cmt manual - netafim 10313. (9) 1.6.2 earthing . the cornerstone of surge and lightning protection...

38
CMT MANUAL 1.6 EARTHING AND PROTECTION

Upload: nguyenkiet

Post on 14-May-2018

248 views

Category:

Documents


12 download

TRANSCRIPT

Page 1: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

CMT MANUAL 1.6 EARTHING AND PROTECTION

Page 2: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 1

TABLE OF CONTENTS

INDEMNITY ............................................................................................................................................ 5

DOCUMENT INFORMATION .................................................................................................................... 5

ACKNOWLEDGEMENTS .......................................................................................................................... 5

1.6.1 INTRODUCTION ............................................................................................................................. 6

1.6.2 EARTHING ..................................................................................................................................... 6

1.6.2.1 THE EARTHING ROUTE ................................................................................................................... 6

1.6.2.2 EARTH IMPEDANCE ........................................................................................................................ 7

1.6.2.3 DIFFERENT VOLTAGES .................................................................................................................... 7

1.6.2.4 WIRE SIZING ................................................................................................................................. 10

1.6.2.5 WIREWAYS ................................................................................................................................... 10

1.6.2.6 EARTH WIRING ............................................................................................................................. 10

1.6.2.6.1 EARTH WIRING - LV – 400 VAC.................................................................................................. 10

1.6.2.6.2 EARTH WIRING - LV – 230 VAC.................................................................................................. 12

1.6.2.6.3 EARTH WIRING - ELV – 24 VAC .................................................................................................. 12

1.6.2.6.4 EARTH WIRING – 1 to 40 VDC ................................................................................................... 13

1.6.2.6.5 EARTH WIRING – COMMUNICATION ........................................................................................ 15

1.6.2.7 CENTRAL EARTHING POINT – EARTHING BUSBAR ....................................................................... 16

1.6.2.8 THE EARTH TERMINAL ................................................................................................................. 17

1.6.2.8.1 FOUNDATION ELECTRODE ........................................................................................................ 17

1.6.2.8.2 RING EARTH ELECTRODE ........................................................................................................... 17

1.6.2.8.3 VERTICAL OR HORIZONTAL EARTH ELECTRODES ...................................................................... 17

1.6.2.9 THE METHOD OF USING HORIZONTAL EARTH ELECTRODES (EARTH RODS) ............................... 18

1.6.3 SURGE PROTECTION .................................................................................................................... 26

1.6.3.1 SURGE PROTECTION – FIRST LAYER ............................................................................................. 26

1.6.3.2 SURGE PROTECTION – SECOND LAYER - DISTRIBUTION BOARD AND IRRIGATION SWITCH BOARD ...................................................................................................................................................... 26

1.6.3.3 SURGE PROTECTION – THIRD LAYER ............................................................................................ 26

1.6.3.3.1 UPS – GENERAL DESCRIPTION .................................................................................................. 26

1.6.3.3.2 LINE-INTERACTIVE UPS ............................................................................................................. 28

1.6.3.3.3 DOUBLE CONVERSION ON-LINE UPS ........................................................................................ 31

1.6.3.3.4 SURGE PROTECTION - POWERLINE PROTECTOR ...................................................................... 33

1.6.3.3.5 SURGE PROTECTION – COMMUNICATION ............................................................................... 33

Page 3: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 2

1.6.3.3.6 LIGHTNING PROTECTION – BUILDING....................................................................................... 33

1.6.3.3.7 LIGHTNING PROTECTION – WEATHER STATION ....................................................................... 33

REFERENCES ........................................................................................................................................ 37

Page 4: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 3

LIST OF TABLES

TABLE 1. MINIMUM EARTH WIRE SIZE .................................................................................................... 11

TABLE 2. DC SENSOR WIRES – DIGITAL INPUT SENSORS ......................................................................... 14

TABLE 3. SENSOR WIRES – ANALOGUE INPUT SENSORS ......................................................................... 14

TABLE 4. FACTOR λ FOR RODS IN A STRAIGHT LINE FOR USE IN EQUATION 2 ........................................ 21

TABLE 5. FACTOR λ FOR RODS ARRANGED IN A SOLID SQUARE FOR USE IN EQUATION 2 ..................... 21

LIST OF EQUATIONS

EQUATION 1. SOIL RESISTIVITY ................................................................................................................ 20

EQUATION 2. EARTH RESISTANCE OF TWO OR MORE RODS .................................................................. 21

EQUATION 3. ‘α FACTOR’ IN EARTH RESISTANCE EQUATION 2 ............................................................... 21

LIST OF FIGURES

FIGURE 1. THE EARTHING ROUTE .............................................................................................................. 7

FIGURE 2. SCHEMATIC OF DIFFERENT VOLTAGES IN A TYPICAL IRRIGATION AND CLIMATE CONTROL SYSTEM ...................................................................................................................................... 8

FIGURE 3. SCHEMATIC HIGHLIGHTING THE 400 VAC WIRING POSITIONS .............................................. 10

FIGURE 4. SCHEMATIC HIGHLIGHTING THE 230 VAC WIRING POSITIONS .............................................. 12

FIGURE 5. SCHEMATIC HIGHLIGHTING THE 230 VAC WIRING POSITIONS .............................................. 12

FIGURE 6. SCHEMATIC HIGHLIGHTING THE DC WIRING POSITIONS ....................................................... 13

FIGURE 7. SCHEMATIC HIGHLIGHTING THE COMMUNICATION WIRING POSITIONS .............................. 15

FIGURE 8. SCREENED TWISTED PAIR - STP CABLE .................................................................................... 15

FIGURE 9. SCREENED SHIELDED TWISTED PAIR CABLE CROSS SECTION ................................................. 16

FIGURE 10. SCREENED UNSHIELDED TWISTED PAIR / FOILED TWISTED PAIR CABLE CROSS SECTION ................................................................................................................................................... 16

FIGURE 11. DRIVING AN EARTH ROD WITH STRIKING CAP INTO THE GROUND ...................................... 18

FIGURE 12. AN EARTH ROD COUPLER ...................................................................................................... 19

FIGURE 13. EARTH WIRE CLAMPED TO AN EARTH ROD .......................................................................... 19

FIGURE 14. EXAMPLE OF EARTH RESISTANCE VS. NUMBER OF RODS .................................................... 20

FIGURE 15. SOIL RESISTIVITY AND EARTH RESISTANCE EXAMPLE IN AN MS EXCEL SPREADSHEET. ....... 25

FIGURE 16. THE CURRENT FROM THE PROVIDER TO THE CONTROLLER ................................................. 27

FIGURE 17. THE CURRENT FROM THE PROVIDER TO THE CONTROLLER VIA A UPS ................................ 27

FIGURE 18. BASIC COMPONENTS OF A LINE-INTERACTIVE UPS .............................................................. 28

Page 5: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 4

FIGURE 19. LINE-INTERACTIVE UPS OUTPUT WITHOUT GOING TO BATTERIES ...................................... 29

FIGURE 20. LINE-INTERACTIVE UPS OUTPUT, WHEN GOING TO BATTERIES ........................................... 30

FIGURE 21. DOUBLE CONVERSION ON-LINE UPS – BASIC COMPONENTS ............................................... 31

FIGURE 22. DOUBLE CONVERSION ON-LINE UPS OUTPUT WITHOUT GOING TO BATTERIES ................. 32

FIGURE 23. A LIGHTNING ROD PROTECTING THE WEATHER STATION ................................................... 35

FIGURE 24. FIXING THE LIGHTNING ROD TO THE WEATHER STATION POLE ........................................... 36

Page 6: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 5

INDEMNITY Netafim South Africa (Pty) Ltd has taken all reasonable care in ensuring the integrity and reliability of the information contained in this document. Despite this Netafim South Africa (Pty) Ltd. takes no responsibility for any damage or loss that may result from the use of this manual. This document should be regarded as the property of Netafim South Africa (Pty) Ltd. This document is not intended for further training and neither may it be reproduced nor copied in its current form or temporary form. This document may not be revealed and/or carried over to any third party without the explicit written consent of Netafim South Africa (Pty) Ltd. This document is presented with the exclusive aim of notifying selected potential clients regarding Earthing and Protection. Receipt or the possession of this document does not imply rights and the contents should be viewed as a proposal only. This document is neither issued as a guarantee, nor does it confirm any legal obligations on Netafim South Africa (Pty) Ltd whatsoever. Netafim South Africa (Pty) Ltd reserves the right to make changes in its products and in the Earthing and Protection without prior notice. DOCUMENT INFORMATION Version: 1.01 Last updated: 19 Jan 2012 ACKNOWLEDGEMENTS Netafim South Africa

Page 7: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 6

1.6.1 INTRODUCTION There is no such thing as total lightning and surge protection. Although the word ‘protection’ is commonly used, ‘mitigation’ or ‘risk reduction’ are probably better terms. The word ‘protection’ is continued to be used here but any protection measures taken reduce the risk; they do not eliminate it. Netafim gives suggestions here to reduce the risks where Netafim equipment is involved. It is necessary though for the broader-based entire electrical system, including non-Netafim equipment, to have sufficient protection against surges and lightning. For these purposes, it is recommended that the services of a lightning protection system (LPS) designer are used. An LPS designer or an LPS installer are able to issue an LPS installation safety report and maintenance certificate according to SANS 10313. (9) 1.6.2 EARTHING The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of no value unless there is adequate earthing. For the Netafim equipment in an installation, the earthing is more involved than the actual surge protection. Once the earthing system has been established, the surge protection methods are relatively more straightforward. 1.6.2.1 THE EARTHING ROUTE Voltage surges must be shunted immediately to earth before causing damage to electrical and electronic equipment. The basis of the earthing is that earth wires should take a route that runs from each electric component to a central point and thence to earth (7), which itself is usually at one point. (14) The earthing route:

• From - Electric component / equipment, • Via - Earth wire, • To - Central point, (earthing busbar) • Thence via - Earth wire, • Finally to - Earth electrode.

Except with a lightning rod:

• From - Lightning rod • Via - Earth wire • To - Earth electrode

The central point would generally be the earthing busbar in the main electrical switchboard panel and the earth electrode would generally be at or near the consumer’s earth terminal, which is provided at the point of the incoming electricity supply. A lightning rod’s earth electrode would be at its base. See FIGURE 1.

Page 8: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 7

FIGURE 1. THE EARTHING ROUTE 1.6.2.2 EARTH IMPEDANCE The route’s earth impedance – the difficulty at which the surge is shunted to earth - must be as low as possible. This can be enhanced (lowered) by:

• Large surface areas of conductors. Lightning surges tend to flow over the surface, so the larger the better.

• Lack of sharp bends in conductors – large radii in bends. Minimum radius of 30cm. (14). • Tight clean connections at all connection points. • Large surface area in contact with the earth. In practice this is achieved with deeper, longer

driven earth rods and multiple rods thereof. 1.6.2.3 DIFFERENT VOLTAGES Alternating current voltages are categorised as follows: (5) (7)

• 0 VAC < Extra low voltage (ELV) ≤ 50 VAC • 50 VAC < Low voltage (LV) ≤ 1,000 VAC • 1,000 VAC < Medium voltage (MV) ≤ 44,000 VAC • 44,000 VAC < High voltage (HV)

Direct current voltages are categorised as: (7)

• 0 VDC < Extra low voltage (ELV) ≤ 120 VDC • 120 VDC < Low voltage (LV) ≤ 1,500 VDC

Electriccomponent

Electriccomponent

Electriccomponent

Electric component e.g. weather station or antenna with lightning rod

Earthing busbar

Earth electrode Earth electrode forlightning rod

Page 9: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 8

FIGURE 2. SCHEMATIC OF DIFFERENT VOLTAGES IN A TYPICAL IRRIGATION AND CLIMATE CONTROL SYSTEM In Netafim’s automation service experience, the lower the voltage, the higher is the risk for lightning or surge damage. Problems are more likely to arise with communication equipment and controller commands for instance, than with three-phase motors. A conductor (wire) with a lower voltage is affected by another conductor that is running parallel to it and carrying a higher voltage. This is called electromagnetic interference (EMI). (Lightning has a similar and potentially much greater effect). When taking power to the various electric components / equipment, differing voltages should be kept separate and not share the same cables or wireways where feasible. For example, the 230 VAC power to a climate controller should not share the same cable or bundle of cables as that controller’s analogue inputs for instance, which are 1 to 40 VDC. Netafim’s equipment may be broadly grouped into 5 voltages.

• Low Voltage Three Phase – 400 VAC • Low Voltage Single Phase – 230 VAC • Extra Low Voltage – 24 VAC • Extra Low Voltage – 1 to 40 VDC • Communication

400 VAC and 230 VAC are treated much the same, as they are both 230 VAC per phase. LV – 400 VAC. Motors.

• NMC-Junior FertiKits 400 VAC • NMC Pro NetaJets 3G 400 VAC • NMC Pro NetaJets 3G – HP 400 VAC • NMC Pro NetaJet HF 400 VAC • NMC Pro NetaJet HF - HP 400 VAC

Electric supplyboard

Digital inputs

Digital outputs

NMC controller /dosing unit

Irrigationswitchboard withearthing busbar

Earthelectrode

Transformer

Distributionboard

PC

Ear

th w

ireLV

400

VA

CLV

230

VA

CE

arth

wire

Earth wireLV 400 VACLV 230 VAC Digital outputs

in switchboard

Ear

th w

ireLV

400

VA

CLV

230

VA

C

Communication

ELV

24

VA

C

Analogue inputs

Analogue inputs- climate box

Analogue inputs- rain sensor

LV 230 VAC

ELV 24 VAC

ELV DC

ELV 24 VAC

ELV DC

Page 10: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 9

LV – 230 VAC. Motors. Controllers.

• Transformer 50 VA (400 V/230 V to 24 VAC) • NMC Junior Irrigation Controller 230 VAC • NMC Pro Irrigation Controller (L) 230 VAC • NMC Junior Climate Controller 230 VAC • NMC 64 Climate Controller (L) 230 VAC • NMC-Junior FertiKits 230 VAC • NMC Rain Sensor 230VAC Power Supply • NMC – RS485 PC Communication Unit + Box

ELV – 24 VAC. Commands. Digital outputs. Backflush timers.

• AC backflush timers • AquaNet Valves – AC • Aquativ AC solenoid • Baccara 8 Watt NC Solenoid • NMC Inside Temperature & Humidity + Box (fan only) • NMC EC and pH Transmitter – SP

ELV – 1 to 40 VDC. Sensors. Analogue inputs. Digital inputs.

Digital inputs: • Water Meter Reed Switch White (EV) Only • NMC Rain Collector • NMC Wind Speed and Direction Sensor (Speed only)

Analogue inputs: • NMC Wind Speed and Direction Sensor (Direction only) • NMC Solar Radiation Sensor - Netafim • NMC Solar Radiation Sensor - Davis • NMC CO2 Sensor EE82 0 – 5000 ppm • NMC Inside Temperature & Humidity + Box (except fan) • NMC Outside Temperature Sensor + Shield • NMC Outside Temperature and RH Sensor + Shield • NMC Rain Sensor (excluding 230 VAC Power Supply)

ELV – Communication

• NMC – RS485 PC Communication Unit + Box • NMC – USR External 56 K Modem • NMC 64/Pro/DC RS485 Card at NMC Controller • NMC Junior RS485 Card for NMC Controller

Page 11: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 10

1.6.2.4 WIRE SIZING Wire sizing for live / phase conductors is not dealt with here. However, the earth wire sizes below are often linked to those of the live / phase wires. The phase wires should be sized according to SANS10142-1:2008. (7). See the sections 1.6.2.6.1 EARTH WIRING - LV – 400 VAC, 1.6.2.6.2 EARTH WIRING - LV – 230 VAC and 1.6.2.7 CENTRAL EARTHING POINT – EARTHING BUSBAR. The maximum voltage drop from the point of supply to the outlet or appliance under design load shall not exceed 5%:

• Voltage drop for a 400 VAC system ≤ 20.0 V • Voltage drop for a 230 VAC system ≤ 11.5 V

1.6.2.5 WIREWAYS Buried wireways (sleaves) are preferred over aerial wireways. Where aerial wireways are used inside or outside a structure, a metal cable tray is preferred. The metal wireway should itself be earthed (7). 1.6.2.6 EARTH WIRING 1.6.2.6.1 EARTH WIRING - LV – 400 VAC

FIGURE 3. SCHEMATIC HIGHLIGHTING THE 400 VAC WIRING POSITIONS 400 VAC only applies to Netafim products where the product contains a three-phase electric motor. These wires are used from the point of supply to the irrigation switchboard and from there to the motor’s starter and motor. South Africa follows the TN-C-S earthing system. Up to the point of supply, there is a combined protective earth and neutral. This though does not affect the installation of Netafim’s equipment. Beyond the point of supply, a separate earth and neutral must be run to each appliance. (7)(5).

Electric supplyboard

Digital inputs

Digital outputs

NMC controller /dosing unit

Irrigationswitchboard withearthing busbar

Earthelectrode

Transformer

Distributionboard

PC

Ear

th w

ireLV

400

VA

CLV

230

VA

CE

arth

wire

Earth wireLV 400 VACLV 230 VAC Digital outputs

in switchboard

Ear

th w

ireLV

400

VA

CLV

230

VA

C

Communication

ELV

24

VA

C

Analogue inputs

Analogue inputs- climate box

Analogue inputs- rain sensor

LV 230 VAC

ELV 24 VAC

ELV DC

ELV 24 VAC

ELV DC

Page 12: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 11

From the point of supply to the earthing busbar in the switchboard, for overload protection the minimum size of the earth wire may be 10 mm2 (7). However for lightning protection the minimum size of this earth wire is 16 mm2. (10). From the earthing busbar in the switchboard to the electric motor, the minimum size of this earth wire is 6 mm2. (12) However in the case of between the point of supply and the switchboard, it could be larger. If the earth wire forms part of a flexible cable, its size shall be the same as the same as the other live cores (7). If the earth wire does not form part of a cable, then the size indicated in TABLE 1 shall apply. (7) TABLE 1. MINIMUM EARTH WIRE SIZE

TABLE 1.

Minimum nominal cross-sectional area of copper continuity conductors

10 16 25 35 50 (mm2) 10 16 25 35 50 Rated

current of protective device (A)

Maximum length of earth continuity conductor (m)

Rated current of protective device (A)

Maximum length of earth continuity conductor (m)

10 805 63 128 204 319 447 639

16 503 805 80 101 161 252 352 503

20 402 644 100 80 129 201 282 402

25 322 515 125 64 103 161 225 322

32 252 402 629 160 80 126 176 252

40 201 322 503 704 200 64 101 141 201

50 161 258 402 563 250 80 113 161

Notes for TABLE 1

• NOTE 1. This table is not to be used to determine the maximum length of live conductors because the voltage drop may be excessive for the current that they carry.

• NOTE 2. The values in the table are based on a fault current of 2.5 times the rated current of the protective device and a touch voltage of 30 V. (Ref. 7. Section 3.81).

• NOTE 3. This table applies to over-current protective devices and might not be appropriate to other types of protective device.

• NOTE 4. If the full load current rating of the protective device is non-standard, the maximum length of the earth continuity conductor shall be taken as that applying to the next higher standard rating.

Page 13: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 12

1.6.2.6.2 EARTH WIRING - LV – 230 VAC

FIGURE 4. SCHEMATIC HIGHLIGHTING THE 230 VAC WIRING POSITIONS 230 VAC applies to Netafim controllers and Netafim products where the product contains a single-phase electric motor or electric component such as a rain sensor. These wires are generally used from the main irrigation switchboard to that electric component. If there is a single-phase supply, they would also run from the point of supply to the switchboard. A separate earth and neutral must be run to each appliance. (7)(5). For lightning protection the minimum size of the earth wire between the earthing busbar and the point of supply is 16 mm2. From the earthing busbar to the controllers and electric components, the minimum size is 6 mm2. (12) 1.6.2.6.3 EARTH WIRING - ELV – 24 VAC

FIGURE 5. SCHEMATIC HIGHLIGHTING THE 230 VAC WIRING POSITIONS

Electric supplyboard

Digital inputs

Digital outputs

NMC controller /dosing unit

Irrigationswitchboard withearthing busbar

Earthelectrode

Transformer

Distributionboard

PCE

arth

wire

LV 4

00 V

AC

LV 2

30 V

AC

Ear

th w

ire

Earth wireLV 400 VACLV 230 VAC Digital outputs

in switchboard

Ear

th w

ireLV

400

VA

CLV

230

VA

C

Communication

ELV

24

VA

C

Analogue inputs

Analogue inputs- climate box

Analogue inputs- rain sensor

LV 230 VAC

ELV 24 VAC

ELV DC

ELV 24 VAC

ELV DC

Electric supplyboard

Digital inputs

Digital outputs

NMC controller /dosing unit

Irrigationswitchboard withearthing busbar

Earthelectrode

Transformer

Distributionboard

PC

Ear

th w

ireLV

400

VA

CLV

230

VA

CE

arth

wire

Earth wireLV 400 VACLV 230 VAC Digital outputs

in switchboard

Ear

th w

ireLV

400

VA

CLV

230

VA

C

Communication

ELV

24

VA

C

Analogue inputs

Analogue inputs- climate box

Analogue inputs- rain sensor

LV 230 VAC

ELV 24 VAC

ELV DC

ELV 24 VAC

ELV DC

Page 14: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 13

24 VAC wires are always from the controller to a digital output.

• Relays – Use a 3 core cable earthed to the controller’s earth terminal. Sometimes, the output is a 24 VAC relay that is mounted inside the same switchboard that provides 230 VAC power to the controller or 400 VAC to a dosing unit. Where feasible, do not use the same wireway for the 24 VAC and either of the 230 or 400 VAC. Keep the wireways at least 10 cm apart.

• Solenoids – Aquativ AC solenoid / AquaNet Valve – AC. These solenoids do not facilitate an earth wire. Use a 2-core wire. If possible, lay the wires in a metal cable tray and earth the cable tray.

• Solenoids – Baccara. These solenoids facilitate an earth wire in addition to the live and neutral wires. Use a 3-core wire earthed to the controller’s earth terminal.

• NMC Inside temperature and humidity box fan. The 24 VAC wires to the fan do not facilitate an earth wire. Use a 2-core cable from the controller but if feasible, keep it separate (at least 10 cm) from the wires to the temperature and humidity sensors, which are DC.

1.6.2.6.4 EARTH WIRING – 1 to 40 VDC

FIGURE 6. SCHEMATIC HIGHLIGHTING THE DC WIRING POSITIONS Within an AC system, Netafim’s DC equipment mainly comprises of sensors – digital and analogue inputs and the NMC’s actual CPU and busboard.

Electric supplyboard

Digital inputs

Digital outputs

NMC controller /dosing unit

Irrigationswitchboard withearthing busbar

Earthelectrode

Transformer

Distributionboard

PC

Ear

th w

ireLV

400

VA

CLV

230

VA

CE

arth

wire

Earth wireLV 400 VACLV 230 VAC Digital outputs

in switchboard

Ear

th w

ireLV

400

VA

CLV

230

VA

C

Communication

ELV

24

VA

CAnalogue inputs

Analogue inputs- climate box

Analogue inputs- rain sensor

LV 230 VAC

ELV 24 VAC

ELV DC

ELV 24 VAC

ELV DC

Page 15: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 14

TABLE 2. DC SENSOR WIRES – DIGITAL INPUT SENSORS

DC sensor wires - Digital input DC lead-out cores With earthing Additional AC wires to be

kept separate from DC Water Meter Reed Switch White (EV)

Only 2 No

NMC Rain Sensor + Power Supply + 2 No 2 wires x 9 VAC from the power supply.

230 VAC Power Supply for the NMC Rain Sensor No 2 wires x 230 VAC to the

power supply NMC Wind Speed and Direction Sensor

– wind speed * Includes 1 x earth wire

NMC Rain Collector - Including Shelf 2 No

+ The incoming 230 VAC power to the Power Supply for the NMC Rain Sensor should not share the same wireway as any DC sensor cable. Keep them at least 10 cm apart. TABLE 3. SENSOR WIRES – ANALOGUE INPUT SENSORS

DC sensor wires - Analogue input DC lead-out cores With earthing Additional AC wires to be

kept separate from DC NMC Outside Temperature Sensor and

Shield 2 Supplied with shield for earth

NMC Outside Temp. and RH Sensor and Shield 3 Supplied with

shield for earth

NMC Wind Speed and Direction Sensor – wind direction * Includes 1 x earth

wire

NMC Solar Radiation Sensor - Netafim 4 Includes 1 x earth wire

NMC Inside Temperature and Humidity with Box** (except fan***) 4 Supplied with

shield 2 wires x 24 VAC power

input for the fan.

NMC Solar Radiation Sensor – Davis 3 No

NMC CO2 Sensor EE82 0 – 5000 ppm 4 No 24 VAC power supply

*The wind sensor has both digital (speed) and analogue (direction) inputs. **In the NMC Inside temperature and humidity sensors and box (except fan), each of the sensors has its own shielded cable terminating inside the box. Join the two sensors’ shields together in one terminal. To connect to the controller, use one shielded 4 core x 0,5mm2 copper cable for these two sensors and earth the shield at one end to the two sensors’ shield and at the other end to the earth terminal at the controller. ***Where possible, the 24 VAC power from the controller to the fan of the temperature and humidity sensors climate box should not share the same wireway as the above sensors cable. Keep them at least 10 cm apart. All shields / earth wires from each sensor should be earthed at the controller. Where the sensor has neither an earth wire nor a shield, there is little that can be done to protect that sensor other than where possible, lay the wires in a metal wireway and earth that wireway.

Page 16: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 15

1.6.2.6.5 EARTH WIRING – COMMUNICATION

FIGURE 7. SCHEMATIC HIGHLIGHTING THE COMMUNICATION WIRING POSITIONS

Communication wiring:

• Do not share any communication cable’s wireway with LV or ELV cables. (7). Keep them at least 10 cm apart.

• Screened shielded twisted pair (S/STP) with an earth strand is preferred (see FIGURE 9) or at least use screened unshielded twisted pair (S/UTP or FTP – foiled twisted pair) (see FIGURE 10).

• The twist rates of each pair must be different. • When bending, STP cable has a minimum radius stipulated by its manufacturer. • Earth the STP cable’s earth strand and shield at each end at the communication card or PC

communication unit as the case may be. (See Section 7.1.2.4 NMC Communication Lighting Protector for details).

• The earth route to ground from the communication wires is through their earth terminal in the NMC RS485 PC communication unit and built-in to its earth terminal for the 230 VAC incoming power supply. (See Section 7.1.2.4 NMC Communication Lighting Protector for details).

FIGURE 8. SCREENED TWISTED PAIR - STP CABLE

Electric supplyboard

Digital inputs

Digital outputs

NMC controller /dosing unit

Irrigationswitchboard withearthing busbar

Earthelectrode

Transformer

Distributionboard

PCE

arth

wire

LV 4

00 V

AC

LV 2

30 V

AC

Ear

th w

ire

Earth wireLV 400 VACLV 230 VAC Digital outputs

in switchboard

Ear

th w

ireLV

400

VA

CLV

230

VA

C

Communication

ELV

24

VA

C

Analogue inputs

Analogue inputs- climate box

Analogue inputs- rain sensor

LV 230 VAC

ELV 24 VAC

ELV DC

ELV 24 VAC

ELV DC

Page 17: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 16

FIGURE 9. SCREENED SHIELDED TWISTED PAIR CABLE CROSS SECTION

FIGURE 10. SCREENED UNSHIELDED TWISTED PAIR / FOILED TWISTED PAIR CABLE CROSS SECTION 1.6.2.7 CENTRAL EARTHING POINT – EARTHING BUSBAR The irrigation and climate system’s main electric board or distribution board must contain an earthing busbar. It is a collection point for all earth wires from the components of the system, each of which is linked to this busbar. (7). Unless specified, the manufacturer of the switch board may not necessarily provide an earthing busbar. (3) The minimum cross section of copper earth wires from internal metal installations to the earthing busbar is 6 mm2. (12) The busbar itself is connected by one copper earth wire to the earth terminal. The minimum cross sectional area of this wire is 16 mm2. (12). It may not carry any current other than fault currents. See Earthing – LV – 400 VAC.

Page 18: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 17

1.6.2.8 THE EARTH TERMINAL Netafim equipment requires a targeted earth resistance at the earth terminal of 3.0 Ω or less but a maximum of 5.0 Ω. There are three types of earth terminal: (8)(5)

• Foundation electrode. The reinforced steel network (rebars) of the building’s concrete

foundations and floor. • Ring earth electrode around the outside of the building. • Vertical or horizontal earth electrodes.

o One or more vertical rods. o One or more horizontal rods or wire “trench earth”.

1.6.2.8.1 FOUNDATION ELECTRODE The network of rebars in a concrete foundation can be used for lightning discharge currents, but not for earth fault currents. (8)(11). This type of earth electrode is feasible in a new installation with a new building, in which case the services of an LPS designer should be used. If earthed to existing rebars, it is possible that the resistance of 3.0 Ω might not be achieved, in which case earth rods may need to be added in addition to this electrode. 1.6.2.8.2 RING EARTH ELECTRODE A ring electrode is a 50 mm2 copper stranded earth wire closed loop around a building, one metre from the building’s perimeter of which at least 80% is buried, preferably to a minimum depth of 0.5 m. (11). This electrode is more feasible with an existing installation. However as with the foundation electrode above, it is possible that should the resistance of 3.0 Ω not be achieved, additional earth rods may needed. 1.6.2.8.3 VERTICAL OR HORIZONTAL EARTH ELECTRODES Earth rods driven into the ground are the simplest form of earth terminal and the quickest to install. The standard earth rod supplied by Netafim is 1.2 m long x 14 mm diameter copper-coated steel. (6). It is necessary that the installer of the rods has an earth resistance meter. The electricity service provider needs only an earth resistance of 15 Ω. (5). This is insufficient for the controllers and other electronic equipment. The target earth resistance for Netafim equipment is 3.0 Ω or less. It is sometimes possible to achieve this with just one rod but normally, several rods will be required. One keeps adding rods - thus lowering the earth resistance - until the desired resistance is achieved. The deeper the rod is buried, the better. Two x 1.2 m rods coupled end-to-end to form one rod driven 2.4 m into the ground will achieve lesser resistance than two x 1.2 m rods placed side-by-side connected with copper earth wire. However the depth to which the rods can be driven would be a limiting factor due to soil depth or other physical impediments in the soil. When the extended rod can be driven no deeper and the desired earth resistance has still not been achieved, it will be necessary to add further rods adjacent to each other.

Page 19: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 18

1.6.2.9 THE METHOD OF USING HORIZONTAL EARTH ELECTRODES (EARTH RODS) Equipment required:

• Copper coated earth rods 1.2 m x 14 mm threaded at each end. • 14 mm striking cap. • One 14 mm coupler for each earth rod. • 14 mm earth rod clamp. • 16 mm² insulated earth wire – for connecting above ground to the electrical system. • 16 mm² uninsulated earth wire – for connecting individual earth rods. • Earth resistance meter. • Heavy hammer - 1.5 kg or more.

Fit a 14 mm striking cap onto one rod and drive its entire length into the ground if possible. After driving the entire length into the ground, measure the rod’s earth resistance. If it is more than 3.0 Ω, replace the striking cap with a 14 mm coupler and couple a second rod. Fit the striking cap to the new rod, hammer it 2.4 m into the ground and measure the resistance. Repeat this process until 3.0 Ω is achieved or one can drive the rod no deeper.

FIGURE 11. DRIVING AN EARTH ROD WITH STRIKING CAP INTO THE GROUND

Page 20: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 19

FIGURE 12. AN EARTH ROD COUPLER Any further reduction in earth resistance can only be gained by adding more rods adjacent to each other and connecting them with buried 16 mm² uninsulated earth wire clamped to each rod. See Figure 13. The addition of each adjacent rod lowers the earth resistance at a diminishing rate. See the graph in Figure 14.

FIGURE 13. EARTH WIRE CLAMPED TO AN EARTH ROD

Page 21: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 20

Space permitting, the distance between adjacent rods must where possible, be at least equal to one rod’s length. For example, no two earth rods that are 2.4 m long should be closer than 2.4 m apart.

FIGURE 14. EXAMPLE OF EARTH RESISTANCE VS. NUMBER OF RODS It may not be feasible to achieve 3.0 Ω as the number of rods required may be uneconomical. If this is the case, the user would need to judge the cost of the rods versus the resistance achieved. To this end, it is possible to estimate the number of adjacent rods that would be required, by calculating the soil resistivity in ohm metres (Ω.m) for the total depth of one vertical rod. (2) EQUATION 1. SOIL RESISTIVITY

𝜌 =𝑅2𝜋𝐿

(log𝑒�8𝐿𝑑� � − 1)

ρ = soil resistivity (Ω.m) R = the earth resistance of one vertical rod (Ω) L = the effective buried length of the vertical rod (m) d = the rod diameter (m) loge = natural log

0

20

40

60

80

100

120

140

160

180

200

1 rod 2 rods 3 rods 4 rods 5 rods

Example of earth resistance vs. number of rods

Earth resistance in Ω

Page 22: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 21

EQUATION 2. EARTH RESISTANCE OF TWO OR MORE RODS

𝑅𝑛 = 𝑅 �1 + 𝜆𝛼

𝑛�

Where EQUATION 3. ‘α FACTOR’ IN EARTH RESISTANCE EQUATION 2

𝛼 = 𝜌

2𝜋𝑅𝑠

Rn = the earth resistance of n rods (Ω) R = the earth resistance of one rod (Ω) n = the number of rods λ = factor in:

o TABLE 4 for rods in one straight line or o TABLE 5 for rods arranged in a solid square

s = the distance between the rods (m) TABLE 4. FACTOR λ FOR RODS IN A STRAIGHT LINE FOR USE IN EQUATION 2

n λ

2 1.00

3 1.66

4 2.15

5 2.54

6 2.87

7 3.15

8 3.39

9 3.61

10 3.81

TABLE 5. FACTOR λ FOR RODS ARRANGED IN A SOLID SQUARE FOR USE IN EQUATION 2

Number of rods along each side of the square n λ

2 rows x 2 rods per row 4 2.7

3 rows x 3 rods per row 9 5.9

4 rows x 4 rods per row 16 8.5

5 rows x 5 rods per row 25 11.4

6 rows x 6 rods per row 36 14.0

7 rows x 7 rods per row 49 16.9

Page 23: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 22

Example 1. An example of high earth resistance overcome by several earth rods. The installer discovers that it is not possible to drive a 14 mm diameter earth rod longer than 2.4 m into the ground. The earth resistance meter measures the resistance of this rod as 27.7 Ω. This is higher than 3.0 Ω and further adjacent rods must be added. Calculate the soil resistivity:

𝜌 =𝑅2𝜋𝐿

(log𝑒�8𝐿𝑑� � − 1)

𝜌 =27.7 𝑥 2𝜋 𝑥 2.4

(log𝑒�8 𝑥 2.40.014� � − 1)

𝜌 =417.71

(log𝑒(1,371.429 ) − 1)

𝜌 =417.71

(7.224 − 1)

𝝆 = 𝟔𝟕.𝟏𝟏 𝜴.𝒎

Attempt to bring the earth resistance down to less than 3.0 Ω by calculating the required number of earth rods necessary to meet this resistance.

𝑅𝑛 = 𝑅 �1 + 𝜆𝛼

𝑛�

where

𝛼 = 𝜌

2𝜋𝑅𝑠

The earth resistance of 4 rows of 4 earth rods 2.4 m apart and arranged in a square, 16 rods in total would be as follows.

𝑅16 = 27.7 �1 + 8.5𝛼

16�

where

𝛼 = 67.11

2𝜋 𝑥 27.7 𝑥 2.4

𝛼 = 0.16

𝑅16 = 27.7 �1 + (8.5 𝑥 0.16)

16�

𝑹𝟏𝟔 = 𝟒.𝟏 𝜴

This is higher than the target of 3.0 Ω.

Page 24: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 23

The earth resistance of 5 rows of 5 earth rods 2.4 m apart and arranged in a square, 25 rods in total would be as follows:

𝑅25 = 27.7 �1 + 11.4𝛼

25�

Where α remains the same as with 16 rods above

𝛼 = 0.16

𝑅25 = 27.7 �1 + (11.4 𝑥 0.16)

25�

𝑹𝟐𝟓 = 𝟑.𝟏 𝜴

These calculations would put the user in the ballpark of how many rods theoretically would be required to achieve the desired earth resistance. 16 rods would give a resistance of 4.1 Ω and 25 rods a resistance of 3.1 Ω. The user may be unwilling to buy 25 rods and may settle for less protection. The actual measured results would vary from those calculated. The installer would need to drive in successive rods and measure the earth resistance after each rod and let the user decide on the number of rods finally installed. Example 2. An example of lower earth resistance overcome by fewer earth rods. The installer discovers that it is not possible to drive a 14 mm diameter earth rod longer than 1.2 m into the ground. The earth resistance meter measures the earth resistance of this rod as 7.3 Ω. This is higher than 3.0 Ω and further adjacent rods must be added. Calculate the soil resistivity:

𝜌 =𝑅2𝜋𝐿

(log𝑒�8𝐿𝑑� � − 1)

𝜌 =7.3 𝑥 2𝜋 𝑥 1.2

(log𝑒�8 𝑥 1.20.014� � − 1)

𝜌 =55.04

(log𝑒(685.714 ) − 1)

𝜌 =55.04

(6.531 − 1)

𝝆 = 𝟗.𝟗𝟓 𝜴.𝒎

Attempt to bring the earth resistance down to less than 3.0 Ω by calculating the required number of earth rods necessary to meet this resistance.

𝑅𝑛 = 𝑅 �1 + 𝜆𝛼

𝑛�

where

𝛼 = 𝜌

2𝜋𝑅𝑠

Page 25: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 24

The earth resistance of 3 earth rods 1.2 m apart and arranged in a straight line would be as follows.

𝑅3 = 7.3 �1 + 1.66𝛼

3�

where

𝛼 = 9.95

2𝜋 𝑥 7.3 𝑥 1.2

𝛼 = 0.18

𝑅3 = 7.3 �1 + (1.66 𝑥 0.18)

3�

𝑹𝟑 = 𝟑.𝟐 𝜴

This is slightly higher than the target of 3.0 Ω. The earth resistance of 4 earth rods 1.2 m apart and arranged in a straight line would be as follows:

𝑅4 = 7.3 �1 + 2.15𝛼

4�

Where α remains the same as with 3 rods above

𝛼 = 0.18

𝑅4 = 7.3 �1 + (2.15 𝑥 0.18)

4�

𝑹𝟒 = 𝟐.𝟓 𝜴

These calculations would put the user in the ballpark of how many rods theoretically would be required to achieve the desired earth resistance. 3 rods would give a resistance of 3.2 Ω and 4 rods a resistance of 2.5 Ω. As with example 1, the actual measured results would vary from those calculated. The installer would need to drive in successive rods and measure the earth resistance after each rod and let the user decide on the number of rods finally installed.

Page 26: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 25

Calculate soil resistivity and earth resistance in MS Excel The above calculations can be done using MS Excel.

FIGURE 15. SOIL RESISTIVITY AND EARTH RESISTANCE EXAMPLE IN AN MS EXCEL SPREADSHEET. Following FIGURE 15, enter the relevant values into cells B5, B6, B7, B15, B16 and B17 Insert the following formula into cell B3 =(B5*2*PI()*B6)/(LN(8*B6/B7)-1) Insert the following formula into cell B11 =B5*((1+(B15*B13))/B16) Insert the following formula into cell B13 =B3/(2*PI()*B5*B17

Page 27: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 26

1.6.3 SURGE PROTECTION Once an adequate earthing system has been established, the means to shunt surges to earth through that earthing system can be planned. This is a layered approach. Surge protection devices (SPD) are installed at three basic layers. (14).

• The first layer is at the main electric supply board. • The second layer is at the distribution board and irrigation switchboard. • The third layer is at the motors and controllers that feed from the switchboard.

The third layer to a controller would generally be an uninterruptable power supply (UPS) with surge protection. (2) (14).

A separate possible source of a surge is through the ‘backdoor’ in the form of a telephone supply or though data cables entering the site from another source, which would also need their own protective devices. 1.6.3.1 SURGE PROTECTION – FIRST LAYER The consumer may not have much control of the surge protection at the point of supply – the first layer - but from thereon, efficient surge protection devices must be installed at the second and third layers. 1.6.3.2 SURGE PROTECTION – SECOND LAYER - DISTRIBUTION BOARD AND IRRIGATION SWITCH BOARD A switch board will normally contain a magnetic circuit breaker (MCB) to each electric device as well as a thermal overload. Both react to an increase in current. With an MCB, an increase in amps pulls in a solenoid (coil) to break the circuit and with a thermal overload, the heat generated by the increased current will bend a bi-metal strip to beak the circuit. However, neither will react to a voltage surge. For this, the incoming supply to the board must be fitted with a 3-phase surge protection device. This SPD has open connections from each of the three phases to earth. The potential between each live phase and earth is 230 V. This connection is immediately closed at 275 V. Unless specified to the switch board manufacturer, this SPD would not normally be provided. (3) 1.6.3.3 SURGE PROTECTION – THIRD LAYER 1.6.3.3.1 UPS – GENERAL DESCRIPTION An uninterruptable power supply unit (UPS) enables IT equipment to tolerate a wide range of voltages without any processing circuits malfunctioning. They will assist in flattening-out voltage surges. They are generally over-current protected and will shunt surges to earth.

Page 28: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 27

There are two main types of UPS.

• Line-interactive UPS. This is a relatively lower-cost type, usually bought to keep IT equipment going in the event of a power cut and provide a degree of voltage regulation. They are sold by Netafim.

• Double Conversion On-line UPS. The type is more sophisticated and provides a much tighter degree of protection against voltage fluctuations.

While a UPS enables a controller to tolerate a wide range of voltages without any processing circuits malfunctioning, even without a UPS, a controller is very tolerant of voltage fluctuations. The voltage from a 50Hz AC supply passes through zero volts 100 times per second (twice per cycle), at which moments there is no power to an electric device. This poses no problem to a device such as an electric light or a motor but a controller’s processing circuits cannot function under such a condition. All computers and controllers therefore operate under a constant flat DC supply. Where the electricity supplied to the controller is AC, this DC power comes from a switch-mode power supply (SMPS), which converts low voltage AC to extra low voltage DC.

FIGURE 16. THE CURRENT FROM THE PROVIDER TO THE CONTROLLER The SMPS uses capacitors that are charged at voltage cycle peaks and which then constantly release electricity that bridges this ‘gap’ when there are zero volts. In the same manner, the SPMS can also overcome an interruption in power supply, albeit very brief. Thus to a small degree, the SMPS is its own mini-UPS. The SMPS can generally achieve these functions providing its own incoming voltage does not vary by more than 10% higher than nominal voltage and 20% lower. In other words the nominal 230V supply should not exceed 253V and should not reduce below 184V. (4). Netafim recommends that the power to its own NMC power supply does not vary by more than 253V or lower than 207V (i.e. ± 10%). A UPS widens this voltage range. It regulates the AC supply to the SMPS but its ability regulate depends on the type chosen.

FIGURE 17. THE CURRENT FROM THE PROVIDER TO THE CONTROLLER VIA A UPS

Controller LV AC ELV DC Electricity provider

SMPS

Electricity provider LV AC UPS LV AC SMPS Controller

ELV DC

Page 29: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 28

1.6.3.3.2 LINE-INTERACTIVE UPS Apart from the batteries, there are two main parts to a line-interactive UPS: a power interface and an inverter. The power interface filters the AC power, suppresses voltage spikes and provides some regulation to the voltage output. The inverter redirects some of the input AC power to keep its batteries fully charged. When the AC input voltage falls outside of the input range of the power interface, the inverter supplies AC power from the batteries. The output voltage varies with the input voltage, although not to the same degree. This output variation is acceptable though, provided it remains within the permissible input voltage range of the SMPS.

Power interface

Inverter

Battery

AC input AC output to SMPS

Normal mode

Stored energy mode

FIGURE 18. BASIC COMPONENTS OF A LINE-INTERACTIVE UPS

Page 30: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 29

The line-interactive UPS supplied by Netafim has an input range from 173V to 276V and an output to the power supply of between 211V to 250V, which is within the power supply’s input range of 207V to 253V.

Line

inte

ract

ive

UP

S o

utpu

t

Line-interactive UPS input

NMC Power supply input

276 VAC

250 VAC

211 VAC

173 VAC

NM

C

pow

er

supp

ly

outp

ut

253 VAC

207 VAC

12 VDC

FIGURE 19. LINE-INTERACTIVE UPS OUTPUT WITHOUT GOING TO BATTERIES

Page 31: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 30

If the voltage goes outside this range, the UPS goes to battery and produces an output in a narrower range of 219 V to 242 V.

Line

inte

ract

ive

UP

S o

utpu

t

Line-interactive UPS input

NMC Power supply input

276 VAC

241 VAC

219 VAC

NM

C

pow

er

supp

ly

outp

ut

253 VAC

207 VAC

12 VDC

Line-interactive UPS input

greater than 276V

Line-interactive UPS input less than

173V

FIGURE 20. LINE-INTERACTIVE UPS OUTPUT, WHEN GOING TO BATTERIES

Page 32: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 31

1.6.3.3.3 DOUBLE CONVERSION ON-LINE UPS The on-line UPS has about three times more components than a line-interactive UPS, but these components are generally smaller. As the name suggests, it converts power twice. First, it is converted from AC to DC using capacitors, just like an SMPS. Then second, it is converted back into tightly regulated AC. When the AC input goes out of its specified range, the on-line UPS draws power from its batteries so that the UPS output is not affected.

Rectifier

Battery to DC

converter

Battery

AC inputAC output to SMPS

Normal mode

Stored energy mode

Inverter

Bypass switch

AC input

DC Link

Bypass mode

Bypass (prime or standby)

FIGURE 21. DOUBLE CONVERSION ON-LINE UPS – BASIC COMPONENTS Unlike a line-interactive UPS, an on-line UPS typically has a bypass, which comes into action when there is either a fault with the UPS or the load exceeds what the UPS is designed to handle

Page 33: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 32

An on-line UPS will operate at a wider input voltage range than a line-interactive UPS and will regulate output much more tightly. An example of this range is shown in FIGURE 22.

On-

line

UP

S

out-

put

Double conversion on-line UPS

input

NMC Power supply input

300 VAC

235 VAC

225 VAC

110 VAC

NM

C

pow

er

supp

ly

outp

ut

253 VAC

207 VAC

12 VDC

FIGURE 22. DOUBLE CONVERSION ON-LINE UPS OUTPUT WITHOUT GOING TO BATTERIES An on-line UPS is more frequency tolerant than a line-interactive UPS. Even though the voltage might be within a line-interactive UPS’s range, if the frequency deviates from 50 Hz, the line-interactive UPS may go to its batteries when the on-line UPS will not necessarily do so. This is because the on-line UPS’s AC output comes from the DC that the input was initially converted to.

Page 34: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 33

A few line-interactive UPSs do have a frequency tolerance and others have no tolerance. All on-line UPSs have a frequency tolerance. This frequency tolerance is important where the main supply is subject to frequency variation and particularly from generator sets. For instance, a genset may give out a frequency of 48 Hz, in which case a line-interactive UPS with 0% frequency tolerance will go to battery when an on-line UPS will not do so, providing its tolerance will allow the frequency to drop the 4% from 50 Hz to 48 Hz. 1.6.3.3.4 SURGE PROTECTION - POWERLINE PROTECTOR Netafim provides the NMC Power Line Protector as a surge protection device. As well as being fused, it contains several components such as varistors that divert surges to its earth terminal. Like the UPS, this is a third layer SPD. It is provided as additional protection and is usually installed at the incoming supply to the UPS. 1.6.3.3.5 SURGE PROTECTION – COMMUNICATION As mentioned in Earthing – Communication Wiring above, the NMC RS485 PC Communication Unit at the PC has its own surge protection with its communication cable to the controller earthed to the ground of its incoming 230 VAC power. The communication card for the NMC 64 / Pro is surge protected and has an earth terminal that will ground through the NMC 64 / Pro controller to which it is fitted. The communication card for the NMC Junior is not surge protected and has no earth terminal. It is necessary to use an additional device, an NMC Junior COMS lightning protector at each NMC Junior in the communication network. This device is earthed at the incoming power to the NMC Junior. 1.6.3.3.6 LIGHTNING PROTECTION – BUILDING Lightning protection of a building is specialised and is best undertaken by an LPS designer or an LPS installer. They are able to issue an LPS installation safety report and maintenance certificate according to SANS 10313. 1.6.3.3.7 LIGHTNING PROTECTION – WEATHER STATION The weather station is mounted at the top of a pole / mast, normally of 50 mm diameter aluminium. Its protection from lightning may not necessarily be done by the LPS designer, who would mainly be concerned with the building mentioned above. The weather station must be protected at the top with a lighting rod that is earthed at the mast’s base as well as to the central earthing busbar. A suitable lightening rod is the standard 1.2 m long x 14 mm diameter earth rod supplied by Netafim, described above in Vertical or Horizontal Earth Electrodes. The height of its tip above the weather station should be such that it provides a cone of protection where the angle of the cone’s apex is 70⁰. Effectively this means that one 1.2 m rod will suffice for a weather station without any wind sensor and a 2.4 m rod would be needed if there is a wind sensor. (9)(11). See FIGURE 23. The bottom end of the lightning rod is connected to a small length of 10 mm² earth wire, which wire in turn is clamped to the mast. This wire is necessary as the clamps holding the rod to the mast give

Page 35: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 34

too much resistance by themselves. The mast itself will act as a conductor. It must be earthed at its base in a similar manner as described in The Earth Terminal above. It should also be earthed at the central earthing busbar. (12) The lightning rod must be offset from the pole in order to clear the weather station mounting arm. See FIGURE 24.

Page 36: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 35

FIGURE 23. A LIGHTNING ROD PROTECTING THE WEATHER STATION

1700

1380

500

70°

Top of a 1.2m lightning rod.Minimum height for weather station without wind sensor

Minimum height for weather station with a wind sensor

70°

Cone of protection

Top of a 2.4m lightning rod

430

70°

Connect the rod to the pole with 10mm² earth wire

Ø 50mm aluminium pole

210

700

Page 37: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 36

FIGURE 24. FIXING THE LIGHTNING ROD TO THE WEATHER STATION POLE

430

500

210

Lightning rod

Ø 50mm aluminium pole10mm² earth wire

U bolt and clamps

130

154

50

30°

77

Page 38: CMT MANUAL - Netafim 10313. (9) 1.6.2 EARTHING . The cornerstone of surge and lightning protection is earthing. Any surge and lightning protection is of

Version 1.01 JA20120119 Earthing and Protection Page 37

REFERENCES Some references specify wire sizes that are not used in South Africa, in which case the text specifies the next highest commercially available size. For example, should a reference specify an earth wire size of 14 mm², which is not used in SA, the text will specify 16 mm². 1. Buijs, Machiel. 2010. Buys Electrical, Krugersdorp. Personal communication. 2. Cloete, Johannes. 2009. Lightning Protection and Earthing (Grounding). Input Output Agricultural Controls CC. Brakenfell 3. Colussi, Renato. 2010. Electroparts, Cape Town. Personal communication. 4. Samstad, Jeffrey. Hoff, Michael. 2004. Technical comparison of on-line vs. line interactive UPS designs. American Power Corporation. 5. South African Bureau of Standards. 2010. SABS 0292:2001. Earthing of low-voltage (LV) distribution systems. Pretoria 6. South African Bureau of Standards. 2008. SANS 1063:2008. Earth rods, couplers and connections. Pretoria. 7. South African Bureau of Standards. 2008. SANS 10142-1:2008. The wiring of premises. Part 1: Low-voltage installations. Pretoria. 8. South African Bureau of Standards. 2004. SANS 10199:2004. The design and installation of earth electrodes. Pretoria. 9. South African Bureau of Standards. 2010. SANS 10313:2010. Protection against lightning – Physical damage to structures and life hazard. Pretoria 10. South African Bureau of Standards. 2007. SANS 62305 -1:2007. Protection against lightning. Part 1: General principles. Pretoria. 11. South African Bureau of Standards. 2007. SANS 62305 -3:2007. Protection against lightning. Part 3: Physical damage to structures and life hazard. Pretoria. 12. South African Bureau of Standards. 2007. SANS 62305 -4:2007. Protection against lightning. Part 4: Electrical and electronic systems within structures. Pretoria. 13. Uys, Phil. 2010. Stellenbosch. Personal communication. 14. Woolsey, Jeff. 2000. Don’t let lightning zap you. GMPro magazine. November Issue.