DISCLAIMER: 1001-A PITTSBURG ANTIOCH HWY PITTSBURG, CA 94565 ENG. DEPT. 925.473-9340 FAX 925.473.9124 www.cemcosteel.com CEMCO assumes no liability for failure resulting from the use of it's drawings, or for failure resulting from the use of alternate materials, or improper application or installation. This drawing is supplied solely to assist in the selection and application of CEMCO products. This drawing is generic in nature and should not be used in design or construction without an independent evaluation by a qualified Architect or Engineer of Record. CATEGORY: NON-LOAD BEARING WALL SYSTEMS, DETAIL NUMBER AND DETAIL DESCRIPTION REV: 0 NON-LOAD BEARING WALL SYSTEMS NON-LOAD BEARING WALL DETAILS RELEASE: 12/12/2011

Upload: nguyennguyet

Post on 15-Feb-2018

227 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

NON-LOAD BEARING WALL SYSTEMS, DETAIL NUMBER AND DETAIL DESCRIPTION

REV: 0

NON-LOAD BEARING WALL SYSTEMS

NON-LOADBEARING WALL

DETAILS

RELEASE: 12/12/2011

Page 2: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

1 DEFLECTION TRACK ASSEMBLY - SINGLE TRACK WITH DOUBLE FLAT STRAP SCALE: N.T.S.

REV: 0REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 3: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

1A DEFLECTION TRACK ASSEMBLY - FAS TRACK DL2WITH DOUBLE FLAT STRAP SCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 4: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

2 DEFLECTION TRACK ASSEMBLY - SINGLE TRACK WITH COLD-ROLLED CHANNEL SCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 5: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

2A DEFLECTION TRACK ASSEMBLY - FAS TRACK DL2WITH COLD-ROLLED CHANNEL SCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 6: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

3 DEFLECTION TRACK ASSEMBLY - DOUBLE DEFLECTION TRACKSCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 7: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

3A DEFLECTION TRACK ASSEMBLY - DOUBLE DEFLECTION TRACKWITH CEMCO FAS TRACK DL2 SCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 8: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

4 DEFLECTION TRACK ASSEMBLY - SINGLE SLOTTED TRACKSCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 9: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

4A DEFLECTION TRACK ASSEMBLY - FAS TRACK DLSCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 10: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

5 WALL DEFLECTION - CEMCO DEFLEX VERTICAL SLIDE CLIPSCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 11: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

6 BRIDGING - SINGLE FLAT STRAP WITH BLOCKINGSCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 12: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

7 BRIDGING - DOUBLE FLAT STRAP WITH BLOCKINGSCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 13: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

8 BRIDGING - COLD ROLLED CHANNEL WITH CLIP ANGLESCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 14: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

9 WINDOW NON-LOAD BEARINGSINGLE TRACK HEADER & SILL, SINGLE JAMB SCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 15: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

10 WINDOW NON-LOAD BEARINGSINGLE TRACK HEADER & SILL, BOXED JAMB SCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 16: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

11 WINDOW NON-LOAD BEARINGSINGLE TRACK HEADER & SILL, BACK-TO-BACK JAMB SCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 17: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

12 DOOR NON-LOAD BEARINGSINGLE TRACK HEADER & SINGLE JAMB SCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 18: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

13 DOOR NON-LOAD BEARINGSINGLE TRACK HEADER & BOXED JAMB SCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 19: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

14 DOOR NON-LOAD BEARINGSINGLE TRACK HEADER & BACK-TO-BACK JAMB SCALE: N.T.S.

REV: 0

NON-LOADBEARING WALL

DETAILS

RELEASE: 12/12/2011

Page 20: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

15 NON-LOAD BEARING WALL - INTERIOR WALL FRAMED ABOVE CEILING WITH DIAGONAL BRACE SCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS

Page 21: CEMCO-Non Load Bearing Wall Details - cemcosteel.com Bearing Wall... · non-load bearing wall systems, detail number and detail description rev: 0 non-load bearing wall systems non-load

DISCLAIMER:

1001-A PITTSBURG ANTIOCH HWYPITTSBURG, CA 94565ENG. DEPT. 925.473-9340FAX 925.473.9124www.cemcosteel.com

CEMCO assumes no liability for failure resultingfrom the use of it's drawings, or for failureresulting from the use of alternate materials,or improper application or installation. Thisdrawing is supplied solely to assist in theselection and application of CEMCO products.This drawing is generic in nature and shouldnot be used in design or construction withoutan independent evaluation by a qualifiedArchitect or Engineer of Record.

CATEGORY:

16 NON-LOAD BEARING WALL - INTERIOR WALL FRAMED TOCEILING WITH DIAGONAL BRACE SCALE: N.T.S.

REV: 0RELEASE: 12/12/2011

NON-LOADBEARING WALL

DETAILS