case study 31 - asia power quality initiativecase study 31 6 / 21 case study of ht reactor failure-...
TRANSCRIPT
Case Study 31
1 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
Case Study 31
Case Study of HT Reactor failure- A Resonance
Phenomenon in 11KV Water Pumping Station
Abstract
A booster pumping station (BPS) in South India with high power HT pumping motors reported
sudden failures due to flashover of the current limiting reactors of the PF correction capacitor
circuit. The pumping circuit has its own power factor correction capacitor circuits. The failures were
reported repeatedly over three/ four days during December 2009. Extensive re-look on design
aspects and simulations studies pointed out no major design issues. Finally it was concluded that the
failures were due to the inherent design and workmanship limitations of the reactors itself to handle
transient over currents during switching. To find out the specific reasons for such failures (which
happened after three to four years’ of working), it was decided to undertake power quality studies.
The longer duration period of logging at identified points it was noted that at a certain random
periods , the voltage and current total harmonic distortions increases abnormally high. It was also
noted that the predominant in harmonic content. Detailed investigations provided the reason for
such random failures due to harmonic environment that too occurring at random intervals. This has
lead to shunt resonance situation for the LC circuit resulting into the failure of the reactor. Larger
sized current limiting reactors were found to be the best and economical solution in this case.
Background
The past six decades have witnessed phenomenal growth of urban population in India. At least 10
million people are being migrating to it each year. The services of municipal bodies and also utility
companies cover most basic needs like drinking water, street lighting, garbage handling, drainage and
sewage system etc.
Supplying potable quality piped drinking water to huge population has been one of the primary tasks
of the water utilities. Thus the reliable operation of the pumping station for 24x7 days has been the
top most priority for these water installations. There has been continuous attempt to follow the
“Best operating practices” at these places, though the money availability may not be adequate in
some cases.
Case Study 31
2 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
The basic equipment design takes care of the pump motor requirements including the requirement
of providing reactive power compensation at different station loads. However the reliability aspect of
such large equipment, the design itself should ensure adequacy of uninterrupted operation under
different conditions. It should also take care of unpredictable and / or peculiar failures of equipment
taking place all of a sudden, leading to disruption of the service. One of the major reasons for such
unpredictable failures in electrical systems could be due to the quality of the power supply and hence
enhanced awareness for the end users is essential. The power supply with harmonics could result in
a peculiar type of failures. It is always a challenging task to exactly pin point the reasons for such
failures as it requires special analysis of the equipment/system utilizing the advanced
technique/knowledge. The case study presented here highlights the necessity of visualizing such
problems at design stage itself as the equipment have to work under poorer power quality
environment. Only systematic Power and power quality study would help in identifying the reasons
for such unexpected and sudden failures and the best possible solution.
Demonstration Site
One of the southern India based water pumping installation has large water handling capacity of
180Million litres per day. This booster station has 3 numbers of 90 MLD capacity pumps, each one
being driven by 1800KW capacity motor at 11KV. A Fluid coupling box arrangement is made use for
speed reduction arrangement between motor and the pump .Normally, one pump operates
continuously but the second pump is also brought into operation few times in a week, based on the
consumer water supply requirements. The third pump is kept on standby. All the three pumps are
utilised in a planned schedule.
Details of Power/Distribution system at Booster station
The 11KV power supply is provided from a dedicated 110kV sub-station where there are 2x10MVA,
110/11KV power transformers. For enhancing the reliability of the power supply, the pumping station
has two 11KV feeders. The power supply arrangement is complete with two pole structures, main HT
panel, distribution panels with vacuum breakers and FCMA type starter panel (rotor side reactors
whose value is controlled to exhibit large value of impedance during staring to limit the starting
current and which subsequently gets saturated and exhibits low impedance when running) for
each of 11KV, 1800 kW slip ring induction motors. Each motor panel has its own power factor
correction HT capacitors’ bank of 500 KVAR, to improve the power factor from 0.88 to 0.98,along
with series connected current limiting iron core reactors.
Case Study 31
3 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
The reactors have been provided to achieve the required current limiting in the capacitor circuit
during motor starting and at the same time have reduced power loss. Normally the standard
recommended value of the series reactor for such requirements is 5% of the capacitor value.
However the reactor provided in the present case was only 0.2 % at the design stage possibly to
reduce the dimensions as well as the cost of the current limiting reactor. [Detailed as figure #1]
The design with the reduced reactor value had also worked for nearly three / four years before the
multiple failure of these reactors had taken place over couple of days in December 2009when the
second pump was getting started.
This case study is related to the analysis of this failure undertaken by the utility company,their
suppliers and finally (from May 2010) by the faculty of a leading institution. The original premise with
which the fault analysis was conducted, was to look for a possible reason for over voltage causing a
flash over and the resultant over current.
The electro-magnetic transient ( E M T )analysis conducted as part of the present case study
indicated that the selection of 0.2 % reactor would also serve the original purpose of limiting the
current through the PF capacitors during starting provided adequate design requirements to handle
larger transient currents during the short starting times are taken care of assuming that the input
supply is sinusoidal .It is to be mentioned that the starting requirements happen once in a while.
However when connected to a power system with harmonic voltages, the series filter circuit (
made up of a 0.2% reactor and 500 kVAR capacitor bank)could resonate at its tuned frequency,
which unfortunately, in the present case, happened to be one of the predominant harmonic
voltages ( 13th harmonic voltage )getting injected into the system at totally random times (not
always) from an external source connected to the grid.
The peculiarity of the present case was that, in the utility pumping station under consideration,there
is no non- linear load and hence the possibility of getting affected by power quality issue was not
considered at all. Also , as it was subsequently seen , the power quality problem comes as a
disturbance over certain durations( it is not present always )and hence was not identified until the
long time recording of parameters was conducted.
The station has also 2 x200KVA capacity auxiliary transformers of 200KVA rating for power supply to
other station LT loads.
Case Study 31
4 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
While, HT panel incomer is provided with Earth fault, over current and under voltage protections
each of the HT motor panels are with MRO (motor protection) relay for comprehensive protection to
the motors.
A typical wiring diagram of motor panel is illustrated below in Figure1
Figure 1: Wiring diagram for motor circuit
PQ issues at pumping installation
During December 2009, the water pumping installation had reported a series of failure of the current
limiting series reactors in the P.F correcting capacitor panel of motor, affecting severely their two
pump mode operation requirements. This was stated to be four times within a short span of four
days. The failure was observed only when the second pump was put into operation in parallel to the
already running first pump motor. The water utility had to organize urgent replacement/rewinding of
reactors and the replacements were used in the circuit after heating the same in oven. The failures
had also taken place randomly in any one of the phases but majority of the failures were in the
Case Study 31
5 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
second motor set capacitor current limiting reactors and also once of the first running motor’s
power factor capacitor reactor.
Further, during last event of failure,there was transformer tripping with Buchholz relay operation,
requiring removal of the transformer from site andfurther investigation and repairsat the
transformer manufacturer’s factory.
The photographs of the failed HT reactors and the incoming transformer are given as under :
Figure #2 HT Reactor ( 0.2% ) in series with PF capacitor Failure
Figure #3 Damaged10 MVA input Transformer under repair in the Factory
The physical inspection /photographs of the earlier failed reactors ( 4sets ) and the main input
transformer revealed the following:
a) Badly charred reactor indicated the flow path of a large quantity of current.
b) Minor inter-turn flashovers are observed for other three cases
c) Severe movement of LT coils alongwith their anchoring clamping /bolting arrangement indicated
the passage of heavy current on the secondary of the transformer.
After this fault the utility continued the operation with P.F correction for one pump motor only and
whenever the second pumping unit is brought into operation, the same was without the P F
correction unit.
Case Study 31
6 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
The above observations and the description of the faults observed required, a step–by –step study
of the entire system for identification of the possible reason(s) for the failure of these reactors
during two pump operation and then arrive at a solution to overcome the same .
The major studies, in the conventional approach, undertaken as part of the studies were:
Load flow analysis (to determine the equipment adequacy of the existing system).
Short circuit studies and fault level calculation (to determine the adequacy of the fault
rating of the existing system).
Review of the present relay settings (To determine improved recommendations for closer
coordination).
Adequacy of existing earthing and grounding system (for 110 / 11 kV switch yard ) and
finally
EMTP (Electromagnetic transient performance) related switching transient studies (to
determine the over voltages / over currents during the motor starting and capacitor
energisation.)
Preliminary findings
After the initial studies, analysis and findings by the college team , it was indicated to the utility
company during the month of Aug 2010 that the failure of the reactors are most probably due to
their inherent limitations in terms of their specification, design and workmanship to handle the
transient over currents.
This above decision was arrived at after all the other studies and analysis (as indicated above) did not
indicate any other definite and specific problems. The EMT (Electro Magnetic Transient) studies were
also carried out to find out the reason for the failure of the reactors under transient conditions (such
as starting of the motors). This was done for both the conditions -the existing reactor with an
impedance value of 0.2% and also for the normally recommended values (the standard value) of 5%
impedance. The studies only indicated that the transient currents are much larger with 0.2 % reactor
but there was no definite reason for the multiple failures of reactors after they were working for
number of years
Case Study 31
7 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
EMT Simulation studies with the existing 0.2 % Reactor for the PF compensation capacitor
circuit:
Figure-4(a)Transient switching current waveform-Inrush current through first pump reactor - 0.2%
reactor impedance value
Figure-4(b) Transient switching current waveform-Inrush current through second pump reactor -
0.2% reactor impedance value
EMT Simulation studies with the standard 5% Reactor for the PF compensation capacitor
circuit :
Figure-5(a)Transient switching current waveform-Inrush current through first pump reactor - 5%
reactor
Case Study 31
8 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
Figure-5(b)Transient switching current waveform-Inrush current through second pump reactor -
5% reactor impedance value
With 0.2% reactor, the transient currents observed were almost 15 times the rated currents; hence
this aspect must be specified while procuring the new reactors. The old specifications indicated only
the steady state values and not the transient currents which are actually encountered by the
reactors at the installation. Thus it was concluded that the reactors were inadequately specified and
manufactured.
With 5% impedance value, the transient currents for the reactor is found to be well within the
normal switching transient currents generally encountered for such application- about 3/ 4 times
for a short duration..
The above studies (EMT) also indicated that there was no occurrence of significant over voltages
which could cause flash-over during transient conditions.
The other possibility of over voltage considered was the pole discrepancy (of the closing contacts) of
any particular motor side breaker. This was also ruled out, since the failures were taking place
randomly in any of the three breakers which were in operation.
The earthing of the system was also tested (since poor earthing can result in system over voltages
under steady state or under switching modes) and no inadequacy was found.
Based on the above and after the physical inspection of two of the failed reactors it was concluded
that the design and manufacture of these reactors have major shortcomings which can be the
reasons for their failures. The original specification of these reactors received from the client,
considered only the steady state current and apparently the large transient currents experienced
during the starting of the pumps have not been considered.
Case Study 31
9 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
It is also noticed that the core of the reactors have got overheated ; the quality of the core
material also needed review from the point of view of losses and from the point of getting
saturated etc. Hence it was recommended to customer that the specification of the reactor should
consider the above aspects and an appropriate specification of the reactor be arrived at.
Causes for Multiple failures of reactors
After the preliminary report was submitted and discussed , it was decided as a last measure (
before the final report is submitted ) to monitor the various electrical parameters of the incoming
power system on a long time basis to find out the presence of any other random phenomena which
could have caused the problems and affect the system performance. In fact the team was looking
for supply voltage transients (over voltages due to switching of a short duration).
Customer was also looking for a more convincing explanation of the multiple failure of these
reactors all of a sudden and was not fully convinced that the failures were due to only the
inadequacy of the design and manufacturing of the reactors
Hence, a 24 hours continuous and simultaneous power quality monitoring recording was carried out
to record the various electrical parameters. Out of these recorded parameters, only the recordings
of voltage and current THD levels indicated an unexpected phenomenon not considered till then .All
other parameters were found to be of normal value.
The harmonics recording showed increased trend to a significant level during just a particular
interval, out of the total 24 hours . A typical recording of increased Harmonics levels for voltage and
current components on 6/7 September2010 is shown below as Figure6 (a)
It may be noted that the pump has been operating with steady loading for the total period of 24
hours both on 6/7 September and 7/8 October 2010 when the 24 hours long time recordings
were carried out.
Case Study 31
10 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
Figure 6(a) : Voltage and Current harmonics between 11:45 PM to 5:45 AM
This study was repeated again on 7th and 8th October 2010 with further continuous recording to
identify the individual harmonics also on another day after one month. These recordings indicated
significant presence of 13th harmonic components for both voltage and currents occurring at random
intervals.
Figure-6(b) below highlights the presence of high level of 13th level of harmonics for a typical day.
Case Study 31
11 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
The following Figure-6(c ), indicates the further increased values for both voltages and currents
(13th Harmonic) are seen
After this unexpected finding, the site Engineers had also confided the presence of increased reactor
noise during those random intervals, indicating the occurrence of high harmonic current levels.
Subsequently, harmonic analysis / study was conducted of the total electrical system to find its
natural frequency and which can result into series resonance conditions causing transient
amplification of the reactor currents.It was found that for the existing system the series resonance
condition sets in at 12.92 times the supply frequency. This was a startling finding as the major
harmonics which were noticed in the supply system when the power quality disturbance had
taken place was 13th harmonic.
The direct solution to this problem is to provide appropriate de-tuning filter circuit of appropriate
harmonic number and rating. However considering the randomness of the occurrence of the
harmonic voltage, it was recommended to go for shifting the resonance condition– occurrence of
minimum impedance- by modifying the values of the reactor (L) and capacitor(C).
Refer annexures for details of calculations to arrive at the final solution of Reactor designs.
Case Study 31
12 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
[Annexures contain exhibit#1 &2 and table #1 & 2]
The exhibit #1 provides the calculations for the 0.2 % reactor and exhibit #2 provides the
calculation for the 5 % reactor.
The minimum circuit impedance results with 0.2% reactor at 12.92ndharmonic frequency
corresponding to 646 HZ and the same is only 0.0393 Ohms. Considering the 13th harmonic which is
predominant as per measurement, the corresponding impedance is 0.1349 ohms . Also it is seen that
the minimum impedance occurs at the two pump operation due to the paralleling of the
impedances which also explains the failures taking place only at two pump operation.
The table #1 provides the results for 0.2 % reactors considering different values of X/R as well as
for different values for the capacitor bank. With this reactor even assuming smaller values of
X/R – i.e. larger resistance- the circuit impedance is still 0.1584 ohms at 13th harmonic and hence it
is still providing a low impedance path and hence is not safe.
The minimum circuit impedance results with 5% reactor at 2.6th harmonic frequency corresponding
to 130 HZ and the same is 1.279 Ohms even considering the two pump operation. At 13th harmonic,
the corresponding impedance will be even more .
The table #2 provides the result of the calculations with the other values of reactors , 0.5%, 1% and
5%. It is quite clear that with 5% reactor there is little possibility of series resonance.
From the above , it can be derived that at significant levels of 13th harmonic voltages (found to
be appearing randomly as per the recordings carried out), there will be large 13thharmonic reactor
circuit current. The cable reactance at 13th harmonic will however limit the reactor current to safe
values provided the 13th harmonic voltage are within the limits.
It is also seen that the harmonic voltage levels generally exhibit larger values during starting
conditions. Hence under a combined worst situation of starting the second pumpwith supply side
13th harmonic voltages at significant levels, large amplified reactor circuit currents would result .
The above condition, together with the above mentioned shortcomings( in the reactor
specification, design and workmanship), could have caused the failure of the reactors.
The solution considered is to shift the likely resonance condition to a frequency away from the
significant voltage harmonics noted, by adjusting the L and C values of the power factor
Case Study 31
13 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
compensation circuit. Shifting of the resonance frequency to a safe lower frequency value is possible
with increased value of the reactors. Calculations considering typical higher values of reactors at
0.5%, 1% and 5 % indicate shifting of the occurrence of minimum impedance at lower harmonic
values.
The simple and the most inexpensive solution for this sitewas to connect the power factor correction
capacitors in star connection instead of the existing delta connection ( by which the capacitor value is
effectively reduced by a factor of 3) even with the existing 0.2%reactor value. With this condition the
resonant frequency is shifted to a value more than 22, which is away from the present magnification
level of 13th harmonic number; this could be a safe value. But the problem is that the resultant kVAr
available would be less (as per the calculations done) and would result into poorer power factor of
0.92. Hence this was not recommended.
Thus the option to use different values of the reactors keeping the capacitor value the same only was
considered. The Calculations were done for higher values of reactors of 0.5 %, 1%, 5%.
With 0.5 % and 1% reactors, the series resonance conditions do occur but the resonance frequency
is only shifted to 8.2th and 5.6th harmonic numbers respectively. Even though in the actual
harmonic voltages noted (as per the recordings) the 5th, 7th and 9th harmonics are
comparatively low ( as compared to the 13th harmonic ), considering the randomness of the
supply harmonics , the solution of going for smaller values of the inductors may not be completely
fool-proof or safe.
It is seen that with 5% reactor, there is hardly any resonance condition and hence it is quite safe
to operate with this value. It is also seen under EMT ( simulations ) that with 5 % reactor, the
transient switching currents are lower and they are also in the range of the normal over current
capabilities of such current Limiting inductors.
Final Recommendations
It is noted that 5% reactor indicates almost no resonance condition. Thus , it was recommended to
opt for the standard value of the current limiting reactors ( normally recommended values as per
the literature for such current limiting applications ) , i.e. 5% impedance reactors. The rating was
also fixed at the steady state current values of 32A rating, as the reactor needs to withstand only
three times the normal steady state current during switching operation lasting for about 1.2
seconds.
Case Study 31
14 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
With the value of 5% reactor, the maximum inrush current value could be limited at 128 A (about 5
times to nominal current of capacitor). This is much less than the maximum inrush current of 374 A (
about 15 times ) expected to be occurring with the existing value of the reactor ( 0.2 % ) used in
the plant.
Thus this selection of 5% reactor not only limits the transient currents within the safe acceptable
values, and also the possibility of occurrence of resonance condition is also totally eliminated.
Post implementation
The recommended current Limiting reactor specification given to the reactor manufacturer is for
11KV , with 5% rating for Xc for 32A design. The other special requirements of reactor specification
were as follows:
i. The reactor needs to withstand 3 times the normal steady state current during
switching operation which happens occasionally .The switching transients last for about
1.2 seconds.
ii. The core and the windings to be appropriately designed
a. to avoid saturation of the core,
b. needs to withstand the resultant forces during transient currents and
c. to have appropriate insulation class to ensure non-deterioration of the same over its
life period.
iii. Iii A reactor has to be type testedfor switching transient currents.
Simulated Transient switching Current waveforms ( simulated ) with 5% reactor are given below :
Case Study 31
15 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
The Inrush current flowing through the first pump PF circuit series reactor considering 5% series
reactor
The Inrush current flowing through the second pump series reactor considering 5% series reactor
Cost benefit Analysis
Customer has already received offer for the purchase of these 5% reactors. The new reactor with
copper winding costs around Rs. 6.0 lacs(landed cost).The cost of repairs and transportation of
transformer was around Rs.5.00 lacs, while the failed reactor to be replaced cost around Rs. 1.10 lacs.
The simple payback period works out to less than an year. However, if cost of electricity bills due to
reduced consumption, is also considered, the pay back shall work out to 6-8 months, which is quite
attractive. The cost of missed billing of water supply during the shutdown of second pump, is not
considered. This itself was a huge revenue missed by the utility, as there was a demand of 120MLD ,
Case Study 31
16 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
10 days a month, for nearly 9-10 months, at the time of problem and the utility could supply only 90
MLD from one pump.
Current Status
The new reactor has not been as yet implemented as the demand for the water requirement –
feeding a industrial belt – has reduced to nearly 60 / 80 MLD- due to the industry recession- and
hence the customer is able to meet the demand at present, with one pump operating.
Conclusion
A Harmonic resonance condition may occur in the power factor correction capacitors and its current
limiting reactors for a large motor system. This interaction may lead to considerable magnification of
harmonic currents and voltages, causing disruption of the equipment operation. The predominant
harmonic frequencies normally fall in the vicinity of the 5th to the 13th harmonics. Care has to be
taken to ensure that the selected values of the PF capacitor and the reactor do not resonate at
these normal harmonic voltages. Detailed study of the impact of harmonics in this circuit, as has been
done in the present case, would help to properly design this apparently simple LC circuit
About the authors and institution
Authors : Prof.K.Narayanan
Dr.R.Meenakumari
Ms. A. Sheela
Company : 1. Professor , EEE department; Chief coordinator , Industry Institute Partnership
Cell,Kongu Engineering College, Perundurai, Erode-638052,Tamilnadu,India.
2. Professor and Head of the EEE department , Kongu Engineering College,
Perundurai, Erode-638052,Tamilnadu,India.
3. Assistant Professor( Senior Grade ), EEE department , Kongu Engineering College,
Perundurai, Erode-638052,Tamilnadu,India.
The simulation work was assisted by Dr.R.Nagaraja , PRDC, Bangalore.
M/s Kongu Engineering College (KEC) is a leading Institution, offering technical education and research with
state of the art facilities. It is an autonomous Institution affiliated to Anna University, Coimbatore and has
completed 27 years of dedicated service to the students of India and also from abroad.
Case Study 31
17 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
The Industry Institute Partnership Cell (IIPC) of Kongu Engineering College is in existence from 2002 started
with the grant in aid funding from All India Council of Technical Education (AICTE), New Delhi and it is
undertaking various consultancies for the nearby industries with the involvement of the expertise of the
appropriate departments of the college.
ANNEXURES GIVING DETAILS OF CALCULATIONS FOR REACTOR DESIGNS:
Exhibit:1RESULT OF RESONANCE FREQUENCY FOR X/R=20 ; 0.2 % reactor (2 Pumps )
Base MVA 100 Voltage 11 Base Z 1.21 Frequency 50
System data Filter data
Fault
MVA 94
X/R 10
C Delta 4.36E-06 C Star 1.31E-05
XL of Xc 0.002 XL 1.46E+00
p.u L 0.004648
Zsys 1.06383 X/R 20
Rsys 0.105855 R1 7.30E-02
Xsys 1.05855 Xl 1.46E+00
Xc 2.43E+02
Actual X/R 20
Zsys 1.287234 R2 7.30E-02
Rsys 0.128085 Xl 1.46E+00
Xsys 1.280846 Xc 2.43E+02
Zvalue Hz H.no Z value Hz H.no Z13
MinF_resonan
ce 0.039308 646 12.92 Max_resonance
602.79
31 389 7.78
0.1349
63
Hz Harmon
ic no Zsysinv
Zfilter1
Inv Zfilter2 Inv Zth zabs
38
9 7.78
0.0012-
0.10033i
0.00018+
0.05020i
0.000+
0.05020i
602.31-
24.042i 602.7931
64
6 12.92
0.00046-
0.0604i
11.79122-
4.740i
11.7912-
4.7408i
0.0364+
0.0147i
0.039308
Case Study 31
18 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
Exhibit 2 : RESULT OF RESONANCE FREQUENCY FOR X/R=12( 5 % reactor) (2 pumps )
Base MVA 100 Base Voltage 11 Base Z 1.21 Frequency 50
System data Filter data
Fault MVA 94
X/R 10
C Delta 4.36E-06 C Star 1.31E-05
XL of Xc 0.002 XL 3.65E+01
p.u L 0.116194
Zsys 1.06383
Rsys 0.105855
Xsys 1.05855 X/R of coil 12
R 3.04E+00
Actual Xl 3.65E+00
Zsys 1.287234 Xc 2.43E+02
Rsys 0.128085
Xsys 1.280846
Z value Hz H.no Z value Hz H.no Z 13
Min F_resonance 1.279639 130 2.6
Max
F_resonance 4.682827 126 2.52
z Harmonic no Zsysinv Zfilter1
Inv Zfilter2 Inv Zth Zabs
126 2.52 0.01227-
0.309324i
0.10058+
0.15143i
0.10058+
0.15143i
4.6807+
0.13926i
4.682827
130 2.6 0.01153-
0.29983i
0.2772-
0.11941i
0.27728-
0.119441i
0.92697+
0.882155i
1.279639
Case Study 31
19 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
Table 1: For the existing reactor value of 0.2 %
Calculation of minimum and Maximum impedances for both 1 filter and 2 filter for
various values of X/R ratio
Calculation of impedances for X/R=12
and C=4.36X10-6
(star connected) and
for C=8.72X10-6
(star connected)
S.N
o
Parameters X/R=20 X/R=12 X/R=10 X/R=8 C=4.36X10-6
(star
connected)
C=8.72X10-6
(star
connected)
(1
Fil
te
r)
(2
filter)
(1
Filter)
(2
filter)
(1
Filter)
(2
filter)
(1
Filter)
(2
filter)
(1
Filter)
(2
filter)
(1 Filter) (2
Filter)
1 Maximum
Impedance
72
3.
09
57
602.7
931
582.69
47
525.21
21
531.1
122
493.4
569
468.8
462
452.4
256
1749.
636
1559.
126
874.8585
780.314
2
1.1
Correspondin
g Harmonic
no.
9.
42 7.78 9.42
7.78
9.42
7.78
9.42
7.78
16.32
13.48
11.54
9.52
2 Minimum
Impedance
0.
07
85
44
0.039
308
0.1249
37
0.0625
27
0.148
655
0.074
398
0.184
508
0.092
344
0.121
699
0.060
849
0.124087
0.06208
4
2.1
Correspondin
g Harmonic
no.
12
.9
2
12.92 12.92 12.92
12.92
12.92
12.92
12.92
22.36
22.36
15.82
15.82
3 Impedance at
13th
Harmonic
0.
26
78
28
0.134
963
0.2844
5
0.1433
4
0.295
327
0.148
826
0.314
376
0.158
429
- - - -
Case Study 31
20 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
Table 2: Calculations for 5%, 1% and 0.5 % reactors :
Calculation of minimum and Maximum impedances for both 1 filter and 2 filter for various values of
X/R = 12 of 5%, 1% and 0.5%
S.No Parameters 5% 1% 0.5%
(1 Filter) (2 filter) (1 Filter) (2 filter) (1 Filter) (2 filter)
1 Maximum Impedance
5.1536 4.682827
63.66429
4.332184 186.9688
229.2909
1.1 Corresponding Harmonic no.
2.52 2.52 5.32 5.42 7.02 6.26
1.2 Hz 126 126 266 271 351 313
2 Minimum Impedance
1.964136 1.279639
0.605127
0.30544 0.307175
0.153397
2.1 Corresponding Harmonic no.
2.6 2.6 5.78 5.78 8.16 8.16
2.2 Hz 130 130 289 289 408 408
Case Study 31
21 / 21
Case Study of HT Reactor failure- A Resonance Phenomenon in
11KV Water Pumping Station
The sole responsibility for the content of this document lies with the authors. It does not represent the opinion of the Asia
Power Quality Initiative and /or ICPCI/ICA network. APQI and ICA network are not responsible for any use that may be made
of the information contained therein.
APQI was initiated with support of Asia Invest Europe Aid Co-operation office. It is nurtured by ICA network and supported
by Leonardo Power Quality Initiative as knowledge partner