icone20-power2012 july 30 - august 3, 2012, anaheim
TRANSCRIPT
SUBSYNCHRONOUS RESONANCE AND TORSIONAL EFFECTS ON A STEAM TURBINE GENERATOR IN TRANSMISSION SYSTEMS WITH SERIES CAPACITOR COMPENSATION
K.R. Mutama Newmont Nevada Energy
Investments Elko, Nevada, USA
J. Seeliger Newmont Nevada Energy
Investments Elko, Nevada, USA
D.H. Baker GE Energy
Schenectady, New York, USA
R. D’Aquila GE Energy
Schenectady, New York, USA
B. Fitzgerald GE Energy
Schenectady, New York, USA
C. Wegner GE Energy
Schenectady, New York, USA
R.M. Staulters GE Energy
Schenectady, New York, USA
ABSTRACT Turbine-generators which connect to transmission systems
with series capacitor compensated lines can experience
problems with the torsional oscillations of the shaft interacting
with the electrical oscillations of the series capacitors and
transmission system inductance. This resonant interaction is
called Subsynchronous Resonance (SSR) since it involves
torsional and electrical oscillations which are below the
synchronous operating frequency of the power system. The
transmission lines near the Newmont TS Power Plant will soon
have series capacitors installed. Modeling studies based on
calculated torsional frequencies and estimated torsional
damping showed that the turbine-generator could have
instabilities of the torsional oscillations under some operating
conditions. After the modeling studies were completed, actual
tests on the steam turbine generator were conducted to measure
the frequency and mechanical damping of the torsional
oscillations. Field measurements validated modeling studies
and showed the SSR risk may be higher than originally
estimated. As a result of these investigations, a torsional stress
relay is being installed to protect the unit from subsynchronous
torsional effects of the series capacitors. The torsional stress
relay will trip the unit if damaging torsional oscillations or
torsional instabilities occur.
INTRODUCTION
Numerous high voltage transmission projects are being
planned and developed throughout all of the North American
grid. The need for many of these transmission lines is driven
by new generation projects, particularly renewable generation.
In most cases, the source of generation is remote from load
centers and requires long distance transmission lines.
Compensating the long transmission lines with series capacitors
is a very cost-effective way to increase transmission capability
and minimize the total amount of new transmission required.
A significant side effect of series capacitors is the
introduction of series-resonant conditions in the grid at
frequencies below synchronous, i.e. subsynchronous.
Conventional power generation can interact adversely with
these series resonances, often resulting in destabilization or
excessive stimulation of torsional vibrations within the turbine-
generator set. This effect has been termed ―Subsynchronous
Resonance‖ (SSR) [1].
In 1970, and again in 1971, the Mohave generator in
Nevada, USA experienced a gradually growing torsional
vibration that eventually led to a fracture of the shaft section
between the generator and the rotating exciter [2,3].
Investigations uncovered an electrical resonance coincident
with the frequency of the second torsional vibration mode of
the turbine-generator. Over the past 35 years the industry has
learned to manage SSR, with specialized analysis often
Proceedings of the 2012 20th International Conference on Nuclear Engineering collocated with the
ASME 2012 Power Conference ICONE20-POWER2012
July 30 - August 3, 2012, Anaheim, California, USA
1 Copyright © 2012 by ASME
ICONE20-POWER2012-55029
required to finalize system design and special torsional
protection equipment applied to machines with potential
exposure.
NOMENCLATURE SSR – Subsynchronous Resonance
TSR – Torsional Stress Relay
FFT – Fast Fourier Transform
kV – kiloVolts of the transmission system
HP/IP – combined High and Intermediate Pressure Turbine
LP – Low Pressure Turbine
fo – operating frequency of the power grid
fe – frequency of electrical system oscillation
fm – frequency of torsional system oscillation
NEWMONT TS POWER PLANT The Newmont TS power plant is a 200 MW plant located
in Northern Nevada. The turbine and generator were
manufactured by Toshiba. The transmission system around
Newmont is shown in Figure 1. The Newmont generator is
connected by a 120 kV transmission line to the Falcon
substation. Three other 120 kV transmission lines and one
120/345 kV transformer are connected to the Falcon 120 kV
substation. The Falcon 345 kV bus has lines to Valmy and
Gondor. A new substation (Robinson) has been constructed
between Falcon and Gondor. Robinson has a 345/500 kV
transformer and a 500 kV line going south to the Harry Allen
substation (north of Las Vegas).
To increase the power transfer capability of the 345 kV
transmission line between Falcon and Robinson, series
capacitors are being installed at each end of the line. At 60 Hz,
these series capacitors have a reactance that is a negative 70%
of the reactance of the transmission line inductance at 60 Hz.
The result is the line only appears to have 30% of its original 60
Hz reactance. This lower effective reactance allows a larger
power flow along the line without reducing the transient
stability of the power system.
Newmont Generator
Falcon 120
Falcon 345 kV Robinson 345
Robinson 500
Gondor 345
Valmy 345
Harry Allen 500
Figure 1 Transmission System Around Newmont
The Newmont TS Power Plant turbine is composed of a
combined High and Intermediate Pressure (HP/IP) turbine and
a single Low Pressures (LP) turbine. The generator and a
rotating exciter complete the shaft system. These four elements
have rotating inertia and the shafts connecting them have
torsional stiffness. This results in torsional modes of oscillation
for the shaft system. The rotor inertias and shaft torsional
stiffnesses of the torsional system are given in Table 1. This
data was supplied by the turbine-generator manufacturer.
The four inertias and three shaft stiffnesses of the torsional
system result in calculated torsional modes of oscillation at the
frequencies given in Table 2. There are two frequencies (24.0
and 34.3 Hz) below the 60 Hz operating frequency of the unit
and these are called subsynchronous frequencies. The third
torsional mode at 78.5 Hz is above the operating frequency.
Mode shapes for the torsional oscillations are also given in
Table 2 and shown graphically in Figure 2. The mode shapes
show relative motion of each turbine-generator section and are
normalized on the section with the highest motion. For
example, the exciter has the greatest motion for torsional mode
1. The HP/IP turbine will oscillate at 72% of the magnitude of
oscillation of the exciter but in the opposite direction. This
results in a slight twisting of the shaft from one end to the other
at mode 1 torsional frequency (24 Hz). For mode 2, the 34.3
Hz oscillations would result in the most motion of the HP/IP
turbine with the exciter moving at 13% of the magnitude and in
the same direction, but the LP turbine would be moving in the
opposite direction at 18% of the magnitude. Mode 3 at 78.5 Hz
has motion mostly in the exciter inertia.
Table 1 Rotor Inertias and Torsional Stiffnesses (Metric Units)
Inertia Name Inertia Constant WR
2 (J)
kg-m2
Spring Constant (K)
kg m/rad
HP/IP 1275 (J1)
5.12×106
(K12)
LP 9425 (J2)
7.26×106
(K23)
Generator 4050 (J3)
3.00×106
(K34)
Exciter 125 (J4)
Table 2 Torsional Mode Frequencies and Mode Shapes
Mode 1 2 3
Frequency (Hz) 24.0 34.3 78.5
Location Mode Shape (Normalized Amplitude)
HP/IP -0.7191 1.0000 -0.0002
LP -0.3042 -0.1816 0.0011
Generator 0.9035 0.1038 -0.0333
Exciter 1.0000 0.1294 1.0000
2 Copyright © 2012 by ASME
SUBSYNCHRONOUS RESONANCE With no series capacitors, unit torsional oscillations are
dormant or have little or no magnitude. Torsional oscillations
can be excited by operations in the transmission grid such as
line switching or faults. The mechanical damping, though
small, results in these oscillations being damped in five to 10
seconds. Mechanical damping is higher at rated load in
torsional modes which have significant motion in the turbine
elements. This is due to steam flow for steam turbines (or gas
flow for gas turbines).
Figure 2 Newmont Torsional Mode Shapes
Unless repeated transmission grid events occur close together
(such as high speed reclosing of transmission lines following
faults) the torsional oscillations do not reach an amplitude that
results in shaft fatigue.
However, the presence of series capacitors in the
transmission lines will result in an electrical system resonance.
For a simple radial system the resonance would be at an
electrical frequency corresponding to 𝑓𝑒 = √𝑋
𝑋 , where XC is
the 60 Hz reactance of the capacitor and XLT is the 60 Hz
reactance of the total series inductance of the generators,
transformers, and transmissions lines. Since XC would be less
than XL of just the transmission line, the electrical frequency
would be less that 60 Hz or the system operating frequency, fo.
Subsynchronous currents at frequency fe, flowing in the
generator stator windings will produce an electrical torque
component at frequencies fo-fe and fo+fe since electrical torque
is produced by flux times current and the stator flux is changing
at frequency fo. Conversely, a torsional oscillation at frequency
fm will produce stator voltage components at fo-fm and fo+fm
since stator voltage is the product of speed times the stator flux.
If fe is close to fo-fm, an interaction occurs where the stator
voltages produce stator currents and the stator currents produce
electrical torque and the electrical torque produces speed
variations which then produce stator voltages. This feedback
process can produce unstable oscillations. This is a resonant
condition of the interaction of two closely corresponding
system modes of oscillation. Since these are frequencies below
synchronous operating frequency, the process has been given
the name Subsynchronous Resonance [1] or SSR. The
interplay between the electrical and torsional systems that
produce unstable oscillations has been further identified as
torsional interaction in the definitions. Since the unstable
oscillations are most evident in the shaft torsional system, they
are often referred to as unstable torsional oscillations.
Another aspect of SSR is shaft torque amplification where
the torsional oscillations following a system disturbance are
larger in the series compensated system even if they are still
stable.
TORSIONAL TESTS AT NEWMONT Initial SSR analysis of the Newmont TS plant was
performed using the calculated torsional frequencies listed in
Table 2, and estimated torsional damping. This analysis
showed a potential for unstable SSR conditions.
Analytical torsional frequency estimates can have an
uncertainty of up to a few Hz and mechanical damping cannot
be calculated. The authors experience has shown that calculated
torsional frequencies are within 1 Hz of measured for a large
percentage of tested units. However, errors in calculated
frequency of 2 Hz or more have been observed. Therefore,
when analysis indicates that SSR may be a potential concern,
field testing may be performed to confirm the findings. Testing
of the torsional frequencies and torsional damping at Newmont
was performed during April 2011.
The speed of the turbine generator was measured from a
front standard toothed wheel. The torsional frequencies can be
measured during normal operation of the unit by sampling a
long time period and performing a fast Fourier transform (FFT)
of the change in speed as shown in Figure 3. The
subsynchronous torsional frequencies were measured at
Newmont operating at full load as 24.3 and 33.5 Hz. This is
0.3 and 0.2 Hz higher than the calculated frequencies.
Torsional damping was measured by stimulating the
torsional oscillations via transmission line switching (out and
then back in), unit tripping at low load and unit
synchronization.
The results of a synchronizing event are shown in Figure 4.
The TWIB2 signal is the raw measurement of unit speed
deviation (0 corresponds to synchronized speed). The bottom
3 Copyright © 2012 by ASME
trace shows the TWIB signal filtered to torsional mode 1 at
24.3 Hz.
The damping is measured by performing an FFT of the
speed signal as shown in Figure 5. The top trace shows the
magnitude of a 24.3 Hz signal versus time and the bottom trace
the log of the magnitude versus time. The slope of the line
fitting the log magnitude corresponds to damping. The on line
damping constant (σ) and damping ratio () measured is σ = -
0.107 sec-1
(=0.00070).
Figure 3 FFT Measurement of Torsional Oscillations
Figure 4 Mode 1 Response to Unit Synchronization
Unit synchronization immediately followed by a reopening
the generator breaker but keeping the turbine operating allowed
the no load mechanical damping to be measured. These values
are:
Mode 1 σNo Load = -0.009 sec-1
(=0.000059)
Mode 2 σNo Load = -0.014 sec-1
(=0.000067)
Figure 5 Measurement of Torsional Damping
Testing when synchronizing and remaining on line gives a
combined mechanical and electrical damping effect on the
torsional oscillations. Taking the difference from on line to off
line gives the electrical contribution. This is then subtracted
from the full load damping measurements to get the full load
mechanical damping. These values are:
4 Copyright © 2012 by ASME
Mode 1 σFull Load = -0.045 sec-1
(=0.00029)
Mode 2 σFull Lload = -0.221 sec-1
(=0.00105)
These values are used in the plots of electrical damping in
the following section.
SSR ANALYSIS FOR NEWMONT One way of analyzing SSR stability is to calculate the
damping torque. This is the real part of the transfer function
from rotor speed to electrical torque modeling the electrical
portion of the generator and the transmission system to which it
is connected. This analysis includes the integral of rotor speed
to rotor angle with respect to the rest of the electrical system.
This calculation can be made by eigenvalue analysis and
transfer function calculation. Methods have also been
developed to calculate damping torque by combining frequency
scans at the two complementary frequencies of fo-fm and fo+fm
[4,5].
A torsional mode of oscillation can be modeled by the
―modal oscillator‖ as shown in Figure 6. The generator speed
(g) and rotor angle (g) are the sum of the modal speeds and
angles (including a rigid body mode) with a factor (QGi) for the
generator location of the mode shape factor for the ―i‖th
torsional mode. Through the electrical system calculations
speed (and angle) produce the electrical torque. The electrical
torque is applied back to the modal oscillator with the same
factor (QGi). Parameters of the modal oscillator are the modal
inertia (Jni), the modal frequency (fni), and the mechanical
damping (mi), all for the ―i‖th torsional mode.
Modulating speed (and hence angle) as a function of
frequency produces ―damping torque‖ (De(f)) as the real part of
the transfer function and ―synchronizing torque‖ as the
imaginary part. The mode shape factor squared times the
damping torque at the torsional frequency is a damping
contribution. The value of (QGi)2
*De(fni) gives the electrical
system damping contribution and 2*mi gives mechanical
damping contribution. When the electrical damping
contribution is negative and its magnitude exceeds the
mechanical damping contribution, instability occurs.
1
Jni
QXi
QTi
1s
2mi
1s
(2fni
)2
QGi
QGi
Te
Tex
Tm
ni
QGi
G
Other
Modes
Other
Modes
G
+--
-
Te
G(f) = D
e(f) -j
Ke(f)
2f
-
Figure 6 Modal Oscillator Representation of Torsional
Vibration Mode
The damping torque calculated for Newmont is shown in
Figure 7. Sixteen cases are plotted for all combinations of lines
in and out for the three 120 kV lines out of the Falcon
substation and the 345 kV line to Valmy from Falcon. Two ―I-
bars‖ are also plotted which show the subsynchronous torsional
frequencies. The top of the ―I-bar‖ corresponds to no load
mechanical damping and the bottom of the ―I-bar‖ to full load
mechanical damping. The cases generally fall into two groups
depending upon whether the line from Falcon to Valmy is in or
out of service. With the Falcon to Valmy line in service, there
is a negative dip in the damping torque around mode 1 torsional
frequency (24.3 Hz). With the Falcon to Valmy line out of
service, there is a much larger dip in damping torque around the
mode 2 torsional frequency (33.5 Hz).
Mode 1 would be unstable for all load conditions with the
Falcon to Valmy line in service since the negative damping
torque exceeds the mechanical damping.
Reducing the series compensation to 60% of the line
impedance would solve the SSR problems as shown in Figure 8
except for possibly at very light load conditions following
synchronization with multiple lines out of service. Torsional
protection of the unit for these conditions was considered
necessary.
Figure 7 Damping Torque for 70% Compensation
TORSIONAL STRESS RELAY If a turbine-generator has torsional problems due to SSR
(or interactions with nearby large power electronic converters,
steel mill arc furnaces, etc.) then torsional protection should be
considered to trip the unit during SSR events before significant
damage occurs. GE's protection offering is called the Torsional
5 Copyright © 2012 by ASME
Stress Relay (TSR). Newmont's SSR problems are severe
enough to justify a TSR and one will be installed in the spring
of 2012.
The TSR measures the shaft speed at one or two points
along the shaft as necessary to measure all subsynchronous
torsional frequencies that are to be protected. The signals are
then processed to separate the oscillations of the different
modes and determine their magnitude. The speed measurement
of the shaft for each mode is correlated to the turbine-generator
shaft section which is most sensitive to the modal oscillations.
Figure 8 Damping Torque for 60% Compensation
Based upon shaft fatigue curves of the correlated shaft, a
cumulative time inverse curve is used to determine when to trip
the turbine-generator due to excessive torsional oscillations.
Alarms are also given for low, medium, and high level torsional
oscillations. An instability trip is also incorporated to trip the
unit sooner if instability is determined. The trip time versus
torsional amplitude for Newmont mode 1 is given in Figure 9.
In addition to the generator trip contact, a line/aux trip output
contact is provided which may be used in some special
applications.
Figure 9 Newmont TSR Protective Curve for Mode 1
CONCLUDING REMARKS Subsynchronous resonance studies were conducted at the
Newmont TS Power Plant which will soon have series
capacitors installed on nearby transmission lines. Modeling
studies based on calculated torsional frequencies and estimated
torsional damping showed that the turbine-generator could have
instabilities of the torsional oscillations under some operating
conditions. Calculated torsional frequencies were in close
agreement with the measured frequencies of 24.3 and 33.3 Hz.
Mechanical damping of the torsional oscillations were also
measured by stimulating the torsional oscillations via
transmission line switching, unit tripping at low load and unit
synchronization. As a result of these studies a torsional stress
relay is being installed to protect the unit from subsynchronous
and torsional effects of the series capacitors. The torsional
stress relay will trip the unit if damaging torsional oscillations
or torsional instabilities occur.
Turbine-generators which are connected to series
compensated transmission lines need to be evaluated for
potential subsynchronous resonance. Studies must be
performed to evaluate SSR risk and potential solutions.
Torsional testing may also be required to measure torsional
frequencies and damping. In cases like Newmont, where there
is a risk of unstable SSR conditions, protection is needed. In
addition, SSR mitigation might be needed if 70% series
compensation is installed on the Falcon-Robinson transmission
line. The SSR risk will need to be re-evaluated as changes are
made to the transmission grid.
ACKNOWLEDGMENTS The authors would like to thank Newmont Nevada Energy
Investments for their permission to publish the work. The
authors would like to acknowledge George Zielinski, Dan
Leonard and Richard Piwko of GE Energy for their
involvement in torsional testing and TSRs. The authors would
also like to thank engineers at NV Energy during the execution
of this project for their cooperation and collaboration.
6 Copyright © 2012 by ASME
REFERENCES [1] ―Proposed Terms and Definitions for Subsynchronous
Oscillation,‖ IEEE Subsynchronous Resonance Working
Group, IEEE Trans. on Power Apparatus and Systems. Vol.
PAS-99, No. 2, Mar-April 1980, pp. 506-511.
[2] ―Experience With 500-kV Subsynchronous Resonance and
Resulting Turbine Generator Shaft Damage at Mohave
Generating Station,‖ M. C. Hall, D. A, Hodges, IEEE PES
Special Publication 76 CII l066-0-PWR, pp. 22-29.
[3] ―Results of the Subsynchronous Resonance Tests at
Mohave,‖ D. N. Walker, C. E, J. Bowler, R. L. Jackson, D.
A. Hodges, IEEE Trans. on Power Apparatus and Systems.
Vol. PAS-94, No. 5, Sept/Dec. 1975, pp. 1878-89.
[4] ―Understanding Subsynchronous Resonance,‖ C. E. J.
Bowler, IEEE PES Special Publication 76CH 1066-0-
PWR, pp. 66-73.
[5] ―Use of Frequency Scanning Techniques for
Subsynchronous Resonance Analysis,‖ R. G. Farmer and
B. L. Agrawal, IEEE Power Apparatus and Systems, Vol.
PAS—98, No. 2, March—April 1979, pp. 341—348.
7 Copyright © 2012 by ASME