BuildingEnvelope ® Table of Contents 1-866-Oldcastle (653-2278) - www.obe.com 1-866-OLDCASTLE (653-2278) www.obe.com 00-FG-3000-TOC September 2018 Elev-Fg3000-CenterSet H0601-Horiz-OutsideGlz H0602-Head-OutsideGlz H0603-Sill-OutsideGlz-10psf H0604-Sill-OutsideGlz H0605-Sill-OutsideGlz-Option H0606-Stacked-Horiz-OutsideGlz H0607-Stacked-Head-OutsideGlz H0608-Stacked-Sill-OutsideGlz H0611-Head-w-1Pc-Receptor H0612-Head-w-2Pc-Receptor H0614-Horiz-InsideGlz H0615-Head-InsideGlz H0616-Sill-InsideGlz H0619-Horiz-w-OpWin H0641-Horiz-Sdlt-Base H0643-Sill-Sdlt-Base H0648-Glass-Options H0650-Subsill-Splice V0601-Jamb-Standard V0602-Jamb-Option V0603-Vertical-Stacked V0604-Vertical-Standard V0605-Vertical-Heavy V0606-Vertical-ScrSpln V0607-Expansion-Vertical V0608-Adjustable-Vertical V0609-Vertical-w-Steel V0610-135-Outside-Corner V0611-90-Outside-Corner V0612-90-Inside-Corner V0614-135-Inside-Corner V0615-180-Post V0616-3-Way-Corner V0617-4-Way-Corner FG-3000 STOREFRONT 2" X 4-1/2" / 1" GLAZING

Upload: others

Post on 12-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

BuildingEnvelope®

Table of Contents

1-866-Oldcastle (653-2278) - www.obe.com

1-866-OLDCASTLE (653-2278) www.obe.com00-FG-3000-TOC

September 2018

Elev-Fg3000-CenterSet

H0601-Horiz-OutsideGlz

H0602-Head-OutsideGlz

H0603-Sill-OutsideGlz-10psf

H0604-Sill-OutsideGlz

H0605-Sill-OutsideGlz-Option

H0606-Stacked-Horiz-OutsideGlz

H0607-Stacked-Head-OutsideGlz

H0608-Stacked-Sill-OutsideGlz

H0611-Head-w-1Pc-Receptor

H0612-Head-w-2Pc-Receptor

H0614-Horiz-InsideGlz

H0615-Head-InsideGlz

H0616-Sill-InsideGlz

H0619-Horiz-w-OpWin

H0641-Horiz-Sdlt-Base

H0643-Sill-Sdlt-Base

H0648-Glass-Options

H0650-Subsill-Splice

V0601-Jamb-Standard

V0602-Jamb-Option

V0603-Vertical-Stacked

V0604-Vertical-Standard

V0605-Vertical-Heavy

V0606-Vertical-ScrSpln

V0607-Expansion-Vertical

V0608-Adjustable-Vertical

V0609-Vertical-w-Steel

V0610-135-Outside-Corner

V0611-90-Outside-Corner

V0612-90-Inside-Corner

V0614-135-Inside-Corner

V0615-180-Post

V0616-3-Way-Corner

V0617-4-Way-Corner

FG-3000 STOREFRONT

2" X 4-1/2" / 1" GLAZING

Page 2: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 Flush Glaze Center Set Storefront

2" x 4-1/2" w/ 1" Glazing - Elevation

Elev-Fg3000-CenterSetSeptember 2018

180 DEG POST

V0615

V0611

135 OSC

V0602

V0612

135 ISC

V0606

V0605

H0611 H0612

HEAD RECEPTOR

V0616

3-WAY

CORNER POST

H0604

H0601

H0602

V0607

V0608

V0604

OUTSIDE GLAZED

V0614

V0610

90 ISC

90 OSC

V0601

H0648

GLASS OPTIONS

OPTIONAL DETAILS

H0619

OPERABLE WINDOW

H0608

H0606

H0607

V0603

STACK ASSEMBLY

V0601

H0616

H0614

H0615

V0604

INSIDE GLAZED

V0601

H0641

H0643

V0609

H0650

SPLICE & END DAMS

H0603

H0605

Page 3: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Intermediate Horizontal - H0601

H0601-Horiz-OutsideGlzSeptember 2018

FG-3144

GLASS STOP

1"

GLAZING

FG-1133

TYP.

AC-119-1 SHEAR BLOCK

@ TUBULAR MULLIONS

FG-3142

HORIZONTAL

FG-1000-FP-2 WATER DIVERTER

SET IN SEALANT

2"

D.L.O

.D

.L.O

.

4 1/2"

FG-3146 SETTING BLOCK

(2) PER D.L.O.

Page 4: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Head Horizontal - H0602

H0602-Head-Hrz-Outside-GlzSeptember 2018

SHIM, BACKER

ROD & SEALANT

(BY OTHERS)

FG-2122 ALUM. FILLER

4" LONG AT ANCHORS,

FG-2188 VINYL FILLER / CAULK

SUPPORT RUNS BETWEEN

ALUM. FILLER (OPTIONAL)

ANCHOR BOLT @

CENTER LINE

(BY OTHERS)

AC-108-1 SHEAR BLOCK

@ TUBULAR MULLIONS

FG-3103

HEAD

FG-1133

TYP.

1"

GLAZING

2"

D.L.O

.

4 1/2"

Page 5: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Sill Horizontal - H0603

H0603-Sill-OutsideGlz-10psfSeptember 2018

FG-1133

TYP.

CONT. SEAL

(BY OTHERS)

FG-2169 10 P.S.F.

SILL FLASHING

COSMETIC SEAL

(OPTIONAL)

AC-119-1

SHEAR BLOCK

@ TUBULAR

MULLIONS

FG-2000-FP-3

SILL ANCHOR

1"

GLAZING

FG-3146 SETTING BLOCK

(2) PER D.L.O.

FG-3144 GLASS STOP

SEAL @ MULLION

FG-3161 SILL

ANCHOR BOLT CAP SEALED

(BY OTHERS)

CONT. SEAL EXCEPT 1/2" TO

3/4" WEEP @ CENTERLINE

OF MULLIONS

2"

D.L.O

.

4 1/2"

Page 6: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Sill Horizontal - H0604

H0604-Sill-OutsideGlzSeptember 2018

FG-1133

TYP.

CONT. SEAL

(BY OTHERS)

FG-2260 SILL

FLASHING

COSMETIC SEAL

(OPTIONAL)

AC-119-1

SHEAR BLOCK

@ TUBULAR

MULLIONS

FG-2000-FP-3

SILL ANCHOR

1"

GLAZING

FG-3146 SETTING BLOCK

(2) PER D.L.O.

FG-3144 GLASS STOP

SEAL @ MULLION

FG-3161 SILL

ANCHOR BOLT CAP SEALED

(BY OTHERS)

CONT. SEAL EXCEPT 1/2" TO

3/4" WEEP @ CENTERLINE

OF MULLIONS

2"

D.L.O

.

4 1/2"

Page 7: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Sill Horizontal - H0605

H0605-Sill-OutsideGlz-OptionSeptember 2018

FG-1133 TYP.

FG-3161 SILL

AC-119-1 SHEAR BLOCK

@ TUBULAR MULLIONS

CONT. SEAL

(BY OTHERS)

FG-2246 SILL

FLASHING

FG-3000-FP-78

END DAM

ATTACH TO SILL

FLASHING W/ (2)

FS-320 U-DRIVE

COSMETIC SEAL

(OPTIONAL)

FG-3146 SETTING BLOCK

(2) PER D.L.O.

FG-3144 GLASS STOP

SEAL @ MULLION

CONT. SEAL

1/4" WEEP @

MID-LITES

SHIM, BACKER

ROD & SEALANT

(BY OTHERS)

ANCHOR BOLT

CAP SEALED

(BY OTHERS)

1" GLAZING

Page 8: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Intermediate Horizontal - H0606

H0606-Stacked-Horiz-OutsideGlzSeptember 2018

FG-1133

TYP.

AC-122-1 SHEAR BLOCK

@ TUBULAR MULLIONS

FG-3164 FILLER

1"

GLAZING

FG-3146 SETTING BLOCK

(2) PER D.L.O.

SEAL INSIDE HORIZ.

BETWEEN MULL. &

HORIZONTAL

SEAL BETWEEN SHEAR

BLOCK & HORIZONTAL

FG-1000-FP-2

WATER DIVERTER

SET IN SEALANT

FG-3144 GLASS STOP

SEAL @ MULLION

FG-3192 HORIZONTAL

SEAL @ MULLION

2"

D.L.O

.D

.L.O

.

4 1/2"

Page 9: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Head Horizontal - H0607

H0607-Stacked-Head-Outside-GlzSeptember 2018

FG-3204 HEAD FILLER

FG-3203 HEAD

RECEPTOR

CENTERLINE ANCHOR

BOLT CAP SEALED

(BY OTHERS)

SHIM, BACKER

ROD & SEALANT

(BY OTHERS)

FG-1133

TYP.

1"

GLAZING

SEAL @ HORIZONTAL JOINTS

AND CONTINUOUS SEAL

ALONG EDGE OF FG-3204

(BY OTHERS)

AC-121-1 TWIST-IN ANCHOR

FITS INTO VERTICAL

3/4"

2"

D.L.O

.

4 1/2"

TOP OF

VERTICAL

Page 10: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Sill Horizontal - H0608

H0608-Stacked-Sill-OutsideGlzSeptember 2018

FG-3191 SILL

SEAL @ MULLION

FG-3205 SILL

FLASHING

ANCHOR BOLT

(BY OTHERS)

SHIM, BACKER

ROD & SEALANT

(BY OTHERS)

FG-1133

TYP.

1" GLAZING

FG-3144 GLASS STOP

SEAL @ MULLION

1/4" WEEP @ MID-LITE

CONT. SEAL

(BY OTHERS)

FG-3146 SETTING BLOCK

(2) PER D.L.O.

1/2"

2"

D.L.O

.4 1/2"

Page 11: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Head Horizontal - H0611

H0611-Head-w-1pc-ReceptorSeptember 2018

FG-2139 HEAD

RECEPTOR W/

V-11 GASKETS

FG-3103 HEAD

SHIM, BACKER

ROD & SEALANT

(BY OTHERS)

CENTERLINE

ANCHOR BOLT

(BY OTHERS)

AC-108-1

SHEAR BLOCK

@ TUBULAR

MULLIONS

FG-1133

TYP.

2"

D.L.O

.

4 1/2"

1" GLAZING

Page 12: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Head Horizontal - H0612

H0612-Head-w-2pc-ReceptorSeptember 2018

MO-243 & MO-244

HEAD RECEPTORS

W/ V-11 GASKETS

FG-3103 HEAD

SHIM, BACKER

ROD & SEALANT

(BY OTHERS)

CENTERLINE

ANCHOR BOLT

(BY OTHERS)

AC-108-1

SHEAR BLOCK

@ TUBULAR

MULLIONS

FG-1133

TYP.

2"

D.L.O

.

4 1/2"

1" GLAZING

Page 13: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Intermediate Horizontal - H0614

H0614-Horiz-InsideGlzSeptember 2018

FG-3210 GLASS STOP

FG-3142

HORIZONTAL

1" GLAZING ON HP-17

SETTING BLOCK

FG-1133

TYP.

AC-119-1 SHEAR BLOCK

@ TUBULAR MULLIONS

FG-1000-FP-2

WATER DIVERTER

SET IN SEALANT

2"

D.L.O

.D

.L.O

.

4 1/2"

Page 14: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Head Horizontal - H0615

H0615-Head-InsideGlzSeptember 2018

SHIM, BACKER

ROD & SEALANT

(BY OTHERS)

CENTERLINE ANCHOR BOLT

(BY OTHERS)

FG-3210

GLASS STOP

ACCESS

HOLE

FG-3161 HEAD

AC-119-1

SHEAR BLOCK

@ TUBULAR

MULLIONS

1"

GLAZING

FG-2122 ALUM. FILLER

4" LONG AT ANCHORS, RUN

FG-2188 VINYL FILLER BETWEEN

FOR CAULK SUPPORT (OPTIONAL)

2"

D.L.O

.

4 1/2"

FG-1133

TYP.

Page 15: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Sill Horizontal - H0616

H0616-Sill-InsideGlzSeptember 2018

FG-2246 SILL

FLASHING

CONT. SEAL

(BY OTHERS)

FG-3103 SILL

SHIM, BACKER

ROD & SEALANT

(BY OTHERS)

1/4" WEEP

@ MID-LITE

CENTER LINE ANCHOR BOLT

(BY OTHERS)

2"

1/2"

D.L.O

.

4 1/2"

1" GLAZING ON FG-3220

SETTING BLOCK

FG-1133 TYP.

Page 16: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Horizontal at Operable Window - H0619

H0619-Horiz-w-OpWinSeptember 2018

FG-3144

GLASS STOP

1"

GLAZING

FG-1133

TYP.

AC-119-1 SHEAR BLOCK

@ TUBULAR MULLIONS

FG-3142

HORIZONTAL

2"

D.L.O

.

4 1/2"

FG-3146 SETTING BLOCK

(2) PER D.L.O.

FG-3126 POCKET FILLER

ZERO SIGHTLINE TYPE

OPERABLE WINDOW (GO TO

WWW.OBE.COM/PRODUCTS/

ARCHITECTURAL-WINDOWS

FOR THE MOST CURRENT

DETAILS AND VENT OPTIONS)

Page 17: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Sidelite Base Horizontal - H0641

H0641-Horiz-Sdlt-BaseSeptember 2018

FG-3144 (BOTH SIDES)

SEAL @ MULLION

(BY OTHERS)

FG-1133

TYP.

1" GLAZING

FG-1000-FP-2

WATER DIVERTER

SET IN SEALANT

FG2000-FP-10 SHEAR BLOCK

@ TUBULAR MULLIONS

FG-3146 SETTING BLOCK

(2) PER D.L.O.

FG-2141 SIDELITE

BASE/HORIZONTAL

CONT. SEAL

FG-3102 FILLER

CONT. SEAL

(BY OTHERS)

4 1

3/1

6"

4 1/2"

Page 18: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Sidelite Base Sill - H0643

H0643-Sill-Sdlt-BaseSeptember 2018

FG-3144 (BOTH SIDES)

SEAL @ MULLION

(BY OTHERS)

FG-1133

TYP.

FG-3146 SETTING BLOCK

(2) PER D.L.O.

FG-2141 SIDELITE

BASE/HORIZONTAL

CONT. SEAL

(BY OTHERS)

4 1

3/1

6"

ACCESS

HOLE

FG-2000-FP-3

SILL ANCHOR

CONT. SEAL EXCEPT FOR 1/2" - 3/4"

SPACE UNDER MULL FOR WEEPS

(BY OTHERS)

ANCHOR BOLT

CAP SEALED

(BY OTHERS)

CONT. SEAL

(BY OTHERS)

FG-2169 10 P.S.F.

SILL FLASHING

OPTIONAL COSMETIC

SEAL

4 1/2"

1" GLAZING

1/2

"

FG2000-FP-10 SHEAR BLOCK

@ TUBULAR MULLIONS

Page 19: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Glass Options - H0648

H0648-Glass-OptionsSeptember 2018

1/4" GLASS 5/16" GLASS 3/8" GLASS 7/16" GLASS

11/16" GLASS5/8" GLASS9/16" GLASS1/2" GLASS

3/4" GLASS

FG-3194

FG-1133

FG-1133

FG-3236

FG-5125

FG-5125

FG-3236

FG-5125

FG-1133

FG-3236

FG-1133

FG-1133

FG-3237

FG-5125

FG-5125

FG-3237

FG-5125

FG-1133

FG-3237

FG-1133

FG-1133

FG-3237

FG-1133

FG-1134

FG-3237

FG-1134

FG-1134

FG-5125

FG-5125

7/8" GLASS

FG-5125

FG-1133

15/16" GLASS 1" GLASS

FG-1133

FG-1133

1-1/16" GLASS

FG-1134

FG-1133

1-1/8" GLASS

FG-1134

FG-1134

Page 20: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Sub Sill Splice & End Dam - H0650

H0650-SubSill-Splice-EndDamSeptember 2018

Note: Ref installation manual for additional splice & end dam info.

FG-2000-FP-7

FG-3217

FG-2000-FP-4

End Dam

Splice

FG-2169

FG-3000-FP-11

FG-3000-FP-4

Splice Package

FG-3000-FP-78

ATTACH TO SUB SILL

W/ (2) FS-320 U-DRIVE

FG-2246

FG-2000-FP-18

Page 21: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Jamb Vertical - V0601

V0601-Jamb-StandardSeptember 2018

FG-3100 JAMB

FS-8 (#14 X 1" HH SLOTTED)

ASS'Y SCREW (TYP.)

FG-1133 TYP.

1" GLAZING

SHIM, BACKER

ROD & SEALANT

(BY OTHERS)

CENTERLINE ANCHOR

BOLT, CAP SEALED

(BY OTHERS)

ACCESS HOLE

FG-2122 ALUM. FILLER

4" LONG @ ANCHORS, RUN

FG-2188 VINYL FILLER BETWEEN

2" D.L.O.

4 1/2"

Page 22: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Jamb Vertical - V0602

V0602-Jamb-ScrSplnSeptember 2018

FG-3103 JAMB

FS-8 (#14 X 1" HH SLOTTED)

ASS'Y SCREW (TYP.)

FG-1133 TYP.

1" GLAZING

SHIM, BACKER

ROD & SEALANT

(BY OTHERS)

CENTERLINE ANCHOR

BOLT, CAP SEALED

(BY OTHERS)

ACCESS HOLE

FG-2122 ALUM. FILLER

4" LONG @ ANCHORS, RUN

FG-2188 VINYL FILLER BETWEEN

2" D.L.O.

4 1/2"

Page 23: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Intermediate Vertical - V0603

V0603-Vertical-StackedSeptember 2018

NOTE: HORIZONTALS ATTACHED

W/ SHEAR BLOCKS

FG-3107 MULLION

FG-1133 TYP.

1" GLAZING

2"

4 1/2"

Page 24: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Intermediate Vertical - V0604

V0604-Vertical-StandardSeptember 2018

FG-3100 MULLION

FG-1133 TYP.

FG-3102 FILLER

1" GLAZING

FS-8 (#14 X 1" HH SLOTTED)

ASS'Y SCREW TYP.

2"

4 1/2"

Page 25: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Intermediate Vertical - Heavy - V0605

V0605-Vertical-HeavySeptember 2018

FG-3101 MULLION

FG-1133 TYP.

FG-3102 FILLER

1" GLAZING

FS-8 (#14 X 1" HH SLOTTED)

ASS'Y SCREW TYP.

2"

4 1/2"

Page 26: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Intermediate Vertical - V0606

V0606-Vertical-ScrSplnSeptember 2018

FG-3103 MULLION

FG-1133 TYP.

FG-3102 FILLER

1" GLAZING

FS-8 (#14 X 1" HH SLOTTED)

ASS'Y SCREW TYP.

2"

4 1/2"

Page 27: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Expansion Vertical - V0607

V0607-Expansion-VerticalSeptember 2018

V-11

GASKET

FG-3108 FG-3109

FS-8 (#14 X 1" HH SLOTTED)

ASS'Y SCREW TYP.

FG-1133 TYP.

1" GLAZING

4 1/2"

2"

Page 28: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Adjustable Vertical 2° to 12° - V0608

V0608-Adjustable-VerticalSeptember 2018

FG-3180 FG-3181

FS-8 (#14 X 1" HH SLOTTED)

ASS'Y SCREW TYP.

FG-1133 TYP.

1" GLAZING

4 1/2"

Page 29: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

Vertical w/ Steel - V0609

V0609-Vertical-w-SteelSeptember 2018

FG-3135 MULLION

FG-3164 FILLER

FG-1133 TYP.

1" GLAZING

FS-8 (#14 X 1" HH

SLOTTED) ASS'Y

SCREW TYP.

RS-1 REINF. STEEL

DETERMINED BY

STRUCTURAL

REQUIREMENTS

NOTE: THIS MULLION UTILIZES A

NON-STANDARD GLASS BITE OF

3/8". GLASS SIZE FOR WIDTH IS

THEREFORE D.L.O. + 3/4".

4 1/2"

2"

Page 30: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

135° Outside Corner - V0610

V0610-135-Outside-CornerSeptember 2018

FG-3141 FILLER

(BOTH SIDES)

FG-1133

TYP.

1" GLAZING

FG-2138

MULLION

FS-8 (#14 X 1" HH

SLOTTED) ASS'Y

SCREW TYP.

2 3/8"

4 1/2"

Page 31: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

90° Outside Corner - V0611

V0611-90-Outside-CornerSeptember 2018

ACCESS

HOLE

FG-1133 TYP.

FG-3111

FG-3110

1"

GLAZING

FS-8 (#14 X 1" HH

SLOTTED) ASS'Y

SCREW TYP.

4 1/2"

4 1/2"

Page 32: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

90° Inside Corner - V0612

V0612-90-Inside-CornerSeptember 2018

ACCESS

HOLE

FG-1133 TYP.

FG-3111

FG-3110

1"

GLAZING

FS-8 (#14 X 1" HH

SLOTTED) ASS'Y

SCREW TYP.

4 1/2"

4 1/2"

Page 33: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

135° Inside Corner - V0614

V0614-135-Inside-CornerSeptember 2018

FG-3141 FILLER

(BOTH SIDES)

FG-1133

TYP.

1" GLAZING

FG-2138

MULLION

FS-8 (#14 X 1" HH

SLOTTED) ASS'Y

SCREW TYP.

2 3/8"

4 1/2"

1/2"

Page 34: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

180° Post - V0615

V0615-180-PostSeptember 2018

FG-3110

FG-3110

FG-1133 TYP.

1" GLAZING

FS-8 (#14 X 1" HH

SLOTTED) ASS'Y

SCREW TYP.

4 1/2"

4 1/2"

Page 35: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

3-Way-Corner - V0616

V0616-3-Way-CornerSeptember 2018

ACCESS

HOLE

FG-3111

FG-3201 CORNER MULLION

REQUIRES SHEAR BLOCKS FOR

HORIZONTAL ATTACHMENT

FG-1133 TYP.

1" GLAZING

FS-8 (#14 X 1" HH

SLOTTED) ASS'Y

SCREW TYP.

4 1/2"

4 1/2"

Page 36: BuildingEnvelope - OBE · 2019-07-16 · 1-866-OLDCASTLE (653-2278) FG-3000 - Storefront Intermediate Horizontal - H0601 September 2018 H0601-Horiz-OutsideGlz FG-3144 GLASS STOP 1"

1-866-OLDCASTLE (653-2278) www.obe.com

FG-3000 - Storefront

4-Way Corner - V0617

V0617-4-Way-CornerSeptember 2018

FG-3201

FG-3201

FG-1133 TYP.

1" GLAZING

NOTE: FG-3201

REQUIRES SHEAR

BLOCKS FOR

HORIZ. ATTACH-

MENT

4 1/2"