Outsulation® Panelized DUK111
Lightweight Insulated Exterior Wall Panels
Outsulation Panel System Fabrication/Installation Details
1-02
1/023
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
GRADE LEVEL HORIZONTAL
ANGLE
OP 0.0.09
OP 0.0.07
OP 0.0.06
OP 0.0.05
OP 0.0.04
OP 0.0.03
OP 0.0.02
OP 0.0.01
OP 0.0.10
OP 0.0.08
INTERMEDIATE LEVEL - CONTINUOUS
WINDOW SILL - A
OP 0.0.11OP 0.0.12WINDOW JAMB
WINDOW HEAD OP 0.0.13OP 0.0.14
OP 0.0.17OP 0.0.16
OP 0.0.15
OP 0.0.18OP 0.0.19OP 0.0.20
OP 0.0.21
OP 0.0.24
OP 0.0.23
OP 0.0.22
SYSTEM PENETRATIONS
OP 0.0.25OP 0.0.26
OP 0.0.27
OP 0.0.28
OP 0.0.29
SPANDREL PANEL
SPANDREL PANELINTERMEDIATE LEVEL HORIZONTAL
INTERMEDIATE LEVEL HORIZONTALSPANDREL PANEL
SPANDREL PANEL WITH SOFFITGRADE LEVEL HORIZONTAL
HORIZONTAL SPANDREL PANELINTERMEDIATE LEVEL 3-D
ROOF LEVEL HORIZONTALPARAPET PANEL
PARAPET PANEL WITH SOFFITROOF LEVEL HORIZONTAL
BOLTED TRACK TO CONCRETE SLAB
WINDOW SILL - BWINDOW SILL - C
WINDOW HEAD - WITH SOFFITPARAPET PANEL - METAL CAP
FLASHINGHORIZONTAL PANEL JOINTVERTICAL PANEL JOINT
EPS GRAPHICS
ANGLEINTERMEDIATE LEVEL - SLIDE CLIP
INTERMEDIATE LEVEL - CONNECTIONTO STRUCTURAL BEAM
INTERMEDIATE LEVEL - WELDED CLIPTO PERIMETER ANGLE
AT PANEL FRAMING
PANEL BRACE CONNECTION
BRACE TO DECK CONNECTIONCOLUMN COVER - STEEL
CONSTRUCTION
CONSTRUCTIONCOLUMN COVER - CONCRETE
CORNER COLUMN COVER - STEELCONSTRUCTION
RADIUS VERTICAL PANEL
28
29
2526
27
24
23
3
121314
1716
15
181920
21
22
9
7
6
5
4
10
8
11
2
1
DETAIL PAGE DETAIL PAGE
NOTE
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC
DRYVIT MAKES NO REPRESENTATION REGARDING CONFORMITY
OF ITS SUGGESTIONS TO MODEL BUILDING CODES, ENGINEERING
CRITERIA, SPECIFIC APPLICATIONS OR PROJECT LOCATIONS.
ALL COMPONENTS INDICATED IN ILLUSTRATIONS, AS WELL AS
OTHERS THAT MAY BE REQUIRED FOR THE INTEGRITY OF THE
SYSTEM SHALL BE DESIGNED, DETAILED AND ENGINEERED BY
REPRESENTATIVES OF THE ARCHITECT, OWNER OR CONTRACTOR
TO BE IN CONFORMANCE WITH MODEL CODES, ARCHITECTURAL
AND ENGINEERING REQUIREMENTS PERTAINING TO SPECIFIC
BUILDING PROJECTS.
DRYVIT MAKES NO WARRANTY, EXPRESSED OR IMPLIED,
AS TO THE ARCHITECTURAL DESIGN, ENGINEERING, OR
WORKMANSHIP OF PROJECTS UTILIZING DRYVIT SYSTEMS
OR PRODUCTS.
THE LIABILITIES OF DRYVIT SHALL BE AS STATED IN DRYVIT'S
STANDARD WARRANTY. CONTACT DRYVIT FOR A FULL AND
COMPLETE COPY OF THE WARRANTY.
RS
Grade Level Horizontal Spandrel Panel
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
Printed in U.S.A.1998 DryvitC
APPROVED BY: REV:
R
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship of
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
DATE:
version.
RS
Intermediate Level Horizontal Spandrel Panel
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Intermediate Level Horizontal Spandrel Panel with Brace
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Grade Level Spandrel Panel With Soffit
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Intermediate Level 3-D Horizontal Spandrel Panel
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Roof Level Parapet Panel
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Roof Level Parapet Panel With Soffit
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Bolted Track to Concrete Slab
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Window Sill - A
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Window Sill - B
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC
®
™
™
RS
Window Sill - C
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC
®
™
™
RS
Window Jamb
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC
®
™
RS
Window Head
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
®
™
Window Head with Soffit
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC
®
™
RS
Parapet Panel - Metal Cap Flashing
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Horizontal Panel Joint
1/022
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
®
™
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Vertical Panel Joint
1/022
NOTE:
1.
TM
R
TM
APPROVED BY: REV: DATE:
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD
BE INDICATED ON CONTRACT DRAWINGS.
®
™
RS
Outsulation Panelized
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC
System Penetrations
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC
®
™
RS
EPS Graphics
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Intermediate Level - Continuous Angle
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Intermediate Level - Slide Clip Angle
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Intermediate Level - Connection to Structural Beam
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Intermediate Level - Welded Clip to Perimeter Angle
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Panel Brace Connection at Panel Framing
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Brace to Deck Connection
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC RS
Column Cover - Steel Construction
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC
®
™
RS
Column Cover - Concrete Construction
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC
®
™
RS
Corner Column Cover - Steel Construction
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC
®
™
RS
Radius Vertical Panel
1/022
DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED
TO ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NOTE:
1.
TM
R
TM
Outsulation Panelized
APPROVED BY: REV:
R
DATE:
and Dryvit specifically disclaims any liability for the use of this
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Printed in U.S.A.1998 DryvitC
®
™
RS