0

Inspector Name : Signature:

FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Pass

Are Lamps and Displays Operating Properly

Power Supplies Simplex 4009

Ground fault

Panel Secondary power loss

Open Circuit Detection

Panel Power Loss

GD-4765-8N

Waterflow Switches System Sensor VSR

Simplex

Simplex

2099-9101

Duct Detectors Simplex

Nibco

(678) 691-0011

3645 Coal Mountain Drive

30028

Simplex

Front Office by Reception

Model Name

Cumming GA

Is the Panel Monitored Yes

4010

EI1273

North Forsyth Middle School

6/9/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC Security (888-745-4733)Monitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Who Was Notified Prior to the Start of Testing Monitoring Company & Staff

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Batteries

4098-9756

David Piorkowski

Pass

Pullstations

Smoke Detectors 4098-9714

Power Patrol

4010Control Panel

Pass

Device

Simplex

Interface Equipment

David Piorkowski

Tamper Switches

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 485: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Expired (2015) 13.4 Fail

Expired (2015) 13.3 Fail

Good (2019) 13.5 Pass

Good (2019) 13.6 Pass

Good (2019) 13.8 Pass

Good (2019) 13.7 Pass

Expired (2015) 13.3 Fail

Expired (2015) 13.4 Fail

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

N/A

Pass

N/AFM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

Fire Pump Running Reports to Panel

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

12V 7AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Supervisory Signals

Site Water Level /Temp

Fire Alarm Control Panel (Left)

Fire Alarm Control Panel (Right) 12V 7AH

BPS #2 RM 542 (Left) 12V 7AH

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Magnetic Door Holders

BPS #2 RM 542 (Right) 12V 7AH

Voice Control Panel Rm 106 (Left) 12V 7AH

Voice Control Panel Rm 106 (Right) 12V 7AH

12V 7AH

BPS #1 next to FACP (Right) 12V 7AH

Fire Pump Trouble

Fire Pump Phase Reversal

BPS #1 next to FACP (Left)

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Emergency Communications Equipment

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

Battery Testing

Each Phone Set Activated and Operation VerifiedPhone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 486: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Pull Station MAIN OFFICE REAR EXIT 1 M1 1 Pass

Duct Detector OUTSIDE MECHANICAL RM A191 1 M1 2 Pass

Pull Station MAIN LOBBY EXIT 1 M1 3 Pass

Pull Station CAFÉ 130 FRONT EXIT 1 M1 4 Pass

Pull Station CAFÉ 130 FRONT EXIT 1 M1 5 Pass

Pull Station LOBBY A101 EXIT @ MENS RR 1 M1 6 Not Found

Pull Station MAIN OFFICE FRONT DOOR EXIT 1 M1 9 Pass

Pull Station 6 GRD CORR 200 EXIT @ 257 1 M1 12 Pass

Pull Station 285 CORR EXIT @ 324 1 M1 13 Pass

Pull Station 7 GRND CORR 300 EXIT @ 357 1 M1 16 Pass

Pull Station 8 GRD 400 CORR EXIT @ 457 1 M1 31 Pass

Tamper Switch MECH RM A120 TAMPER #1 1 M1 38 Pass

Waterflow Switch MECH RM A120 HIGH PRESSURE #1 1 M1 39 Pass

Duct Detector MECHANICAL RM A120 1 M1 40 Pass

Pull Station KITCHEN A107 REAR EXIT 1 M1 42 Pass

Duct Detector MECHANICAL RM 607 1 M1 50 Pass

Pull Station MEDIA CENTER A176 REAR EXIT 1 M1 51 Pass

Duct Detector MECHANICAL RM 602 1 M1 52 Pass

Pull Station 500 CORR SIDE EXIT @ MEDIA 1 M1 53 Pass

Pull Station MUSIC ROOM 509 EXIT 1 M1 62 Pass

Duct Detector MECHANICAL RM E120 1 M1 63 Pass

Pull Station TECH ROOM 514 EXIT 1 M1 64 Pass

Pull Station ART LAB RM 525 EXIT 1 M1 69 Pass

Pull Station GYM LOBBY EXIT 1 M1 74 Pass

Pull Station GYM FRONT EXIT @ STORAGE 1 M1 78 Pass

Pull Station GYM FRONT EXIT @ STORAGE 1 M1 79 Pass

Pull Station GYM REAR EXIT @ OFFICE 587 1 M1 84 Pass

Low Air GYM ELEC 605 LOW PRESSURE 1 M1 85 Pass

Waterflow Switch GYM ELEC RM 605 HIGH PRESSURE 1 M1 86 Pass

Tamper Switch GYM ELEC RM 605 TAMPER 1 M1 87 Pass

Pull Station GYM REAR EXIT @ OFFICE 586 1 M1 88 Pass

Pull Station 285 CORR EXIT @ 422 1 M1 89 Pass

Pull Station 285 CORR EXIT @ RM 415 1 M1 90 Pass

Monitor KITCHEN A107 ANSUL SYSTEM 1 M1 91 Pass

Tamper Switch MECH RM A120 TAMPER #2 1 M1 92 PassWaterflow Switch MECH RM A120 HIGH PRESSURE #2 1 M1 96 Pass

Low Air MECH RM A120 HIGH PRESSURE #1 1 M1 97 Pass

Low Air MECH RM A120 HIGH PRESSURE #2 1 M1 98 Pass

Smoke Detector LOBBY A101 SMOKE DOORS 1 M1 107 Pass

Smoke Detector LOBBY A101 SMOKE DOORS 1 M1 109 Pass

Smoke Detector 285 CORR @ 6 GRD SMK DRS 1 M1 117 Pass

Smoke Detector 285 CORR @ 6 GRD SMK DRS 1 M1 118 Pass

Smoke Detector 6 GRD SMK DR @ 231 1 M1 119 Pass

Smoke Detector 6 GRD SMK DR @ 232 1 M1 120 Pass

Smoke Detector 85 CORR @ 7 GRD SMK DR 1 M1 121 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 487: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector 85 CORR @ 7 GRD SMK DR 1 M1 122 Pass

Smoke Detector GRD SMK DR @ 331 1 M1 123 Pass

Smoke Detector GRD SMK DR @ 331 1 M1 124 Pass

Smoke Detector 85 CORR @ 8 GRD SMK DR 1 M1 125 Pass

Smoke Detector 85 CORR @ 8 GRD SMK DR 1 M1 126 Pass

Smoke Detector GRD SMK DR @ 431 1 M1 127 Pass

Smoke Detector GRD SMK DR @ 432 1 M1 128 Pass

Smoke Detector CAFÉ @ FOOD COURT EXIT 1 M1 132 Pass

Smoke Detector CAFÉ @ FOOD COURT EXIT 1 M1 133 Pass

Smoke Detector CAFÉ 130 TRAY RETURN 1 M1 134 Pass

Smoke Detector FOOD COURT @ CAFÉ EXIT 1 M1 135 Pass

Smoke Detector FOOD COURT @ CAFÉ EXIT 1 M1 136 Pass

Heat Detector KITCHEN A107 @ DISHWASHER 1 M1 137 Pass

Heat Detector KITCHEN A107 @ OFFICE A115 1 M1 141 Pass

Smoke Detector FOOD COURT ENTRANCE 1 M1 143 Pass

Smoke Detector FOOD COURT ENTRANCE 1 M1 144 Pass

Smoke Detector CORR @ FOOD COURT ENTRANCE 1 M1 145 Pass

Smoke Detector CORR @ FOOD COURT ENTRANCE 1 M1 146 Pass

Heat Detector BREAK RM 409 @ KITCHEN 163 1 M1 147 Pass

Heat Detector MUSIC ROOM 509 1 M1 154 Pass

Heat Detector MUSIC ROOM 509 1 M1 155 Pass

Heat Detector MUSIC ROOM 509 1 M1 156 Pass

Heat Detector MUSIC ROOM 509 1 M1 157 Pass

Smoke Detector 500 CORR SMOKE DR @ 508 1 M1 158 Pass

Smoke Detector 500 CORR SMOKE DR @ 508 1 M1 159 Pass

Smoke Detector 500 CORR SMOKE DR @ 512 1 M1 160 Pass

Smoke Detector 500 CORR SMOKE DR @ 512 1 M1 161 Pass

Smoke Detector 500 CORR SMK DR @ GYM ENT 1 M1 165 Pass

Smoke Detector CORR 500 SMOKE DRS @ GYM 1 M1 166 Pass

Smoke Detector GYM ENT SMK DR @ 500 CORR 1 M1 167 Pass

Smoke Detector GYM ENT SMK DR @ 500 CORR 1 M1 168 Pass

Smoke Detector CONCESSION STAND 549 1 M1 172 Pass

Smoke Detector GYM LOBBY @ CONCESSION 1 M1 173 Pass

Smoke Detector GYM LOBBY ENTRY TO GYM 1 M1 175 Pass

Smoke Detector GYM LOBBY ENTRY TO GYM 1 M1 176 Pass

Smoke Detector GYM CEILING @ STOR RM 571 1 M1 177 Pass

Smoke Detector GYM CEILING @ STOR RM 572 1 M1 180 Pass

Smoke Detector GYM CEILING @ REAR EXIT 1 M1 181 Pass

Smoke Detector GYM CEILING @ REAR EXIT 1 M1 182 Pass

Smoke Detector GYM REAR CORR @ OFFICE 587 1 M1 183 Pass

Smoke Detector GYM REAR CORR @ OFFICE 585 1 M1 185 Pass

Heat Detector MUSIC ROOM 509 1 M1 192 Pass

Duct Detector BEHIND GYM-AHU 1 M1 201 Pass

Duct Detector BEHIND GYM-AHU 1 M1 202 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 488: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

1. (4) 12V 7AH Back up batteries are expired and need replacement.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 489: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 490: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

6 0

16 0

27 0

93 1

21 4

3 0

3 0

Inspector Name : Signature:

Tamper Switches SPF GBV-3

Waterflow Switches Potter VSR-F

(678) 691-0011

7455 Wallace Tatum Road

30028

Notifier

Admin Area

Model Name

Cumming GA

Is the Panel Monitored Yes

AFP-400

EI1273

Matt Elementary

6/10/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC Security (888-745-4733)Monitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Pass

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing Monitoring Company & Staff

Batteries FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Notifier FCPS-24S8

David Piorkowski

Pass

Pullstations

Smoke Detectors FSP-751

Power Patrol

AFP-400Control Panel

Pass

Device

Notifier

Interface Equipment

David Piorkowski

Notifier

Notifier

NBG-12LX

Duct Detectors System Sensor DH100ACDI

Voice Evac Signal Communications DVS-25

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 491: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.6 Pass

Good (2020) 13.7 Pass

Good (2020) 13.5 Pass

Good (2020) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

N/A

Pass

N/A

Phone Sets

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

Fire Alarm Control Panel (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Magnetic Door Holders

Voice Control Panel Rm 552 (Left) 12V 7AH

Voice Control Panel Rm 552 (Right) 12V 7AH

Fire Pump Trouble

Fire Alarm Control Panel (Right) 12V 7AH

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Emergency Communications Equipment

Fire Pump Phase Reversal

Continued on Page 3 - Battery Testing

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Fire Pump Running

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 492: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Floor Condition Voltage Load Test

1 Good (2020) 13.6 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.6 Pass

BPS #5 Rm 674 (Right) 12V 7AH

BPS #6 Rm 677 (Left) 12V 7AH

BPS #6 Rm 677 (Right) 12V 7AH

Battery Testing (continued).

Location Size

BPS #1 Rm 433 (Left) 12V 7AH

BPS #5 Rm 674 (Left) 12V 7AH

BPS #2 Rm 451(Left) 12V 7AH

BPS #2 Rm 451 (Right) 12V 7AH

BPS #1 Rm 433 (Right) 12V 7AH

BPS #4 Rm 671 (Right) 12V 7AH

BPS #3 Rm 457 (Left) 12V 7AH

BPS #3 Rm 457 (Right) 12V 7AH

BPS #4 Rm 671 (Left) 12V 7AH

Page 493: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Smoke Detector ZN3 1 1D 1 Pass

Smoke Detector RM 334 1 1D 2 Pass

Smoke Detector RM 333 1 1D 3 Pass

Smoke Detector RM 338 1 1D 4 Pass

Smoke Detector RM 318 1 1D 5 Pass

Smoke Detector RM 337 1 1D 6 Pass

Smoke Detector RM 317 1 1D 7 Pass

Smoke Detector RM 314 1 1D 8 Pass

Smoke Detector RM 304 1 1D 9 Pass

Smoke Detector RM 313 1 1D 10 Pass

Smoke Detector RM 303 1 1D 11 Pass

Duct Detector 2ND GRADE CORRIDOR 1 1D 12 Fail

Duct Detector 2ND GRADE CORRIDOR 1 1D 13 Pass

Smoke Detector 2ND GRADE CORRIDOR 1 1D 14 Pass

Smoke Detector COMMUNICATION FM 455 1 1D 15 Pass

Smoke Detector JANITOR RM 301 1 1D 16 Pass

Smoke Detector 2ND GRADE CORRIDOR 1 1D 17 Pass

Smoke Detector BOOK RM 302 1 1D 18 Pass

Smoke Detector 1ST GRADE STORAGE 250 1 1D 19 Pass

Smoke Detector 1ST GRADE STORAGE 250 1 1D 20 Pass

Smoke Detector 1ST GRADE STORAGE 250 1 1D 21 Pass

Smoke Detector 1ST GRADE RM 324 1 1D 22 Pass

Smoke Detector RM 235 1 1D 23 Pass

Smoke Detector RM 228 1 1D 24 Pass

Smoke Detector RM 218 1 1D 25 Pass

Smoke Detector RM 227 1 1D 26 Pass

Smoke Detector RM 217 1 1D 27 Pass

Smoke Detector RM 214 1 1D 28 Pass

Smoke Detector RM 213 1 1D 29 Pass

Smoke Detector RM 203 1 1D 30 Pass

Smoke Detector COMMUNICATION RM 453 1 1D 31 Pass

Smoke Detector ELECTRIC RM 451 1 1D 32 Pass

Smoke Detector JANITOR RM 202 1 1D 33 Pass

Duct Detector 1ST GRADE CORRIDOR 1 1D 34 Pass

Duct Detector 1ST GRADE CORRIDOR 1 1D 35 Fail

Smoke Detector 1ST GRADE CORRIDOR 1 1D 36 Pass

Duct Detector MECHANICAL RM 201 1 1D 37 Fail

Smoke Detector 1ST GRADE CORRIDOR 1 1D 38 Pass

Smoke Detector KINDERGARDEN RM 134 1 1D 40 Pass

Smoke Detector KINDERGARDEN RM 133 1 1D 41 Pass

Smoke Detector KINDRGARDEN RM 127 1 1D 42 Pass

Smoke Detector RM 117 1 1D 43 Pass

Smoke Detector RM 128 1 1D 44 Pass

Smoke Detector RM 118 1 1D 45 Pass

Smoke Detector RM 118 1 1D 46 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 494: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector RM 103 1 1D 47 Pass

Smoke Detector RM 114 1 1D 48 Pass

Smoke Detector RM 104 1 1D 49 Pass

Smoke Detector COMMUNICATION RM 453 1 1D 50 Pass

Smoke Detector ELECTRIC RM 433 1 1D 51 Pass

Smoke Detector JANITOR RM 102 1 1D 52 Pass

Smoke Detector KINDERGARDEN CORRIDOR 1 1D 53 Pass

Smoke Detector BOOK RM 101 1 1D 54 Pass

Smoke Detector KINDERGARDEN CORRIDOR 1 1D 55 Pass

Smoke Detector KINDERGARDEN CORRIDOR 1 1D 56 Pass

Smoke Detector KINDERGARDEN CORRIDOR 1 1D 57 Pass

Smoke Detector SPECIAL ED 1 1D 58 Pass

Duct Detector MECHANICAL RM 201 1 1D 59 Pass

Smoke Detector RM 403 CUSTODIAL 1 1D 62 Pass

Smoke Detector ART RM KILN 1 1D 64 Pass

Smoke Detector ART RM STORAGE 1 1D 65 Pass

Smoke Detector MEDIA CENTER STORAGE 1 1D 66 Pass

Smoke Detector AV STORAGE 1 1D 67 Pass

Smoke Detector CONFERENCE RM 1 1D 68 Pass

Smoke Detector WORK RM 1 1D 69 Pass

Duct Detector MECHANICAL RM 502 1 1D 70 Pass

Duct Detector MECHANICAL RM 502 1 1D 71 Pass

Duct Detector MECHANICAL RM 501 1 1D 72 Pass

Duct Detector MECHANICAL RM 501 1 1D 73 Pass

Smoke Detector ZN3 1 1D 74 Pass

Pull Station NEAR ROOM 333 1 1M 1 Pass

Pull Station NEAR ROOM 302 1 1M 2 Pass

Pull Station NEAR MECHANICAL RM 302 1 1M 3 Pass

Pull Station NEAR ROOM 250 1 1M 4 Pass

Pull Station NEAR ROOM 133 1 1M 5 Pass

Pull Station NEAR OFFICE 432 1 1M 6 Pass

Pull Station CORRIDOR NEAR OFFICE 1 1M 7 Pass

Pull Station FORYER 1 1M 8 Pass

Pull Station CORRIDOR NEAR OFFICE 1 1M 9 Pass

Smoke Detector BOOK RM 701 1 2D 1 Pass

Smoke Detector 5TH GRADE CORRIDOR 1 2D 3 Pass

Duct Detector 5TH GRADE CORRIDOR 1 2D 4 Pass

Smoke Detector 5TH GRADE CORRIDOR 1 2D 5 Pass

Smoke Detector ELECTRIC RM 671 1 2D 6 Pass

Smoke Detector COMMUNICATION RM 672 1 2D 7 Pass

Smoke Detector COMMUNICATION RM 673 1 2D 8 Pass

Smoke Detector ELECTRIC RM 674 1 2D 9 Pass

Smoke Detector 4TH GRADE CORRIDOR 1 2D 10 Pass

Duct Detector 4TH GRADE CORRIDOR 1 2D 11 Pass

Smoke Detector 4TH GRADE CORRIDOR 1 2D 12 Pass

Duct Detector MECHANICAL RM 802 1 2D 13 Pass

Duct Detector MECHANICAL RM 802 1 2D 14 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 495: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector 5TH GRADE CORRIDOR 1 2D 15 Pass

Duct Detector MECHANICAL RM 802 1 2D 16 Pass

Smoke Detector COMMUNICATION RM 676 1 2D 17 Pass

Smoke Detector ELECTRIC RM 677 1 2D 18 Pass

Smoke Detector JANITOR RM 901 1 2D 19 Pass

Smoke Detector 3RD GRADE CORRIDOR 1 2D 20 Pass

Duct Detector 3RD GRADE COMPUTER 1 2D 21 Pass

Smoke Detector 3RD GRADE CORRIDOR 1 2D 22 Pass

Duct Detector 3RD GRADE COMPUTER 1 2D 23 Fail

Smoke Detector BOOKROOM 902 1 2D 24 Pass

Smoke Detector MECHANICAL RM 679 1 2D 25 Pass

Smoke Detector STORAGE RM 668 1 2D 26 Pass

Smoke Detector MUSIC STORAGE RM 621 1 2D 27 Pass

Smoke Detector DINING RM STORAGE 1 2D 31 Pass

Duct Detector SERVING LINE 1 2D 32 Pass

Duct Detector SERVING LINE 1 2D 33 Pass

Smoke Detector SMOKE DOOR SERVING LINE 1 2D 34 Pass

Smoke Detector DINING SMOKE DOOR 1 2D 35 Pass

Smoke Detector MAIN ELECTRICAL RM 1 2D 36 Pass

Smoke Detector GYM SMOKE DOOR 1 2D 37 Pass

Smoke Detector GYM SMOKE DOOR 1 2D 38 Pass

Smoke Detector CAN WASH 1 2D 39 Pass

Smoke Detector GYM SMOKE DOOR 1 2D 40 Pass

Smoke Detector GYM SMOKE DOOR 1 2D 41 Fail

Smoke Detector ZN3 1 2D 42 Pass

Smoke Detector KITCHEN JANITOR RM 1 2D 43 Pass

Smoke Detector OUTSIDE EQUIPMENT STORAGE 1 2D 44 Pass

Smoke Detector ZN3 1 2D 45 Pass

Smoke Detector ART RM 627 1 2D 46 Pass

Smoke Detector RM 629 STORAGE 1 2D 47 Pass

Duct Detector DRY STORAGE 1 2D 56 Pass

Pull Station NEAR RM 918 1 2M 1 Pass

Pull Station NEAR RM 902 1 2M 4 Pass

Pull Station NEAR RM 208 1 2M 8 Pass

Pull Station NEAR RM 701 1 2M 9 Pass

Pull Station NEAR RM 718 1 2M 10 Pass

Pull Station DINING RM 1 2M 13 Pass

Pull Station MAIN ELECTRICAL RM 1 2M 14 Pass

Pull Station GYM 1 2M 15 Pass

Pull Station MAIN ELECTRICAL RM 1 2M 16 Pass

Waterflow Switch MECH ROOM 584 1 2M 17 Pass

Pull Station OUTSIDE EQUIPMENT RM 1 2M 19 Pass

Pull Station GYM 1 2M 20 Pass

Pull Station GYM 1 2M 21 Pass

Pull Station GYM MULTI-PURPOSE RM 1 2M 22 Pass

Pull Station GYM MULTI-PURPOSE RM 1 2M 23 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 496: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station GYM 1 2M 24 Pass

Pull Station CAN WASH RM 1 2M 25 Pass

Pull Station KITCHEN 1 2M 26 Pass

Pull Station DINING RM 1 2M 27 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 497: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

3. 1st grade Corridor & 3rd grade Computer room.

5. (1) Duct detector did not report to FACP @ Mechanical Room# 201.

Deficiencies

1. (1) Smoke detector above Gym smoke door does not report to FACP.

2. (2) Duct detectors sample tubes are not penetrating duct work at 1st grade Corridor & 3rd grade Computer room,

4. (1) Duct detector missing cover @ 1st grade Corridor.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 498: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 499: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

6 0

16 0

27 0

93 1

21 4

3 0

3 0

Inspector Name : Signature:

Tamper Switches SPF GBV-3

Waterflow Switches Potter VSR-F

(678) 691-0011

7455 Wallace Tatum Road

30028

Notifier

Admin Area

Model Name

Cumming GA

Is the Panel Monitored Yes

AFP-400

EI1273

Matt Elementary

6/10/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC Security (888-745-4733)Monitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Pass

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing Monitoring Company & Staff

Batteries FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Notifier FCPS-24S8

David Piorkowski

Pass

Pullstations

Smoke Detectors FSP-751

Power Patrol

AFP-400Control Panel

Pass

Device

Notifier

Interface Equipment

David Piorkowski

Notifier

Notifier

NBG-12LX

Duct Detectors System Sensor DH100ACDI

Voice Evac Signal Communications DVS-25

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 500: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2020) 13.6 Pass

Good (2020) 13.7 Pass

Good (2020) 13.5 Pass

Good (2020) 13.6 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

N/A

Pass

N/A

Phone Sets

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

Fire Alarm Control Panel (Left)

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Kitchen Hoods

Location Size

Magnetic Door Holders

Voice Control Panel Rm 552 (Left) 12V 7AH

Voice Control Panel Rm 552 (Right) 12V 7AH

Fire Pump Trouble

Fire Alarm Control Panel (Right) 12V 7AH

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Emergency Communications Equipment

Fire Pump Phase Reversal

Continued on Page 3 - Battery Testing

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Speakers/Horns

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Fire Pump Running

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 501: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Floor Condition Voltage Load Test

1 Good (2020) 13.6 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.7 Pass

1 Good (2020) 13.6 Pass

1 Good (2020) 13.6 Pass

BPS #5 Rm 674 (Right) 12V 7AH

BPS #6 Rm 677 (Left) 12V 7AH

BPS #6 Rm 677 (Right) 12V 7AH

Battery Testing (continued).

Location Size

BPS #1 Rm 433 (Left) 12V 7AH

BPS #5 Rm 674 (Left) 12V 7AH

BPS #2 Rm 451(Left) 12V 7AH

BPS #2 Rm 451 (Right) 12V 7AH

BPS #1 Rm 433 (Right) 12V 7AH

BPS #4 Rm 671 (Right) 12V 7AH

BPS #3 Rm 457 (Left) 12V 7AH

BPS #3 Rm 457 (Right) 12V 7AH

BPS #4 Rm 671 (Left) 12V 7AH

Page 502: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Smoke Detector ZN3 1 1D 1 Pass

Smoke Detector RM 334 1 1D 2 Pass

Smoke Detector RM 333 1 1D 3 Pass

Smoke Detector RM 338 1 1D 4 Pass

Smoke Detector RM 318 1 1D 5 Pass

Smoke Detector RM 337 1 1D 6 Pass

Smoke Detector RM 317 1 1D 7 Pass

Smoke Detector RM 314 1 1D 8 Pass

Smoke Detector RM 304 1 1D 9 Pass

Smoke Detector RM 313 1 1D 10 Pass

Smoke Detector RM 303 1 1D 11 Pass

Duct Detector 2ND GRADE CORRIDOR 1 1D 12 Fail

Duct Detector 2ND GRADE CORRIDOR 1 1D 13 Pass

Smoke Detector 2ND GRADE CORRIDOR 1 1D 14 Pass

Smoke Detector COMMUNICATION FM 455 1 1D 15 Pass

Smoke Detector JANITOR RM 301 1 1D 16 Pass

Smoke Detector 2ND GRADE CORRIDOR 1 1D 17 Pass

Smoke Detector BOOK RM 302 1 1D 18 Pass

Smoke Detector 1ST GRADE STORAGE 250 1 1D 19 Pass

Smoke Detector 1ST GRADE STORAGE 250 1 1D 20 Pass

Smoke Detector 1ST GRADE STORAGE 250 1 1D 21 Pass

Smoke Detector 1ST GRADE RM 324 1 1D 22 Pass

Smoke Detector RM 235 1 1D 23 Pass

Smoke Detector RM 228 1 1D 24 Pass

Smoke Detector RM 218 1 1D 25 Pass

Smoke Detector RM 227 1 1D 26 Pass

Smoke Detector RM 217 1 1D 27 Pass

Smoke Detector RM 214 1 1D 28 Pass

Smoke Detector RM 213 1 1D 29 Pass

Smoke Detector RM 203 1 1D 30 Pass

Smoke Detector COMMUNICATION RM 453 1 1D 31 Pass

Smoke Detector ELECTRIC RM 451 1 1D 32 Pass

Smoke Detector JANITOR RM 202 1 1D 33 Pass

Duct Detector 1ST GRADE CORRIDOR 1 1D 34 Pass

Duct Detector 1ST GRADE CORRIDOR 1 1D 35 Fail

Smoke Detector 1ST GRADE CORRIDOR 1 1D 36 Pass

Duct Detector MECHANICAL RM 201 1 1D 37 Fail

Smoke Detector 1ST GRADE CORRIDOR 1 1D 38 Pass

Smoke Detector KINDERGARDEN RM 134 1 1D 40 Pass

Smoke Detector KINDERGARDEN RM 133 1 1D 41 Pass

Smoke Detector KINDRGARDEN RM 127 1 1D 42 Pass

Smoke Detector RM 117 1 1D 43 Pass

Smoke Detector RM 128 1 1D 44 Pass

Smoke Detector RM 118 1 1D 45 Pass

Smoke Detector RM 118 1 1D 46 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 503: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector RM 103 1 1D 47 Pass

Smoke Detector RM 114 1 1D 48 Pass

Smoke Detector RM 104 1 1D 49 Pass

Smoke Detector COMMUNICATION RM 453 1 1D 50 Pass

Smoke Detector ELECTRIC RM 433 1 1D 51 Pass

Smoke Detector JANITOR RM 102 1 1D 52 Pass

Smoke Detector KINDERGARDEN CORRIDOR 1 1D 53 Pass

Smoke Detector BOOK RM 101 1 1D 54 Pass

Smoke Detector KINDERGARDEN CORRIDOR 1 1D 55 Pass

Smoke Detector KINDERGARDEN CORRIDOR 1 1D 56 Pass

Smoke Detector KINDERGARDEN CORRIDOR 1 1D 57 Pass

Smoke Detector SPECIAL ED 1 1D 58 Pass

Duct Detector MECHANICAL RM 201 1 1D 59 Pass

Smoke Detector RM 403 CUSTODIAL 1 1D 62 Pass

Smoke Detector ART RM KILN 1 1D 64 Pass

Smoke Detector ART RM STORAGE 1 1D 65 Pass

Smoke Detector MEDIA CENTER STORAGE 1 1D 66 Pass

Smoke Detector AV STORAGE 1 1D 67 Pass

Smoke Detector CONFERENCE RM 1 1D 68 Pass

Smoke Detector WORK RM 1 1D 69 Pass

Duct Detector MECHANICAL RM 502 1 1D 70 Pass

Duct Detector MECHANICAL RM 502 1 1D 71 Pass

Duct Detector MECHANICAL RM 501 1 1D 72 Pass

Duct Detector MECHANICAL RM 501 1 1D 73 Pass

Smoke Detector ZN3 1 1D 74 Pass

Pull Station NEAR ROOM 333 1 1M 1 Pass

Pull Station NEAR ROOM 302 1 1M 2 Pass

Pull Station NEAR MECHANICAL RM 302 1 1M 3 Pass

Pull Station NEAR ROOM 250 1 1M 4 Pass

Pull Station NEAR ROOM 133 1 1M 5 Pass

Pull Station NEAR OFFICE 432 1 1M 6 Pass

Pull Station CORRIDOR NEAR OFFICE 1 1M 7 Pass

Pull Station FORYER 1 1M 8 Pass

Pull Station CORRIDOR NEAR OFFICE 1 1M 9 Pass

Smoke Detector BOOK RM 701 1 2D 1 Pass

Smoke Detector 5TH GRADE CORRIDOR 1 2D 3 Pass

Duct Detector 5TH GRADE CORRIDOR 1 2D 4 Pass

Smoke Detector 5TH GRADE CORRIDOR 1 2D 5 Pass

Smoke Detector ELECTRIC RM 671 1 2D 6 Pass

Smoke Detector COMMUNICATION RM 672 1 2D 7 Pass

Smoke Detector COMMUNICATION RM 673 1 2D 8 Pass

Smoke Detector ELECTRIC RM 674 1 2D 9 Pass

Smoke Detector 4TH GRADE CORRIDOR 1 2D 10 Pass

Duct Detector 4TH GRADE CORRIDOR 1 2D 11 Pass

Smoke Detector 4TH GRADE CORRIDOR 1 2D 12 Pass

Duct Detector MECHANICAL RM 802 1 2D 13 Pass

Duct Detector MECHANICAL RM 802 1 2D 14 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 504: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Duct Detector 5TH GRADE CORRIDOR 1 2D 15 Pass

Duct Detector MECHANICAL RM 802 1 2D 16 Pass

Smoke Detector COMMUNICATION RM 676 1 2D 17 Pass

Smoke Detector ELECTRIC RM 677 1 2D 18 Pass

Smoke Detector JANITOR RM 901 1 2D 19 Pass

Smoke Detector 3RD GRADE CORRIDOR 1 2D 20 Pass

Duct Detector 3RD GRADE COMPUTER 1 2D 21 Pass

Smoke Detector 3RD GRADE CORRIDOR 1 2D 22 Pass

Duct Detector 3RD GRADE COMPUTER 1 2D 23 Fail

Smoke Detector BOOKROOM 902 1 2D 24 Pass

Smoke Detector MECHANICAL RM 679 1 2D 25 Pass

Smoke Detector STORAGE RM 668 1 2D 26 Pass

Smoke Detector MUSIC STORAGE RM 621 1 2D 27 Pass

Smoke Detector DINING RM STORAGE 1 2D 31 Pass

Duct Detector SERVING LINE 1 2D 32 Pass

Duct Detector SERVING LINE 1 2D 33 Pass

Smoke Detector SMOKE DOOR SERVING LINE 1 2D 34 Pass

Smoke Detector DINING SMOKE DOOR 1 2D 35 Pass

Smoke Detector MAIN ELECTRICAL RM 1 2D 36 Pass

Smoke Detector GYM SMOKE DOOR 1 2D 37 Pass

Smoke Detector GYM SMOKE DOOR 1 2D 38 Pass

Smoke Detector CAN WASH 1 2D 39 Pass

Smoke Detector GYM SMOKE DOOR 1 2D 40 Pass

Smoke Detector GYM SMOKE DOOR 1 2D 41 Fail

Smoke Detector ZN3 1 2D 42 Pass

Smoke Detector KITCHEN JANITOR RM 1 2D 43 Pass

Smoke Detector OUTSIDE EQUIPMENT STORAGE 1 2D 44 Pass

Smoke Detector ZN3 1 2D 45 Pass

Smoke Detector ART RM 627 1 2D 46 Pass

Smoke Detector RM 629 STORAGE 1 2D 47 Pass

Duct Detector DRY STORAGE 1 2D 56 Pass

Pull Station NEAR RM 918 1 2M 1 Pass

Pull Station NEAR RM 902 1 2M 4 Pass

Pull Station NEAR RM 208 1 2M 8 Pass

Pull Station NEAR RM 701 1 2M 9 Pass

Pull Station NEAR RM 718 1 2M 10 Pass

Pull Station DINING RM 1 2M 13 Pass

Pull Station MAIN ELECTRICAL RM 1 2M 14 Pass

Pull Station GYM 1 2M 15 Pass

Pull Station MAIN ELECTRICAL RM 1 2M 16 Pass

Waterflow Switch MECH ROOM 584 1 2M 17 Pass

Pull Station OUTSIDE EQUIPMENT RM 1 2M 19 Pass

Pull Station GYM 1 2M 20 Pass

Pull Station GYM 1 2M 21 Pass

Pull Station GYM MULTI-PURPOSE RM 1 2M 22 Pass

Pull Station GYM MULTI-PURPOSE RM 1 2M 23 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 505: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pull Station GYM 1 2M 24 Pass

Pull Station CAN WASH RM 1 2M 25 Pass

Pull Station KITCHEN 1 2M 26 Pass

Pull Station DINING RM 1 2M 27 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 506: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

3. 1st grade Corridor & 3rd grade Computer room.

5. (1) Duct detector did not report to FACP @ Mechanical Room# 201.

Deficiencies

1. (1) Smoke detector above Gym smoke door does not report to FACP.

2. (2) Duct detectors sample tubes are not penetrating duct work at 1st grade Corridor & 3rd grade Computer room,

4. (1) Duct detector missing cover @ 1st grade Corridor.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 507: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 508: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

5 0

14 0

28 0

59 0

28 0

14 0

2 0

2 0

Inspector Name : Signature: David Piorkowski

Pass

Pullstations

Smoke Detectors FSP-751

Power Patrol

AFP-400Control Panel

Pass

Device

Notifier

Interface Equipment

David Piorkowski

Notifier

Notifier

NBG-12LX

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing Monitoring Company & Office Staff

Batteries FAS1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival

Ground fault

Panel Secondary power loss

Open Circuit Detection

Power Supplies Notifier

6/11/2020

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Pass

Tamper Switches Potter OSYSU-2

(678) 691-0011

3777 Samples Road

30041

Simplex

Admin Area Work Area

Model Name

Cumming GA

Is the Panel Monitored Yes

4010

EI1273 / WO #155451

Mashburn Elementary School

Voice Evac Signal Communications DVS-25

VSR-FPotterWaterflow Switches

Heat Detectors Notifier FSP-751R

Duct Detectors Notifier DHX-501

FCPS-24S8

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 509: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Pass

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2019) 13.6 Pass

Good (2019) 13.6 Pass

Good (2019) 13.4 Pass

Good (2019) 13.5 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

Pass

N/A

Pass

Pass

N/A

N/A

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

Continued on Page 3 - Battery Testing

FACP 12V 7A

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 7A

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door HoldersMagnetic Door Holders

Voice 12V 7A

Voice 12V 7A

Speakers/Horns

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 510: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Floor Condition Voltage Load Test

1 Good (2019) 13.7 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.6 Pass

1 Good (2019) 13.7 Pass

1 Good (2018) 13.7 Pass

1 Good (2018) 13.7 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.7 Pass

1 Good (2019) 13.8 Pass

BPS #4 Book Storage Rm 151 (Left) 12V 7AH

BPS #3 Custodial Rm 152 (Left) 12V 7AH

BPS #3 Custodial Rm 152 (Right) 12V 7AH

BPS #2 Elec Rm 204 (Left) 12V 7AH

BPS #2 Elec Rm 204 (Right) 12V 7AH

BPS #1 Elec Rm 301 (Right) 12V 7AH

Battery Testing (Continued)

Location Size

BPS #1 Elec Rm 301 (Left) 12V 7AH

BPS #4 Book Storage Rm 151 (Right) 12V 7AH

BPS#5 Custodial Rm 192 (Left) 12v 7AH

BPS#5 Custodial Rm 192 (Right) 12V 7AH

Page 511: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Loop Address Results

Pull Station LOBBY 1 M 101 Pass

Pull Station ADMIN EXIT 1 M 102 Pass

Pull Station MEDIA CENTER 1 M 103 Pass

Pull Station MEDIA CENTER 1 M 104 Pass

Pull Station NEAR ROOM 138 1 M 105 Pass

Pull Station NEAR ROOM 161 1 M 106 Pass

Pull Station CAFETERIA 1 M 107 Pass

Pull Station NEAR RM 168 1 M 108 Pass

Pull Station GYM 1 M 109 Pass

Pull Station GYM 1 M 110 Pass

Pull Station GYM 1 M 111 Pass

Pull Station 2ND GRADE PASSAGEWAY 1 M 112 Pass

Pull Station 2ND GRADE PASSAGEWAY 1 M 113 Pass

Pull Station MECH RM 331 1 M 114 Pass

Pull Station MECH RM 330 1 M 115 Pass

Pull Station NEAR RM 322 1 M 116 Pass

Pull Station 3RD GRADE PASSAGEWAY 1 M 117 Pass

Pull Station 3RD GRADE PASSAGEWAY 1 M 118 Pass

Pull Station NEAR RM 205 1 M 119 Pass

Pull Station NEAR RM 238 1 M 120 Pass

Pull Station MECH RM 241 1 M 121 Pass

Pull Station CAFETERIA 1 M 122 Pass

Waterflow Switch JANITOR RM 202 1 M 123 Pass

Waterflow Switch JANITOR RM 202 1 M 124 Pass

Tamper Switch JANITOR RM 202 1 M 125 Pass

Tamper Switch JANITOR RM 202 1 M 126 Pass

Pull Station CAFÉ STORAGE 1 M 127 Pass

Pull Station CANOPY EXIT 1 M 128 Pass

Pull Station KITCHEN EXIT 1 M 135 Pass

Pull Station EXIT C CORRIDOR 100 1 M 197 Pass

Pull Station EXIT B CORRIDOR 100 1 M 198 Pass

Pull Station EXIT A CORRIDOR 100 1 M 199 Pass

Duct Detector MECH ROOM 331 1 D 109 Pass

Smoke Detector LOBBY 108 CORR 1 D 110 Pass

Duct Detector MECH RM 331 1 D 111 Pass

Duct Detector 1ST GRADE HALL 1 D 112 Pass

Duct Detector ERU 1 SUPPLY 1 D 113 Pass

Smoke Detector K GARDEN HALL 1 D 114 Pass

Smoke Detector CLASS RM 122 1 D 115 Pass

Smoke Detector CLASS RM 121 1 D 116 Pass

Smoke Detector K GARDEN HALL 1 D 117 Pass

Smoke Detector CLASS RM 126 1 D 118 Pass

Smoke Detector CLASS RM 125 1 D 119 Pass

Smoke Detector K GARDEN HALL 1 D 120 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 512: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Smoke Detector MEDIA CONF ROOM 1 D 121 Pass

Smoke Detector MEDIA STORAGE 1 D 122 Pass

Smoke Detector CLASS RM 134 1 D 123 Pass

Smoke Detector K GARDEN HALL 1 D 124 Pass

Smoke Detector FIRST GRADE HALL 1 D 125 Pass

Smoke Detector 1ST GRADE HALL 1 D 126 Pass

Smoke Detector MEDIA CENTER 1 D 127 Pass

Smoke Detector MEDIA CENTER 1 D 128 Pass

Heat Detector JANITOR CLOSET FIRST GRADE 1 D 129 Pass

Smoke Detector FIRST GRADE HALL 1 D 130 Pass

Smoke Detector SPECIAL ED A 1 D 131 Pass

Smoke Detector SPECIAL ED B 1 D 132 Pass

Smoke Detector COMPUTER LAB 1 D 133 Pass

Smoke Detector 3RD GRADE HALL 1 D 134 Pass

Heat Detector ELEC RM 3RD GRADE 1 D 135 Pass

Heat Detector MECH RM 3RD GRADE 1 D 136 Pass

Smoke Detector 3RD GRADE HALL 1 D 137 Pass

Smoke Detector DRY STORAGE 1 D 138 No Access

Smoke Detector CAFETERIA 1 D 139 Pass

Duct Detector MECH ROOM 330 1 D 140 Pass

Heat Detector KITCHEN 1 D 141 Pass

Heat Detector KITCHEN 1 D 142 Pass

Heat Detector KITCHEN 1 D 143 Pass

Smoke Detector CAFETERIA 1 D 144 Pass

Smoke Detector CAFETERIA 1 D 145 Pass

Smoke Detector 3RD GRADE HALL 1 D 146 Pass

Smoke Detector 2ND GRADE PASSAGEWAY 1 D 147 Pass

Smoke Detector 2ND GRADE PASSAGEWAY 1 D 148 Pass

Smoke Detector 2ND GRADE PASSAGEWAY 1 D 149 Pass

Heat Detector ELEC RM 2ND GRADE 1 D 150 Pass

Heat Detector 2 GRADE HALL JAN CLOSET 1 D 151 Pass

Smoke Detector 2ND GRADE PASSAGEWAY 1 D 152 Pass

Heat Detector 2 GRADE BLDG MECH ROOM 1 D 153 Pass

Smoke Detector COUNCILOR 2ND GRADE 1 D 154 Pass

Duct Detector KITCHEN 1 D 155 Pass

Duct Detector KITCHEN 1 D 156 Pass

Heat Detector 2 GRADE BLDG MECH ROOM 1 D 157 Pass

Duct Detector ERU 1 RETURN 1 D 158 Pass

Smoke Detector 2ND GRADE PASSAGEWAY 1 D 159 Pass

Smoke Detector 2ND GRADE PASSAGEWAY 1 D 160 Pass

Smoke Detector GYM COURT AREA 1 D 161 Pass

Smoke Detector GYM COURT AREA 1 D 162 Pass

Smoke Detector GYM COURT AREA 1 D 163 Pass

Smoke Detector GYM COURT AREA 1 D 164 Pass

Smoke Detector GYM COURT AREA 1 D 165 Pass

Smoke Detector GYM COURT AREA 1 D 166 Pass

Heat Detector GYM STORAGE 1 D 167 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 513: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Heat Detector GYM COAT RM 1 D 168 Pass

Heat Detector GYM JANITOR CLOSET 1 D 169 Pass

Duct Detector GYM 1 D 170 Pass

Smoke Detector SPECIAL ED RM 157 1 D 171 Pass

Smoke Detector 3RD GRADE PASSAGEWAY 1 D 172 Pass

Smoke Detector 3RD GRADE PASSAGEWAY 1 D 173 Pass

Smoke Detector 3RD GRADE PASSAGEWAY 1 D 174 Pass

Heat Detector JANITOR CLOSET 202 1 D 175 Pass

Heat Detector DETECTOR 176 1 D 176 Pass

Smoke Detector STORAGE 216 1 D 177 Pass

Duct Detector MECH RM 241 1 D 178 Pass

Heat Detector MECH RM 214 1 D 179 Pass

Heat Detector MECH 214 1 D 180 Pass

Duct Detector MECH RM 241 1 D 181 Pass

Smoke Detector 3RD GRADE HALL 1 D 182 Pass

Smoke Detector 3RD GRADE HALL 1 D 183 Pass

Heat Detector RM 219 1 D 184 Pass

Heat Detector TEACHERS LOUNGE 1 D 185 Pass

Heat Detector 4 GRD CLOSET 220 1 D 186 Pass

Heat Detector 4 GRD CLOSET 225 1 D 187 Pass

Smoke Detector 4TH GRADE HALL 1 D 188 Pass

Heat Detector RM 231 1 D 189 Pass

Smoke Detector 210 CORRIDOR 1 D 190 Pass

Heat Detector RM 230 1 D 191 Pass

Heat Detector RM 237 1 D 192 Pass

Heat Detector RM 236 1 D 193 Pass

Duct Detector ERU 2 SUPPLY 1 D 194 Pass

Smoke Detector 5TH GRADE HALL 1 D 195 Pass

Smoke Detector 5TH GRADE HALL 1 D 196 Pass

Duct Detector ERU 2 RETURN 1 D 197 Pass

Smoke Detector SMOKE DOORS CORRIDOR 100 1 D 198 Pass

Smoke Detector SMOKE DOORS CORRIDOR 100 1 D 199 Pass

Smoke Detector OFFICE WORK RM 1 D 201 Pass

Heat Detector VAULT 1 D 202 Pass

Smoke Detector PRINCIPALS OFFICE 1 D 203 Pass

Smoke Detector OFFICE 108 CORR 1 D 204 Pass

Heat Detector OFFICE LOUNGE 1 D 205 Pass

Smoke Detector CLINIC 1 D 206 Pass

Heat Detector ELECTRICAL RM 117 1 D 207 Pass

Smoke Detector TECH OFFICE RM 112 1 D 208 Pass

Smoke Detector OFFICE CORR 1 D 209 Pass

Duct Detector 108 CORRIDOR 1 D 211 Pass

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 514: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 515: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 516: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Job #

Date

Name

Address

City State Zip

Fire Control Panel Inspection

Manufacturer

Panel Location

Account #

Total

Devices

Number of

Devices Failed

1 0

1 0

3 0

2 0

5 0

2 0

Inspector Name : Signature: David Piorkowski

Pass

Pullstations

Smoke Detectors 5193SD

Power Patrol

VISTA-128FBPControl Panel

Pass

Device

Honeywell

Interface Equipment

David Piorkowski

Fire-Lite

Ground fault

All- Star Fire LLC

Model

Device Summary

Manufacturer

TBD EMC SecurityMonitoring Company

Loss of Secondary Power (Batteries/Generator) is Detected

3284 Medlock Bridge Rd Suite 300

Norcross, GA 30092

Interfaced Equipment Tested for Circuit Supervision Pass

Pass

Panel Power Loss

Are Lamps and Displays Operating Properly

Who Was Notified Prior to the Start of Testing

(678) 691-0011

460 McFarland Road

30004

Honeywell

Upstairs MDF Room

Model Name

Alpharetta GA

Is the Panel Monitored Yes

VISTA-128FBP

EI1273 / WO # 156069

6/30/2020

Maintenance Shop (South)

Heat Detectors Honeywell BK-5601P

Fire-Lite

Honeywell

Power Supplies

BG-12

FCPS-24S8

Monitoring Company & Maintenance Staff

Batteries SEC1075

Open Circuits are Detected by Fire Alarm Control Panel

Pass

PassLoss of AC is Detected by the Fire Alarm Control Panel

Ground Faults Detected by Control Panel

Was the Panel Free of Troubles and in Normal Operating Condition Upon Arrival Pass

Panel Secondary power loss

Open Circuit Detection

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 517: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

N/A

Pass

Y

Pass

Pass

N/A

N/A

N/A

Condition Voltage Load Test

Good (2017) 13.5 Pass

Good (2017) 13.7 Pass

Good (2017) 13.7 Pass

N/A

N/A

N/A

N/A

Fire Pump Controller Troubles Report to Panel N/A

Phase Reversal on Pump Controller Reports to Panel N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Fire Pump Trouble

Fire Pump Phase Reversal

Notification Devices

Voice Evacuation Does the Voice Evacuation Work Properly and is it Intelligible

NAC Circuits Are the Notification Appliance Circuits Monitored for Integrity

Circuit Style

Strobes Each Strobe Operates Properly

Each Device Operates Properly

What Style are the Notification Circuits

BPS #1 (Right)

BPS #1 (Left) 12V 7A

12V 7A

Kitchen Hoods

Location Size

Emergency Communications Equipment

Phone Sets

Phone Jacks

Amplifiers/Tone Generators Correct Switching and Operation Verified

Visually Inspected and Operation Verified

Battery Testing

Each Phone Set Activated and Operation Verified

Maglock Release

Elevator Recall

HVAC Shutdown

Stairwell Pressurization

Fire Pump Running

Magnetic Door Holders

Generator In Auto

Generator Trouble

Interface Equipment

Fire Alarm Properly Recall Elevators

Fire Alarm Release Maglocks

Generator Signals Report to Panel

Are stairwell Pressurization Fans Activated by Fire Alarm

Fire Alarm Properly Shutdown HVAC Units

Speakers/Horns

FM-200 / Preaction Systems

Kitchen Hood Suppression System Report Correctly

FM-200/Preaction Systems Report Correctly

12V 18AH

Fire Pump Power Loss

Building Temp Temperature Switch Reports to Panel When Activated

Water Level/Water Temp Sensors Report Correctly

Power Loss on Fire Pump Reports to Panel

Fire Pump Running Reports to Panel

Supervisory Signals

Site Water Level /Temp

FACP

Generator Trouble Reports to Panel

Fire Alarm Release Magnetic Door Holders

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 518: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Device Type Location Floor Zone Results

Pull Station Side Entry 1 10 Pass

Smoke Detector Office 1 1 11 Pass

Smoke Detector Office 2 1 12 Pass

Smoke Detector Plans Room 1 13 Pass

Smoke Detector Break Room 1 14 Pass

Heat Detector Warehouse 1 15 Pass

Heat Detector Warehouse 1 15 Pass

Pull Station Shop Entry 1 16 Pass

Smoke Detector MDF Room 2 17 Pass

Initiating Device Testing

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 519: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Deficiencies

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011

Page 520: Annual Fire Alarm Inspection - forsyth.k12.ga.us...Smoke Detectors 4098-9714 Interstate Control Panel 4100U Pass Device Simplex Interface Equipment David Piorkowski Simplex Simplex

Annual Fire Alarm Inspection

Recommendations

None.

All-Star Fire, LLC

3284 Medlock Bridge Rd, Suite 300, Norcross, GA 30092 (678) 691-0011