dorman smith air circuit breaker

Upload: ashby-kb

Post on 15-Feb-2018

281 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    1/28

    http://energy.tycoelectronics.com

    Energy Division

    Loadline Z-Frame Air Circuit Breakers

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    2/28

    Loadline Z-Frame Air Circuit Breakers

    The Dorman Smith Z Frame ACB range offers current ratings from 800A - 4000A in 3

    frame sizes. Up to 3200A accommodated within the same height and depth. All

    utilize a double break contact system ensuring a fast interruption time of short circuit

    currents and a high making capacity offering greater operator safety. With more than

    20 design patents registered on the Z frame ACB, this range encompasses moderntechnology to control and protect your system.

    Z frame is a comprehensive range of ACB's with associated accessories ideallysuited for any application where high fault level currents may be present. Thecompact design and innovative features present Z frame as one of the smallest and

    most advanced ranges of ACB available.

    Features

    3 compact frame sizes

    Small depth size 290mm

    Identical height and depth up to 3200A

    True RMS protection

    High making capacity

    Benefits

    High stacking density in switchboards

    Identical cut outs for panel mounting

    Reduced switchboard size

    Maximum operator safety

    Applications

    L.V. Transformer protection

    L.V. Power distribution

    L.V. Circuit protection

    Approvals

    IEC 60947-2

    EN 60947-2

    AS 3947-2

    NEMA PUB No.SG3

    ANSI C37.13

    Contents Page No.

    Loadline Z-Frame

    International Compliance 1-2

    Loadline Z-Frame - Over Current ReleaseLoadline Z-Frame Characteristics 3

    OCR Characteristics 4

    AGR11L - OCR Protective Functions 5

    AGR21L - OCR Protective Functions 6

    AGR22L - OCR Protective Functions 7

    Loadline Z-Frame Catalogue Number Selection

    Air Circuit Breaker Selection 8-9

    Loadline Z-Frame Accessories

    Accessories Factory Fitted 10-12

    Accessories Factory Fitted Order Codes 13

    Accessories Supplied Loose 14-17

    Loadline Z-Frame Dimensions

    Z2 Draw-out Type 18

    Z2 Fixed Type 19

    Z3 Draw-out Type 20

    Z3 Fixed Type 21

    Z4 Draw-out Type 22

    Loadline Z-Frame Circuit Diagrams

    AGR - 11L OCR fitted or without OCR 23

    AGR - 21L or 22L OCR fitted 24

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    3/28

    Loadline Z-Frame International Compliance

    1

    1) Values in open air at 40c

    2) Values of 800A ~ 1600A for draw-out type with horizontal terminals Values of 2000A ~ 4000A for draw-out type with verticalterminals

    3) For 2 poles use both opposite ends poles of 3 poles ACBs

    4) 4 poles ACBs without Neutral phase protection can not be applied to IT earthing systems.

    5) Rated insulation voltage depends on applied standard: 1000V AC according to IEC 60947-2

    6) Rated operational voltage depends on applied standard: 690V according to IEC 60947-27) Cannot apply IT earthing system, ie, insulated from earth.

    8) For 500V AC.

    9) Please contact Dorman Smith for DC application.

    10) 3 poles in series should be applied for 600V DC.

    11) For vertical terminals or horizontal terminals

    Frame Z2 Z3 Z4

    a

    b

    cd

    a

    b

    c

    d

    Fixed Type

    Draw-out

    Type (11)

    Rated Current (max) [In] (A) IEC, EN AS 800 1250 1600 2000 2500 3200 4000

    (1) (2) NEMA, ANSI 800 1250 1540 2000 2500 3200 3700

    Neutral Pole Amperes Frame (A) 800 1250 1600 2000 2500 3200 4000

    Number of Poles (3) (4) 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4

    AC Rated Insulated Voltage [Ui](V.50/60Hz) (5) 1000 1000 1000 1000 1000 1000 1000

    Rated Operational Voltage [Ue](V.50/60Hz) (6) 690 690 690 690 690 690 690

    (AC Rated Breaking Cap [kA sym rms)/

    MAKING CAP [kA peak]

    IEC, EN, AS AC 690V (7) 50/105 50/105 50/105 50/105 65/143 65/143 75/165

    [/cs = /cu] 440V 65/143 (8) 65/143 (8) 65/143 (8) 65/143 (8) 85/187 (8) 85/187 (8) 100/220 (8)

    NEMA AC 600V 42/96.6 42/96.6 42.96.6 42/96.6 50/115 50/115 65/149.5

    ANSI 480V 50/115 50/115 50/115 50/115 65/149.5 65/149.5 75/172.5

    240V 65/149.5 65/149.5 65/149.5 65/149.5 85/195.5 85/195.5 100/230

    (9) DC 600V (10) 40/40 40/40 40/40 40/40 40/40 40/40 40/40250V 40/40 40/40 40/40 40/40 40/40 40/40 40/40

    Non Automatic Unit

    Rated Impulse Withstand Voltage [Uimp] (kV) 12 12 12 12 12 12 12

    Rated Short Time Withstand 1s 65 65 65 65 85 85 100

    Current[/cw][kA rms] 3s 50 50 50 50 65 65 75

    Latching Current (kA) 65 65 65 65 85 85 100

    Total Breaking Time (s) 0.03 0.03 0.03 0.03 0.03 0.03 0.03

    Closing Operation Time

    Spring Charging Time (s) max. 10 10 10 10 10 10 10

    Close Time (s) max. 0.08 0.08 0.08 0.08 0.08 0.08 0.08

    Weight (kg) draw-out type 73 - 86 73 - 86 76 - 90 79 - 94 105 - 125 105 - 125 139 - 176

    Outlined Dimensions (mm)

    360 - 445 360 - 445 360 - 445 360 - 445 466 - 586 466 - 586 - -

    460 460 460 460 460 460 - -

    290 290 290 290 290 290 - -75 75 75 75 75 75 - -

    354 - 439 354 - 439 354 - 439 354 - 439 460 - 580 460 - 580 631 - 801

    460 460 460 460 460 460 460

    345 345 345 345 345 345 345

    40 40 40 40 40 40 53

    800KA & 100KA Icu available end of 2003. Contact Dorman Smith for availability.

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    4/28

    Loadline Z-Frame International Compliance

    2

    Circuit Withstand Voltage (at 50/60Hz) Rated ImpulseWithstand Voltage U imp

    Main Circuit

    ControlCircu

    its

    Connecting Bar Sizes (mm)

    Based Standards Ambient temp (C) 2x50x5 2x80x5 2x100x5 3x100x5 2x100x10 3x100x10 4x150x6

    IEC60947-2 40 (Standard) 800 1250 1600 2000 2500 3200 4000

    EN60947-2 45 800 1250 1600 2000 2500 3200 4000

    AN3947.2 50 800 1250 1600 2000 2500 3200 4000

    55 800 1250 1600 1820 2500 2990 4000

    60 800 1250 1460 1740 2400 2850 3760

    NEMA, SG-3 40 (Standard) 800 1250 1540 2000 2500 3200 3700

    ANSI C37.13 45 800 1240 1470 1960 2500 3010 3580

    50 800 1180 1390 1860 2440 2860 3470

    55 800 1110 1310 1750 2300 2690 3350

    60 800 1040 1230 1640 2150 2520 3150

    Note: The values of 800A, 1250A & 1600A are for horizontal terminals on both line and load side.The values of 2000A, 2500A, 3200A & 4000A are for vertical terminals on both line and load side.

    Above figures are subject to the design of the enclosure and rating of busbar.

    Dielectric Strength

    Derating

    Between terminals AC3500V for 1 minute

    terminal group to earth

    Terminal group to earth AC2500V for 1 minute

    Terminal group to earth AC2000V for 1 minute

    Terminal group to earth AC2000V for 1 minute

    Terminal group to earth AC2000V for 1 minute

    Terminal group to earth AC2500V for 1 minute

    Terminal group to earth AC2000V for 1 minuteOther Accessories

    Note: The values shown above are those measured on phase connections and cannot be applied to control terminals on the ACB.

    Auxiliary switches For general service

    For microload

    Position switches

    Over-current release (OCR)

    Power supply for undervoltage

    12kV

    6kV

    4kV

    4kV

    4kV

    6kV

    4kV

    Frame

    Rated current (A) 800 1250 1600 2000 2500 3200 4000

    DC internal resistance per pole (m!) 0.030 0.030 0.028 0.024 0.014 0.014 0.014

    AC power consumption for 3 poles (W) 170 310 350 490 600 780 1060

    Z4

    Internal Resistance and Power Consumption

    Z3Z2

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    5/28

    Loadline Z-Frame Characteristics

    3

    100 200 300 500 1000 2000 ; 6 graduations75 175 275 475 975 1975

    170 270 370 570 1070 2070

    Time-delay [time] (s) 0 - 0.1 - 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8 - 1.0 ; 10 graduations

    Power consumption: 5VA

    AC100 - 120V DC100 - 125V DC24VAC200 - 240V DC200 - 250V DC48V

    Pick-up voltage (V)

    External Supply voltage

    Note. Regd for AGR11L - AL, AGR11L - GL

    [ICT]x(0.1 - 0.2 - 0.3 - 0.4 - 0.6 - 0.8 - 1.0 - NON) ; 8 graduations

    UVT rated supply voltage [Uc]x(0.8 - 0.85 - 0.9 - 0.95) ;

    4 graduations

    Current setting tolerance (%)

    Time-delay [tp1] (sResettable time (ms)

    Max. total clearing time (ms)

    +20%

    OCR Control Voltage

    GF

    UVT

    Common) Common) Common)

    PTA Adjustable Pre-trip Alarm Characteristics

    Adjustable Long Time-delay Trip Characteristics

    Type AGR-11L, 21L, 22L

    Protection Functions Setting Range

    LT

    ST

    Pick-up current [ IR ] (A)

    Pick-up current [Ii] (A)

    Pick-up current [Isd] (A)

    Time-delay [tR] (s)

    Time-delay [tsd] (ms) Relay time

    Resettable time (ms)

    Max. total clearing time (ms)

    Current setting tolerance (%)

    Time -delay setting tolerance (0%)

    [In]x(0.8 - 0.85 - 0.9 - 0.95 - 1.0 - NON) ; 6 graduations

    Non tripping when load current < ([IR]x1.05).

    Tripping when ([IR]x1.05)< load current< ([IR]x1.2)

    [In]x(1 - 1.5 - 2 - 2.5 - 3 - 4 - 6 - 8 - 10 NON) ; 10 graduations

    +15%

    50 100 200 400 600 800 ; 6 graduations

    25 75 175 375 575 775

    120 170 270 470 670 870

    (0.5 - 1.25 - 2.5 - 5 - 10 - 15 - 20 - 25 - 30) at 600% of [ IR]; 9 graduations

    +15% + 150ms - 0ms

    Adjustable Short Time-delay Trip Characteristics

    Tripping at 600% of [In] with LT time-delay [tR]

    INST

    MCRAdjustable Instantaneous Trip Characteristics

    [In]x(2 - 4 - 6 - 8 - 10 - 12 - 14 - 16 - NON) ; 9 graduations

    Time-delay [tp1] (s) (5 - 10 - 15 - 20 - 40 - 60 - 80 - 120 - 160 - 200) at [IP1 or more ;

    10 graduations

    Time-delay setting tolerance (%) +15% + 100ms - 0ms

    Current setting tolerance (%) +20%

    Pick-up current [Ip1] (A) [In]x(0.75 - 0.8 - 0.85 - 0.9 - 0.95 - 1.0) ; 6 graduations

    Pick-up current [Ig] (A)

    Current setting tolerance (%) +7.5%

    Current setting tolerance (%)

    Time-delay [tp1] (s)

    +15% +150ms - 0ms

    N-phase Protection CharacteristicsNP

    [ICT]x(0.4 - 0.5 - 0.63 - 0.8 - 1.0); Factory set to a user-specified value

    Non tripping when load current < ([IR]x1.05).

    Tripping when ([IR]x1.05)< load current< ([IR]x1.2)

    Key _ : Default Setting

    Undervoltage Trip Characteristics (AGR -21,22 only)

    Adjustable Ground Fault Trip Characteristics Note; Set [Ig] to 1200A or less

    Pick-up current [Ig] (A)

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    6/28

    Loadline Z-Frame OCR Characteristics

    4

    LT - Overload Protection

    Adjustable from 40 - 100% of rated current incorporating true r.m.s. detection.Microprocessor controlled devices eliminate nuisance tripping by responding tothe true r.m.s. value of the waveform. Neutral protection for all Triple-N harmonics,such as 3rd, 9th and 15th, and also a thermal memory as standard.

    ST - Short Time

    Adjustable in current and time the current can be set so discrimination is achievedwith the down stream device. There is also a ramp selector switch to reduce theangle of the curve from a right angle to a 45 angle allowing better discrimination.The time setting enhances this by allowing the down stream device time to clear thefault before the ACB trips.

    INST - Instantaneous Trip

    Adjustable from 2 X In upto 16 X In or none. This setting protects from short circuitcurrents on the system, detects and executes the tripping in a short time less than0.02 seconds.

    NP - N-phase Protection Function (Optional)

    In a 3-phase, 4-wire system with some harmonic distortion, the 3rd harmonic maycause a large current flow through the neutral conductor. The N-phase protectionfunction prevents the neutral conductor from sustaining damage or burnout due to alarge N-phase 3rd harmonic current.

    GF - Ground Fault Protection

    Restricted and unrestricted ground fault protection is available on the same relay asa special specification. There is no need to use a separate relay with LoadlineZ-frame ACB, thus saving panel space and cost. Furthermore, fewer CTs and busbarconnections are required which reduces heat and power consumption.

    NB. Neutral CT supplied, loose with all 3 pole ACBs.

    UVT - Integral Under Volt Trip Function (Adjustable)

    With adjustable voltage pick up and adjustable time delay. This provides fine tuningof voltage trip levels. (AGR-21, 22 only).

    LT Characteristic

    ST Characteristic

    INST Characteristic

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    7/28

    Loadline Z-Frame OCR Characteristics

    5

    AGR11L - Protective FunctionsThis unit provides an adjustable time delay on overload (L) and also the I2t rampcharacteristics (S) As shown, these are essential to provide selectivity when gradingwith other protective devices such as downstream fuses and upstream relays.

    The standard LSI curve provides more than five million combinations of uniquetime current characteristics. Zone selective interlocking is available to provide zero

    time delay selectivity.

    LT - Adjustable Long

    Time-delay Trip

    FunctionRMS sensing is used toaccurately read throughdistorted waveforms.

    HOT start mode

    HOT or COLD start mode is

    user-selectable. In HOT startmode, the OCR operatesfaster than in COLD startmode in response to anoverload. The HOT start modegives protection, takingaccount of the behaviour ofloads under heat stress.

    Characteristics shown are withRamp (I2t Sw) in off position.

    Settings Shown

    LT 100%ST 400%INST 1000%

    1

    1

    2

    2

    3

    3

    4

    5

    4 5

    Optional

    q - When the OCR is set to start operation

    at 50% of the rated current, its operating

    time in HOT start mode is approx. 80% ofthat in COLD start mode.

    w - When the OCR is set to start

    operation at 75% of the rated current,its operating time in HOT start mode is

    approx. 60% of that in COLD start mode.

    e - When the OCR is set to start operationat 100% of the rated current, its operatingtime in HOT start mode is approx. 20% of

    that in COLD start mode.

    Operatingtime

    HOT start mode

    COLD start curve

    HOT startcurves

    Current

    q

    w

    e}

    RampCharacteristic Curve

    (L characteristic)

    Operatingtime

    Current

    2.5

    /sd

    tsd0.1

    200% 1000%

    ST - Adjustable Short Time-delay Trip Function

    The ST delay trip function has a definite time delay characteristic and a rampcharacteristic. These characteristics are switch-selectable. The ramp characteristicprovides close selectivity with down stream circuit breakers or fuses. The AGR21Lcomes in to operation with the definite time characteristic when the load current

    reaches 1000% or more of the rated current [In]. The ST trip function is factory set tothe definite time characteristic.

    INST/MCR - Adjustable Instantaneous Trip FunctionThe INST trip function trips the ACB when the short circuit current exceeds thepickup current setting, irrespective of the state of the ACB. The making currentrelease (MCR) trips the ACB when the short circuit current exceeds the pickupcurrent setting during closing operation. After the ACB is closed, the MCR is lockedand kept inoperative. The INST and MCR are switch-selectable.

    (Note) The MCR needs the control power. If the control power is lost, the MCRprovides the INST trip function only.

    As Described on page 6. Available for AGR11L

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    8/286

    PTA - Adjustable Pre-trip Alarm FunctionThe pre-trip alarm function provides an alarm signal via the alarm contact(1A-contact) when the load current exceeding a predetermined value lasts for a predetermined time. The pre-trip alarm is automatically reset when the load currentdrops to the predetermined value. Note that this function needs the control power.

    UVT - Adjustable Integral Undervoltage Trip Function(For AGR21 and AGR22 only)

    The application rated voltages are AC100 - 120V, AC200 - 240V, and AC380 - 460VThe UVT function trips the ACB when the UVT control voltage drops to a value equal

    to 65% of the rated value. Operating time can be set in ten levels: instantaneousthrough to 1 second. The ACB can be closed 2 seconds after the UVT control voltagehas returned to the pick-up voltage. Phase failure protection is available byconnecting R,S and T-phase (See page 24). The UVT function comes with LED andcontact output operation indications. The UVT function trips the ACB when anysingle phase is lost.

    NP - N-phase Protection Function (optional)This NP function is available on 4-pole ACBs and prevents the neutral conductorfrom suffering damage or burnout due to overcurrent. The NP trip pickup currentcan be set between 40% and 100% of the OCR rated primary current. It is factory setto 0.4 IcT or a value specified at the time of ordering.*

    The NP trip function comes usually with operation indications (LED and contact

    output). The NP trip pickup current setting is shared by the LT trip function.The HOT start mode is available. The operating time for the NP trip function is linkedto that for the LT trip function.

    As AGR11L

    1

    1 2 3

    2

    3

    4

    4

    5

    5

    6

    6

    GF - Ground FaultTrip FunctionThe peak value sensing is used(the residual current of eachphase is detected). The GFpickup current can be setbetween 10% and 100% of the

    CT rated primary current [ICT].[Ramp characteristic is added]The ramp and definite timecharacteristics are switchselectable. The GF trip functioncomes in operation with thedefinite time characteristicswhen the load current reaches

    100% or more of the CT ratedprimary current [ICT]. TheGF trip function is factory set tothe definite time characteristics.When using a 3-pole ACB in a3-phase, 4-wire system, be sureto use the supplied CT forneutral lineNote 1: The G trip functioncomes usually with operationindications (LED and contactoutput). Ground fault indicationwithout a ground fault trippingoperation, is available.*

    AGR21L - Protective Functions

    Loadline Z-Frame OCR Characteristics

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    9/287

    As AGR21L with LCD Display & Communications

    Data Measuring and Output FunctionIn some cases it may not be cost effective to upgrade to a digital network so thetraditional analogue 4mA - 20mA signal is supported. The function measures phasecurrents, line voltages (or phase voltages), electric power, and electric energy.

    Monitoring Various Data on L.C.D. DisplayType AGR-22 OCR can monitor phase currents, line voltages (or phase voltages),power, energy, power factor, frequency, etc. on the L.C.D. display.

    Communication Function (optional)This function supports the LonTalk protocol and enables transmission of variousdata via LonWorks networks.

    Energy Measurement

    A,V, kW, MWh, kvar, cos, frequency

    Intelligent Fault Analysis

    Status, fault type, fault size, tripping time, fault history

    Maintenance Information

    Trip circuit supervision, protection relay supervision, contact wear indication,contact temperature measurement. The communication system uses LonWorks

    network of Echelon Corporation, however other protocols can be supported.

    Loadline Z-Frame OCR Characteristics

    AGR22L - Protective Functions

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    10/28

    Loadline Z-Frame Catalogue Number Selection

    8

    How To Select The Loadline Z-Frame Air Circuit Breaker

    Items Supplied as

    Standard on all ACBs

    1) IP31 Door Flange

    2) 4 No AB AuxiliarySwitches

    3) Mechanical indication ofspring status

    4) Mechanical open andclose buttons andindicators

    5) Open and close buttonpadlock facility

    6) Test report for ACB &OCR (when fitted)

    7) Operation manual

    Items Supplied with

    Draw out ACB

    1) Draw out handle

    2) Draw out portionindication

    3) Draw out portionposition padlockfacility

    4) Fixed portion mainsafety shuttles

    padlockable

    5) Fixed portioncontrol circuitssocket shutters

    Factory Fitted Accessories

    1) Castell/cylinder lock/padlockfacility

    2) Shunt trip

    3) UVR fixed type (for OCR type11L or Non Auto)

    4) Aux switches

    5) Position switches (drawoutonly)

    6) Mechanical Interlocks

    7) Spring charged indicator switch

    8) Auto spring discharge device(draw out only)

    9) Remotely tripped indicatorcontact (for information oftripping by external means)

    Note 1

    Trip Indicator contacts only

    Note 2

    Long time trip contactShort/INST trip contactPretrip alarm contact groundfault trip contact systemalarm contact (selfdiagnostic)

    Note 3

    As Note 2 plus UVT tripcontact Spring chargeindicator contact

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    11/28

    Loadline Z-Frame Catalogue Number Selection

    9

    Technical Key

    Chosen

    Product Code

    Resulting

    Code

    Z2

    Z2D

    Z2D3

    Z2D3J

    Z2D3J16

    Z2D3J16H

    Z2D3J16H0

    Z2D3J16H0A

    Z2D3J16H0AD

    Z2D3J16H0ADA

    Frame Size

    D = DrawoutF = Fixed

    3 = 3 Poles

    4 = 4 Poles

    Breaking Capacity

    J = 60 - 65kA

    K = 80 - 85kA

    L = 100kA

    08 = 800A 20 = 2000A12 = 1250A 25 = 2500A16 = 1600A 32 = 3200A40 = 4000A

    Terminal Type

    H - Horizontal, V = Vertical, F = Front

    For Combinations contactDorman Smith Switchgear

    OCR Type

    A = 11L, B = 21L, C = 22L, D = NO OCR

    OCR Control VoltageA = 100 - 120Vac & 200 - 240Vac, B = 100 - 125vDC & 200 - 250Vdc,C = 24Vdc & 48Vdc

    OCR Functions

    Order Type LT ST INST/ PTA GF UVT NP

    Code MCR

    A AL

    B GL

    C PS

    D PG

    E PGU

    F AL + NP

    G GL + NP

    H PS + NP

    J PG + NP

    K PGU + NP

    Charging Type

    See Table

    Order OCR TypeCode 11L - Non Auto 21L - 22L

    0 Manual Manual1 240v ac 200-240v ac2 220v ac NA

    3 200v ac NA

    4 120v ac 100-120v ac5 110v ac NA

    6 100v ac NA

    7 24v dc 24v dc

    8 48v dc 48v dc

    9 100v dc NA

    10 110v dc NA

    11 125v dc 100-125v dc

    12 200v dc NA

    13 220v dc NA

    14 NA 200-250v dc

    10) Control circuits terminal cover

    11) IP55 cover

    12) OCR checker

    13) Motor Step-Down Transformer(220Vac motor to be specified)

    14) Capacitor Trip Device

    (48Vdc shunt trip to be specified)

    15) Mechanical Interlock Cables

    Loosegear Accessories

    1) Shutter padlocking device (pair)

    2) Fixing bolts (drawout only)

    3) Mal insertion device (drawout only)

    4) Test jumper cable 5 meters

    5) ACB Lifter

    6) Spare drawout handle

    7) Terminal Barrier

    8) Cycle counter

    9) Lifting plates

    Current

    Rating

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    12/2810

    Loadline Z-Frame Accessories - Factory Fitted

    Locking DeviceCastell Lock

    Key released when ACB locked in off position.

    Cylinder Lock

    Key released when ACB locked in off position.

    Padlockable Devices

    Padlock fitted with ACB in off position

    Keylock

    Order

    Code

    Order

    Code

    Rated

    Voltage (V)

    Operational

    Voltage (V)

    Peak

    Excitation

    Current (A)

    Steady-state

    Current (A)

    Open Time

    (max.)

    (ms)

    Description

    0

    1

    2

    3

    4

    8

    9

    Not Fitted

    Castell Ref DS1 Fitted

    Castell Ref DS2 Fitted

    Castell Ref DS3 Fitted

    Castell Provision only for FS2 type (with angular movement 90 clockwise to trap key)

    Cylinder Lock

    Padlockable Device

    Continuously-rated Shunt Trip DeviceThe continuous-rated shunt trip device allows the ACB to be opened when anexternal protection relay against overcurrent or reverse power is activated. Becauseof its continuous rating, the device can be used to provide an electrical interlock tothe ACB. When an AGR-11L OCR is fitted or no OCR is fitted, continuously ratedshunt trip and fixed type undervoltage trip can not be fitted to the same ACB.

    Note: For Time Delay Shunt Trip contact Dorman Smith for details

    0 Not Fitted

    1 AC240 AC168-264 0.18 0.12 40

    2 AC220 AC154-242 0.19 0.13 403 AC200 AC140-220 0.24 0.16 40

    4 AC120 AC84-132 0.37 0.24 40

    5 AC110 AC77-121 0.39 0.26 40

    6 AC100 AC70-110 0.48 0.32 40

    7 DC24 DC16.8-26.4 1.65 1.1 40

    8 DC48 DC33.6-52.8 0.86 0.57 40

    Undervoltage Trip For AGR-11L or Without OCRThe undervoltage trip (UVT) automatically trips the ACB when the control powervoltage drops below a pre-determined value. When the control voltage is restored toa value equal to or greater than the pick-up value, the ACB can be closed.

    The UVT consists of a tripping mechanism fitted internally to the ACB and a tripcontrol unit supplied with a 2 metre lead for mounting external to the ACB.

    The UVT is an instantaneous Trip Type. A Timed Delay version is available.Contact Dorman Smith Switchgear for details.

    Remote opening of the circuit breaker by the UVT is possible by connection of a

    normally open push button across terminals 24 and 30 .

    Note: Shunt Trip and UVT cannot be fitted on same ACB

    Order Rated Control Opening Pick-up Coil Excitation Power ConsumptionCode Voltage (V) Voltage (V) Voltage (V) Current (A) Normal Reset

    0 Not Fitted

    1 AC240 84-168 204 0.3 30 50

    2 AC220 77-154 187 0.3 30 50

    3 AC 200 70-140 170 0.3 30 50

    4 AC 120 42-84 102 0.3 30 50

    5 AC 110 38.5-77 93.5 0.3 30 50

    6 AC 100 35-70 85 0.3 30 507 AC 440 154-308 374 0.3 30 50

    8 AC 415 145-290 352 0.3 30 50

    9 AC 380 133-266 323 0.3 30 50

    232mm

    140m

    m

    81mm

    UVT Control Unit

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    13/28

    Loadline Z-Frame Accessories - Factory Fitted

    11

    Auxiliary SwitchesAll auxiliary switches are change over single gap contacts rated at 5A for generaluse. Microload type for electronic circuits are available as an option.

    The auxiliary switches in a fixed type ACB operate during the breakers ON/OFFoperation. The draw out type have the Auxiliary contacts operating in the

    CONNECTED and TEST positions.

    Auxiliary Switch

    0 = Supplied as standard 4 - 4

    1 7 - 7

    2 10 - 10

    3 4 3* 7

    4 7 3* 10

    Category For General Service Microload

    Voltage Resistive Inductive AC: cos > 0.3 Resistive Inductive AC: cos > 0.6 min. applicable

    load (A) load (A) DC: L/R < 0.01 load (A) load (A) DC: L/R < 0.007 load

    AC100-250V 5 5 0.1 0.1AC251-500V 5 5 - -

    DC30V1 1 0.1 0.1

    DC125-250V 1 1 - -

    Order Code Standard Contact

    5A

    Microload0.1A

    Total Contacts

    DC5V 1mA

    Position SwitchesThe position switches operate to give indication of breaker positions: CONNECTED,TEST, ISOLATED, and INSERT.

    There are two contact arrangements: 2c and 4c.

    Connections to the switches are made via screw terminals.

    The following table lists the available types of switches.

    OrderCode Insert Isolated Test ConnType Number ofContacts Contact Arrangement

    0 Nothing Fitted

    1 ALR-0101P 2 c 0 1 0 1

    2 ALR1111P 1 1 1 1

    3 ALR-0211P 4c 0 2 1 1

    4 ALR-0112P 0 1 1 2

    5 ALR-0202P 0 2 0 2

    Voltage

    AC 100-250V

    DC 250V

    DC 125V

    DC 30V

    DC8V

    Resistive Load (A)

    11

    0.3

    0.6

    6

    10

    Inductive Load (A)

    (COS = 0.6, L/R = 0 07)

    6

    0.3

    0.6

    5

    6

    Position Switch Operation Sequence

    Position Switch Ratings

    CONNECTED

    position switch

    TEST

    position switch

    ISOLATED

    position switch

    INSERT

    position switch

    ISOLATED TEST CONNECTED

    a- contact ON

    a- contact ON

    a- contact ON

    a- contact ON

    Inset position means the breaker is in any position between isolated andconnected

    * Suitable for electronic circuits

    Trip Indication SwitchThis switch indicates when the breaker has been tripped from a source other thanthe OCR unit.

    Order Code

    0 = None

    1 = Fitted

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    14/2812

    Loadline Z-Frame Accessories - Factory Fitted

    Mechanical Interlock Horizontal TypeThe mechanical interlock uses a cable system to provide a positive interlock betweentwo or three ACBs. In conjunction with an electrical interlock, it will enhance safetyand reliability of power distribution systems.Interlocking is possible between any frame size within the Dorman Smith FrameRange.

    Vertical TypeMinimum pitch (550mm) is possible.

    Contact Dorman Smith for the details of vertical type.

    Auto Spring Discharge DeviceThis device allows the charged springs to be automatically released when the ACB isdrawn out from the isolated position to the removed position.

    Order code: 0 = None 1 = Fitted

    Spring Charge Indicator SwitchThe switch can be used to indicate that the closing springs have been fully charged.

    Order code: 0 = None 1 = Fitted

    With AGR-11L OCR or without OCR

    Mechanical Interlock

    Mechanism Type

    Type A Configuration

    Any one breaker can be closed outof three. Each breaker to be orderedseparately with appropriate mech type.

    Example:-

    Breaker reference Mains 1 requiresmech type.

    Breaker reference Mains 2 requiresmech type.

    Breaker reference Generator requiresmech type.

    Type B Configuration

    Any two breakers can be closed out

    of three.

    Type C Configuration

    Any one breaker can be closed out

    of two.

    Order Codes

    0 = None

    1 = Mechanism Type

    2 = Mechanism Type

    4 = Mechanism Type

    Cable pairs to be ordered separately

    see page 17

    Type A

    Configuration

    Type B

    Configuration

    Type C

    Configuration

    AC

    DC

    6

    0.1

    0.5

    3

    Inductive Load

    3

    0.1

    0.5

    2

    Voltage(V)

    AC

    DC

    Resistive Load

    0.5

    0.27

    0.5

    2

    Inductive Load

    0.2

    0.04

    0.2

    0.7

    250 250

    125 30

    250 250

    125 30

    With AGR-21 or AGR-22 OCR

    Voltage

    (V)

    Switch Contact Ratings (A)

    Switch Contact Ratings (A)

    Resistive Load

    1

    1

    2

    1 1

    3 3 3

    1 2 1

    1

    2

    3

    Mains 1 Mains 2 Generator

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    15/28

    Loadline Z-Frame Accessories - Factory Fitted Order Codes

    13

    How to Select Factory Fitted AccessoriesCatalogue No. Example:- Z2D3J16HOADA fitted with :-

    DS1 Castell Lock, 120Vac shunt trip, 10c Auxiliary Switches, 1111 Position Switches = Z2D3J16HOADA14022

    Order Code

    Order Code

    Order Code

    Order Code

    Order Code

    Position Switches

    DS 1

    CastellFitted

    DS 2

    CastellFitted

    DS 3

    CastellFitted

    Castell

    Provision

    Cylinder

    Lock Off

    Padlock

    OffNone Spare

    None240V

    AC

    220V

    AC

    200V

    AC

    120V

    AC

    110V

    AC

    100V

    AC

    24V

    DC

    48V

    DC

    None

    None

    None 0101 0211 01121111 0202

    7c SW's 10c SW's 4c SW's+3c (microload) 7c SW's+3c (microload)

    240V

    AC

    220V

    AC

    200V

    AC

    120V

    AC

    110V

    AC

    100V

    AC

    440V

    AC

    380V

    AC

    415V

    AC

    None Fitted

    None Fitted

    None Fitted

    1

    0

    0

    0

    MechanicalInterlock

    0

    None

    0

    Interlock Mechanism

    Type 1

    1

    0 1

    0 1

    0 1

    Interlock Mechanism

    Type 2

    2

    Interlock Mechanism

    Type 3

    3

    1 2 3 4 5

    1 2 3 4

    1 2 3 4 5 6 7 8 9

    1 2 3 4 5 6 7 8

    2 3 4 5 6 7

    Shunt Trip

    Auxiliary Switches

    Order Code

    Spring ChargeIndicating Switch

    Auto SpringDischarge Device

    Remotely TrippedIndicator Contact

    Order Code

    Order Code

    Locks

    Order Code

    UVT for OCR 11L& None Auto

    Catalogue No. Example:- Z2D3J16HOADA14022

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    16/28

    Loadline Z-Frame Accessories - Supplied Loose

    14

    Shutter Padlocking Device

    Fixing Bolts

    Mal-Insertion Prevention Device

    Test Jumper Cable

    Shutter Padlocking Device

    The main circuit safety shutters automatically conceal the main circuit contacts onthe draw-out cradle when the ACB is drawn out.

    The top and bottom shutters operate independently and can be separately padlockedin the closed position.

    Up to three padlocks (with 6 hasp) can be installed on each side using padlocking

    unit. (Padlock not supplied)

    In the closed position, the shutters are locked to the extent that they cannot be easilyunlocked by hand. They can be unlocked and held open if required for the purposeof inspection or maintenance.

    Description: Catalogue Number:

    Z2 & Z3 Frames Z23DSPD

    Z4 Frame Z4DSPD

    Fixing BoltsThe breaker fixing bolts hold the breaker body securely to the draw-out cradle inposition. Use them if the ACB is subject to strong vibration.

    Catalogue Number:

    ZDFB

    Mal-Insertion Prevention DeviceInterchangeability exists within the Z frame range of ACBs. Because of this feature,there is a possibility for an ACB of a different specification being placed into thedraw-out cradle. Using the mal-insertion prevention device eliminates such apossibility.

    This device is capable of distinguishing nine different breaker bodies.

    Catalogue Number:

    ZDMID

    Test Jumper CableThe test jumper is a plug-in type, and allows ON-OFF tests on all the Z frame rangeof ACBs with the breaker body drawn out from the draw-out cradle.

    The standard jumper cable is 5m long.

    Catalogue Number:

    ZDTJC

    Spare Drawout Handle

    Cranked handle for withdrawing moving chassis from fixed portion. Stowaway

    handle for withdrawing moving chassis can be stored within moving chassis .

    Description: Catalogue Number:

    Cranked Handle ZDH

    Stowaway Handle ZDHS

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    17/28

    Control Circuit Terminal Cover

    Loadline Z-Frame Accessories - Supplied Loose

    15

    Terminal BarrierAn inter-pole terminal barrier prevents a possible short-circuit due to foreign objectsentering between the poles of the main circuit terminals or between the line andload ends, thus enhancing operational reliability of the ACB.

    This barrier cannot be applied to ACBs that are supplied with front connections.

    Description: Catalogue Numbers:Z2 Frame, 3 Pole Z2D3TB

    Z3 Frame, 3 Pole Z3D3TB

    Z4 Frame, 3 Pole Z4D3TB

    Z2 Frame, 4 Pole Z2D4TB

    Z3 Frame, 4 Pole Z3D4TB

    Z4 Frame, 4 Pole Z4D4TB

    Control Circuit Terminal CoverA control circuit terminal cover protects the terminal blocks for auxiliary switches,position switches, and control circuits from being accidentally touched, thusenhancing safety.

    Description: Catalogue Numbers:

    Z2 Frame, 3 Pole Z2D3CCTC

    Z3 Frame, 3 Pole Z3D3CCTC

    Z4 Frame, 3 Pole Z4D3CCTC

    Z2 Frame, 4 Pole Z2D4CCTC

    Z3 Frame, 4 Pole Z3D4CCTC

    Z4 Frame, 4 Pole Z4D4CCTC

    Cycle CounterThe ON-OFF cycle counter is a mechanical 5-digit readout that shows the number ofON-OFF cycles of the ACB.

    Counter readings serve as a guide for maintenance or inspection.

    Catalogue Number:

    ZCC

    Lifting PlatesLifting plates are detachable tools that can be used to lift a breaker body out of adraw-out cradle.

    Catalogue Number:

    ZLPLTS

    ACB LifterA special lifter is available to allow easy and safe transportation or installation of theACB. A drop prevention mechanism is standard.

    Description: Catalogue Number:

    Z2 and Z3 Frame Z23DLIFT

    Z4 Frame Z4DLIFT

    Terminal Barrier

    Cycle Counter

    Lifting Plates

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    18/28

    Loadline Z-Frame Accessories - Supplied Loose

    16

    IP55 CoverAn IP cover provides an IP55 grade of protection as defined in IEC 60529. Even if thebreaker body is on the ISOLATED position, IP cover can still be fitted on the ACB.

    Catalogue Number:

    ZIP55

    OCR CheckerThe OCR checker allows easy checking of the long time-delay trip, short time-delaytrip, instantaneous trip, and ground fault trip functions and the pre-trip alarmfunction of the OCR in the field.

    Ratings and Specification

    Power Supply AC100/110V, 50/60Hz or 4 x AA alkaline cells

    Power Consumption 3W

    Dimensions 101 (w) x 195 (h) x 44 (d) mm

    Weight 400g

    Catalogue Number:

    ZOCRC

    Motor Step-Down TransformerThe maximum rated control voltage applicable to the operation power supply isAC240V. If higher voltages required, a step-down transformer is needed. Thefollowing step-down transformers are available as options. (22Vac motor to bespecified)

    Rated Control Transformer

    Voltage Type Capacity Voltage Ratio

    AC410-470V TSE-30M 300VA 450/220V

    AC350-395V TSE-30M 300VA 380/220V

    Description: Catalogue Number:

    450V/220V ZMT4522A

    380V/220V ZMT3822A

    Capacitor Trip DeviceIn conjunction with the continuously-rated shunt trip device, the capacitor trip devicecan be used to trip the ACB within a limited period of 30 seconds if large voltagedrop occurs due to a ac power failure or short-circuit.

    When the continuously-rated shunt trip is used with the capacitor trip device, acontact of auxiliary switch of ACB should be inserted in series. Otherwise, theinternal resistor may be damaged.

    When ordering the capacitor trip device a 48V dc shunt trip is required to be orderedseparately.

    Ratings and Specification

    Type AQR-1

    Rated Voltage AC100-120V

    Operational Voltage Rated Voltage x 70 to 110%

    Rated Frequency 50/60Hz

    Rated Voltage of Shunt Trip Used DC48V

    Power Consumption 100VA

    Catalogue Number:

    ZSTCD

    IP55 Cover

    OCR Checker

    Control Circuit

    Outline Dimensions

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    19/28

    Loadline Z-Frame Accessories - Supplied Loose

    17

    Mechanical Interlock CablesUsed in conjunction with Horizontal Interlocking Mechanism.

    Pitch X or Y Cable Length Catalogue Numbers:

    500 or 600 1120mm (PAIR) ZMECHHC1120

    700 1220mm (PAIR) ZMECHHC1220

    800 1320mm (PAIR) ZMECHHC1320900 1420mm (PAIR) ZMECHHC1420

    1000 1520mm (PAIR) ZMECHHC1520

    1100 or 1200 1620mm (PAIR) ZMECHHC1620

    1720mm (PAIR) ZMECHHC1720

    1920mm (PAIR) ZMECHHC1920

    2120mm (PAIR) ZMECHHC2120

    2320mm (PAIR) ZMECHHC2320

    2520mm (PAIR) ZMECHHC2520

    2720mm (PAIR) ZMECHHC2720

    Length of Cable Z = (Cable length for pitch X) + Ymm

    e.g. If X = 800mm and Y = 600mm

    Cable Z = (1320mm) + 600mm = 1920mm cable length.

    Current Transformer for NeutralCatalogue Numbers: Supplied as standard with all 3 pole ACBs with Ground FaultOCRs

    When using a 3-pole ACB with the ground fault protection function to protect a3-phase, 4-wire system against ground fault, this current transformer (CT) should befitted to the neutral line of the system. This CT is supplied as standard with all 3 poleACBs with Ground Fault OCRs.

    Outline dimension of CT for neutral line

    Z2 Frame, 800A

    1250A

    1600A

    Z3 Frame, 2000A

    2500A

    3200A

    Z4 Frame, 4000A

    Type CW80-40LS

    Rated 200 1250

    Primary 400 1600Current (A) 800

    Rated secondary current is 5A

    Type EC160-40LS

    Rated 1600 3200

    Primary 2000 4000Current (A) 2500Rated secondary current is 5A

    Mechanical Interlock Cables

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    20/28

    Loadline Z-Frame Dimensions

    18

    1: UVT controller is required when fixed type undervoltage trip is fitted with

    AGR-11L OCR or without OCR.

    2: Conductors including connecting bolts should be separated min-7mm from

    Draw-out arm.

    N represents the neutral pole of 4-pole ACBs.

    Terminal Size

    Type t1 t2 t3 W

    800A 10 10 15 17.5

    1250A 10 10 15 17.5

    1600A 20 15 25 22.52000A 20 15 25 ----

    Z2 Draw-out Type

    UVT Controller

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    21/28

    UVT Controller

    Loadline Z-Frame Dimensions

    19

    UVT controller is required when fixed type undervoltage trip is fitted with

    AGR-11L OCR or without OCR.

    N represents the neutral pole of 4-pole ACBs.

    Terminal Size

    Type t1 t2 t3 W

    800A 10 10 15 17.5

    1250A 10 10 15 17.5

    1600A 20 15 25 22.52000A 20 15 25 ----

    Z2 Fixed Type

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    22/28

    Loadline Z-Frame Dimensions

    20

    UVT controller is required when fixed type undervoltage trip is fitted with

    AGR-11L OCR or without OCR.

    Conductors including connecting bolts should be separated min-7mm from

    Draw-out arm.

    N represents the neutral pole of 4-pole ACBs.

    Z3 Draw-out Type

    UVT Controller

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    23/28

    Loadline Z-Frame Dimensions

    21

    UVT controller is required when fixed type undervoltage trip is fitted with

    AGR-11L OCR or without OCR.

    Conductors including connecting bolts should be separated min-7mm from

    Draw-out arm.

    N represents the neutral pole of 4-pole ACBs.

    Z3 Fixed Type

    UVT Controller

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    24/28

    Loadline Z-Frame Dimensions

    22

    UVT controller is required when fixed type undervoltage trip is fitted with

    AGR-11L OCR or without OCR.

    Conductors including connecting bolts should be separated min-7mm from

    Draw-out arm.

    N represents the neutral pole of 4-pole ACBs.

    Z4 Draw-out Type

    UVT Controller

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    25/28

    Loadline Z-Frame Circuit Diagrams

    23

    1: Do not connect b contact ofauxiliary switch to ON switch inseries, otherwise, pumping

    may occur.

    2: Use a contact of auxiliary switchof ACB.

    Symbols for Accessories

    01 21 Control power supply AC200 - 240V, DC200 - 250V DC48V01 11 Control power supply AC100 -120V11 21 Control power supply DC100 - 125V, DC24V02 22 Operation power supply AC100 - 240V, DC100 - 220V, DC24V, DC48V12 Operation switch, common 03 ON switch05 Operation indication terminal, common15 LT trip indication or single-contact indication 25 ST/INST trip indication06 PTA indication 16 GF trip indication 26 System Alarm indication17 Trip indication 27 Spring charge indicator10 20 Continuously-rated shunt trip 19 Separate CT for neutral line (k)29 Separate CT for neutral line ( )08 18 28 UVT power supply 109 UVT power supply common

    Term No. AC100V AC200V AC400V

    coil coil coil

    08 - 09 100V 200V 380V

    18 - 09 110V 220V 415V

    28 - 09 120V 240V 440V

    For single-contact indication only 05 and 15

    Designation of Terminals for Auxiliary and Position Switches

    With AGR-11L OCR or without OCR

    CT1 - CT3 : Power CTs

    S1 - S3 : Current sensors

    M : Charging motor

    LRC : Latch release coil

    MHT : Magnetic hold trigger

    Isolating terminal connector

    (for draw-out type)

    Manual connector

    User wiring

    Relay or Indicator

    1: Common, 2:b-contact,

    4:a contact

    1: Auxiliary switch

    2: Position switch (for CONNECTED)

    3: Position switch (for TESTED)

    4: Position switch (for ISOLATED)

    5: Position switch (for INSERT)

    1-0: Switch numbers

    A,B,C: Auxiliary switches

    for microload(

    * * *CONNECTED positions: 121-124 ON

    121-122 OFF

    TEST positions: 131-134 ON

    131-132 OFF

    ISOLATED positions: 141-144 ON

    141-142 OFF

    INSERT position: 151-154 ON

    151-152 OFF

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    26/2824

    01 21 Control power supply AC200 - 240V, DC200 - 250V DC48V

    01 11 Control power supply AC100 -120V11 21 Control power supply DC100 - 125V, DC24V02 22 Operation power supply AC100 - 240V, DC100 - 250V, DC24V, DC48V12 Operation switch, common 03 ON switch 1 13 OFF switch 123 Reset switch 1 13 Operation switch for signal separation 214 Operation switch for signal separation 205 Operation indication terminal, common15 LT trip indication or single-contact indication 25 ST/INST trip indication06 PTA indication 16 GF, trip indication 26 System Alarm indication07 Heat indication 17 UVT indication 3 27 Spring charge indicator08 18 28 UVT power supply R.S.T. (Max. AC460V)

    09 N-phase voltage detection 19 Separate CT for neutral line (k)29 Separate CT for neutral line (e) 10 20 Continuously-rated shunt trip30

    __

    08 18 28

    R-Phase S-Phase

    Designation of Terminals for Auxiliary and Position Switches

    1: Common, 2:b-contact,

    4:a contact

    1: Auxiliary switch

    2: Position switch (for CONNECTED)

    3: Position switch (for TESTED)

    4: Position switch (for ISOLATED)

    5: Position switch (for INSERT)

    1-0: Switch numbers

    A,B,C: Auxiliary switches

    for microload

    1: Operate input signal is rated at

    40V 5mA.

    2: Used for separation of operationinput signals.

    3: Can be used for trip indicator inplace of UVT indication.

    4: For AGR-22L OCR connect themeasured power source to theterminals, 08,18 , 28.

    In case of no reverse power tripfunction with AGR-21L OCR, UVTcan be used with single phasepower supply as right.

    Symbols for Accessories

    CT1 - CT3 : Power CTs

    S1 - S3 : Current sensors

    M : Charging motor

    LRC : Latch release coil

    TC : Tripping coil

    Isolating terminal connector

    (for draw-out type)

    Manual connectorUser wiring

    Relay or Indicator

    (

    * * *CONNECTED positions: 121-124 ON

    121-122 OFF

    TEST positions: 131-134 ON

    131-132 OFF

    ISOLATED positions: 141-144 ON

    141-142 OFF

    INSERT position: 151-154 ON

    151-152 OFF

    Loadline Z-Frame Circuit Diagrams

    With AGR-21L, 22L OCR

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    27/28

  • 7/23/2019 Dorman Smith Air Circuit Breaker

    28/28

    TycoElectronicsDOS-EPP-ZFRAME-09/03

    Energy Division a pioneer in the development of economical solutions for

    the electrical power industry. Our product range includes: Cable accessories,

    connectors & fittings, electrical equipment, instruments, lighting, insulators &

    insulation enhancement and surge arresters.

    For more information and your country contact person, please visit us at:

    All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable.Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particularquality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forthin our standard terms and conditions of sale. ALR, AMP, AXICOM, B&H, BOWTHORPE EMP, CROMPTON INSTRUMENTS, DORMAN SMITH, DULMISON, GURO, HELLSTERN,LA PRAIRIE, MORLYNN, RAYCHEM, and SIMEL are trademarks.