Auckland Tel: 09-525 1753 Fax: 09-525 1756 Email: [email protected] Web: www.carrel-electrade.co.nz Christchurch Tel: 03-366 1242 Fax: 03-379 1991 CARREL-ELECTRADE LTD not just products... solutions! CARREL-ELECTRADE LIMITED New Zealand Owned and Operated 0014 DIN Integra 1630 Series Digital Metering System Multifunction Integra 1630 digital metering systems provide high accuracy 0.2% measurement, display and communication of all major electrical and power quality parameters including total harmonic distortion (THD) measurement up to the 31st harmonic. To suit user requirements, the range includes single-phase, three-phase three-wire and triple-phase four-wire capability, all selectable at the point of installation. This DIN 96 panel mounted enclosure offers simple programming and display of up to 35 electrical measurement parameters via a simple menu-driven user interface on the front panel. Integra 1630 digital metering system benefits from optional pulsed and digital communication outputs. This allows enhanced status information of up to 60 measured parameters to be communicated to SCADA, building management or other systems. Additionally, a simple Windows-based software package is available to remotely configure the Integra and display all 60 major electrical and power quality parameters. Features Low profile High contrast LED display 0.2% accuracy LED annunciators for each measured parameter Profibus TM User programmable system configuration (4-wire default) Fully programmable VT and CT ratios Current demand per phase Elapsed time counter for connected loads Optional bezel for very low profile applications • Profibus TM NOW NOW with Profibus DP Communications Option ENERGY DIVISION

Upload: others

Post on 12-Sep-2021

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DIN Integra 1630 Series Digital Metering System

Auckland Tel: 09-525 1753Fax: 09-525 1756

Email: [email protected]: www.carrel-electrade.co.nz

Christchurch Tel: 03-366 1242Fax: 03-379 1991

CARREL-ELECTRADE LTDnot just products... solutions!

C A R R E L - E L E C T R A D E L I M I T E D

New Zealand Owned and Operated

0014

DIN Integra 1630 Series Digital Metering System

Multifunction Integra 1630 digital metering systems provide high accuracy 0.2% measurement, display and communication of all major electrical and power quality parameters including total harmonic distortion (THD)measurement up to the 31st harmonic. To suit user requirements, the rangeincludes single-phase, three-phase three-wire and triple-phase four-wirecapability, all selectable at the point of installation.

This DIN 96 panel mounted enclosure offers simple programming and display of up to 35 electrical measurement parameters via a simple menu-driven userinterface on the front panel. Integra 1630 digital metering system benefits from optional pulsed and digital communication outputs. This allows enhanced status information of up to 60 measured parameters to becommunicated to SCADA, building management or other systems. Additionally,a simple Windows-based software package is available to remotely configure the Integra and display all 60 major electrical and power quality parameters.

FeaturesLow profile

High contrast LED display

0.2% accuracy

LED annunciators for each measuredparameter

ProfibusTM

User programmable system configuration(4-wire default)

Fully programmable VT and CT ratios

Current demand per phase

Elapsed time counter for connected loads

Optional bezel for very low profileapplications

• ProfibusTM

NOWNOWwith Profibus DP

Communications Option

ENERGY DIVISION

Page 2: DIN Integra 1630 Series Digital Metering System

Product Codes

I N T – X X X X – X - X – X - X X X

Product System Type Input Input Auxiliary OptionsFamily V I V

16 30–LED DIN96 L - 57.7 - 139 L - N 5 – 5A L – 12 - 48 V DC 000 - No Option

(100 - 240 L - L) 1 – 1A M - 100 – 250V 010 - Modbus

Low User M - 140 - 277 L - N AC/DC 100 - One PulseProfile Selectable System (241 - 480 L - L) 110 - One Pulse

Type One Modbus

Features as Factory Default 200 - Two PulseSpecified - 4 Wire 210 - Two Pulse

One Modbus

050 - ProfibusTM

250 + Two pulse ProfibusTM

CT Accessories

Crompton Instruments also offer a complete range of high qualitycurrent transformers offering comprehensive measuring and protectionclass accuracies. The range offers a wide selection of system currentratings, busbar sizes, case widths, apertures and mounting options toevery application.

FeaturesCost effective moulded case measuring current transformers

Limited range include the seven most popular sizes of current transformers

Ratio ratings from 30/5 to 4000/5

Comprehensive measurement of class accuracy

Wide range of system current ratings, busbar sizes, case widths and apertures

Wire sealable terminal covers

Feet mounting and busbar options

Order Code ExampleINT-1630-M-5-M-250Integra 1630 digital metering system, 3-phase 4-wire, nominal input voltage, 140-277V L-N (241-480V) L-L, 5A CTinput, auxiliary supply 100 to 250V AC or DC, two relay pulsed output and one Profibus communication port.

Tyco Electronics UK Limited, Crompton InstrumentsFreebournes Road, Witham, Essex, CM8 3AH, UKPhone: ++44 (0) 870 870 7500 Fax: ++44 (0) 870 240 5289www.crompton-instruments.com

a vital part of your world

© Tyco Electronics CI-EPP-Integra1630-03/07

All of the above information, including drawings, illustrations and graphic design, reflects our present understanding and is to thebest of our knowledge and belief correct and reliable. Users, however, should independently evaluate the suitability of each productfor the desired application. Under no circumstances, does this constitute an assurance of any particular quality or performance. Suchan assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for theseproducts is set forth in our standard terms and conditions of sale. Tyco is a trademark. CROMPTON is a trademark of CromptonParkinson Ltd. and is used by Tyco Electronics under licence. Profibus is a trademark of PROFIBUS Nutzerorganisation e.v

Energy Division –economical solutions for the electrical power industry: cable accessories,connectors & fittings, electrical equipment, instruments, lighting controls, insulators &insulation enhancement and surge arresters.

Auckland Tel: 09-525 1753Fax: 09-525 1756

Email: [email protected]: www.carrel-electrade.co.nz

Christchurch Tel: 03-366 1242Fax: 03-379 1991

CARREL-ELECTRADE LTDnot just products... solutions!

C A R R E L - E L E C T R A D E L I M I T E D

New Zealand Owned and Operated

0014

A range of 3-in-1 current transformers combine threetraditional current transformers in one moulded case. 3-in-1 current transformers can be directly installed next to a three-phase moulded case circuit breaker, thus savinginstallation time where fitting three standard individualcurrent transformers would be required. The M3N1 range of current transformers offers primary currents between60-630A with 5A secondaries with up to class 0.5 accuracy performance.

3-in-1 Current Transformers

Features• Cost effective three-phase

moulded case

• Ratio's ranging from 60/5 to 630/5

• Integrated wire sealableterminal cover

• Busbar, DIN-rail and metal feetmounting hardware supplied

• Combined M4 posi/slot screw

Benefits• Isolated output for safety• Faster installation• Compact size• Ex-stock delivery

Applications• Switchgear• Distribution systems• Generator sets• Control panels

Energy Division

Specifications

System voltage 720V maximum

Test voltage 3kV for 1 minute

System frequency 50Hz or 60Hz

Primary ratings 60A to 630A

Short circuit thermal current 60 x rated primary current (lth): for 1 sec

Overload withstand 1.2 x rated current continuously

Rated dynamic current = 2.55 x lht

Secondary terminals M4 screw terminals

Enclosure Flame retardant grade classified UL 94V-O

Aperture holes centres 25, 35, 45mm

Operating temperature -20°C to +85°C

Accuracy Class 0.5, 1, 3Mounting hardware Plug-in metal feet for wall or base mounting Busbar and DIN-rail mounting

Compliant with IEC/EN 60044-1