no damage pres

Upload: tod123

Post on 03-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 No Damage Pres

    1/29

    2003 Cooper Bussmann, Inc.

    No Damage MotorStarter Protection

    Type 2 Protection

  • 7/29/2019 No Damage Pres

    2/29

    2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Motor starters are very susceptible to

    damage during fault conditions Motor starters are tested and listed to UL

    508 for Industrial Control Equipment.

  • 7/29/2019 No Damage Pres

    3/29

    2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Q. Will a device applied inaccordance with the NEC that

    is tested and listed according toUL 508 be operable after a faulton the motor circuit?

  • 7/29/2019 No Damage Pres

    4/29

    2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    A. Not necessarily!

  • 7/29/2019 No Damage Pres

    5/29

    2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    UL 508 Table 53.1 lists the maximumdamage criteria.

    device is able to be inoperative at

    the conclusion of the test. The contactsare able to weld or

    completely disintegrate.

    Overload relays can be burned out,and do not have to maintaincalibration.

  • 7/29/2019 No Damage Pres

    6/29

    2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Example of contacts after a fault on amotor starter.

    This is acceptable per UL 508.

  • 7/29/2019 No Damage Pres

    7/29

    2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    UL 508 acceptance criteria onlyrequires that the damage be confinedwithin the enclosure.

    Some deformation is allowed, but thedoor must not blow open.

    The door must be able to be opened

    after the test. No discharge of parts, or risk of fire

    is allowed.

  • 7/29/2019 No Damage Pres

    8/29

    2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Short-circuit test on a 10HP motor starterwith MCP for short-circuit protection.

    Before test.

  • 7/29/2019 No Damage Pres

    9/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Short-circuit test on a 10HP motor starterwith MCP for short-circuit protection.

    The heater elements vaporized and the contacts were severelywelded. Extensive repair or replacement would be required. Thislevel of damage is permitted by UL 508.

    During test.

  • 7/29/2019 No Damage Pres

    10/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Q. If UL 508 does not guarantee nodamage protection, what can bedone?

  • 7/29/2019 No Damage Pres

    11/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    A. Specify Type 2 protection for NEMAand IEC motor starters.

    UL 508E is an outline of investigation

    that allows motor starters to be testedfor Type 2 protection.

    Q. If UL 508 does not guarantee nodamage protection, what can bedone?

  • 7/29/2019 No Damage Pres

    12/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Q. What is Type 2 protection?

  • 7/29/2019 No Damage Pres

    13/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    A. Under short circuit conditions, the controllershall not result in danger to persons or theinstallation, and after the short-circuit testthe controller shall be capable of further use.

    Nationally Recognized Testing Laboratories

    will verify the results of the Type 2 testing.

    Q. What is Type 2 protection?

  • 7/29/2019 No Damage Pres

    14/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    UL 508E section 15.4.1 lists themaximum damage criteria.

    No damage to the overload relay orother parts shall occur, except thatwelding of contactor or starter contacts ispermitted when they are easily separated(as by a screwdriver) without significantdeformation. No parts are to be replacedduring the tests, except that in the case offuse protection, all the fuse links are to bereplaced.

  • 7/29/2019 No Damage Pres

    15/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Same short-circuit test on the same typeof 10HP motor starter with LPJ fuses forprotection.

    Before test.

  • 7/29/2019 No Damage Pres

    16/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    This photo taken during the test illustrates the level of protectionrequired by UL 508E. After the test, the overload relaysmaintained factory calibration, which is important to retainoverload protection. This starter could be put back into servicewithout any repair.

    Same short-circuit test on the same typeof 10HP motor starter with LPJ fuses forprotection.

    During test.

  • 7/29/2019 No Damage Pres

    17/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Example of contacts after a fault on acircuit with Type 2 protection.

    Damage is not allowed.

  • 7/29/2019 No Damage Pres

    18/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Q. How can Type 2protection beachieved?

  • 7/29/2019 No Damage Pres

    19/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    A. By using Bussmann Low-Peak fuses sizedaccording to Type 2

    protection tables.

    Q. How can Type 2protection beachieved?

  • 7/29/2019 No Damage Pres

    20/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Q. Where can Type 2 protection tables befound?

  • 7/29/2019 No Damage Pres

    21/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    A. They are available online at: http://www.bussmann.com/products/datasheet.asp?prmS

    Data sheets 8108-8114

    In the SPD Handbook on pages 128-141.

    Q. Where can Type 2 protection tables befound?

    http://www.bussmann.com/products/datasheet.asp?prmSort=Datasheethttp://www.bussmann.com/products/datasheet.asp?prmSort=Datasheet
  • 7/29/2019 No Damage Pres

    22/29 2003 Cooper Bussmann, Inc.

    Example of Type 2 Table

  • 7/29/2019 No Damage Pres

    23/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Q. How are the tables used?

  • 7/29/2019 No Damage Pres

    24/29 2003 Cooper Bussmann, Inc.

    Example of Type 2 Table

  • 7/29/2019 No Damage Pres

    25/29 2003 Cooper Bussmann, Inc.

    Example of Type 2 Table

    A. For 480V, 3 HP, size 0 starter, Square D partnumber SB02V02S with heater B7.70.

    Choose from Bussmann Low Peak fuses:

    LPS-RK-8SP, LPJ-9SP, or LP-CC-12

  • 7/29/2019 No Damage Pres

    26/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Type 2 tables are available for:

    General Electric

    Rockwell Automation/Allen-Bradley

    Square D Co.

    Siemens Cutler-Hammer

  • 7/29/2019 No Damage Pres

    27/29 2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    Q. What do I get when I specify Type 2protection with Low-Peak fuses?

  • 7/29/2019 No Damage Pres

    28/29

    2003 Cooper Bussmann, Inc.

    Motor Starter Protection

    A. Maximum safety for personnel andequipment.

    Minimum cost to stay in service.

    Maximum productivity from the equipment.

    Minimum downtime after a fault.

    Q. What do I get when I specify Type 2protection with Low-Peak fuses?

  • 7/29/2019 No Damage Pres

    29/29