Master Examination Practice Drill #6 2011
![Page 2: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/2.jpg)
O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at LEAST ______ inside the fountain, when measuring from the outside edges of the fountain.A. 2 feetB. 3 feetC. 4 feetD. 5 feet
![Page 3: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/3.jpg)
O 1. D
O 680.57(C)(1)
![Page 4: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/4.jpg)
O In an aircraft hanger, the area that extends upward from the floor level ________ above the upper surface of aircraft wings, power plants and fuel tanks shall be classified as a Class I, Division 2 or Zone 2 location.A. 5 feetB. 6 feetC. 8 feetD. 10 feet
![Page 5: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/5.jpg)
O 2. A
O 513.3
![Page 6: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/6.jpg)
O Conductors supplying outlets for arc and xenon motion picture projectors of the professional type shall be a MINIMUM size of __________.A. 12 AWGB. 10 AWGC. 8 AWGD. 6 AWG
![Page 7: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/7.jpg)
O 3. C
O 540.13
![Page 8: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/8.jpg)
O Where rigid polyvinyl chloride (PVC) conduit is installed underground to supply a gasoline dispensing unit, threaded rigid metal conduit (RMC) or threaded intermediate metal conduit (IMC) shall be used for the LAST ______ of the underground run to where the conduit emerges.A. 2 feetB. 4 feetC. 5 feetD. 6 feet
![Page 9: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/9.jpg)
O 4. A
O 514.8, Ex. 2
![Page 10: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/10.jpg)
O Where electrical metallic tubing (EMT) is installed under metal-corrugated sheet roofing decking, a clearance of at LEAST _____ must be maintained between the top of the tubing and the surface of the roof decking.A. 1 in.B. 1 ¼ inC. 1 ½ in.D. 2 in.
![Page 11: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/11.jpg)
O 5. C
O 300.4(E)
![Page 12: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/12.jpg)
O After applying all demand factors, the ampacity of the service-entrance conductors are required to be NOT less than _____ where both the overcurrent device and its assembly are not listed for operation at 100 percent of their rating.A. 125 percent of the loads on the branch
circuitsB. The sum of the loads on the branch
circuitsC. The sum of the noncontinuous loads
plus 125 percent of the continuous loads
D. The sum of all branch-circuit overcurrent protection devices.
![Page 13: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/13.jpg)
O 6. C
O 230.42(A)(1)
![Page 14: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/14.jpg)
O The demand factor of any electrical system is the ratio of the maximum demand for a system to:A. The totally connected load of the
system.B. 125% of the total connected load
of the system.C. 125% of the total connected
continuous load of the system.D. 80% of the total connected
noncontinuous load plus 125% of the total connected continuous-load of the system.
![Page 15: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/15.jpg)
O 7. A
O Article 100
![Page 16: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/16.jpg)
O The accessible portion of abandoned supply circuits and interconnecting cables located in an information technology equipment room shall be removed, UNLESS _________.A. Tagged and identified as abandonedB. Identified as Type CMPC. Contained in a racewayD. Disconnected from their supply
source
![Page 17: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/17.jpg)
O 8. C
O 645.5(G)
![Page 18: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/18.jpg)
O A residential branch circuit is to supply two (2) wall-mounted ovens rated at 4 kW each and one (1) 6 kW counter-mounted cooktop. Where all the equipment is 240 volts, single-phase, the branch-circuit conductors supplying this kitchen equipment shall have an ampacity of at LEAST __________.A. 22 amperesB. 27 amperesC. 33 amperesD. 37 amperes
![Page 19: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/19.jpg)
O 9. DO T220.55 Note 4 Treat as one unitO 6kw+4kw+4kw= 14kwO 14-12=2x5=10 O 8000 x 1.10= 8800 watts/ 240V=
36.7 A
![Page 20: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/20.jpg)
O On ac circuits, an ac general-use snap switch may be used for controlling a stationary motor rated 2 hp or less, if 300 volts or less, NOT exceeding _________ of the ampere rating of the switch at its rated voltage.A. 50 percentB. 80 percentC. 115 percentD. 125 percent
![Page 21: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/21.jpg)
O 10. B
O 430.83(C)(2)
![Page 22: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/22.jpg)
O What MINIMUM size THWN copper conductors are required to supply a continuous-duty, 25 hp, 208-volt, 3-phase motor? Given: The motor is on the end of a short conduit run that contains only three (3) conductors, at an ambient temperature of 50°C. Consider the motor termination to be rated for 75°CA. 6 AWGB. 3 AWGC. 2 AWGD. 1 AWG
![Page 23: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/23.jpg)
O 11. D
O T430.250O 430.22O T 310.15(B)(16)O 74.8 x 1.25= 93.5 AO 93.5 / .75 ( Temp Correction)= 124.6
AO Use the 75C col.
![Page 24: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/24.jpg)
O Which of the following statements regarding busways is/are true? Busways shall not be installed _________.A. Where subject to severe physical
damageB. Outdoors or in wet or damp
locations unless identified for such use
C. In hoistwaysD. All of the above are true.
![Page 25: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/25.jpg)
O 12. D
O 368.12(A), (B) and (D)
![Page 26: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/26.jpg)
O Which of the following shall be installed on the critical branch of the emergency system in a health care facility?A. Exit signsB. Nurse call systemsC. Communication systemsD. Fire alarms
![Page 27: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/27.jpg)
O 13. B
O 517.33 (A)(5)
![Page 28: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/28.jpg)
O The emergency controls for attended self-service gasoline stations and convenience stores with motor fuel dispensers must be located NOT more than ________ from the motor fuel dispensers.A. 20 feetB. 50 feetC. 75 feetD. 100 feet
![Page 29: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/29.jpg)
O 14. D
O 514.11(B)
![Page 30: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/30.jpg)
O Which of the following listed wiring methods is not approved for use in assembly locations, UNLESS encased in concrete?A. EMTB. Schedule 80 PVCC. Type MC cableD. Type AC cable
![Page 31: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/31.jpg)
O 15. B
O 518.4(A)
![Page 32: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/32.jpg)
O Where transformer vaults are not protected with an automatic fire-suppression system, they shall be constructed of materials that have a MINIMUM fire-resistance rating of __________.A. 1 hourB. 2 hoursC. 3 hoursD. 4 hours
![Page 33: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/33.jpg)
O 16. C
O 450.42
![Page 34: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/34.jpg)
O What percent of electrical supplied spaces in a recreational vehicle park must have 30-ampere, 125-volt receptacle outlets provided?A. 60 percentB. 70 percentC. 90 percentD. 100 percent
![Page 35: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/35.jpg)
O 17. B
O 551.71
![Page 36: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/36.jpg)
O What is the MINIMUM bend radius of trade size 4 in. rigid metal conduit (RMC) where the bend is not made with a one-shot or full-shoe bender?A. 16 inchesB. 18 inchesC. 24 inchesD. 30 inches
![Page 37: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/37.jpg)
O 18. C
O Cpt. 9, Table 2
![Page 38: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/38.jpg)
O Type AC cable shall NOT be used _______.A. In lengths of more than 6 ft.B. In cable traysC. As concealed feedersD. Where embedded in plaster in
wet locations.
![Page 39: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/39.jpg)
O 19. D
O 320.12(5)
![Page 40: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/40.jpg)
O Where portions of a cable, raceway or sleeve are known to be subjected to different temperatures and where condensation is known to be a problem, the raceway or sleeve shall ________.A. Be filled with an approved
materialB. Have an explosionproof sealC. Be provided with a drainD. Be installed below the level of
the terminations.
![Page 41: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/41.jpg)
O 20. A
O 300.7(A)
![Page 42: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/42.jpg)
O What is the MINIMUM size 75°C copper service-entrance conductors require for a 200 ampere rated commercial service?A. 4/0 THWB. 2/0 THW C. 3/0 THHND. 3/0 THW
![Page 43: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/43.jpg)
O 21. D
O T310.15(B)(16)
![Page 44: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/44.jpg)
O Determine the MINIMUM size THWN copper feeder conductors required by the NEC® to supply the following 480-volt, continuous duty, 3-phase, induction type, Design B, motors. Motor terminations are assumed to be rated at 75 degrees C. 1 – 40 hp1 – 50 hp1 – 60 hp
A. 2/0 AWGB. 3/0 AWGC. 4/0 AWGD. 250 kcmil
![Page 45: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/45.jpg)
O 22. CO 77 x 1.25= 96+65+52= 213 A
O Use 75C column of T310.15(B)(16)
![Page 46: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/46.jpg)
O Two (2) or more motors may be installed without individual overcurrent protection devices if rated less than 1 hp each, and the full-load current rating of each motor does NOT exceed __________, if they are on a 120-volt, 20 ampere branch circuit.A. 2 amperesB. 4 amperesC. 5 amperesD. 6 amperes
![Page 47: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/47.jpg)
O 23. D
O 430.53(A)(1)
![Page 48: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/48.jpg)
O Where a listed packaged spa or hot tub is installed outdoors, the unit is permitted to be cord-and-plug connected, provided the cord is NOT longer than _______ and protected by a GFCI.A. 6 feetB. 10 feetC. 15 feetD. 20 feet
![Page 49: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/49.jpg)
O 24. C
O 680.42(A)(2)
![Page 50: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/50.jpg)
O Given: A three-phase, 480-volt, 100 ampere noncontinuous load is located 390 feet from a panelboard. What MINIMUM size THWN aluminum feeder conductors are required to limit the voltage drop to 3 percent?
(K= 21.2)A. 2 AWGB. 1 AWGC. 1/0 AWGD. 2/0 AWG
![Page 51: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/51.jpg)
O 25. CO 3% of 480V = 14.4
O 1.732KDI / Max. Allowed VD= CMO 1.732 x 21.2 x 100 x 390 / 14.4= 99446 CM
![Page 52: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/52.jpg)
Click Here to Advance to Non Timed Slides
![Page 53: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/53.jpg)
O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at LEAST ______ inside the fountain, when measuring from the outside edges of the fountain.A. 2 feetB. 3 feetC. 4 feetD. 5 feet
![Page 54: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/54.jpg)
O 1. D
O 680.57(C)(1)
![Page 55: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/55.jpg)
O In an aircraft hanger, the area that extends upward from the floor level ________ above the upper surface of aircraft wings, power plants and fuel tanks shall be classified as a Class I, Division 2 or Zone 2 location.A. 5 feetB. 6 feetC. 8 feetD. 10 feet
![Page 56: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/56.jpg)
O 2. A
O 513.3
![Page 57: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/57.jpg)
O Conductors supplying outlets for arc and xenon motion picture projectors of the professional type shall be a MINIMUM size of __________.A. 12 AWGB. 10 AWGC. 8 AWGD. 6 AWG
![Page 58: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/58.jpg)
O 3. C
O 540.13
![Page 59: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/59.jpg)
O Where rigid polyvinyl chloride (PVC) conduit is installed underground to supply a gasoline dispensing unit, threaded rigid metal conduit (RMC) or threaded intermediate metal conduit (IMC) shall be used for the LAST ______ of the underground run to where the conduit emerges.A. 2 feetB. 4 feetC. 5 feetD. 6 feet
![Page 60: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/60.jpg)
O 4. A
O 514.8, Ex. 2
![Page 61: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/61.jpg)
O Where electrical metallic tubing (EMT) is installed under metal-corrugated sheet roofing decking, a clearance of at LEAST _____ must be maintained between the top of the tubing and the surface of the roof decking.A. 1 in.B. 1 ¼ inC. 1 ½ in.D. 2 in.
![Page 62: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/62.jpg)
O 5. C
O 300.4(E)
![Page 63: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/63.jpg)
O After applying all demand factors, the ampacity of the service-entrance conductors are required to be NOT less than _____ where both the overcurrent device and its assembly are not listed for operation at 100 percent of their rating.A. 125 percent of the loads on the branch
circuitsB. The sum of the loads on the branch
circuitsC. The sum of the noncontinuous loads
plus 125 percent of the continuous loads
D. The sum of all branch-circuit overcurrent protection devices.
![Page 64: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/64.jpg)
O 6. C
O 230.42(A)(1)
![Page 65: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/65.jpg)
O The demand factor of any electrical system is the ratio of the maximum demand for a system to:A. The totally connected load of the
system.B. 125% of the total connected load
of the system.C. 125% of the total connected
continuous load of the system.D. 80% of the total connected
noncontinuous load plus 125% of the total connected continuous-load of the system.
![Page 66: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/66.jpg)
O 7. A
O Article 100
![Page 67: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/67.jpg)
O The accessible portion of abandoned supply circuits and interconnecting cables located in an information technology equipment room shall be removed, UNLESS _________.A. Tagged and identified as abandonedB. Identified as Type CMPC. Contained in a racewayD. Disconnected from their supply
source
![Page 68: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/68.jpg)
O 8. C
O 645.5(G)
![Page 69: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/69.jpg)
O A residential branch circuit is to supply two (2) wall-mounted ovens rated at 4 kW each and one (1) 6 kW counter-mounted cooktop. Where all the equipment is 240 volts, single-phase, the branch-circuit conductors supplying this kitchen equipment shall have an ampacity of at LEAST __________.A. 22 amperesB. 27 amperesC. 33 amperesD. 37 amperes
![Page 70: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/70.jpg)
O 9. DO T220.55 Note 4 Treat as one unitO 6kw+4kw+4kw= 14kwO 14-12=2x5=10 O 8000 x 1.10= 8800 watts/ 240V=
36.7 A
![Page 71: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/71.jpg)
O On ac circuits, an ac general-use snap switch may be used for controlling a stationary motor rated 2 hp or less, if 300 volts or less, NOT exceeding _________ of the ampere rating of the switch at its rated voltage.A. 50 percentB. 80 percentC. 115 percentD. 125 percent
![Page 72: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/72.jpg)
O 10. B
O 430.83(C)(2)
![Page 73: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/73.jpg)
O What MINIMUM size THWN copper conductors are required to supply a continuous-duty, 25 hp, 208-volt, 3-phase motor? Given: The motor is on the end of a short conduit run that contains only three (3) conductors, at an ambient temperature of 50°C. Consider the motor termination to be rated for 75°CA. 6 AWGB. 3 AWGC. 2 AWGD. 1 AWG
![Page 74: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/74.jpg)
O 11. D
O T430.250O 430.22O T 310.15(B)(16)O 74.8 x 1.25= 93.5 AO 93.5 / .75 ( Temp Correction)= 124.6
AO Use the 75C col.
![Page 75: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/75.jpg)
O Which of the following statements regarding busways is/are true? Busways shall not be installed _________.A. Where subject to severe physical
damageB. Outdoors or in wet or damp
locations unless identified for such use
C. In hoistwaysD. All of the above are true.
![Page 76: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/76.jpg)
O 12. D
O 368.12(A), (B) and (D)
![Page 77: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/77.jpg)
O Which of the following shall be installed on the critical branch of the emergency system in a health care facility?A. Exit signsB. Nurse call systemsC. Communication systemsD. Fire alarms
![Page 78: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/78.jpg)
O 13. B
O 517.33 (A)(5)
![Page 79: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/79.jpg)
O The emergency controls for attended self-service gasoline stations and convenience stores with motor fuel dispensers must be located NOT more than ________ from the motor fuel dispensers.A. 20 feetB. 50 feetC. 75 feetD. 100 feet
![Page 80: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/80.jpg)
O 14. D
O 514.11(B)
![Page 81: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/81.jpg)
O Which of the following listed wiring methods is not approved for use in assembly locations, UNLESS encased in concrete?A. EMTB. Schedule 80 PVCC. Type MC cableD. Type AC cable
![Page 82: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/82.jpg)
O 15. B
O 518.4(A)
![Page 83: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/83.jpg)
O Where transformer vaults are not protected with an automatic fire-suppression system, they shall be constructed of materials that have a MINIMUM fire-resistance rating of __________.A. 1 hourB. 2 hoursC. 3 hoursD. 4 hours
![Page 84: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/84.jpg)
O 16. C
O 450.42
![Page 85: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/85.jpg)
O What percent of electrical supplied spaces in a recreational vehicle park must have 30-ampere, 125-volt receptacle outlets provided?A. 60 percentB. 70 percentC. 90 percentD. 100 percent
![Page 86: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/86.jpg)
O 17. B
O 551.71
![Page 87: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/87.jpg)
O What is the MINIMUM bend radius of trade size 4 in. rigid metal conduit (RMC) where the bend is not made with a one-shot or full-shoe bender?A. 16 inchesB. 18 inchesC. 24 inchesD. 30 inches
![Page 88: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/88.jpg)
O 18. C
O Cpt. 9, Table 2
![Page 89: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/89.jpg)
O Type AC cable shall NOT be used _______.A. In lengths of more than 6 ft.B. In cable traysC. As concealed feedersD. Where embedded in plaster in
wet locations.
![Page 90: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/90.jpg)
O 19. D
O 320.12(5)
![Page 91: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/91.jpg)
O Where portions of a cable, raceway or sleeve are known to be subjected to different temperatures and where condensation is known to be a problem, the raceway or sleeve shall ________.A. Be filled with an approved
materialB. Have an explosionproof sealC. Be provided with a drainD. Be installed below the level of
the terminations.
![Page 92: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/92.jpg)
O 20. A
O 300.7(A)
![Page 93: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/93.jpg)
O What is the MINIMUM size 75°C copper service-entrance conductors require for a 200 ampere rated commercial service?A. 4/0 THWB. 2/0 THW C. 3/0 THHND. 3/0 THW
![Page 94: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/94.jpg)
O 21. D
O T310.15(B)(16)
![Page 95: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/95.jpg)
O Determine the MINIMUM size THWN copper feeder conductors required by the NEC® to supply the following 480-volt, continuous duty, 3-phase, induction type, Design B, motors. Motor terminations are assumed to be rated at 75 degrees C. 1 – 40 hp1 – 50 hp1 – 60 hp
A. 2/0 AWGB. 3/0 AWGC. 4/0 AWGD. 250 kcmil
![Page 96: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/96.jpg)
O 22. CO 77 x 1.25= 96+65+52= 213 A
O Use 75C column of T310.15(B)(16)
![Page 97: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/97.jpg)
O Two (2) or more motors may be installed without individual overcurrent protection devices if rated less than 1 hp each, and the full-load current rating of each motor does NOT exceed __________, if they are on a 120-volt, 20 ampere branch circuit.A. 2 amperesB. 4 amperesC. 5 amperesD. 6 amperes
![Page 98: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/98.jpg)
O 23. D
O 430.53(A)(1)
![Page 99: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/99.jpg)
O Where a listed packaged spa or hot tub is installed outdoors, the unit is permitted to be cord-and-plug connected, provided the cord is NOT longer than _______ and protected by a GFCI.A. 6 feetB. 10 feetC. 15 feetD. 20 feet
![Page 100: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/100.jpg)
O 24. C
O 680.42(A)(2)
![Page 101: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/101.jpg)
O Given: A three-phase, 480-volt, 100 ampere noncontinuous load is located 390 feet from a panelboard. What MINIMUM size THWN aluminum feeder conductors are required to limit the voltage drop to 3 percent?
(K= 21.2)A. 2 AWGB. 1 AWGC. 1/0 AWGD. 2/0 AWG
![Page 102: Master Examination Practice Drill #6 2011 O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at](https://reader038.vdocuments.net/reader038/viewer/2022103123/56649d8d5503460f94a754cf/html5/thumbnails/102.jpg)
O 25. CO 3% of 480V = 14.4
O 1.732KDI / Max. Allowed VD= CMO 1.732 x 21.2 x 100 x 390 / 14.4= 99446 CM