 : . - - - - : . . Inverter Series R410A N E W ! SPLIT -TYPE AIR CONDITIONERS L-179-13-MD034-A SI-1308 Printed in Japan(MDOC) New publication effective August. 2013 Specifications subject to change without notice. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN http://Global.MitsubishiElectric.com  

Upload: denise-koh-chin-hui

Post on 09-Oct-2015

636 views

Category:

Documents


29 download

DESCRIPTION

vrf

TRANSCRIPT

  • L-179-13-MD034-A SI-1308 Printed in Japan(MDOC)New publication effective August. 2013

    Specifications subject to change without notice.

    HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANhttp://Global.MitsubishiElectric.com

    Inverter Series

    R410A

    NEW!

    SPLIT-TYPE AIR CONDITIONERS

    L-179-13-MD034-A SI-1308 Printed in Japan(MDOC)New publication effective August. 2013

    Specifications subject to change without notice.

    HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANhttp://Global.MitsubishiElectric.com

    Inverter Series

    R410A

    NEW!

    SPLIT-TYPE AIR CONDITIONERS

  • Outdoor unit

    Inverter Series 01-02

    4hp3hp2.5hp2hp

    PRODUCT LINE-UPRemote controller

    Ceiling-cassette

    Ceiling-suspended

    Ceiling-concealed

    PLY

    PCY

    PEY

    INVERTER TECHNOLOGIESMitsubishi Electric inverters ensure superior performance including the optimum control of operation frequency. As a result, optimum power is applied in all heating/cooling ranges and maximum comfort is achieved while consuming minimal energy. Fast, comfortable operation and amazingly low running cost Thats the Mitsubishi Electric promise.

    Inverters electronically control the electrical voltage, current and frequency of electrical devices such as the compressor motor in an air conditioner. They receive information from sensors monitoring operat-ing conditions, and adjust the revolution speed of the compressor, which directly regulates air condi-tioner output. Optimum control of operation frequency results in eliminating the consumption of excessive electricity and providing the most comfortable room environment.

    INVERTERS HOW THEY WORK

    Simple comparison of air conditioner operation control with inverter and Non-inverter.

    Non-inverter air conditioner repeats working and stopping operation to keep room temperature. Therefore, it brings lower energy-saving and uncomfortable operation.

    TRUE COMFORT

    Inverter Operation Image

    PAM

    Conventionalinverter

    Merits of PAM Control Power increasedEfficient voltage increase realises increased power

    Significant energy savingsRemarkable reduction in power loss saves electricity

    Limited powerInsufficient power when needed

    Limited energy savingsElectricity is wasted

    Without PAM control With PAM controlSupplyvoltage

    CurrentTime

    Time

    PAM adjusts the form of the current wave so that it becomes close to that of the supply voltage wave. High harmonics are reduced and 98% of the electricity is utilized.

    Magnetic torque+

    Reluctance torque

    DC compressor motor ( rotor )

    Neodymiummagnets

    PLY-P24BAPLY-P18BA PLY-P30BA PLY-P36BA optional

    PCY-P24KAPCY-P18KA PCY-P30KA PCY-P36KA optionaloptional

    optionalPEY-P24JAPEY-P18JA

    SUY-KA18VA

    PEY-P30JA PEY-P36JA

    SUY-KA24VA SUY-KA30VA SUY-KA36VA

    optional

    Joint Lap DC Motor

    Mitsubishi Electric has developed a unique motor, called the Poki-Poki Motor in Japan, which is manufac-tured using a joint lapping technique. This innovative motor operates based on a high-density, high-mag-netic force, leading to extremely high efficiency and reliability.

    Rare Earth Magnet Rotor (Compressor)

    An innovative motor with a rare earth magnet rotor is equipped in the compressor to ensure excellent efficiency. The rare earth magnet has a residual magnetic flux density threefold that of the previously used ferrite magnet.

    Grooved Piping

    High-performance grooved piping is used in heat exchangers to increase the heat exchange area.

    PAM (Pulse Amplitude Modulation)

    DC Fan Motor

    A highly efficient DC motor drives the fan of the outdoor unit. Efficiency is much higher than an equivalent AC motor.

    Reluctance DC Rotary Compressor

    Powerful neodymium magnets are used in the rotor of the reluctance DC motor. More efficient operation is realised by strong mag-netic and reluctance torques produced by the magnets. (SUY-KA24/30/36VA Only)

    Grooved piping

    Cross-sectional viewPipe image

    PAM is a technology that controls the current waveform so that it resembles the supply voltage wave, thereby reducing loss and realising more efficient use of elec-tricity. Using PAM control, 98% of the input power supply is used effectively.

    Change in room temperature

    Optimum Control of frequencykeeps preset room temperature

    Inverter air conditioner

    TimeCompressor operation

    Minimum power operation

    Constant room temperature

    Pre

    set

    tem

    per

    atur

    e

    Compressor operation

    Change in room temperature

    On/off operation of compressor keeps room temperature

    Non-inverter air conditioner

    ON

    Time

    Full power

    getting too hot getting too cool

    Pre

    set

    tem

    per

    atur

    e

    ON ONOFF OFF

  • SERIESPLYSERIES

    Advancements in PLY series improve style and performance for ensured indoor comfort

    Wide Airflow

    Wide-angle outlets distribute air-flow to all corners of the room, en-suring the room is sufficiently cooled/heated. Horizontal airflow and a fan speed reduced by 20% compared to conventional models also contribute to increased com-fort for occupants.

    Conventional model

    PLY-PBA

    Less Cold Draft

    The horizontal airflow function prevents cold drafts from striking the body directly, thereby keep-ing the body from becoming over-chilled.

    Automatic air-speed adjustment

    An automatic air speed adjustment mode is provided in addition to the four air-speed stages, of High, Medium 1, Medium 2, and Low. Air speed can be changed freely in accordance with a difference between the set temperature and the room temperature. The auto-matic air speed adjustment mode offers quick cooling of a room in high mode, such as at the starting up of cooling operation. After the room temperature is stabilized, the low mode will be applied automatically to maintain comfort.

    Automatic vane shutter*

    When the air conditioner is not operating, the vane shutter closes automatically to conceal the air outlet and create an aesthetically appealing flat surface.

    Unit height of only 258mm (PLY-P18/24BA)

    The high-power ceiling cas-settes offer a wide-flow air outlet that enables effective air conditioning of rooms with atrium ceilings up to 4.5m in height. The de-mands of high-ceiling applications such as halls, showrooms or shopping malls can now be fully answered thanks to this powerful yet highly effi-cient airflow.

    Wide-flow air outlet

    Pure White color harmonized with the interior dcor

    A "Pure White" color is adopted for the decoration panel and wired remote controller so as to blend with any interior dcor.

    Ceiling cassette models boast a slim body height for smooth and aes-thetic installation even in narrow plenum spaces.

    Quiet Operation

    An improved airflow path and powerful high-capacity flow fan contribute to the realisation of quieter operation.

    Power flow fan

    Other Features

    Maximum upward draining of 850mmWireless remote controller availableDuct flange for Fresh-air IntakeBranch duct

    Automatic Grille LoweringFunction (Option)

    Easy to use/Simple maintenanceAn automatic grille lowering function capable of stopping at eight different heights is avail-able to simplify filter maintenance.

    (comes with the automatic elevation panel)

    1.2m

    1.6m

    2.0m

    2.4m

    2.8m

    3.2m

    3.6m

    4.0m

    Automaticelevation to

    4.0m

    The i-see Sensor built into the optional corner panel eliminates uneven temperature distribution and reduces electricity consumption.

    The i-see Sensor temperature-sensing technology improves energy efficiency and enhances room comfort

    The i-see Sensor is an innovative Mitsubishi Electric technology that uses a radiation-based sensor to monitor temperature through-out an entire room. When connected to the air conditioner control panel, the i-see Sensor works to maximize room comfort.

    The i-see Sensor rotates 90 at intervals of 5sec,accurately measuring the temperature throughoutthe room (covering entire floor space).

    i-see Sensor Operation

    90rotation

    90rotation

    90rotation

    5secmeasurement

    5secmeasurement

    5secmeasurement

    5secmeasurement

    Sensible temperature control prevents excessive cooling through pioneering control technologyBy measuring the inlet temperature and floor temperature, tempera-tures felt by the human body (sensible temperature) will be com-puted. This allows the proper sensible temperature to always be maintained through the suppression of excessive cooling.

    Elevating (up-down) controller

    optional

    PLY-P18/24/30/36BA

    (i-see Sensor: optional)

    Inverter Series 03-04

    4-way Ceiling Cassette

    HighLow Automatic air- speed adjustmentMedium 2 Medium 1

    *This feature will not activate when the vane is set at the fixed position.

    (When using the wireless remote controller, an extra setting is required.)

    Vane shutter closes automatically

    During operation When turned off

    PLY-P18/24BA

    PLY-P30/36BA

    PLY-P18/24BA PLY-P30/36BA

    If required to set Low Ceiling Mode in a high humidity condition, please consult with dealers since there is some risk of condensation.

    3-way 2.7 3.0 3.0 3.6 4.53.5

    4-way 2.5 2.7 2.7 3.2 4.53.5

    Specification according to ceiling height

    (PLY-P30/36BA)

    Horizontal airflow prevents drafty feeling

    (optional corner panel)

    The i-see Sensor automatically controls over-coolingby detecting the optimum temperatures.

    Fixed condition Fixed condition

    Temperature set at 26 27C, without the i-see Sensor

    Temperature set at 28C, with i-see Sensor and automatic air-speed adjustment mode

    Felt temperature: 26.5C Felt temperature: 28C

    32C

    23C

    14C

    28C

    30 minutes

    26.5C

    Inlet temperature

    Floor temperatureFelt temperature

    28 C

    30 minutes

    26.5 CInlet temperature

    Floor temperatureFelt temperature

    No drops in felt temperature

    Fixed condition Fixed condition

    Felt temperature drops

    Example When you want the felt temperature to be 28C.

    With optional i-see Sensor corner panel

    The felt temperature drops according to the drop in floor-level temperature. If the floor-level temperature is not monitored during long cooling operation, the felt temperature becomes chilly.

    Air temperature is adjusted according to the floor temperature to keep the felt temperature at 28C.

  • PCYSERIESSERIES

    A stylish indoor unit design and airflow settings for both high- and low-ceiling interiors expand installation possibilities

    Stylish Indoor Unit Design

    A stylish square-like design is adopted for the indoor units of all models. As a result, the units blend in better with the ceiling.

    PC-GAKD

    PCY-PKAOptional Drain Pump for Full-capacity Models

    The pumping height of the optional drain pump has been increased from 400mm to 600mm, expanding flexibility in choosing unit location during installation work.

    Drainage outlet canbe 600mm aboveceiling surface

    Drain pump installationpossible

    Ceilingsurface

    Equipped with Automatic Air-speed Adjustment

    In addition to the conventional 4-speed setting, units are now equipped with an automatic air-speed adjustment mode. This setting automatically adjusts the air-speed to conditions that match the room environment. At the start of cooling operation, the airflow is set to high-speed to quickly cool the room. When the room temperature reaches the desired setting, theairflow speed is decreased automatically for stable comfort-able cooling operation.

    Start of cooling After room

    temperature is stabilised

    Strong Gentle

    Fresh Outside-air Intake

    Airflow volume (m3/min)

    500

    50100150200250300

    0 1 2 3 4

    Sta

    tic p

    ress

    ure

    (Pa)

    Outside-air intake characteristics

    PCY-P30/36KAPCY-P18/24KA

    Flockless vanes

    With the adoption of flockless vanes, dirt and other impurities can be cleaned off easily with mild household detergent.

    optionaloptional

    Ceiling-suspended

    PCY-P18/24/30/36KA

    PEYSERIESSERIES

    The thin, ceiling-concealed indoor unitsof the PEY series are the perfect answerfor the air conditioning requirements of buildings with minimum ceiling installation space and wide-ranging external static pressure. Energy-saving efficiency has been improved, thereby reducing electricity consumption and contributing to a further reduction in operating cost.

    Compact Indoor Units

    For all models, unit height are unified to 250mm. Compared to the previous model, the height size is reduced, allowing installation in tight spaces, such as ceiling cavities or drop-ceilings.

    Air Inlet

    The units with bottom inlet make more noise than those with rear inlet. It is recommended that the rear inlet be selected when install-ing the units in the rooms that should be quiet such as bedrooms.

    Wide Selection of Fan Speeds and ExternalStatic Pressure

    Five-stage external static pressure conversions and three fan speed selections are available. Capable of being set to a maxi-mum of 125Pa, units are applicable to a wide range of building types.

    1Rear inlet 2Bottom inlet

    PEY-P18/24/30/36JA

    optionaloptional

    250mm

    Ceiling-concealed

    External static pressure setting

    Series

    PEY-P.JA

    18 24 30 36

    35/50/70/100/125Pa

    Reduction in height size

    Air inlet

    Air outlet Air outletAir inlet

    Inverter Series 05-06

    Units are equipped with a knock-out hole that enables the in-duction of fresh outside-air.

  • Inverter Series 07-08CONTROL TECHNOLOGIES

    PAR-31MAA(Optional)

    Easier to read thanks to use of a full dot liquid-crystal display with backlight, and easier to use owing to adopting a menu format that has reduced the number of operating buttons.

    Energy-efficient Control

    Operation Control Functions

    Easy To Read & Easy To Use

    Multi-language DisplayControl panel operation in eightdifferent languages

    Display Example [Operation Mode]

    Full Dot LCD

    Using a temperature that is 1C higher for cooling results in a 10% reduction in power consumption.* Temperature Range Restriction limits the maximum and minimum temperature settings, contributing to the prevention of overcooling. *In-house calculations

    Temperature Range Restrictionprevents overcooling

    TemperatureRangeRestriction

    When using Auto-off Timer, even if one forgets to turn off the unit, operation stops automatically after the preset time elapses, thereby preventing wasteful opera-tion. Auto-off Timer can be set in 10-minute units, in a range between 30 minutes and 4 hours. Eliminates all anxiety about forgetting to turn off the unit.

    Turns cooling off automatically after preset time elapses

    Auto-offTimer

    After adjusting the temperature for initialing on a hot day, it is easy to forget to return the temperature setting to its original value. The Auto-return function auto-matically resets the temperature back to the original setting after a specified period of time, thereby preventing overcooling. The Auto-return activation time can be set in 10-minute units, in a range between 30 and 120 minutes.*Auto-return cannot be used when Temperature Range Restrictions is in use.

    Prevents wasteful operation byautomatically returning to the preset temperature after specified operating time

    Auto-return

    This function monitors the room temperature and automatically activates the cooling mode when the temperature rises above the preset maximum tempera-ture setting.

    Keep desired room temperaturesautomatically

    NightSetback

    Choose the desired language, among the following languages.

    Multi-Ianguage

    Full Dot Liquid-crystal Display Adopted

    [English] [Italian] [German][Spanish] [Swedish] [Russian] [Portuguese][French]

    Cooling/Dry (Setting example of minimum temp. in 25C)

    Lower temperature limit

    Possible temperature range setting

    19(C) 30(C)

    30(C)25(C)

    To prevent excessive coolingLower temperatures cannotbe selected

    Meeting room Changing roomRecommended for

    In addition to operation start/stop, the operation mode, temperature setting and air-flow direction can be locked. Unwanted adjustment of temperature settings is pre-vented and an appropriate temperature is constantly maintained, leading to energy savings. This feature is also useful in preventing erroneous operation or tampering.

    Fixed temperature setting promotesenergy savings

    OperationLock

    The Weekly Timer enables the setting of operation start and finish times and adjust-ing the temperature as standard features. Up to 8 patterns per day can be set, pro-viding operation that matches the varying conditions of each period, such as the number of customers in the store.*Weekly Timer cannot be used when On/Off Timer is in use.

    Set up to 8 patterns per day including temperature control

    WeeklyTimer

    Auto-descending panel operation is available as an option. Panels can be lowered/raised using a button on the wired remote controller. Filter cleaning can be performed easily.

    Easily raise/lower panels using the remote controller

    Auto-descending Panel Operation (4-way ceiling cassette)

    Office Restaurant

    Office Restaurant

    Recommended for

    PAR-31MAA

    The adoption of dot liquid-crystal display (LCD) technology and a large display screen for the control panel optimises visibility. Op-eration and control status are easily read at a glance.

    Energy-efficient Control

    Operation Control Functions

    Easy to Read/Easy to Use

    Multi-language DisplayControl panel operation in eight different languages

    Display Example [Operation Mode]

    Dot LCD Choose the desired language, among the following languages.

    Multi-Ianguage

    Dot Liquid-crystal Display Adopted

    PAR-21MAA

    User-friendly Deluxe Remote Controller with Excellent

    Operability and VisibilityPAR-21MAA

    Advanced MA Remote Controller

    A Progressive Step in the Evolution of Air Conditioning Control

    Reassuring Troubleshooting Navigation Function

    Contact Details Displayed When Abnormality Occurs Easily contact a service company when there is a problem.

    The telephone number of a service company and other information can be input and stored in advance. When a problem occurs, the contact details are dis-played automatically, and a call for help can be made without delay.

    Set the time for the air conditioner to turn off automatically. The timer can be set in the range from 30 minutes up to 4 hours in 30-minute intervals.The Simple Timerstarts/stops in units of 1 hour in a 72-hour periodis set at the time of shipment from the factory. It can be changed to the Auto-off Timer function using the remote controller.

    Automatically turns offair conditioner

    Auto-off Timer

    Units can be set so that the operation mode cannot be changed. When Opera-tion Lock is activated, new temperature setting commands are not accepted, thereby ensuring that the unit runs in the specified (locked in) temperature range. This promotes energy savings and prevents erroneous/ mischievous operation.Only the administrator can change settings when using the Operation Lock mode.

    Prevent operation settingsfrom being changed

    Operation Lock

    Set the upper and lower limits for the temperature range during operation. Exces-sive cooling is prevented, leading to increased energy savings.

    Air conditioner operation restrictedto within a specified operating range

    Temperature Range Restriction

    Control temperature on a weekly basisTemperature settings and On/Off control can be managed over a period of one week using the Weekly Timer. Up to eight setting patterns per calendar day are possible.

    Introduced in response tomarket demand

    WeeklyTimer

    [English] [Italian] [German][Spanish]

    [Japanese] [Russian] [Chinese][French]

    Cooling/Dry

    Recommended for

    Lower temperature limit

    Possible temperature range setting

    19(C) 30(C)

    30(C)25(C)

    To prevent excessive coolingLower temperatures cannotbe selected

    (Setting example of minimum temp. in 25C)

    Busyhours

    Off-peakhours

    4

    26

    25

    24

    23

    22

    0 10 12 14 16 18 20 22 24

    Tem

    per

    atu

    re s

    etti

    ng

    (C

    )

    Opening time

    Lunch time Dinner time

    7-patterns setting

    Closing time

    Set to lower temperature Set to higher temperature

    1

    2

    3 5

    6 7

    (Time)

    (Results of cooperative study with Japan Facility Solutions, Inc.)

    Meeting roomRecommended for Changing room

    Recommended for

    Computer server facility

    Office School

    Hospital

    Public hall

    Recommended for

    Computer server facility

    Office School

    Hospital

    Public hall

    Setting Example (restaurant in summer time)

    Busyhours

    5

    26

    25

    24

    23

    22

    0 10 12 14 16 18 20 22 24

    Tem

    per

    atu

    re s

    etti

    ng

    (C

    )

    Openingtime

    Lunch time

    Preparation

    Dinner time

    8-patterns setting

    Closing time

    Set to lower temperature Set to higher temperature1

    2 4

    3

    6

    7 8

    (Time)*Joint research conducted with Japan Facility Solutions, Inc.

    Off-peakhours

    Setting Example (restaurant in summer time)

  • Ceiling-Concealed TypeModels

    kWCMMCFM

    kWBTU/h

    Cooling capacity

    Total input

    Indoorunit

    Outdoorunit

    EERModel name

    Fan motor output

    Airflow(low-mid-high)

    External static pressureOperation control & thermostatNoise level(low-mid-high)Unit drain pipe O.D.

    Dimensions

    WeightModel name SUY-KA18VA SUY-KA36VASUY-KA30VASUY-KA24VA

    PEY-P18JA

    425-510-600Pa

    dB(A)mmmmmm

    WD

    12-14.5-17

    5.3(2.8-5.4)18000

    kW 1.57W/W 3.38

    PEY-P18JA

    620-740-88517.5-21-25

    850-1025-120024-29-34

    30-34-39 33-38-42

    732

    External finish Munsell 3.0Y 7.8/1.1Refrigerant (R410A) control Liner Expansion ValveCompressor output

    Protection devices Discharge thermo, Comp.shell thermo, Over current protection, (Compressor)Over heat protection, Over current protection, (Fan motor)

    mmH 250

    46(1625)

    kg

    kW

    1040-1225-148529.5-35.5-42

    0.085 0.121

    32

    7

    36-40-44

    38

    1.2

    39

    1400

    0.244

    30-35-39

    1100900

    2927

    0.9

    Fan motor output kW 0.060.05Airflow CMM(CFM) 51(1800)34(1200)

    54 56Noise level

    Dimensions

    dB(A) 5851

    47 50Weight kg 513315MAX.height difference m 1230MAX.piping length m 20

    Liquid:9.52 Gas:15.88Pipe size O.D. mm Liquid:6.35 Gas:12.7Chargeless piping length m

    W 840mm 800D 330mm 285H 880mm 550

    Power SupplyExternal finish

    PEY-P36JA10.6(4.1-10.7)

    360003.333.18

    PEY-P36JA

    Gralvanized sheet

    35-50-70-100-125Remote control & Built-in

    PEY-P30JA8.8(4.1-9.7)

    300002.5

    3.52PEY-P30JA

    PEY-P24JA7.1(3.6-8.9)

    24000

    3.51PEY-P24JA

    2.02

    1ph 220-240V 50Hz / 1ph 220V 60Hz

    System Controls Versatile system controls can be realised by using optional parts, relay circuits, control panels, etc.

    Inverter Series 09-10SPECIFICATIONS

    FOR INDOOR UNITS

    2-remote Controller Control

    With two remote controllers, control can be performed locally and remotely from two locations.

    Operation Control by Level Signal

    Air conditioner can be started/stopped remotely. In addition, On/Off operation by local remote controller can be prohibited/permitted.

    Operation Control by Pulse Signal

    Remote Display of Operating Status

    Operating status can be displayed at a remote location.

    Allows On/Off operation with timer*For control by an external

    timer, refer to B Operation Control by Level Signal.

    Timer Operation

    Wired Remote ControllerPAR-31MAAPAR-21MAA

    Wireless Remote ControllerPAR-SL97A-E (for PEY)

    Wireless Remote Controller Kit for PCYPAR-SL94B-E

    Adapter for remote On/Off PAC-SE55RA-E

    Relay box (to be purchased locally) Remote control panel (to be purchased

    locally)

    Standard functions of PAR-31MAA

    A

    B

    C

    D

    E

    Details Major Optional Parts RequiredSystem Examples

    Wired remote controller Wireless remote controller

    Up to two remote controllers can be connected to one group.

    Both wired and wireless remote controllers can be used in combination.

    Operation other than On/Off (e.g., adjust-ment of temperature, fan speed, and airflow) can be performed even when remote controller operation is prohibited.

    Timer control is possible with an external timer.

    Connector cable for remote display PAC-SA88HA-E / PAC-725AD(10 pcs. x PAC-SA88HA-E)

    Relay box (to be purchased locally) Remote control panel (to be purchased

    locally)

    The pulse signal can be turned On/Off. Operation/emergency signal can be

    received at a remote location.

    Operation/emergency signal can be received at a remote location (when channeled through the PAC-SF40RMno-voltage signal, when channeled through the PAC-SA88HA-E DC 12V signal).

    Weekly Timer:On/Off and up to 8 pattern temperatures can be set for each calendar day. (Initial setting)

    On/Off Timer:On/Off can be set once each within 72 hr. in intervals of 5-minute units.

    Auto-off Timer:Operation will be switched off after a certain time elapse. Set time can be changed from30 min. to 4 hr. at 10 min. intervals. *Simple Timer and Auto-off Timer cannot be used at the same time.

    Remote display panel (to be purchased locally)

    Connector cable for remote display PAC-SA88HA-E / PAC-725AD(10 pcs. x PAC-SA88HA-E)

    Relay box (to be purchased locally) Remote operation adapter PAC-SF40RM *Unable to use with wireless remote controller

    PAR-31MAAPAR-21MAA PAR-31MAA

    PAR-21MAA

    (Example of 1 : 1 system)

    (Example of 1 : 1 system)

    Relay box (to be purchased) locally)

    Relay box (to be purchased) locally)

    Adapter for remote On/Off

    Adapter for remote On/Off

    PAR-SL97A-E

    PAR-SL97A-E

    (Example of 1 : 1 system)

    PAR-31MAA

    (Example of 1 : 1 system x 2)

    Relay box (to be purchased locally)

    (Example of 1 : 1 system x 2)

    * Set "Main" and "Sub" remote controllers. * When using wired and

    wireless remote controllers

    PAR-SL97A-E

    Remote display panel

    Remote display panelPAR-31/

    21MAA

    Remote control panel

    Remote control panelWired remote

    controller

    Connector cable for remote display

    Connector cable for remote display

    PAR-SL97A-E

    (Example of 1 : 1 system x 2)

    Relay box (to be purchased locally)

    (Example of 1 : 1 system x 2)

    Remote control panel

    Remote control panelWired remote

    controller

    Remote operation adapter/Connector cable for remote display + Relay box

    Remote operation adapter/Connector cable for remote display + Relay box

    MAJOR SYSTEM CONTROL

    PAR-31MAA ControlPAR-21MAA Control

    System Group Control

    M-NET Connections

    PAR-31MAA (Wired remote controller) PAR-21MAA (Wired remote controller)

    MAC-333IF-E (Interface) PAR-31MAA (Wired remote controller) PAR-21MAA (Wired remote controller)

    A

    B

    C

    Details Major Optional Parts Required

    System Examples

    PLY,PCY,PEY Series Indoor Unit

    SUY Series Outdoor

    Indoor Unit

    Outdoor Unit

    Standard equipment (for indoor units compatible with wired remote controllers)

    One remote controller can control plural air conditioners with the same settings simultaneously.

    One remote controller can control up to 16 refrigerant systems.

    Up to two remote controller can be connected.

    MAC-333IF-E MELANS System controller PAC-SC51KUA (power supply unit)

    Group of air conditioners can be controlled by MELANS system controller (M-NET).

    PAR-31MAAPAR-21MAA

    MAC-333IF-E

    Outdoorunit

    Indoor unit

    MAC-333IF-E MELANSsystem controller(AG-150A etc)

    PAC-SC51KUAPower supplyunit

    City Multi indoor unit

    Outdoorunit

    Indoor unit

    PAR-31MAAPAR-21MAA

    PAR-31MAAPAR-21MAA

    PAR-31MAAPAR-21MAA

    Ceiling-Suspended TypeModels

    kWCMMCFM

    kWBTU/h

    Cooling capacity

    Total input

    Indoorunit

    Outdoorunit

    EERModel name

    Fan motor output

    Airflow(low-mid2-mid1-high)

    External static pressureOperation control & thermostatNoise level(low-mid2-mid1-high)Unit drain pipe I.D.

    Dimensions

    WeightModel name SUY-KA18VA SUY-KA36VASUY-KA30VASUY-KA24VA

    PCY-P18KA

    0.095

    565-600-635-705Pa

    dB(A)mmmmmm

    WD

    16-17-18-20

    5.3(2.8-5.4)18000

    kW 1.51W/W 3.51

    PCY-P18KA

    565-635-705-77516-18-20-22

    0.16

    850-920-990-106024-26-28-30

    34-36-40-42 39-41-43-45

    680

    External finish Munsell 3.0Y 7.8/1.1Refrigerant (R410A) control Liner Expansion ValveCompressor output

    Protection devices Discharge thermo, Comp.shell thermo, Over current protection, (Compressor)Over heat protection, Over current protection, (Fan motor)

    mmH 230

    46(1625)

    kg

    kW

    32

    955-1025-1130-120027-29-32-34

    26

    7

    42-44-46-48

    37

    1.2

    40

    1280 1600

    34-36-38-40

    0.9

    Fan motor output kW 0.060.05Airflow CMM(CFM) 51(1800)34(1200)

    54 56Noise level

    Dimensions

    dB(A) 5851

    47 50Weight kg 513315MAX.height difference m 1230MAX.piping length m 20

    Liquid:9.52 Gas:15.88Pipe size O.D. mm Liquid:6.35 Gas:12.7Chargeless piping length m

    W 840mm 800D 330mm 285H 880mm 550

    Power SupplyExternal finish

    PCY-P36KA10.6(4.1-10.7)

    360003.133.39

    PCY-P36KA

    Munsell 6.4Y 8.9/0.4

    0 (direct blow)Remote control & Built-in

    PCY-P30KA8.8(4.1-9.7)

    300002.6

    3.38PCY-P30KA

    PCY-P24KA7.1(3.6-8.9)

    24000

    3.38PCY-P24KA

    2.1

    1ph 220-240V 50Hz / 1ph 220V 60Hz

    Ceiling Cassette TypeModels

    kWCMMCFM

    kWBTU/h

    Cooling capacity

    Total input

    Indoorunit

    Outdoorunit

    EERModel name

    Fan motor output

    Airflow(low-mid2-mid1-high)

    External static pressureOperation control & thermostatNoise level(low-mid2-mid1-high)Unit drain pipe O.D.

    Dimensions

    Weight ( ):Panel

    ( ):Panel

    Model name SUY-KA18VA SUY-KA36VA SUY-KA30VASUY-KA24VA

    PLY-P18BA

    425-460-495-565Pa

    dB(A)mmmmmm

    WD

    12-13-14-16

    5.3(2.8-5.4)18000

    kW 1.47W/W 3.61

    PLY-P18BA

    495-565-635-70514-16-18-20

    705-775-885-99020-22-25-28

    28-30-32-34 33-35-38-41

    840(950)840(950)

    External finish Munsell 3.0Y 7.8/1.1Refrigerant (R410A) control Liner Expansion ValveCompressor output

    Protection devices Discharge thermo, Comp.shell thermo, Over current protection, (Compressor)Over heat protection, Over current protection, (Fan motor)

    mmH

    46(1625)

    kg

    kW

    850-920-1025-113024-26-29-32

    0.05

    32

    7

    37-39-41-44

    24(6)

    1.2

    26(6)

    0.12

    258(35) 298(35)

    28-29-30-32

    22(6)19(6)

    0.9

    Fan motor output kW 0.060.05Airflow CMM(CFM) 51(1800)34(1200)

    54 56Noise level

    Dimensions

    dB(A) 5851

    47 50Weight kg 513315MAX.height difference m 1230MAX.piping length m 20

    Liquid:9.52 Gas:15.88Pipe size O.D. mm Liquid:6.35 Gas:12.7Chargeless piping length m

    W 840mm 800D 330mm 285H 880mm 550

    Power SupplyExternal finish

    PLY-P36BA10.6(4.1-10.7)

    360003.133.39

    PLY-P36BA

    Munsell 6.4Y 8.9/0.4

    0 (direct blow)Remote control & Built-in

    PLY-P30BA8.8(4.1-9.7)

    300002.363.73

    PLY-P30BA

    PLY-P24BA7.1(3.6-8.9)

    24000

    3.51PLY-P24BA

    2.02

    1ph 220-240V 50Hz / 1ph 220V 60Hz

  • Inverter Series 11-12EXTERNAL DIMENSIONS

    Unit : mm

    10

    69

    800

    302.5

    500 Bolt pitch for installation

    150

    22.3

    Handle

    550

    280

    164.

    5

    99.5 170.5

    23Service panel

    Service port

    285

    344.

    5 44

    400Air in

    Air out

    Air in

    17.5

    Bol

    t pitc

    h fo

    rin

    stal

    latio

    n30

    4~32

    5

    40

    Liquid refrigerant pipe joint

    Gas refrigerant pipe joint

    4335

    2 holes 10X21

    Drain hole

    SUY-KA18VAOUTDOOR UNIT

    SUY-KA24VA SUY-KA30VA SUY-KA36VAOUTDOOR UNIT

    417.5

    4042Drain hole

    175 500

    330 5

    0

    Air in

    Air out2-holes 10 21

    360

    840109

    81

    880

    452

    Service panel

    99.5

    164.

    5

    195

    35

    44

    Liquid refrigerantpipe joint

    Gas refrigerantpipe joint

    42

    Bol

    t pitc

    h fo

    rin

    stal

    latio

    n

    Air in

    Unit : mm

    Ceiling hole

    Branch duct hole

    Indoor unit/Outdoor unit connecting terminal block Indoor power supplyterminal block(optional part)

    Branch duct hole

    Fresh air intake hole

    Ceilin

    g ho

    le

    Susp

    ensio

    n bo

    lt pitc

    hSuspension bolt pitch

    Remote controller terminal block

    (7.5)

    (7.5)

    605

    +35

    -

    5

    620

    160

    160

    160

    840

    150

    90 C D

    840187.5

    20~45 860~910 20~45

    810

    20~4

    586

    0~91

    020

    ~45

    24 160

    950

    Cut out hole

    Cut out hole

    Burring hole pitch Burring hole175

    167

    130

    100

    70

    155

    350

    90 100 100 90

    Detail connecting of branch duct

    14- 2.8150

    37728460 Drain pipe

    Ceiling

    Grille

    Power supply wire,Indoor unit/Outdoor unit connecting wire entryControl wire entry Keep approximately

    10 to 15mm spacebetween unit ceiling and ceiling slab.

    Suspension bolt M10 or W3/8

    A17

    +5 0

    B35

    190

    156

    105

    140

    50~7

    0Suspension bolt lower edge

    170

    Models BA C D

    241 25880

    85

    74

    29877

    281

    PLY-P18BAPLY-P24BAPLY-P30BAPLY-P36BA

    PLY-P18BA PLY-P24BA PLY-P30BA PLY-P36BAINDOOR UNIT

    950

    Refrigerant pipe

    Refrigerant pipe

    (liquid)

    (gas)

    INDOOR UNIT

    When drain socket is installed(Drainage)

    (

    PCY-P30KA PCY-P36KA

    233

    510

    51

    246

    180200

    236

    8488

    195 230

    5725

    447

    668

    0

    182 851518

    1600 221493

    Air outlet

    Air intake

    (gas)(liquid)

    PCY-P18KA PCY-P24KA

    INDOOR UNIT

    Air intake

    Air outlet

    8488

    195 230

    57

    254

    476

    680

    182 85

    1198

    1280 221173

    When drain socket is installed

    233

    5

    10

    51

    246

    A

    B

    236

    (Drainage)

    (gas)

    (liquid)

    ((

    PEY-P18JA PEY-P24JA PEY-P30JA PEY-P36JA INDOOR UNIT

    Models

    PEY-P30JAPEY-P36JA

    PEY-P24JAPEY-P18JA

    A900

    11001400

    954B

    11541454

    860D

    10601360

    9E

    1114

    1200

    C

    1500

    1000

    13001000

    F800

    13581058

    G858

    Models

    PCY-P24KAPCY-P18KA

    A184180

    203B

    200

    5778

    250

    3312

    2

    15

    24

    5710

    100

    100x

    (E-1

    )=F

    AB

    (Sus

    pens

    ion

    bolt

    pitc

    h) C

    23

    643(Suspension bolt pitch)

    30

    20D

    (Duc

    t)17

    8(D

    uct)

    4023

    1032 700

    732

    136 67356

    100

    217

    Suspension bolt hole 4-14x30 Slot

    Airoutlet

    Airinlet

    Refrigerant piping Flare connection(liquid)

    Refrigerant piping Flare connection(gas)

    Control box

    Terminal block (Indoor/Outdoorconnecting line)

    Terminal block (Remote controllertransmission line)

    2xE- 2.9

    2x2- 2.9

    Drain pipe(O.D. 32)

  • Inverter Series 13-14

    SUY-KA

    Upper limit (DB)

    Lower limit (DB)

    46C

    18C

    Cooling

    Guaranteed Operating Range

    Sound Pressure Level Sound pressure measurements were conducted in an anechoic chamber.

    The actual noise level depends on the distance from the unit and the acoustic environment.

    Single-phase, 220-240VSingle-phase, 220-240V50Hz

    Single-phase, 220VSingle-phase, 220V60Hz

    Notes for All Specifications

    Rating conditionsCooling - Indoor: 27C (80F) DB, 19C (66F) WB Outdoor: 35C (95F) DB

    Refrigerant piping length (one-way): 7.5m (25ft.)

    Total input based on the indicated voltage (indoor/outdoor)

    Indoor Outdoor

    Refrigerant Piping

    SUY-KA18

    SUY-KA24

    12

    15

    20

    30

    SUY-KA30

    SUY-KA36

    15

    15

    30

    30

    Liquid: 9.52

    Gas: 15.88

    Liquid: 9.52

    Gas: 12.7

    Liquid: 6.35

    Gas: 15.88

    Liquid: 9.52

    Gas: 15.88

    t 0.8

    t 1.0

    t 0.8

    t 0.8

    t 0.8

    t 1.0

    t 0.8

    t 1.0

    Thickness (mm)Pipe size OD (mm)CapacityBetween indoor & outdoor units

    Max. height difference (m) Max. piping length (m)

    Amount of Necessary Refrigerant (R410A: kg)

    SUY-KA18

    SUY-KA24

    SUY-KA30

    SUY-KA36

    1.2

    2.0

    2.1

    2.5

    0.05

    0.06

    0.06

    0.06

    0.12

    0.16

    0.16

    0.16

    0.2

    0.26

    0.26

    0.26

    0.36

    0.36

    0.36

    0.36

    0.46

    0.46

    Xg = 15g/m (length-7)m

    Xg = 20g/m (length-7)m

    30m25m20m15m10m7m

    Factory charged Additional charged

    CalculationPiping length

    NOTICE

    Do not install indoor units in areas (e.g., mobile phone base stations) where the emission of VOCs such as phthalate compounds and formaldehyde is known to be high as this may result in a chemical reaction.

    When installing or relocating or servicing the air conditioners, use only the specified refrigerant (R410A) to charge the refrigerant lines.Do not mix it with any other refrigerant and do not allow air to remain in the lines.If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant lines, and may result in an explosion and other hazards.The use of any refrigerant other than that specified for the system will cause mechanical failure or system malfunction or unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety.

    Outdoor Unit Installation Location

    A

    D

    C

    A

    B

    A

    C

    A

    C

    B

    SUY-KA18VA SUY-KA24VASUY-KA30VASUY-KA36VA

    Outdoor unitVentilation and service space

    100 mm or more 350 mm or moreBasically open 100 mm or more without any obstruction in front and both sides of the unit.200 mm or more (Open two sides of left, eight, or rear side.)

    SUY-KA18VAA B

    100 mm or more 350 mm or more 500 mm or more SUY-KA24VA SUY-KA30VA SUY-KA36VA

    A B C

    C

    D

    When the piping is to be attached to a wall containing metals (tin plated) or metal netting, use a chemically treated wooden piece 20mm or thicker between the wall and the piping or wrap 7 to 8 tums of insulation vinyl tape around the piping.

    Units should be installed by licensed contractor accordingly to local code requirement.

    Optional Parts

    Part name Model name Application name

    PCY-P24/30/36PAC-SH84DM-E

    PCY-P18PAC-SH85DM-E

    PLY-PPAC-SH65OF-EFlange for fresh-air intake

    Drain pump

    All indoor unitsMAC-333IF-E

    PLY-P / PEY-PPAR-SL97A-E

    M-NET&Terminal interface

    Wireless remote controller

    PEY-PPAR-SA9CA-EWireless remote controllersignal receiver PLY-PPAR-SA9FA-E

    PCY-P18/24PAC-SH89KF-E

    PCY-P30/36PAC-SH90KF-E

    PLY-PPAC-SH59KF-E

    PEY-P18PAC-KE92TB-E

    High efficiency filter element

    Filter box PEY-P24PAC-KE93TB-E

    PEY-P30/36PAC-KE94TB-E

    PLY-PPAC-SA1ME-E

    PLY-PPAC-SH51SP-E

    i-see sensor corner panel

    Shutter plate

    PLY-PPAC-SH53TM-EMulti-function casement

    All indoor unitsPAC-SE55RA-ERemote On/Off adaptor

    All indoor unitsPAC-SF40RM-ERemote operation adaptor

    All indoor unitsPAC-SE41TS-ERemote sensor

    PLY-PPAC-SH48AS-ESpace panel

    All indoor unitsPAC-SA88HA-EConnector cable for remote display

    Wired remote controller

    Air discharge guide

    Multiple remote controller adaptor

    All indoor unitsPAR-31MAA

    All indoor unitsPAR-21MAA

    SUY-KA18MAC-881SG

    SUY-KA24/30/36MAC-886SG

    PCY-PPAR-SL94B-EWireless remote controller kit(Sender & Receiver)

    PAC-725AD All indoor units

    High efficiency filter