diagnostic techniques for condition monitoring of transformers
TRANSCRIPT
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
1/121
1
( & )( & )
00 00
2
1.
Electrical distribution equipment is generallydesigned for a certain economic service life.
Equipment life is dependent on operatingenvironment, maintenance program and the qualityof the original manufacture and installation.
Beyond this service life period they are not expectedto render their services up to expectation withdesired efficiency.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
2/121
3
1. Generally due to poor quality of raw material,
workmanship and manufacturing techniques or dueto frequent electrical, mechanical and thermalstresses during the operation, many equipment failmuch earlier than their expected economic life span.
The concept of simple replacement of failed powerequipments in the system either before or after theireconomic service life, is no more valid in the presentscenario of financial constraints.
1.
Explore new approaches/techniques of monitoring,diagnosis, life assessment and condition evaluation,and possibility of extending the life of existing assets(i.e. circuit breaker, cables, transformers, etc.)
Minimization of the service life cycle cost is one ofthe stated tasks of the electrical power systemengineers. For electrical utilities this implies forexample to fulfill requirements from customers andauthorities on reliability in power supply at a minimaltotal cost.
The main goal is therefore to reach a cost effectivesolution using available resources which is capturedby the concept ofAsset Management.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
3/121
ASSETMANAGEMENT
OperateOperateOperateOperate
efficientlyefficientlyefficientlyefficiently
High PerformanceHigh PerformanceHigh PerformanceHigh Performance
ReasonableReasonableReasonableReasonable
returnsreturnsreturnsreturns
Low CostLow CostLow CostLow Cost
SAIFI, SAIDI
Power quality
Power availability
Reduced Loss etc.
Investment
O&M
Stocking etc.
Balancing cost, risk,
and performance in
the context of asset
full life cycle
&
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
4/121
With the increasing age of the population of power
system equipment utilities are making efforts to
assess the internal condition of the equipment while
in service before catastrophic failures can take place
Different types of maintenance being done on
equipment are:
Breakdown maintenance
Time or Calendar Based maintenance
Condition based maintenance
Reliability centered maintenance
Today the paradigm has changed from traditional
calendar based to condition based maintenance and
efforts are being channeled to explore techniques to
monitor, diagnose and assess condition of power
system equipment
This has led to the development of various on- and
off-line non-intrusive tests in recent years that allowdiagnosing the integrity of power system equipment
to optimize the maintenance effort thereby ensuring
maximum availability and reliability
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
5/121
10
Ageing asset population
Age by itself is not a good predictor of
future performance
Must be able to fully justify decisions in
terms of proven engineering principles
Cannot make sound asset management
decisions unless you understand asset
condition!
11
Combining all available practical and theoretical
knowledge and experience of assets to:
Define current condition and use this to estimate future
condition and performance
Provide a sound engineering basis for evaluating risks and
benefits of potential investment strategies
Uses a well developed methodology (with practical
experience of successful application)Provides a framework for continual improvement
(information and definition of condition)
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
6/121
12
Ageing asset population
Pressures to maintain/improve performance and to
reduce costs
Age (by itself) is not an acceptable reason to replace
assets
Must demonstrate need and consequences, condition
and future performance
Cannot make good Asset Management decisions
unless you understand asset condition!
13
Define asset condition (Health Index)
Link condition to performance & probability of failure
(PoF)
Calibrate Health Index/PoF against historic fault rates
Estimate future condition and performance
Evaluate effect of investment programmes on future
condition and performance
Provides an ENGINEERING basis to evaluate risk and
determine investment requirements
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
7/121
1
Need understanding of:
Degradation and failure processes
Condition assessment techniques
Practical knowledge of assets,
Operating context
Everything is related back to physical condition and
degradation processes - maximising the value of
available experience of the assets
1
A consistent and logical means of combining
relatively complex information
A way to rank assets (on basis of proximity to
EOL or probability of failure)
Relatively simplistic
It is NOT a substitute for engineering expertise
and judgement it is an additional aid toengineers
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
8/121
1
A Health Index is a means to define proximity to EOL
by combining varied and relatively complex condition
information as a single number
Define significant condition criteria
Code information numerically,
Apply weightings
Develop a simple algorithm to generate a HI for
each asset Rank and apply calibration
1
Condition Remnant Life (years) Probability of
failure
5 - 10Poor
Fair
Good
At EOL (20
High
Medium
Low
Very Low
10
0
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
9/121
1
0 3 5 10
MMeeaassuurraabblleeddeetteerriioorraattiioonnbbuuttnnoo
ssiiggnniiffiiccaannttiinnccrreeaasseeiinnPP((ff))
SSiiggnniiffiiccaannttddeetteerriioorraattiioonnssmmaallll
iinnccrreeaasseeiinnPP((ff))
SSeerriioouussddeetteerriioorraattiioonnssiiggnniiffiiccaa
nntt
iinnccrreeaasseeiinnPP((ff))
ProbabilityoffailurePf)
Health Index
1
Actual condition information
Risk factors with direct condition implications -
failure rates, specific or generic problems,
design issues etc
Other non condition based risk factors can bemapped on later to evaluate overall risk
(Criticality, load, obsolescence etc)
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
10/121
20
Means of determining probability of failure
It does not consider consequences of failure
Ultimately require combination of both to
evaluate overall risk
CBHI is the 1st step (phase 1)
Phase 2 use of results in a risk model
21
1 ( )
Define
Assets
Define
EOL
Issues
Review
Condition
Assessment
Techniques
Data and
Information
Analysis
Formulation
and Population
of HI
HI to
Probability
of Failure
Change of
HI (PF) with
time
Documentation
Conclusions
Report
CONSEQUENCES
Phase 2
Define
Assets
Define
EOL
Issues
Review
Condition
Assessment
Techniques
Data and
Information
Analysis
Formulation
and Population
of HI
HI to
Probability
of Failure
Change of
HI (PF) with
time
Documentation
Conclusions
Report
CONSEQUENCES
Phase 2
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
11/121
( & )( & )
200 200
&
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
12/121
&
Types of Transformers
Core Type
Shell Type
Oil-Immersed Type,
Dry Type
&
Core Type Transformers
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
13/121
&
Shell Type Transformers
&
Typical Winding Connections
Delta Star
Star - Delta
Star Star
Delta Delta
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
14/121
&
Other Winding Connections
Zig Zag Connections
Tertiary Windings
Double Secondary
Scott (T-T) Connections
Autotransformers
Earthing Transformers
The transformer has been designed,
manufactured and tested according to
IEC 60076 part 1 to 5. Power Transformer
It consist of : core, winding, insulation, core
and winding assembly, tank.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
15/121
Grain Oriented Electrical Steel
Type M5 (0.3mm), M4 (0.27mm) and ZDKH
(0.23mm)
Are designed to meet three fundamental requirement :
1. Electrical
2. Mechanical
3. Thermal
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
16/121
Round, Oval or rectangular in shape
and are wound concentrically.
LV winding is wound with foil
conductor (Distribution)
HV winding is wound with rectangular
strip conductor.
HV winding is wound on LV winding.
The interlayer insulation are of high quality epoxy
coated kraft paper (DDP)
Corrugated pressboards are placed within the
coil for cooling within the coil.
Thickness of layer insulation
in accordance with voltage
and number of layers.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
17/121
& Arrangement of windings with respect to the core :
CORE - LV WINDING - HV WINDING
For tapping lead connection normally use stranded copper or
round conductor.
Bushing Lead :-
1. HV - stranded copper
2. LV - copper bar or flexible copper base on LV ratedcurrent.
It is hermetically sealed type and full fill with insulation liquid.
Oil expansion or contraction due to the change in the
transformer load is accommodated by the corrugated finwall
of the transformer tank.
Corrugated fins are use to
provide sufficient cooling
surface to dissipate the heat
generated by the windings.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
18/121
Both HV & LV is open bushing termination.
Cable Box
Core Cutting
Core
Building
Tanking
Process
Despatch Finishing Testing
Paper Covering
High Voltage
Winding
Drying
Process
1. Rectangular copper
2. Foil Sheet
Fabrication
Vacuum & Oil
Filling
Low Voltage
Winding
Core Winding
Assembly
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
19/121
&
Phasor Relationships
Transformer winding connections
produced a Phase Shift between primary
& secondary
Angle of phase shift depend upon the
winding connection method adopted for
primary and secondary
&
Phasor Relationships
Eg.
Phase Shift of secondary
windings is +30 wrt primary
designated with Dyn11
Significant of Phase Shift Paralleling of Transformer &
interconnection of system
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
20/121
&
Tapping & Tap Changers
&
Tapping & Tap Changers Functions
To compensate for changes in the appliedvoltage on bulk supply
To compensate for regulation within thetransformer & maintain the output voltageconstant
To assist in the control of system VArs flows
To allow for compensation for factors notaccurately known at the time of planning
To allow for future changes in system conditions
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
21/121
& Type of Tap Changers
On-Load Tap Changer (OLTC)
Off Circuit Tap Changer (OCTC)
Tap Changer Mounting
Internal (In-tank)
External (Side mounted)
&
OLTC Technology
Oil Type OLTC
Vacuum Type OLTC (Vacutap)
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
22/121
& OLTC Main Components
Tap Selector
Diverter Switch
Selector Switch
Change-over selector
Transition Impedance
&
Motor Drive Mechanism to operate OLTC
Step-by-step control
Tap Position Indicator
Limiting Devices
Parallel Control Devices
Emergency Tripping Device
Overcurrent Blocking Device Restarting Device
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
23/121
Pressure Relief Device
Gas & Oil Actuated Relays (Buchholz)
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
24/121
Temperature Indicators
Winding HV & LV
Top Oil
Fans Control
Oil Level Indicators
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
25/121
Other Ancillary Equipment
Conservator Tank
Cooling System/Radiators
Bushings
Cable Box
Oil Valves
Thermometer Pockets
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
26/121
( & )( & )
200 200
Transformer Insulating Oil
& Paper Diagnostics
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
27/121
& &
1. Oil Quality Test
Physical Properties
Visual Appearance
Colour
Flash Point
Viscosity
Density
Pour Point
IFT
Particle Count
& &
1. Oil Quality Test
Chemical Properties
Moisture Content
Acidity
Corrosive Sulphur
Oxidation Stability
Sludge Sediment
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
28/121
& &
1. Oil Quality Test
Electrical Properties
Breakdown Voltage
Dissipation Power Factor
2. DGA
Life Span of Power Transformers Depends on Integrity of Insulation
Most Commonly Used Insulations for Power Transformers
OIL
Provides overall insulation to the transformers
Acts as coolant in extinguishing arcs
Provides the means to monitor insulation condition and operation of
transformers
PAPER
Provides insulation to the conductor in the transformer windings
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
29/121
PRIMARY STRESSES
1. Stresses applied on the transformer due to normal
operation:
Thermal
Electrical
Mechanical
2. Application of these stresses can be:
Continuous
Cyclic Intermittent
SECONDARY STRESSES
1. Factors that can influence the ageing rate when primary
stresses are applied
2. Simply known asAgeing Factors
Examples of these Ageing Factors can be:
3. Operational factors of the transformers
Environmental factors i.e. radiation, moisture or
water, oxidative agents and corrosive materials
Technological factors i.e. type of oil and paper used Tests done on the transformers that can influence
the performance of the insulation system
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
30/121
Oil Insulation Deterioration Reversible
1. Oil insulation condition can be reversed through on-line filtration
2. Can reduce the effect of the Ageing Factors
3. Can prolong serviceability of the oil insulation
Paper Insulation Degradation Irreversible
Paper insulation degradation is irreversible
Oil filtration has negligible effect on reversibility of paper
degradation
Ageing of paper directly linked to its mechanical
strength
Loss of mechanical strength eventually leads to loss of
dielectric strength
Once paper loses its dielectric strength, the transformer
is deemed to have reached the end of its service life
Thus, the life of a transformer can be effectively
determined by the life of its paper insulation
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
31/121
Three most common degradation factors of cellulose:
Thermal
1. When exposed to heat up to 220C, the glycosidic bond tend to
break and open the glucose molecule rings
2. By-products:
Free glucose
H20
CO
CO2
Organic acids
Glycosidicbonds broken
and glucose
rings opened
Generates the
following:
H20 CO CO2
H
O
OH
Heat
Three most common degradation factors of cellulose:
Oxidative
1. Presence of oxygen promotes oxidation
2. Glycosidic bond weakens
3. Causes scission to the cellulose chain
4. By-products include H20
Hydrolytic
1. Presence of water and acids
2. Glycosidic bond exposed to slicing
3. Causes scission to the cellulose chain
4. By-products include free glucose
Glycosidic
bonds
weakened
and
moisture
produced
CH2OH
COOH COOH
CHO
O2
Free glucoseproduced
HO OH
CH2OH
H20 or acids
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
32/121
Degradation By-Products
1. It can be observed that by-products related to paper degradation
can include the followings:
CO
CO2 H2O
Organic acids
Free glucose molecules
2. With H2O and organic acids present in the oil, the free glucose
molecules can degrade to 5-hydroxymethyl-2-furfuryl or 5H2F
Degradation By-Products
3. 5H2F is an unstable free glucose molecule and can decompose
further to other furaldehyde as follows:
2-furfuryl alcohol (2FOL)
2-furaldehyde (2FAL)
2-acetyl furan (2ACF)
5-methyl-2-furfuryl (5M2F)
4. All these 5 compounds of glucose or degradation of glucose are
known as Furans.5. 2FAL is the most stable in the group
6. Furan generation is exclusively due to paper degradation unlike
CO, CO2, H2O or acids which can also be produced through oil
oxidation or breakdown.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
33/121
When taking an oil sample from a sealed tanktransformer, ensure that the transformer is not undervacuum by checking the vacuum/pressure gauge
Use a clean glass syringe/beaker (provided by thelaboratory) and follow the proper sampling procedure
ASTM D923 & D3613 (IEC 60475 & IEC 60567)
Interpret the quantified results to help determine therelative health of the transformer, offer clues to the origin
of potential problems and develop a strategy to avoidcatastrophic failure IEEE C57.106
Important factors to be considered prior to taking asample:
1. Sample Containers
2. Sampling Technique
3. Weather condition
4. Sample storage and transport
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
34/121
Characteristic of Sample Containers: 500 ml or 1 liter (Duplicate)
Syringe DGA
Seal the sample from external contamination
Store samples in the dark to prevent from photo-degradation
Cleaning and preparation of valves
Avoid liquid spillage, some oil may still contains PCBs Identification of the sample and apparatus information
Sampling outdoors in rain, strong wind and night time
should be avoided
Should not be stored longer than a few days beforesending to the laboratory for analysis
Dark Brown
Bottle
500 mL
Valve
Adaptor
Plastic
tube Cap
Transformer
Seal
Waste
Vessel
Filled
Sample
bottle
Use correct vessel (good cap and seal)
Sufficient sample
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
35/121
Valve
Adaptor
Plastic
tubeSyringeTransformer
Waste
Vessel
Sufficient sample
To effectively interpret DGA results requires insights in
the characteristics of dissolved gas in oil evolution, an
understanding of transformer design, and knowledge of
materials used by transformer manufacturer and
operating conditions ASTM D3612
ASTM D3612 Test methods for analysis of dissolved
gases by gas chromatography
IEEE C57.104 Guide for interpretation of gases
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
36/121
On-Line Assessment of Insulation Condition
1. Oil Quality Tests to assess the physical, electrical and
chemical properties of the oil
2. Dissolved Gas-in-oil Analysis to detect and identify
incipient faults
3. Furan Compound Analysis to detect and identify
degradation of paper insulation (on-line test)
4. Degree of Polymerization Test to measure
degradation of paper insulation (intrusive mechanism)
Oil Screening Tests
1. Colour serious contamination
2. IFT moisture in oil (> 15 mN/ m)
3. Neutralization Number level of acidity (< 0.2 mg KOH / gm)
4. Dielectric Strength contaminants (water & conducting
particles) ( > 30 kV)
5. 5. Water Content amount of dissolved water in ppm
(< 30 ppm)
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
37/121
IEEE C57.106 Limits Oil Quality Tests
Colour 0.5
IFT > 25 mN/ m for 69 kV
Neutralization Number < 0.2 mg KOH / gm
Dielectric Strength > 20 kV for 69 kV for 1 mm gap
Water Content < 27 ppm for 69 kV at 50 0C
Other Oil Quality Tests
Specific Gravity
Viscosity
Power Factor
Resistivity
Flash Point
Visual PCB Content
Inhibitor Content
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
38/121
Water Content (D 1533 / IEC 733)A low water contentis necessary to obtain and maintain acceptable electricalstrength and low dielectric losses in insulation systems.
Color (D 1500) The color of a new oil is generallyaccepted as an index of the degree of refinement. Foroils in service, an increasing or high color number is anindication of contamination, deterioration, or both.
Dielectric Breakdown (D 877 / D 1816 / IEC 156) It is ameasure of the ability of an oil to withstand electricalstress at power frequencies without failure. A low value
for the dielectric-breakdown voltage generally serves toindicate the presence of contaminants such as water,dirt, or other conducting particles in the oil.
Neutralization Number, NN (D 664)A used oil having a highneutralization number indicates that theoil is either oxidizedor contaminated with materials such as varnish, paint, or otherforeign matter.
Interfacial Tension, IFT (D 971) The interfacial tension of anoil is the force in dynes per centimeter or millinewton permeter required to rupture theoil film existing at an oil-waterinterface. When certain contaminants such as soaps, paints,varnishes, and oxidation products are present in theoil, thefilm strength of the oil is weakened, thus requiring less forceto rupture. For oils in service, a decreasing value indicates theaccumulation of contaminants, oxidation products, or both.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
39/121
Index = IFT/NN. This index provides a more sensitive andreliable guide in determining the remaining useful life of atransformer oil. A Index below 100 indicates that theoil issignificantly oxidized and that theoil needs to be replaced inthe near future.
Non-fault gases - Oxygen (O2) & Nitrogen (N2)
Note: If the ratio O2/N2 is less than 0.3 then it indicates overheating
of oil. This is not a standard, use with caution.
Fault gases - Hydrogen (H2), Acetylene (C2H2)
Carbon Monoxide (CO), Carbon Dioxide
(CO2) Ethylene (C2H4), Ethane (C2H6)Methane (CH4)
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
40/121
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
41/121
Dissolved Gas-in-oil Analysis
Fault Condition Key Gases
Overheated Oil Methane, Ethane & Ethylene
Partial Discharge Hydrogen & Acetylene
Overheated Cellulose Carbon Monoxide & Carbon
Dioxide
Non-Fault Gases are Oxygen & Nitrogen
Dissolved Gas-in-oil Analysis
Fault Condition Key Gases
Thermal Oil Major Ethylene & Methane
Minor Ethane & Hydrogen
Electrical low energy Major Hydrogen & Methane
Minor Ethane & Ethylene
Electrical high energy Major Acetylene & Hydrogen
Minor Ethylene & Methane
Thermal Cellulose Major Carbon monoxide & Carbon dioxide
Minor Methane & Ethylene
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
42/121
IEEE Limit
Hydrogen (H2) 100 ppm
Oxygen (O2) N/A
Nitrogen (N2) N/A
Carbon Monoxide (CO) 350
Methane (CH4) 120
Carbon Dioxide (CO2) 2500
Ethylene (C2H4) 50
Ethane (C2H6) 65 Acetylene (C2H2) 35
Dissolved Gas-in-oil Analysis
Ratio Method is used for fault analyzing, not for fault detection.
Ratio Method Ratios
Rogers C2H2/C2H4 , CH4/H2 & C2H4/ C2H6
IEEE CH4/H2, C2H2/C2H4, C2H2/ CH4, C2H6/ C2H2,C2H4/ C2H6
Never make a decision based on only ratio. Take into consideration
the gas generation rates and amount of total combustible gases.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
43/121
Rogers Ratio comparison methods look at pairs of gases, anddevelop a coding system to help define potential fault conditions
Rogers Ratio Code
C2H2 / C2H4 CH4 / H2 C2 H4 / C2H6
< 0.1 0 1 0
0.1 -
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
44/121
TDCG (ppm) Status Remark
720 Condition 1 Transformer working satisfactorily. Look
for individual gas exceeding respective limit.
721-1920 Condition 2 Faults may be present. Additional
investigation required based on individual
gas exceeding respective limit.
1921-4630 Condition 3 Faults probably present. Additional
investigation required based on individual
gas exceeding respective limit.
> 4630 Condition 4 Continued operation could result in failure of
the transformer
As per IEEE C57.104
CO2/ CO ratio indicates cellulose degradation
CO2 / CO ratio Condition of Cellulose
< 3 Severe Arcing & Short circuit damage
3 -
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
45/121
( )
Transformer Gas Analysis
Component ppm in oil
HYDROGEN (H2) 10
OXYGEN (O2) 26200
NITROGEN (N2) 48500
CARBON MONOXIDE (CO) 41
METHANE (CH4) 5
CARBON DIOXIDE (CO2) 570
ETHYLENE (C2H4) 2
ETHANE (C2H6) 2ACETYLENE (C2H2) 1
Transformer Gas Analysis
Component ppm in oil
HYDROGEN (H2) 720
OXYGEN & ARGON (O2 + A) 17000
NITROGEN (N2) 45400
CARBON MONOXIDE (CO) 405
METHANE (CH4) 1310
CARBON DIOXIDE (CO2) 6050
ETHYLENE (C2H4) 5200
ETHANE (C2H6) 1810
ACETYLENE (C2H2) 256
( )
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
46/121
Transformer Gas AnalysisComponent ppm in oil
HYDROGEN (H2) 105
OXYGEN & ARGON (O2) 18000
NITROGEN (N2) 33400
CARBON MONOXIDE (CO) 870
METHANE (CH4) 400
CARBON DIOXIDE (CO2) 12,100
ETHYLENE (C2H4) 260
ETHANE (C2H6) 28
ACETYLENE (C2H2) 52ppb in oil
2FAL 195
( )
Transformer Gas Analysis
Component ppm in oil
HYDROGEN (H2) 103
OXYGEN & ARGON (O2 + A) 16762
NITROGEN (N2) 20458
CARBON MONOXIDE (CO) 0
METHANE (CH4) 814
CARBON DIOXIDE (CO2) 1816
ETHYLENE (C2H4) 109ETHANE (C2H6) 75
ACETYLENE (C2H2) 118
ppb in oil
2FAL 225
( + )
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
47/121
Furanic Compound Analysis
Fault Condition Furan Compound
Overheating or Short circuit 2FAL
Excessive Moisture 2FOL
Lightning Strikes 2ACF
Intense Overheating 5M2F
Oxidation 5H2F
Concentration limits of furan compounds must be supported by
CO2/CO Ratio to assess paper degradation
2FAL limits (ppb in oil):
58 292 Normal Aging
654 2021 Accelerated Aging
2374 3277 Excessive Aging
3851 4524 High Risk of Failure
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
48/121
Criteria to select transformers for further investigation
Transformer Age
Operational Criterion number of faults, switching, lightning, etc.
DGA Criterion (oil) Individual concentrations of CH4, C2H2,
C2H4, C2H6 & H2 in ppm & Rogers/IEEE Ratio
DGA Criterion (paper) Individual concentrations of CO2 & CO in
ppm & CO2/CO Ratio
Furan Criterion 2FAL concentration in ppb & others if detected
Correlation between TS, DP and Furan
Ageing of paper insulation is related to the decrease in
TS.
TS is directly related to DP ASTM D 4243.
Decrease in DP is directly related to the increase in
Furan.
Thus, as paper aged, it loses its TS. Loss of TS
indicates decrease of DP. Decrease of DP causes
increase in Furan in the insulating oil. It can be deduced
that as paper aged towards its end of service life, the
level of Furan content increases.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
49/121
Degree of Polymerization
One of the most dependable means of determining
paper deterioration and remaining life of the cellulose.
The cellulose molecules is made up of a long chain of
glucose rings which form the mechanical strength of the
molecule and the paper.
DP is the average number of these rings in the
molecule.
As paper ages or deteriorates from heat, acids, oxygen
and water the number of these rings decrease.
Degree of Polymerization
Following Table has been developed by EPRI to estimate
remaining paper life
1. New insulation 1000 DP to 1400 DP
2. 60% to 66% life remaining 500 DP
3. 30% life remaining 300 DP
4. 0 life remaining 200 DP
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
50/121
The life of a transformer can be effectively determined by the life of its
paper insulation.
DP is considered direct approach to determine the paper insulation
condition but it is intrusive. Some are skeptical since integrity of paper
insulation may be disturbed and may further damage the paper insulation.
Alternatively, it can be achieved through the use of paper degradation by-
products e.g. CO, CO2, CO2/CO, 2 FAL, H2 as indicators. It is non-intrusive
and requires only samples of the transformer oil which can be obtained
without any shutdown.
The challenge is to develop a Mathematical Model to Estimate DP Value of
Paper Insulation based on the Paper Degradation By-Products i.e.
DP = f(CO, CO2, CO2/CO, 2 FAL, H2)
By plotting the relative percentages of methane, ethylene
and acetylene onto a special triangular coordinatesystem, a graphical output of the likely cause of gassingis generated.
The causes are categorized as follows.
D1 Discharges of low energy
D2 Discharges of high energy
T1 Thermal faults < 300C
T2 Thermal faults 300C to 700C
T3 - Thermal faults > 700C
DT Mixture of thermal and electrical faults
PD Partial discharge (No samples indicated this typeof fault)
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
51/121
The following gas levels were detected via DGA on the
oil from the load tap changer:
42 ppm of methane
17 ppm of Ethylene
0 ppm of acetylene
Calculate percentages of each gas and use Duvals
triangle approach to find the cause
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
52/121
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
53/121
( & )( & )
2008 2008
Transformer Basic On-Site &Off Line Diagnostic Testing
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
54/121
1. Basic Electrical Tests
Insulation Resistance Traditional Polarization Index (PI) test
to detect moisture content
Tan Delta To detect water in cellulose
and chemical contamination
Winding Resistance To detect open or short circuits or poor electrical connection in
the windings Turns Ratio
To detect Shorted Turns
Insulation Condition
Assessment
2. Advanced DiagnosticTests
Frequency Response Analysis (FRA)
Recovery Voltage Measurement (RVM)
Polarization Depolarization (PDC)
Frequency Dielectric Spectroscopy (FDS)
Partial Discharge (PD)
OLTC Motor Current Signature Analysis (MCSA) OLTC Vibration Signature Analysis (VSA)
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
55/121
Categorization of On-site Tests
Destructive off-line tests are go/no go tests
Non destructive off-line tests are diagnostic
tests
Non destructive on-line tests are condition
monitoring tests
These on-site tests are performed individually or in
combination :
Before energizing a new equipment as a
commissioning test
After maintenance After network alteration
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
56/121
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
57/121
105
130
155
180
220
Class A Class B Class F Class H Class C100
125
150
175
200
225
250
De
greesCentigrade
Insulation Classes by Degrees Centigrade
Class SClass R
240 240+
Class N
200
Insulation resistance test (a)
Insulation current test (b)
Power factor (c)
DC voltage withstand (d)
AC voltage with-stand (e)
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
58/121
Method (e) is primarily used in factory tests
Method (d) is primarily used as commissioning test
Practically all routine field tests are made using
nondestructive methods (a), (b) and (c)
Methods (a) and (c) must also be used as
commissioning test
No single test method can be relied upon for
indicating all conditions of weakened insulation
Basic Electrical TestsInsulation Resistance
Reading corrected to 20oC
Insulation resistance varies inversely with temperature for
most insulting materials
To properly compare periodic measurements of insulation
resistance, it is necessary either to take each measurement
at the same temperature, or to convert each measurement to
the same base temperature i.e. 200C
Polarisation Index is the ratio of the IR reading after 10
minutes to the IR reading after 1minute PI is used as an index of dryness
Discharge the winding after a Polarisation Index Test for
sufficient time before handling or performing other tests
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
59/121
Polarization Index
Interpretation of Polarization Index (PI) Measurements
PI Value Interpretation
> 4.0 Healthy
4.0 2.0 OK
2.0 1.5 Marginal Pass
1.5 1.0 Deteriorated condition
< 1.0 Failure
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
60/121
Volume Current
Insulation Resistance
Tester
Surface leakagecurrent
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
61/121
Capacitive
Current
DielectricAbsorption
Current
Conduction
Current
Total
current
Time
A
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
62/121
3
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
63/121
Effect of Previous Charge
Effect of Temperature
Effect of Moisture
Effect of Age and Curing
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
64/121
Hot resistance test - at least 4 hours after shutdown from full-loadoperation, or until temperature is stabilized:
Disconnect the equipment to be tested from other equipment
Ground the winding to be tested for at least 10 minutes
Remove the ground connection and connect the insulationresistance tester
Take readings at 1 -minute and at 10 minutes
Record the temperature of equipment being tested
Ground the winding again for at least 10 minutes
Cold resistance test - Four to eight hours after the hot resistance test or
when equipment has cooled to approximately ambient temperature Use same procedure as outlined for the hot resistance test
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
65/121
Dry type insulation 40C ambient
Liquid type insulation 20C ambient
Insulating materials have negative resistance
characteristics
Spot test reading must be corrected to a base
temperature
Conversion Factors For ConvertingInsulation Resistance Test Temperature to 20 C
Temperature Multiplier
C F
Apparatus
Containing Immersed
Oil Insulations
Apparatus
Containing Solid
Insulations
0 32 0.25 0.40
5 41 0.36 0.45
10 50 0.50 0.50
15 59 0.75 0.75
20 68 1.00 1.00
25 77 1.40 1.30
30 86 1.98 1.60
35 95 2.80 2.05
40 104 3.95 2.50
45 113 5.60 3.25
50 122 7.85 4.00
55 131 11.20 5.20
60 140 15.85 6.40
65 149 22.40 8.70
70 158 31.75 10.00
75 167 44.70 13.00
80 176 63.50 16.00
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
66/121
Polarization index = R10/R1 = I1/I10
(keeping voltage constant)
where:
R10 = megohms insulation resistance at 10 minutes
R1 = megohms insulation resistanceI at 1 minute
I1 = insulation current at 1 minute
I10 = insulation current at 10 minutes
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
67/121
INSULATION 60/30 SECOND RATIO 10/1 MINUTE RATIO
CONDITION Dielectric Absorption Ratio Polarization Index
Dangerous Less than 1 Less than 1
Poor Less than 1.1 Less than 1.5
Questionable 1.1 to 1.25 1.5 to 2
Fair 1.25 to 1.4 2 to 3
Good 1.4 to 1.6 3 to 4
Excellent Above 1.6 Above 4
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
68/121
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
69/121
PI & DLF
PI
If a PI falls by 30% or more from the previous value then remedial
action such as cleaning, oil-filtering or further investigation should
be considered.
Tan Delta
If the IFT and oil moisture content exceed their respective limits
then Tan Delta test is recommended. This is a good complement to
PI test and as remedial action drying is usually performed.Field test results must be corrected to 20o C before comparison.
Tan Delta (DLF) test
In on site tan delta measurement there are two modes namely Grounded
Specimen Test (GST) and Ungrounded Specimen Test (UST). During GST
mode, the dielectric loss of insulation between one of the windings to
ground will be measured depending on the winding that is being excited.
Under UST mode, dielectric loss of insulation between the two windings
will be measured irrespective of the winding being excited.
The ratio obtained from the field test should agree with nameplate
value within 0.2% for the insulation system between the high
voltage and low voltage winding at all taps. Otherwise, winding
repair is recommended.
The ratio obtained from the field test should be within the limit of
0.5% for the insulation system between the high voltage winding
and ground. Otherwise, winding repair is recommended.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
70/121
Power Factor = cos = ir / it
900 =
Dissipation Factor = tan = ir / ic
For small , Cos (90 ) = tan
tan = ir / ic
ic = CV
ir = CV tan
Power loss (dielectric loss) = V ir= CV2 tan watt
Dielectric loss is dependent on voltage and frequency Variation of tan with voltage is an important diagnostic method
and will be part of this course
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
71/121
Power factor or dissipation factor is a measure of insulation
dielectric power loss
Not a direct measure of dielectric strength
Power-factor values are independent of insulation area orthickness
Increase in dielectric loss may accelerate insulationdeterioration because of the increased heating
Insulation power factor increases directly with temperature
Temperature corrections to a base temperature must bemade, usually to 20 degree C
Windings not at test potential should be grounded
Refer to IEEE Standard No. 262, 1973
Test sets consist of a completely shielded, high-voltage,50-Hz power supply which applies up to 10 kV to theequipment being tested
Much simpler and less expensive tester is also availablewhich applies about 80 volts to the equipment being
tested but not sufficiently shielded against inducedvoltages
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
72/121
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
73/121
From IEEE Standard No. 262, 1973
where:
FP20 = power factor corrected to 20 degree C
FPT = power factor measured at T degree C
T = test temperature
K = correction factor from table
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
74/121
Material Power Factor approx.)
Bakelite 2 - 10%
Vulcanized Fibre 5%
Varnished Cambric 6 - 8%
Mica 2%
Polyethylene 0.03%
New Insulating Oil 0.01-0.2%
High Voltage DC/AC Test
The voltage is slowly raised in discrete steps, allowingthe leakage current to stabilize for a predetermined time
A plot of the leakage current as a function of test voltageyields information on the condition of the insulation
If the curve is a straight line, it indicates good conditionof the cable
If the current begins to increase at a rapid rate, indicatesdegradation / defects in the cable insulation
After the completion of the test, the cable under test isgrounded for sufficient time to discharge the voltagebuild up due to effects of absorption currents
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
75/121
HVDC
A
Applied Voltage (% of Maximum Voltage)
20 40 60 80 100
20
40
60
80
100
120
HealthyIndicates
Concern
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
76/121
, /
Very little supply power is required to operate the DCtest set
The DC test set is portable and smaller than an ac, high-voltage tester
Disconnect the buswork from the unit
The dc breakdown voltage may range from 1.41 timesthe rms ac breakdown voltage to 2.5 times the rms acpuncture voltage
Cases have indicated that on winding insulation withsome deterioration, the application of overpotential testsmay cause further deterioration, even though theinsulation may not puncture
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
77/121
The machine winding should be grounded for at least 1hour before conducting the test
The phases should be separated and tested individually
Lightning arresters and capacitors must be disconnected
Cables and/or buswork should be disconnected if it isconvenient to do so
If the separation of phases is difficult then separation isneeded once for the benchmark tests, and thereafter thephases may be tested together until deviation from normalis detected
The voltage should be raised abruptly to the first voltagelevel with the start of timing for the test.
The ratio of the 1-minute to the l0-minute reading ofinsulation current will afford useful indication ofpolarization index
This gives the test engineer an idea of insulation drynessearly in the test
The test schedules are arranged to include a minimum ofthree points up to and including the maximum voltage
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
78/121
If the insulation microampere versus voltage plots arestraight lines, the test may be continued to the maximumtest voltages
The quality of the insulation may be judged by theposition of any curvature or knee in the plot of insulationcurrent versus test voltage
If curvature or knee appears, the test should be stopped
Upon completion of the dc, high- voltage test, thewinding should be discharged through the specialdischarge resistor usually provided with the test set
The winding may be solidly grounded when the voltagehas dropped to zero or after a few minutes of discharge
have occurred A winding should remain solidly grounded long enough
before restoring the machine to service
,
The ramped technique of insulation testing uses aprogrammable dc, high-voltage test set andautomatically ramps the high voltage at a preselectedrate (usually 1 kV/min)
Insulation current versus applied voltage is plotted on anx-y recorder providing continuous observation andanalysis of insulation current response as the testprogresses
The principal advantages of the ramp test over theconventional step method is the elimination of the humanfactor which makes it much more accurate andrepeatable
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
79/121
/
High Voltage DC/AC
Less capable of revealing voids or cavities left inside theaccessories
Useful in detecting the defects related to contaminationalong the interface between the different components ofthe insulation system
Voltage applied is usually three to four times the nominalphase-to earth voltage for 15 minutes or more
This is destructive test
Turns Ratio test
This test only needs to be performed if a problem is suspected
from the DGA.
It indicates shorted turns.
Shorted turns may result from short circuits or dielectric
(insulation) failures.
The ratio obtained from the field test should agree with the factory
within 0.5%. Otherwise winding repair is recommended.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
80/121
Turns Ratio test
Turns Ratio test
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
81/121
Winding Resistance test
This test only needs to be performed if there is a high rate of generation
of ethylene and ethane.
Turns ratio test give indications that winding resistance testing is
warranted.
Resistances measured in the field can be compared to the original
factory measurements or to sister transformers.
Agreement within 5% for any of the above comparisons is considered
satisfactory.
If winding resistances are to be compared to factory values, resistances
measurements will have to be converted to the reference temperature
used at the factory.
Winding Resistance test
Since the winding resistance changes with temperature, the winding and oil
temperatures must be recorded at the time of measurement and all test
readings must be converted to common temperature to give meaningful results.
Most factory test data are converted to 75C which has become the most
commonly used temperature.
Rs = Resistance at the factory reference temperature (found in t he transformer
manual)
Rm = Resistance you actually measured
Ts = Factory reference temperature (usually 75 C)
Tm = Temperature at which you took the measurements
Tk = A constant for the particular metal the winding is made from:
234.5 C for copper 225 C for aluminum
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
82/121
Four terminal testing set up
V
I
P1 P2C1 C2
Measured Resistance (R) = V/I
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
83/121
( & )( & )
00 00
Transformer Advanced Off-LineDiagnostic Testing
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
84/121
Most of the techniques, whether chemical or electricalmethods, or destructive or non-destructive methods, onlyprovide partial information about the state of theinsulation condition of power transformers.
More advanced condition monitoring or conditionassessment techniques have been developed and arenow starting to come into more general use.
They have been developed in response to the need fornew materials assessment methods.
However, in some advanced diagnotics tools are still in
the developmental stage, either in the technicaldevelopment or, more likely, in the methods of analysisand interpretation of the test data.
Recovery Voltage Measurement (RVM)
Polarization and Depolarization Current Measurement (PDC)
Frequency Domain Dielectric Spectroscopy (FDS)
Frequency Response Analysis (FRA)
Partial Discharge (PD) Measurement
RVM, PDC & FDS are based on the used of the dielectricresponse of insulating materials to the application of electricfields Conductivity, Polarization & Dielectric Response
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
85/121
When a dielectric material with polar molecular structure issubjected to a DC voltage, the electric dipoles are oriented withinthe material in response to the applied electric field.
There is thus a polarization charge induced by the dipolemovement and realignment and this will effectively give a voltageacross the capacitance. When the dielectric is short circuited, thestored charge in the dielectric capacitance is dissipated by acurrent discharge with a time constant determined by theeffective intrinsic resistance and capacitance.
During the short circuit the voltage across the dielectric is zero,but when the short circuit is removed before total charge to
equilibrium occurs, then a voltage will appear across thedielectric. This measured voltage is known as the recoveryvoltage.
()
()
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
86/121
()
A dielectric material becomes polarized when exposed to an electric field.Polarization is proportional to the intensity of the electric field and bymeasuring the current, polarization process can be observed. The currentdensity is the sum of the conduction current and the displacement current.
When the insulating material is exposed to a step voltage, polarizationcurrent is obtained. If the step voltage is removed, a reverse polarity currentknown as depolarization current is obtained. These two currents can beused to determine the response function and the conductivity of thedielectric material.
The PDC is a DC testing method which determining the polarizationspectrum in time constant domain between 10e-3 10e3 seconds in whichthe interface polarization phenomena of long time constant are active. The
range of polarization is strongly influenced by the absorbed moisture andthe deterioration by product content of the paper insulation. It applies a500V step of DC voltage to the high or low voltage winding insulations oftransformers. Time of voltage application is typically up to 10000 seconds.Both the polarization and depolarization times are performed for the sameperiod of time.
& ()
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
87/121
The polarization current pulse has a peak magnitude, a finalsteady state level and a time constant and duration that aredetermined by the quality of the oil including both the moisturelevel and the electrical conductivity. In genera the electricalconductivity affects the peak current in the first 100 seconds orso of the current pulse. The moisture in the insulation affects thelonger term polarization current level after about 1000 seconds.[Figure 8.6]
Polarization and depolarization current measurement methodgives general information about the state of insulation condition.This technique is proved to be a useful testing method inpredicting of moisture and development of ageing phenomena.
& ()
Effect of moisture in oil and cellulose paper on the polarizationdepolarization current measurement
& ()
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
88/121
In the FDS technique, a known sinusoidal voltage is applied andmeasured together with the current passing across the insulationmaterial.
The measurement is repeated for several frequency sweeps -from high frequency to low frequency for minimizing the memoryeffects.
Advantage - the complete diagnostic on the property change inthe material can be discerned
By dividing the current by the voltage and comparing the phasedifference, both the capacitance and the loss at the particularfrequency and amplitude can be calculated.
()
The advantage of an analysis of the dissipation factor frequencyas compare at fixed frequency:
Behaviour of insulation caused by moisture affects can be evaluated.
At higher frequencies the pressboard and the oil volume determinethe dielectric loss, at medium frequencies the oil conductivity is thedominant factor and the lower frequency range is dominated by thepressboard dielectric loss.
()
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
89/121
Example on how moisture affects the dissipation factor of kraftpaper at 20C
()
Measurement results of the insulation between primary andsecondary to tertiary windings on a power transformer.
()
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
90/121
PROGRAMMA IDA 200 ()
How do you know whether you can energize A
TRANSFORMER after transportation to site or
after a protection trip?
Check Mechanical Integrity
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
91/121
When does Mechanical Integrity matter?
Re-location
Short Circuit
Lightning
Tap-changer fault
Transportation damage can occur if the clamping andrestraints are inadequate; such damage may lead to coreand winding movement.
Radial buckling or axial deformation may occur due toexcessive short circuit forces while in service.
What you can identify by checking mechanical integrity?
Core Movement
Winding Deformation
Faulty Core Grounds
Partial Winding Collapse
Hoop Buckling
Broken or Loosened Clamping Structures Shorted Turns and Open Windings
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
92/121
What Test can be Done?
Frequency response analysis (FRA) using a
low voltage AC wave of varying frequency to
identify changes in natural resonance
Why FRA?
FRA Technique: The technique covers the full dynamic range andmaintains the same energy level for each frequency, providing resultsthat are repeatable and accurate.
Impulse Technique: This technique requires high sampling rates andhigh resolution to obtain a valid measurement. The applied impulse does
not produce constant energy across the specified frequency, which cancause poor repeatability that is influenced by the non-linear properties ofthe test specimen.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
93/121
What is FRA ?
FRA is a tool that can give an indication of core or windingmovement in transformers.
This is done by performing a measurement to look at how wella transformer winding transmits a low voltage signal that variesin frequency.
Transformer does this in relation to its impedance, thecapacitive and inductive elements which are intimately relatedto the physical construction of the transformer.
Changes in frequency response as measured by FRA
techniques may indicate a physical change inside thetransformer, the cause of which then needs to be identified andinvestigated.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
94/121
Test Equipment
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
95/121
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
96/121
What is the frequency range?
The measured frequency range is normally very large,
which can be from 5Hz up to 10MHz
This frequency range covers the most important
diagnostic areas:
Core and Magnetic Properties Winding Movement and Deformation
Interconnections-Leads and Load Tap Changer
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
97/121
The magnitude and the angle of the complex transfer functioncan be obtained using a network-analyzer
The resulting amplitude of the measurement can be expressedas,
H (dB) = 20 log10 [(ZS)/(ZS+ZT)]
The resulting phase is defined by
H () = tan-1 [(ZS)/(ZS+ZT)]
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
98/121
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
99/121
What are the ANALYZING TECHNIQUES?
Signature
Difference
Transfer Function
Statistical
FRA Signatures are analyzed based on 3 bandmethods
What do the 3 Bands mean?
5Hz up to 10KHz defect in core and magnetic
circuit
10KHz up to 600KHz deformation in winding
geometry
600KHz up to 10MHz abnormalities in theinter-connection and test
system
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
100/121
SIGNATURE TECHNIQUE
SIGNATURE TECHNIQUE
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
101/121
SIGNATURE TECHNIQUE
DIFFERENCE TECHNIQUE
(Phase A before)
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
102/121
DIFFERENCE TECHNIQUE
(Phase A after)
DIFFERENCE TECHNIQUEThis technique can analyze the windings phase by phase, which is not
possible in the signature technique
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
103/121
Historical data or Baseline Reference are, undoubtedly,the best reference to be used for FRA analysis
However, it is not practically easy to get historical data dueto constraints of outages
Criteria to choose reference FRA measurements in theabsence of historical data or baseline reference
DifferentDifferentSameSamePeer
DifferentSameSameSameSister
SameSameSameSameTwin
S/S
LOCATION
MANU-
FACTURER
MVA
RATING
KV RATIOCATEGORY
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
104/121
What is PD Electric discharge that do not completelybridge the electrodes
Discharge magnitude is usually small but can causeprogressive deterioration and lead to failure Overeating of dielectric boundary
Charges trapped in the surface
Attack by ultraviolet rays & soft X-rays
Formation of chemicals such as nitric acid & ozone
Therefore presence of PD need to be detected in a
non-destructive test
PD Classification
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
105/121
PD Classification
Occurrence of PD Inception Voltage
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
106/121
Occurrence of PD Inception Voltage
Occurrence & Recognition
Detection
Measurement
Location
Evaluation
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
107/121
Evaluation
Amplitude in dB
Energy or charge in pC
Duration in ms
On-line acoustic PD Detection - Physical Acoustic DISP-24
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
108/121
Why SFRA in a factory environment?
Quality assurance
Baseline reference
Relocation and commissioning preparation
Manufacturers are using SFRA as part of their quality program to ensure
transformer production is identical between units in a batch
Why SFRA in a field environment?
Relocation and commissioning validation Post incident: lightning, fault, short circuit, seismic event
etc
Once a transformer arrives on site after relocation it must be tested
immediately, to gain confidence in the mechanical integrity of theunit prior to commissioning
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
109/121
Frequency Response Analysis is a very effective tool for
diagnosing transformer mechanical integrity both in the
factory and in the field,
which cannot always be detected using other means
The best way to obtain baseline reference results is,
undoubtedly, on completion of the manufacturing
process at the factory
However, in the absence of baseline reference the
proposed criterion of twin, sister, and peer transformers
can be used as references with reasonable degree ofaccuracy
( ) Electrical Tests
Perform insulation-resistance tests winding-to-windingand each winding-to-ground
Perform turns ratio tests at the designated tap position
Perform power-factor or dissipation-factor tests
Measure the resistance of each winding at thedesignated tap position
Measure core insulation-resistance at 500 volts dc ifcore is insulated
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
110/121
Inspection - look for cracks, dirt etc., tracking, copper wash,
mechanical damage
Cleaning - Wash, dry wipe
Repairs - Usually replace except special cases
Testing - Megger & Power Factor test
Do not climb on or use for personal support!
( ) Visual inspection
Inspect physical condition for evidence of moisture and corona
Verify operation of cooling fans
Verify operation of temperature and level indicators, pressurerelief device, and gas relay
Verify correct liquid level in all tanks and bushings
Verify correct equipment grounding
Verify the presence of transformer surge arresters
Test load tap-changer
Inspect all bolted electrical connections for high resistance usingone of the following methods:
1. Use of low-resistance ohmmeter
2. Perform thermographic survey
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
111/121
( )
Electrical Tests
Perform turns ratio tests at all tap positions
Perform power-factor or dissipation-factor tests
Measure the resistance of each winding at all tap positions
Perform insulation-resistance tests winding-to-winding and eachwinding-to-ground
If core ground strap is accessible, measure core insulationresistance at 500 volts dc
Remove a sample of insulating liquid in accordance with ASTMD923
Test for Oil Quality, DGA and Furan
Diagnostic Testing provides a powerful tool for the
complete and economic assessment of the transformer
condition
There is nevertheless still a lack on how to integrate the
information obtained by the on-line monitoring into the
actions taken onto the service of the transformer
The supplementary information obtained by the off-linediagnostic after the detection of an abnormal condition is a
worth-full information to be integrated into future on-line
monitoring systems
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
112/121
( & )( & )
2008 2008
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
113/121
1. Scoring can be applied to test results to indicate
acceptable condition level of transformers.
Transformer condition indicator scoring is somewhatsubjective, relying on transformer condition experts.
Relative terms are used and compared to industryaccepted levels; or to baseline or previous(acceptable) levels on this transformer; or totransformers of similar design, construction, or age
operating in a similar environment.
2.
Weighting factors is used to recognize that some
condition indicators, affects the Condition Index to a
greater or lesser degree than other indicators.
These weighting factors were arrived at by
consensus among transformer design and
maintenance personnel with extensive experience.
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
114/121
3. Every transformer is unique and, therefore cannot
quantify all factors that affect individual transformer
condition.
It is important that the Transformer Condition Index
arrived at be scrutinized by experts.
Mitigating factors specific to the utility may determine
the final Transformer Condition Index and the final
decision on transformer replacement or
rehabilitation.
1.
Perform appropriate advanced
electrical tests tests as recommended
by the expert or internal inspection of
main tank immediately.
0% tan > 5
The monitoring frequency should be
revised to 3 months. Make arrangement
for advanced electrical tests tests.
14
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
115/121
2.
Perform appropriate advanced
electrical tests tests as recommendedby the expert or internal inspection of
main tank and OLTC tank
immediately.
0% deviation >0.5
The monitoring frequency should be
revised to 3 months. Make
arrangement for advanced electrical
tests tests.
10.3
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
116/121
4.
Perform appropriate advanced electrical teststests as recommended by the expert or
internal inspection of main tank
immediately.
0PI value < 1.0
The monitoring periodicity should be revised
to 3 months. Make arrangement for
advanced electrical tests tests.
11.0< PI value < 1.5
The monitoring periodicity should be revised
to 6 months.
21.0< PI value < 3.0
Normal. The monitoring periodicity of 24
months can be maintained.
3PI value 3.0
ActionScoreResults
This test is done on transformer tail at regular interval of 24 months under normal condition. This
test results are considered for condition assessment of an in-service transformer.
5().
0.2
0.4
0.1
0.3
Weightage
Power factor4
Acidity3
BDV2
Moisture1
CriteriaNo
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
117/121
5().
> 0.5
0.31 0.5
0.21 0.3
0.11 0.2
0.091 0.1
0.071 0.09
0.051 0.07
0.031 0.05
0.01 0.03
< 0.010
IFT
>0.31
0.25-0.3
0.21-0.24
0.17-0.20
0.13-0.16
0.1-0.12
0.07-0.09
0.05-0.06
0.02-0.04
50
246-50
341-45
436-40
531-35
626-30
721-25
816-20
911-15
100-10
Condition Indicator
Score
Moisture
(ppm)
6.
> 4000> 1400> 800> 150> 150> 80> 1420Condition 4
1916 -
4000
571 -
1400
401 -
800
101 -
150
101 -
150
46 - 80701
1420
Condition 3
721 -
1915
351 -
570
121 -
400
66 -
100
51 - 10036 - 45101
700
Condition 2
720350120655035100Condition 1
TDCGCOCH4C2H6C2H4C2H2H2Status
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
118/121
7.
1
2
23
4
5
5
6
7
8
8
9
10
ConditionIndicator Score
7
5-6
3-4
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
119/121
9. , &
Seek immediate advice from the expert
to perform advanced electrical test or
internal inspection
0Overall ranking 1.5
The monitoring periodicity should be
revised to 3 months. Make
arrangement for advanced electrical
tests.
11.5 Overall ranking 4.0
The monitoring periodicity should be
revised to 6 months.
24.0 Overall ranking 7.5
Normal. The monitoring periodicity of
12 months can be maintained.
37.5 Overall ranking 10
ActionScoreResults
This test is done on transformer at regular interval under normal condition. This test results are
considered for condition assessment of an in-service transformer.
10.
Indicates serious problem requiring immediate
evaluation, additional testing (if applicable)
and immediate consultation with experts
Subtract 1.5Significant deviation
Comparison between phases (using Cross-
correlation Index):
CCI at low freq zone
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
120/121
11.
Indicates serious problem requiring
immediate evaluation, additional
testing (if applicable) and immediate
consultation with experts
Subtract 1.5% moisture in paper > 4
Retest the transformer for FDS after 3
months. Arrange for replacement of
defective section(s).
Subtract 1.02 < % moisture in paper < 4
Retest the transformer for FDS after 6
months. The monitoring periodicity of
all basic electrical tests tests should be
maintained at 6 months.
Subtract 0.51.5 < % moisture in paper < 2
The monitoring periodicity of all basic
electrical tests tests should be
maintained at 6 months. Practice FDS
test if necessary.
Subtract 0% moisture in paper < 1.5
ActionScore
AdjustmentResults
12.
Indicates serious problem requiring
immediate evaluation, additional
testing and immediate consultation
with expert. Recommendation is to
remove the transformer from service
immediately.
Subtract 1.5Amplitude 80-90 dB
Energy 400-500
Duration 4000 ms-5000 ms
Retest the transformer for PD after 3
months. Arrange for replacement of
defective section(s).
Subtract 1.0Amplitude 70-80 dB
Energy 200-400
Duration 3000 ms-4000 ms
Retest the transformer for PD after 6
months. The monitoring periodicity
of all basic electrical tests tests should
be maintained at 6 months.
Subtract 0.5Amplitude 60-70 dB
Energy 200-300
Duration 200 ms-3000 ms
The monitoring periodicity of all
basic electrical tests tests should be
maintained at 6 months. Practice PD
test if necessary.
Subtract 0Amplitude 40-60 dB
Energy 1-200
Duration 100 ms-2000 ms
ActionScore
AdjustmentResults*
-
8/13/2019 Diagnostic Techniques for Condition Monitoring of Transformers
121/121