Outsulation® Panelized DUK111 Lightweight Insulated Exterior Wall Panels Outsulation Panel System Fabrication/Installation Details 1-02

Upload: others

Post on 03-Feb-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

Outsulation® Panelized DUK111

Lightweight Insulated Exterior Wall Panels

Outsulation Panel System Fabrication/Installation Details

1-02

1/023

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

GRADE LEVEL HORIZONTAL

ANGLE

OP 0.0.09

OP 0.0.07

OP 0.0.06

OP 0.0.05

OP 0.0.04

OP 0.0.03

OP 0.0.02

OP 0.0.01

OP 0.0.10

OP 0.0.08

INTERMEDIATE LEVEL - CONTINUOUS

WINDOW SILL - A

OP 0.0.11OP 0.0.12WINDOW JAMB

WINDOW HEAD OP 0.0.13OP 0.0.14

OP 0.0.17OP 0.0.16

OP 0.0.15

OP 0.0.18OP 0.0.19OP 0.0.20

OP 0.0.21

OP 0.0.24

OP 0.0.23

OP 0.0.22

SYSTEM PENETRATIONS

OP 0.0.25OP 0.0.26

OP 0.0.27

OP 0.0.28

OP 0.0.29

SPANDREL PANEL

SPANDREL PANELINTERMEDIATE LEVEL HORIZONTAL

INTERMEDIATE LEVEL HORIZONTALSPANDREL PANEL

SPANDREL PANEL WITH SOFFITGRADE LEVEL HORIZONTAL

HORIZONTAL SPANDREL PANELINTERMEDIATE LEVEL 3-D

ROOF LEVEL HORIZONTALPARAPET PANEL

PARAPET PANEL WITH SOFFITROOF LEVEL HORIZONTAL

BOLTED TRACK TO CONCRETE SLAB

WINDOW SILL - BWINDOW SILL - C

WINDOW HEAD - WITH SOFFITPARAPET PANEL - METAL CAP

FLASHINGHORIZONTAL PANEL JOINTVERTICAL PANEL JOINT

EPS GRAPHICS

ANGLEINTERMEDIATE LEVEL - SLIDE CLIP

INTERMEDIATE LEVEL - CONNECTIONTO STRUCTURAL BEAM

INTERMEDIATE LEVEL - WELDED CLIPTO PERIMETER ANGLE

AT PANEL FRAMING

PANEL BRACE CONNECTION

BRACE TO DECK CONNECTIONCOLUMN COVER - STEEL

CONSTRUCTION

CONSTRUCTIONCOLUMN COVER - CONCRETE

CORNER COLUMN COVER - STEELCONSTRUCTION

RADIUS VERTICAL PANEL

28

29

2526

27

24

23

3

121314

1716

15

181920

21

22

9

7

6

5

4

10

8

11

2

1

DETAIL PAGE DETAIL PAGE

NOTE

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC

DRYVIT MAKES NO REPRESENTATION REGARDING CONFORMITY

OF ITS SUGGESTIONS TO MODEL BUILDING CODES, ENGINEERING

CRITERIA, SPECIFIC APPLICATIONS OR PROJECT LOCATIONS.

ALL COMPONENTS INDICATED IN ILLUSTRATIONS, AS WELL AS

OTHERS THAT MAY BE REQUIRED FOR THE INTEGRITY OF THE

SYSTEM SHALL BE DESIGNED, DETAILED AND ENGINEERED BY

REPRESENTATIVES OF THE ARCHITECT, OWNER OR CONTRACTOR

TO BE IN CONFORMANCE WITH MODEL CODES, ARCHITECTURAL

AND ENGINEERING REQUIREMENTS PERTAINING TO SPECIFIC

BUILDING PROJECTS.

DRYVIT MAKES NO WARRANTY, EXPRESSED OR IMPLIED,

AS TO THE ARCHITECTURAL DESIGN, ENGINEERING, OR

WORKMANSHIP OF PROJECTS UTILIZING DRYVIT SYSTEMS

OR PRODUCTS.

THE LIABILITIES OF DRYVIT SHALL BE AS STATED IN DRYVIT'S

STANDARD WARRANTY. CONTACT DRYVIT FOR A FULL AND

COMPLETE COPY OF THE WARRANTY.

RS

Grade Level Horizontal Spandrel Panel

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

Printed in U.S.A.1998 DryvitC

APPROVED BY: REV:

R

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship of

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

DATE:

version.

RS

Intermediate Level Horizontal Spandrel Panel

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Intermediate Level Horizontal Spandrel Panel with Brace

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Grade Level Spandrel Panel With Soffit

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Intermediate Level 3-D Horizontal Spandrel Panel

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Roof Level Parapet Panel

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Roof Level Parapet Panel With Soffit

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Bolted Track to Concrete Slab

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Window Sill - A

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Window Sill - B

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC

®

RS

Window Sill - C

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC

®

RS

Window Jamb

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC

®

RS

Window Head

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

®

Window Head with Soffit

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC

®

RS

Parapet Panel - Metal Cap Flashing

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Horizontal Panel Joint

1/022

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

®

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Vertical Panel Joint

1/022

NOTE:

1.

TM

R

TM

APPROVED BY: REV: DATE:

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD

BE INDICATED ON CONTRACT DRAWINGS.

®

RS

Outsulation Panelized

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC

System Penetrations

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC

®

RS

EPS Graphics

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Intermediate Level - Continuous Angle

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Intermediate Level - Slide Clip Angle

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Intermediate Level - Connection to Structural Beam

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Intermediate Level - Welded Clip to Perimeter Angle

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Panel Brace Connection at Panel Framing

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Brace to Deck Connection

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC RS

Column Cover - Steel Construction

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC

®

RS

Column Cover - Concrete Construction

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC

®

RS

Corner Column Cover - Steel Construction

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Printed in U.S.A.1998 DryvitC

®

RS

Radius Vertical Panel

1/022

DRYVIT RECOMMENDS THAT GROUND FLOOR

APPLICATIONS AND ALL FACADES EXPOSED

TO ABNORMAL STRESS, HIGH TRAFFIC, OR

DELIBERATE IMPACT HAVE THE BASE COAT

REINFORCED WITH PANZER MESH PRIOR TO

STANDARD OR STANDARD PLUS MESH.

LOCATION OF HIGH IMPACT ZONES SHOULD BE

INDICATED ON CONTRACT DRAWINGS.

NOTE:

1.

TM

R

TM

Outsulation Panelized

APPROVED BY: REV:

R

DATE:

and Dryvit specifically disclaims any liability for the use of this

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.