Features Displays instantaneous flow rate, total and accumulated total. 15 point linearisation of the flowcurve - with interpolation. Large 17mm (0.67") digit selection for flow rate or total. Selectable on-screen engineering units; volumetric or mass. Auto backup of settings and running totals. Operational temperature -40°C up to +80°C (- 40°F up to 176°F). Very compact design for panel mount, wall mount or field mount applications. Rugged aluminum field mount enclosure IP67/NEMA4X. Intrinsically Safe - ATEX and IECEx approval for gas and dust applications. Explosion/flame proof II 2 GD EEx d IIB T5. Analog and pulse signal outputs. Full Modbus communication RS232/485/TTL. Loop or battery powered, 8 - 24V AC/DC or 115 - 230V AC power supply. Sensor supply 3.2 / 8.2 / 12 / 24V DC. Signal output (0)4 - 20mA / 0 - 10V DC according to linearised flow rate. Scaled pulse output according to linearised accumulated total. Signal input Flow • Reed-switch. • NAMUR. • NPN/PNP pulse. Sine wave (coil). Active pulse signals. (0)4 - 20mA. 0 - 10V DC. Applications Liquid flow measurement with mechanical flowmeters where a precise calculation over the full measurement range is required. Also re-transmission of the flow rate and/or totalizer functions or serial communication is desired. Alternative basic model: F016 or more advanced F118. DATASHEET F112 - FLOW RATE INDICATOR / TOTALIZER 1 FLOW RATE INDICATOR / TOTALIZER WITH LINEARISATION AND ANALOG / PULSE SIGNAL OUTPUTS

Upload: others

Post on 12-Jul-2022

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

Features• Displays instantaneous flow rate, total and

accumulated total.• 15 point linearisation of the flowcurve - with

interpolation.• Large 17mm (0.67") digit selection for flow

rate or total.• Selectable on-screen engineering units;

volumetric or mass.• Auto backup of settings and running totals.• Operational temperature -40°C up to +80°C (-

40°F up to 176°F).• Very compact design for panel mount,

wall mount or field mount applications.• Rugged aluminum field mount enclosure

IP67/NEMA4X.• Intrinsically Safe - ATEX and IECEx approval

for gas and dust applications.• Explosion/flame proof II 2 GD EEx d IIB T5.• Analog and pulse signal outputs.• Full Modbus communication RS232/485/TTL.• Loop or battery powered, 8 - 24V AC/DC or

115 - 230V AC power supply.• Sensor supply 3.2 / 8.2 / 12 / 24V DC.

Signal output• (0)4 - 20mA / 0 - 10V DC according to

linearised flow rate.• Scaled pulse output according to linearised

accumulated total.

Signal inputFlow• Reed-switch.• NAMUR.• NPN/PNP pulse.• Sine wave (coil).• Active pulse signals.• (0)4 - 20mA.• 0 - 10V DC.

Applications• Liquid flow measurement with mechanical

flowmeters where a precise calculation overthe full measurement range is required. Also re-transmission of the flow rate and/ortotalizer functions or serial communication isdesired. Alternative basic model: F016 ormore advanced F118.

DA

TAS

HE

ET

F11

2 -

FLO

W R

ATE

IN

DIC

ATO

R /

TO

TALI

ZE

R

1

FLOW RATE INDICATOR / TOTALIZER WITH LINEARISATION AND ANALOG / PULSE

SIGNAL OUTPUTS

Page 2: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

General informationIntroductionThe F112 provide very precise linearisation ofthe flowmeters signal. In addition to the averageK-Factor or Span, fifteen linearisation points canbe entered with there frequencies or values. The unit will interpolate between these pointsgreatly enhancing accuracy in any flowrange.Even for very low frequency applications iscatered for. This linearisation effects all displayedinformation as well as the signal outputs. A wideselection of options further enhances thecapabilities of this model, which includes Intrin-sic Safety and full Modbus communication.

DisplayThe display has large 17mm (0.67”) and 8mm(0.31”) digits which show flow rate and totals.On-screen engineering units are easilyconfigured from a comprehensive menu. Thelinearised accumulated total can register up to11 digits and is backed-up in EEPROM memoryevery minute.

ConfigurationAll configuration settings are accessed via asimple operator menu which can be pass-codeprotected. Each setting is clearly indicated withan alphanumerical description, which avoidesconfusing abbreviations. Once familiar with oneF-series product, you will be able to program allmodels in the series without a manual. All set-tings are safely stored in EEPROM memory inthe event of sudden power failure.

Analog output signalThe linearised flow rate is re-transmitted withthe (0)4 - 20mA or 0 - 10V DC output signal.The output signal is updated ten times persecond with a filter function being available tosmoothen out the signal if desired. The output value is user defined in relation tothe flow rate, e.g. 4mA equals to 15L/Hr and20mA equals to 2000L/Hr. The output signal canbe passive, active or isolated where the passiveoutput type will loop power the F112 as well.

Pulse outputThe scaleable pulse output, reflects the count onthe accumulated display. The pulse length isuser defined from 0.008 second up to 2 seconds.

The maximum output frequency is 64Hz. The output signal can be a passive NPN, activePNP or an isolated electro-mechanical relay.

Signal inputThe F112 accepts most pulse and analog inputsignals for volumetric flow or mass flowmeasurement. The input signal type can beselected by the user in the configuration menuwithout having to adjust any sensitivemechanical dip-switches.

CommunicationAll process data and settings can be read andmodified manually or through the Modbuscommunication link (RS232 / RS485). Full Modbus functionality remains available forthe Intrinsically Safe version (TTL).

Hazardous areasThis model has been ATEX and IECEx certifiedIntrinsically Safe for gas and dust applications,with an allowed operational temperature of -40°C to +70°C (-40°F to +158°F). A flame proof enclosure with ATEX certificationoffers the rating II 2 GD EEx d IIB T5.

EnclosuresVarious types of enclosures can be selected, allATEX and IECEx approved. As standard theF112 is supplied in an GRP panel mountenclosure, which can be converted to an IP67 /NEMA 4X GRP field mount enclosure by theaddition of a back case. Most popular is ourrugged aluminum field mount enclosure withIP67 / NEMA 4X rating. Both European or U.S.cable gland entry threads are available.

Overview application F112

Pulse output Analog output Communication link

external reset button

Flowmeterinput

Linearization

F1122

Page 3: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

Dimensions enclosuresAluminum & GRP panel mount enclosure

Aluminum & GRP field / wall mount enclosures

Terminal connections

Display example - 90 x 40mm (3.5” x 1.6”)

CB: R

S232

CH: R

S485

- 2 w

ire

AB

YZ

RX

DTX

D

CT: T

TL In

trinsic

ally S

afe

P: re

ed sw

itch /

NPN

P: co

il

P: na

mur

P: P

NP

A: (0

)4 -

20mA

P: ac

tive s

ignal

U: 0

- 10V

-

+

==

56

PULS

E OU

TPUT

12

POW

ER S

UPPL

Y

GN

D

-+

PD: 8

- 24

V AC

PD: 8

- 24

V DC

-+

PF: 2

4V A

C

PM: 1

15 -

230V

AC

PF: 2

4V D

C

PD-X

I: 16 -

30V

DC

+-

+

OT: p

assiv

e tra

ns.

OA: a

ctive

24V

DC

OR: m

ech.

relay

+

==

34

PULS

E OU

TPUT

1011

FLOW

METE

R IN

PUT

9

+

+ -+

+

+ +

AP: 4

- 20

mA

AA: 4

- 20

mA

AF: 4

- 20

mA

AU: 0

- 10

V

AI: 4

- 20

mA

AB: 0

- 20

mA

78

ANAL

OG O

UTPU

T

+II-

+I +U

I U

+II

+II-

+II

OT: p

assiv

e tra

ns.

OA: a

ctive

24V

DC

OR: m

ech.

relay

+

+

+I +U

IB: R

eset

total13

14

RESE

T IN

PUT

1218

1917

1516

2728

COMM

UNIC

ATIO

N / B

ACKL

IGHT

2623

2425

2122

2029

3031

DTR

+12V

CI: R

S485

- 4 w

ire

AB

RX

DTX

DD

TR+1

2V

+

ZB: B

ackli

ght o

ption

++

+

(With

PD

/ PF

/ PM

termi

nals

26 / 3

1 are

not a

vaila

ble,

back

light

powe

r sup

ply is

integ

rated

.)

PX: 8

- 30

V DC

Outpu

t loop

powe

red u

nit w

ith ty

pe A

P(te

rmina

ls GN

D - 1

- 2 a

re no

t ava

ilable

)

A - P

L: 4 -

20mA +I

PB / P

C: ba

ttery

powe

red

Inter

nal lo

ng lif

e Lith

ium ba

ttery

(term

inals

GND

- 1 -

2 are

not a

vaila

ble)

PL: in

put lo

op po

were

d(te

rmina

ls GN

D - 1

- 2 a

re no

t ava

ilable

)

F112 3

130 mm (5.12")

120

mm

(4.7

2")

31 mm(1.22")

29 mm(1.14")

115 (4.53")

98

(3.8

6")

panel cut-outHB & HC enclosures

75 mm (2.95")

130 mm (5.12")

112 mm (4.40")

60 m

m (2

.36"

)

120

mm

(4.7

2")

M20 x 1,5PG9 PG9

30mm 30mm

22,5

0mm

M20 x 1,5M16 x 1,5 M16 x 1,5

30mm 30mm

22,5

0mm

M20 x 1,5

22,5

0mm

M20 x 1,5 M20 x 1,5

25mm 25mm

22,5

0mm

1/2"NPT

0.9"

1/2"NPT1/2"NPT 1/2"NPT

1.18" 1.18"

0.9"

HA

HM

HN

HO

HD

HP

HE

HT

HF

HU

HG

HV

HH6 x M12

12mm 12mm

24mm24mm36mm36mm

14m

m17

mm

Ø12

12mm 12mm

24mm24mm36mm36mm

14m

m17

mm

HK

22,5

0mm

30mm 30mm

Ø16 Ø16Ø20

HJ

22,5

0mm

(0.9

")30mm (1.18") 30mm (1.18")

Ø22 ( 7/8") Ø22 ( 7/8")Ø22 ( 7/8")

22,5

0mm

(0.9

")

Ø22 ( 7/8")

22,5

0mm

25mm 25mm

Ø20 Ø20

Aluminum GRP

Flat bottom, no holes available.

4 x M20 x 1.5

15mm 15mm

HZ

16m

m15

mm

38mm

Ø 7mm (0.27") Ø 7mm (0.27")

Page 4: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

Typical wiring diagram F112-P-(AP)-CH-IB-(OT)-PB Typical wiring diagram F112-P-AP-CH-IB-OT-PX

910

1112

65

13

Common ground

Signal

Supply *

Common ground

TERMINAL CONNECTORSF100-series

78

Common ground

Flowmeter input type: Ppulse

Circu

it dep

ends

on

type o

f sign

al

2827

2629

8 - 30V DC

+

-

A

Common ground

B

Common ground

+ 3.2Vlow-pass

filter

1M

* Supply voltage: 1.2 / 3.2V DC to sensor

123456e.g. counter

Status input type IB:reset total

e.g. indicator

Analog output type AP: passive 4 - 20mA (loop powered)

Modbus communication type CH: RS485 - 2 wire

Pulse output type OT:

passive transistor

OUTPUT LOOP POWERED9

1011

Common ground

Common ground

Signal

Supply *

TERMINAL CONNECTORSF100-series

78

Common ground

Circu

it dep

ends

on

type o

f sign

al

2826

29

A

Common ground

B

* Supply voltage: 1.2 / 3.2V DC to sensor

Flowmeter input type: Ppulse

Modbus communication type CH: RS485 - 2 wire

Analog output type AP:Passive 4 - 20mA

(not used in this example)

BATTERY POWERED

Status input type IB:reset total

1213

+ 3.2Vlow-pass

filter

1M

65Common ground

Please note: AP may be used in combination with the

battery!

AP will power the unit (output loop powered);

the battery will be disabled automatically untill power

is disconnected).

Pulse output type OT: passive transistor

(not used in this example)

F1124

Page 5: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

Typical wiring diagram F112-A-AA-CB-IB-OA-PD Typical wiring diagram F112-A-AI-CI-IB-OR-PM

01

29

1011

126

513

Common ground

Signal

Supply *

Common ground

TERMINAL CONNECTORSF100-series

8 - 24V DC

+

-7

8

Common ground

Common ground

Main supply

2827

2629

Common ground

Common ground

+ 3.2Vlow-pass

filter

1M

* Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor

RXD

TXD

DTR12V

8 - 24V AC

Pulse output type OA:active 24V DC pulse

Analog output type AA:active 4 - 20mA

Flowmeter input type A:(0)4 - 20mA

e.g. indicator

+

-

+

- e.g. counter123456

Earth

Status input type IB:reset total

Modbus communication type CB: RS232

Power supply type PD: 8 - 24V AC / DC

24V AC / DC POWER SUPPLY

01

29

1011

65

TERMINAL CONNECTORSF100-series

N

78

Common ground

Main supply

26

8 - 30V DC

+

-

Common ground

Common ground

Signal

Supply *

Earth

e.g. counter123456

L1

Flowmeter input type A:(0)4 - 20mA

Pulse output type OR:mechanic relay

e.g. indicator

1213

Common ground

+ 3.2V 1M

Status input type IB:reset total

Power supply type PM:115 - 230V AC

Analog output type AI:passive isolated 4 - 20mA

2831

3029

Y

Z

A

B

Modbus communication type CI: RS485 - 4 wire

115 - 230V AC POWER SUPPLY

* Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor

low-passfilter

F112 5

Page 6: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

Hazardous area applicationsThe F112-XI has been certified accordingATEX and IECEx by DEKRA for use inIntrinsically Safe applications with anambient temperature of -40°C to +70°C (-40°F to +158°F). • The ATEX markings for gas and dust

applications are:II 1 G Ex ia IIB/IIC T4 GaII 1 D Ex ia IIIC T100 ¡ C Da IP6X.

• The IECEx markings for gas and dustapplications are: Ex ia IIC/IIB T4 Ga andEx ia IIIC T100 ¡ C Da IP6X.

Besides the I.S. power supply for the pulseoutput, it is allowed to connect up to threeI.S. power supplies in IIB/IIIC applicationsor one in IIC applications. Consult thecertificate for the maximum input and outputvalues of the circuits. Full functionality of theF112 remains available, including 4 - 20mAoutput, pulse output and Modbuscommunication (type CT). Power supply typePD-XI offers a 8.2V sensor supply e.g. for oneNamur sensor. A flame proof enclosure with rating ATEX

II 2 GD EEx d IIB T5 is available as well. Please contact your supplier for further details.

Certificate of conformity KEMA 03ATEX1074 X• IECEx DEK 11.0042X

TERMINAL CONNECTORSF100-series

HAZARDOUS AREA SAFE AREA

910

11

Common ground

Signal

Supply *

Circu

it dep

ends

on

type o

f sign

al

* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.

Flowmeter input type: Ppulse

Common ground 78

RXD

Common ground

TXD

2826

29

Modbus communication type CT: TTLPossible for battery powered applications

(not used in this example).

Please note: communciation type CT is not allowed in IIC applications.

DTR+12V

27

Status input type IB:reset total

Ci is negligiblysmall

1213

Common ground

+ 3.2Vlow-pass

filter

1M

56

Common ground

Ci is negligiblysmall

Analog output type AP:passive 4 - 20mA

(not used in this example)

Please note: AP may be used in combination with the

battery!

AP will power the unit (output loop powered);

the battery will be disabled automatically untill power

is disconnected).

Pulse output type OT: passive transistor

(not used in this example)

Configuration example IIB / IIIC and IIC F112-P-(AP)-(CT)-IB-(OT)-PC-XI - Battery powered unit

F1126

Page 7: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

Configuration example IIB / IIIC and IIC - F112-P-AP-(CT)-IB-OT-PX-XI - Output loop powered

910

11

Common ground

Signal

Supply *

Circu

it dep

ends

on

type o

f sign

al

Analog output type AP:passive 4 - 20mA (output loop powered)

56

Common ground

123456

Ci = 17nF

78

Flowmeter input type: Ppulse

Common grounde.g. counter

+

-

POWER SUPPLYe.g. MTL 5525

and / or REPEATER

e.g. MTL 5541

Uo=max 30V

Io=max 100mA

Po=max 750mW

+

-

POWER SUPPLYe.g. MTL 5525

or SWITCH INTERFACE

e.g. MTL 5511

Uo=max 30V

Io=max 100mA

Po=max 750mWe.g. counter

123456

e.g. indicator

e.g. indicator

TERMINAL CONNECTORSF100-series

HAZARDOUS AREA SAFE AREA

Status input type IB:reset total

Ci is negligiblysmall

1213

Common ground

RXD

Common ground

TXD

2826

29

DTR+12V

27

ISOLATOR:I.S. Certified Isolator

TTL to RS232 / RS422 / TTL

For example: MTL5051

Uo=max 30V

Io=max 250mA

Po=max 850mW

+

-

e.g. PC

+ 3.2Vlow-pass

filter

1M

Modbus communication type CT: TTLPlease note: communciation type CT is not allowed in IIC applications.

* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.

Pulse output type OT:passive transistor

Ci is negligiblysmall

Ci is negligiblysmall

Note: above values are safety values.Consult the technical specification for operational values.

* Note: Communication only allowed when configured as IIB / IIIC.

F112 7

Page 8: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

Configuration example IIB / IIIC and IIC - F112-A-AF-(CT)-IB-OT-PD-XI - Power supply 16 - 30V DC

Common ground

TOTAL Co OF ALL CONNECTEDANALOG APPARATUS IN IICAPPLICATIONS MAY NOT

EXCEED 66nF MINUS 17nF(17nF IS USED BY THE ANALOG

OUTPUT SIGNAL TERMINAL 7 + 8).

Main supply Power supply type PD: 16 - 30V DC (please note: PD and battery supply (type PC) is NOT allowed in IIC applications).

56

Common ground

01

2

123456

Ci = 17nF Analog output type AF:passive floating 4 - 20mA

78

910

11

Common ground

Signal

Supply *

Circu

it dep

ends

on

type o

f sign

al

Ci is negligiblysmall

Flowmeter input type: A(0)4 - 20mA

e.g. counter

+

-

POWER SUPPLY

For example MTL5525

Uo=max 30V

Io=max 100mA

Po=max 750mW

+

-

Uo=max 30V

Io=max 100mA

Po=max 750mW e.g. counter

123456

e.g. indicator

* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).

TERMINAL CONNECTORSF100-series

HAZARDOUS AREA SAFE AREA

Status input type IB:reset total

Ci is negligiblysmall

1213

Common ground

RXD

Common ground

TXD

2826

29

DTR+12V

27

ISOLATOR:I.S. Certified Isolator

TTL to RS232 / RS422 / TTL

For example: MTL5051

Uo=max 30V

Io=max 250mA

Po=max 850mW

+

-

e.g. PC

+ 3.2Vlow-pass

filter

1M

Modbus communication type CT: TTLPlease note: communciation type CT is not allowed in IIC applications.

Pulse output type OT:passive transistor

Ci is negligiblysmall

POWER SUPPLYe.g. MTL 5525

or SWITCH INTERFACE

e.g. MTL 5511

Note: above values are safety values.Consult the technical specification for operational values.

* Note: Communication only allowed when configured as IIB / IIIC.

F1128

Page 9: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

Configuration example IIB / IIIC - F112-A-AF-CT-IB-OT-(PC)-(PD)-XI - Power supply 16 - 30V DC or battery powered

Ci = 17nF

910

11

Common ground

Common ground

Signal

Supply *

Main supply

Circ

uit de

pend

s on

type o

f sign

al

* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).

Power supply type PD: 16 - 30V DC

Analog output type AF:passive floating 4 - 20mA

56

Common ground

01

27

8

123456

Flowmeter input type: A(0)4 - 20mA

e.g. counter

+

-

+

-

POWER SUPPLYe.g. MTL 5525

and / or REPEATER

e.g. MTL 5541

Uo=max 30V

Io=max 100mA

Po=max 750mW

Uo=max 30V

Io=max 100mA

Po=max 750mW

+

-

POWER SUPPLY

For example MTL5525

Uo=max 30V

Io=max 100mA

Po=max 750mW

+

-

POWER SUPPLYe.g. MTL 5525

or SWITCH INTERFACE

e.g. MTL 5511

Uo=max 30V

Io=max 100mA

Po=max 750mWe.g. counter

123456

e.g. indicator

e.g. indicator

TERMINAL CONNECTORSF100-series

HAZARDOUS AREA SAFE AREA

Status input type IB:reset total

Ci is negligiblysmall

1213

Common ground

RXD

Common ground

TXD

2826

29

DTR+12V

27

ISOLATOR:I.S. Certified Isolator

TTL to RS232 / RS422 / TTL

For example: MTL5051

Uo=max 30V

Io=max 250mA

Po=max 850mW

+

-

e.g. PC

+ 3.2Vlow-pass

filter

1M

Modbus communication type CT: TTL

Due to analog output type AF, the unit has to be powered with battery type PC or with external power supply type PD.

Pulse output type OT:passive transistor

Ci is negligiblysmall

Ci is negligiblysmall

Note: above values are safety values.Consult the technical specification for operational values.

REPEATERFor example

MTL5541

F112 9

Page 10: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

Technical specificationGeneral

DisplayType High intensity reflective numeric and

alphanumeric LCD, UV-resistant.Dimensions 90 x 40mm (3.5” x 1.6”).Digits Seven 17mm (0.67") and eleven 8mm (0.31") digits.

Various symbols and measuring units.Refresh rate User definable: 8 times/sec. - 1 time/30 secs.Option ZB Transflective LCD with green LED backlight.

Good readings in full sunlight and darkness. Note ZB Only available for safe area applications.

Operating temperatureStandard unit -40°C to +80°C (-40°F to +176°F).Intrinsically Safe -40°C to +70°C (-40°F to +158°F).

Power requirementsType PB Long life Lithium battery - life-time depends upon

settings and configuration - up to 5 years.Type PC Intrinsically Safe long life lithium battery - life-time

depends upon settings and configuration - up to 5 years.

Type PD 8 - 24V AC / DC ± 10%. Power consumption max. 10 Watt. Intrinsically Safe: 16 - 30V DC; power consumption max. 0.75 Watt.

Type PF 24V AC / DC ± 10%. Power consumption max. 15 Watt.Type PL Input loop powered from sensor signal 4 - 20mA

(type “A”) - requires types AI or AF and OT (not Xi).Type PM 115 - 230V AC ± 10%. Power consumption max. 15 Watt.Type PX 8 - 30V DC. Power consumption max. 0.5 Watt. Type ZB 12 - 24V DC ± 10% or internally powered with type PD

/ PF / PM. Power consumption max. 1 Watt.Note PB/PF/PM Not availble Intrinsically Safe.Note PF/PM The total consumption of the sensors and outputs

may not exceed 400mA @ 24V.Note For Intrinsically Safe applications, consult the safety

values in the certificate.

Sensor excitationType PB/PC/PX 3.2V DC for pulse signals and 1.2V DC for coil pick-up.

Note This is not a real sensor supply. Only suitable for sensors with a very low power consumption like coils(sine wave) and reed-switches.

Type PD 1.2 / 3.2 / 8.2 / 12 / 24V DC - max. 50mA @ 24V DC.Type PD-XI 1.2 / 3.2 / 8.2V DC - max. 7mA @ 8.2V DC and mains

power supply voltage (as connected to terminal 1).Note In case PD-XI and signal A or U: the sensor supply

voltage is according to the power supply voltage connected to terminal 1. Also terminal 2 offers the same voltage.

Type PF / PM 1.2 / 3.2 / 8.2 / 12 / 24V DC - max. 400mA @ 24V DC.

Terminal connectionsType Removable plug-in terminal strip.

Wire max. 1.5mm2 and 2.5mm2.

Data protectionType EEPROM backup of all settings. Backup of running

totals every minute. Data retention at least 10 years.Pass-code Configuration settings can be pass-code protected.

CasingGeneralWindow Polycarbonate window.Sealing Silicone.Control keys Three industrial micro-switch keys. UV-resistant

silicone keypad.

Aluminum wall / field mount enclosuresGeneral Die-cast aluminum wall/field mount enclosure IP67 /

NEMA 4X with 2-component UV-resistant coating.Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.Weight 1100 gr.

Type HA Cable entry: 2 x PG9 and 1 x M20. Type HM Cable entry: 2 x M16 and 1 x M20. Type HN Cable entry: 1 x M20. Type HO Cable entry: 2 x M20. Type HP Cable entry: 6 x M12. Type HT Cable entry: 1 x 1/2" NPT.Type HU Cable entry: 3 x 1/2" NPT.Type HV Cable entry: 4 x M20. Type HZ Cable entry: no holes.

GRP wall / field mount enclosuresGeneral GRP wall/field mount enclosure IP67 / NEMA 4X,

UV-resistant and flame retardant. Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.Weight 600 gr.

Type HD Cable entry: no holes.Type HE Cable entry: 2 x Ø 16mm and 1 x Ø 20mm.Type HF Cable entry: 1 x Ø 22mm (7/8").Type HG Cable entry: 2 x Ø 20mm. Type HH Cable entry: 6 x Ø 12mm. Type HJ Cable entry: 3 x Ø 22mm (7/8"). Type HK Flat bottom, cable entry: no holes.

Panel mount enclosuresDimensions 130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D.Panel cut-out 115 x 98mm (4.53" x 3.86") L x H.

Type HB Die-cast aluminum panel mount enclosure IP65 / NEMA 4X.

Weight 600 gr.Type HC GRP panel mount enclosure IP65 / NEMA 4X,

UV-resistant and flame retardant.Weight 450 gr.

ABS wall / field mount enclosuresGeneral Silicone free ABS wall/field mount enclosure IP65

with EPDM and PE sealings. UV-resisitant polyester keypad (old HD enclosure).

Dimensions 130 x 114 x 71mm (5.1" x 4.5" x 2.8") - W x H x D.Weight 450 gr.

Type HS Cable entry: no holes.

F11210

Page 11: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

Hazardous areaIntrinsically Safe (Type XI)ATEX II 1 G Ex ia IIB/IIC T4 Ga.certification II 1 D Ex ia IIIC T100 °C Da IP6X.IECEx Ex ia IIC/IIB T4 Ga.certification Ex ia IIIC T100 °C Da IP6X.Ambient Ta -40°C to +70°C (-40°F to +158°F).

Explosion proof (Type XF)ATEX certification II 2 GD EEx d IIB T5.Dimensions 300 x 250 x 200mm (11.8" x 9.9" x 7.9") L x H x D.Weight Appr. 15kg.

EnvironmentElectromagnetic Compliant ref: EN 61326 (1997), EN 61010-1 (1993).compatibility

Signal inputsFlowmeterType P Coil / sine wave (minimum 20mVpp or 80mVpp -

sensitivity selectable), NPN/PNP, open collector, reed-switch, Namur, active pulse signals 8 - 12 and 24V DC.

Frequency Minimum 0Hz - maximum 7kHz for total and flow rate. Maximum frequency depends on signal type and internal low-pass filter. E.g. reed switch with low-pass filter: max. frequency 120Hz.

K-Factor 0.000010 - 9,999,999 with variable decimal position.Low-pass filter Available for all pulse signals.Option ZF coil sensitivity 10mVpp.

Type A (0)4 - 20mA. Analog input signal can be scaled to anydesired range within 0 - 20mA.

Type U 0 - 10V DC. Analog input signal can be scaled to any desired range within 0 - 10V DC.

Accuracy Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS. Low level cut-off programmable.

Span 0.000010 - 9,999,999 with variable decimal position.Update time Four times per second.Voltage drop Type A: 2.5V @ 2omA.Load impedance Type U: 3kΩ.Relationship Linear and square root calculation.Note For signal type A and U: external power to sensor is

required; e.g. type PD.

Logic inputsFunction • Terminal input to reset total remotely.

• If this terminal input is closed, the “clear total”-function is disabled.

Type IB Internally pulled-up switch contact - NPN.Duration Minimum pulse duration 100msec.

Signal outputsCommunication optionFunction Reading display information, reading / writing all

configuration settings.Protocol Modbus RTU.Speed 1200 - 2400 - 4800 - 9600 baud.Addressing Maximum 255 addresses.Type CB RS232Type CH RS485 2-wire Type CI RS485 4-wireType CT TTL Intrinsically Safe.

Analog outputFunction Transmitting linearised flow rate.Accuracy 10 bit. Error < 0.05%. Analog output signal can be

scaled to any desired range.Update time Ten times per second.Type AA Active 4 - 20mA output (requires PD, PF or PM).Type AB Active 0 - 20mA output (requires PD, PF or PM).Type AF Passive floating 4 - 20mA output for Intrinsically

Safe applications (requires XI + PC or PD).Type AI Passive galvanically isolated 4 - 20mA output - also

available for battery powered models (requires PB, PD, PF, PL or PM).

Type AP Passive 4 - 20mA output - not isolated. Unit will beloop powered.

Type AU Active 0 - 10V DC output (requires PD, PF or PM).

Pulse outputFunction Pulse output - transmitting accumulated total.Frequency Max. 64Hz. Pulse length user definable between

7.8 msec up to 2 seconds.Type OA One active 24V DC transistor output (PNP);

max. 50mA per output (requires PD, PF or PM).Type OR One electro-mechanical relay output - isolated;

max. switch power 230V AC (N.O.) - 0.5A per relay (requires PF or PM).

Type OT One passive transistor output (NPN) - not isolated. Max. 50V DC - 300mA per output.

OperationalOperator functionsDisplayed • Linearised flow rate and / or total.Functions • Linearised total and accumulated total.

• Total can be reset to zero by pressing the CLEAR-key twice.

TotalDigits 7 digits.Units L, m3, GAL, USGAL, kg, lb, bbl, no unit.Decimals 0 - 1 - 2 or 3. Note Total can be reset to zero.

Accumulated totalDigits 11 digits.Units / decimals According to selection for total.Note Can not be reset to zero.

Flow rateDigits 7 digits.Units mL, L, m3, Gallons, kg, Ton, lb, bl, cf, RND, ft3, scf,

Nm3, Nl, igal - no units.Decimals 0 - 1 - 2 or 3.Time units /sec - /min - /hr - /day.

F112 11

Page 12: FLOW RATE INDICATOR / TOTALIZER WITH ... - platon-direct.eu

Specifications are subject to change without notice.

Ordering information Standard configuration: F112-P-AP-CX-EX-HC-IX-OT-PX-TX-XX-ZX.Ordering information: F112 -_ -A _ -C _ _EX -H _ -I _ -O _ -P _ -TX -X _ -Z _Flowmeter input signalA (0)4 - 20mA input.P Pulse input: coil, npn, pnp, namur, reed-switch.U 0 - 10V DC input.Analog output signalAA Active 4 - 20mA output - requires PD, PF or PM.AB Active 0 - 20mA output - requires PD, PF or PM.AF I.S. floating 4 - 20mA output - requires XI + PC or PD.AI Isolated 4 - 20mA output - requires PB, PD, PF, PL or PM.AP Passive 4 - 20mA output, loop powered unit.AU Active 0 - 10V DC output - requires PD, PF or PM.CommunicationCB Communication RS232 - Modbus RTU.CH Communication RS485 - 2-wire - Modbus RTU.CI Communication RS485 - 4-wire - Modbus RTU.CT Intrinsically Safe TTL - Modbus RTU.CX No communication.Flow equationsEX No flow equations.Panel mount enclosures - IP65 / NEMA4XHB Aluminum enclosure.HC GRP enclosure.GRP field / wall mount enclosures - IP67 / NEMA4XHD Cable entry: no holes.HE Cable entry: 2 x Ø 16mm & 1 x Ø 20mm.HF Cable entry: 1 x Ø 22mm (7/8”).HG Cable entry: 2 x Ø 20mm.HH Cable entry: 6 x Ø 12mm.HJ Cable entry: 3 x Ø 22mm (7/8”).HK Flat bottom, cable entry: no holes.Aluminum field / wall mount enclosures - IP67 / NEMA4XHA Cable entry: 2 x PG9 + 1 x M20.HM Cable entry: 2 x M16 + 1 x M20.HN Cable entry: 1 x M20.HO Cable entry: 2 x M20.HP Cable entry: 6 x M12.HT Cable entry: 1 x 1/2”NPT.HU Cable entry: 3 x 1/2”NPT.HV Cable entry: 4 x M20.HZ Cable entry: no holes.ABS field / wall mount enclosures - IP65HS Silicone free ABS field enclosure – Cable entry: no holes (old HD enclosure).Additional inputsIB Terminal input to reset total.IX No external input.OutputsOA One active transistor output - requires PD, PF or PM.OR One mechanical relay output - requires PF or PM.OT One passive transistor output - standard configuration.Power supplyPB Lithium battery powered.PC Lithium battery powered - Intrinsically Safe.PD 8 - 24V AC/DC + sensor supply - with XI: 16 - 30V DC.PF 24V AC/DC + sensor supply.PL Input loop powered from sensor signal type “A” - requires AI or AF and OT (not Xi).PM 115 - 230V AC + sensor supply.PX Basic power supply 8 - 30V DC (no real sensor supply). Unit requires external loop AP.Temperature input signalTX No temperature input signal.Hazardous areaXI Intrinsically Safe, according ATEX and IECEx.XF EExd enclosure - 3 keys.XX Safe area only.Other optionsZB Backlight. ZF Coil input 10mVpp.ZX No options.

The bold marked text contains the standard configuration.Available Intrinsically Safe.

Cop

yrig

ht: F

luid

wel

l bv

- 201

1 - F

112-

DA

TA-E

N-V

1121

12

Fluidwell bvP.O. Box 65460 AA - Veghel - The NetherlandsTel.: +31 (0)413 343786Fax.: +31 (0)413 [email protected]: www.fluidwell.com