harmonics analysis and mitigation using passive...
TRANSCRIPT
Harmonics Analysis and Mitigation Using Passive Filters
By:
Rooh Ul Amin Shaikh 11EL01
Abdul Basit Lashari 11EL16
Irfan Ansari 11EL37
Supervised By:
Prof. Dr. ZUBAIR AHMED MEMON
DEPARTMENT OF ELECTRICAL ENGINEERING,
MEHRAN UNIVERSITY OF ENGINEERING & TECHNOLOGY,
JAMSHORO
Submitted in partial fulfillment of the requirement for the degree of
Bachelors of Electrical Engineering
January, 2015
In the name of Almighty Allah,
The most gracious and the most
merciful
CERTIFICATE
This is to certify that the work presented in this thesis titled “Harmonics Analysis
and Mitigation Using Passive Filters” is written by the following students as a
partial fulfillment of the requirements for the degree of Bachelors of Electrical
Engineering under the supervision of the Prof. Dr. Zubair Ahmed Memon
Rooh Ul Amin Shaikh 11EL01
Abdul Basit Lashari 11EL16
Irfan Ansari 11EL37
ACKNOWLEGEMENTS
We are grateful to our thesis mentor, Prof. Dr. Zubair Ahmed Memon for providing
us the opportunity and guidance to complete this work, which is an integral part of the
curriculum of Bachelors of Electrical Engineering at Mehran University of
Engineering & Technology.
i
ABSTRACT
Both electric utilities and end users of electric power are becoming increasingly
concerned about the quality of electric power. It is an umbrella concept for a
multitude of individual types of power system disturbances. One such major concern
is the harmonics which is made the focus of study in this work. When electronic
power converters first became commonplace in the late 1970s, many utility engineers
became quite concerned about the ability of the power system to accommodate the
harmonic distortion. Harmonics problems counter many of the conventional rules of
power system design and operation that consider only the fundamental frequency.
Therefore, the engineer is faced with unfamiliar phenomena that require unfamiliar
tools to analyze and unfamiliar equipment to solve.
This thesis is basically concerned with the Analysis and Mitigation of Harmonics
generated by Power Electronic Converters. The investigation of harmonics has been
carried out using Fast Fourier Transform (FFT) to evaluate the Total Harmonic
Distortion (THD) of the converters with and without filters. And
MATLAB/SIMULINK has been employed for presenting the simulation results
because it is well established and recognized simulation software for the power
system. Next, the designing of Passive Filter is carried out after a literature review and
have been applied to the converters for harmonics mitigation.
In the future, we would proceed to work on Active Filters for Harmonics Mitigation.
ii
CONTENTS
CHAPTER 01
INTRODUCTION
1.1 ELECTRIC POWER QUALITY 01
1.2 SOURCES OF ELECTRIC POWER QUALITY DETERIORATION IN
A POWER SYSTEM 02
1.3 NEED FOR ASSESSMENT OF ELECTRIC POWER QUALITY 02
1.4 CLASSIFICATION OF POWER SYSTEM DISTURBANCES 03
1.5 WHY ARE WE CONCERNED ABOUT POWER QUALITY? 06
CHAPTER 02
FUNDAMENTALS OF HARMONICS
2.1 INTRODUCTION 07
2.2 TYPES OF HARMONICS 08
2.2.1 Odd harmonics 08
2.2.2 Even harmonics 08
2.2.3 Inter harmonics 08
2.2.4 Sub harmonics 08
2.3 NON-SINUSOIDAL WAVEFORM 09
2.3.1 Average value 09
2.3.2 RMS value 09
2.3.3 Form factor 09
2.3.4 Harmonic power 09
2.3.5 Total active power 10
2.4 SOURCES OF HARMONICS 10
2.4.1 Magnetization nonlinearities of transformer 10
2.4.2 Rotating machines 11
iii
2.4.3 Arcing devices 12
2.4.4 Power supplies with semiconductor devices 12
2.4.5 Inverter Fed A.C drives 12
2.4.6 Thyristor controlled reactors 12
2.4.7 Phase controllers & AC regulators 12
2.5 EFFECTS OF HARMONICS 12
2.5.1 Resonance and effect on capacitor banks 13
2.5.2 Poor damping 13
2.5.3 Effects of harmonics on rotating machines 13
2.5.4 Effects on transformer 13
2.5.5 Effects on transmission lines 13
2.5.6 Harmonic interference with power system protection 14
2.5.7 Effects of harmonics on consumer equipment 14
2.6 HARMONIC INDICES 14
2.6.1 Total harmonic distortion 15
2.6.2 Total demand distortion 15
2.7 PRINCIPLES FOR HARMONICS CONTROL 16
2.8 WHERE TO CONTROL HARMONICS 16
2.8.1 on utility distribution Feeders 17
2.8.2 In End-User Facilities 17
2.9 USEFUL TOOLS FOR HARMONICS ASSESMENT 18
CHAPTER 03
HARMONIC FILTERS
3.1 INTRODUCTION 19
3.2 PASSIVE FILTERS 19
3.2.1 Passive shunt filters 20
iv
3.2.2 Passive series filter 22
3.3 ACTIVE FILTERS 22
3.4 HYBRID FILTERS 23
3.5 DESIGN STEPS OF SERIES TUNED FILTERS 23
3.6 DESIGN STEPS OF 2ND ORDER HIGH PASS FILTER 24
3.7 QUALITY FACTOR, BANDWIDTH AND SELECTIVITY 25
CHAPTER 04
STANDARD LIMITS OF HARMONIC DISTORTION
4.1 INTRODUCTION 27
4.2 VOLTAGE HARMONIC DISTORTION LIMITS 27
4.3 CURRENT HARMONICS DISTORTION LIMITS 28
CHAPTER 05
MATLAB SIMULATION & RESULTS
5.1 POWER CONVERTERS HARMONIC BEHAVIOUR 30
5.2 HARMONIC ANALYSIS OF THREE PHASE 12 PULSE AC-DC
CONVERTERS 31
5.3 HARMONIC ANALYSIS OF THREE PHASE INVERTER 36
CHAPTER 06
CONCLUSIONS
REFERENCES
v
LIST OF FIGURES
Figure 1.1 Harmonics of laptop 04
Figure 1.2 Utility Capacitor Switching Transient 04
Figure 1.3 Voltage Sag 04
Figure 1.4 Voltage Swell 05
Figure 1.5 Flicker 05
Figure 2.1 Harmonic representation 07
Figure 2.2 Harmonic currents flow in a radial system 17
Figure 3.1 Passive shunt filters 20
Figure 3.2 Impedance vs Frequency curve of series tuned filter 21
Figure 3.3 Impedance vs Frequency curve of damped filter 21
Figure 3.4 Passive series filter 22
Figure 3.5 Quality factor effect on resonance curve 25
Figure 3.6 Quality factor effect on selectivity 26
Figure 5.1 Displacement of harmonics as a function of firing angle 30
Figure 5.2 FFT analysis of three phase inverter 31
Figure 5.3 Three phase 12 pulse AC-DC converter model 32
Figure 5.4 Source voltage without filters 32
Figure 5.5 Source current without filters 33
Figure 5.6 FFT analysis of distorted source voltage 33
Figure 5.7 FFT analysis of distorted source current 33
Figure 5.8 Impedance vs Frequency response of designed filter 34
Figure 5.9 Source voltage after filtration 35
vi
Figure 5.10 Source current after filtration 35
Figure 5.11 FFT analysis of filtered source voltage 35
Figure 5.12 FFT analysis of filtered source voltage 36
Figure 5.13 Inverter circuit with MOSFETs 36
Figure 5.14 Three phase inverter model schematic 37
Figure 5.15 AC side voltage and FFT analysis without filters 37
Figure 5.16 AC side current and FFT analysis without filters 38
Figure 5.17 Three phase inverter model schematic with filter 38
Figure 5.18 AC voltage with filtration 39
Figure 5.19 FFT window of AC voltage with filtration 39
Figure 5.20 AC current with filtration 40
Figure 5.21 FFT window of AC current with filtration 40
vii
ABBREVATIONS
EPQ Electric Power Quality
THD Total Harmonic Distortion
TDD Total Demand Distortion
FFT Fast Fourier Transform
RMS Root Mean Square
APFs Active Power Filters
PPFs Passive Power Filters
viii
TABLES
Table 4.1- ANSI/IEEE 519 voltage distortion limits
Table 4.2-IEC 61000-2-2 voltage harmonic distortion limits in public
low-voltage network
Table 4.3- IEC 61000-2-4 voltage harmonic distortion limits in industrial
plants
Table 4.4-IEC 61000-22-4 class 3
Table 4.5-IEC 61000-3-2 maximum permissible harmonic currents for
class D equipment
Table 4.6- IEEE 519 current distortion limits.
Table5.1- Circuit parameters of 12 pulse AC-DC converter
Table 5.2-Designed Series tuned filter specifications
Table 5.3- Circuit parameters of three phase inverter
Table5.4-Designed Passive series filter specifications
1
CHAPTER # 1
INTRODUCTION
1.1 ELECTRIC POWER QUALITY
“Electric Power Quality (EPQ) is a term that refers to maintaining the near sinusoidal
waveform of power distribution bus voltages and currents at rated magnitude and
frequency”
Thus Electric Power Quality is often used to express voltage quality, current quality,
reliability of service, quality of power supply, etc.
Power Quality is ultimately a consumer driven issue defined as:
“Any power problem manifested in voltage, current or frequency deviation that results
in failure or mal-operation of consumers equipment”.
In the study of (EPQ), different branches are being formed which deals with different
issues related to electric power quality .These branches are divided into following
stages.
1. Fundamental concepts
2. Sources
3. Effects
4. Modeling and Analysis
5. Instrumentation
6. Solutions
(i) Fundamental concepts
The ‘fundamental concept’ of EPQ identifies the parameters and their degree of
variation with respect to their rated magnitude which are the base reason for
degradation of quality of electric power.
(ii) Sources
Sources are the regions or locations or events which causes the unwanted variation of
those parameters. It’s really a big challenge to the power engineers to find out the
exact sources of power quality related disturbance in the ever increasing complex
network.
2
(iii) Effects
Effects of poor quality of power are the effects faced by the system and consumer
equipment after the occurrence of different disturbances.
(iv) Modeling and Analysis
In modeling and analysis, attempts are taken to configure the disturbance, its
occurrence, sources and effect; mainly based on the mathematical background.
(v) Instrumentation
For monitoring of EPQ, constant measurement and ‘instrumentation’ of the electric
parameters are necessary.
(vi) Solutions
Complete solution, i.e. delivery of pure power to the consumer side is practically
impossible. Our target is to minimize the probability of occurrence of disturbances
and to reduce the effects of EPQ problems.
1.2 SOURCES FOR ELECTRIC POWER QUALITY DETERIORATION IN A
POWER SYSTEM
The sources of poor power quality can be categorized in two groups:
(i) Actual loads, Equipment and Components.
(ii) Subsystems of transmission and distribution systems.
Poor quality is normally caused by power line disturbances such as impulses, notches,
voltage sag and swell, voltage and current unbalances, momentary interruption and
harmonic distortions. The major contributors to poor power quality are harmonics and
reactive power. Solid state control of ac power using high speed switches are the main
source of harmonics whereas different non-linear loads contribute to excessive drawl
of reactive power from supply.
It leads to catastrophic consequences such as long production downtimes, mal-
function of devices and shortened equipment life.
1.3 NEED FOR ASSESSMENT OF ELECTRIC POWER QUALITY
It is common experience that electric power of poor quality has detrimental effects on
health of different equipment and systems. Moreover, power system stability,
continuity and reliability fall with the degradation of quality of electric power.
3
To avoid such effects, it is important to continuously assess the quality of power
supplied to a consumer.
1.4 CLASSIFICATION OF POWER SYSTEM DISTURBANCES
Power quality problems occur due to various types of electrical disturbances. Most of
the EPQ disturbances depend on amplitude or frequency or on both frequency and
amplitude. Based on the duration of existence of EPQ disturbances, events can
divided into short, medium or long type. These disturbances are mainly classified as:
(i) Interruption/under voltage/over voltage
During power interruption, voltage level of a particular bus goes down to zero. The
interruption may occur for short or medium or long period. Under voltage and over
voltage are fall and rise of voltage levels of a particular bus with respect to standard
bus voltage. Such disturbances increase the amount of reactive power drawn or
deliver by a system, insulation problems and voltage stability.
(ii) Voltage/Current unbalance
Voltage and current unbalance may occur due to the unbalance in drop in the
generating system or transmission system and unbalanced loading. During unbalance,
negative sequence components appear. It hampers system performance and voltage
stability.
(iii) Harmonics
Harmonics are sinusoidal voltages or currents having frequencies that are integer
multiples of the frequency at which the supply system is designed to operate (termed
the fundamental frequency; usually 50 or 60 Hz). Periodically distorted waveforms
can be decomposed into a sum of the fundamental frequency and the harmonics.
Harmonic distortion originates due to the nonlinear characteristics of devices and
loads on the power system. Harmonics are classified as integer harmonics, sub
harmonics and inter harmonics. Integer harmonics have frequencies which are integer
multiple of fundamental frequency, sub harmonics have frequencies which are smaller
than fundamental frequency and inter harmonics have frequencies which are greater
than fundamental frequencies. Sometimes harmonics are classified as time harmonics
and spatial (space) harmonics. Monitoring of harmonics with respect to fundamental
is important consideration in power system application.
4
Figure 1.1
(iv) Transients
Transients which are the sudden rise of signal may generate in the system itself or
may come from the other system. Transients are classified into two categories: dc
transient and ac transient. The figure 1.2 shows utility capacitor-switching transient.
Figure 1.2
(v) Voltage Sag
It is a short duration disturbance. During voltage sag, RMS voltage falls to a very low
level for short period of time. It is actually a reduction in RMS voltage over a range of
0.1–0.9 pu for a duration greater than 10 ms but less than 1 s
Figure 1.3
5
(vi) Voltage Swell
It is a short duration disturbance. During voltage sag, RMS voltage increases to a very
high level for short period of time. It is an increase in RMS voltage over a range of
1.1–1.8 pu for a duration greater than 10 ms but less than 1 s.
Figure 1.4
(vii) Flicker
It is undesired variation of system frequency. The voltage variations resulting from
flicker are often within the normal service voltage range, but the changes are
sufficiently rapid to be irritating to certain end users. Flicker can be separated into two
types: cyclic and noncyclic. Cyclic flicker is a result of periodic voltage fluctuations
on the system, while Non-cyclic is a result of occasional voltage fluctuations.
The usual method for expressing flicker is similar to that of percent voltage
modulation. It is usually expressed as a percent of the total change in voltage with
respect to the average voltage ( V/V) over a certain period of time. The figure 1.5-
shows a typical flicker waveform.
Figure 1.5
6
(viii) Ringing waves
Oscillatory disturbance of decaying magnitude for short period of time is known as
ringing wave. It may be called a special type transient.
(ix) Outage
It is special type of interruption where power cut has occurred for not more than 60 s.
1.5 WHY ARE WE CONCERNED ABOUT POWER QUALITY?
The ultimate reason that we are interested in power quality is economic value. There
are economic impacts on utilities, their customers, and suppliers of load equipment.
The quality of power can have a direct economic impact on many industrial
consumers. There is big money associated with these disturbances. It is not
uncommon for a single, commonplace, momentary utility breaker operation to result
in a $10,000 loss to an average-sized industrial concern by shutting down a
production line that requires 4 hours to restart. In the semiconductor manufacturing
industry, the economic impacts associated with equipment sensitivity to momentary
voltage sags resulted in the development of a whole new standard for equipment ride-
through.
The electric utility is concerned about power quality issues as well. Meeting customer
expectations and maintaining customer confidence are strong motivators. The loss of
a disgruntled customer to a competing power supplier can have a very significant
impact financially on a utility.
7
Chapter # 2
FUNDAMENTALS OF HARMONICS
2.1 INTRODUCTION
A pure poly-phase system is expected to have pure sinusoidal alternating current and
voltage waveforms of single frequency. But, the real situation deviates from this
purity. Real voltage and current waveforms are distorted. Normally they are called
non sinusoidal waveforms. Non sinusoidal waveform is formed with the combination
of many sine waves of different frequencies. Thus actual power system signals have
fundamental component as well as harmonic components.
Harmonic distortion is caused by nonlinear devices in the power system. A nonlinear
device is one in which the current is not proportional to the applied voltage. When a
waveform is identical from one cycle to the next, it can be represented as a sum of
pure sine waves in which the frequency of each sinusoid is an integer multiple of the
fundamental frequency of the distorted wave. This multiple is called a harmonic of the
fundamental, hence the name of this subject matter. The sum of sinusoids is referred
to as a Fourier series, named after the great mathematician who discovered the
concept.
Harmonic component of current of order n can be represented as
in = In sin 2πnft (2.1)
Where In is the amplitude of harmonic component of order n.
Figure 2.1
8
Figure 2.1 illustrates that any periodic, distorted waveform can be expressed as sum
of sinusoids.
2.2 TYPES OF HARMONICS
Integer harmonics are divided into two categories: odd harmonics and even
harmonics. Other than integer harmonics there are sub and inter harmonics where n is
fractional.
2.2.1 Odd Harmonics: Integer harmonics having frequencies which are odd integer
multiple of fundamental frequency are known as odd harmonics. Odd harmonics may
be expressed as
in = In sin 2πnft (2.2)
Where, n = 3, 5, 7, . . . etc. and In is the amplitude of harmonic component of order n.
2.2.2 Even Harmonics: Integer harmonics having frequencies which are even integer
multiple of fundamental frequency are knows as even harmonics. Even harmonics
may be expressed as
in = In sin 2πnft (2.3)
Where, n = 2, 4, 6, . . . etc. and In is the amplitude of harmonic component of order n.
2.2.3 Inter Harmonics: Often in non-sinusoidal waveform there are harmonics
having frequencies which are greater than fundamental but not integer multiple of
fundamental frequency. These are known as inter-harmonics. Mathematically,
in = In sin 2πnft (2.4)
Where, n > 1 but not integer; e.g.: 1.2, 1.5, 2.7 . . . etc
2.2.4 Sub Harmonics: Often in non-sinusoidal waveform there are harmonics having
frequencies which are smaller than fundamental frequency. These are known as sub-
harmonics. Mathematically,
in = In sin 2πnft (2.5)
Where, n < 1; e.g.: 0.2, 0.5, 0.7 . . . etc
9
2.3 NON-SINUSOIDAL WAVEFORM
Non-sinusoidal wave is constituted by the combination of odd-even harmonic
components as well as fundamental component. Thus, mathematically, it can be
expressed as:
i=∑ ∑ (2.6)
A non-sinusoidal wave may be expressed in terms of harmonics as
i=∑ ∑ =
= I1 sin 2πft + I2 sin 4πft + I3 sin 6πnft + I4 sin 8πnft + I5 sin 10πnft+· · · ·
= I1 sin 2πf1ft + I2 sin 2πf2t + I3 sin 2πf3t + I4 sin 2πf4t + I5 sin 2πf5t . . . . (2.7)
2.3.1 Average Value
Harmonic components having phase angle (αn) can be expressed as:
in = In sin (2πfnt − αn) (2.8)
Average value is given by:
inav = (
) (
) (2.9)
2.3.2 RMS Value
RMS value of the non-sinusoidal current wave is given by:
iRMS = √ = √∑
(2.10)
2.3.3 Form Factor
Form factor is the ratio of RMS value to average value. In case of non-sinusoidal
wave it is given by:
Form Factor =
(2.11)
2.3.4 Harmonic Power
The current and voltage are respectively given as:
i = ∑ (2.12)
10
v = ∑ (2.13)
Power contributed by harmonic components of voltage and current waveforms can
be expressed as:
Average power of harmonics of order n, Pn
= ∫
= in RMS vn RMS cos (2.14)
Where = = phase difference between harmonic component of voltage
and current waveforms of order n.
2.3.5 Total Active Power
Total active power is contributed by fundamental as well as harmonic components of
voltage and current waveform. Thus total power is written as:
p = ∑ = ∑
= i1 rmsv1 rms cos ϕ1 + i2 rmsv2 rms cos ϕ2 + i3 rmsv3 rms cos ϕ3 (2.15)
2.4 SOURCES OF HARMONICS
The main sources of harmonics in electric power systems can be categorized as:
a) Magnetization nonlinearities of transformer
b) Rotating machines
c) Arcing devices
d) Semi-conductor based power supply
e) Inverter fed A.C drives
f) Thyristor controlled reactors
g) Phase controllers
h) A.C regulators
2.4.1Magnetization nonlinearities of transformer
Transformers magnetic material characteristic is non-linear. This non linearity is the
main reason for harmonics during excitation. Sources of harmonics in transformer
may be classified into four categories as follows:
11
a .Normal Excitation: Normal excitation current of a transformer is non-sinusoidal.
The distortion is mainly caused by zero sequence triplen harmonics and particularly
the third present in the excitation current.
b .Symmetrical Over Excitation: When transformers are subjected to a rise in voltage,
the cores face a considerable rise in magnetic flux density, which often causes
considerable saturation. This saturation with symmetrical magnetizing current
generates all the odd harmonics.
c .Inrush Current Harmonics: A switched-off transformer with residual flux in the
core is re-energized, the flux density rises to peak levels of twice the maximum flux
density or more, thus producing high-ampere turns causing magnetizing currents to
reach up to 5-10 per unit of the rated value, typically known as inrush current. This
causes generation of enormous second order harmonic component in the transformer
current
d .D.C Magnetization: Under magnetic unbalance, the core contains an average value
of flux (φdc), which is equivalent to a direct component of excitation current of the
transformer which contains both odd and even harmonic components.
2.4.2 Rotating machines
Rotating machines also contribute in generation of harmonics, this maybe further
classified as:
a) Magnetic Nonlinearities of the core material causes harmonic generation
b) Non-uniform flux distribution in the air gap leads to harmonic production
c) Slots and Teeth presence changes the reluctance of magnetic flux and this
variation results in harmonics
d) Rotor Saliency also brings the variation of reluctance in the magnetic path and
reactance in electric path which contribute to harmonics generation
e) Crawling is a common problem faced by induction motors. During this fault, odd
harmonics like 5th and 7th orders appear.
f) Cogging, a problem when motor fails to start produces harmonics different from
those in the normal condition
g) Some other causes are Rotor misalignment, Mass unbalance, Fractal error and
Unsymmetrical faults.
12
2.4.3 Arcing devices
Electric Arc Furnace, Discharge type lighting, Arc welders have highly non-linear
voltage vs current characteristics. Therefore, arc ignition is equivalent to a short-
circuit with a decrease in voltage. Hence they are a major source of power system
harmonics.
2.4.4 Power supplies with semiconductor devices
Harmonics generated by such supplies include integer, inter and sub harmonics whose
magnitudes and frequencies depend upon the type of semiconductor devices used,
operating point, nature of load variation, etc.
2.4.5 Inverter Fed A.C drives
The use of switching devices like GTO, IGBT, etc. along with PWM technique has
become popular in AC Drives applications which are sources of integer as well as
fractional harmonics.
2.4.6 Thyristor controlled reactors
Different types of thyristor controlled reactors used in power system like series
controller, shunt controller, static VAR compensator (SVC), fixed capacitor thyristor
controlled reactor (FCTCR), thyristor switched capacitor thyristor controlled reactor
(TSCTCR) are sources of harmonics in power system.
2.4.7 Phase controllers & AC regulators
Phase Controller for the supply of balanced electric power and AC voltage regulators
when applied both online and offline for voltage regulation will result in harmonic
generation.
2.5 EFFECTS OF HARMONICS
Harmonics are not desirable in most applications and operations of electrical power
system; therefore it has wide adverse effects on the system. The effects of harmonics
may be classified as:
13
2.5.1 Resonance and effect on capacitor banks:
Resonance occurs when the frequency at which the capacitive and inductive reactance
of the circuit impedance are equal. At the resonant frequency, a parallel resonance has
high impedance and series resonance low impedance. Harmonic resonances create
problems in operation of power factor correction capacitors. Capacitors used for
power factor correction cause system resonances due to harmonic frequencies. This
results in excessive high current, which can produce damage to the capacitors. Change
of harmonic contents sometimes increases reactive power over permissible
manufacturer tolerances.
2.5.2 Poor damping:
In the presence of harmonics, undesirable variation of the degree of damping changes
the operating performance of different measuring and controlling instruments.
2.5.3 Effects of harmonics on rotating machines:
Harmonic voltages and currents increase losses in the stator windings, rotor circuit,
and stator and rotor lamination; resulting in overheating and efficiency reduction.
Harmonic currents present in the stator of an AC machine produce induction motoring
action (i.e. positive harmonic slips Sn), which gives rise to shaft torques in the same
direction as the harmonic field velocities in such a way that all positive sequence
harmonics will develop shaft torques aiding shaft rotation whereas negative sequence
harmonics will have the opposite effect, thus affecting the speed/torque characteristic
considerably.
2.5.4 Effects on transformer:
Harmonic Voltage increases the core losses in laminations and stresses the insulation,
while harmonic current increase copper losses. They also cause increase in core
vibrations.
2.5.5 Effects on transmission lines:
Harmonics tend to increase Skin and Proximity Effects since both are frequency
dependent. Harmonic currents reduce the power transmitting capacity by increasing
copper losses and also produce harmonic voltage drops across various circuit
impedances. As a result, a weak system of large impedance has low fault level and
14
greater voltage disturbances where as a stiff system of low impedance has high fault
level and lower voltage disturbance. Harmonic voltages reduce dielectric strength of
cables by causing an increase in dielectric losses.
2.5.6 Harmonic interference with power system protection:
Harmonics degrade the operating characteristics of protective relays. Some digital
relays and algorithms operate on sample data and zero crossing moment. Harmonic
distortion creates error on such operation. Harmonics make higher di/dt at zero
crossings and the current sensing ability of the thermal magnetic breakers and change
trip point due to extra heating in the solenoid. Current harmonic distortion affects the
interruption capability of circuit breakers and fuses.
2.5.7 Effects of harmonics on consumer equipment:
IEEE Task Force on the Effects of Harmonics on Equipment has made a wide study
on this matter. The result can be summarized as follows:
a) Television Receivers: Harmonics changes in TV picture size and brightness. Inter-
harmonics change amplitude modulation of the fundamental frequency. For
example, even a 0.5% inter harmonic level can produce periodic enlargement and
reduction of the image of the cathode ray tube.
b) Fluorescent and mercury arc lighting: Capacitors used in such lighting
applications together with the inductance of the ballast and circuit produce a
resonant frequency. It results in excessive heating and failure in operation.
Audible noise is produced due to harmonic voltage distortion.
c) Computers: Harmonics create problems in monitor and CPU operation. Harmonic
rate (geometric) measured in vacuum must be less than −3% (Honeywell, DEC) or
5% (IBM). CDC specifies that the ratio of peak to effective value of the supply
voltage must equal to 1.41±0.1.
2.6 HARMONIC INDICES
The two most commonly used indices for measuring the harmonic content of a
waveform are the Total Harmonic Distortion (THD) and the Total Demand Distortion.
15
2.6.1 Total harmonic distortion
The THD is a measure of the effective value of the harmonic components of a
distorted waveform. That is, it is the potential heating value of the harmonics relative
to the fundamental. This index can be calculated for either voltage or current:
THD=√∑ ⁄ (2.16)
Where Mh is the RMS value of harmonic component h of the quantity M.
The RMS value of a distorted waveform is the square root of the sum of the squares
as shown in Equations (2.16) and (2.17). The THD is related to the rms value of the
waveform as follows:
RMS=√∑ = M1√ (2.17)
The THD is a very useful quantity for many applications, but its limitations must be
realized. It can provide a good idea of how much extra heat will be realized when a
distorted voltage is applied across a resistive load. Likewise, it can give an indication
of the additional losses caused by the current flowing through a conductor. However,
it is not a good indicator of the voltage stress within a capacitor because that is related
to the peak value of the voltage waveform, not its heating value. The THD index is
most often used to describe voltage harmonic distortion.
Harmonic voltages are almost always referenced to the fundamental value of the
waveform at the time of the sample. Because fundamental voltage varies by only a
few percent, the voltage THD is nearly always a meaningful number.
2.6.2 Total demand distortion
Current distortion levels can be characterized by a THD value but this can often be
misleading. A small current may have a high THD but not be a significant threat to
the system.
For example, many adjustable-speed drives will exhibit high THD values for the input
current when they are operating at very light loads. This is not necessarily a
16
significant concern because the magnitude of harmonic current is low, even though its
relative current distortion is high.
Some analysts have attempted to avoid this difficulty by referring THD to the
fundamental of the peak demand load current rather than the fundamental of the
present sample. This is called total demand distortion and serves as the basis for the
guidelines in IEEE Standard 519-1992, Recommended Practices and Requirements
for Harmonic Control in Electrical Power Systems. It is defined as follows:
TDD=
√∑
(2.18)
IL is the peak, or maximum, demand load current at the fundamental frequency
component measured at the point of common coupling (PCC).
2.7 PRINCIPLES FOR HARMONICS CONTROL
Harmonic distortion is present to some degree on all power systems. Fundamentally,
one needs to control harmonics only when they become a problem. There are three
common causes of harmonic problems:
1. The source of harmonic currents is too great.
2. The path in which the currents flow is too long (electrically), resulting in either
high voltage distortion or telephone interference.
3. The response of the system magnifies one or more harmonics to a greater degree
than can be tolerated.
When a problem occurs, the basic options for controlling harmonics are:
1. Reduce the harmonic currents produced by the load.
2. Add filters to siphon the harmonic currents off the system, block the currents from
entering the system, or supply the harmonic currents locally.
3. Modify the frequency response of the system by filters, inductors, or capacitors.
2.8 WHERE TO CONTROL HARMONICS?
The strategies for mitigating harmonic distortion problems differ somewhat by
location. The following techniques are ways for controlling harmonic distortion on
both the utility distribution feeder and end user power system.
17
2.8.1 On Utility Distribution Feeders
Harmonic problems on distribution feeders often exist only at light load. The voltage
rises, causing the distribution transformers to produce more harmonic currents and
there is less load to damp out resonance. Switching the capacitors off at this time
frequently solves the problem.
Should harmonic currents from widely dispersed sources require filtering on
distribution feeders, the general idea is to distribute a few filters toward the ends of
the feeder. Figure 2.2 shows one example of a filter installed on an overhead
distribution feeder. This shortens the average path for the harmonic currents, reducing
the opportunity for telephone interference and reducing the harmonic voltage drop in
the lines. The filters appear as nearly a short circuit to at least one harmonic
component. This keeps the voltage distortion on the feeder to a minimum.
Figure 2.2
2.8.2 In End-User Facilities
When harmonic problems arise in an end-user facility, the first step is to determine if
the main cause is resonance with power factor capacitors in the facility. If this is the
case, a simple solution would be to use a different capacitor size. Installation of filters
on end-user low-voltage systems is generally more practical and economical than on
18
utility distribution systems. The criteria for filter installation are more easily met, and
filtering equipment is more readily available on the market.
2.9 USEFUL TOOLS FOR HARMONICS ASSESSMENT
The basis of all harmonic assessment still depends on the measurement of amplitude
and phase angle of the harmonics components. Different mathematical tools have
come out for this purpose. Some of them are capable of measuring both integer and
non-integer order of harmonics. Some of them are capable of measuring only integer
type of harmonics. Also, in many cases, signals could not be captured in continuous
form.To overcome these limitations modified mathematical tools have been
developed to handle discrete signals. Mathematical tools for harmonics analysis may
be in time domain, or frequency domain or both time-frequency domains.
One of old techniques used in analysis of non-sinusoidal signals is Fourier transform.
Fourier analysis has been used for power quality assessment for a long period.
It permits mapping of signals from time domain to frequency domain by
decomposing the signals into several frequency components. The transform method
suffers from limitation to handle discrete or discontinuous, multi-valued and
undefined signals which are often faced by electrical applications. In this thesis, we
have employed Fast Fourier Transform (FFT) built-in tool available in MATLAB
which can be directly applicable or after some alteration on captured discrete signals.
19
Chapter # 3
HARMONIC FILTERS
3.1 INTRODUCTION
Any combination of passive (R, L, C) and/or active (transistors, op-amps) elements
designed to select or reject a band of frequencies is called a filter. Filters are used to
filter out any unwanted frequencies due to nonlinear characteristics of some electronic
devices or signals picked up by the surrounding medium.
Filters are one of those corrective (remedial) solutions aimed at overcoming harmonic
problems and to keep them within safe limits. They provide a low impedance path or
‘trap’ to a harmonic to which a filter is tuned, hence are called tuned (resonant)
circuits. The process of tuning aims at setting the circuit to fr (resonant frequency)
where the response is or at maximum. The circuit is then said to be in state of
resonance.
There are three types of filters.
1. Passive filters
2. Active filters
3. Hybrid filters
We will be dealing with only Passive Filters as these are the main concern of this
thesis work. A short description about active and hybrid filters is also provided in
what follows:
3.2 PASSIVE FILTERS
Passive filters are basically topologies or arrangements of R, L and C elements
connected in different combinations to gain desired suppression of harmonics. They
are employed either to shunt the harmonic currents off the line or to block their flow
between parts of the system by tuning the elements to create a resonance at a selected
frequency. The also provide the reactive power compensation to the system and hence
improve the power quality. However, they have the disadvantage of potentially
interacting adversely with the power system and the performance of passive filter
depends mainly on the system source impedance. On the other hand they can be used
20
for elimination of a particular harmonic frequency, so number of passive filters
increase with increase in number of harmonics on the system. They can be classified
into:
1. Passive shunt filter
2. Passive series filter
Passive shunt filters are the main focus of study in this thesis and are discussed here in
detail while a little thought is presented on series filters.
3.2.1 Passive Shunt Filters
They are classified as shown in the figure 3.1 below:
Figure 3.1
Single Tuned Filter:
The most common type of passive filter is the single-tuned “notch” filter. This is the
most economical type and is frequently sufficient for the application. The notch filter
is series-tuned to present low impedance to a particular harmonic current and is
connected in shunt with the power system. Thus, harmonic currents are diverted from
their normal flow path on the line through the filter Notch filters can provide power
factor correction in addition to harmonic suppression. In fact, power factor correction
capacitors may be used to make single-tuned filters. They are tuned at low harmonic
frequencies. At the tuned harmonic, capacitor and reactor have equal reactance and
the filter has purely resistive impedance. A general schematic diagram of series tuned
filter is shown in the figure 3.1.
The impedance vs frequency curve of this filter is shown in Figure 3.2.
21
Figure 3.2
Double Band Pass Filters:
A double Band Pass Filter is a series combination of a main capacitor, a main reactor
and a tuning device which consists of a tuning capacitor and a tuning reactor
connected in parallel. The impedance of such a filter is low at two tuned frequencies.
Damped Filters:
They can be 1st, 2
nd, or 3
rd order type. The most commonly used is the 2
nd order. A 2
nd
order damped filter consists of a capacitor in series with a parallel combination of a
reactor and a resistor. It provides low impedance for a moderately wide range of
frequencies. When used to eliminate high order harmonics ( 17th
and above), a
damped filter is referred to as High Pass Filter, providing a low impedance for high
frequencies but stopping low ones.
Damped filters are usually tuned to hn<hr, that is 10.7, 16.5 and so on. The
Impedance Vs Frequency curve of Second-Order High Pass Filter is shown in figure
3.3
Figure 3.3
22
3.2.2 Passive Series Filter
Unlike a notch filter which is connected in shunt with the power system, a series
passive filter is connected in series with the load. The inductance and capacitance are
connected in parallel and are tuned to provide high impedance at a selected harmonic
frequency. The high impedance then blocks the flow of harmonic currents at the tuned
frequency only. At fundamental frequency, the filter would be designed to yield low
impedance, thereby allowing the fundamental current to flow with only minor
additional impedance and losses. Figure 3.4 shows a typical series filter arrangement.
Series filters are used to block a single harmonic current (such as the third harmonic)
and are especially useful in a single-phase circuit where it is not possible to take
advantage of zero-sequence characteristics. The use of the series filters is limited in
blocking multiple harmonic currents. Each harmonic current requires a series filter
tuned to that harmonic. This arrangement can create significant losses at the
fundamental frequency.
Figure 3.4
3.3 ACTIVE FILTERS
Active filters are relatively new types of devices for eliminating harmonics. They are
based on sophisticated power electronics and are much more expensive than passive
filters. However, they have the distinct advantage that they do not resonate with the
system. They can work independently of the system impedance characteristics. Thus,
they can be used in very difficult circumstances where passive filters cannot operate
successfully because of parallel resonance problems. They can also address more than
one harmonic at a time and combat other power quality problems such as flicker.
They are particularly useful for large, distorting loads fed from relatively weak points
on the power system
23
3.4 HYBRID FILTERS
Since the APFs (Active Power Filters) topologies are not cost-effective for the
application of high power because of their high rating and very high switching
frequency of PMW (Pulse Width Modulator) converters. Thus LC PPFs (Passive
Power Filters) are used for harmonic filtration of such large nonlinear loads.
However, Passive filters suffer from some shortcomings for example, the performance
of these filters is affected due to the varying impedance of the system and with the
utility system the series and parallel resonances may be created, which cause current
harmonics increase in the supply. Therefore, another solution of harmonic mitigation,
called HAPF (Hybrid Active Power Filter), has been introduced. HAPF provides the
combined advantages of APF and PPF and eliminate their disadvantages. These
topologies are cost effective solutions of the high-power power quality problems with
well filtering performance.
3.5 DESIGN STEPS OF SERIES TUNED FILTERS
In design of the filter, the proper selection of the capacitor size is very essential from
power factor point of view. A series-tuned filters is a capacitor designed to trap a
certain harmonic by adding a reactor such that XL=Xc at the frequency fn.
To design series-tuned following step are followed:
Determine the capacitor size Qc in MVAR, say the reactive power requirement of
the source.
The capacitor reactance is
(3.1)
Capacitance for filters is calculated by
(3.2)
Where n=number of filters to be designed
The resonance condition will occur when capacitive reactance is equal to
inductive reactance as:
XL=XC (3.3)
24
To trap the harmonics of order h, the reactance should be of size
(3.4)
The resistance of filter depends on the quality factor (Q) by which sharpness of
the tuning is measured.
√
(3.5)
Where Q is the quality factor and for series tuned is 30<Q≤100.
3.6 DESIGN STEPS OF 2ND
ORDER HIGH PASS FILTER
To design 2nd
order high pass filter, following step are followed:
Determine the capacitor size Qc in MVAR, say the reactive power requirement of
the source.
The capacitor reactance is
(3.6)
Capacitance for filters is calculated by
(3.7)
Where n=number of filters to be designed
The resonance condition will occur when capacitive reactance is equal to
inductive reactance as:
XL=XC (3.8)
To trap the harmonics of order h, the reactance should be of size
(3.9)
The resistance of filter depends on the quality factor (Q) by which sharpness of the
tuning is measured.
R = √
* Q (3.10)
Where Q, the quality factor is 0.5 <Q< 5.
25
3.7 QUALITY FACTOR, BANDWIDTH AND SELECTIVITY
The quality factor of a resonant circuit is defined as the ratio of reactive power of
either the inductor or capacitor to the average power of resistor at resonance.
Q
For a Series Resonant Circuit,
Qs=
=
√
(3.11)
Where XL is the inductive reactance, R is the resistance, Qs is the quality factor of
series resonant circuit and is the angular frequency that account for resonance.
Then, fS=
√ is called the resonant frequency of the series resonant circuit.
The quality factor is a measure of the sharpness of the tuning frequency. It is
determined by the resistance value. The effect of Q factor on the response curve is as
shown in the figure 3.5
Figure 3.5
In terms of Qs, if R is large for the same XL, then Qs is less. A small Qs, therefore, is
associated with a resonance curve having a large bandwidth and a small selectivity
while a large Qs indicates otherwise.
The selectivity indicates that one must be selective in choosing the frequency to
ensure that it is in the bandwidth. The smaller the bandwidth, the higher is its
selectivity as shown in the figure 3.6
26
Figure 3.6
The larger value of the quality factor gives the best reduction in harmonic reduction.
However, it is necessary to take care of the harmonic frequencies because these
harmonic current frequencies will also follow the least impedance path. These
currents cause the increased power loss. Therefore it is necessary to perform the
computer based harmonic simulation for analyzing the performance of the filters.
The Bandwidth is related o the Quality Factor as:
BW=
or (3.12)
BW= f2-f1 =
(3.13)
Where f1 and f2 are the cutoff frequencies or half power frequencies which specify the
range of Band Width
27
Chapter # 4
STANDARD LIMITS OF HARMONIC DISTORTION
4.1 INTRODUCTION
The limits of allowable voltage and current harmonics distortion set by IEEE and IEC
have been presented in this chapter which are just based on the personal experiences
and involvement of Power Quality analysts in harmonic analysis research. These
standards provide guidelines for power quality usages and practices.
4.2 VOLTAGE HARMONIC DISTORTION LIMITS
Bus voltage at PCC Individual Vh , % Voltage THD , %
V<69KV 3.0 5.0
69≤V<161KV 1.5 2.5
V≥161KV 1.0 1.5
Table 4.1- ANSI/IEEE 519 voltage distortion limits
Odd harmonics Even harmonics Triplen harmonics
H % Vh H % Vh H % Vh
5 6 2 2 5
7 5 4 1 9 1.5
11 3.5 6 0.5 15 0.3
13 3 8 0.5 15 0.3
177 2 10 0.5 ≥21 0.2
19 1.5 ≥12 0.2
23 1.5
Table 4.2-IEC 61000-2-2 voltage harmonic distortion limits in public low-voltage
network
28
Even harmonics Triplen harmonics
H % vh H % Vh H % Vh
5 6 2 2 3 5
7 5 4 1 9 1.5
11 3.5 6 0.5 15 0.3
13 3 8 0.5 15 0.3
17 2 10 0.5
19 1.5 ≥12 0.2
23 1.5
25 1.5
≥29 x
Table 4.3- IEC 61000-2-4 voltage harmonic distortion limits in industrial plants
Odd harmonics Even harmonics Triplen harmonics
H % , Vh H % , Vh H %, Vh
5 8 2 3 3 6
7 7 4 1.5 9 2.5
11 5 ≥6 1 15 2
13 4.5 21 1.75
17 4 ≥27 1
19 4
23 3.5
Table 4.4-IEC 61000-22-4 class 3
4.2 CURRENT HARMONIC DISTORTION LIMITS
H 3 5 7 9 11 13 15…………39
Max Ih 2.3 1.14 0.77 0.40 0.33 0.21 0.15……….15 ∕ h
Equipment input current ≤ 16 A per phase
Table 4.5-IEC 61000-3-2 maximum permissible harmonic currents for class D
equipment
29
ISC/IL Ih / IL , % ---- general distribution systems (120V-69KV) TDD
h<11 11≤h<17 17≤h<23 23h≤h<35 h≥35
<20 4.0 2.0 1.5 0.6 0.3 5
20-50 7.0 3.5 2.5 1.0 0.5 8
50-
100
10 4.5 4.0 1.5 0.7 12
100-
1000
12 5.5 5.0 2.0 1.0 15
>1000 15 7.0 6.0 2.5 1.4 20
ISC/IL Ih / IL , % ---- general sub transmission systems (69-161KV) TDD
h<11 11≤h<17 17≤h<23 23≤h<35 h≥35
ISC/IL Ih / IL , % ---- general transmission systems (>161KV) TDD
% h<11 11≤h<17 17≤h<23 23≤h<35 h≥35
<50 2.0 1.0 0.75 0.3 0.15 2.5
≥50 3.0 1.5 1.15 0.45 0.22 3.75
Table 4.6- IEEE 519 current distortion limits.
30
Chapter # 5
MATLAB SIMULATION & RESULTS
5.1 POWER CONVERTERS HARMONIC BEHAVIOUR
In almost all electronic equipment, the devices directly connected with the power
network are converters; their characteristics determine the harmonic behavior of the
complete system and the impact on power supply depends on the rectifier topology
and the type of power devices employed.
The characteristic harmonic components of the current pulses supplying converters
have harmonic orders n, such as n = k · p±1, where k = 1, 2, 3, 4… and p is the
number of converter arms (pulse number).
Thyristor rectifiers have the advantage of a relatively simple control system over
uncontrolled rectifiers and can be found in D.C drives or other many applications. The
harmonics generated by a phase-controlled rectifier on the A.C side may be calculated
as for uncontrolled rectifiers, depending on pulse number.
For example, for six-pulse rectifiers, the main harmonic components are the fifth and
the seventh. However, in this case, new even and odd harmonics, referred to as non-
characteristic harmonics, of low amplitudes, are produced; on the other hand, the
amplitudes of the characteristic harmonics are modified by several factors including
asymmetry, inaccuracy in thyristor firing times, switching times, imperfect filtering.
A displacement of the harmonics as a function of the thyristor phase angle may also
be observed as shown in the figure 5.1 below:
Figure 5.1
31
Three-phase electronic power converters differ from single-phase converters mainly
because they do not generate third-harmonic currents as shown in the figure 5.2 for a
three phase inverter circuit. This is a great advantage because the third-harmonic
current is the largest component of harmonics. However, they can still be significant
sources of harmonics at their characteristic frequencies.
Figure 5.2
5.2 HARMOINIC ANALYSIS OF THREE PHASE 12 PULSE AC-DC
CONVERTER
In this work, three-phase ac to dc converter has been simulated with and without
passive shunt filters using MATLAB/SIMULINK environment. This system is
analyzed without and with passive filters using Total Harmonic Distortion as an
index.The circuit parameters used in simulation are presented in table below:
Supply Voltage 220 V RMS
Source Inductance 1.06mH
Load (Resistive) 100 ohms
Transformer (three winding) Yg/y/d1, 1200 VA, 220V/100V/100V
Table 5.1
The system considered for harmonic analysis here consists of a three phase converter
consisting of two 6 pulse bridges modeled to work as an uncontrolled rectifier. The
schematic of the system is shown in the figure 5.3.
32
Figure 5.3
The circuit response without filters is demonstrated in what follows. The figure 5.4
and 5.5 shows three phase supply voltage and current respectively. The FFT analysis
windows of VS and Is are given in figure 5.6 and 5.7 which shows the percentage
harmonics in the spectrum before the filters are incorporated. Since the waveforms are
distorted, it implies the presence of harmonics.
Figure 5.4
33
Figure 5.5
Figure 5.6
Figure 5.7
Without passive filters the total harmonic distortion of the current is above the range
specified by the power quality standards. To follow the recommended IEEE 519
power harmonic standards the total harmonic distortion must be less than 5%. This
34
can be obtained by connecting the passive filters to the system. For reducing the THD
below 5% passive filters have been designed. There are three filters used, two of
which are single tuned at 11th
and 13th
harmonic and the other is high pass filter for
high order harmonics. The filters specifications for each type of filter are shown in the
below:
Harmonic Order Capacitance (µF) Inductance(mH) Resistance
11th
165.1 50.71 0.04375
13th
28.5 2.1036 0.21478
Higher order 39.3 1.5535 7.4775
Table 5.2
The Q Factor for the filters is chosen to be 40. The Impedance VS Frequency curve
for the desired response is as shown in the figure 5.8
Figure 5.8
After connecting the filters the three-phase supply currents become near to sinusoidal
and harmonics are decreased below 5%. The simulation results are presented in
Figure 5.9 and 5.10 for the voltage and current on the AC side. The FFT analysis
windows of the source voltage and current are given in figure 5.11 and 5.12
respectively which shows the percentage harmonics in the spectrum with the filters
incorporated.
35
Figure 5.9
Figure 5.10
Figure 5.11
36
Figure 5.12
5.3 HARMONIC ANALYSIS OF THREE PHASE INVERTER
In this analysis, a three phase inverter supplying a three phase resistive load has been
investigated with and without passive series filters and the effects on parameters on
AC side has been analyzed with THD as an index.
The inverter model along with circuit parameters are presented in the table below:
Vdc 678V
Three Phase Load (Resistive) 53kW
Table 5.3
Figure 5.13
37
Figure 5.14
The circuit waveforms without filters for the voltage and current on AC side along
with their FFT analysis are shown respectively in the figures below:
Figure 5.15
38
Figure 5.16
When LC series filter is employed, it is observed that THD becomes less than 5% and
the waveforms become near to sinusoidal. The model is as shown in the figure. Its
waveforms along with FFT analysis are also shown.
Figure 5.17
The values of filter’s inductance and capacitance are :
Capacitance (µF) Inductance (mH)
20 10.33
39
Figure 5.18
Figure 5.19
40
Figure 5.20
Figure 5.21
41
Chapter 5
Conclusions
Thus passive harmonic filters are an effective, easy and economical option to counter
the issue of harmonics arising in small and large scale power systems or networks
involving non-linear loads. However passive filters suffer from the following
shortcomings.
More number of filters is required for mitigating more harmonic orders. This
might increase the initial capital cost.
They are characterized by sharp resonant operating points which might sometimes
cause damage to the apparatus.
Flexibility in control cannot be achieved using passive filters but on the contrary
power systems are dynamic in nature and hence there is a need for flexible and
automated control.
But nevertheless passive filters are always looked upon as a viable choice from
economical point of view. They are also found to be effective when the system is
affected by specific order harmonics to a great extent.
Moreover, while dealing with Fast Fourier Transform, we concluded that:
FFT does not allows analysis of fractional harmonics
FFT leads to incorrect results if signal contains noise or dc component of decaying
magnitude
Active harmonic filters can also be used along with passive filters as hybrid filters to
compensate the shortcomings of passive harmonic filters. They are being developed to
alleviate the disadvantage of conventional passive filters, namely:
The filtering characteristics being dependent on the source impedance
Aggravating the impedance below the lowest tuned harmonic
Being inadequate for filtering non-characteristic harmonics ( different from the
filters tuned frequency), such as those produced by cycloconverters
42
REFERENCES:
I. “Harmonics Mitigation of Industrial Power System Using Passive Filters” by
Zubair Ahmed Memon, Mehran University Research Journal of Engineering &
Technology, Volume 31, No. 2
II. “Design of Three-Phase Hybrid Active Power Filter for Compensating the
Harmonic Currents of Three-Phase System” by Zubair Ahmed Memon, Mehran
University Research Journal of Engineering & Technology, Volume 31, No. 2
III. Electric Power Quality by Surajit Chattopadhyay ,Madhuchhanda Mitra, Samarjit
Sengupta
IV. Bollen, M.H.J.: Understanding Power Quality Problems-Voltage Sags and
Interruptions. IEEE Press, NewYork (2001)
V. Electrical Power Systems Quality, by Roger C. Dugan/ Mark F.
McGranaghan/Surya Santoso, Mcgraw Hill Pulishers.
VI. Power System Harmonics (Filter Designs), George J. Wakileh
VII. Handbook of Power Quality, Angelo Baggini University of Bergamo, Italy