dynamic analysis and control design of a single-phase ups...

12
International Review of Electrical Engineering (¡.R.E.E.), Vol. 4, N. 4 July-August 2009 Dynamic Analysis and Control Design of a Single-Phase UPS Inverter with Novel Topology and Experimental Verification Ghazanfar Shahgholian , Jawad Faiz , Mohsen Arezoomand Abstract - An uninterruptible power supply (UPS) system with two kinds of fitters in the inverter output is analyzed and simulated. The purpose of a voltage controller for UPS irrverters is to produce .stähle output voltage with low distortion under all loading conditions, particularly under nonlinear loads and load transients. The system modeled consists of the output filter, the control system and the single phase inverter. A state-space mathematical model for .system is used. The results show that system voltage total harmonic distortion to le.ss than 5% even when .supplying nonlinear loads which draw current with a crest factor of 3. The simulation results are confirmed by the experimental results. Copyright © 2009 Praise Worthy Prize S.r.l. - AH rights reserved. Keywords: Uninterruptible Power Supply (UPS), Filter, Harmonic, Two-Port Network, Stability L Introduction With the growth of internet and information teciinolo- gy industry, the need for reliable continuous power to protect dala integrity and ensuring uninterrupted service Is an important requirement. The major function of a UPS is to provide a high quality output waveform, a fast dynamic response and the capability of carrying any load factors. There are many publications describing the various topologies, analysis and control design of UPS inverter 11]-[2]. In [3], a feed forward based on a particu- lar type of on line trained neural network controller in parallel with a proportional-derivative controller for Improving the dynamic response proposed for the control of UPS inverters. The design consideration and perfo- rmance analysis of an on-line, low-cost, high performance, and single-phase UPS system based on a boost integrated fly back rectifier/energy storage dc/dc converter to achieve power factor correction, fast dynamic response, low battery voltage, and desired output voltage is present in [4]. A simple digital feedba- ck voltage controller for high-performance single-phase UPS inverters proposed in |5]. The proposed control strategy focuses on reducing the output impedance of inverters by a feedback of the load current. An innovativ- e tuning technique based on optimization tools with considers practical design constraints for the design of multi loop lag-lead compensators that are normally used in industrial UPS systems based on the H-infinity robust control theory presented in [6]. in [7] inner-outer loop controllers are adopted to regulate output voltage and to improve system response, and a current weighting distribution control strategy for multi-inverter systems to achieve current sharing is presented. In [8] an improved single-phase passive-standby UPS includes an input rectifier/charger and a switching inverter with or without a dc/dc boost stage according to ones low battery voltage for low cost application is described. Two control strategies for three-phase series-parallel uninterruptible power supplies are described and compared in [9]. In [lOJ a unified control scheme as well as a novel connection arrangement is developed to simplify the inverter circuit for design of line interactive UPS without load current sensors. An optimal control strategy based on the LQR approach for single phase UPS in continuous time proposed in [11]. The objective of the paper is to develop an uninterrup- tible power supply (UPS) control system with multiple- filter. The influences of these filters upon the reduction of the output voltage distortion are shown. The remai- nder of this paper can be outlined as follows. The single phase inverter is describing in section II. The small signal model of the system consists of the output filter, the control system, different loads shown in section 111. The two port model of inverter output filter is shown in section IV. In section V, the system open loop transfer functions are described based on averaged model of the inverters. A comparative analysis of the voltage droop and power loss in mono- and multiple-filter is presented in section VI. The output impedance, which is an index for determining the effect of loading on the inverter, is shown in section VII. In section VIII, simulation results of the output voltage for different changes in the input voltage and load have been reported. The analysis is performed by using Matlab program and Simulink toolbox to analyze on waveform quality and overall voltage waveform and spectra. Finally, the experimental results are given for linear and nonlinear load in section IX and discussed in section X. Manuscript received and revised July 2009. accepted August 2009 Copyright © 2009 Praise Worthy Prize S. rl-A It rights reserved 513

Upload: others

Post on 23-Oct-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

  • International Review of Electrical Engineering (¡.R.E.E.), Vol. 4, N. 4July-August 2009

    Dynamic Analysis and Control Design of a Single-Phase UPS Inverterwith Novel Topology and Experimental Verification

    Ghazanfar Shahgholian , Jawad Faiz , Mohsen Arezoomand

    Abstract - An uninterruptible power supply (UPS) system with two kinds of fitters in the inverteroutput is analyzed and simulated. The purpose of a voltage controller for UPS irrverters is toproduce .stähle output voltage with low distortion under all loading conditions, particularly undernonlinear loads and load transients. The system modeled consists of the output filter, the controlsystem and the single phase inverter. A state-space mathematical model for .system is used. Theresults show that system voltage total harmonic distortion to le.ss than 5% even when .supplyingnonlinear loads which draw current with a crest factor of 3. The simulation results are confirmedby the experimental results. Copyright © 2009 Praise Worthy Prize S.r.l. - AH rights reserved.

    Keywords: Uninterruptible Power Supply (UPS), Filter, Harmonic, Two-Port Network, Stability

    L IntroductionWith the growth of internet and information teciinolo-

    gy industry, the need for reliable continuous power toprotect dala integrity and ensuring uninterrupted serviceIs an important requirement. The major function of aUPS is to provide a high quality output waveform, a fastdynamic response and the capability of carrying any loadfactors. There are many publications describing thevarious topologies, analysis and control design of UPSinverter 11]-[2]. In [3], a feed forward based on a particu-lar type of on line trained neural network controller inparallel with a proportional-derivative controller forImproving the dynamic response proposed for the controlof UPS inverters. The design consideration and perfo-rmance analysis of an on-line, low-cost, highperformance, and single-phase UPS system based on aboost integrated fly back rectifier/energy storage dc/dcconverter to achieve power factor correction, fastdynamic response, low battery voltage, and desiredoutput voltage is present in [4]. A simple digital feedba-ck voltage controller for high-performance single-phaseUPS inverters proposed in |5]. The proposed controlstrategy focuses on reducing the output impedance ofinverters by a feedback of the load current. An innovativ-e tuning technique based on optimization tools withconsiders practical design constraints for the design ofmulti loop lag-lead compensators that are normally usedin industrial UPS systems based on the H-infinity robustcontrol theory presented in [6]. in [7] inner-outer loopcontrollers are adopted to regulate output voltage and toimprove system response, and a current weightingdistribution control strategy for multi-inverter systems toachieve current sharing is presented. In [8] an improvedsingle-phase passive-standby UPS includes an inputrectifier/charger and a switching inverter with or without

    a dc/dc boost stage according to ones low batteryvoltage for low cost application is described. Twocontrol strategies for three-phase series-paralleluninterruptible power supplies are described andcompared in [9]. In [lOJ a unified control scheme as wellas a novel connection arrangement is developed tosimplify the inverter circuit for design of line interactiveUPS without load current sensors. An optimal controlstrategy based on the LQR approach for single phaseUPS in continuous time proposed in [11].

    The objective of the paper is to develop an uninterrup-tible power supply (UPS) control system with multiple-filter. The influences of these filters upon the reductionof the output voltage distortion are shown. The remai-nder of this paper can be outlined as follows. The singlephase inverter is describing in section II.

    The small signal model of the system consists of theoutput filter, the control system, different loads shown insection 111. The two port model of inverter output filter isshown in section IV. In section V, the system open looptransfer functions are described based on averaged modelof the inverters.

    A comparative analysis of the voltage droop andpower loss in mono- and multiple-filter is presented insection VI. The output impedance, which is an index fordetermining the effect of loading on the inverter, isshown in section VII.

    In section VIII, simulation results of the outputvoltage for different changes in the input voltage andload have been reported. The analysis is performed byusing Matlab program and Simulink toolbox to analyzeon waveform quality and overall voltage waveform andspectra.

    Finally, the experimental results are given for linearand nonlinear load in section IX and discussed in sectionX.

    Manuscript received and revised July 2009. accepted August 2009 Copyright © 2009 Praise Worthy Prize S. rl-A It rights reserved

    513

  • G. Shahgholian, J. Faiz, M. Arezoomand

    II. Voltage Source UPS Inverter

    Fig. 1 shows the main circuit of a single-phase UPSinverter. The system modeled eonsists of the controllerpart and power circuit parts. The controller part includesIhe micro controller running the control algorithms anddriver circuits. The power circuit part includes the fullbridge inverter, filter, dc voltage and the critical load.

    Fig 1 Main circuit of single-phase UPS inverter

    //./. PWM Inverter

    There are two PWM switching technique in order toshape the output ac voltage to be as close to a sine waveas possible: unipolar and bipolar PWM switching. In thispaper the unipolar pulse width modulation (UPWM)technique (Fig. 2) for the control is used, because theundesired harmonics are shifted to the frequenciesaround double the earner frequency (Fig. 3), which ismuch higher than the reference sinusoidal frequency, andthus can be easily filtered out. In Fig. 2, Mp is frequencymodulation index and MA is amplitude modulation ratio.

    (JNIPCl.*n pwm TECHNIQUE

    O 0 D06 0 Ct nnia nts ti •?£ ata 0 036 o (M

    Fig. 2. Unipolar PWM technique for single-phase inverter

    -i--1

    h

    lililí,i1

    .lili,.in.lao isti

    Fig. 3. Fourier spectnim of inverter Output voltage

    //, 2. Inverter Output Filter

    Filters are used to reduce the harmonic content of thevoltage injected to the load. With single filter someharmonics mange to pass to the load. The harmonics canbe further reduced by going for multiple filters. The

    distortion in the output voltage waveform, are muchmore effectively attenuated by going for two filters. Figs.4-5 show the multiple-filter in the inverter output and theblock diagram of a single-phase inverter with two filtersin the output, respectively, where i,,, û are current andvoltage load, un, u^: are filter capacitor voltage, ipi, î •2are filter inductor current, ici, ic2 are filter capacitorcurrent, LFI, LF2 are filter inductance, CFI. CF2 are filtercapacitance, Rpi, RK2 are equivalent series resistance(ESR) of the filter. In this paper, the parameters of thesystem are LFi=0.09mH, CF,=100 l̂F and Udc=50 volt.

    fint LC filttr

    Fig 4, Multiple-filter

    Fig. 5. Transfer function model ol" the single-phase inverter withmultiple fillers in the output

    In the conventional methods of filter design, the latteris used as interference and the former is considered onlyto determine the filter values. Ignoring the filtersresistances, the open loop state space equation of outputfilter can be written as:

    R

    d_.

    d( '''^

    d_

    d i "'••' "

    d— We-, =

    /• L

    U-;'/-I

    F\

    Fl

    _1_

    _ 1

    Lr:

    I

    'FlF 2

    (1)

    dt Fl

    'Fl

    a. 3. Load Model

    The load on a power system consists of a variety ofelectrical devices. A linear element in a power system isa component in wbich the current is proportional to thevoltage. Typical examples of linear loads include heaters,motors and incandescent lamps. The differential equationwith linear load (RL-LL) is given by:

    d_. __A¿ . J_cW L, " L,

    (2)

    raise Worthy Prize S.r.l - AH rights reserved Intemational Review of Electrical Engineering, Vol. 4. N. 4

    514

  • G. Shahgholian, J. Faiz, M. Arezoomanä

    With ihe increasing use of nonlinear loads in powersystems, the harmonic pollution becomes more and moreserious. The non-linear load causes a periodic dist-urbance. Nonlinear loads draw non-sinusoidal current,even though connected to a sinusoidal voltage. Also, thevoltage and current waveforms are not of the same shapeand contain fundamental frequency as well as non-fundamental frequencies. With nonlinear loads, thevoltage and current waveform will be distorted and theTHD will be inevitably increased. Typical examples ofnonlinear loads include adjustable speed motor drives,rectitler, ferromagnetic devices and arcing equipment[12]. The non-linear load as shown in Fig. 6, includesingle phase full bridge rectifier, second order filter (L-C) and resistor RL.

    Fig. 6. Nonlinear load

    The LC filter is for smoothing the current andattenuating the ripple voltage in the dc side. The differe-ntial equation describing the behavior of the system vari-ables with non linear load are given by:a) When one diode pair is on:

    d . 1 1,

    d 1 . 1— Ur =—'/tt ^ C '' R,(

    b) When diodes are off:i, =0

    •u,. = u,.

    (3)

    (4)

    (5)

    (6)

    where it and uc are current and voltage of DC-side LCfilter. Therefore Z|.(s) for nonlinear load is [13] (eq. (7)):

    where rectifier bridge turn off

    LisR,C LC

    where rectifier bridge turn on

    RrC

    is possible to represent MIMO (Multi Input - MultiOutput) system as shown in Fig. 7. The output voltageand output current of inverter in terms of load voltageand current voltage in Laplace domain are as follows:

    Fig 7, Transfer functicin model of inverter output filter

    Uj (s)= A{s)Vo U)+ Bis) It, is) (8)

    J,is)=Cis) Uais)+ Dis) I,,is) (9)

    where A, B. C and D are transfer parameters of filler.Assuming that the resistance associated with the filterinductor is negligibly small; the equivalent parametersfor different inverter output filters are shown in Table I.The output voltage is:

    o U)=H¡j is) U¡ is) - H, is) I,, is) (10)

    where the transferring characteristic and inverter outputimpedance are:

    1

    ff I it) =

    Ais)

    Bis)Ais)

    ( i l )

    02)

    In linear loads the function Hr(s) has little effect but innonlinear loads and load variations its effect cannot beignored. If the filter resistances are disregarded, then thefunction HLIOÍO) will be real and H|(jcü) will be imag-inary. Inverters may be confronted with no-load or smallload conditions due to interferences. No-load or tightload cases has no effect on the stability of the UPSsystem, therefore sensitivity of the load change has littleeffect on the inverter output impedance. The outputvoltage harmonics depend on both the hamionics genera-ted by the inverter output voltage and load current. Thetransfer function of output voltage and inverter outputcurrent is represented as follows:

    Unis) f is)Ais) Z¡is)+ Bis)

    (13)

    ¡1.4. Two-Port Model

    TTie plant of output filter satisfies linear property, so itT( ) ^

    Ais)[Ais)Z,is)+Bis)]

    Copyright O 2009 Praise Worthy Prte S. r.l.-A ¡I rights reserved InlemaiioHo! Review of Electrical Engineering, Vol. 4. N. 4

    515

  • G. Shahgholian, J. Faiz, M. Arezoomand

    TABLE1EQUAL PAR/Wlirri-IRS O r Dll-KERKNT INVERTER OUTPUT FILTER

    Paramcier

    A

    B

    C

    D

    Mono filter

    1 + /,^.,C,., s

    L,,s

    1

    LCL lüter Multiple filter

    1 + 1 ^ + ¿

    The transfer function of capacitor current of secondfilter is given by:

    (15)

    The plant open loop roots are dependent on the loadimpedance. The open loop root locus with toad resistancechanging form zero to infinite for multiple-filter andmono-filter are shown in Figs. 8 and 9 respectively.

    As shown in the diagram, the points marked by (A)are the pole positions under no load condition. Thepoints marked by (B) are the plant pole root positionsunder zero load condition. It can be observed that thelocation of the system poles vary with different kinds ofloads, input dc voltage, the parameters of inverter outputfilter and the incremental change in the modulationindex.

    i n . Voltage Droop and Loss Reduction

    By ignoring the filter capacitor series resistance, theequivalent circuits of the averaged system for mono- andmultiple-filter are shown in Figs. 10 and 11 respectively.In the mono-filter, L̂ is filter inductance. Cr is filtercapacitance and RK is equivalent series resistance (ESR)of the filter. In this section analysis is based on acriterion such as the same load impedance, dc voltage,total inductance and capacitance, therefore LF^LKI+LH-J,CK-CFI+CF2 and RK=RK,+RI.-2. If LK2-KFU, and Cn= Kc

    CFI, the inductors and capacitors reactance in themultiple-filter in terms of the inductor and capacitor rea-ctance in the mono-fiiter are:

    (16)

    (17)

    Fig. 8. Open loop roo! locus with load resistancechanging wiih mono-fTlter

    Fig .9. Open loop root locus with load resistancechanging with multiple-filter

    (18)

    (19)

    Fig. 10. Equivalent circuit of the averaged system with mono-filter

    Fig 11. Equivalent circuit of the averaged system with multiple-fil ter

    The system variables in the steady state in terms of theload parameters and filter components at the modulatingsignal frequency (tu), are obtained using the phasor anal-ysis. The filter inductor current in the steady state formono-filter for a pure resistive load with resistance RL is:

    R,(20)

    Copyright G 2009 Praise Worthy Prize S.r.l. • All rí^ts reserved international Review of Electrical Engineering. Vol. 4. N. 4

    516

  • G. Shahgholian, J. Faiz, M. Arezoomand

    The niter inductors currents in the steady state formultiple-filter for a pure resistive load with resistance RLare:

    (21)

    and (eq. (22)):

    R,

    kf_K/,X,: R,.

    Consequently, voltage droop in multiple-filter is lessthan mono-filter Figs. 12 and 13 shows the frequencycharacteristic of the open loop system of the output volt-age in terms of change of KC"CF;/CFI and KH"LV2/LFÍ-

    At high frequency ranges (more than 1000 Hz), harm-onics attenuation is 80 dB per decade in two filter case.Thus a multiple-filter with the same size as a secondorder niter causes more attenuation in harmonics. Usingmultiple filter the resonance frequency given by equation( 16), depends only to values of the filter components.

    1

    ¿,..,1

    = 0(28)

    The ESR of the inductor filter is very small and it

    means that 1 -L,,-Cy

  • G. Shahgholian, J. Faiz, M. Arezoomand

    change of Ko and Kp, which is the resonant frequency ofone filter:

    (29)

    Figs. 14. The change of small resonant frequency in terms ofchange of IQ.- and K|.

    1

    ^ ^ ^ ^

    -K^iB---

    '•

    '

    > <

    — — , - — .

    •Ä?7n?r.»i'!

    i•I 02 03 04 as 0« 07 OB 09

    10

    T

    e

    »

    4

    2

    "T—— •-•.•.::-i it:::::

    I 0.1 as D.< us D.e Di* oe o s i

    Figs. 15. The change of big resonant frequency changes in terms ofchange of K

  • G. Shahgholian, J. Faiz, M. Arezoomand

    mercially is the proponional-integral-derivative (PID)controller. The three-mode or PID controllers are widelyutilized in industries, because of its available, simplicityand low cost. It us weil know that the main controlobjective in a ups inverter is the tracking of the deliveredvoltage towards a desired sinusoidal reference in spite ofthe presence of distorted loads [ 18].

    The system block diagram of controller is shown inFig. 17, where KPWM is gain of PWM inverter, KB isfeedback gain. The error signal (UK) is obtained fromsuccessive comparison of the output voltage (UQ) withreference voltage (UR). The inverter switching pattern isthen obtained from a comparison of error signal and afixed high frequency triangular waveform.

    In order to reduce the steady state error between theoutput voltage and its reference waveform, a PI controll-er may be used in the feed forward path of the outer loadvoltage feedback loop. When a PI controller is used forthe system, the load voltage is given by:

    (30)Bis)

    where:

    (31)

    The closed loop transfer function of the controlsystem is:

    (32)

    B{s)+ Z, is) [A(S)+ K

    The steady state error between the output voltage andits reference waveform decreases with increasing valuesof K.|. Conversely, increasing the Kp decreases the boththe main components of output voltage and THD.

    The state space equations of the closed loop systemwith inductive load as shown Fig. 18 are given by:

    ±i" ' • • '

    -/•I

    py

    d_dt c //.,-

    (33)

    1

    -'Fl

    (35)

    d^

    dt-^^io (36)

    d . Rr—-h

    d_

    dt

    (37)

    (38)

    where er is output of integral control, Kp is proportionalgain, K.| is integral gain and state variables vector is:

    =[//.! ¡¡.2 n " / •/ • 2 (39)

    The closed loop system root loci for changing ofcontroller parameters are presented in Figs. 19 and 20.The step response with Kp̂ O.Ol and K.j-40 is show inFig. 21.

    VI. Simulation Results

    Simulink is widely used in many fields because it cando most type of simulation for industrial application. Inthis section, a Simulink model of the control scheme asshown in Fig. 22 are developed to study the performanceand dynamic system simulation of the basic UPS system.

    Fig. 17. Transfer function model of closed loop system

    Fig. 18, Block diagram of closed loop system in state space

    LOO« m o r LOCUS MITHNIKMtiCM CONSTANT CHWQMO

    Fig 19, Closed loop root locus for change of K¡ (Kp=O,OI )

    Copyright O 2009 Praise Worthy Prize S.r.l - AU rights reserved international Review of Electrical Engineering. Vol. 4> N. 4

    519

  • G. Shahgholian, J. Faiz, M. Arezoomand

    Q ' C L C S E ) LOOP ROOT L0aSV>im4 PROf-CftT)OWU. CONSTA^^T O I M M M O

    IS [

    8TEP RESPONSE UNOER REBISTtVC LOAO

    W—

    <

    <

    Gain = 0.0U

    Ciin-0

    \

    Gail

    1

    t1

    .

    -wn -3nni .xm -lam -isn -inn -MD n

    Fig. 20. Closed loop root locus for c h a i ^ of K)- (K|=40)

    Fig. 21. Step response of closed loop system withand K,=40

    Runge-Kutta is used for Ihe calculation method of themain circuit and the calculating step size Is sel at 1 ^s.

    4

    1 '

    U

    ••(•cur

    IDoonia

    1 ion 1 » 2

    Fig. 22. System Simulink model

    Figs. 23 show the Bode diagram of the open loop tran-sfer function of the illter capacitor current and Figs. 24are the Bode diagram of the open loop transfer functionof the output voltage for two types of filters In the invert-er output under inductive load (ZL=3.4, PF=O.8). At highfrequency ranges (higher than 1000 Hz), harmonicsattenuation is 40 dB per decade in LC filter and 80 dBper decade in two filter case. At low frequencies theharmonic attenuation is almost the same in filters, inother words the behavior of two filters is similar to thesingle one. Thus a multiple LC filter with the same sizeas a LC filter causes more attenuation in harmonics. Thevalues of Lpi and LR are lower in two filter case than thevalue of Lp in the single case and there is less voltageloss in the two-filter case. The main problem of the twofilter case is a high current ripple in Ihe inductor Lpi.Bode diagram of the close-loop transfer function of theouter voltage loop of the UPS system for mono- andmultiple-filter shown in Figs. 25.

    ...liliUilli

    'I

    J

    Figs. 23, Frequency characteristic of the open loop syslem of thecapacitor current for different filters

    Copyright O 2009 Praise Worthy Prize S.r.l. - All rights reserved International Review of Electrical Engineering. Vol. 4. N. 4

    520

  • G. Shahgholian. J. Faiz. M. Arezoomand

    Figs. 24. Frequency characteristic ofthe upen loop syslcm of theoutput voltage for different filters

    -11 --Ik

    1

    s

    I]

    1...

    1

    1!1!

    •.'-• T. , .,1

    ,v\̂

    1

    's,

    Figs 25 Bode diagram ofthe close loop transfer function ofthe outervoilage for multiple filter (solid) and mono Tiller (dot)

    The characteristics ofthe control system for Kp=0.05and Ki=40 for resistive load (R|=3.4n), inductive load(Ri_-3.4Í5, LL-0.02H) and no load are shown in Table II.Fig. 26 shows the Fourier spectrum of inverter outputvoltage under linear load. Figs. 27-28 show simulationresults under nonlinear load with L^O, C^2000|iF and

    TABLE IISiMl iI-ATION RFSULTS WlTH DlFrEKHNT I.OADR

    DilTcrciil Liiads

    100% Load50% Uad

    20(1% LoadNo Lnac!

    Kiiiidamcnial [ V)

    33.0433.0633 0233.07

    THD1%)0.54%045%0 42%1) 99%

    •0

    •ft

    10

    j

    f...X

    i 1

    f̂ t r^ T t' T 1

    I 1

    / \/ \

    \ y

    r\/ \\ /\J_—_j

    / \/ \

    i—t

    \ ,

    \ /

    \J

    t\i \f

    \ J

    \ y

    ñ Í

    Fig. 27- Simulation results under nonlinear load

    Figs. 28. Simulation results under nonlinear load -and currenl of dc-load

    voltage

    VII. System Tests and VerificationTo show the validity ofthe proposed output filter and

    control method, a small experimental system with thescheme as shown in Fig. 29 was built and operated in thelaboratory. The system has an inverter consisted of asingle phase MOSFET füll bridge with a switchingfrequency of 8000 Hz and multiple output filters. ThePWM pulse generation circuit. Inverter controller andPWM pulse generation circuit for switches in the eachlink are shown in Figs. 30-31-32, respectively. The deadtime force circuit show in Fig. 33.

    Fig 26 Fourier spectrum of inverter output voltage under linear load Fig. 29. Set of practical test

    Copyright O 2009 Praise Worthy Prize S.r.l - All right'! reserved International Review of Electrical Engineering, Vol. 4, N, 4

    521

  • G. Shahgholian, J. Faiz, M. Arezoomand

    P3LM311

    3 e

    Fig. 30. PWM puise generation circuit

    S.1K S.1K

    Fig. 31 PI controller

    Fig. 32. PWM pulse generation circuit for switches in the each link

    The experimental results corresponding to the simulat-ed cases are presented in Figs. 34-35. When loads conne-cted at the output of the inverter are nonlinear in nature,the load currents consists of harmonics in addition to thefundamental frequency component. The advantages ofmultiple-filter are reduction of devices size and voltageratings for the switches, more attenuation in harmonics,less voltage loss and the improvement of control res-ponse.

    (a) Voltage scale 20V/div, time scale Sms/div

    (b) Voilage scale 2ÛV/div, lime scale 5msMiv

    Figs, 34. Output voltage of the single inverter system operating with apure resistance (a) simulation with Matlab (b) measurement

    • à g0!-!C

    Fig. 33, Dead time force circuit

    Figs. 35, Thcresultswaveformof I-oad current withnonlinear loadExperimental result (upper) - Simulation result (down)

    (Cun-ent scale lOA/div. Time scale 50ms/div)

    Also, the THD of load voltage reduction, because theharmonics reduced by going for multiple filters.

    VIII. Conclusion

    In this paper an uninterruptible power supply (UPS)system with two LC filter in the inverter output is analys-es and their effects on reducing the distortion in theoutput voltage are shown. The proposed model uses theLaplace transform and two-port network. Also, it hasbeen implemented in Matlab/Simulink. By running thesimulation model, the comprehensive performances ofmulti-filter can be obtained efficiently. Fourier analysisuse to predict the load voltage harmonic spectrum. Inve-rter output voltage have THD to less than 5% even whensupplying power to highly nonlinear loads which draw

    Copyright © 2009 Praise Worthy Prize S.r.l. - All rights reserved Inlemational Review of Electrical Engineering. Vol. 4. N. 4

    522

  • G. Shahgholian, J. Faiz, M. Arezoomand

    cun-ent with a crest factor of 3. Finally, simulation andexperimental results have been reported and discussed.

    The simulation is achieved under the dc sourcevoltage is ripple free and constant. Also, in the simulatio-n, the inverter switching devices are assumed as idealswitches, but SPWM modulation is not an ideal amplifi-cation including dead time and conducting resistance ofdevice. Therefore, the THD of experimental result ishigher than the simulation.

    References11 ] J.Faiz, G.Shahgholian. M Ehsan, "Stability analysis and simulati-

    on of the singte-pha.se voltage source UPS inverter with two-stagecascade output filter". Euro. Trans. Elecir. Peru.. No.¡S. 2008.pp 29-49.

    [2] H L Jou, J C Wu. C.Tsai, K D Wu, M.S.Huang, 'Novel line inter-active uninterruplibic power supply", lEE Prac. Elecir.. Pow.AppI.. K(?/,/i;..Va.î,pp.359-364, May 2004

    [3] J Kim. J.Lee, K Nam. "Inverter ba.sed local AC bus voltagecontrol utilizing two IX)F control". /£>,'£" Tran. On I'ow. Elec.Vol.23. No.3. May2U08, pp 1288-1298

    |4| M.Arias, DGLamar, M Rodriguez, M.Hcmando, A Fernandez,"Simple droop voltage control .system for parallel operation ofUPS", ¡EEE/APEC. February 2008. pp 1296-1302

    [5] J Faiz, G.Shahgholian, "Uninterruptible power supply - Areview", Electomotion. Voll3. No.4. Nov/Dec 2006, pp 276-289

    [6] H Deng. R Oruganti, D Srinivasan, "Neural controller for UPSmvertcrs based on B-splinc Netuork", ¡EEE Tran. On Ind. Elec.Vol.55. No.2. February 2008, pp 899-909

    ]7] A Nasiri. Z Nie, S B.Bekiarov, A.Emadi, "An on-lmc UPS systemwith power factor conection and electric isolation using BIFREDconverter", ¡EEE Tran. On Indu. Elec. Vol.55. No.2, Febmary2008. pp 722-730.

    |8] H Deng, R.Oruganti, D Srinivasan, "A simple control method forhigh-performance ÜP.S inverters through output-impedancereduction", IEEE Tran. On ¡nd. Elec. Vol.55. No.2, February2008, pp.888-898

    [9] G Willmann, D F Coutinho, I. F A Pereira, F B Libano, "Múltipleloop H-infinity control design for uninterruptible power supplies",¡EEE Tran. On ¡nd. Elec. yol.54. No.3, June 2007. pp 1591-1602

    [10] TFWu, YEWu, HMHsieh, Y K Chen, "Cunem weightingdistribution control strategy for multi-inverter systems to achievecurrent sharing". ¡EEE Trun. On Pow. Elei, Vol.22. No.l, January2007. pp 160-168

    [II] MTTsai. C H Liu. "Design and implementation of a costeffective quasi line interactivo ups with novel topology", ¡EEETrans. On Pow. Elect.. Vo¡. 18. No.4. My 200i,pp 1002-1011.

    ]12] M NiriKimand, H R.Karshenas," Performances specifications ofseries-parallel UPS's with different control strategies", ¡nte. Rev.of Elec Eng (IREE). Vol.4. No!. Jan-Feb. 2009, pp. 14-21.

    [13] H.Komurcugil, O.Kukrer, A.Doganalp, "Optimal control forsingle phase UPS inveners based on linear quadratic regulatorapproach", ¡EEE/SPEEDAK4, pp74-29. May 2006.

    [ 14] F S Pai, S J Huang, "A novel design of line interactive unintcnu-ptihle power supplies without load current sensors", ¡EEE Trans.On PovK Elec. Vol.21. No.l. pp.202-210, January 2006.

    [15] J.Faiz, G Shahgbolian, "Modeling and simulation of a three-phaseinverter with rectifier-type nonlinear loads", ¡nter. Con. Semi.Mic & Nano. (ICSMNJ. Tsakhcadzor, Armenia, July 2009.

    [16] ¡favA. Gh Shahgholian. "Study and Simulation of a Single PhaseUPS Inverter with Rectifier Load", ECTI-CON. May 2006,pp 417-420.

    ]17] J K Steinke. "Use of an LC filter to achieve a motor friendlyperformance of the PWM voltage source inverter", ¡EEE Trans.On Ene. Conv.. I'ol 14. No.3. September 1999, pp 649-654.

    [18] R Zhang. F C Lee, D Boroycvich, H Mao, "New high power, h i ^

    performance power converter .systems", ¡EEE Trans. On Powe.Klecir.. Vol. 15. NoJ, May 2000, pp.456-463

    119| S J Chiang. TL Tai. T S Lee, "Variable structure control of UPSinverters", ¡EE Proc. Elecir. Power. Apll.. Vol.145, No.6,November 1998, pp 559-567

    ]20] M.J Ryan, W (i.Brumsicklc, R.D.Lorenz, "Control topology opti-ons for single phase UPS inverters". IEEE Trans. On Ind. AppI..Vol.33. No.2, March/Apnl 1997, pp 493-501

    |2l] G Escohar, A A Valde7, J L Ramos, PMatlavelli, "Repetitivebased controller for a UPS inverter to compensate unbalance andharmonic distortion". ¡EEE Trans. On Indu. Elec. Vol.54. No.l.February 2007, pp.504-510.

    Authors' informationDepartment of HIectrical hngineering, Islamic Azad Univcrsrty.

    Najafabad Branch, Najafabad. Esfahan, Iran,

    'Department of Electrical and Computer Engineering, Faculty ofEngineering. University of Tehran, Iran

    Gha/^nTar Shuhfiholixn was born in Hsfahan.Iran, on December 7, 1968 He graduated in cicct-"^^' '̂ "g"'*-''̂ '̂ 'ng 'Ĵ """ Hsfahan University ofIcchnology (lUf), Isfahan, Iran, m 1992. liereceived the M Sc and PhD in electrical engineer-ing from Tabriz University, Tabriz, Iran in 1994and from Islamic Azad University, Science andResearch Branch, Tehran, Iran, in 2006, respecti-

    vely He is now an associate professor at Department of l-lectricalEngineering, Faculty of Engineering, Islamic Azad tlnivcrsityNajafabad Branch His teaching and research interests include applicat-ion of control theory to power system dynamics, power electronics andpower system simulation

    Jawad f»it received his Ph.D. in ElectricalI-'ngineering from the University of Newcastleupon Tyne. England in 1988 He is now aProfessor at lieparlmem of Electrical and(•(imputer l-ngineering. Faculty of Engineering,University of Tehran He is the author of 215publ ications in intemationai journals andconference proceedings Dr Faiz is a senior

    member of IEEE. He is also a member of Iran Academy of SciencesHis teaching and research interests are switched reluctance and VRmotors design, design and modeling of electrical machines, drives, aniltransformers,

    Mohsen Arezoomand was bom in Isfahan. Iran.on September 2. 1976. He graduated in electricalengineenng from Isfahan University ofTechnology (IUT), Isfahan, Iran, in 1992 Hereceived the MSc in control engineering fromIsfahan University of Technology (IUT). Isfah-an, Iran m 2002 respectively His researchinterests include application of automation con-

    trol, power elccuonics and power system simulation

    Copyright C 2009 Praise Worthy Prize S.r.l. - All rights reserved International Review of Electrical Engineering. Vo¡. 4. N. 4

    523