OUTSULATION PE OSPE SE430 - 1
SECUROCK EXOAIR 430 SYSTEM
BUILDING FACADE OSPE SE430 - 2
INSULATION BOARD LAYOUT OSPE SE430 - 3
OUTSIDE CORNER - OSPE SE430 - 4
INSULATION BOARD LAYOUT
INSULATION BOARD - OSPE SE430 - 5
GROOVE PATTERN
COMPARTMENT SEPARATION OSPE SE430 - 6
FOUNDATION OSPE SE430 - 7
TERMINATION AT CONCRETE OSPE SE430 - 8
HEAD/SILL OSPE SE430 - 9
JAMB OSPE SE430 - 10
PARAPET - STEEL FRAMED, OSPE SE430 - 11
METAL COPING
PARAPET - SOLID SUBSTRATE, OSPE SE430 - 12
METAL COPING
SOFFIT/FASCIA INTERSECTION OSPE SE430 - 13
INSIDE/OUTSIDE CORNERS OSPE SE430 - 14
OUTSIDE CORNER - HIGH IMPACT OSPE SE430 - 15
HORIZONTAL EXPANSION JOINT OSPE SE430 - 16
HORIZONTAL SLIP JOINT OSPE SE430 - 17
VERTICAL EXPANSION JOINT OPTIONS OSPE SE430 - 18
STRCTURAL EXPANSION JOINTS OSPE SE430 - 19
MINOR PENETRATIONS OSPE SE430 - 20
MAJOR PENETRATIONS OSPE SE430 - 21
SIGN ATTACHMENT OSPE SE430 - 22
AESTHETIC REVEALS OSPE SE430 - 23
PROJECTING GRAPHICS OSPE SE430 - 24
RECESSED GRAPHICS OSPE SE430 - 25
DRYVIT VENT ASSEMBLY™ OSPE SE430 - 26
UNITED STATES GYPSUM COMPANY ("USG"), TREMCO
INCORPORATED ("TREMCO") AND DRYVIT SYSTEMS, INC.
("DRYVIT") MAKE NO REPRESENTATION REGARDING
CONFORMITY OF ITS SUGGESTIONS TO MODEL BUILDING
CODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS,
OR PROJECT LOCATIONS. ALL COMPONENTS INDICATED
IN ILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BE
REQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BE
DESIGNED, DETAILED, AND ENGINEERED BY
REPRESENTATIVES OF THE ARCHITECT, OWNER, OR
CONTRACTOR TO BE IN CONFORMANCE WITH MODEL
CODES, ARCHITECTURAL, AND ENGINEERING
REQUIREMENTS PERTAINING TO SPECIFIC BUILDING
PROJECTS.
USG, TREMCO AND DRYVIT MAKE NO WARRANTY,
EXPRESSED OR IMPLIED, AS TO THE ARCHITECTURAL
DESIGN, ENGINEERING, OR WORKMANSHIP OF PROJECTS
UTILIZING USG, TREMCO AND DRYVIT SYSTEMS OR
PRODUCTS.
THE LIABILITIES OF USG, TREMCO AND DRYVIT SHALL BE
AS STATED IN THE OUTSULATION PE SECUROCK EXOAIR
430 SYSTEM LIMITED COMMERCIAL WARRANTY. CONTACT
DRYVIT FOR A FULL AND COMPLETE COPY OF THE
WARRANTY.
DRYVIT SYSTEMS, INC AND TREMCO ARE A PART OF
TREMCO CONSTRUCTION PRODUCTS GROUP.
DETAIL NOTE
Outsulation® PE Securock® ExoAir 430 System® TABLE OF CONTENTS
©
Dryvit Systems, Inc.Date Issued: 4/2020
The architecture, engineering, and design of the project using United States Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit
Systems, Inc. ("Dryvit") products is the responsibility of the project's design professional. All systems must comply with local building codes and standards.
This detail is for general information and guidance only and the aforementioned specifically disclaim any liability for the use of this detail and for the
architecture, design, engineering or workmanship of any project. The project design professional determines, in its sole discretion, whether this detail or a
functionally equivalent detail is best suited for the project. Use of a functionally equivalent detail does not violate the warranty. This detail is subject to
change without notice.
Outsulation PE Securock ExoAir 430 System
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
™
SECUROCK EXOAIR 430®®
®
™
EIMA
STANDARD
IMPACT
EIMA
ULTRA-HIGH
IMPACT
FRAMING
SECUROCK EXOAIR 430
EPS INSULATION BOARD
DRYVIT REINFORCING MESH
DRYVIT FINISH
DRYVIT VENT ASSEMBLY
DRYVIT BASE COAT
PANZER® 15 OR 20 REINFORCING MESH
(SEE NOTE 1)
DRYVIT BASE COAT
DRYVIT ADHESIVE IN VERTICAL
NOTCHED TROWEL CONFIGURATION
DRYVIT VENT TRACK™
DRYVIT FINISH
DRYVIT VENT ASSEMBLY™
DRYVIT BASE COAT
DYMONIC 100 AT 40 MILS OVER VERTICAL LEG
OF DRYVIT VENT TRACK™, 25 MM (1") MIN. ON
BOTH SUBSTRATES
DRYVIT BASE COAT
SECUROCK EXOAIR 430
FRAMING
INSULATION BOARD
DRYVIT REINFORCING MESH
DRYVIT ADHESIVE IN VERTICAL
NOTCHED TROWEL CONFIGURATION
DRYVIT BASE COAT
DYMONIC 100 AT 40 MILS OVER VERTICAL LEG
OF DRYVIT VENT TRACK™, 25 MM (1") MIN. ON
BOTH SUBSTRATES
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 1
©
Dryvit Systems, Inc.Date Issued: 4/2020
Outsulation PE Securock ExoAir 430 System
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
DRYVIT PANZER® MESH PRIOR TO DRYVIT
REINFORCING MESH. LOCATION OF HIGH IMPACT
ZONES SHOULD BE INDICATED ON CONTRACT
DRAWINGS.
2. LIGHTLY SAND SURFACE OF DRAINAGE
TRACK TO MAXIMIZE ADHESION.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
v
v
v
v
v
v
v
v
v
v
v
v
DRYVIT VENT ASSEMBLY™
DRYVIT VENT TRACK™ (DRAIN HOLE
LOCATED AT VENT ASSEMBLY)
DRYVIT TRACK (NO DRAIN HOLES)
COMPARTMENT
SEPARATION TYP.
152 MM (6" DRYVIT CLOSURE
BLOCKS TYP.
152 MM (6") DRYVIT
STARTER STRIP TYP.
305 MM (12") DRYVIT
CLOSURE BLOCKS TYP.
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 2
©
Dryvit Systems, Inc.Date Issued: 4/2020
Building Facade
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. COMPARTMENT LOCATIONS DETERMINED PER
ASCE 7-10 AND DRYVIT OUTSULATION PE SYSTEM
SPECIFICATIONS DS844.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
BY OTHERS
FRAMING, BY OTHERS
SECUROCK EXOAIR 430
INSULATION BOARD
VERTICAL DRAINAGE
GROOVES (ALIGNED)
HORIZONTAL BEVELED
GROOVES
DRYVIT STARTER STRIP
DRYVIT VENT ASSEMBLY™
DRYVIT VENT TRACK™
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 3
©
Dryvit Systems, Inc.Date Issued: 4/2020
Insulation Board Layout
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
305 MM
(1'-0")"
152 MM (0'-6")
610 MM (2'-0")
ALTERNATING SQUARE
EDGED CORNER CLOSURE
BLOCKS (TYPICAL)
DRYVIT VENT
ASSEMBLY™
VERTICAL DRAINAGE
GROOVES (ALIGNED)
DRYVIT STARTER STRIP
MITER JOINT BETWEEN STARTER STRIPS
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 4
©
Dryvit Systems, Inc.Date Issued: 4/2020
Outside Corner - Insulation Board
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. INSTALL SQUARE EDGED CORNER CLOSURE
BLOCKS ON ALTERNATING SIDES OF OUTSIDE
CORNERS.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
BEVEL
DETAIL
51 MM (2") MIN
12.7 MM (1/2")
1
.2
M
(4
'-0
"
)
3
0
5
M
M
(
1
2
"
)
O
N
C
E
N
T
E
R
610 MM
(2'-0")
6.4 MM X 25 MM (
1
4
" X 1")
VERTICAL DRAINAGE GROOVE
BEVEL ALONG PERIMETER
OF INSULATION BOARD
45
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 5
©
Dryvit Systems, Inc.Date Issued: 4/2020
Insulation Board - Groove Pattern
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
BY OTHERS
VERTICAL DRAINAGE
GROOVES (ALIGNED)
INSULATION BOARD
DRYVIT VENT ASSEMBLY™
INSULATION BOARD CLOSURE BLOCK
(SEE NOTE 1)
DRYVIT STARTER STRIP
(SEE NOTE 1)
DRYVIT VENT TRACK™
DRYVIT/TREMCO APPROVED ADHESIVE
(SEE NOTES 2, 4)
DYMONIC 100 AT 40 MILS OVER VERTICAL LEG
OF DRYVIT VENT TRACK™, 25 MM (1") MIN. ON
BOTH SUBSTRATES
SECUROCK EXOAIR 430
FRAMING
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 6
©
Dryvit Systems, Inc.Date Issued: 4/2020
Compartment Separation
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. ADHERE CLOSURE BLOCKS AND STARTER STRIPS
USING "RIBBON & DAB" ADHESIVE PATTERN TO
PROVIDE COMPARTMENT CLOSURE.
2. FILL DRYVIT VENT TRACK AT CLOSURE BLOCK
LOCATION WITH AP ADHESIVE PRIOR TO SETTING
CLOSURE BLOCK, TO PROVIDE COMPARTMENT
CLOSURE.
3. LIGHTLY SAND SURFACE OF DRAINAGE TRACK TO
MAXIMIZE ADHESION.
4. REFERENCE DS920 FOR APPROVED SEALANTS.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
152 MM (6") MIN.
BY OTHERS
SLOPE GRADE AWAY
FROM FOUNDATION WALL
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
19 MM (3/4") MIN.
SECUROCK EXOAIR 430
DYMONIC 100 AT 40 MILS OVER VERTICAL LEG
OF DRYVIT VENT TRACK™, 25 MM (1") MIN. ON
BOTH SUBSTRATES
INSULATION BOARD
DRYVIT VENT TRACK™
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
WRAP DRYVIT DETAIL MESH®
64 MM (2
1
2
") MIN. AT UNDERSIDE
OF INSULATION
DRYVIT VENT ASSEMBLY™
DRYVIT ADHESIVE
DYMONIC 100 AT 40 MILS, 25 MM (1") MIN.
ON BOTH SUBSTRATES
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 7
©
Dryvit Systems, Inc.Date Issued: 4/2020
Foundation
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR
STANDARD PLUS™ MESH. LOCATION OF HIGH
IMPACT ZONES SHOULD BE INDICATED ON
CONTRACT DRAWINGS.
2. DRYVIT VENT ASSEMBLY IS INSTALLED ONLY AT
PUNCHOUT IN DRYVIT VENT TRACK.
3. EXPANSION JOINT IS REQUIRED ALONG TOP OF
FOUNDATION IF 610 MM (2'-0') DIMENSION IS
EXCEEDED.
4. LIGHTLY SAND SURFACE OF DRAINAGE TRACK TO
MAXIMIZE ADHESION.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
BY OTHERS
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
19 MM (3/4") MIN.
19 MM (3/4") MIN.
SECUROCK EXOAIR 430
DRYVIT VENT TRACK™
DRYVIT/TREMCO APPROVED SEALANT AND
CLOSED CELL BACKER ROD, BY OTHERS
(SEE NOTE 3)
DRYVIT FINISH
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DYMONIC 100 AT 40 MILS OVER
VERTICAL LEG OF DRYVIT VENT
TRACK™, 25 MM (1") MIN. ON BOTH
SUBSTRATES
DRYVIT VENT ASSEMBLY™
WRAP DRYVIT DETAIL MESH® 64 MM
(2
1
2
") MIN. AT BACKSIDE OF INSULATION
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACES TO RECEIVE SEALANT
DRYVIT ADHESIVE
INSULATION BOARD
DYMONIC 100 AT 40 MILS, 25 MM (1") MIN.
ON BOTH SUBSTRATES
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 8
©
Dryvit Systems, Inc.Date Issued: 4/2020
Termination at Concrete
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR
STANDARD PLUS™ MESH. LOCATION OF HIGH
IMPACT ZONES SHOULD BE INDICATED ON
CONTRACT DRAWINGS.
2. LIGHTLY SAND SURFACE OF DRAINAGE TRACK TO
MAXIMIZE ADHESION.
3. REFERENCE DS920 FOR APPROVED SEALANTS.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
SILL PAN FLASHING
SILL
HEAD
BY OTHERS
OUSTULATION PE SECUROCK
EXOAIR 430 SYSTEM
64 MM
(2-1/2") MIN.
12.7 MM
(1/2")
19 MM (3/4") MIN.
SECUROCK EXOAIR 430
DRYVIT VENT TRACK™
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT STARTER STRIP
DRYVIT FINISH
WRAP DRYVIT DETAIL MESH® 64 MM (2
1
2
")
MIN. AT BACKSIDE OF INSULATION BOARD
DYMONIC 100 AT 40 MILS
DRYVIT/TREMCO APPROVED SEALANT WITH
BOND BREAKER, BY OTHERS (SEE NOTE 3)
INSULATION BOARD
INSULATION BOARD CLOSURE BLOCK
DRYVIT ADHESIVE
DYMONIC 100 AT 40 MILS OVER
VERTICAL LEG OF DRYVIT VENT TRACK,
25 MM (1") MIN. ON BOTH SUBSTRATES
(SEE NOTE 4)
DYMONIC 100 AT 40 MILS, 25 MM (1") MIN.
ON BOTH SUBSTRATES
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACE(S) TO RECEIVE SEALANT
CONTINUOUS FLASHING, BY OTHERS
CONTINUOUS FLASHING, BY OTHERS
DRYVIT/TREMCO APPROVED SEALANT WITH
CLOSED CELL BACKER ROD, BY OTHERS
(SEE NOTE 3)
26 MM (1") MIN.
42 MM (1
5
8
") MIN.
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 9
©
Dryvit Systems, Inc.Date Issued: 4/2020
Head/Sill
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR
STANDARD PLUS™ MESH. LOCATION OF HIGH
IMPACT ZONES SHOULD BE INDICATED ON
CONTRACT DRAWINGS.
2. FOR CONTINUOUS WINDOWS, USE CLOSURE
BLOCKS TO TERMINATE SYSTEM AT SILL.
3. REFERENCE DS920 FOR APPROVED SEALANTS.
4. LIGHTLY SAND SURFACE OF TRACK TO MAXIMIZE
ADHESION.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
SECUROCK EXOAIR 430
OUTSULATION PE
SECUROCK EXOAIR
430 SYSTEM
BY OTHERS
19 MM
(3/4") MIN.
DYMONIC 100 AT 40 MILS
DRYVIT/TREMCO APPROVED SEALANT AND
CLOSED CELL BACKER ROD (SEE NOTE 2)
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACE(S) TO RECEIVE SEALANT
WRAP DRYVIT DETAIL MESH® 64 MM (2
1
2
")
MIN. AT BACKSIDE OF INSULATION BOARD
DRYVIT ADHESIVE
INSULATION BOARD
CLOSURE BLOCK
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE
COAT
DRYVIT FINISH
26 MM (1") MIN.
42 MM (1
5
8
") MIN.
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 10
©
Dryvit Systems, Inc.Date Issued: 4/2020
Jamb
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR
STANDARD PLUS™ MESH. LOCATION OF HIGH
IMPACT ZONES SHOULD BE INDICATED ON
CONTRACT DRAWINGS.
2. REFERENCE DS920 FOR APPROVED SEALANTS.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
BY OTHERSOUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
64 MM (2 1/2") MIN.64 MM (2 1/2") MIN.
76 MM (3") MIN.
EXOAIR 110AT
(SEE NOTE 3)
CONTINUOUS COPING,
BY OTHERS
SEALANT WITH BOND
BREAKER (TYP.),
BY OTHERS
DRYVIT/TREMCO APPROVED SEALANT,
BY OTHERS (SEE NOTE 2)
WRAP DRYVIT DETAIL MESH® 64 MM (2
1
2
")
MIN. AT BACKSIDE OF INSULATION BOARD
SECUROCK EXOAIR 430
DRYVIT ADHESIVE
INSULATION BOARD CLOSURE BLOCK
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
INSULATION BOARD
DYMONIC 100 AT 40 MILS
APPLIED OVER EXOAIR 110AT
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 11
©
Dryvit Systems, Inc.Date Issued: 4/2020
Parapet - Steel Framed, Metal Coping
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR
STANDARD PLUS™ MESH. LOCATION OF HIGH
IMPACT ZONES SHOULD BE INDICATED ON
CONTRACT DRAWINGS.
2. REFERENCE DS920 FOR APPROVED SEALANTS.
3. DYMONIC 100 AT 40 MILS MAY BE USED IN LIEU OF
EXOAIR 110AT.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
BY OTHERS OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
64 MM (2-1/2") MIN.
152 MM
(6") MIN.
(SEE NOTE 4)
76 MM (3") MIN.
EXOAIR 110AT
(SEE NOTE 3)
DRYVIT/TREMCO APPROVED SEALANT,
BY OTHERS (SEE NOTE 2)
WRAP DRYVIT DETAIL MESH® 64 MM (2
1
2
")
MIN. AT BACKSIDE OF INSULATION BOARD
INSULATION BOARD CLOSURE BLOCK
APPROVED SUBSTRATE
DRYVIT/TREMCO APPROVED
AIR/WATER RESISTIVE BARRIER
DRYVIT ADHESIVE
INSULATION BOARD
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
ROOF ASSEMBLY,
BY OTHERS
ROOF FLASHING AND
COUNTERFLASHING,
BY OTHERS
DYMONIC 100 LAPPED ONTO ROOF
FLASHING AT 40 MILS, 25 MM (1")
MIN. ON BOTH SUBSTRATES
WRAP DRYVIT DETAIL MESH® 64 MM (2
1
2
")
MIN. AT BACKSIDE OF INSULATION BOARD
METAL CAP FLASHING,
BY OTHERS
DYMONIC 100 AT 40 MILS
APPLIED OVER EXOAIR 110AT
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 12
©
Dryvit Systems, Inc.Date Issued: 4/2020
Parapet - Solid Substrate, Metal Coping
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR
STANDARD PLUS™ MESH. LOCATION OF HIGH
IMPACT ZONES SHOULD BE INDICATED ON
CONTRACT DRAWINGS.
2. REFERENCE DS920 FOR APPROVED SEALANTS.
3. DYMONIC 100 AT 40 MILS MAY BE USED IN LIEU OF
EXOAIR 110AT.
4. DIMENSIONS GREATER THAN 600 MM (2'-0")
REQUIRE SYSTEM CONFIGURATION SIMILAR TO
WALL FACE.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
OVERLAP 64 MM (2-1/2") MIN.
19 MM (3/4") MIN.
BY OTHERS OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
19MM (3/4") MIN.
SECUROCK EXOAIR 430
DRYVIT ADHESIVE
INSULATION BOARD
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DYMONIC 100 AT 40 MILS OVER VERTICAL LEG OF
DRYVIT VENT TRACK™, 25 MM (1") MIN. ON BOTH
SUBSTRATES (SEE NOTE 2)
DRYVIT VENT TRACK
DRYVIT VENT ASSEMBLY™
(SEE NOTE 3)
DYMONIC 100 AT 40 MILS
DRYVIT DETAIL MESH®
EMBEDDED IN BASE COAT
DRIP GROOVE
26 MM (1") MIN.
42 MM (1
5
8
") MIN.
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 13
©
Dryvit Systems, Inc.Date Issued: 4/2020
Soffit/Fascia Intersection
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR STANDARD
PLUS™ MESH. LOCATION OF HIGH IMPACT ZONES
SHOULD BE INDICATED ON CONTRACT DRAWINGS.
2. LIGHTLY SAND SURFACE OF TRACK TO MAXIMIZE
ADHESION.
3. DRYVIT VENT ASSEMBLY IS INSTALLED ONLY AT
PUNCHOUT IN DRYVIT VENT TRACK.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
203 MM (8") MIN.
SEE NOTES 2 AND 3
BY OTHERS
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
203 MM (8") MIN.
SEE NOTES 2 AND 3
26 MM (1") MIN.
42 MM (1
5
8
") MIN.
SECUROCK EXOAIR 430
DRYVIT ADHESIVE
INSULATION BOARD
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DYMONIC 100 AT 40 MILS
INSULATION BOARD CLOSURE BLOCK
DRYVIT ADHESIVE
SECUROCK EXOAIR 430
INSULATION BOARD
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
13 MM X 13MM (
1
2
" X
1
2
") CANT BEAD OF
DYMONIC 100. RASP INSULATION
BOARD TO ACCOMMODATE AS NEEDED.
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 14
©
Dryvit Systems, Inc.Date Issued: 4/2020
Inside/Outside Corners
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR STANDARD
PLUS™ MESH. LOCATION OF HIGH IMPACT ZONES
SHOULD BE INDICATED ON CONTRACT DRAWINGS.
2. DOUBLE WRAP OUTSIDE AND INSIDE CORNERS WITH
REINFORCING MESH OR USE CORNER MESH.
3. DO NOT LAP REINFORCING MESH WITHIN 203 MM (8")
OF A CORNER.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
2
0
3
M
M
(
8
"
)
M
I
N
(
S
E
E
N
O
T
E
2
)
BY OTHERS
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
SECUROCK EXOAIR 430
DRYVIT ADHESIVE
INSULATION BOARD CLOSURE BLOCK
DRYVIT BASE COAT
DRYVIT PANZER® 15 OR 20
REINFORCING MESH
DRYVIT CORNER MESH
DRYVIT REINFORCING MESH OVERLAP
MIN. OF 203 MM (8") AT CORNER
DRYVIT FINISH
(
2
6
M
M
)
1
"
M
I
N
.
(
4
2
M
M
)
1
5
8 "
M
I
N
.
DYMONIC 100 AT 40 MILS
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 15
©
Dryvit Systems, Inc.Date Issued: 4/2020
Outside Corner - High Impact
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR STANDARD
PLUS™ MESH. LOCATION OF HIGH IMPACT ZONES
SHOULD BE INDICATED ON CONTRACT DRAWINGS.
2. DO NOT LAP REINFORCING MESH WITHIN 203 MM (8")
OF A CORNER.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
BY OTHERS
Section A-A
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
A A
SEALANT MATERIAL,
BY OTHERS (SEE NOTE 4)
CLOSED CELL BACKER
ROD, BY OTHERS
19MM (3/4") MIN.
19 MM (3/4") MIN
SECUROCK EXOAIR 430
DRYVIT ADHESIVE
INSULATION BOARD
DRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DYMONIC 100 AT 40 MILS OVER VERTICAL LEG OF
DRYVIT VENT TRACK™, 25 MM (1") MIN. ON BOTH
SUBSTRATES
(SEE NOTE 3)
DRYVIT VENT TRACK™
DRYVIT VENT ASSEMBLY™
DYMONIC 100 AT 40 MILS, 25 MM (1") MIN.
ON BOTH SUBSTRATES
DRYVIT/TREMCO APPROVED SEALANT
(SEE NOTE 4)
SLOPE SURFACE TO DRAIN (MIN. 1:5)
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACE(S) TO RECEIVE SEALANT
INSULATION BOARD CLOSURE BLOCK
WRAP DRYVIT DETAIL MESH® 64 MM (2
1
2
")
MIN. AT BACKSIDE OF INSULATION BOARD
77 MM (3") MIN.
DRYVIT/TREMCO APPROVED AIR/WATER RESISTIVE BARRIER
SEALANT AND BOND BREAKER AGAINST
DYMONIC 100 AT VENT ASSEMBLY ONLY
LOCATION OF VENT ASSEMBLY
DYMONIC 100
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 16
©
Dryvit Systems, Inc.Date Issued: 4/2020
Horizontal Expansion Joint
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR STANDARD
PLUS™ MESH. LOCATION OF HIGH IMPACT ZONES
SHOULD BE INDICATED ON CONTRACT DRAWINGS.
2. DRYVIT VENT ASSEMBLY IS INSTALLED ONLY AT
PUNCHOUT IN DRYVIT VENT TRACK.
3. LIGHTLY SAND SURFACE OF TRACK TO MAXIMIZE
ADHESION.
4. REFERENCE DS920 FOR APPROVED SEALANTS.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
BY OTHERS
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
A A 19 MM (3/4") MIN.
19 MM (3/4") MIN.
Section A-A
SEALANT MATERIAL,
BY OTHERS (SEE NOTE 5)
CLOSED CELL BACKER
ROD, BY OTHERS
SEALANT AND BOND BREAKER AGAINST
DYMONIC SIMPLE SEAL AT VENT ASSEMBLY ONLY
LOCATION OF VENT ASSEMBLY
DYMONIC 100
SECUROCK EXOAIR 430
DRYVIT ADHESIVE
INSULATION BOARD
DRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DYMONIC 100 AT 40 MILS OVER VERTICAL LEG OF
DRYVIT VENT TRACK™, 25 MM (1") MIN. ON BOTH
SUBSTRATES
(SEE NOTE 4)
DRYVIT VENT TRACK™
DRYVIT VENT ASSEMBLY™
DYMONIC SIMPLE SEAL OVER CLOSED CELL
BACKER ROD, CENTERED OVER JOINT
ADHERED WITH DYMONIC 100 AT BOTH ENDS
SLOPE SURFACE TO DRAIN (MIN. 1:5)
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACE(S) TO RECEIVE SEALANT
INSULATION BOARD CLOSURE BLOCK
WRAP DRYVIT DETAIL MESH® 64 MM (2
1
2
")
MIN. AT BACKSIDE OF INSULATION BOARD
SLIP TYPE
CONNECTION
26 MM (1") MIN -
38 MM (1
1
2
") MAX.
(BOTH ENDS OF
DYMONIC
SIMPLE SEAL)
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 17
©
Dryvit Systems, Inc.Date Issued: 4/2020
Horizontal Slip Joint
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR STANDARD
PLUS™ MESH. LOCATION OF HIGH IMPACT ZONES
SHOULD BE INDICATED ON CONTRACT DRAWINGS.
2. EXPANSION JOINT IN THE OUTSULATION PE
SECUROCK EXOAIR 430 SYSTEM IS NECESSARY WHERE
SIGNIFICANT DIFFERENTIAL MOVEMENT IS EXPECTED
AT FLOOR LINES.
3. LOCATE EXTERNAL SEALANT JOINT A MAXIMUM OF 51
MM (2") BELOW BREAK IN SUBSTRATE.
4. LIGHTLY SAND SURFACE OF TRACK TO MAXIMIZE
ADHESION.
5. REFERENCE DS920 FOR APPROVED SEALANTS.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
19 MM (3/4") MIN.
OPTION
A
A
A-A
BY OTHERS
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
REAR SEAL (SEE NOTE 2)
SECUROCK EXOAIR 430
DYMONIC 100 AT 40 MILS, 25 MM (1") MIN.
ON BOTH SUBSTRATES
WRAP DRYVIT DETAIL MESH® 64 MM (2
1
2
")
MIN. AT BACKSIDE OF INSULATION BOARD
DRYVIT/TREMCO APPROVED SEALANT
(SEE NOTE 2)
APPROVED SUBSTRATE
DRYVIT/TREMCO APPROVED
AIR/WATER RESISTIVE
BARRIER
DRYVIT ADHESIVE
INSULATION CLOSURE
BLOCK
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACE(S) TO RECEIVE SEALANT
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACE(S) TO RECEIVE SEALANT
DRYVIT/TREMCO APPROVED SEALANT
(SEE NOTE 2)
FACE SEAL
REAR SEAL
VENT
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 18
©
Dryvit Systems, Inc.Date Issued: 4/2020
Vertical Expansion Joint Options
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR STANDARD
PLUS™ MESH. LOCATION OF HIGH IMPACT ZONES
SHOULD BE INDICATED ON CONTRACT DRAWINGS.
2. REFERENCE DS920 FOR APPROVED SEALANTS.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
BY OTHERS
19 MM (3/4") MIN.
APPROVED SUBSTRATE
DRYVIT/TREMCO APPROVED
AIR/WATER RESISTIVE
BARRIER
WRAP DRYVIT DETAIL MESH® 64 MM (2
1
2
")
MIN. AT BACKSIDE OF INSULATION BOARD
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACE(S) TO RECEIVE SEALANT
DRYVIT/TREMCO APPROVED SEALANT
(SEE NOTE 2)
OPTIOINAL WILLSEAL
SECONDARY SEAL,
BY OTHERS
SECUROCK EXOAIR 430
DRYVIT ADHESIVE
INSULATION BOARD
CLOSURE BLOCK
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
INSULATION BOARD
DRYVIT FINISH
DYMONIC SIMPLE SEAL OVER CLOSED
CELL BACKER ROD, CENTERED OVER
JOINT ADHERED WITH DYMONIC 100 AT
BOTH ENDS
26 MM (1") MIN -
38 MM (1
1
2
") MAX.
(BOTH ENDS OF
DYMONIC
SIMPLE SEAL)
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 19
©
Dryvit Systems, Inc.Date Issued: 4/2020
Structural Expansion Joints
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR STANDARD
PLUS™ MESH. LOCATION OF HIGH IMPACT ZONES
SHOULD BE INDICATED ON CONTRACT DRAWINGS.
2. REFERENCE DS920 FOR APPROVED SEALANTS.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
19 MM (3/4") MIN.
102 MM (4") MAX.
(SEE NOTE 2)
BY OTHERS
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
19 MM (3/4") MIN.
SECUROCK EXOAIR 430
DRYVIT ADHESIVE
INSULATION BOARD
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
WRAP DRYVIT DETAIL MESH® 64 MM (2
1
2
")
MIN. AT BACKSIDE OF INSULATION BOARD
DRYVIT/TREMCO APPROVED SEALANT
(SEE NOTE 3)
DRYVIT DEMANDIT® OR COLOR PRIME™
ON SURFACE(S) TO RECEIVE SEALANT
DYMONIC 100 OVER CLOSED CELL BACKER ROD
OPTIOINAL WILLSEAL SECONDARY
SEAL, BY OTHERS
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 20
©
Dryvit Systems, Inc.Date Issued: 4/2020
Minor Penetrations
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR STANDARD
PLUS™ MESH. LOCATION OF HIGH IMPACT ZONES
SHOULD BE INDICATED ON CONTRACT DRAWINGS.
2. FOR LARGER PENETRATIONS REFER TO MAJOR
PENETRATIONS DETAIL.
3. REFERENCE DS920 FOR APPROVED SEALANTS.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
INSULATION BOARD
DRYVIT TRACK
241 MM X 305 MM
(9-1/2" X 12") DETAIL
MESH® "BUTTERFLIES"
INSULATION BOARD CLOSURE
BLOCKS WRAPPED WITH DRYVIT
DETAIL MESH®
WRAP DRYVIT DETAIL MESH® 64 MM (2
1
2
")
MIN. AT BACKSIDE OF INSULATION BOARD
EXTEND DETAIL MESH 152 MM (6") ON
SILL & JAMB; HEAD & JAMB SIMILAR
SPLICE PIECE OF DETAIL REINFORCING
MESH REQUIRED AT CORNER
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 21
©
Dryvit Systems, Inc.Date Issued: 4/2020
Major Penetrations
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR STANDARD
PLUS™ MESH. LOCATION OF HIGH IMPACT ZONES
SHOULD BE INDICATED ON CONTRACT DRAWINGS.
2. LOCATE INSULATION BOARDS SUCH THAT BOARD
EDGES DO NOT ALIGN WITH CORNERS OF
PENETRATION.
3. TO MINIMIZE CRACKING AT CORNERS OF
PENETRATIONS INSTALL DIAGONAL REINFORCING
MESH.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
OUTSULATION
PE
SECUCOCK
EXOAIR
430
SYSTEM
BY OTHERS BY OTHERS
12.7 MM (1/2") MIN.
SECUROCK EXOAIR 430
NON-CORROSIVE SLEEVE
DRYVIT/TREMCO APPROVED
SEALANT (SEE NOTE ***)
SIGN FIXTURE
BEARING WASHER
SCREW/BOLT ATTACHMENT
TO BUILDING FRAMING
DRYVIT ADHESIVE
INSULATION BOARD
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
BLOCKING (SECURED
TO FRAMING)
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 22
©
Dryvit Systems, Inc.Date Issued: 4/2020
Sign Attachment
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR STANDARD
PLUS™ MESH. LOCATION OF HIGH IMPACT ZONES
SHOULD BE INDICATED ON CONTRACT DRAWINGS.
2. ENTIRE PERIMETER OF PIPE SLEEVE IS CAULKED TO
PREVENT WATER ENTRY INTO WALL.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
64 MM (2 1/2")
BY OTHERSOUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
51 MM (2") MIN.
(SEE NOTE 2)
SECUROCK EXOAIR 430
DRYVIT ADHESIVE
INSULATION BOARD
DRYVIT DETAIL MESH® EMBEDDED
IN DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
SLOPE BOTTOM SURFACE
FOR DRAINAGE (TYP.)
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 23
©
Dryvit Systems, Inc.Date Issued: 4/2020
Aesthetic Reveals
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR DELIBERATE
IMPACT HAVE THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD™ OR STANDARD
PLUS™ MESH. LOCATION OF HIGH IMPACT ZONES
SHOULD BE INDICATED ON CONTRACT DRAWINGS.
2. 51 MM (2") THICKNESS OF EPS IS REQUIRED AT BASE
OF REVEALS.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
BY OTHERS
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
OVERLAP 64 MM (2 1/2")
SLOPE TOP SURFACE FOR
POSITIVE DRAINAGE
SECUROCK EXOAIR 430
DRYVIT ADHESIVE
INSULATION BOARD
DRYVIT REINFORCING
MESH EMBEDDED IN
DRYVIT BASE COAT
DRYVIT FINISH
SECUROCK EXOAIR 430
INSULATION BOARD
DRYVIT ADHESIVE
DRYVIT DETAIL MESH® LAPPED 64
MM (2
1
2
") MIN. ONTO ADJACENT EPS
DRYVIT FINISH
DRYVIT ADHESIVE
EPS FOAM SHAPE (SEE NOTES 1, 2)
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 24
©
Dryvit Systems, Inc.Date Issued: 4/2020
Projecting Graphics
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
NOTE:
1. MAXIMUM THICKNESS OF EPS BUILT OUT SHAPES
SHALL NOT EXCEED 318 MM (12
1
2
" INCHES) AT ANY
POINT MEASURED FROM THE SUBSTRATE.
2. PERCENTAGE OF WALL AREA COVERED BY EPS
FOAM SHAPES IN EXCESS OF 102 MM (4 IN) IN
THICKNESS SHALL NOT EXCEED 15%.
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
51 MM (2") MIN.
OUTSULATION PE SECUROCK
EXOAIR 430 SYSTEM
BY OTHERS
SLOPE GRAPHIC FOR
POSITIVE DRAINAGE
SECUROCK EXOAIR 430
DRYVIT ADHESIVE
INSULATION BOARD
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE
COAT
DRYVIT FINISH
SECUROCK EXOAIR 430
INSULATION BOARD
DRYVIT ADHESIVE DRYVIT DETAIL MESH® LAPPED 64
MM (2
1
2
") MIN. BENEATH DRYVIT
REINFORCING MESH EMBEDDED IN
DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 25
©
Dryvit Systems, Inc.Date Issued: 4/2020
Recessed Graphics
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.
51 MM (2")
152 MM
(6")
305 MM (12")
203 MM (8")
19 MM (3/4")
143 MM
(5 5/8")
Outsulation® PE Securock® ExoAir 430 System® OSPE SE430 - 26
©
Dryvit Systems, Inc.Date Issued: 4/2020
Dryvit Vent Assembly™
550 West Adams StreetChicago, IL 60661
USG Technical & Customer Support:800.USG.4YOU (874-4968)
3735 Green RoadBeachwood, OH 44122
Tremco Technical Support:866.209.2404
One Energy WayWest Warwick, RI 02893
Dryvit Support:800.556.7752
™
SECUROCK EXOAIR 430®®
®
™
The architecture, engineering, and design of the project using United States
Gypsum Company ("USG"), Tremco Incorporated ("Tremco") and Dryvit Systems,
Inc. ("Dryvit") products is the responsibility of the project's design professional. All
systems must comply with local building codes and standards. This detail is for
general information and guidance only and the aforementioned specifically disclaim
any liability for the use of this detail and for the architecture, design, engineering or
workmanship of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is best suited for the
project. Use of a functionally equivalent detail does not violate the warranty. This
detail is subject to change without notice.