diesel generator set mtu 16v2000 ds1100 · bene ts — low fuel consumption — optimized system...
TRANSCRIPT
-
MTU 16V2000 DS1100Diesel Generator Set
Product highlights
380V-415V/50Hz/datacentercontinuous/fuelconsumptiomoptimized/16V2000G26F/air charge air cooling
Bene�ts— Lowfuelconsumption— Optimizedsystemintegrationability— Highreliabilityandavailabilityofpower— Longmaintenanceintervals— Optimizedratiobetweensizeandpower— Wideoperatingrangewithoutderating
Support— Globalproductsupportoffered
Standards— Engine-generatorsetisdesignedandmanufacturedinfacilitiescertifiedtostandardsISO2008:9001andISO2004:14001
— GeneratorsetcompliestoG3accordingtoISO8528— GeneratormeetsNEMAMG1,BS5000,ISO,DINENandIECstandards
— NFPA110
Powerrating— Systemrating:1000kVA— AcceptsratedloadinonestepperNFPA110— GeneratorsetcompliestoG3accordingtoISO8528-5— GeneratorsetexceedsloadstepsaccordingtoISO8528-5
Performanceassurancecerti�cation(PAC)— Engine-generatorsettestedtoISO8528-5fortransientresponse— 100%loadfactorforcontinuouspowerapplications— Verifiedproductdesign,qualityandperformanceintegrity— Allenginesystemsareprototypeandfactorytested
Completerangeofaccessoriesavailable— Controlpanel— Powerpanel— Fuelsystem— Fuelconnectionswithshut-offvalvemountedtobaseframe— Starting/chargingsystem— Exhaustsystem— Mechanicalradiator— Oversizedvoltagealternators
Emissions— Fuelconsumptionoptimized— TA-Luft,Tier2andNEA(ORDE)optimizationoptionallyavailable
Certi�cations— CEcertificationoption— VDE4110Certification
Optionalequipmentandfinishingshown.Standardmayvary.Optionalequipmentandfinishingshown.Standardmayvary.
-
1 AlldatarefersonlytotheengineandisbasedonISOstandardconditions(25°Cand100mabovesealevel).
2 EmissionoptimizeddatarefertoTA-LuftoptimizedandNEA(ORDE)optimized/Tier2compliantengines.
3 ValuesreferencedareinaccordancewithISO3046-1.Conversioncalculatedwithfueldensityof0.83g/ml.Allfuelconsumptionvaluesrefertoratedenginepower.
Applicationdata1)
Engine Fuelconsump.opt. Emissionopt.2)
Manufacturer MTU MTU Model 16V2000G26F 16V2000G26F Type 4-cycle 4-cycle Arrangement 16V 16V Displacement:l 35.7 35.7 Bore:mm 135 135 Stroke:mm 156 156 Compressionratio 17.5 17.5 Ratedspeed:rpm 1500 1500 Enginegovernor ADEC ADEC Speedregulation ±0.25% ±0.25% Maxpower:kWm 890 890 Meaneffectivepressure:bar 19.9 19.9 Aircleaner dry dry
FuelsystemMaximumfuellift:m 5 5 Totalfuelflow:l/min 30 30
Fuelconsumption3)
At100%ofpowerrating:l/hr 205/191 216/201 At75%ofpowerrating:l/hr 156/194 165/205 At50%ofpowerrating:l/hr 108/202 115/214
LubeoilsystemTotaloilsystemcapacity:l 102 102 Max.lubeoiltemp.(alarm):°C 103 103 Max.lubeoiltemp.(shutdown):°C 105 105 Min.lubeoilpressure(alarm):bar 4.5 4.5 Min.lubeoilpressure(shutdown):bar 4 4
CombustionairrequirementsCombustionairvolume:m3/s 1.03 1.19 Max.airintakerestriction:mbar 40 40
Cooling/radiatorsystem Fuelconsump.opt. Emissionopt.2)
Coolantflowrate(HTcircuit):m3/hr 41.6 41.6 Heatrejectiontocoolant:kW 370 350Heatrejectiontochargeair:kW 145 205Heatradiatedtoambient:kW 40 40Fanpowerformech.radiator(40°C):kWm 43.4 43.4Fanpowerformech.radiator(50°C):kWm 43.4 43.4Airflowrequiredformech.radiator(40°C) cooledunit:m3/min 1462 1462 Airflowrequiredformech.radiator(50°C) cooledunit:m3/min 1462 1462 Enginecoolantcapacity (withoutcoolingequipment):l 70 70 Radiatorcoolantcapacity(40°C):l 74 74 Radiatorcoolantcapacity(50°C):l 106 106 Max.coolanttemperature(warning):°C 102 102 Max.coolanttemperature(shutdown):°C 105 105
ExhaustSystemExhaustgastemp.(afterturbocharger):°C 530 515 Exhaustgasvolume:m3/s 2.78 3.07 Maximumallowablebackpressure:mbar 50 50 Minimumallowablebackpressure:mbar 30 30
GeneratorProtectionclass IP23 IP23 Insulationclass H H Voltageregulation(steadystate) ±0.25% ±0.25% Radointerferenceclass N N
-
Engine
4-Cycle Standardsinglestageairfilter Oildrainextension&shut-offvalve Fullflowoilfilters Closedcrankcaseventilation
Governor-electronicisochronous ADEC/ECU9 Commonrailfuelinjection Dryexhaustmanifold Electricstartingmotor(24V)
Fuelconsumptionoptimizedengine TA-Luftoptimizedengine Tier2optimizedengine NEA(ORDE)optimizedengine
Generator
LeroySomerlowvoltagegenerator MeetsNEMAMG1,BS5000, IEC60034-1,VDE0530, DINEN12601,AS1359 andISO8528requirements Superiorvoltagewaveform Solidstate,volts-per-Hertzregulator 4polethree-phasesynchronous generator Brushless,self-excited,self-regulating,self-ventilated Digitalvoltageregulator Anticondensationheater
StatorwindingY-connected, accessibleneutral(broughtout) ProtectionIP23 lessthan5%harmonicdistorsion 2/3pitchstatorwindings Noloadtofullloadregulation ±0.25%voltageregulationnoloadto fullload InsulationclassH,utilizationacc.toH RadiosuppressionEN55011, group1,cl.B Shortcircuitcapability3xInfor10sec
Sustainedshortcircuitcurrentofupto300%oftheratedcurrentforupto10seconds(LeroySomergenerator) WindingandbearingRTDs (withoutmonitoring) ExcitationbyAREP+PMI MountingofCT´s:3x2coreCT´s Voltagesetpointadjustment±10V Sustainedshortcircuitcurrentofupto250%oftheratedcurrentforupto10seconds(Marathongenerator) Marathonlowvoltagegenerator Oversizedgeneratoror
Representsstandardfeatures
Representsoptionalfeatures
Standardandoptionalfeatures
Systemratings(kW/kVA)
Generatormodel Voltage withmechanicalradiator**
kWel kVA* AMPS
LeroySomerLSA50.2M6 (Lowvoltage LeroySomerstandard)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391
LeroySomerLSA50.2L7 (Lowvoltage LeroySomeroversized)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391
Marathon740RSL7183 (Lowvoltage Marathonstandard)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391
Marathon742RSL7185 (Lowvoltage Marathonoversized)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391 *cosphi=0.8 **BE,fueloptimized:max.poweravailableupto:openpowerunit40°C/400m;TAL,EPATier2compl.,NEA:standardoperatingconditions/openpowerunit25°C/100m Electricaloutputsmayvarydependingongeneratorvoltageandambientconditions.ForpoweroutputsconsultyourMTUdealer. Intakeairdepression/mbar:15mbar Exhaustbackpressure/mbar:30mbar
-
Standardandoptionalfeatures
Representsstandardfeatures
Representsoptionalfeatures
Controlpanel
Pre-wiredcontrolcabinetforeasyapplicationofcustomizedcontroller(V1+) Islandoperation(V2) Automaticmainsfailureoperationwith ATS(V3a) Automaticmainsfailureoperation incl.controlofgeneratorandmainsbreaker(V3b) Islandparalleloperationof multiplegensets(V4) Automaticmainsfailureoperationwithshort(<10s)mainsparalleloverlapsynchronization(V5) Mainsparalleloperationofa singlegenset(V6)
Mainsparalleloperationof multiplegensets(V7) Baslercontroller Deifcontroller Completesystemmetering Digitalmetering Engineparameters GeneratorProtectionFunctions Engineprotection SAEJ1939engineECUcommunications Parametrizationsoftware Multilingualcapability Multipleprogrammablecontactinputs Multiplecontactoutputs Eventrecording
IP54frontpanelratingwith integratedgasket Differentexpansionmodules Remoteannunciator Daytankcontrol Generatorwindingtemperature monitoring Generatorbearingtemperature monitoring Differentialprotectionwith multi-functionprotectionrelay ModbusTCP-IP
Coolingsystem
Jacketwaterpump Thermostat(s)
Airchargeaircooling Mechanicalradiator
Jacketwaterheater
Powerpanel
Availablein600x600 Phasemonitoringrelay230V/400V
Supplyforbatterycharger Supplyforjacketwaterheater
Plugsocketcabinetfor230V compatibleEuro
Fuelsystem
Flexiblefuelconnectorsmountedtobaseframe
Fuelfilterwithwaterseparator Switchablefuelfilterwith waterseparator
Fuel cooler
Starting/chargingsystem
24Vstarter Starterbatteries,cables,rack, disconnect switch
Batterycharger Redundantstarter2x7.5kW
Mountingsystem
Weldedbaseframe Resilientengineandgeneratormounting Modularbaseframedesign
Exhaustsystem
Exhaustbellowswithconnectionflange Exhaustsilencerwith10dB(A)soundattenuation
Exhaustsilencerwith 30dB(A)soundattenuation
Exhaustsilencerwith 40dB(A)soundattenuation Y-connection-pipe
-
Rolls-RoyceGroupwww.mtu-solutions.com/powergen
Weightsanddimensions
Sound data
— ConsultyourlocalMTUdistributorforsounddata.
Emissionsdata
— ConsultyourlocalMTUdistributorforemissionsdata.
Ratingdefinitionsandconditions
— DataCenterContinuousPowerratingsapplytoDataCenterinstallationswhereareliableutilitypowerisavailableandcomplywithUptimeInstituteTierIIIandIVrequirements.Atconstantorvaryingload,thenumberofgeneratorsetoperatinghoursisunlimited.A10%overloadcapacityisavailableforonehourintwelve.RatingsareinaccordancewithISO8528-1,ISO3046-1, BS5514andAS2789.Averageloadfactor:≤100%.
— ConsultyourlocalMTUdistributorforderatinginformation.
Drawingaboveforillustrationpurposesonly,basedonastandardopenpower400Voltengine-generatorset.Lengthsmayvarywithothervoltages.Donotuseforinstallationdesign.Seewebsiteforunitspecifictemplatedrawings.
Subjecttochange.|3239781|Edition01/19|ESM2019-12.
Weightsanddimensionsarebasedonopenpowerunitsandareestimatesonly.Consultthefactoryforaccurateweightsanddimensionsforyourspecificengine-generatorset.
System Dimensions(LxWxH) Weight(dry/lesstank)
Openpowerunit(OPU) 4440x1990x2200mm 6550kg