meeting the new selective coordination code requirements · published fuse selective coordination...
TRANSCRIPT
The Bussmann®
Coordination Module™
Saves You Time & MoneyBy Providing An All-In-One Solution• Meets New 2005 Code
Complies with the new 2005 NEC® Selective CoordinationRequirements for Emergency, Legally Required Standby andEssential Electrical Systems per 700.27, 701.18, and 517.26.
Per the 2005 NEC®: Coordination (Selective) is the localizationof an overcurrent condition to restrict outages to the circuit or equipment affected, accomplished by the choice ofovercurrent protective devices and their ratings or settings.
• Increases SafetyThe objective of the new selective coordination requirementsis to ensure system uptime with the goal of safety of humanlife during emergencies or for essential health care functions.The Coordination Module™ meets this objective by providingreliable current-limiting operation to minimize the effects of anoutage to the smallest portion of the system as possible.
• Saves TimeThe Coordination Module™ provides a fast and easy solutionto meeting new coordination Code requirements. Simply utilizepublished fuse selective coordination ratios to select the correct upstream fuse ratings. In addition, locate open fusesfast with the Class CC easyID™ neon indicator.
• Saves MoneyOffers significant savings compared to other fused panels and selectively coordinated circuit breaker systems.
Meeting The NewSelective CoordinationCode Requirements Is Easy
Coordination Module™ Specifications
Coordination Module* Main Device Branch CircuitCatalog Voltage Short Circuit Amp Amp Number ofNumbers Rating Rating Dimensions Type Rating Rating Circuits
EP2M23012GCC 120/208 100kA** 28" W X 36" H X 5.75" D MLO 200 30 12EP2M23024GCC 120/208 100kA** 28" W X 36" H X 5.75" D MLO 200 30 24EP2M23036GCC 120/208 100kA** 28" W X 48" H X 5.75" D MLO 200 30 36EP2M23042GCC 120/208 100kA** 28" W X 48" H X 5.75" D MLO 200 30 42EP4M23012GCC 277/480 100kA*** 28" W X 36" H X 5.75" D MLO 200 30 12EP4M23024GCC 277/480 100kA*** 28" W X 36" H X 5.75" D MLO 200 30 24EP4M23036GCC 277/480 100kA*** 28" W X 48" H X 5.75" D MLO 200 30 36EP4M23042GCC 277/480 100kA*** 28" W X 48" H X 5.75" D MLO 200 30 42
* Meets UL 67 (Panelboards) and UL 50 (Cabinets and Boxes).
** When protected by upstream LPN-RK 100A max, LPJ 200A max or JJN 200A max, otherwise 10kA.
*** When protected by upstream LPS-RK 200A max, LPJ 200A max or JJS 200A max, otherwise 14kA.
Ground BarBolted with set screw terminations.
200A Copper Main Bus
12 to 42 Circuits
120/208V or 277/480V Main LugsWith AGW 6-300Kcmil terminations.
Branch Circuit BreakersProvide circuit isolation.
NEMA Type 1 EnclosureWith surface mount trim.
Class CC Fuse Holders With easyID Neon IndicatorProvides ease of coordination with superior overcurrent protection and open fuse indication.
Full-Sized Neutral BarWith set-screw terminations.
©2005 Cooper Bussmann • St . Louis, MO 63178636-394-2877 • www.bussmann.com
Reorder # 3115 1-05-5M