elecrical equipment maintenance in pipelines
TRANSCRIPT
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
1/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
1submitted by Anirban Das
ELECRICAL EQUIPMENT MAINTENANCE IN PIPELINES
1. INTRODUCTION:
The most economical way of transporting petroleum products from one place to
another is through the pipelines. The pipeline offers low operating cost and high reliability of
transportation of fluids.
Generally pipeline consists of the following major systems:
Tank farms
Pumping stations
Metering stations
Valve manifolds
Pigging stations
SCADA systems
Corrosion control systems
Figure-1: Product pipe line system
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
2/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
2submitted by Anirban Das
The major electrical equipments that are used in pipelines are:
POWER SUPPLY AND DISTRIBUTION
SUB STATIONS
TRANSFORMERS
SWITCH GEAR
ELECTRIC MOTORS
MOV ACTUATORS
CATHODIC PROTECTION SYSTEMS
EMERGENCY GENERATORS
2. POWER SUPPLY AND DISTRIBUTION
The power supply and distribution depend on the electrical power requirements (or
maximum demand load) for the installation.
2.1 LOAD ESTIMATION:
Load estimation requires analysis of load characteristics and will take into account
the demand factor relationship between connected loads and the actual demand imposed on the
system. For load estimation the following factors are used.
2.1.1 Preliminary loads:
The minimum loads which are connected to power system.
2.1.2 Demand Factor:
It is defined as ratio of maximum demand (largest demand during a specified time) to
the total connected load.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
3/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
3submitted by Anirban Das
By this demand factor we can know the capacity of transformer and the conductor
size, and all equipment associated with distribution of electrical power to utilization equipment.
2.1.3 Diversity Factor:
Diversity factor is defined as the ratio of the sum of the individual maximum
demands of various subsystems within a system to the maximum demand of the system.
2.1.4 Load Factor:
Load factor is defined as the ratio of the average load over a designated period of
time to the peak load occurring in that period.
A low load factor indicates short-time demand peaks which can result in heavy
charges to the Using Agency. Low load factor will be corrected by shedding loads or by peak-
shaving generation during periods of peak demand.
2.2 Voltage Requirement:
The voltage requirement is based on the type of distribution. That means
primary distribution and secondary distribution.
Primary distribution means distribution from main substations to local substations.
Secondary distribution means local substations to domestic users.
The voltage requirement is also based the type of equipment we are using.
3. SUBSTATIONS
Substations mainly consist of:
Power transformers
Underground cables
Air circuit breakers or Oil circuit breakers
Buses
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
4/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
4submitted by Anirban Das
Protective relays
Current transformers and Voltage transformers
LT/HT control panels
Lightening or Surge arrestor
Grounding
Figure-2: An 11 KV substation (single line diagram)
4. TRANSFORMERS
4.1 BASIC PRINCIPLE:
The transformer is based on two principles:
An electric current can produce a magnetic field (electromagnetism)
A changing magnetic field within a coil of wire induces a voltage across the ends of the
coil (electromagnetic induction).
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
5/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
5submitted by Anirban Das
Figure -3: An ideal step-down Transformer
4.2 SWITCHING ON AND OPERATION:
4.2.1 HV Energisation:
When the installation has been fully checked, the HV side can first be switched-on and
following this, the LV side. It is recommended that the transformer is left energized for a few
hours before switching-on the LV side and applying load. During this time the transformer should
be closely supervised paying attention to both coolant oil level and temperature. Verify the voltage
between the low voltage phases and phase to neutral if used.
4.2.2 Re-adjusting the tap switch:
The tap switch enables sections of the HV winding to be in or out of the turns ratio
thus affecting the secondary low voltage side. When the voltage measured at the low voltage side
deviates from the required value this usually indicates that the incoming HV voltage is too high or
too low. Normally the supply voltage is held within limits of plus or minus 6%. The tapping switch
can compensate for variations of plus or minus 5% in 2.5% steps. If adjustment is desired then the
following procedure should be followed.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
6/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
6submitted by Anirban Das
Disconnect the transformer from both the HV systems and the LV systems.
Unlock and remove the padlock, if fitted. Release the tapping switch mechanism by lifting
the operating handle.
Turn the handle to the desired position to increase LV volts - turn to a higher tap position
number, which will decrease the HV, turns in circuit and proportionally increase the output
voltage.
4.3 MAINTENANCE:
4.3.1 ONLINE MAINTENANCE:
Frequency of routine maintenance is quarterly for distribution transformers and daily
for grid transformers.
Check load current: If more than rated, reduce non priority loads
Check voltage: control the appropriate voltage H.V voltage and L.V voltage variations. If
online tap changer (O.L.T.C) is provided change the tap positions as required.
Check OTI&WTI readings:
Check the temperature does not increase beyond rated temperature.
Check oil level in Transformer and O.L.T.C: check the oil level in respective conservators.
Ensure that they are not beyond rated temperature. If not top up with dry transformer oil.
Check transformer for oil leaks.
Check breather on transformer and O.L.T.C: check color of silica gel. It should be blue. If
it is pink replace it by spare charge.
Check sound level: Certified sound levels determined in accordance with NEMA, shall not
exceed the following:
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
7/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
7submitted by Anirban Das
Transformer Rating
Sound Level Rating
0 - 9 KVA 40 dB
10 - 50 KVA 45 dB
51 - 150 KVA 50 dB
151 - 300 KVA 55 dB
301 - 500 KVA 60 dB
TABLE-01
4.3.2 ANNUAL SHUTDOWN MAINTENANCE:
Visual inspection of transformers for oil leakage, oil level, and silica gel conditions should
be done.
Clean the transformer body and paint it if necessary.
Check the oil level and top-up in necessary.
Remove the silica gel and reactivate if necessary.
Open H.T terminal box and check for loose connections, heating and oil leakage from
bushings.
Open L.T terminal box and check for the same.
Check the body and neutral earthing joints.
Check the tap changer for pitting and overheating etc;
Examine Bucholzs relay, OTI (oil temperature indicator) and WTI (winding temperature
indicator) relays operation and check for accuracy.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
8/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
8submitted by Anirban Das
4.3.3 CAPITAL OVERHAUL:
Capital over haul shall include overhaul inspection, lifting of core and coils, cleaning
of transformer tank. Frequency of overhaul will be normally in between 7 to 8 years.
TRANSFORMER OIL: Properties
S.N Description New oil Old oil
1
2
3
4
Electrical strength
Moisture, Mechanicalimpurities
Flash Point
Viscosity at 270C
40kv
None
140
0
C
27 cst
25kv/40kv
25/35 ppm
Max. 5
0
C lower
27 cst
TABLE-02
After one year any changes in the oil properties above said, the oil should be changed. The old
mineral oil should be reconditioned.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
9/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
9submitted by Anirban Das
The following table depicts the transformer trouble shooting
SYMPTOM CAUSE CORRECTIVE
MAINTENANCE
High Temperature.
Fractured metal or
porcelain parts of thebushings.
Badly discolored oil.
DRY_TYPE
TRASNFORMERS:
High temperatures
Moisture
Over voltage.
Over current.
High ambient temperatures.
Insufficient cooling.
Unusual strains place on
terminal connections.
Contaminated by varnishes.
Carbonized oil due to
switching.
Winding or core failure.
Insufficient air flow
Transformer in moisture
atmosphere or accidental
wetting
Change the circuit voltage or
transformer connections to avoid
over excitation.
If possible reduce the load.
Heating can often be reduced by
improving power factor of load.
Check parallel circuits for
circulating currents which may be
caused by improper ratios of their
impedances.
Either improve ventilation or
relocate transformer in lower
ambient temperature.
Make sure cooling is adequate.
Cables and bus bars attached to
the transformers should beadequately supported. In the case
of heavy leads, flexible
connections should be provided to
remove strain on the terminal and
bushing porcelain.
Retain oil if di-electric strength is
satisfactory.
Filter/ reclaim/ replace oil.
Repair transformer.
Check that in take is not
obstructed. If unit is fan cooled
check fan speed.
Transformers dry out to be done.
TABLE-03
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
10/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
10submitted by Anirban Das
5. ELECTRICAL POWER CABLES
5.1 INTRODUCTION:
A power cable is an assembly of two or more electrical conductors, usually held
together with an overall sheath. The assembly is used for transmission of electrical power.
Power cables may be installed as permanent wiring buried in the ground, run overhead, or
exposed. Flexible power cables are used for portable devices, mobile tools and machinery.
For constructional details of power cables see ANNEXURE- A
For cable selection criterion see ANNEXURE-B
For cable laying details see ANNEXURE-C
For testing of cables see ANNEXURE-D
For NETA insulation standards see ANNEXURE-E
5.2 CABLE FAULTS:
The problems occurs in the cables due to
Environmental changes.
Changes in the thermal resistivity of the soil.
Defects in the earthing and bonding.
Excavation by other utilities.
The most frequent faults are short circuit faults and earth leakage faults and
insulation breakdown. Due to these, some part of the cable (specifically, underground) get
heated up and burst.
5.3 LOCATING CABLE FAULT:
There are two basic methods of locating an underground cable fault.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
11/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
11submitted by Anirban Das
5.3.1 Sectionalizing:
In this procedure, we divide the cable into smaller sections and examine the insulation
resistance or continuity.
5.3.2 Thumping:
When we supply a high voltage to a faulted cable, the resulting high-current arc
makes a noise loud enough for us to hear above ground. While this method eliminates the
sectionalizing method's cutting and splicing, it has its own drawback. Thumping requires a
current on the order of tens of thousands of amps at voltages as high as 25kV to make an
underground noise loud enough for you to hear above ground.
The heating from this high current often causes some degradation of the cable insulation.
There are some relatively new methods of locating cable faults that use rather
sophisticated technology.
5.3.3 Time Domain Reflectometry (TDR):
The TDR sends a low-energy signal through the cable, causing no insulation
degradation. A theoretically perfect cable returns the signal in a known time and in a known
profile. Impedance variations in a "real-world" cable alter both the time and profile, which
the TDR screen or printout graphically represents. This graph (called a "trace") gives the user
approximate distances to "landmarks" such as opens, splices, Y-taps, transformers, and water
ingression.
One weakness of TDR is that it does not pinpoint faults. TDR is accurate to
within about 1% of testing range.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
12/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
12submitted by Anirban Das
Another weakness of TDR is that reflectometers cannot see faults-to-ground with
resistances much greater than 200 ohms. So, in the case of a "bleeding fault" rather than a
short or near-short, TDR is blind.
5.3.4 High-voltage radar method:
There are three basic methods for high-voltage radar, they are
Arc reflection
Surge pulse reflection
Voltage pulse reflection
The arc reflection method uses a TDR with a filter and thumper. The filter limits both
the surge current and voltage that can reach the cable under test, thus allowing
minimal stress to the cable. Arc reflection provides an approximate distance to the
fault (when there is an ionizing, clean arc produced at the fault and the TDR in use is
powerful enough to sense and display a reflected pulse).
The surge pulse reflection method uses a current coupler and a storage oscilloscope
with a thumper. The advantage of this method is its superior ability to ionize difficult
and distant faults. Its disadvantages are that its high output surge can damage the
cable, and interpreting the trace requires more skill than with the other methods.
The voltage pulse reflection method uses a voltage coupler and an analyzer with a
dielectric test set or proof tester. This method provides a way to find faults that occur
at voltages above the maximum thumper voltage of 25kV.
One test to detect an open neutral requires shorting a known good conductor to a
suspect neutral, then measuring the resistance with an ohmmeter. If the reading is 10
ohms or higher, we can suspect an open neutral. Remember, other objects can
complete the circuit.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
13/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
13submitted by Anirban Das
5.4 REPAIRING OF CABLES:
The repairing is nothing but locating the cable fault and cut the cable and re-joint
the cables. There are two methods presently used in jointing of the cable, they are
Polyurethane Cable Jointing.
Heat shrinkable Cable Jointing.
5.4.1 POLYURETHANE CABLE JOINT:
Underground cable joints in electricity distribution networks must remain
moisture free to prevent arc failure of any joint. Because the joints are created on-site, the
quality of the jointing technique is critical.
The quality of the joint is such that it does not add any resistant to the circuit. The
materials and technique so designed to give adequate mechanical and electrical protection to
the joints under all service conditions.
Polyurethane kit consists of
Adequate number of mechanical conductors.
PTFE (Polytetrafluoroethylene) tube set to provide primary electrical insulation and
correct cable positioning.
Cast metal conducting tubes to make the electrical cable connection with snap -off
bolt heads to ensure that perfect compression torque is applied.
Armour bonding system in case of armoured cables (Earth continuity).
A pair of white Glassfibre-Reinforced-Polyester (GRP) mating shell moulds which
completely enclose and seal the joint, forming the inner shell.
A container of liquid silicone, which is poured into the polyester mould, completely
encasing the cable joint.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
14/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
14submitted by Anirban Das
Figure-4: Cutaway view of straight water resistance medium voltage underground joint
Figure-5: Cable jointing Kit
Figure-6: Conductor joints in the cable
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
15/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
15submitted by Anirban Das
Figure-7: POLYURETHANE JOINTING PROCESS
The above figure shows us how the polyurethane jointing process is going. The
third from right connector is having its white, inner shell mould filled with liquid silicone.
Note the temporarily placed funnel, mounted in the white inner shell, towards the foreground,
which ensures the correct level of the silicone fill and zero air entrapment, and the support
frame holding the container, as the filling is carried out. The liquid silicone container has two
outlets, and the flow rate into the white, inner shell, is controlled by the gentle release of the
seal on the second, (red) cap. As soon as the silicon pour is completed, the entry holes into
this white mould are sealed. The whole process is cold, ideal for hazardous zoned areas.
5.4.2 HEAT SHRINKABLE CABLE JOINT:
Heat shrinksplices are available as a series of heat shrinkable tubes. Some may
be preassembled by the manufacturer to reduce the number that must be handled in the field.
The tubes must be slipped over the cable prior to connecting the conductors. After
positioning each tubeover the connected cables, heat is applied to shrinkthe tube snugly over
the underlying surface and soften anymastic material used in the assembly. Stress relief is
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
16/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
16submitted by Anirban Das
generally provided by stresscontrol tubesthat arealso shrunkinto place sothat endsof the
stress control tubeoverlap both cable insulation shields. The joint is finished in thenormal
manner.
Figure-8: Heat shrinkable cable jointing Kit
During the heat shrink installation process, the stored recovery force of the tube
is released in addition to the recovery force of the heat shrinkable outer layer. A pre-designed
screen and thick layer of insulation is installed in one simple process. This allows extremely
tight electrical interfaces due to the shrink force generated. The elastomeric (tube) insulation
characteristic combined with the rigid outer heat shrinkable screen layer enables the joint to
follow the thermally induced dimensional changes of the cable insulation.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
17/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
17submitted by Anirban Das
5.5 MAINTENANCE:
SCHEDULE EQUIPMENT TASK
Annually Cable Terminations Check connections for security
(Except switchgear connections)
Cable above ground Check for outer sheath damageCheck attachment to poleWhere fitted, ensure protectivepipe is secure.
Cable loading Where fitted, check and recordDemand indicator readings(MV cable loadings are normallyestablished by load flow studies).
Earthing Check all earth connections forsecurity.
5 yearly Earthing Test all earth connections at MVand LV substations and compareto standards.
TABLE-04
6. SWITCH GEARS AND PROTECTIVE RELAYS
6.1 INTRODUCTION:
Switch gears are available in many forms, from single simple isolator to
sophisticated vacuum breakers.
The term switchgear, used in association with the electric power system, or grid,
refers to the combination of electrical disconnects, fuses and/or circuit breakers used to isolate
electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done
and to clear faults downstream.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
18/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
18submitted by Anirban Das
6.2 TYPES OF CIRCUIT BREAKERS:
The circuit breakers are classified on the basis of insulating medium present in it.
They are
Air circuit breaker
Vacuum circuit breaker
SF6 circuit breaker
Oil circuit breaker
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
19/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
19submitted by Anirban Das
Figure-9: A 25 kv Single phase Air Circuit Breaker
For the circuit breaker it is necessary to beak the circuit immediately when the fault
occurs and isolates the fault position from healthy position.
To ensure the equipment remains safe and reliable, regular examination is essential.
6.3 MAINTENANCE:
Essential areas requirements for inspection and testing:
6.3.1 INSULATION:
Insulation systems must be closely inspected for sings of over heating, cracking and
other defects.
6.3.2 CONTACTS:
Inspect the contacts for signs of excessive wear and over heating. Free movement of
the contactors also examined.
6.3.3 TERMINALS:
All terminals must be checked for firmness and signs of over heat.
6.3.4 CABLES:
Power and control cables must be examined with the connecting equipment.
6.3.5 BUS BARS:
Bus bars shall subject to periodic inspection.
6.4 MAINTENANCE OF POWER AIR CIRCUIRT BREAKER:
Power air circuit breaker should be maintained annually.
To perform maintenance, withdraw the circuit breaker from its enclosure and do the following:
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
20/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
20submitted by Anirban Das
Inspect alignment of movable and stationary contacts. Make adjustments as
recommended in manufacturers manual.
Wipe bushings, barriers, and insulating parts. Remove the dust, smoke, and any foreign
deposits. Replace the damaged parts.
Check control devices and replace if needed.
Check breaker control wiring and ensure that the connections will be tight.
Operating breaker in fully opened and closed position after service. Check for any
binding before going to put in the circuit.
6.5 MAINTENANCE OF CONTACTOR:
The duty of the contactor is very often in a day. Such duty reflected in mechanical wear and tear
and also electrical contact wear. The maintenance process:
Cleaning
Dressing or renewal of main and auxiliary contacts.
Checking contact alignment.
Trip mechanism inspection.
Check tightness and conditions of all connections.
Arc chute inspection.
Lubrication.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
21/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
21submitted by Anirban Das
6.6 MAINTENANCE OF ISOLATOR:
The maintenance of isolator mainly consists of:
Cleaning, checking contact conditions and tightness of connections and confirming the
tightness and continuity of the fuses, if fitted.
6.7 PROTECTIVE RELAY MAINTENANCE:
The maintenance of protective relays should include general inspection of physical condition of
all parts at regular intervals. Maintenance as follows:
Relays are provided with dust proof covers and before a cover is removed, the cases
should be carefully dusted.
Relay interior should be free from dust, iron particles etc.
Dust and dirt should be carefully wiped off by a soft squirrel hair brush. Mechanical
blowers or blowing by mouth is not recommended.
The internal wiring, ICs, printed circuits should be examined for corrosion. Excessive
heat may damage the insulation.
Relay flags/targets should operate freely without friction and also reset freely.
Perform complete tripping and operational tests to verify all control and protective
functions and alarms and tripping mechanism.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
22/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
22submitted by Anirban Das
TROUBLE SHOOTING:
SYMPTOM CAUSE CORRECTIVE
MAINTENANCE
Over heating
Breaker is not closing.
Improper alignment and
adjustment of contactor.
Burnt and pitted due to
lack of attention after
many heavy operations,
or too frequent
operations.
Breaker kept closed (oropen) for a too long
period.
Transmission of heat to
the breaker from
overheated or inadequate
cables or connection bars.
Failure of latching device.
Damaged trip coil
Damaged or dirty
contacts of tripping
circuit
Faulty connections in trip
circuit (loose or broken)
Insufficient voltage
caused by too much drop
in leads.
Poor voltage regulation
Loose connections
Contacts should be aligned and
adjusted properly. Contacts to be
repaired or replaced properly.
Burnt and pitted contacts should
be dressed up if possible or
replace with new parts. Dressing
up to be done carefully.
Contacts to be wiped out forcleaning and if possible silver-to-
silver contacts to be arranged.
If heat is due to excess current,
fault should be corrected. If
cable size is in adequate, cable
should be replaced.
Examine surface of the latch, if
worn or corroded, check latch,wipe, and adjust according to
instruction book.
Replace it.
Dress or replace damaged
contacts. Clean the dirty
contacts.
Replace faulty wires. All
connections are to be tightened.
Replace with oversize wires.
Improve contact at connections.
Check up voltage, if less correct
it.
Tighten the connections.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
23/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
23submitted by Anirban Das
Frequent damage of
moving and fixing
contacts
Bushing problems
Inadequate current
carrying capacity
Improper replacement of
switch gear during
maintenance.
Misalignment of controls
or inadequate pressure
between moving and
fixed contacts
Accumulation of dirt or
other deposits
Flash over due to foreign
deposits like salt, cement
dust etc.
Capacity of contactors as well as
breakers should be examined.
Capacity of original switch gear
should be matched with new one.
Contacts to be dressed up. Spring
etc. to be checked for proper
pressure.
Clean external surface.
Frequency of cleaning to be
increased. Carbon tetra chloride
or liquid ammonia or any other
suitable agent may be used to
clean porcelain.
TABLE-05
7. ELECTRIC MOTOR
7.1 INTRODUCTION:
Motors covert electrical energy into mechanical energy. Mainly motors are classified
into two types:
D.C motors
A.C motors
D.C. motors are mainly used in traction works and cranes where constant speed
characteristics are necessary. These are not used in domestic and industrial purposes because the
cost of the D.C motor is high and also the supply of D.C power also costly one.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
24/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
24submitted by Anirban Das
So the best alternative is using A.C motors. In general most of industries are using 3-
phase motors. Hence we here consider 3-phase motors only.
The motors are classified into two types:
Induction motors
Synchronous motors
Let us briefly discuss about induction motors because many industries using
induction motors only.
7.2 CONSTRUCTION:
Motor mainly consists of two basic parts know as
Stator
Rotor
Figure-10: cut way view of squirrel cage induction motor
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
25/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
25submitted by Anirban Das
Figure-11: Rotor of the squirrel cage induction motor
The stator winding and rotor windings are insulated. The primary purpose of
insulation is to withstand turn-to-turn, phase to-phase and phase-to-ground voltage such that to
direct the stator phase currents through the desired paths of stator windings.
The insulations are classified as:
Class A: 105C
Class B: 130C
Class F: 155C
Class G: 180C
For motors having high temperature rise class F insulation is uses.
7.3 MAINTENANCE OF MOTOR:
Motors are designed to give many years of reliable service with less attention. A
definite schedule of preventive/inspection/predictive maintenance should be established to avoid
breakdown. The schedule depends on the operating conditions and experience with the similar
equipment.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
26/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
26submitted by Anirban Das
7.3.1 PREDECTIVE MAINTENACE:
The main goal of the predictive maintenance is to predict and fix the faults by using
following techniques before they occur.
The techniques are:
Vibration analysis:
This technique involves measuring machinery vibration to identify ongoing
conditions through vibrometer. This tells us the bearing damages.
Motor circuit analysis:
This technology monitors the conditions of complete motor circuit parameters like phase
resistance, inductance and capacitance.
7.3.2 PREVENTIVE MAINTENANCE:
7.3.2.1 A schedule for LT&HT motors (Half yearly):
Counter check that equipment is isolated positively.
Check the terminal box for loose connection in the cable termination.
Perform regreasing.
Remove front and rear grease cups if regreasing system is not healthy.
Check the condition of the grease. Top up grease if condition is not o.k.
Put back grease cups.
Connect the terminal box.
Check the earthing and return the clearance.
Perform the visual inspection of the stator module, cable terminals.
7.3.2.2 B schedule for LT&HT motors(Predictive):
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
27/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
27submitted by Anirban Das
Counter check that equipment is isolated positively by means of LT/HT tester.
Get the motor decoupled.
Open the terminal cover and remove the cable connections.
Open the foundation bolts and take out the motor from foundation and send to electrical
workshop for schedule.
Inspect the motor for visible damages and rotor freeness.
Open the fan cover and remove the fan from the shaft.
Remove the grease cups on both sides. Inspect the condition of grease.
Take out both rear and front end shields.
Check the bearing housing for correct measurement of the bearing with sufficient
tolerances.
Remove both front and rear bearing from the shaft.
Clean all the grease using suitable solvent. Then wash the bearing with diesel and dry air.
Remove the rotor from stator.
Inspect rotor thoroughly for the loose bars and cage/shorting rings.
Inspect the bearing seat. If it is worn out and loose metalize the bearing.
Check the rotor trueness. If the shaft is bent send it for reshafting.
Replace the studs and nuts of the grease cups if worn out.
Inspect the stator winding for loose coils, loose connections, heating effect, deterioration
of insulation etc.
Clean the stator winding with clean dry cloth and blower.
Heat the winding in heating chamber up to 100C for 8 hours.
Again clean the winding.
Heat the stator for 6 hours.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
28/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
28submitted by Anirban Das
Apply protective coat of varnish.
Heat the windings (80C) till the varnish is dried.
Clean the stator and make ready for the assembly.
Clean the rotor also and insert the rotor in position.
Put the bearings on the shaft.
Assemble the motor with end shields in position.
Put back the fan on shaft.
Put back coupling on the shaft.
Run the motor and monitor the performance for four hours.
TROUBLE SHOOTING:
SYMPTOM CAUSE CORRECTIVE
MAINTENANCE
Motor will not start Overload control trip
Power not connected to motor
Faulty (open) fuses
Low voltage
Wrong control connections
Loose terminal lead connections
Open circuit in stator or rotor
winding
Short circuit in stator winding
Wait for overload to cool. Try
starting again. If motor still
doesnt start, check all thecauses shown below.
Connect power to motor.
Test fuses and circuit breakers.
Check motor name plate values
with power supply. Check
voltage at motor terminals with
motor under load to be sure wire
size is adequate.
Check connection with control
wiring diagram.
Tight connections.
Check for open circuits.
Check for shorted coil.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
29/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
29submitted by Anirban Das
Motor noisy
Motor vibrates
At higher than normal
temperature or
smoking
Bearings stiff
Over load
Motor running in single phase
Electrical load unbalance
Vibration due to unbalance or
misalignment
Mechanical system resonance
Air gap is non uniform
Noisy ball bearings
Loose punching or loose rotor
on shaft
Objects caught between fan and
end shields
Motor loose on foundation
Coupling loose
Overload
Electrical load unbalance
Restricted ventilation
Incorrect voltage and frequency.
Stator winding shorted
Rotor winding with loose
Free bearings or replace.
Reduce the load.
Stop motor and then try to start
motor, it will not start in singlephase.
Check current balance.
Balance or align the machine.
Remove motor from load. If
motor is still noisy, rebalance
the rotor.
Centre the rotor and if necessary
replace the bearings.
Check the lubrication. Replace
bearings if noise is excessive.
Tighten all holding bolts.
Disassemble motor and clean it.
Tighten holding-down bolts.
Check coupling joint, check
alignment. Tighten coupling.
Measure the motor load with
ammeter and reduce the load.
Check for voltage un balance orsingle phasing.
Clean air passages and
windings.
Check motor name plate values
with power supply.
Use insulation testing
procedures.
Tighten if possible or replace
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
30/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
30submitted by Anirban Das
Bearings hot
Sleeve bearings
connections
Motor used for rapid reversing
service
Bent shaft
Insufficient oil
Foreign materials in oil or poor
grade of oil
Oil rings rotating slowly or not
rotating at all
Defective bearings or roughshaft
with another rotor.
Replace with motor designed for
reversing service.
Straighten the bent shaft atservice shop.
Add oil if oil is very low.
Drain, oil flush, and re lubricate
using industrial lubricant.
Oil too heavy, drain and replace.
Replace bearings. Resurface
shaft.
TABLE-06
8. MOV ACTUATORS
8.1 DESCRIPTION:
Electrically operated motor operated valves are widely used in power plant/process
units and play a critical role. A typical actuator consists of
3-phase induction motor
Control gear
Travel limit switches and torque switches
Local controls
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
31/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
31submitted by Anirban Das
Electronics circuit consists of power supply unit, remote operating unit, and logic cords.
Figure-12: Sectional View of Motor operated valve
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
32/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
32submitted by Anirban Das
Figure-13: Motor Operated Valve
8.2 MAINTENANCE:
Schedule:
Based on the plant run length and application, a routine maintenance program is to
be developed. The maintenance period will be 1 year.
Check for evidence of oil leakage and rectify
Check the condition of gear case oil and replace if necessary.
Check the security of actuator mounting bolts.
Check cable connections to the actuator.
Check motor winding insulation resistance and check winding resistance is balance.
Check engagement of the clutch.
Energize the actuator and check direction of rotation.
Check electrical operation to limits.
In intelligent units check the healthiness from the diagnostic codes as per the vendors
manual.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
33/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
33submitted by Anirban Das
TROUBLE SHOOTING:
TABLE-07
9. CATHODIC PROTECTION
9.1 INTRODUCTION:
Cathodic protection is an electrochemical method used to prevent or control
corrosion of buried or submerged metallic structures.
After a CP system is installed and adjusted to provide adequate protection, currents
and potentials should remain relatively stable; changes in currents or potentials indicate a
problem.
SYMPTOM CORRECTIVE MAINTENANCE
MOV not operating
MOV not operating
although 3 phase
supply is healthy
MOV not operatingfor intelligent type
MOV
Check healthiness of 3 phase supply.
Check mechanism for freeness.
Check control gear/contactor.
Check PCBs.
Check control circuit.
Check limit switch.
Check internal battery.
Check PCBs.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
34/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
34submitted by Anirban Das
9.2 CATHODIC PROTECTION METHODS:
Sacrificial (Galvanic) Cathodic protection.
Impressed current Cathodic protection.
Out of these two methods impressed current protection is the most economical one
for the long pipelines. The disadvantages of the Galvanic protection is small driving voltage is
available, and small current available in higher resistivity electrolytes. Here we discuss briefly
about impressed current CP protection.
In an impressed current system, the protective current is supplied by a rectifier (or
other DC power source) to the structure.
Figure-14: Impressed Current Cathodic Protection System
Impressed current Cathodic protection systems use alternating current or solar
powered rectifiers as a power source.
Rectifiers used for Cathodic protection commonly use an
Adjustable step down transformer,
Rectifier stacks,
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
35/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
35submitted by Anirban Das
A shunt to measure output current,
Meters to indicate output current and voltage.
The function of the rectifier is to convert alternating current into controlled direct current.
Figure-15: Impressed current Cathodic protection system Rectifier
9.3 RECTIFIERS USED IN CATHODIC PROTECTION:
Silicon diodes
Thyristors
Switch mode
9.4 ANODE MATERIAL:
The anodes of an impressed current system provide the means for the protective
current to enter the electrolyte. Since the anodes form the corroding part of the system, the best
material is one that has a low rate of weight loss per ampere-year. The most commonly used
materials for impressed current anodes are graphite and high-silicon cast iron.
9.5 MAINTENANCE:
9.5.1 RECTIFIER OPERATIONAL INSPECTION:
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
36/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
36submitted by Anirban Das
The purpose of the rectifier operational inspection is to determine the serviceability
of all components required to impress current to the anodes of the impressed current system.
Maintenance Schedule:
Thirty days after cathodic protection system is installed and properly adjusted.
One to two years after that.
Procedure:
Visually check all rectifier components, shunt box components, safety switches.
Tighten all accessible connections and check temperature of all the components.
For rectifiers with more than one circuit, measure the output voltage and current for each
circuit using a dependable hand-held meter, and calibrate the rectifier meters, if present.
Calculate the cathodic protection system circuit resistance of each circuit by dividing the
rectifier DC voltage output of each circuit by the rectifier DC ampere output for that
circuit.
9.5.2 IMPRESSED CURRENT CHECK:
Maintenance schedule:
Sixty days after rectifier inspection, more frequent checks may be required by local
conditions.
Procedure:
Measure output D.C voltage and current from the rectifier.
Ensure the DC ampere output of the rectifier meets the current (ampere) requirement of
the system.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
37/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
37submitted by Anirban Das
Calculate the cathodic protection system circuit resistance of each circuit by dividing the
rectifier DC voltage output of each circuit by the rectifier DC ampere output for that
circuit.
Calculate the D.C out put voltage of the rectifier and check that it is rated or not.
TROUBLE SHOOTING:
Figure-16: Wiring diagram of a Rectifier
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
38/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
38submitted by Anirban Das
.
TABLE-08
10. EMERGENCY GENERATOR
10.1 INTRODUCTION:
Generator is the alternate energy source for emergency power needs in the pumping
station. There are many names for generator such as A.C generator and alternator. Alternator is
the commonly used name.
A typical pump station consists of diesel engine driven alternator to cater to
emergency power requirements like,
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
39/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
39submitted by Anirban Das
Radiator motors of mainline engines
Air compressors
Centrifuges
UPS system
Lighting in the pump shed and control room etc.
10.2 GENERATOR CONSTRUCTION:
The stationary field
The rotating dc magnetic field.
The armature, normally containing a three-phase winding, is mounted on the shaft.
The armature winding is fed through three slip rings (collectors) and a set of brushes
sliding on them.
The rectifier-bridge is fed from a shaft-mounted alternator, which is itself excited by
the pilot exciter.
The core is slotted (normally open slots), and the coils making the winding are placed
in the slots.
.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
40/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
40submitted by Anirban Das
Figure-17: The figure shows Silent type Generator
10.3 MACHINE RATINGS:
A generator is usually described by giving it a rating. This rating is given at the generators
capability point of maximum continuous power output. The terms generally used to provide
the rating are as follows:
Apparent power MVA Mega volt amperes
Real power MW Mega watts
Reactive power MVARs Mega volt amps reactance
Power factor pf A dimensionless quantity
Stator terminal- Voltage Vt Alternating voltage
Stator current Ia Alternating current amperes
Field voltage Vf Direct voltage
Field current If Direct current amperes
Frequency Hz Hertz
Speed rpm Revolutions per minute
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
41/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
41submitted by Anirban Das
Figure-21: Name plate details of A Generator
10.4 GENERATOR MAINTENANCE:
10.4.1 Weekly Maintenance: Before starting engine
Check oil level (add oil as needed).
Check coolant level.
Walk around inspection.
Check air cleaner indication (change filter as needed).
Fuel system- check for leaks.
Inspect belts, adjust or repair as needed.
Check generator for moisture, dust, &debris and clean it.
10.4.2 Weekly Maintenance: With engine running
Check for proper oil pressure.
Check for proper jacket water temperature.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
42/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
42submitted by Anirban Das
Check for proper fuel pressure.
Check frequency and voltage.
Record engine run hours.
10.4.3 Weekly Maintenance: After stopping engine
Automatic switches- check switches in proper position for automatic start.
Check fuel level; refill the tank if below 3/4 full.
10.4.4 Yearly Maintenance: Before starting the engine
Perform all weekly before starting engine maintenance first.
Add coolant conditioner as needed.
Drain water and sediment from fuel tank.
Change fuel filter.
Inspect and clean or replace air filter element if needed.
Check and adjust all linkages.
Test all engine protective devices.
Check generator winding with mega ohm meter.
Check generator bearing. Lubricate as required.
10.4.5 Yearly Maintenance: With engine running
Perform all weeklywith running engine maintenance first.
Inspect engine mounts. Check for proper torque.
Load test to minimum 30% its rated load for minimum 2 hours. Record all the gauge
readings.
Jacket water temperature will be higher compared to weekly no-load tests.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
43/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
43submitted by Anirban Das
10.4.6 Yearly Maintenance: After stopping engine
Perform all weekly after stopping engine maintenance first.
Obtain oil sample for analysis of chemical and physical test.
Change engine oil.
Replace oil filter. Cut filter and inspect for foreign material.
10.4.7 Three years maintenance: Before starting engine
Perform all weekly & yearly before starting engine first.
Cooling system
Drain, clean and flush.
Replace thermostats.
Refill with coolant solution and conditioner.
Inspect radiator cap and replace if needed.
Replace all hoses and belts.
Inspect turbo charger for proper operation.
Perform engine adjustment & tune up.
10.4.8 Three years maintenance: With engine running
Perform all weekly & yearly before starting engine first.
Check engine mounts. Check for proper torque.
Check exhaust system for leaks. Repair as needed.
10.4.9 Three years maintenance: After stopping engine
Perform all weekly & yearly after stopping engine first.
Obtain oil samples for analysis.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
44/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
44submitted by Anirban Das
10.4.10 Grounding Cables:
Schedule: Monthly:
All generator frames and casings are grounded to the power plant grounding system.
This is usually done at one location only to allow control over the ground current flow, and to
ensure that there are no circulating currents in the generator frame structure that will cause arcing
between components inside the machine.
Figure-19: Grounding of a Generator
The ground cables should be inspected to ensure they are tight and in generally good condition.
Signs of damage would be corrosion, overheating, fraying, or cracking.
11. SAFETY WHILE DOING ELECTRICAL MAINTENANCE
While doing maintenance works every one should follow the safety procedures.
A routine task can easily become a hazard if the required procedure is not followed or if
attention to detail is not applied.
Do not assume that the hazards in your work area are always at your eye/foot level. Be
aware of ALL your surroundings.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
45/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
45submitted by Anirban Das
A complete review of all systems should be conducted prior to any maintenance work.
All electrical equipment connected to line voltage must be bonded to ground
Necessary electrical repairs should be made by a qualified electrician.
ALWAYS de-energize electrical power source before making any adjustments
Discharge capacitors (if present) to prevent electrical shock.
Beware of moving parts.
Remove and replace any safety guards.
Figure-20: Protective Equipment
Wear Common Protective or Safety Equipment such as Safety Shoes, Glasses, Gloves,
Hearing Protection, Hard Hats, or Life Jackets.
When working on cables that are close to energized cables, particularly if they are
running in parallel, precautions shall be taken to minimize the risk of injury to personnel.
Similar precautions are required when working within 100 meters of a Zone.
Jointing of high voltage cables shall only be carried out by personnel trained and
accredited for a particular joint type.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
46/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
46submitted by Anirban Das
Jointing of high voltage cables is not permitted if it is raining.
Make sure that system is properly earthed.
Tag out the devices.
ANNEXURE-A:
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
47/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
47submitted by Anirban Das
CONSTRUCTION:
Cables consist of three major components: conductors, insulation, and protective jacket. The
makeup of individual cables varies according to application. The construction and material
are determined by three main factors:
Working voltage, determining the thickness of the insulation
Current-carrying capacity, determining the cross-sectional size
Environmental conditions such as temperature, water, chemical or sunlight exposure,
and mechanical impact, determining the form and composition of the outer cable
jacket.
Fig:Cut way view of the cable
TYPES OF CABLES USED FOR DISTRIBUTION NETWORK
MAJOR TYPES MAJOR SIZES
(Sq mm)
33kv underground
22kv underground
11kv underground
LT cables underground
XLPE
PILC
PILC
XLPE
400,300
300
240,120,70
240,120,50
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
48/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
48submitted by Anirban Das
XLPE- CROSS LINKED POLY ETHYLENE CONDUCTOR
PILC- PAPRE INSULATED LEAD SHEATHED CONDUCTOR
HT CABLES:
FIG: CROSS SECTIONAL DRAWING FOR 33KV 3CX400 sq.mm-A2XWY CABLE
HT cable components:
Conductors:
H4 grade Aluminum conductor of electrolytic grade stranded of circular cross section
complying with IS-8130/1984.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
49/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
49submitted by Anirban Das
Size
mm2
Min. Number of
strands/wires per conductor
Min. Diameter of each strand/
Wire (mm)
1000
400
300
150
89
59
36
36
3.93
3.04
3.4
2.4
Conductor Screening:
Either non-metallic semi-conducting tape or a layer of extruded semi-conducting compound
or a combination of two.
Insulation:
XLPE extruded insulation
Insulation Screening:
Extruded Semi-conducting screening with water swellable tapes and metallic screening.
Inner Sheath:
Pressure extruded inner sheathing of Black PVC.
Armour:
The Armour shall be of galvanized steel round wires with fault level of 1500 MVA at 33kV
& 500 MVA at 11 kV. Duration of fault level is one (1) second.
Outer Sheath:
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
50/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
50submitted by Anirban Das
An extruded outer sheathing of Blue PVC.
LT CABLES:
LT cables Standardized Ratings are:
2 core 25 sq. mm
4 core 25 sq. mm
4 core 50 sq. mm
3.5 core 120 /240 sq. mm
3.5 core 150 / 300 sq. mm
SECTOR SHAPED
CROSS SECTIONAL DRAWING FOR3.5 C X 240 sqmm (A2 X FY) L.T. CABLE
ALLUMINUM CONDUCTOR
XLPE INSULATION EXTRUDED PVCOUTER SHEATH
INNER SHEATHEXTRUDED PVC
FLAT G.S.STRIP
D:\\ OLDHDD\MISC\cross sectional view of 3.5 c x 240 sqmm cable
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
51/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
51submitted by Anirban Das
Insulation:
XLPE extruded insulation
Inner Sheath:
An extruded inner sheathing of Black PVC conforming to the requirement of type
ST-2.
Armour:
The dimension of galvanized steel Strips shall be as specified and shall conform to IS:
7098/Pt-1
Outer Sheath:
An extruded outer sheathing of Yellow PVC.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
52/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
52submitted by Anirban Das
ANNEXURE-B:
Cable Selection Criterion:
Cable Types- XLPE, PILC & PVC.
XLPE cables are most popular because of its better electrical and thermal properties like
higher continuous operating temperature, Short Circuit temperature, Break Down strength
etc.
Main Consideration:
For 11 kV,22 kV and 33 kV cables, the cable size is determined by continuous current
rating and short circuit rating.
For 1.1 kV cable, the selection of size is determined by continuous current rating, the
maximum permissible voltage drop and short circuit rating.
In addition to above, following are some factors for deciding the type and size of
cable.
1. Earth fault current carrying capacity.
2. Voltage drop (For low voltage system)
3. Power loss
ANNEXURE- C:
METHODS OF CABLE LAYING:
Laying direct in ground
Drawing in Ducts
Horizontal drilling
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
53/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
53submitted by Anirban Das
The cables are laid directly in the ground with a depth of 1 meter. Cables are also pulled in
ducts. The pulling tension is important and depends on the method of pulling.
Maximum allowable pulling tension:
The maximum allowable tension on cable conductors that should be used during
pulls must be based on experience as well as good engineering. Factors that have an impact
on the value include type of metal, temper, and factors of safety.
METAL TEMPER POUNDS PER
CIRCULAR MILL
Copper
Aluminum
Aluminum
Aluminum
Aluminum
Soft
Hard
Hard
Hard
Soft
0.008
0.008
0.006-0.008
0.003-0.004
0.002-0.004
Ref: AEIC CG5-(2nd Edition)-2005
Pulling tension calculation:
The basic equation to calculate the pulling tension is
T= W*L*f
Where T= tension in pounds
W= weight of one foot of cable in pounds
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
54/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
54submitted by Anirban Das
L= length of pull in feet
f = co-efficient of friction for the duct material and outer layer of the cable.
Horizontal drilling is employed where excavation of roads for cable laying is not possible. In
this method the road is drilled horizontally and cables are laid through Hume pipes which are
inserted into the drilled holes.
CABLE INSTALLATION PLAN:
On completion of laying, termination and jointing of cables, a computerized
drawing is prepared, which contains the following details of the installation.
Type of cables, cross-section area, rated voltage, details of construction, cable number and
drum number;
a. Year and month of laying;
b. Actual length between joint-to-joint or ends;
c. Location of cables and joints in relation to certain fixed reference points, for e.g.-
Buildings, hydrant etc;
d. Name of the jointer who carried the jointing work;
e. Date of making joint and Result of original electrical measurements and testing on
cable installation;
All subsequent changes in the cable drawings are entered after the job. All drawings are
maintained in digital format.
CABLE MARKING AND LOCATION:
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
55/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
55submitted by Anirban Das
Cables shall be marked with one tag indicating direction or exit from underground
facilities
This tag shall indicate the general direction of the cable(s) to the next facility where
the cable is located.
All tags will be labeled with the next point of connection (i.e. transformer 1 to
transformer
A redplastic warning tape shall be spread above the underground electrical cable
within the right-of-way at a depth of 0.6 m from the ground surface.
ANNEXURE-D:
TESTING OF CABLES:
The testing methods are
Direct voltage testing
Low voltage D.C testing
High voltage D.C testing
Power frequency testing
Low voltage testing:
This test is used to determine the insulation resistance of the cable. In this test Cable phases
not under test should have their conductors grounded. Ends, both at test location and remote,
should be protected from accidental contact by personnel, energized equipment and grounds.
Apply the prescribed test voltage for specified period of time. It may be advantageous to
conduct the test with morethan one voltage level and record readings of more than one time
period.
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
56/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
56submitted by Anirban Das
High voltage testing:
This test is used to determine the leakage current in the cable. Apply the prescribed test
voltage for the specifiedperiod of time.Totalapparent leakage output current is recorded asa
functionof time at a prescribed voltage level.
Power frequency testing:
As the name implies, these test methods are based on using alternating current at the
operating frequency of the system as the test source. This test is used to determine the Partial
Discharge.Partial discharge measurement is an important method of assessing the quality of
the insulation of power cable systems, particularly for extruded insulation materials.
PD testing is an evolving technology for periodic diagnostic testing of XLPE-
insulated cables. Partial discharges occur at voids in insulation and at the interface layers
between cable and accessory insulation. These discharges emit broadband radiation in the
range of 50 kHz to 500 MHzs PD testing is a nondestructive testing method, generally
accepted as one of the most effective techniques for locating defects in XLPE cables.
ANNEXURE-E:
Insulation Resistance Test Values Electrical Apparatus and Systems
Nominal Rating
of Equipment in Volts Minimum Test Voltage, DC
Recommended Minimum
Insulation Resistance in
Megohms
250 500 25
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
57/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
57submitted by Anirban Das
600 1,000 100
1,000 1,000 100
2,500 1,000 500
5,000 2,500 1,000
8,000 2,500 2,00015,000 2,500 5,000
25,000 5,000 20,000
34,500 and above 15,000 100,000
REF: INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
ANNEXURE-F: ELECTRICAL TOOL KIT FOR MAINTENANCE WORKS
S.No Tool name
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
58/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
58submitted by Anirban Das
1
2
3
4
5
67
8
9
10
11
12
13
14
15
16
1718
19
20
21
22
23
24
25
26
27
28
D-24 Reversible Screwdriver, 3/set
D-74-L Screwdriver w/Checker
D-81 Reversible Stubby Screwdriver
D-331-150 Screwdriver
D-332-150 Phillips Screwdriver
N-9-150 Diagonal Cutting PliersN-838 Snips
P-15-150 Long Nose Pliers w/Cutter
P-56-175 Pliers w/Side Cutter
P-86-125 Tweezers
P-211Z-150 Slip Joint Pliers
P-245 Slip Joint Pliers
P-704 Crimping Tool, w/Stripper
P-95 Wire Stripper
W-210-200 Adjustable Wrench
W-210-300 Adjustable Wrench
W-521 Open End Wrench SetZ-341 Measure Tape
Hammer
Quick-point Knife (Large)
Sealing Tape
Vinyl Tape
Plastic mallet
Penlight (with Batteries)
Brush
Hex Wrench Set
Multi meter
B-56-B Tool Box
-
8/10/2019 Elecrical Equipment Maintenance in Pipelines
59/59
ELECTRICAL EQUIPMENT MAINTENANCE IN PIPELINES
List of Standards:
IEEE Standard 43-2000 is the .Recommended Practice for Testing Insulation
Resistance of Rotating Machinery.
IEEE Standard 389-1996 is the IEEE Recommended Practice for Testing Electronics
Transformers and Inductors.
IEEE Standard 1415-2006 IEEE Guide for Induction Machinery Maintenance Testing
and Failure Analysis.
NACE SP0169:2007 - Control of External Corrosion on Underground or
Submerged Metallic Piping Systems.
NACE TM 0497 - Measurement Techniques Related to Criteria for Cathodic
Protection on Underground or Submerged Metallic Piping Systems.
NEMA (National Electrical Manufacturing Association) TR1-1993(R2000)
Transformers.
IS: 2705 for current transformer compilation.
IS: 3156 for voltage transformer compilation.
AEIC (Association of Edison illuminating Companies) G7-90 testing practices of
underground cables.
IEEE P-400 Guide for Field Testing and Evaluation of Shielded Power Cables