MAHARASHT Subject Code: 12231 Important Instruction to examin 1) The answers should be model answer scheme. 2) The model answer and th assess the understanding 3) The language errors su importance.(Not applicable 4) While assessing figures, figure. The figures drawn credit for any equivalent fi 5) Credits may be given step values may vary and the answer. 6) In case some questions answer based on candida 7) For programming langua equivalent concept. Q.1 a) Attempt any Three of t i) Define the terminologies 1) Safety: The meaning o The any method or tec is called as safety. OR The preventive measur safety. Safety 2) Hazard: Hazard is a prob Hazard is a potentia accident. OR TRA STATE BOARAD OF TECHNICAL EDU (Autonomous) (ISO/IEC-27001-2005 Certified) SUMMER – 13 EXAMINATION Model Answer ners: examined by key words and not as word-t he answer written by candidate may vary but g level of the candidate. uch as grammatical, spelling errors shou e for subject English and Communication Sk examiner may give credit for principle com by candidate and model answer may vary. igure drawn. p wise for numerical problems. In some cases ere may be some difference in the candidat credit may be given by judgment on part ate understands. age papers, credit may be given to any ot the following used in: (Note : OR means any one statem (Eac of the term safety is being safe, not being dang chnique or process which can minimize unwan res which are taken to avoid small or big acci Risk 1 α bable or possible cause of an accident. OR al condition a waiting to be converted in to an UCATIOD Page No: 1 of 39 to-word as given in the the examiner may try to uld not be given more kills) mponents indicated in a The examiner may give s, the assumed constant te’s answers and model of examiner of relevant ther program based on 12 Marks ment expected) ch Definition 1 Mark) gerous or in danger OR nted events or accidents idents is known as n unwanted event or

Upload: vannhu

Post on 01-Sep-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

Important Instruction to examiners

1) The answers should be examined by key words and not as wordmodel answer scheme.

2) The model answer and the answer written by candidate may vary but the examiner may try to assess the understanding

3) The language errors such as grammatical, spelling errors should not be given more importance.(Not applicable for subject English and Communication Skills)

4) While assessing figures, examiner may give credit for principle components infigure. The figures drawn by candidate and model answer may vary. The examiner may give credit for any equivalent figure drawn.

5) Credits may be given step wise for numerical problems. In some cases, the assumed constant values may vary and theranswer.

6) In case some questions answer based on candidate understands

7) For programming language papers, credit may be given to any equivalent concept.

Q.1 a) Attempt any Three of the following

i) Define the terminologies used in

1) Safety:

The meaning of the term safety is being safe,

The any method or technique or process which can minimize unwanted events or accidents

is called as safety. OR

The preventive measures which are taken to avoid small or big accidents is known as

safety. Safety

2) Hazard:

Hazard is a probable or possible cause of an accident.

Hazard is a potential condition a waiting to be converted in to an unwanted event or

accident. OR

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

to examiners:

The answers should be examined by key words and not as word-to

The model answer and the answer written by candidate may vary but the examiner may try to assess the understanding level of the candidate. The language errors such as grammatical, spelling errors should not be given more

(Not applicable for subject English and Communication Skills)While assessing figures, examiner may give credit for principle components infigure. The figures drawn by candidate and model answer may vary. The examiner may give credit for any equivalent figure drawn. Credits may be given step wise for numerical problems. In some cases, the assumed constant values may vary and there may be some difference in the candidate’s answers and model

credit may be given by judgment on part of examiner candidate understands.

For programming language papers, credit may be given to any other program based on

of the following

Define the terminologies used in: (Note : OR means any one statement expected)

(Each Definition 1 Mark)

The meaning of the term safety is being safe, not being dangerous or in danger

The any method or technique or process which can minimize unwanted events or accidents

The preventive measures which are taken to avoid small or big accidents is known as

Risk

Hazard is a probable or possible cause of an accident. OR

Hazard is a potential condition a waiting to be converted in to an unwanted event or

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 1 of 39

to-word as given in the

The model answer and the answer written by candidate may vary but the examiner may try to

The language errors such as grammatical, spelling errors should not be given more (Not applicable for subject English and Communication Skills)

While assessing figures, examiner may give credit for principle components indicated in a figure. The figures drawn by candidate and model answer may vary. The examiner may give

Credits may be given step wise for numerical problems. In some cases, the assumed constant e may be some difference in the candidate’s answers and model

on part of examiner of relevant

other program based on

12 Marks

(Note : OR means any one statement expected)

(Each Definition 1 Mark)

not being dangerous or in danger OR

The any method or technique or process which can minimize unwanted events or accidents

The preventive measures which are taken to avoid small or big accidents is known as

Hazard is a potential condition a waiting to be converted in to an unwanted event or

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

The things that arises wit

3) Authority :

The person who has power to give orders & make others to obey the some is called as

authority.

4) Responsibility:

The meaning of responsibility is being responsible or accountable for ev

which are undergoes activities under the plant in charge.

ii) Explain why testing is carried out on machines or equipments.

Due to following reason testing is carried out on machines or equipments

Expected – 1 Mark each)

1) Testing of electrical machine/ equipment is done to confirm whether the performance is

as per design data or not

2) It is done at manufacture’s end & also by consumer

3) Variation in the actual values & designed values must be within tole

specified by ISS (Indian Standards

4) If the variations in results are not within tolerance limit it is necessary to modify design

& material used.

5) Objectives of testing

6) Testing in all respect is also required when a new design or modified

check whether the new product works as per the revised designed or not.

7) Testing of equipment/machinery is also done after major maintenance of equipment.

8) Testing is necessary to avoid

1) Due to testing it confirms

data or not.

2) It verifies the actual values during testing and values specified by ISS

3) Testing verifies the difference between actual values & design values are whether within

permissible limits or not.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

The things that arises without planning or random

The person who has power to give orders & make others to obey the some is called as

The meaning of responsibility is being responsible or accountable for ev

which are undergoes activities under the plant in charge.

Explain why testing is carried out on machines or equipments.

Due to following reason testing is carried out on machines or equipments

1 Mark each)

cal machine/ equipment is done to confirm whether the performance is

as per design data or not.

It is done at manufacture’s end & also by consumer before commissioning.

Variation in the actual values & designed values must be within tole

(Indian Standards Specification)

the variations in results are not within tolerance limit it is necessary to modify design

Objectives of testing are to determine the quality of material used & workmanship.

espect is also required when a new design or modified

new product works as per the revised designed or not.

Testing of equipment/machinery is also done after major maintenance of equipment.

Testing is necessary to avoid in convinces, avoid accidents & for safety purpose also.

OR

confirms whether machine/equipment is manufactures as per design

It verifies the actual values during testing and values specified by ISS

the difference between actual values & design values are whether within

permissible limits or not.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 2 of 39

The person who has power to give orders & make others to obey the some is called as

The meaning of responsibility is being responsible or accountable for everything

Due to following reason testing is carried out on machines or equipments: (Any Four

cal machine/ equipment is done to confirm whether the performance is

before commissioning.

Variation in the actual values & designed values must be within tolerance limits as

the variations in results are not within tolerance limit it is necessary to modify design

to determine the quality of material used & workmanship.

espect is also required when a new design or modified design is used, to

new product works as per the revised designed or not.

Testing of equipment/machinery is also done after major maintenance of equipment.

& for safety purpose also.

s manufactures as per design

It verifies the actual values during testing and values specified by ISS

the difference between actual values & design values are whether within

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

4) Due to testing we can confirm quality of material & workmanship.

5) Due to testing it avoids in convinces avoid accidents.

iii) Give the maintenance schedule of D

(Note: - Any Four P

Maintenance Schedule of

10028:1981:-

No Frequency of inspection

Inspection

1 Hourly Current, temperature,

2 Daily Dehydrating breather

3 Monthly Oil level intransformer

4 Quarterly Bushing

5 Half yearly Conservator

6 Yearly a) oil in transformer

7 Yearly b) Earth resistance

8 Yearly c) Relay, alarms and their circuits etc

9 Two Yearly Non-conservator transformer

10 Five yearly or after internal fault

Maintenance Schedule of Distribution

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Due to testing we can confirm quality of material & workmanship.

Due to testing it avoids in convinces avoid accidents.

Give the maintenance schedule of Distribution transformer as per ISS 10028:1981

Any Four Points from Below Are Expected & Not All)

Maintenance Schedule of distribution transformer up to 1000 KVA

Inspection Inspection details

Current, Voltage, temperature,

Check against rated figure

Dehydrating breather

Check that air passages are clear & check colour of acting agent

Oil level in transformer

Check transformer oil level

Bushing Examine for cracks and dirt deposits

Conservator Check for moisture cover

oil in transformer

Check for dielectric strength and water content, check for acidity and sluge

b) Earth resistance

Relay, alarms their circuits

Examine relay alarms contacts, their operation fuses etc; check relay accuracy etc

conservator transformer

Internal inspection above core Overall inspection lifting of core and coils

OR

Distribution transformer above 1000 KVA as per ISS 10028:1981

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 3 of 39

Due to testing we can confirm quality of material & workmanship.

istribution transformer as per ISS 10028:1981

(1 Mark each point)

Below Are Expected & Not All)

to 1000 KVA as per ISS

Action required when conditions are unsatisfactory Starts fans if necessary

It silica gel is pink change it or reactivate it for use again If low add dry oil, examine the transformer for leads Clean or replace

Improve ventilation check oil Take suitable action to restore quality of oil

Take suitable action if resistance is high Clean the components and replace contacts and fuses if necessary, change setting if necessary Filter oil regardless of condition Wash by housing down with clean dry oil.

as per ISS 10028:1981

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

No Frequency of inspection

Inspection

1

Hourly

a) Ambient temperatureb) winding temperaturec) Oil temperatured) Load voltage

2 Daily

a) Oil level in transformer levelb) Oil level in bushingc) Leakage of water into coolerd) Relief

e) Silica jel Breather

3 Quarterly a) Bushings

b) oil in transf

c) Cooler fan bearing motors and operating mechanism

4 Half Yearly Oil cooler

5

Yearly or earlier if transformer can conveniently be taken out for checking

a) Oil in transformerb) Oil filled bushingc) Gasket joints

d) Cable boxes

e) Surge diverter and gaps f) Relays, alarm and their circuits etc

g) Earth resistance

6 5 Yearly 1000 to 3000 KVA

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Inspection Inspection details

Ambient temperature

Check that temperature is reasonable than normal

winding temperature

Oil temperature Load voltage Check against rated figures Oil level in

mer level Check against transformer oil transformer for leaks

Oil level in bushing - Leakage of water

into cooler -

Relief diaphragm -

Silica jel Breather Check that air passages are free, Check colour of active agent

a) Bushings Examine for cracks and direct deposits

oil in transformer Check for dielectric strength and water contents

Cooler fan bearing motors and operating mechanism

Lubricate bearings, check gear box, examine contacts, check manual controls and interlocks

Oil cooler Test for pressure Oil in transformer Check acidity Oil filled bushing Test Oil

c) Gasket joints -

Cable boxes Check for ceiling arrangement for fitting holes, examine compound for leaks

Surge diverter and Examine for crack and dirt deposit

Relays, alarm and their circuits etc

Examine relay and alarm contacts, their operation, fuses etc; check relay accuracy etc.

Earth resistance -

1000 to 3000 KVA Overall inspection

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 4 of 39

Action required when conditions are unsatisfactory If abnormal heating shut down the transformer and investigate if heating is persistent higher.

If low add dry oil examine

- -

Replace if cracked or broken If silica jel is pink change it by active spare charge and the old charge may be reactivated for further use Clean or replace

Take suitable action to restore quantity of oil Replace burnt or worn contacts of other parts.

- Filter or replace and sluge Filter or replace and sluge Tighten the bolts to avoid uneven pressure Replace gaskets if leaking

Clean or replace

Clean the components and replace contacts and fuses if necessary, change setting if necessary Take suitable action if it is high Wash by hosing down

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

iv) Explain the care (protection) to be taken electrical e

inactivity. (Note: Any similar point should be consider)

Following care (protection) to be taken electrical equipments during the period of inactivity

1) All electrical connection sh

2) Surrounding area of equipment should be made clean.

3) Equipment should be covered by suitable means so that no dirt, dust and moisture enter

directly in equipment.

4) Caution board should be placed near

ACTIVE”

Q.1 b) Attempt any ONE of the following

i) Given Data:

V= 217V, I = 4.6A, N= 960 rpm, radius = 0.045 m, F

Solution:

powerInput =

=powerInput

powerInput =

(=TTorque

13(=T

T = 4

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

including lifting of core coils

Explain the care (protection) to be taken electrical equipments during the period of

(Note: Any similar point should be consider)

Following care (protection) to be taken electrical equipments during the period of inactivity

All electrical connection should be disconnected.

Surrounding area of equipment should be made clean.

Equipment should be covered by suitable means so that no dirt, dust and moisture enter

directly in equipment.

board should be placed near machine “ THAT MACHINE IS UNDER I

of the following

V= 217V, I = 4.6A, N= 960 rpm, radius = 0.045 m, F1= 13kg and

IV ×= ---------------------------------------------------------

6.4217×=

Watt2.998 ---------------------------------------------------

81.9)21( ××− rFF -------------------------------------------

81.9045.0)3.313 ××−

mN −282.4 -------------------------------------------------

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 5 of 39

with clean dry coils

quipments during the period of

(Note: Any similar point should be consider) (4 Marks)

Following care (protection) to be taken electrical equipments during the period of inactivity

Equipment should be covered by suitable means so that no dirt, dust and moisture enter

THAT MACHINE IS UNDER I N

6 Marks

13kg and F2= 3.3kg

--------------------------------------------------------- (1 Mark)

--------------------------------------------------- (1 Mark)

------------------------------------------- (1 Mark)

------------------------------------------------- (1 Mark)

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

wattinpowerOutput

powerOutput

powerOutput

=MotorofEfficency

MotorofEfficency

ofEfficency

ii) Explain the procedure for back to back test on transformer with neat circuit diagram.

State advantages and disadvantages of this method.

Marks and advantages –

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

60

2 NTwatt

π×=

60

9602282.4

×××= πpower

WattWin 473.430= ------------------------------------------

100×=wattinmotorofinput

wattinmotorofoutput

1002.998

473.430 ×=Motor

00124.43=Motor ---------------------------------------------

Explain the procedure for back to back test on transformer with neat circuit diagram.

State advantages and disadvantages of this method. (Procedure-2 Mark, Digaram

– 1 Mark , Disadvanatges-1 Mark )

Or equivalent figure

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 6 of 39

------------------------------------------ (1 Mark)

--------------------------------------------- (1 Mark)

Explain the procedure for back to back test on transformer with neat circuit diagram.

2 Mark, Digaram-2

Or equivalent figure

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

Procedure:-

i) Make the connection as per circuit diagram shown in above experimental setup.

ii) The primary is connected in parallel while

iii) One voltage regulator is required to inject voltage t

iv) Now supply is given at rated voltage & rated frequency (usually LV winding)

v) Take a reading of voltmeter V

vi) Close switch ‘S’ and increase the auxiliary supply voltage

current in secondary &

vii) Take the reads of voltmeter

side.

Advantages:- (Any one advantages expected)

1. Power consumption is low (only to met the losses)

2. No external load is required.

3. In addition to temperature rise we can determine efficiency & regulation of a

transformer by this test.

4. Transformer with full flux drawing full load currents & hence is closest to the actual

loading conditions with a physical load.

Disadvantages:-

1. The primary current of transformer 1 is less (being

of transformer (being phasor sum of I

Thus the two transformer do not operate under identica

slightly less temperature than the other (or more heating effect of one as compared to

other)

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Make the connection as per circuit diagram shown in above experimental setup.

The primary is connected in parallel while secondaries are connected in series opposition.

One voltage regulator is required to inject voltage to secondary of transformer.

Now supply is given at rated voltage & rated frequency (usually LV winding)

Take a reading of voltmeter V1, ammeter A1 and wattmeter W1 in the circuit of primary side.

Close switch ‘S’ and increase the auxiliary supply voltage in steps to circulate ,full load

ake the reads of voltmeter V2, ammeter A2 and wattmeter W2in the circuit of

(Any one advantages expected)

Power consumption is low (only to met the losses)

load is required.

In addition to temperature rise we can determine efficiency & regulation of a

transformer by this test.

Transformer with full flux drawing full load currents & hence is closest to the actual

loading conditions with a physical load.

The primary current of transformer 1 is less (being phasor difference of I

of transformer (being phasor sum of I1 & I0) where 2I0 is the load current.

Thus the two transformer do not operate under identical conditions one may have

slightly less temperature than the other (or more heating effect of one as compared to

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 7 of 39

Make the connection as per circuit diagram shown in above experimental setup.

are connected in series opposition.

o secondary of transformer.

Now supply is given at rated voltage & rated frequency (usually LV winding)

in the circuit of primary side.

in steps to circulate ,full load

in the circuit of secondary

In addition to temperature rise we can determine efficiency & regulation of a

Transformer with full flux drawing full load currents & hence is closest to the actual

difference of I1 & I0) than that

is the load current.

l conditions one may have

slightly less temperature than the other (or more heating effect of one as compared to

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

Q.2 Attempt any Four of the following

a) Describe the open delta (delta

2 Mark)

Open Delta (Delta-Delta) Test on Transformer: Circuit Diagram:-

Explanation-

This method is applicable in case of a delta to delta connected transformer.

1. To circulate the current in the secondary as well as primary the connection are made as

shown in figure.

2. Secondary voltage of aux

through 3-ph transformer secondary (as recorded by Ammeter A)

3. It will cause Full load current to circulate through transformer primary also.

4. Hence a condition similar to full load working

5. To measure the temperature rise, the transformer is kept under rated load condition for several hours till maximum steady temperature is attained.

b) What are the factors to be considered in designing the machine foundation?

Following factors to be considered in designing the machine foundationMarks) Note: Any Similar points may be consider

1. The foundation should absorb the vibrations created by the machine while operating at its

full capacity.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

of the following

open delta (delta-delta) test on transformers. (Figure-2 Mark & Explanation

Delta) Test on Transformer:-

Or equivalent fig

This method is applicable in case of a delta to delta connected transformer.

To circulate the current in the secondary as well as primary the connection are made as

Secondary voltage of auxiliary transformer is so adjusted that full load current circulates

ph transformer secondary (as recorded by Ammeter A)

It will cause Full load current to circulate through transformer primary also.

Hence a condition similar to full load working conditions is developed.

To measure the temperature rise, the transformer is kept under rated load condition for several hours till maximum steady temperature is attained.

What are the factors to be considered in designing the machine foundation?

ng factors to be considered in designing the machine foundationNote: Any Similar points may be consider

The foundation should absorb the vibrations created by the machine while operating at its

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 8 of 39

16 Marks

2 Mark & Explanation -

Or equivalent figure

This method is applicable in case of a delta to delta connected transformer.

To circulate the current in the secondary as well as primary the connection are made as

iliary transformer is so adjusted that full load current circulates

ph transformer secondary (as recorded by Ammeter A)

It will cause Full load current to circulate through transformer primary also.

conditions is developed.

To measure the temperature rise, the transformer is kept under rated load condition for

What are the factors to be considered in designing the machine foundation?

ng factors to be considered in designing the machine foundation: - (Each point 1

The foundation should absorb the vibrations created by the machine while operating at its

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

2. The foundation should

over the soil more than its safe bearing capacity.

3. The frictional resistance between foundation block and the soil should be sufficient to

withstand the possible horizontal thr

4. The foundation block should be so spread that the resultant of all the forces should pass

within the foundation block.

c) Give the four reasons for developing

reason-2 Mark & Magnetic fault reason

1) Following are some reasons due to Electrical faults:

1. Low insulation resistance.

2. Punctured insulation between adjacent turns.

3. Punctured insulating separators between HV a

4. Punctured insulation between ends of winding and yoke.

1. Punctured insulator

2. Turn to turn short circuit.

3. Bad contacts of loss of contact

4. Burning and darkening of Commutator

5. Poor contacts in armature winding connection with Commutator

6. Wrong setting of brushes on Commutator

7. Wrong pole polarity. In case of transformer, puncturing of insulating separator,

former between HV and LV end face insulation between ends of winding and yoke,

failure of oil layer insulation between current carrying p

2) Following are some reasons due to Magnetic Faults:

Transformer may fail due to following magnetic faults:

1. Warped and dented core laminations

2. Break down of insulation between laminatio

3. Core legs or yoke are loose or not fully tightened.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

The foundation should spread over as much area that will not exceed the intensity of load

over the soil more than its safe bearing capacity.

The frictional resistance between foundation block and the soil should be sufficient to

withstand the possible horizontal thrust caused by machine while in operation.

The foundation block should be so spread that the resultant of all the forces should pass

within the foundation block.

Give the four reasons for developing electrical and magnetic faults.

2 Mark & Magnetic fault reason- 2 Marks)

Following are some reasons due to Electrical faults:- (Any Two reasons are

Low insulation resistance.

Punctured insulation between adjacent turns.

Punctured insulating separators between HV and LV winding.

Punctured insulation between ends of winding and yoke.

OR

Punctured insulator

Turn to turn short circuit.

Bad contacts of loss of contact.

Burning and darkening of Commutator.

Poor contacts in armature winding connection with Commutator

ong setting of brushes on Commutator.

Wrong pole polarity. In case of transformer, puncturing of insulating separator,

former between HV and LV end face insulation between ends of winding and yoke,

failure of oil layer insulation between current carrying parts and tank wall.

Following are some reasons due to Magnetic Faults:- (Any Two reasons are

Transformer may fail due to following magnetic faults:-

Warped and dented core laminations

Break down of insulation between laminations.

Core legs or yoke are loose or not fully tightened.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 9 of 39

spread over as much area that will not exceed the intensity of load

The frictional resistance between foundation block and the soil should be sufficient to

ust caused by machine while in operation.

The foundation block should be so spread that the resultant of all the forces should pass

(Electrical fault

reasons are expected)

nd LV winding.

Poor contacts in armature winding connection with Commutator.

Wrong pole polarity. In case of transformer, puncturing of insulating separator,

former between HV and LV end face insulation between ends of winding and yoke,

arts and tank wall.

reasons are expected)

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

4. Faulty insulation of clamping studs.

5. Mis-aligned and damaged core clamping parts

1. Abnormal heating of core due to breakdown of insulation between core laminations

or non- uniform distribution of m

2. Failure of insulation between core clamping bolts and core, short circuit between

armature laminations, framing of laminations at teeth, loose pole fasting, mis

alignment of poles

3. Non –uniformity of air gap. In case

laminations, burned iron due to sharp rise of losses in the core.

4. Turn to turn short circuit.

5. Bad contacts of loss of contact

d) List the four agents which contaminates the insulating oil.

The insulating oil agents contaminated when the following impurities are present in oil

1. Presence of water.

2. Presence of dissolved moisture.

3. Presence of carbon deposits.

4. Presence of dirt & dust.

5. Presence of sulpher.

6. Presence of gases.

7. Presence of acids.

8. Presence of alcohol.

9. Presence of acetones & aldehydes.

10. Presence of sludge.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Faulty insulation of clamping studs.

aligned and damaged core clamping parts.

OR

Abnormal heating of core due to breakdown of insulation between core laminations

uniform distribution of magnetic flux between parallel branches.

Failure of insulation between core clamping bolts and core, short circuit between

armature laminations, framing of laminations at teeth, loose pole fasting, mis

alignment of poles

uniformity of air gap. In case of transformer wrapped and dented core

laminations, burned iron due to sharp rise of losses in the core.

Turn to turn short circuit.

Bad contacts of loss of contact.

List the four agents which contaminates the insulating oil. (Any Four Point

The insulating oil agents contaminated when the following impurities are present in oil

Presence of water.

Presence of dissolved moisture.

Presence of carbon deposits.

Presence of dirt & dust.

Presence of sulpher.

Presence of gases.

e of acids.

Presence of alcohol.

Presence of acetones & aldehydes.

Presence of sludge.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 10 of 39

Abnormal heating of core due to breakdown of insulation between core laminations

agnetic flux between parallel branches.

Failure of insulation between core clamping bolts and core, short circuit between

armature laminations, framing of laminations at teeth, loose pole fasting, mis-

of transformer wrapped and dented core

laminations, burned iron due to sharp rise of losses in the core.

(Any Four Point- 1 Mark each)

The insulating oil agents contaminated when the following impurities are present in oil:

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

e) List the four factors affecting preventive maintenance schedule

following Factors affecting preventive maintenance schedule

1. Type of machine & its working condition.

2. Working environment of industry.

chemical fumes, moisture in the air

3. Load cycle

4. Operating cycle of equipment or machine, or whether the machine is continuously working

or otherwise.

5. If the machine is continuously overload it needs early maintenance

times for preventive maintenance.

6. If the machine fails, how mush loss of money it will cause due to its down period.

7. Large capacity machine or equipments are used in industry it require a sound policy for

maintenance.

8. Aging of machine OR

the cost of the machine, and whether it can be replaced by a new one.

9. The machine used in the production work comes under essential equipments and they need

suitable time for preventive maintenance.

10. Some industry find heavy load during particular period of year and during other period they

are lightly loaded, during which maintenance can be carried out. It means that the operating

cycle of plant affects the schedule.

11. Sometimes through maintenance may be nece

the machine may be kept running to complete the production quota. It means that at a

particular time production is most urgent and profitable than the cost breakdown and down

period of machine during repair.

12. Cost of the maintenance.

13. Availability of trained & skilled technician.

14. Availability of spares & raw material.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

List the four factors affecting preventive maintenance schedule

affecting preventive maintenance schedule:

(Any four points expected

Type of machine & its working condition.

Working environment of industry. OR Atmospheric temperature, presence of dust,

chemical fumes, moisture in the air.

Operating cycle of equipment or machine, or whether the machine is continuously working

If the machine is continuously overload it needs early maintenance

s for preventive maintenance.

If the machine fails, how mush loss of money it will cause due to its down period.

Large capacity machine or equipments are used in industry it require a sound policy for

Aging of machine OR If the breakdown takes place, the cost of the repair will be more than

the cost of the machine, and whether it can be replaced by a new one.

The machine used in the production work comes under essential equipments and they need

suitable time for preventive maintenance.

dustry find heavy load during particular period of year and during other period they

are lightly loaded, during which maintenance can be carried out. It means that the operating

cycle of plant affects the schedule.

Sometimes through maintenance may be necessary if the production requirement needs that

the machine may be kept running to complete the production quota. It means that at a

particular time production is most urgent and profitable than the cost breakdown and down

period of machine during repair.

ost of the maintenance.

Availability of trained & skilled technician.

Availability of spares & raw material.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 11 of 39

(Any four points expected- 1 Marks each point)

Atmospheric temperature, presence of dust, dirt,

Operating cycle of equipment or machine, or whether the machine is continuously working

it will also need suitable

If the machine fails, how mush loss of money it will cause due to its down period.

Large capacity machine or equipments are used in industry it require a sound policy for

s place, the cost of the repair will be more than

the cost of the machine, and whether it can be replaced by a new one.

The machine used in the production work comes under essential equipments and they need

dustry find heavy load during particular period of year and during other period they

are lightly loaded, during which maintenance can be carried out. It means that the operating

ssary if the production requirement needs that

the machine may be kept running to complete the production quota. It means that at a

particular time production is most urgent and profitable than the cost breakdown and down

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

f) List the common troubles in electrical installation.

Note: In this question questions cr

relevant answer based on candidate understands

List the common troubles in Electrical Installation for example:

1. Open circuit fault trouble

2. Short circuit fault trouble

3. Earth fault trouble

OR

(Note: - Any Four Points from Below Are Expected & Not All)

a) Troubles in D.C Machines:

4. Shorted coils 5. Grounded coils6. Open coils 7. Reverse filed poles8. Reverse commutating pole winding9. Shorted armature coil10. Open armature coil11. Flash over between positive & Negative brush12. Grounded armature coil

b) Troubles in A.C Machines:

1. Shorted stator coils2. Grounded stator coils3. Open Stator coils4. Broken rotor bar or open rotor bar

c) Troubles in Transformer:

1. Open circuit (either i2. Short circuit (between in H.V and L.V)3. Ground fault (between H.V and core)4. Ground fault (between H.V and supporting structure)5. Shorted turns (either in H.V or L.V)6. Presence of moisture in transformer oil.7. Failure of magnetic circuit

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

List the common troubles in electrical installation.

Note: In this question questions credit may be given by judgment on part of examiner of

relevant answer based on candidate understands

List the common troubles in Electrical Installation for example:-

Open circuit fault trouble

Short circuit fault trouble

trouble

OR Student may write any one of the following

Any Four Points from Below Are Expected & Not All)

C Machines:-

Grounded coils

Reverse filed poles Reverse commutating pole winding Shorted armature coil

ature coil Flash over between positive & Negative brush Grounded armature coil

Machines:-

Shorted stator coils Grounded stator coils Open Stator coils Broken rotor bar or open rotor bar

Troubles in Transformer:-

Open circuit (either in H.V or L.V) Short circuit (between in H.V and L.V) Ground fault (between H.V and core) Ground fault (between H.V and supporting structure) Shorted turns (either in H.V or L.V) Presence of moisture in transformer oil. Failure of magnetic circuit

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 12 of 39

(4 Marks)

edit may be given by judgment on part of examiner of

may write any one of the following

Any Four Points from Below Are Expected & Not All)

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

d) Troubles in circuit breakers:

1. Damage of arcing contacts2. Loosening of nuts and bolts of operating mechanisms.3. Damage of arc control device4. Failure of operating mechanism5. Relay failure

Q.3 Attempt any Four of the following

a) Explain the four factors on which severity of electrical shock depends.

The following Factors on which severity of Electrical shock depends

Expected- 1 Mark each)

The effect of electrical shock on human bodies depends on following factors.

i) Magnitude voltage of the system.

ii) The period or duration

iii) It is also depends on supply system i.e. A.C or D.C.

iv) Body resistance (If wet resistance of body re

v) Shock may occur even when voltage 50V rms AC low or 75V DC sometimes

voltage does not mean low hazard.

vi) Path of current through body.

The magnitude of current passing through the

S.No The current strength1 A.C current of low frequency

between 1m amp to 8 mA2 8mA-15mA

3 20mA-50mA

4 50mA-100mA

5 100mA-200mA6 Above -200mA

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

in circuit breakers:

Damage of arcing contacts Loosening of nuts and bolts of operating mechanisms. Damage of arc control device Failure of operating mechanism

of the following

Explain the four factors on which severity of electrical shock depends.

The following Factors on which severity of Electrical shock depends

l shock on human bodies depends on following factors.

oltage of the system.

or duration for which the areas of contact with live part.

It is also depends on supply system i.e. A.C or D.C.

Body resistance (If wet resistance of body reduces)

occur even when voltage 50V rms AC low or 75V DC sometimes

voltage does not mean low hazard.

Path of current through body.

OR

The magnitude of current passing through the body:-

The current strength Effect on human systemA.C current of low frequency between 1m amp to 8 mA

Are just bearable does not cause any pains

Give painful shock without loss of muscular control.

50mA If passes through chest, it may stop breathing

100mA May result in ventricular fibrillation.

200mA May cause fibration of heart200mA Causes death, severe burns

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 13 of 39

16 Marks

Explain the four factors on which severity of electrical shock depends.

The following Factors on which severity of Electrical shock depends: (Any four point

l shock on human bodies depends on following factors.

for which the areas of contact with live part.

occur even when voltage 50V rms AC low or 75V DC sometimes OR Low

Effect on human system Are just bearable does not cause any pains

Give painful shock without loss of muscular

If passes through chest, it may stop

icular cavity in body

May cause fibration of heart Causes death, severe burns

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

b) Explain the importance of batteries in a sub

of batteries.

Importance of batteries in sub

1. The DC auxiliary power source is required for protection system to operate protective

relays of circuit breaker.

2. The DC auxiliary power source is req

3. As a emergency supply for lighting and fan in control room.

Care of storage batteries: (Any four points Daily:-

1. Inspect the battery and the room for general clean2. Check the height of the electrode.

3. Keep the record of the topping if done.

4. Check the voltage of the pilot cells.

5. Record and check the specific gravity and temperature of the electrolyte of the pilot cells.

6. Record and check the ambient temperature.

Weekly:-

1. Inspect the battery very carefully a)

clean and dry.

2. Check the cells for cracks and electrolyte leakage if so take remedial measures.

3. Record and check the specific gravity, voltage and tempera

4. Check for plate bucking, collection of sediments at the bottom of the cell etc.

5. Give quick fleshing charge after every heavy discharge.

Fortnightly:-

1. Carry out inspection schedule as laid down above.

2. Topping of all the cells be do

Quarterly:-

1. Check specific gravity and temperature of each cell.

2. Check the voltage of the battery and each cell.

3. Check the level of electrolyte of each cell.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Explain the importance of batteries in a sub-station and describe how you will take care

(Importance -2 Marks & Care

Importance of batteries in sub-station:

The DC auxiliary power source is required for protection system to operate protective

relays of circuit breaker.

The DC auxiliary power source is required for control system in sub

As a emergency supply for lighting and fan in control room.

(Any four points from below total points are expected and not all)

Inspect the battery and the room for general cleanliness. Check the height of the electrode.

Keep the record of the topping if done.

Check the voltage of the pilot cells.

Record and check the specific gravity and temperature of the electrolyte of the pilot cells.

Record and check the ambient temperature.

Inspect the battery very carefully a) Remove dust or dirt if accumulated b) Keep the battery

Check the cells for cracks and electrolyte leakage if so take remedial measures.

Record and check the specific gravity, voltage and temperature of the pilot cells.

Check for plate bucking, collection of sediments at the bottom of the cell etc.

Give quick fleshing charge after every heavy discharge.

Carry out inspection schedule as laid down above.

Topping of all the cells be done with distilled water.

Check specific gravity and temperature of each cell.

Check the voltage of the battery and each cell.

Check the level of electrolyte of each cell.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 14 of 39

station and describe how you will take care

2 Marks & Care- 2 Marks)

The DC auxiliary power source is required for protection system to operate protective

control system in sub-station.

are expected and not all)

Record and check the specific gravity and temperature of the electrolyte of the pilot cells.

Remove dust or dirt if accumulated b) Keep the battery

Check the cells for cracks and electrolyte leakage if so take remedial measures.

ture of the pilot cells.

Check for plate bucking, collection of sediments at the bottom of the cell etc.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

4. All the bolts and nuts should be checked for tightness. Petroleum jelly o

be applied.

5. Check float and/or trickle charges.

6. Test the battery load and small continuously load.

Yearly Inspection:-

In addition to the inspection schedule given above, check for the following.

1. Condition of the individual c

2. Resistance i.e terminal as well as cell to cell.

3. Inspection of battery rack.

4. Level of the sediments if collected at the bottom of the cell.

5. Paint a fresh the racks, walls of the room with acid resistance paint if needed.

c) Explain the polarity test a

and explanation-1 Mark for each test )

1) Polarity test on Transformer :

Figure:-

The primary & secondary are supposed to have the same polarity when the turns in

both winding go round the core in the same direction & the start & end leads are marked in the

same ways. The direction of current in the two winding will t

Subtractive Polarity:

If ‘X’ & ‘Y’ connected together the voltage across X

V1-V2 & the polarity is said to be same is called subtractive polarity.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

All the bolts and nuts should be checked for tightness. Petroleum jelly o

Check float and/or trickle charges.

Test the battery load and small continuously load.

In addition to the inspection schedule given above, check for the following.

Condition of the individual cell.

Resistance i.e terminal as well as cell to cell.

Inspection of battery rack.

Level of the sediments if collected at the bottom of the cell.

fresh the racks, walls of the room with acid resistance paint if needed.

Explain the polarity test and phasing out test on transformer with diagram.

1 Mark for each test )

Polarity test on Transformer :-

Or equivalent figure

secondary are supposed to have the same polarity when the turns in

both winding go round the core in the same direction & the start & end leads are marked in the

same ways. The direction of current in the two winding will then be the same.

If ‘X’ & ‘Y’ connected together the voltage across X1 & Y1

& the polarity is said to be same is called subtractive polarity.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 15 of 39

All the bolts and nuts should be checked for tightness. Petroleum jelly or Vaseline should

In addition to the inspection schedule given above, check for the following.

fresh the racks, walls of the room with acid resistance paint if needed.

nd phasing out test on transformer with diagram. (Figure -1

Or equivalent figure

secondary are supposed to have the same polarity when the turns in

both winding go round the core in the same direction & the start & end leads are marked in the

hen be the same.

will be found to be V=

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

Additive Polarity: -

If ‘X’ & ‘Y’ connected together the voltage across X

V1+V2 & the polarity is said to be opposite is called additive polarity.

2) Phasing out test on transformer:

Figure: -

Explanation:-

� Short primary & secondary winding of other phases expect the one under test.

� Connect voltmeter to secondary winding.

� A small DC current is circulated through the primary winding through switch.

� Now with the help of switch interrupt the DC supply instantly & repeatedly.

� If voltmeter indicator deflects than it indicates the two windings concerned belong to the

same phase.

� If not deflect then two windings are not belong to same phase.

� Repeat the procedure by connecting voltmeter to secondary side to next secondary

winding till voltmeter gives deflection.

In this way we can search the phasing out test.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

If ‘X’ & ‘Y’ connected together the voltage across X1 & Y1 will be found to be V=

& the polarity is said to be opposite is called additive polarity.

Phasing out test on transformer:

Or equivalent figure

Short primary & secondary winding of other phases expect the one under test.

Connect voltmeter to secondary winding.

current is circulated through the primary winding through switch.

Now with the help of switch interrupt the DC supply instantly & repeatedly.

If voltmeter indicator deflects than it indicates the two windings concerned belong to the

lect then two windings are not belong to same phase.

Repeat the procedure by connecting voltmeter to secondary side to next secondary

winding till voltmeter gives deflection.

In this way we can search the phasing out test.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 16 of 39

will be found to be V=

Or equivalent figure

Short primary & secondary winding of other phases expect the one under test.

current is circulated through the primary winding through switch.

Now with the help of switch interrupt the DC supply instantly & repeatedly.

If voltmeter indicator deflects than it indicates the two windings concerned belong to the

Repeat the procedure by connecting voltmeter to secondary side to next secondary

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

d) Describe routine, preventive and breakdown maintenance with suitable examples.

mark each meaning and 1 Marks to all example )

Note: In this question questions credit may be given by judgment on part of examiner of

relevant answer based on candi

Routine Maintenance means� It should be carried out

� The maintenance schedule is usually in the form of log sheets on which days, weeks,

months of the year are tabulate

� Routine maintenance is carried out without dismantling the equipment, but it must

always be disconnected from supply before any repairs are undertaken.

� The routine maintenance work is carried out by the maintenance staff.

� Routine maintenance means ch

machine/equipment.

For Example (Activities)

� It includes visual inspection, cleaning, minor repairs s

and adjustment of equipment.

� Routine maintenance includes a

dust & dirt.

� Cleaning of the fitting, tank cover, b

� Cleaning the fixed & moving contacts of starters and replacement of burnt contacts.

� Routine maintenances of electric

checking of control equipment and replacement of carbon brushes.

� Periodic visual inspection of various equipments to locate initial condition leading to

breakdown.

� Inspect plant under working condition an

� Up keep of equipment and plant & r

� Checking of stationary parts.

� Checking of movable parts.

� Checking of working condition of equipment or machinery.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Describe routine, preventive and breakdown maintenance with suitable examples.

mark each meaning and 1 Marks to all example )

Note: In this question questions credit may be given by judgment on part of examiner of

relevant answer based on candidate understands

means:- (Any one of the following point should be consider)It should be carried out daily if possible.

The maintenance schedule is usually in the form of log sheets on which days, weeks,

months of the year are tabulated.

Routine maintenance is carried out without dismantling the equipment, but it must

always be disconnected from supply before any repairs are undertaken.

The routine maintenance work is carried out by the maintenance staff.

Routine maintenance means checking/Cleaning/Repairing/Replacement of

machine/equipment.

(Activities)-: (Any one expected)

ual inspection, cleaning, minor repairs such as replacement of small parts

and adjustment of equipment.

Routine maintenance includes all work required in cleaning of electrical equipment from

ng of the fitting, tank cover, bushing of power transformers

leaning the fixed & moving contacts of starters and replacement of burnt contacts.

Routine maintenances of electric motors involve washing and lubrication of bearing,

checking of control equipment and replacement of carbon brushes.

Periodic visual inspection of various equipments to locate initial condition leading to

Inspect plant under working condition and also when it as rest.

Up keep of equipment and plant & repair defects at their initial s

Checking of stationary parts.

Checking of movable parts.

Checking of working condition of equipment or machinery.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 17 of 39

Describe routine, preventive and breakdown maintenance with suitable examples. (One

Note: In this question questions credit may be given by judgment on part of examiner of

(Any one of the following point should be consider)

The maintenance schedule is usually in the form of log sheets on which days, weeks,

Routine maintenance is carried out without dismantling the equipment, but it must

always be disconnected from supply before any repairs are undertaken.

The routine maintenance work is carried out by the maintenance staff.

ecking/Cleaning/Repairing/Replacement of

uch as replacement of small parts

ll work required in cleaning of electrical equipment from

ushing of power transformers.

leaning the fixed & moving contacts of starters and replacement of burnt contacts.

motors involve washing and lubrication of bearing,

checking of control equipment and replacement of carbon brushes.

Periodic visual inspection of various equipments to locate initial condition leading to

epair defects at their initial stage.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

� Checking of surrounding in which the machinery

atmospheric condition.

� Checking of safety measures.

� Checking of protective device

1. Preventive Maintenance:

Preventive maintenance is carried out to reduce the failure of equipment to minimum

Preventive maintenance means

failure of equipment to minimum. It consists of adoption of measures

breakdown

For example: - (Any one expected)

1. Measurement of insulation resistance by megger,

2. Cleaning of machine by suitable blower to blown out dust, dirt etc

3. Checking of oil lubricated bearings.

4. Overhaul control equipment

5. It includes inspection of loose connection, ventilation, replacement of worn parts,

change of oil, checking of insulation etc.

6. Overhaul

2. Corrective or Breakdown Maintenance :

Corrective maintenance is carried out when an equipment fails or does not work

satisfactory. OR

When industrial plants or electrical machines are running and stop incidentally, it is

known as breakdown. Breakdown maintenance is carried out when machine fail to run.

For example: - (Any one expected)

1. In this type of maintenance, immediate steps are taken to repair the fault.

2. Rewinding is carried out if winding is burnt out or parts are rep

3. At the same time, following checks are carried out so that further breakdown should be not

taking place.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Checking of surrounding in which the machinery or equipment has to work i.e

atmospheric condition.

Checking of safety measures.

Checking of protective device

Preventive Maintenance:-

Preventive maintenance is carried out to reduce the failure of equipment to minimum

Preventive maintenance means proper maintenance and is carried out to reduce the

failure of equipment to minimum. It consists of adoption of measures (reasons)

Any one expected)

Measurement of insulation resistance by megger,

hine by suitable blower to blown out dust, dirt etc

Checking of oil lubricated bearings.

Overhaul control equipment

It includes inspection of loose connection, ventilation, replacement of worn parts,

change of oil, checking of insulation etc.

orrective or Breakdown Maintenance :

Corrective maintenance is carried out when an equipment fails or does not work

When industrial plants or electrical machines are running and stop incidentally, it is

as breakdown. Breakdown maintenance is carried out when machine fail to run.

Any one expected)

In this type of maintenance, immediate steps are taken to repair the fault.

Rewinding is carried out if winding is burnt out or parts are replaced immediately.

At the same time, following checks are carried out so that further breakdown should be not

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 18 of 39

or equipment has to work i.e

Preventive maintenance is carried out to reduce the failure of equipment to minimum. OR

proper maintenance and is carried out to reduce the

(reasons) to know before

hine by suitable blower to blown out dust, dirt etc

It includes inspection of loose connection, ventilation, replacement of worn parts,

Corrective maintenance is carried out when an equipment fails or does not work

When industrial plants or electrical machines are running and stop incidentally, it is

as breakdown. Breakdown maintenance is carried out when machine fail to run.

In this type of maintenance, immediate steps are taken to repair the fault.

laced immediately.

At the same time, following checks are carried out so that further breakdown should be not

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

i) Tightness of stationary parts is checked.

ii) It is also checked that the moving parts are free to move and there is no damage to it.

iii) Reasons for the fault to take place, which can be eliminated.

Atmospheric condition and surroundings in which the machine has to work

e) Explain one dark lamp and two equally bright lamp method of synchronization with

diagram.

One dark lamp and two equally bright lamp method of synchronization

VL1 = Voltage across the lamps L

VL2 = Voltage across the lamps L

VL3 = Voltage across the lamps L

� The 3 lamp pairs L1 &

connected as shown in figure across the switch and to the bus bar and alternator terminals.

� The Phasor diagram of the bus bar voltages (V

voltage of incoming alternator (V

� The lamps will still flickers in this case also and the rate of their flickering will depend on

the amount of diff of the frequencies of the two alternators.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Tightness of stationary parts is checked.

It is also checked that the moving parts are free to move and there is no damage to it.

asons for the fault to take place, which can be eliminated.

Atmospheric condition and surroundings in which the machine has to work

Explain one dark lamp and two equally bright lamp method of synchronization with

(Explanation-2 Marks & Figure

One dark lamp and two equally bright lamp method of synchronization

Or equivalent figure

= Voltage across the lamps L1 = VR1 – VR2

= Voltage across the lamps L2 = VY1 – VY2

= Voltage across the lamps L3 = VB1 – VB2

L2, and L2 & L 2, and L3 & L 3 of equal wattage and voltage rating are

connected as shown in figure across the switch and to the bus bar and alternator terminals.

The Phasor diagram of the bus bar voltages (VR1=VY1=VB1) and the Phasor diagram of

incoming alternator (VR2=VY2=VB2) are shown in the figure.

The lamps will still flickers in this case also and the rate of their flickering will depend on

the amount of diff of the frequencies of the two alternators.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 19 of 39

It is also checked that the moving parts are free to move and there is no damage to it.

Atmospheric condition and surroundings in which the machine has to work

Explain one dark lamp and two equally bright lamp method of synchronization with

2 Marks & Figure-2 Marks)

One dark lamp and two equally bright lamp method of synchronization:

Or equivalent figure

of equal wattage and voltage rating are

connected as shown in figure across the switch and to the bus bar and alternator terminals.

) and the Phasor diagram of

) are shown in the figure.

The lamps will still flickers in this case also and the rate of their flickering will depend on

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

� The correctness of the phase sequence i

after another and not simultaneously.

� The correct instant of closing the synchronizing switch is when the straight connected

lamps are dark and the cross connected lamps are equally bright.

Method of synchronizing by means lamps

� If the synchroscope

� There are different methods of lamp connection. The method of two bright and one

dark lamp indication is illustrated

� In this connection the lamps become bright and dark as follows for correct phase

sequence. “Two lamps bright and one lamp dark at a time”.

� If all the lamps become simultaneously dark or bright, the phase sequence is wrong.

� The switch is closed when the voltage, frequency and the lamps (2 bright and 1 Dark)

satisfy the condition of synchronism.

Q.4. a) Attempt any Three of the following

i) Explain the methods of testing : 1)

Mark & Example 1 Mark for each test )

1) Direct loading method of testing:

� Direct method of testing

with the help of brake arrangement or coupling a calibrated machine to its shaft for

loading purpose.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

The correctness of the phase sequence is indicated by the lamps blowing bright or dark, one

after another and not simultaneously.

The correct instant of closing the synchronizing switch is when the straight connected

lamps are dark and the cross connected lamps are equally bright.

OR

synchronizing by means lamps:

If the synchroscope is not available, synchronizing lamp method is used.

There are different methods of lamp connection. The method of two bright and one

dark lamp indication is illustrated in above figure.

In this connection the lamps become bright and dark as follows for correct phase

sequence. “Two lamps bright and one lamp dark at a time”.

If all the lamps become simultaneously dark or bright, the phase sequence is wrong.

osed when the voltage, frequency and the lamps (2 bright and 1 Dark)

satisfy the condition of synchronism.

of the following

s of testing : 1) Direct 2) Indirect by giving example

Mark & Example 1 Mark for each test )

method of testing:-

Direct method of testing is, in which the machine under test can be loaded directly

help of brake arrangement or coupling a calibrated machine to its shaft for

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 20 of 39

s indicated by the lamps blowing bright or dark, one

The correct instant of closing the synchronizing switch is when the straight connected

is not available, synchronizing lamp method is used.

There are different methods of lamp connection. The method of two bright and one

In this connection the lamps become bright and dark as follows for correct phase

If all the lamps become simultaneously dark or bright, the phase sequence is wrong.

osed when the voltage, frequency and the lamps (2 bright and 1 Dark)

12 Marks

Indirect by giving example (Explanation- 1

in which the machine under test can be loaded directly, either

help of brake arrangement or coupling a calibrated machine to its shaft for

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

� This test is conducted for small capacity equipment/machine/transformer.

� Power consumption is more

� During this test more heat is generated.

� Results obtain are mo

For Example Methods:

a) Brake load Test b) Calibrated machine test

2) Indirect loading Method of testing:

� In case of indirect testing method equipment/mach

but machine runs on No

� Its performance characteristics are determined by using the data obtained in the no

test performed on the machine.

� This test is conducted for large capacity equipment/machine/tran

� Power consumption is less.

� Efficiency at any desired load condition, even over loads can be determined by this test.

For example :- Swinburne’s Test,

ii) Describe the impulse voltage withstand

Figure-2 Mark)

Figure:-

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

This test is conducted for small capacity equipment/machine/transformer.

Power consumption is more

During this test more heat is generated.

Results obtain are more accurate.

Methods:

Test b) Calibrated machine test

Method of testing:-

In case of indirect testing method equipment/machine/transformer are not directly loaded

but machine runs on No- load.

ts performance characteristics are determined by using the data obtained in the no

test performed on the machine.

This test is conducted for large capacity equipment/machine/transformer.

Power consumption is less.

Efficiency at any desired load condition, even over loads can be determined by this test.

Swinburne’s Test, OC/SC Test, To draw the circle diagram of 3

Describe the impulse voltage withstand test on transformers. (Explanation

Or equivalent figure

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 21 of 39

This test is conducted for small capacity equipment/machine/transformer.

ine/transformer are not directly loaded

ts performance characteristics are determined by using the data obtained in the no-load

sformer.

Efficiency at any desired load condition, even over loads can be determined by this test.

, To draw the circle diagram of 3-ph I.M

(Explanation-2 Mark &

Or equivalent figure

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

Objectives:-

� To ensure the effectiveness

against lighting impulse.

� The impulse voltage withstand test is intended to check the ability of the transformer to

withstand over-voltages of atmospheric origin.

Equipment used:

Impulse voltage test is conducted for this impulse generator is used to obta

specified impulse voltage wave.

1. Lightning impulse: 12/50 micro sec.

2. Switching impulse: 250/2500 micro sec.(test is conducted for power transformer

above 365K

Chopped impulse wave: 1.2/50 wave chopped

impulse test is special test performed if user needed.

Impulse frequency test voltages fo

is expected not all)

No. Normal system Voltage KV rms

1 3.3 2 6.6 3 11 4 22 5 33 6 66 7 110 8 132 9 220 10 400 *Applicable where the

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

To ensure the effectiveness i.e. dielectric strength of the insulation system of transformer

against lighting impulse.

ulse voltage withstand test is intended to check the ability of the transformer to

voltages of atmospheric origin.

Impulse voltage test is conducted for this impulse generator is used to obta

specified impulse voltage wave. The standard impulse waves are of three types:

Lightning impulse: 12/50 micro sec.

Switching impulse: 250/2500 micro sec.(test is conducted for power transformer

above 365KV)

Chopped impulse wave: 1.2/50 wave chopped at about 5 micro sec.(

impulse test is special test performed if user needed.)

frequency test voltages for oil immersed transformer table :( Note

Highest system voltage KV rms

Impulse withstand voltage 1/50 wave positive & negative polarity KV (crest)

3.6 457.2 6012 7524 12536 170

72.5 325123 450*145 550*245 900*420 1425*

Applicable where the system is effectively earthed

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 22 of 39

of the insulation system of transformer

ulse voltage withstand test is intended to check the ability of the transformer to

Impulse voltage test is conducted for this impulse generator is used to obtain

The standard impulse waves are of three types:

Switching impulse: 250/2500 micro sec.(test is conducted for power transformer

at about 5 micro sec.( chopped

( Note: Any one voltage

Impulse withstand voltage 1/50 wave positive & negative polarity KV (crest)

45 60 75 125 170 325 450* 550* 900* 1425*

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

iii) State four properties of good transformer oil.

Following Properties of Good Transformer oil:

1. It should be have a high dielectric strength (N

the electrodes or 20KV (rms)

2. It should be free from moisture contents & water vapour limiting value should not be more.

3. Acidity contents should be very in the oil limiting value 0.4mg of KOH/g.

4. It should have high flash point i.e. 160

(1450C).

5. The temperature at which the oil will ignite & continue burning should be about 200

6. The oil should be chemically stable.

7. It should be not contain impurities such as sulpher & i

sludge formation.

8. It should posses low viscosity.

9. Sludge value of the oil after treating should be 1.2% (limiting value is less than 0.1%)

10. Density of oil at 200C should be 0.89 gm/cm

11. Relative permittivity should be 2.2

12. The oil should be frequently clear & plane in colour, transparent & free from suspended

matter sediments.

13. Mineral oil grade B should be used.

14. The properties of good transformer & switchgear oil are recommended by IS 335

15. And for maintain the propertie

iv) What are the effects of mis

The following Effects of Mis

1. Misalignment causes, it reduces the machine’s life and causes a decrease in motor

arrangement efficiency, and misaligned machinery is more prone to failure due to increased

load on bearing, seals and coupling.

2. In most of the cases, misalignment in motor exhibits the combination of both types of

misalignment.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

State four properties of good transformer oil.

Following Properties of Good Transformer oil:- (Any four point expected

a high dielectric strength (Not less than 30KV (rms) for the gap 4

ectrodes or 20KV (rms) for the gap 2.5mm of the electrodes)

It should be free from moisture contents & water vapour limiting value should not be more.

Acidity contents should be very in the oil limiting value 0.4mg of KOH/g.

flash point i.e. 1600C & lower point as per specification led down

The temperature at which the oil will ignite & continue burning should be about 200

The oil should be chemically stable.

It should be not contain impurities such as sulpher & i ts compounds to avoid rusting &

It should posses low viscosity.

Sludge value of the oil after treating should be 1.2% (limiting value is less than 0.1%)

C should be 0.89 gm/cm3.

Relative permittivity should be 2.2

The oil should be frequently clear & plane in colour, transparent & free from suspended

Mineral oil grade B should be used.

The properties of good transformer & switchgear oil are recommended by IS 335

And for maintain the properties IS code of practice No. 1866-1961 to be refer.

What are the effects of mis-alignment?

The following Effects of Mis-alignment:- (Any four point expected

it reduces the machine’s life and causes a decrease in motor

angement efficiency, and misaligned machinery is more prone to failure due to increased

load on bearing, seals and coupling.

In most of the cases, misalignment in motor exhibits the combination of both types of

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 23 of 39

(Any four point expected-1 Mark each pt)

ot less than 30KV (rms) for the gap 4mm of

It should be free from moisture contents & water vapour limiting value should not be more.

Acidity contents should be very in the oil limiting value 0.4mg of KOH/g.

C & lower point as per specification led down

The temperature at which the oil will ignite & continue burning should be about 2000C.

ts compounds to avoid rusting &

Sludge value of the oil after treating should be 1.2% (limiting value is less than 0.1%)

The oil should be frequently clear & plane in colour, transparent & free from suspended

The properties of good transformer & switchgear oil are recommended by IS 335-1963.

1961 to be refer.

(Any four point expected – 1 Mark each)

it reduces the machine’s life and causes a decrease in motor

angement efficiency, and misaligned machinery is more prone to failure due to increased

In most of the cases, misalignment in motor exhibits the combination of both types of

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

3. Offset Misalignment which is t

are out of parallel alignment and Angular Misalignment which is the amount by which the

alignment of driver and driven shaft

4. Detection of misalignment using broken rotor bar sideband and componen

5. Effect of increased vibration is premature bearing failure.

6. cause increased vibration and loads on the

designed

7. Reduce the bearing life

Q.4. b) Attempt any ONE of the following

i) Explain the following tests on transformer oil 1)

point test

1) Acidity Test: The limits of permissible acidity

i) Acidity below 0.5 mg (KOH)/g:

all other respects.

ii) Acidity between 0.5 mg & 1.0 mg (KOH)/g:

observation.

iii) Acidity exceeds 10 mg (KOH)/g:

2) Sludge Test: -

Sludge is formed when oil gets overheated or due to suspended solid impurities in

oil. Oil which has been contaminated by a fault in

3) Flash point Test:-

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Offset Misalignment which is the amount by which the alignment of driver and driven shaft

are out of parallel alignment and Angular Misalignment which is the amount by which the

alignment of driver and driven shaft.

etection of misalignment using broken rotor bar sideband and componen

of increased vibration is premature bearing failure.

cause increased vibration and loads on the machine parts for which they have not been

Reduce the bearing life.

of the following

Explain the following tests on transformer oil 1) Acidity test 2) Sludge test and 3) Flash

(Each T

The limits of permissible acidity test of oil are:

i) Acidity below 0.5 mg (KOH)/g: - No action need be taken if oil is satisfactory in

all other respects.

ii) Acidity between 0.5 mg & 1.0 mg (KOH)/g: - Oil is to be kept under

observation.

Acidity exceeds 10 mg (KOH)/g: - Oil should be discards or treated.

Sludge is formed when oil gets overheated or due to suspended solid impurities in

oil. Oil which has been contaminated by a fault in a transformer is unsuitable for use.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 24 of 39

he amount by which the alignment of driver and driven shaft

are out of parallel alignment and Angular Misalignment which is the amount by which the

etection of misalignment using broken rotor bar sideband and components.

for which they have not been

6 Marks

Acidity test 2) Sludge test and 3) Flash

(Each Test- 2 Marks)

No action need be taken if oil is satisfactory in

is to be kept under

Oil should be discards or treated.

Sludge is formed when oil gets overheated or due to suspended solid impurities in

a transformer is unsuitable for use.

Or equivalent figure.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

� The sample of oil is down from near the top & bottom of the transformer.

� The gap of electrode is first checked with a gauge.

� The cup is filled with sample of oil to be tested up to about 1 cm above the electrodes.

� The cup to be covered with clean glass plate.

� The supply is switched ON & voltage is raised gradually by the variac.

� Till final break down of oil takes place & circuit breaker gets t

transformer from the main supply.

� The test is performed with 2 or 3 consecutive samples of the oil one by one.

� Average of all subsequent tests is considered as the breakdown voltage of oil sample.

� This value is noted down which must

� If this value is lower than 30 KV than it indicates presence of moisture in oil.

� Oil in good condition when its breakdown voltage is 45 KV (rms) for 4mm gap for one

minute.

ii) Describe the use of following tools

Tools -2 Marks and figure not expected

1) Earth Tester: -

� Earth tester is used for measurement of earth resistance.

� A earth tester works on the same principle as

� The difference being that slip

permit AC supply to the external circuit through the soil to eliminate electrolytic

effects.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

The sample of oil is down from near the top & bottom of the transformer.

The gap of electrode is first checked with a gauge.

ed with sample of oil to be tested up to about 1 cm above the electrodes.

The cup to be covered with clean glass plate.

The supply is switched ON & voltage is raised gradually by the variac.

Till final break down of oil takes place & circuit breaker gets tripped & disconnect the

transformer from the main supply.

The test is performed with 2 or 3 consecutive samples of the oil one by one.

Average of all subsequent tests is considered as the breakdown voltage of oil sample.

This value is noted down which must be 30 KV (rms) for 4 mm +- 0.02 mm gap.

If this value is lower than 30 KV than it indicates presence of moisture in oil.

Oil in good condition when its breakdown voltage is 45 KV (rms) for 4mm gap for one

Describe the use of following tools 1) Earth Tester 2) Megger 3) Multimeter

and figure not expected)

Earth tester is used for measurement of earth resistance.

A earth tester works on the same principle as a megger.

The difference being that slip-rings are also provided on the hand driven generator to

permit AC supply to the external circuit through the soil to eliminate electrolytic

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 25 of 39

The sample of oil is down from near the top & bottom of the transformer.

ed with sample of oil to be tested up to about 1 cm above the electrodes.

The supply is switched ON & voltage is raised gradually by the variac.

ripped & disconnect the

The test is performed with 2 or 3 consecutive samples of the oil one by one.

Average of all subsequent tests is considered as the breakdown voltage of oil sample.

0.02 mm gap.

If this value is lower than 30 KV than it indicates presence of moisture in oil.

Oil in good condition when its breakdown voltage is 45 KV (rms) for 4mm gap for one

1) Earth Tester 2) Megger 3) Multimeter (Each

rings are also provided on the hand driven generator to

permit AC supply to the external circuit through the soil to eliminate electrolytic

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

� A Commutator which will rectify the current before it is applied

elements. Figure represents the circuit diagram for measuring earth electrode

resistance

2) Megger:-

� Megger is used to find out insulation resistance of electrical machine/equipment

� Meggers (mega ohm meter)

Generally in practice 500V meggers are used.

3) Multimeter:- (Any Two expected)

� Measurement of voltage

� Measurements of current

� Measurement of DC resistance

� To check the Continuity

Q.5. Attempt any Two of the following

a) Given Data:

Note: Credits may be given step wise for numerical problems. In some cases, the assumed constant values may vary and therand model answer.

i) No-load Test:

V1= 200V, I0 =5A, W

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

A Commutator which will rectify the current before it is applied

elements. Figure represents the circuit diagram for measuring earth electrode

Megger is used to find out insulation resistance of electrical machine/equipment

(mega ohm meter) are available for DC voltage of 500V

Generally in practice 500V meggers are used.

(Any Two expected)

Measurement of voltage of various ranges.

of current of various ranges.

Measurement of DC resistance

Continuity

of the following

Credits may be given step wise for numerical problems. In some cases, the assumed constant values may vary and there may be some difference in the candidate’s answers

=5A, W0= 350 watt

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 26 of 39

A Commutator which will rectify the current before it is applied to the moving coil

elements. Figure represents the circuit diagram for measuring earth electrode

Megger is used to find out insulation resistance of electrical machine/equipment

are available for DC voltage of 500V to 2500V.

16 Marks

Credits may be given step wise for numerical problems. In some cases, the assumed e may be some difference in the candidate’s answers

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

)3

(01

010

IV

WCos−=φ

Electrical034.780 =φ

ii) Blocked Rotor Test:

VSC= 100V, ISC =26A

3(1

SC

SCSC

IV

WCos−=φ

ElectricalSC082.67=φ

iii)

SCSC

SN IV

VI ×= )(

AI SN 52= ---------------------

iv) Current Scale:

1 cm = 2.5 A,

v) (To write this procedure to draw circle diagram is not expected

Draw Vector OO/ lag behind V

Draw Vector OA lag behind V

Join O/ A This is output line

Draw Horizontal line O/H.

By Drawing perpendicular b

semi circle having radius CA or C

vi) Power Scale:-

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

) = )52003

350(1

××−Cos

lagElectrical ----------------------------------------------------------

=26A, WSC= 1700 watt

)SCI

= )261003

1700(1

××−Cos

lagElectrical -----------------------------------------------------

= 26)100

200( ×

----------------------------------------------------------------

his procedure to draw circle diagram is not expected)

behind V-Axis by 0φ . This is IO

behind V-Axis by SCφ . This is ISN

This is output line

By Drawing perpendicular bi sector of O/ A, It will inter sect O/H at C. C is the centre of required

CA or C O/

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 27 of 39

------------------------------- (1 Marks)

-------------------------------------------- (1 Marks)

---------------------------------------------------------- (1 Marks)

at C. C is the centre of required

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

SC

SN WV

VW ×= 2)(

1700)100

200( 2 ×=SNW

WattsWSN 6800=

Power Scale = Length

Power Scale = 8

6800

Power Scale = 800

vii) Length of AX in cm=

Output=

800

3730=

viii) Draw line parallel to output line

axis at L. The length of vector OL is 6 cm

∴ Full load current = length of OL in cm X

= 6 cm X 2.5

= 15A ----------

ix) To write the following procedure

Torque Line O/ E bi sects AH

Draw a line tangent to semi circle parallel to torque line at

axis, it will intersect torque line at

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

SCW

1700

Watts

cminAGofLength

WSN

5.8

6800

cmwatts /800 -----------------------------------------

ScalePower

wattinOutput

cm66.4800

3730= --------------------------------------------

Draw line parallel to output line O/ A from point ‘X’, it will intersect the semi circle

. The length of vector OL is 6 cm

load current = length of OL in cm X current scale

= 6 cm X 2.5 A/cm

---------------------------------------------------------------

procedure is not expected

ects AH because stator copper losses = Rotor copper losses

Draw a line tangent to semi circle parallel to torque line at ‘S’ . Drop the perpendicular on

, it will intersect torque line at ‘P’. The Length of ‘SP’ in cm represent maximum torque

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 28 of 39

---------------------------------------------- (1 Marks)

--------------- (1 Marks)

intersect the semi circle near V-

---------------------------------------------------------- (1 Marks)

copper losses

. Drop the perpendicular on ‘X’

resent maximum torque

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

and the vertical length from point

torque

loadfull

Maximum

Maximum torque

x) Power factor = OL

LK

Power factor = 0.92

Circle Diagram:-

b) Given Data:

TA = 100 KVA, RA

TB = 50 KVA, RB

Solutions:-

i) Load carried (Shared) by each Transfor

(KVA)L = 125∠

AAA XRZ +=

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

length from point ‘L’ on torque line i.e. ‘LN’ represents maximum full load

cminLN

cminSP

torque

torqueMaximum = =7.4

2.9

Maximum torque =1.96 (full load torque) --------------

6

5.5=cmin

cmin

0.92 ------------------------------------------------------------

= 0.9%, XA = 6%

= 1%, XB = 5%

Load carried (Shared) by each Transformer

KVA8698.36−∠

69.0 jZ A +=

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 29 of 39

represents maximum full load

------------------------- (1 Marks)

----------------------------------------------------------- (1 Marks)

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

810671.6 ∠=AZ

Let the base impedance to base = 100 KVA

Convert the impedance to base KVA

)51(50

100jZB +=

)51(2 jZB +=

102 jZB += Ohm

781980.10 ∠=BZ

9.0(ZZ BA +=+

9.0( +=+ ZZ BA

9.2 jZZ BA +=+

2602.16=+ BA ZZ

i) Load carried (Shared) by

Transformer A = KVA(

(KVA

(KVA

KVA(

KW(

(

(

Transformer B= KVA(

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

4692.81 Ohm------------------------------------------------------

the base impedance to base = 100 KVA

vert the impedance to base KVA

)5 --------------------------------------------------------------------

Ohm

6900.78 Ohm --------------------------------------------------

)102()6 jj +++

)106()2 +++ j

16j

7266.792602∠ Ohm-------------------------------------------

each Transformer:

BA

BLA ZZ

ZKVAKVA

+×= )() -------------------------

7266.792606.16

6900.781980.108698.36125)

∠∠×−∠=AKVA

0366.16271.08698.36125) −∠×−∠=AKVA

KVAKVA A 9064.373950.78) −∠=

)9064.37().( Cosfp A =∴

lagfp A 7890.0).( =∴ -------------------------------------

AAA fpKVAKW ).()() ×=

7890.03950.78)( ×=AKW

KWKW A 8548.61)( = -----------------------------------

BA

BLB ZZ

ZKVAKVA

+×= )()

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 30 of 39

------------------------------------------------------ (1 Mark)

-------------------------------------------------------------------- (1 Mark)

---------------------------------------- (1/2 Marks)

------------- (1/2 Marks)

------------- (1/2 Marks)

7266

6900

0366

------------------------------------- (1/2 Marks)

-------------- (1 Marks)

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

(KVA

(KVA

KVA(

( p∴

p(∴

B KVAKW ()( =

6395.46)( =BKW

KW B 1453.38)( =

I f load is increased continuously which transformer gets loaded first? Why?

If load is increased continuously,

because Load shared by transformer is directly proportional to KVA r

proportional to its impedance.

transformer ‘B’, while impedance of transformer ‘A’ is less than transformer ‘B’

c) Explain the procedure for cleaning, washing and drying of insulation

vacuum impregnation method of varnishing

Marks and Vaccum impregnation Method Explanation

Following procedure of cleaning, washing and drying of insulation of electric

(Any four point expected)

i) Removal of loose dust by blower, the pressure of forced/suction air should be moderate.

ii) Removal of loose dust by vaccum cleaner,

iii) Dry dust can be removed by soft brush.

iv) Clean open dust/dirt on o

v) Sticky dirt can be removed by fibrous scraper smoothly.

vi) Oily viscous films can be removed with approved petroleum solvent & then cleaned by

cotton cloth.

vii) Particularly ‘H’ Class insulation can be cleaned with fresh water & deterg

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

7266.792606.16

4692.810671.68698.36125)

∠∠×−∠=BKVA

7426.13731.08698.36125) −∠×−∠=BKVA

KVAKVA B 1272.356395.46) −∠= ------------------------

)1272.35(). Cosfp B =

lagfp B 8178.0). = ------------------------------------------

BB fpKVA ).() ×

8178.06395×

KW1453 ------------------------------------------------

f load is increased continuously which transformer gets loaded first? Why?

If load is increased continuously, Transformer ‘A’ will get overloaded first,

because Load shared by transformer is directly proportional to KVA r

proportional to its impedance. The KVA rating of the transformer ‘A’ is greater than

, while impedance of transformer ‘A’ is less than transformer ‘B’

Explain the procedure for cleaning, washing and drying of insulation

vacuum impregnation method of varnishing. (Procedure of cleaning, washing& drying

Marks and Vaccum impregnation Method Explanation-2 Marks & Figure

of cleaning, washing and drying of insulation of electric

(Any four point expected)

Removal of loose dust by blower, the pressure of forced/suction air should be moderate.

Removal of loose dust by vaccum cleaner,

Dry dust can be removed by soft brush.

Clean open dust/dirt on open cables by cotton waste.

Sticky dirt can be removed by fibrous scraper smoothly.

Oily viscous films can be removed with approved petroleum solvent & then cleaned by

Particularly ‘H’ Class insulation can be cleaned with fresh water & deterg

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 31 of 39

------------------------ (1 Marks)

------------------------------------------ (1/2 Marks)

----------------------- (1 Marks)

f load is increased continuously which transformer gets loaded first? Why? ----(1/2 Mark)

will get overloaded first,

because Load shared by transformer is directly proportional to KVA rating and inversely

The KVA rating of the transformer ‘A’ is greater than

, while impedance of transformer ‘A’ is less than transformer ‘B’

Explain the procedure for cleaning, washing and drying of insulation and describe the

Procedure of cleaning, washing& drying-4

2 Marks & Figure - 2 Marks )

of cleaning, washing and drying of insulation of electrical machines:-

Removal of loose dust by blower, the pressure of forced/suction air should be moderate.

Oily viscous films can be removed with approved petroleum solvent & then cleaned by

Particularly ‘H’ Class insulation can be cleaned with fresh water & detergent.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

viii) The cleaning should be done as quick as possible & excess moisture can be cleaned by dry

cloth & machine should be booked dry in oven.

Vacuum impregnation method of varnishing

The procedure to impregnate the winding (insulation):

� This method is similar to hot dip method. In Hot Dip method we can’t be sure whether all

the air spaces (pockets inside) the winding are perfectly impregnated with the varnish or

not.

� In vaccum impregnation all the air is

this if proper baking is done the varnishing is perfect and through.

� The plant consists of a large air tight chamber ‘A’ with a removable lid’B’. The varnish is

stored in Tank ‘C’. The compressor can cr

kg/cm2 in tank A as required.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

The cleaning should be done as quick as possible & excess moisture can be cleaned by dry

cloth & machine should be booked dry in oven.

Vacuum impregnation method of varnishing:

Or equivalent figure

regnate the winding (insulation):-

This method is similar to hot dip method. In Hot Dip method we can’t be sure whether all

the air spaces (pockets inside) the winding are perfectly impregnated with the varnish or

In vaccum impregnation all the air is removed, so varnish occupies all such spaces. After

this if proper baking is done the varnishing is perfect and through.

The plant consists of a large air tight chamber ‘A’ with a removable lid’B’. The varnish is

stored in Tank ‘C’. The compressor can create vaccum or pressure of 1.5 kg/cm

in tank A as required.

OR

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 32 of 39

The cleaning should be done as quick as possible & excess moisture can be cleaned by dry

Or equivalent figure

This method is similar to hot dip method. In Hot Dip method we can’t be sure whether all

the air spaces (pockets inside) the winding are perfectly impregnated with the varnish or

removed, so varnish occupies all such spaces. After

The plant consists of a large air tight chamber ‘A’ with a removable lid’B’. The varnish is

eate vaccum or pressure of 1.5 kg/cm2 to 2

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

The procedure to impregnate the winding (insulation

1. The winding is placed in tank A, and then it is heated up to 100

circulating steam or oil throug

coil.

2. During this process the tank is thoroughly evacuated with the help of compressor, for

heating the water or oil, electrical boiler is used and for the circulation of steam or oil, the

pump is used.

3. The value V’ is now opened and as there is

varnish tank ‘C’ rushes into chamber ‘A’. The inflow of varnish continuous until the

winding or coil to be impregnated is fully immersed into the varnish. The va

closed.

4. Air pressure at 1.5 kg/cm

The varnish is now forced into porous spaces inside the coil.

5. The valve ‘V’ is again opened after about half an hour. The varnish flows bac

tank ‘C’ under the pressure present in the chamber ‘A’. When whole of the varnish goes

back to tank ‘C’ valve ‘V’ is again closed.

6. The coil is then removed and kept in a baking oven for 4 to 8 hours at a temperature of

1000C to1100C. This will

temperature should not be more than 110

Q.6. Attempt any Four of the following

a) Explain the procedure for leveling and alignment of electrical machine.

The following procedure for leveling and alignment of electrical Machine

expected)

i) The motor shaft should be level. The motor shaft cannot be made level unless the shaft of

the driven machine is previously leveled. Therefore the driven shaft is leveled 1

shaft must be in line. In case of belt or gear drives, they must be parallel.

ii) The two shafts must be in line, the two shafts should be on the same centre.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

The procedure to impregnate the winding (insulation):-

The winding is placed in tank A, and then it is heated up to 1000C for 2 to 4 hours by

circulating steam or oil through the jacket. This drives all the moisture and air inside the

During this process the tank is thoroughly evacuated with the help of compressor, for

heating the water or oil, electrical boiler is used and for the circulation of steam or oil, the

The value V’ is now opened and as there is vacuum in the chamber ‘A’ the varnish from

varnish tank ‘C’ rushes into chamber ‘A’. The inflow of varnish continuous until the

winding or coil to be impregnated is fully immersed into the varnish. The va

Air pressure at 1.5 kg/cm2 is applied into the space above the varnish level into the tank.

The varnish is now forced into porous spaces inside the coil.

The valve ‘V’ is again opened after about half an hour. The varnish flows bac

tank ‘C’ under the pressure present in the chamber ‘A’. When whole of the varnish goes

back to tank ‘C’ valve ‘V’ is again closed.

The coil is then removed and kept in a baking oven for 4 to 8 hours at a temperature of

C. This will cause the varnish to set properly and become bone dry. The

temperature should not be more than 1100C otherwise insulation will get damaged.

of the following

Explain the procedure for leveling and alignment of electrical machine.

The following procedure for leveling and alignment of electrical Machine

The motor shaft should be level. The motor shaft cannot be made level unless the shaft of

the driven machine is previously leveled. Therefore the driven shaft is leveled 1

be in line. In case of belt or gear drives, they must be parallel.

ii) The two shafts must be in line, the two shafts should be on the same centre.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 33 of 39

C for 2 to 4 hours by

h the jacket. This drives all the moisture and air inside the

During this process the tank is thoroughly evacuated with the help of compressor, for

heating the water or oil, electrical boiler is used and for the circulation of steam or oil, the

in the chamber ‘A’ the varnish from

varnish tank ‘C’ rushes into chamber ‘A’. The inflow of varnish continuous until the

winding or coil to be impregnated is fully immersed into the varnish. The value ‘V’ is then

is applied into the space above the varnish level into the tank.

The valve ‘V’ is again opened after about half an hour. The varnish flows back to varnish

tank ‘C’ under the pressure present in the chamber ‘A’. When whole of the varnish goes

The coil is then removed and kept in a baking oven for 4 to 8 hours at a temperature of

cause the varnish to set properly and become bone dry. The

C otherwise insulation will get damaged.

16 Marks

Explain the procedure for leveling and alignment of electrical machine.

The following procedure for leveling and alignment of electrical Machine: (Any two points

(4 Marks)

The motor shaft should be level. The motor shaft cannot be made level unless the shaft of

the driven machine is previously leveled. Therefore the driven shaft is leveled 1st that is the

be in line. In case of belt or gear drives, they must be parallel.

ii) The two shafts must be in line, the two shafts should be on the same centre.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

iii) The lining up is checked by making measurements with steel tape, from the centre of the

driven shaft to the centre of the motor shaft.

Procedure of alignment of shaft of electrical machine

The shafts of driven and driving machine are aligned by various methods. The most

common one is the alignment by flexible coupling method.

alignment of the shafts.

i) Axial positioning of the shafts.

ii) Paralleling of shafts axis.

iii) Centering of shaft axis

Procedure of alignment of shaft of electrical machine:

i) Align the motor and the driven mach

under their feet.

ii) Mark both half-coupling by means of chalk line. Make accurate measurement between the

gaps between the faces of the vertical surfaces. Turn the motor shaft through 90

and 3600 and note the reading of the gap.

iii) The excess difference is reduced below 0.05 mm by adjusting the shims.

iv) Likewise the difference in the

by suitable method. One of the method of gauging the gap

coupling and the difference in heights is by using single point turn point Run over Gauge.

b) Prepare trouble shooting chart for 3

Mark each point)

(Note: - Any Four Points from Be

S.No Type of fault 1 Motor fails to start up

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

iii) The lining up is checked by making measurements with steel tape, from the centre of the

ven shaft to the centre of the motor shaft.

OR

Procedure of alignment of shaft of electrical machine

The shafts of driven and driving machine are aligned by various methods. The most

common one is the alignment by flexible coupling method. There are three steps in the

Axial positioning of the shafts.

Paralleling of shafts axis.

Centering of shaft axis

OR

Procedure of alignment of shaft of electrical machine: (Any two points

Align the motor and the driven machine on bed-plate in their final position with shims

coupling by means of chalk line. Make accurate measurement between the

gaps between the faces of the vertical surfaces. Turn the motor shaft through 90

and note the reading of the gap.

The excess difference is reduced below 0.05 mm by adjusting the shims.

Likewise the difference in the highs of axis of drive coupling and driven coupling is gauged

by suitable method. One of the method of gauging the gap between vertical surfaces of

coupling and the difference in heights is by using single point turn point Run over Gauge.

Prepare trouble shooting chart for 3-Ph Induction motor. (Any four points

Any Four Points from Below Are Expected & Not All)

Causes -Open circuit in DOL/Star-delta starter. -Brushes make no contact with slip

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 34 of 39

iii) The lining up is checked by making measurements with steel tape, from the centre of the

The shafts of driven and driving machine are aligned by various methods. The most

are three steps in the

two points expected)

plate in their final position with shims

coupling by means of chalk line. Make accurate measurement between the

gaps between the faces of the vertical surfaces. Turn the motor shaft through 900,1800, 2700

The excess difference is reduced below 0.05 mm by adjusting the shims.

of axis of drive coupling and driven coupling is gauged

between vertical surfaces of

coupling and the difference in heights is by using single point turn point Run over Gauge.

(Any four points expected -1

low Are Expected & Not All)

Remedies

Rectify The Cause.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

2 Motor starts up sluggishly/Excessive speed reduction when motor is loaded

3 Motor hums a) During Stat up b) When running

4 Thermal overload protection operate while motor is running

5 Regular Clicking(short sound)

6 Vibration

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

rings. -Rotor of fan rubbing on stator -Worn contacts of star-delta starter. -Excessive load on starting. -Terminals voltage too low - Supply voltage is too low (Voltage

drop when motor is loaded) - Stator connected in Star instead of

delta. - One motor terminal was by mistake

connected to neutral instead of phase

a)Unequal phase resistance - Open circuit - Or inter turn short circuit on rotor b) Short circuit between turn to turns

or parts of stator winding - Multiple winding to frame short

circuit (earth fault)

-System frequency too high -Excessive core loss -Single phasing i.e O.C. in stator winding or supply cable -Stator winding is incorrectly connected i.e. in star instead of delta -Motor was incorrectly selected for type of duty involved. e.g selecting short time or intermittent duty instead of continuous duty at full load -Inadequate ventilation (i.e cooling system) -Air flow obstructed -Thermal overload protection incorrectly rated or adjusted.

Foreign matter in air gap Remove foreign matter

-Misalignment in coupling or flange -Accumulation of dirt on fan. -Vibration in driven machine

-Realign motor& driven equipment.-Clean motor-Run motor disconnected from driven load & check for visource in driven equipment.-Alter rigidity of base

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 35 of 39

Rectify The Cause.

Rectify The Cause.

Rectify The Cause.

Remove foreign matter

Realign motor& driven equipment. Clean motor Run motor disconnected

from driven load & check for vibration. Eliminate source in driven equipment. Alter rigidity of base

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

7 Motor over heating (Check with thermocouple or by resistance method, do not depend on touch)

8 Bearing Overheating

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

-Twisted base or flange -Excessive end play. -Shaft bent or flange face run out

structure-Check flange alignment and shims.-Adjust end play.-Straighten or replace shaft, Reface or replace housing

-Overload -Single phasing - Dirt in motor - Unbalanced voltage - Rotor rubbing on stator - High ambient -Open Stator winding - Air Recirculation -Over voltage/under voltage - Ground - Improper electrical connections -Heat exchanger tubes blocked

- Measure load & compare with nameplate rating and reduce the load. - Check current all phases- Check flow of air, filters, if so equipped and clean motor.- Check voltage, all phases- Check air gap, repair motor as nece-Check air inlet temperature.- Disconnect motor from load. Check idle amps for balance in all phases, check stator resistance in all phases for balance-Check intake & exhaust for obstructions.-Check voltage and compare to rating plate.- Locateinsulation tester and repair-Recheck electrical connections.Clean tubes, if so equipped

- Oil level too high or low -Misalignment - Excessive end thrust - Too much grease (ball or roller Bearing)

- Correct oil - Realign motor and driven equipment.- Reduce thrust. Recheck mounting & alignment.- Relieve supply to point set by manufacture.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 36 of 39

structure Check flange alignment

and shims. Adjust end play. Straighten or replace shaft,

Reface or replace housing Measure load & compare

with nameplate rating and reduce the load.

Check current all phases Check flow of air, filters,

if so equipped and clean motor.

Check voltage, all phases Check air gap, repair

motor as necessary. Check air inlet

temperature. Disconnect motor from

load. Check idle amps for balance in all phases, check stator resistance in all phases for balance Check intake & exhaust for

obstructions. Check voltage and compare

to rating plate. Locate with test lamp or

insulation tester and repair Recheck electrical

connections. Clean tubes, if so equipped

Correct oil level Realign motor and driven

equipment. Reduce thrust. Recheck

mounting & alignment. Relieve supply to point set

by manufacture.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

c) Explain the procedure for developing preventive maintenance schedule.

The following procedure

Well planed Preventive maintenance

should posses following basic

1. Inspection: What to inspect and how to inspect?

2. Frequencies: How often to inspect?

3. Schedules: When to inspect?

4. Records: What to record and how to record?

� The maintenance engineer shou

conditions and also when it is at rest with good planning and preparation.

� Mainly tests can be made during lunch time recess.

� The maintenance schedule is usually in the form of log sheets on which days, we

months of the year are tabulated.

� The planning of maintenance should be categorized in following ways:

1. Routine maintenance

2. Periodically Maintenance

3. Maintenance of fault as and when the fault occ

(Note: - Any Four Points from Below Are Expected & Not All)

i) Periodic visual inspection of various equipments to locate initial condition leading to

breakdown.

ii) Up keep of equipment and plant & r

iii) Checking of stationary parts.

iv) Checking of movable parts.

v) Checking of working condition of equipment or machinery.

vi) Checking of surrounding in which the machinery or equipment has to work i.e

atmospheric condition.

vii) Checking of safety measures.

viii) Checking of protective device

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Explain the procedure for developing preventive maintenance schedule.

following procedure is carried out for developing preventive maintenance schedule

( One Mark for each procedure point

Preventive maintenance programmed /function/maintenance schedule

should posses following basic aspects

Inspection: What to inspect and how to inspect?

Frequencies: How often to inspect?

Schedules: When to inspect?

Records: What to record and how to record?

OR

The maintenance engineer should be inspect the plant periodically under working

conditions and also when it is at rest with good planning and preparation.

Mainly tests can be made during lunch time recess.

The maintenance schedule is usually in the form of log sheets on which days, we

months of the year are tabulated.

The planning of maintenance should be categorized in following ways:

maintenance

Periodically Maintenance (weekly, fortnightly, monthly, quarterly or half yearly)

Maintenance of fault as and when the fault occurs.

OR

Any Four Points from Below Are Expected & Not All)

Periodic visual inspection of various equipments to locate initial condition leading to

Up keep of equipment and plant & repair defects at their initial s

tionary parts.

Checking of movable parts.

Checking of working condition of equipment or machinery.

Checking of surrounding in which the machinery or equipment has to work i.e

atmospheric condition.

Checking of safety measures.

Checking of protective device.

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 37 of 39

Explain the procedure for developing preventive maintenance schedule.

preventive maintenance schedule :

One Mark for each procedure point)

/function/maintenance schedule

ld be inspect the plant periodically under working

conditions and also when it is at rest with good planning and preparation.

The maintenance schedule is usually in the form of log sheets on which days, weeks,

The planning of maintenance should be categorized in following ways:

(weekly, fortnightly, monthly, quarterly or half yearly)

Any Four Points from Below Are Expected & Not All)

Periodic visual inspection of various equipments to locate initial condition leading to

epair defects at their initial stage.

Checking of surrounding in which the machinery or equipment has to work i.e

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

ix) Checking the list of consumable and non consumable items to be used in the equipments

and machinery.

x) Checking of stores and stored inventory.

xi) Checking of tools, trackless, jacks and fixtures etc.

xii) To attend major breakdown and repairs.

d) What are the precautions to be taken, to avoid fire due to electrical reasons?

Fire due to electric current can be prevented by taking the following precautions:

points expected -1 Mark each point)

1. Use superior quality of material (ISI mark)

2. Well insulated & proper size of wires, cables should be used.

3. By the use of proper rating protective devices with the electrical circuits.

4. Overloading of electrical installation & equipment should be avoided.

5. The joints in the electrical system should mechanically & electri

6. There should not be any loose connection in the electrical installation & these should be

checked periodically.

7. Electrical installation & equipments used in hazards area should be satisfied the

specification/type of protection.

8. Clearances should be maintained as per Voltage level.

9. Avoid use of too many device plugged into a circuit, causing heated wire & possible a

fire.

Draw a neat circuit diagram for performing load test on 415V, 3

connected Squirrel cage induction motor

Marks & Ranges of meter

Full Load Test Circuit Diagram:

a) If generator is coupled with induction motor:

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Checking the list of consumable and non consumable items to be used in the equipments

Checking of stores and stored inventory.

Checking of tools, trackless, jacks and fixtures etc.

To attend major breakdown and repairs.

recautions to be taken, to avoid fire due to electrical reasons?

Fire due to electric current can be prevented by taking the following precautions:

1 Mark each point)

Use superior quality of material (ISI mark)

roper size of wires, cables should be used.

By the use of proper rating protective devices with the electrical circuits.

Overloading of electrical installation & equipment should be avoided.

The joints in the electrical system should mechanically & electrically sound.

There should not be any loose connection in the electrical installation & these should be

checked periodically.

Electrical installation & equipments used in hazards area should be satisfied the

specification/type of protection.

ld be maintained as per Voltage level.

Avoid use of too many device plugged into a circuit, causing heated wire & possible a

Draw a neat circuit diagram for performing load test on 415V, 3-Ph, 4.8A, 3HP, Delta

connected Squirrel cage induction motor. Specify the meter reading.

Marks & Ranges of meter -1 Mark) (Any One Figure is expected)

Full Load Test Circuit Diagram:

If generator is coupled with induction motor:-

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 38 of 39

Checking the list of consumable and non consumable items to be used in the equipments

recautions to be taken, to avoid fire due to electrical reasons?

Fire due to electric current can be prevented by taking the following precautions: (Any four

By the use of proper rating protective devices with the electrical circuits.

Overloading of electrical installation & equipment should be avoided.

cally sound.

There should not be any loose connection in the electrical installation & these should be

Electrical installation & equipments used in hazards area should be satisfied the

Avoid use of too many device plugged into a circuit, causing heated wire & possible a

Ph, 4.8A, 3HP, Delta

. Specify the meter reading. (Circuit diagram -3

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Subject Code: 12231

Range Of Meters: AC Side:-

1) Voltmeter = 0 to 600V, 2) Ammeter =

Range Of Meters: D.C Side:

1) Voltmeter = 0 to 300V,

b) If Brake arrangement is used

Range Of Meters: AC Side:-

1) Voltmeter = 0 to 600V, 2) Ammeter =

------------------------------------------

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD(Autonomous)

(ISO/IEC-27001-2005 Certified)

SUMMER – 13 EXAMINATION

Model Answer

Or equivalent figure

- (Note : Nearest standard rating may be consider )

600V, 2) Ammeter = 0 to 5A 3) Wattmeter = 5A, 600V

Range Of Meters: D.C Side:- (Note : Nearest standard rating may be consider )

300V, 2) Ammeter = 0 to 5A

OR Brake arrangement is used:-

Or equivalent figure-

600V, 2) Ammeter = 0 to 5A 3) Wattmeter = 5A, 600V

--------------------------------------------------------END---------------------------------------------------------

MAHARASHTRA STATE BOARAD OF TECHNICAL EDUCATIOD

Page No: 39 of 39

Or equivalent figure

(Note : Nearest standard rating may be consider )

3) Wattmeter = 5A, 600V

(Note : Nearest standard rating may be consider )

Or equivalent figure

5A 3) Wattmeter = 5A, 600V

---------------------------------