    FKS-EU with fusible linkfor 72 °C or 95 °C

    CE compliant accordingto European regulations

    With TROXNETCOM asan option

    Tested to VDI 6022

    12/2015

         H     Y   G     I   E

      N  I S CH G E  T   E   

    S   T     E     T      

    V   D I 

     6 0  2  2

     – DE/en

    Fire dampersType FKS-EU

    1

    Small rectangular fire damper for the isolation of duct penetrations between fire

    compartments, available in many sizes ■ Nominal sizes 200 × 100 to 800 × 200 mm

     ■ Low differential pressure and sound power level

     ■ Optional stainless steel casing or powder-coated casing for increasedcorrosion protection

     ■ Can also be used as an air transfer damper or air transfer unit

     ■ Integration into the central BMS with TROXNETCOM

     ■ Universal installation options

    Optional equipment and accessories ■ Electric actuator 24 V/230 V

     ■ Release temperature 72/95 °C

     ■ Duct smoke detectors

    FKS-EU 1.1–

    X XFKS-EUtestregistrierung

    K4 – 1.1 – 1

    Compact dimensions, ideal for restricted spaces

  • 8/19/2019 Fks-eu de de en Web

    2/34

    Fire dampers

    General information

    12/2015

    FKS-EU

     – en

    Type

    FKS-EU General information 1.1 – 2Correct use 1.1 – 9Order code 1.1 – 12Installation block E 1.1 – 14

    Cover plate B 1.1 – 16Cover grille 1.1 – 17Flexible connector 1.1 – 18Extension piece 1.1 – 19Limit switch 1.1 – 20Spring return actuator 1.1 – 21Spring return actuator and duct smoke detector 1.1 – 22TROXNETCOM 1.1 – 23Duct smoke detectors 1.1 – 24Quick sizing 1.1 – 25Free area and resistance coefficient 1.1 – 27Dimensions and weight – FKS-EU 1.1 – 28

    Dimensions and weight – FKS-EU/.../Z4* 1.1 – 29Dimensions and weight – FKS-EU/.../Z**RM 1.1 – 30Specification text 1.1 – 31

    Basic information and nomenclature 1.3 – 1

    Page

    K4 – 1.1 – 2

    Variants

    Product examples

    FKS-EU with fusible link FKS-EU with spring return actuator

    FKS-EU with fusible link and cover grille usedas an air transfer unit

    FKS-EU as air transfer damper

  • 8/19/2019 Fks-eu de de en Web

    3/34

    Fire dampers

    General information

    12/2015 – en

    FKS-EU

    1Application– Fire dampers of Type FKS-EU, with CE marking

    and declaration of performance, for theisolation of duct penetrations between firecompartments in the event of a fire

    – To prevent the propagation of fire and smoke

    through ductwork to adjacent designated firecompartments

    Classification– Class of performance to EN 13501-3, up to

    EI 120 (ve, ho, i ↔ o) S

    Variants– With fusible link– With spring return actuator– With cover grilles both ends as air transfer unit

    with general building inspectorate licence: Z-19.18-2127

    – With spring return actuator and duct smoke

    detector– With spring return actuator, duct smokedetector and cover grilles on both ends for useas an air transfer opening, with general buildinginspectorate licence Z-6.50-2231

    Nominal sizes– B × H: 200 × 100 – 800 × 200 mm (width in

    increments of 50 mm)– L: 300 mm

    Attachments– Limit switch for damper blade position

    indication– Spring return actuator for 24 V AC/DC or

    230 V AC supply voltage– Network module for the integration with AS-i or

    LON networks– Spring return actuator and pre-wired duct

    smoke detector, 24 V or 230 V supply voltage

    Accessories– Cover plate (to keep the fire damper stable and

    hence facilitate mortaring)– Cover grille– Flexible connectors– Extension piece– Rectangular installation block E

    Useful additions– Duct smoke detector RM-O-3-D– Duct smoke detector with airflow monitor RM-

    O-VS-D

    Special characteristics– Declaration of performance according to

    Construction Products Regulation– Classification to EN 13501-3, up to EI 120 (ve,

    ho, i ↔ o) S– Building inspectorate licence Z-56.4212-991

    for fire resistance properties– Complies with the requirements of EN 15650– Tested to EN 1366-2 for fire resistance

    properties– Hygiene complies with VDI 6022 part 1 (07/

    2011), VDI 3803 (10/2002), DIN 1946 part 4(12/2008), and EN 13779 (09/2007)

    – Corrosion protection according to EN 15650 inconnection with EN 60068-2-52

    – Closed blade air leakage to EN 1751, class 2– Casing air leakage to EN 1751, class C– Low differential pressure and sound power

    level

    – Any airflow direction– Integration into the central BMS with

    TROXNETCOM

    Parts and characteristics– Easy dry mortarless installation into solid walls

    and ceiling slabs, lightweight partition walls, firewalls and shaft walls using an installation block

    – Release temperature 72 °C or 95 °C (for use inwarm air ventilation systems)

    Construction features– Rectangular or square construction, rigid

    casing, both flanges with fixing holes

    (System 30)– Suitable for the connection of ducts, flexibleconnectors or a cover grille

    – The release mechanism is accessible and canbe tested from the outside

    – Two inspection access panels– Intermediate dimensions in 50 mm increments

    for width– Remote control with spring return actuator

    Materials and surfacesCasing:– Galvanised sheet steel– Galvanised sheet steel, powder-coated

    RAL 7001– Stainless steel 1.4301

    Damper blade:– Special insulation material– Special insulation material with coating

    Other components:– Damper blade shaft in stainless steel– Plastic bearings– Seals of elastomer

    The construction variants with stainless steel orpowder-coated casing meet even more critical

    requirements for corrosion protection. Detailedlisting on request.

    Installation and commissioningInstallion is to be carried out according to theoperating and installation manual

    Mortar-based installation:– In solid walls and ceiling slabs– In lightweight partition walls and fire walls with

    metal support structure and cladding on bothsides

    – In shaft walls with metal support structure andcladding on one side

    Dry mortarless installation:– In solid walls and ceiling slabs with installation

    block E

    K4 – 1.1 – 3

    Description

    FKS-EU with spring returnactuator

    For detailed informationon attachments seeChapter K4 – 1.2.

  • 8/19/2019 Fks-eu de de en Web

    4/34

    Fire dampers

    General information

    12/2015

    FKS-EU

     – en

    – In lightweight partition walls with metal supportstructure and cladding on both sides: withinstallation block E

    – In shaft walls with metal support structure andcladding on one side with installation block E

    Standards and guidelines– Construction Products Regulation– EN 15650:2010 Ventilation for buildings – Fire

    dampers– EN 1366-2:1999 Fire resistance tests for

    service installations – Fire dampers– EN 13501-3:2010 Fire classification of

    construction products and building elements– EN 1751:1999 Ventilation for buildings – Air

    terminal devices

    Maintenance

    – The functional reliability of the fire damper mustbe tested at least every six months; this has tobe arranged by the owner of the ventilationsystem; functional tests must be carried out incompliance with the basic maintenanceprinciples stated in EN 13306 and DIN 31051.

    If two consecutive tests, one 6 months after theother, are successful, the next test can beconducted one year later.

    – A functional test involves closing the damperblade and opening it again; with a spring returnactuator this can be done via remote control

    – Fire dampers must be included in the regularcleaning schedule of the ventilation system.

    – For details on maintenance and inspection,refer to the installation and operating manual

    ††

    K4 – 1.1 – 4

    Technical data Nominal sizes 200 × 100 to 800 × 200 mm

    Casing length 300 mm

    Volume flow rate range Up to 1600 l/s or up to 5760 m³/h

    Differential pressure range Up to 1500 Pa

    Operating temperature At least 0 – 50 °C **

    Release temperature   72 °C or 95 °C (for warm air ventilation systems)Upstream velocity*   ≤ 8 m/s with standard construction; ≤ 10 m/s with spring return actuator

  • 8/19/2019 Fks-eu de de en Web

    5/34

    Fire dampers

    General information

    12/2015 – en

    FKS-EU

    1Functional descriptionIn the event of a fire, fire dampers shutautomatically to prevent the propagation of fireand smoke through ductwork to adjacentdesignated fire compartments. In the event of afire, the damper is triggered at 72 °C or at 95 °C

    (use in warm air ventilation systems) by a fusiblelink. The release mechanism is accessible andcan be tested from the outside.††

    Function

    Construction with fusiblelink

    K4 – 1.1 – 5

    Schematic illustration of FKS-EU with fusible link

    ③②

    ②⑦

    ① Casing② Inspection access③ Fusible link④ Damper blade with seal

    ⑤ Travel stop⑥ Handle with interlock and damper blade positionindicator

    ⑦ Release mechanism

  • 8/19/2019 Fks-eu de de en Web

    6/34

    Fire dampers

    General information

    12/2015

    FKS-EU

     – en

    Functional descriptionThe spring return actuator enables the motorisedopening and closing of the damper blade; it canbe activated by the central BMS.In the event of a fire, the damper is triggeredthermoelectrically at 72 °C or 95 °C (use in warm

    air ventilation systems). As long as power issupplied to the actuator, the damper bladeremains open. If the supply voltage fails, thedamper closes (power off to close). Motorised firedampers can be used to shut off ducts. The torqueof each actuator is sufficient to open and close thedamper blade even while the fan is running.The spring return actuator is fitted with limitswitches that can be used for capturing thedamper blade position.††

    Function

    Construction with springreturn actuator

    K4 – 1.1 – 6

    Schematic illustration of FKS-EU with spring return actuator

    ②⑦

    ① Casing② Inspection access③ Temperature sensor④ Damper blade with seal

    ⑤ Travel stop⑥ Thermoelectric release mechanism⑦ Spring return actuator

  • 8/19/2019 Fks-eu de de en Web

    7/34

    Fire dampers

    General information

    12/2015 – en

    FKS-EU

    1Functional descriptionAir transfer units prevent fire and smoke fromspreading in buildings. The thermal releasemechanism closes the air transfer unit when therelease temperature (72 °C) is reached. Smokecan, however, spread below this temperature. Air

    transfer units are installed (mortar-basedinstallation) in places where the general buildinginspectorate sees no risk, for example:

    – As an inlet for additional supply air in the wallsof required corridors (escape routes) if the inletis near the ground (centre line up to 500 mmabove floor surface)

    – In installation shafts as long as they havesufficient fire resistance where they penetratecompartment floors

    – In installation ducts as long as they havesufficient fire resistance where they penetratecompartment floors or walls (except for

    necessary corridors or escape routes)

    The air transfer unit is an FKS-EU fire damper with72 °C thermal release mechanism (constructionwith fusible link) and cover grilles both ends.††

    Special characteristics– General building inspectorate licence Z-19.18-

    2127– Air transfer unit without duct smoke detector

    Note

    – Approved only for internal walls– Not to be connected to ducts in ventilation andair conditioning systems

    Function

    Use as an air transferdamper

    K4 – 1.1 – 7

    Schematic illustration of the FKS-EU as air transfer unit, with fusible link and cover grille

    ③② ④

    ⑦ ⑥ ② ⑤

    ① Casing② Inspection access③ Fusible link④ Damper blade with seal⑤ Travel stop

    ⑥ Handle with interlock and damper blade positionindicator

    ⑦ Release mechanism⑧ Cover grille⑨ Extension piece

  • 8/19/2019 Fks-eu de de en Web

    8/34

    Fire dampers

    General information

    12/2015

    FKS-EU

     – en

    Functional descriptionAir transfer dampers are designed to shut offopenings for air transfer in fire resistant internalwalls and ceiling slabs. To prevent smoke fromspreading in buildings, it is extremely importantthat the smoke is detected at an early stage. Duct

    smoke detector Type RM-O-3-D is required tocontrol and trigger the air transfer damper. Thesmoke detector operates on the principle of lightscattering and detects the smoke regardless of itstemperature so that the fire dampers can beclosed before the release temperature is reached.The thermoelectric release mechanism of thespring return actuator also triggers the closure ofthe damper blade. When the release temperature(72 °C) is reached, the temperature sensor in theairflow interrupts the supply voltage to the springreturn actuator. The spring return in the actuatorcauses the fire damper to close (power off toclose). A second temperature sensor monitors the

    ambient temperature. If the supply voltage fails,the damper closes. Air transfer dampers consist ofan FKS-EU fire damper, an RM-O-3-D duct smokedetector with general building inspectorate

    licence Z-78.6-125, a spring return actuator(24 V AC/DC or 230 V AC) with two integral limitswitches, and cover grilles on both ends.

    Special characteristics– Easy electrical connection

    – Integration into the central BMS withTROXNETCOM– General building inspectorate licence: Z-6.50-

    2231For further and up-to-date information, includingthe general building inspectorate licence and theoperating and installation manual, please refer toour website. For a more detailed selection anddesign of our fire dampers please refer to theEasy Product Finder design programme on ourwebsite.

    Note– Approved only for internal walls and ceilings

    – The B dimension of units installed in ceilingsmust not exceed 500 mm– Not to be connected to ducts in ventilation and

    air conditioning systems

    K4 – 1.1 – 8

    Function

    Air transfer damper

    Schematic illustration of FKS-EU as air transfer damper

    ① ③② ④

    ⑦ ⑥ ⑩

    ⑧⑤ ⑨

    ① Casing② Inspection access③ Temperature sensor④ Damper blade with seal⑤ Travel stop

    ⑥ Thermoelectric release mechanism⑦ Spring return actuator⑧ Cover grille⑨ Extension piece⑩ Duct smoke detector RM-O-3-D

  • 8/19/2019 Fks-eu de de en Web

    9/34

    Fire dampers

    Correct use

    12/2015 – en

    FKS-EU

    1Design information– Approved only for use in ventilation and air

    conditioning sytems– If the fire damper is installed in a solid wall,

    solid ceiling slab, lightweight partition wall orshaft wall with a lower fire resistance class than

    that of the fire damper, the fire resistance classof the wall or ceiling slab applies also to theFKS-EU (details upon request)

    – Ducting must be installed in such a mannerthat it does not impose any significant loads onthe fire damper in the event of a fire.

    – For particular applications it is recommendedthat flexible connectors are used to connectrigid ducting to the unit.

    – For further information relevant to design, inparticular information on installation situations,please refer to the operating and installationmanual.

    Incorrect useNever use the fire damper:

    – in areas with potentially explosive atmospheres– as a smoke control damper– outdoors without sufficient protection against

    the effects of weather– in atmospheres where chemical reactions,

    whether planned or unplanned, may causedamage to the fire damper or lead to corrosion

    If this fire damper is used in Germany:– Do not use it in extract air systems in

    commercial kitchens.

    K4 – 1.1 – 9

  • 8/19/2019 Fks-eu de de en Web

    10/34

    Fire dampers

    Correct use

    12/2015

    FKS-EU

     – enK4 – 1.1 – 10

  • 8/19/2019 Fks-eu de de en Web

    11/34

    Fire dampers

    Correct use

    12/2015 – en

    FKS-EU

    1

    K4 – 1.1 – 11

    Installation orientation Installation orientation with horizontal ducts

    ①②

    ① Release mechanism (mechanical or spring returnactuator)

    ② Duct smoke detector (optional, only together with aspring return actuator)

  • 8/19/2019 Fks-eu de de en Web

    12/34

    Fire dampers

    Order code

    12/2015

    FKS-EU

     – enK4 – 1.1 – 12

    FKS-EU

       

      FKS – EU – 1 / DE / 800×200×300 / E / A0 / Z43

    TypeFKS-EU Fire damper

    Construction  No entry: standard construction1  Powder-coated casing2  Stainless steel casing7  Coated damper blade1 – 7  Powder-coated casing and coated damper

    blade2 – 7  Stainless steel casing and coated damper

    blade

    W¹  With fusible link 95 °C (only for use inwarm air ventilation systems)

    Country of destinationDE  Germany  Other destination countries upon request

    Nominal size [mm]  B × H × L

    Accessories 1  No entry: noneE  Installation blockB  Cover plate

    Accessories 2  No entry: noneA0 – SS

    AttachmentsZ00 – ZA12 

    ¹ W can be combined with all constructions listedunder , but not with attachments Z43RM– Z45RM

    Order code

    Order example

    FKS-EU as an air transfer unit

      FKS – EU – 1 / DE / 800×200×300 / B / AA / Z01

    TypeFKS-EU Fire damper

    Construction  No entry: standard construction1  Powder-coated casing, RAL 70012  Stainless steel casing7  Coated damper blade1 – 7  Powder-coated casing, RAL 7001, and

    coated damper blade2 – 7  Stainless steel casing and coated damper

    blade

    Country of destinationDE  Germany  Other destination countries upon request

    Nominal size [mm]  B × H × L

    Accessories 1  No entry: noneB  Cover plate

    Accessories 2AA  Cover grilles on both ends

    AttachmentsZ00 – Z03

    Order code

    FKS-EU-1/DE/800×200×300/E/SS/Z43

    Construction variant Casing powder-coated, RAL 7001, silver grey

    Country of destination GermanyNominal size 800 × 200 × 300 mm

    Accessories 1 Installation block with cover plate

    Accessories 2 Flexible connector on operating and installation sides

    Attachment Spring return actuator 230 V AC

  • 8/19/2019 Fks-eu de de en Web

    13/34

    Fire dampers

    Order code

    12/2015 – en

    FKS-EU

    1

    K4 – 1.1 – 13

    Order example

    FKS-EU as air transfer damper

      FKS – EU – 1 / DE / 800×200×300 / E / AA / Z43RM

    TypeFKS-EU Air transfer damper

    Construction  No entry: standard construction1  Powder-coated casing, RAL 70012  Stainless steel casing7  Coated damper blade1 – 7  Powder-coated casing, RAL 7001, and

    coated damper blade2 – 7  Stainless steel casing and coated damper

    blade

    Country of destinationDE  Germany  Other destination countries upon request

    Nominal size [mm]  B × H × L

    Accessories 1  No entry: noneE  Installation blockB  Cover plate

    Accessories 2AA  Cover grilles on both ends

    AttachmentsZ43RM – Z45RM

    Order code

    Order example

    FKS-EU-1/DE/500×150×300/AA/Z03

    Construction variant Casing powder-coated, RAL 7001, silver grey

    Country of destination Germany

    Nominal size 500 × 150 × 300 mm

    Accessories 1 Without

    Accessories 2 Cover grilles on both ends

    AttachmentLimit switches for damper blade positions OPEN and

    CLOSED

    FKS-EU/DE/400×125×300/AA/Z43RM

    Construction variant Standard construction

    Country of destination Germany

    Nominal size 400 × 125 × 300 mm

    Accessories 1 Without

    Accessories 2 Cover grilles on both ends

    AttachmentSpring return actuator 230 V AC with factory mounted and

    pre-wired duct smoke detector (air transfer opening)

  • 8/19/2019 Fks-eu de de en Web

    14/34

    Accessories 1

    Installation block E

    12/2015

    FKS-EU

     – en

      / E  /

    Order code detail

    Application– Installation block E for dry mortarless

    installation into solid walls and ceiling slabs,into lightweight partition walls with metalsupport structure and cladding on one side oron both sides, and in lightweight fire walls

    – The installation block is factory mounted to thefire damper

    – The unit is installed without a mortar mix bysimply inserting it into the prepared installationopening

    – In the event of a fire the intumescent sealcloses the remaining gap.

    – A cover plate conceals any gaps and is usedfor screw fixing

    Materials and surfaces– The installation block is sheet steel with a

    special sealing compound– Cover plate and casing of the installation block

    made of galvanised sheet steel (and powder-coated silver grey, RAL 7001, when used with

    powder-coated (1) and stainless steel (2)dampers)

    NoteFor further information relevant to design, inparticular information on installation situations,please refer to the operating and installationmanual.

    Description

    K4 – 1.1 – 14

    Installation block Order code

    Installation block with cover plate E

    FKS-EU with fusible link, dimensions [mm] and weight [kg]

    HB

    200 300 400 500 600 700 800

    100 7.7 9.7 11.6 13.7 15.8 17.8 19.8

    125 8.5 10.5 12.4 14.4 16.4 18.5 20.6

    150 8.8 10.9 12.9 15.1 17.3 19.4 21.4

    160 8.9 11.0 13.1 15.4 17.7 19.7 21.7

    200 9.7 12.1 14.5 16.6 18.7 21.0 23.2

    FKS-EU with installation block E in a solid wall

    B + 150H + 100

    115

    B + 70H + 70

    ①   ② ③   ④

    ① Cover plate② Installation block

    ③ Seal④ Solid wall

  • 8/19/2019 Fks-eu de de en Web

    15/34

    Accessories 1

    Installation block E

    12/2015 – en

    FKS-EU

    1

    K4 – 1.1 – 15

    FKS-EU with installation block E in a lightweight partition wall

    B + 150H + 100

    115

    B + 70

    H + 70

    ①   ② ③   ④

    ① Cover plate② Installation block

    ③ Seal④ Lightweight partition wall

  • 8/19/2019 Fks-eu de de en Web

    16/34

    Accessories 1

    Cover plate B

    12/2015

    FKS-EU

     – en

      / B  /

    Order code detail

    Application– A cover plate facilitates mortar-based

    installation (perimeter mortar infill)

    It is supplied unassembled and allows forpositioning the fire damper in the installation

    opening and for applying the perimeter mortarinfill.

    Materials and surfaces– Cover plate made of galvanised sheet steel

    (and powder-coated silver grey, RAL 7001,when used with powder-coated (1) andstainless steel (2) dampers)

    Description

    K4 – 1.1 – 16

    Cover plate Order code

    Cover plate B

    FKS-EU with cover plate

    B + 80H + 80

    B + 150

    H + 100

    ① Cover plate ② Solid wall or lightweight partition wall

  • 8/19/2019 Fks-eu de de en Web

    17/34

    Accessories 2

    Cover grille

    12/2015 – en

    FKS-EU

    1

    Cover grille for FKS-EU

    Application– If only one end is to be ducted on site, the other

    end must have a cover grille– Fire dampers ordered with a cover grille may

    be supplied with an extension piece if required– The extension is factory mounted to the

    damper– The free area of the cover grille is approx. 65%– Cover grilles are also available separately– An extension piece is required on the

    installation side– Cover grilles both ends are available in

    Germany only for fire dampers with generalbuilding inspectorate licence Z-6.50-2231 or forair transfer units with general buildinginspectorate licence Z-19.18-2127

    Materials and surfaces– Cover grilles made of galvanised sheet steel

    (and powder-coated silver grey, RAL 7001,when used with powder-coated (1) andstainless steel (2) dampers)

    NoteFor further information relevant to design, inparticular information on installation situations,please refer to the operating and installationmanual.

    Description

    K4 – 1.1 – 17

      /   A0 /  

     /   0A /  

     / AA /  

    Order code detail

    The distance »a«between the open damperblade and the cover grilleshould be approx. 50 mm.

    Cover grille for FKS-EU

    Operating side Installation side Order code

    Cover grille – A0

    – Cover grille 0A*

    Cover grille Cover grille AA*

    Cover grille

    ① Cover grille, mesh aperture 10 mm × 10 mm, wirewidth 2 mm; grille thickness approx. 1 mm

    ② Extension piece required on the installation side

    Cover grille

       H     /

       B

    L = 300

    y = 1 ... 51*

       H     /

       B

    L = 300 200

    ① ②

    ③ ③

    ⑤ ④

    ① Without extension piece② With extension piece③ Cover grille, mesh aperture 10 mm × 10 mm, wire

    width 2 mm; grille thickness approx. 1 mm

    ④ Extension piece⑤ Damper bladey = * 51 with H = 200 mm

  • 8/19/2019 Fks-eu de de en Web

    18/34

    Accessories 2

    Flexible connector

    12/2015

    FKS-EU

     – en

    Flexible connector withflange for FKS-EU

    Application– For information on how to limit such loads

    please refer to the guideline regarding fireprotection requirements on ventilation systems(Lüftungsanlagen-Richtlinie, LüAR)

    – As ducts may expand and walls may become

    deformed in the event of a fire, we recommendusing flexible connectors for the followingapplications: installation in lightweight partitionwalls, in lightweight shaft walls and inlightweight fire walls

    – Flexible connectors should be installed in sucha way that both ends can compensate bothtension and compression

    – Flexible ducts can be used as an alternative– An extension piece is required on the

    installation side– Flexible connectors are supplied unassembled– The fixing holes in the flexible connectors and

    extension piece match those in the fire damper

    flanges– Flexible connectors are also available

    separately

    Materials and surfaces– Flexible connectors made of galvanised steel

    and fibre-reinforced plastic– Fire resistance properties to 4102; B2

    Note

    For further information relevant to design, inparticular information on installation situations,please refer to the operating and installationmanual.

    Description

    K4 – 1.1 – 18

      / S0  /

     / 0S  /

     / SS  /

    Order code detail

    The distance »a«between the open damperblade and the flexibleconnector should beapprox. 50 mm.

    Flexible connector for FKS-EU

    Operating side Installation side Order code

    Flexible connector – S0

    – Flexible connector 0S*

    Flexible connector Flexible connector SS*

    Flexible connector

    ①  ①

    ① Flexible connector ② Extension piece required on the installation side

    Flexible connector

       H     /

       B

    L = 300 200

    ~ 185

    ~ 160*

    ~ 185

    ~ 160*

    ③ ②

    ①①

    ① Flexible connector② Extension piece

    ③ Damper blade* flexible length ≥ 100 mm when installed

  • 8/19/2019 Fks-eu de de en Web

    19/34

    Accessories 2

    Extension piece

    12/2015 – en

    FKS-EU

    1

    FKS-EU extension piece

    Application– Fire dampers ordered with flexible connector or

    cover grille are supplied including extensionpiece

    – Extension pieces are also available separately

    Materials and surfaces– Extension piece made of galvanised sheetsteel (and powder-coated silver grey,RAL 7001, when used with powder-coated (1)and stainless steel (2) dampers)

    Installation and commissioning– The distance »a« between the open damper

    blade and the cover grille or circular spigotshould be approx. 50 mm

    Note

    For further information relevant to design, inparticular information on installation situations,please refer to the operating and installationmanual.

    Description

    K4 – 1.1 – 19

    When using cover grilles,circular spigots or flexibleconnectors an extensionpiece may be required forcertain heights.

    Extension piece

         ∅     1     0

    B + 60

       H

       H

        +

       6   0

    B

    B + 30

       H

        +

       3   0

    200

  • 8/19/2019 Fks-eu de de en Web

    20/34

    Attachments

    Limit switch

    12/2015

    FKS-EU

     – en

    Limit switch

    FKS-EU with limit switch– Limit switches with volt-free contacts enable

    the damper blade position indication.– Up to the maximum switch rating, relays or

    indicator lights for fire alarm systems can beused

    – One limit switch each is required for damperblade positions OPEN and CLOSED

    – Fire dampers with a fusible link can be suppliedwith one or two limit switches; the switches canalso be fitted later

    – For technical data and wiring examples refer tothe additional technical leaflet 'Attachments forfire dampers'

    Description

    For detailed informationon limit switches seeChapter 1.2

    K4 – 1.1 – 20

      / Z01 

     / Z02 

     / Z03 

    Order code detail

    Attachments Order code

    Limit switch for damper blade position CLOSED Z01

    Limit switch for damper blade position OPEN Z02

    Limit switches for damper blade positionsCLOSED and OPEN

    Z03

  • 8/19/2019 Fks-eu de de en Web

    21/34

    Attachments

    Spring return actuator

    12/2015 – en

    FKS-EU

    1

    FKS-EU with spring returnactuator

    FKS-EU with spring return actuator– An open/close actuator allows for the remote

    control of the fire damper and/or release by asuitable duct smoke detector

    – If the supply voltage fails, or with thermoelectricrelease, the damper closes (power off to close)

    – Fire dampers with spring return actuators canbe functionally checked OPEN/CLOSED/OPEN

    – Ambient temperature, normal operation–30 to 50 °C

    – Two integral limit switches with volt-freecontacts enable the damper blade positionindication (OPEN and CLOSED)

    – BLF24-T-ST TR: The connecting cables of thespring return actuator are fitted with plugs,which ensure quick and easy connection to theTROX AS-i bus system

    – A conversion kit is available for adding anactuator to the standard construction

    – In case of conventional wiring (Z45) the voltageis supplied by a safety transformer

    Description

    For detailed informationon the spring returnactuator see Chapter 1.2

    K4 – 1.1 – 21

      / Z43 

     / Z45 

    Order code detail

    Attachments Order code

    BLF230-T TR Z43

    BLF24-T-ST TR Z45

  • 8/19/2019 Fks-eu de de en Web

    22/34

    Attachments

    Spring return actuator and duct smoke detector

    12/2015

    FKS-EU

     – DE/en

    FKS-EU as air transferdamper

    FKS-EU with spring return actuator BLF andduct smoke detector RM-O-3-D– An open/close actuator allows for remote

    control of the fire damper and/or release by asuitable duct smoke detector

    – If the supply voltage fails, or with thermoelectric

    release or smoke detection the damper closes(power off to close)– Fire dampers with spring return actuators can

    be functionally checked OPEN/CLOSED/OPEN

    – Two integral limit switches with volt-freecontacts enable the damper blade positionindication (OPEN and CLOSED)

    – If the unit is not connected to ducting, covergrilles are required on both ends.

    – In combination with a spring return actuator, aduct smoke detector RM-O-3-D and covergrilles on both ends this is an air transferdamper with general building inspectorate

    licence: Z-6.50-2231

    To prevent smoke from spreading in buildings, it isextremely important that the smoke is detected atan early stage. A duct smoke detector RM-O-3-Dcan be used to activate FKS-EU fire dampers witha spring return actuator. The duct smoke detectoroperates on the principle of light scattering anddetects the smoke regardless of its temperatureso that the fire dampers can be closed before therelease temperature is reached.

    Duct smoke detector Type RM-O-3-DThe duct smoke detector RM-O-3-D is fitted in thelower inspection access opening of the FKS-EUand hence, just as the spring return actuator, anintegral part of the fire damper.

    Essential characteristics of the duct smokedetector:

    – General building inspectorate licence Z-78.6-125

    – For airflow velocities from 1 – 20 m/s– Independent of the airflow direction– Supply voltage 230 V AC, 50/60 Hz*– Volt-free signal and alarm relays– Integral signal lamps– Contamination level indicator– Automatic adjustment of alarm threshold– Long service life– Temperature range 0 – 60 °C

    * The 24 V DC construction includes a voltagemonitoring module

    Description

    For detailed informationon the spring returnactuator see Chapter 1.2

    For detailed informationon duct smoke detectorssee Chapter 3

    K4 – 1.1 – 22

      / Z43RM 

     / Z45RM 

    Order code detail

    Spring return actuator and pre-wired duct smoke detector, 24 V DC or 230 V supply voltage

    Attachments Order codeDuct smoke detector RM-O-3-D with spring returnactuator BLF230-T TR (cover grilles both endsrequired [AA] for air transfer dampers)

    Z43RM

    Duct smoke detector RM-O-3-D with spring returnactuator BLF24-T ST TR (cover grilles both endsrequired [AA] for air transfer dampers)

    Z45RM

  • 8/19/2019 Fks-eu de de en Web

    23/34

    Attachments

    TROXNETCOM

    12/2015 – en

    FKS-EU

    1FKS-EU with spring return actuator andTROXNETCOM– Fire dampers with spring return actuator

    BLF24-T-ST TR and the modules describedhere as attachments form a functional unitready for automatic operation.

    – The components are factory assembled andwired

    – It enables the integration of differentcomponents (modules) into a networkregardless of the manufacturer

    – The modules control actuators and/or receivesignals from sensors

    ApplicationLON:– LON indicates a standard local operating

    network system with manufacturer-independentcommunications

    – Data transmission is based on a uniform

    protocol– International standards ensure product

    compatibility– Only the bus line and the supply voltage remain

    to be connected by others– LON-WA1/B2: To provide the control input

    signal for up to two fire dampers– LON-WA1/B2-AD: Connection box for

    connecting the second fire damper with24 V DC supply voltage to LON-WA1/B2-AD

    – LON-WA17B2-AD230: Connection box withintegral 230/24 V power supply unit for the

    connection of a second actuator-driven 24 Vfire damper to LON-WA1/B2

    AS-i:– The AS interface is a global standard bus

    system according to EN 50295 and IEC 62026-2

    – The module transmits the control signalsbetween the spring return actuator and thecontroller and power unit

    – This allows for controlling the actuator andmonitoring the actuator running time duringfunctional testing

    – The voltage (24 V DC) for the module and the

    actuator is supplied via the two-wire AS-i flatcable

    – Function display: operation, 4 inputs, 2 outputs††

    K4 – 1.1 – 23

    Description

    FKS-EU withTROXNETCOM module

    For detailed informationon TROXNETCOM seeChapter 6

      / ZL06 

     / ZL07 

     / ZL08 

    Order code detail

      / ZA07 

     / ZA12 

    Order code detail

    Attachments Order code

    LON-WA1/B2 and BLF24-T-ST TR ZL06

    LON-WA1/B2-AD and BLF24-T-ST TR ZL07

    LON-WA1/B2-AD230 and BLF24-T-ST TR ZL08

    AS-EM and BLF24-T-ST TR ZA07

    AS-RM/BD-UE, BLF24-T-ST TR and RM-O-3-D ZA12

  • 8/19/2019 Fks-eu de de en Web

    24/34

    Attachments

    Duct smoke detectors

    12/2015

    FKS-EU

     – en

    Duct smoke detector RM-O-3-D

    Duct smoke detector RM-O-VS-D

    General– To prevent smoke from spreading in buildings,

    it is extremely important that the smoke isdetected at an early stage.

    – Duct smoke detectors that operate on theprinciple of light scattering detect the smoke

    regardless of its temperature so that the firedampers can be closed before the releasetemperature of 72 °C is reached

    – If the air contains suspended particles, as isthe case with smoke, beams of light aredeflected off these. A sensor (photodiode),which does not receive light in clear air, isilluminated by the scattered light.

    – The fire damper or smoke protection damperblade is released when the brightness of thescattered light exceeds a certain threshold

    NoteFor details please refer to the technical leaflets for

    RM-O-3-D and RM-O-VS-D.

    ApplicationRM-O-3-D:– Duct smoke detector for fire dampers and

    smoke protection dampers– General building inspectorate licence Z-78.6-

    125

    – For airflow velocities from 1 – 20 m/s– Independent of the airflow direction– Supply voltage 230 V AC, 50/60 Hz or 24 V DC

    with voltage monitoring module (VWM) (uponrequest)

    – Volt-free signal and alarm relays– Integral signal lamps– Contamination level indicator– Automatic adjustment of alarm threshold– Long service life– Temperature range 0 – 60 °C

    RM-O-VS-D:– Duct smoke detector for fire dampers and

    smoke protection dampers– General building inspectorate licence Z-78.6-

    67– For airflow velocities from 1 – 20 m/s– Independent of the airflow direction– Airflow monitoring with warning for lower limit

    2 m/s– Supply voltage 230 V AC, 50/60 Hz– Volt-free signal and alarm relays– Integral signal lamps– Contamination level indicator– Automatic adjustment of alarm threshold– Long service life– Temperature range 0 – 60 °C

    Description

    For detailed informationon duct smoke detectorssee Chapter 3

    K4 – 1.1 – 24

    Attachments Order code

    Duct smoke detector RM-O-3-D

    Duct smoke detector RM-O-VS-D

  • 8/19/2019 Fks-eu de de en Web

    25/34

    Fire dampers

    Quick sizing

    12/2015 – en

    FKS-EU

    1

    K4 – 1.1 – 25

    Sizing example Given data Quick sizing

    Volume flow rate: 1000 m³/h FKS-EU / 600 × 100 × 300

    Maximum height: 100 mm

    Sound power level: 35 dB(A)

    Volume flow rate [m³/h] at differential pressure Δpst < 35 Pa

    H [mm] LB [mm]

    200 300 400 500 600 700 800

    10035 300 480 660 840 1030 1230 1420

    45 420 670 920 1180 1450 1720 2000

    125 35 410 650 890 1150 1400 1700 194045 570 900 1250 1600 1960 2350 2700

    15035 520 830 1140 1470 1800 2140 2480

    45 730 1160 1600 2060 2520 3000 3480

    16035 570 900 1250 1600 1970 2340 2700

    45 790 1260 1750 2240 2750 3280 3800

    20035 760 1220 1690 2170 2660 3170 3680

    45 1060 1700 2360 3040 3750 4430 5150

  • 8/19/2019 Fks-eu de de en Web

    26/34

    Fire dampers

    Quick sizing

    12/2015

    FKS-EU

     – enK4 – 1.1 – 26

    Sizing example Given data Quick sizing

    Volume flow rate: 650 l/s FKS-EU / 700 × 125 × 300

    Maximum height: 125 mm

    Sound power level: 45 dB(A)

    Volume flow rate [l/s] at differential pressure Δpst < 35 Pa

    H [mm] LB [mm]

    200 300 400 500 600 700 800

    10035 83 133 183 233 286 342 394

    45 117 186 256 328 403 478 556

    125 35 114 181 247 319 389 472 53945 158 250 347 444 544 653 750

    15035 144 231 317 408 500 594 689

    45 203 322 444 572 700 833 967

    16035 158 250 347 444 547 650 750

    45 219 350 486 622 764 911 1056

    20035 211 339 469 603 739 881 1022

    45 294 472 656 844 1042 1231 1431

  • 8/19/2019 Fks-eu de de en Web

    27/34

    Fire dampers

    Free area and resistance coefficient

    12/2015 – en

    FKS-EU

    1

    K4 – 1.1 – 27

    H [mm] ParameterB [mm]

    100 125 150 160 200

    200A [m²] 0.01 0.02 0.02 0.02 0.03

    ζ 1.46 0.98 0.71 0.63 0.43

    300A [m²] 0.02 0.03 0.03 0.04 0.05

    ζ 1.26 0.84 0.60 0.54 0.36

    400A [m²] 0.03 0.04 0.05 0.05 0.07

    ζ 1.17 0.77 0.55 0.49 0.33

    500A [m²] 0.03 0.05 0.06 0.06 0.08

    ζ 1.11 0.73 0.52 0.46 0.31

    600A [m²] 0.04 0.05 0.07 0.08 0.10

    ζ 1.08 0.71 0.50 0.44 0.29

    700A [m²] 0.05 0.06 0.08 0.09 0.12

    ζ 1.05 0.69 0.49 0.43 0.28

    800A [m²] 0.05 0.07 0.09 0.10 0.13

    ζ 1.04 0.68 0.48 0.42 0.28

  • 8/19/2019 Fks-eu de de en Web

    28/34

    Fire dampers

    Dimensions and weight – FKS-EU

    12/2015

    FKS-EU

     – enK4 – 1.1 – 28

    Dimensions

    FKS-EU with fusible link

    Weight

    HB

    200 300 400 500 600 700 800

    100 3.3 4.1 4.9 5.7 6.5 7.4 8.2

    125 3.6 4.5 5.3 6.2 7 7.8 8.6

    150 3.7 4.7 5.6 6.6 7.5 8.4 9.2

    160 3.8 4.8 5.7 6.7 7.7 8.6 9.4

    200 4.1 5.3 6.5 7.5 8.4 9.4 10.3

    FKS-EU with fusible link

    ① Keep clear to provide access to the releasemechanism

    L = 300

    185 B

          H

          3      0

    3030

          3      0

    ~70

    ~175

  • 8/19/2019 Fks-eu de de en Web

    29/34

    Fire dampers

    Dimensions and weight – FKS-EU/.../Z4*

    12/2015 – en

    FKS-EU

    1

    K4 – 1.1 – 29

    Dimensions

    FKS-EU with spring returnactuator

    Weight

    HB

    200 300 400 500 600 700 800

    100 5.3 6.1 6.9 7.7 8.5 9.4 10.2

    125 5.6 6.5 7.3 8.2 9 9.8 10.6

    150 5.7 6.7 7.6 8.6 9.5 10.4 11.2

    160 5.8 6.8 7.7 8.7 9.7 10.6 11.4

    200 6.1 7.3 8.5 9.5 10.4 11.4 12.3

    FKS-EU with spring return actuator (FKS-EU/.../Z4*)

    L = 300

    185 B

          H

          3      0

    ~ 270

          3      0

    3030

    ~100

    ~175

    ① Keep clear to provide access to the spring return

    actuator

  • 8/19/2019 Fks-eu de de en Web

    30/34

    Fire dampers

    Dimensions and weight – FKS-EU/.../Z**RM

    12/2015

    FKS-EU

     – DE/enK4 – 1.1 – 30

    Dimensions

    FKS-EU as air transferdamper

    Weight

    HB

    200 300 400 500 600 700 800

    100 6.3 7.1 7.9 8.7 9.5 10.4 11.2

    125 6.6 7.5 8.3 9.2 10.0 10.8 11.6

    150 6.7 7.7 8.6 9.6 10.5 11.4 12.2

    160 6.8 7.8 8.7 9.7 10.7 11.6 12.4

    200 7.1 8.3 9.5 10.5 11.4 12.4 13.3

    FKS-EU as air transfer damper (FKS-EU/.../Z**RM)

    L = 300

    185 B

          H

          3      0

    ~ 270

          1      5      0

          3      0

    3030

    ~100

    ~175

    200

    ① Keep clear to provide access to the duct smoke

    detector and to the spring return actuator

    ② Extension piece

  • 8/19/2019 Fks-eu de de en Web

    31/34

    Fire dampers

    Specification text

    12/2015 – en

    FKS-EU

    1Rectangular or square fire dampers with flanges,for the isolation of duct penetrations between firecompartments.Tested for fire resistance properties to EN 1366-2,with CE marking and declaration of performanceaccording to the Construction Products

    Regulation.Ready-for-operation unit, which includes a fire-resistant damper blade and a release mechanism.For mortar-based installation and dry mortarlessinstallation into solid walls and ceiling slabs,lightweight partition walls and fire walls withcladding on both sides; also in shaft walls withmetal support structure and cladding on one side.Casing length 300 mm, for the connection to ductsmade of non-combustible or combustiblematerials. Thermal or thermoelectric release at72 °C or 95 °C (warm air ventilation systems).Constructions with spring return actuator foropening and closing the fire damper independent

    of the nominal size and even while the ventilationsystem is running, e.g. for a functional test.Construction with installation block for easy drymortarless installation.

    Special characteristics– Declaration of performance according to

    Construction Products Regulation– Classification to EN 13501-3, up to EI 120 (ve,

    ho, i ↔ o) S– Building inspectorate licence Z-56.4212-991

    for fire resistance properties– Complies with the requirements of EN 15650– Tested to EN 1366-2 for fire resistance

    properties– Hygiene complies with VDI 6022 part 1 (07/

    2011), VDI 3803 (10/2002), DIN 1946 part 4(12/2008), and EN 13779 (09/2007)

    – Corrosion protection according to EN 15650 inconnection with EN 60068-2-52

    – Closed blade air leakage to EN 1751, class 2– Casing air leakage to EN 1751, class C– Low differential pressure and sound power

    level– Any airflow direction– Integration into the central BMS with

    TROXNETCOM

    Materials and surfacesCasing:– Galvanised sheet steel– Galvanised sheet steel, powder-coated

    RAL 7001– Stainless steel 1.4301

    Damper blade:– Special insulation material– Special insulation material with coating

    Other components:– Damper blade shaft in stainless steel– Plastic bearings– Seals of elastomer

    The construction variants with stainless steel orpowder-coated casing meet even more criticalrequirements for corrosion protection. Detailedlisting on request.

    Technical data– Nominal sizes: 200 × 100 mm – 800 × 200 mm– Casing length: 300 mm– Volume flow rate range: Up to 1600 l/s or

    5760 m³/h– Differential pressure: up to 1500 Pa– Operating temperature: at least 0 – 50 °C **– Release temperature 72 °C or 95 °C (for use in

    warm air ventilation systems)– Upstream velocity: ≤ 8 m/s with standard

    construction; ≤ 10 m/s * with actuator

    * Data applies to uniform upstream and

    downstream conditions for the fire damper** Temperatures may differ for units withattachments; details for other applications areavailable on request.

    Sizing data–  ______________________________   [m³/h]– Δpst ______________________________ [Pa]– LWA Air-regenerated noise __________   [dB(A)]

    Description

    This specification textdescribes the generalproperties of the product.Texts for variants can be

    generated with our EasyProduct Finder designprogramme.

    K4 – 1.1 – 31

  • 8/19/2019 Fks-eu de de en Web

    32/34

    Fire dampers

    Specification text

    12/2015

    FKS-EU

     – en

      TypeFKS-EU Fire damper

    Construction  No entry: standard construction

    Country of destination

      Other destination countries uponrequest

    Nominal size [mm]

    1  Powder-coated casing2  Stainless steel casing7  Coated damper blade1 – 7  Powder-coated casing and coated

    damper blade2 – 7  Stainless steel casing and coated

    damper bladeW¹  With fusible link 95 °C (only for use in

    warm air ventilation systems)

    DE  Germany

      B × H × L

    Accessories 1  No entry: none

    Accessories 2  No entry: none

    Attachments

     ¹ W can be combined with all constructions listed

    under , but not with attachmentsZ43RM – Z45RM

    E  Installation blockB  Cover plate

    A0 – SS

    Z00 – ZA12

    K4 – 1.1 – 32

    Order options

  • 8/19/2019 Fks-eu de de en Web

    33/34

    Fire dampers

    Specification text

    12/2015 – DE/en

    FKS-EU as an air transfer unit

    1Square or rectangular fire dampers used as airtransfer units for the following applications:– As an inlet for additional supply air in the walls

    of required corridors (escape routes) if the inletis near the ground (centre line up to 500 mmabove floor surface)

    – In installation shafts as long as they havesufficient fire resistance where they penetratecompartment floors

    – In installation ducts as long as they havesufficient fire resistance where they penetratecompartment floors or walls (except fornecessary corridors or escape routes)

    Tested for fire resistance properties to EN 1366-2,with CE marking and general building inspectoratelicence. Ready-for-operation unit, which includesa fire-resistant damper blade and a releasemechanism. Casing length 300 mm, with covergrilles both ends and an extension piece on theinstallation side, for installation without duct

    connection. Thermal release at 72 °C. For mortar-based installation in internal solid walls, inlightweight partition walls with cladding on bothsides, and in fire walls and shaft walls.

    Special characteristics– General building inspectorate licence Z-19.18-

    2127– Air transfer unit without duct smoke detector

    Note

    – Approved only for internal walls– Not to be connected to ducts in ventilation andair conditioning systems

    Description

    This specification textdescribes the generalproperties of the product.Texts for variants can be

    generated with our EasyProduct Finder designprogramme.

    TypeFKS-EU Fire damper

    Construction  No entry: standard construction

    Country of destination

      Other destination countries uponrequest

    Nominal size [mm]

    1  Powder-coated casing, RAL 7001

    2  Stainless steel casing

    7  Coated damper blade1 – 7  Powder-coated casing, RAL 7001, and

    coated damper blade

    2 – 7  Stainless steel casing and coateddamper blade

    DE  Germany

      B × H × L

    Accessories 1  No entry: none

    Accessories 2

    Attachments

    B  Cover plate

    AA  Cover grilles on both ends

    Z00 – Z03

    K4 – 1.1 – 33

    Order options

  • 8/19/2019 Fks-eu de de en Web

    34/34

    Fire dampers

    Specification text FKS-EU as air transfer damper

    Square or rectangular air transfer dampers forshutting off air transfer openings in fire-resistantwalls or ceilings, to prevent the penetration ofheat, flames and smoke for at least 90 minutes.Ready-for-operation unit, which includes a fire-resistant damper blade, a duct smoke detector, a

    spring return actuator with two integral limitswitches, cover grilles on both ends and anextension piece on the installation side.Tested for fire resistance properties according toEN 1366-2, with general building inspectoratelicence Z-6.50-2231 from the DIBt, Berlin.For installation into solid walls and ceiling slabs,lightweight partition walls and fire walls withcladding on both sides; also in shaft walls withmetal support structure and cladding on one side.Casing length: 500 mm.Thermoelectric release at 72 °C.

    Sizing data

    –  ______________________________   [m³/h]– Δpst ______________________________ [Pa]– LWA Air-regenerated noise __________   [dB(A)]

    Special characteristics– Declaration of performance according to

    Construction Products Regulation– General building inspectorate licence Z-6.50-

    2231 from the DIBt– Tested to EN 1366-2 and DIN 4102 for fire

    resistance properties– Hygiene complies with VDI 6022 part 1 (07/

    2011), VDI 3803 (10/2002), DIN 1946 part 4(12/2008), and EN 13779 (09/2007)

    – Corrosion protection according to EN 15650 inconnection with EN 60068-2-52

    – Closed blade air leakage to EN 1751, class 2– Casing air leakage to EN 1751, class C– Any airflow direction– Integration into the central BMS with

    TROXNETCOM

    Materials and surfacesCasing:

    – Galvanised sheet steel– Galvanised sheet steel, powder-coated

    RAL 7001– Stainless steel 1.4301

    Damper blade:– Special insulation material– Special insulation material with coating

    Other components:– Damper blade shaft in stainless steel– Plastic bearings– Seals of elastomer

    The construction variants with stainless steel orpowder-coated casing meet even more criticalrequirements for corrosion protection. Detailedlisting on request.

    Technical data– Nominal sizes: 200 × 100 mm – 800 × 200 mm– Casing length: 300 mm– Operating temperature: at least 0 – 50 °C– Release temperature: 72 °C

    Description

    This specification textdescribes the generalproperties of the product.Texts for variants can be

    generated with our EasyProduct Finder designprogramme.

    TypeFKS-EU Air transfer damper

    Construction  No entry: standard construction

    Country of destination

      Other destination countries uponrequest

    1  Powder-coated casing, RAL 7001

    2  Stainless steel casing

    7  Coated damper blade

    1 – 7  Powder-coated casing, RAL 7001, andcoated damper blade

    2 – 7  Stainless steel casing and coateddamper blade

    DE  Germany

    Accessories 1  No entry: none

    Accessories 2

    Attachments

    E  Installation blockB  Cover plate

    AA  Cover grilles on both ends

    Z43RM – Z45RM

    Order options