OUTSULATION® PE SYSTEM™
A Pressure – Equalized Rainscreen Exterior Insulation and Finish System With Moisture Drainage That Incorporates Continuous Insulation and An Air/Water-Resistive Barrier
Outsulation PE System Installation Details
DS846
OUTSULATION® PE SYSTEM®
- GROOVE PATTERN
DRYVIT SYSTEMS, INC. MAKES NO REPRESENTATIONREGARDING CONFORMITY OF ITS SUGGESTIONS TO MODELBUILDING CODES, ENGINEERING CRITERIA, SPECIFICAPPLICATIONS OR PROJECT LOCATIONS. ALL COMPONENTSINDICATED IN ILLUSTRATIONS, AS WELL AS OTHERS THATMAY BE REQUIRED FOR THE INTEGRITY OF THE SYSTEMSHALL BE DESIGNED, DETAILED AND ENGINEERED BYREPRESENTATIVES OF THE ARCHITECT, OWNER ORCONTRACTOR TO BE IN CONFORMANCE WITH MODEL CODES,ARCHITECTURAL AND ENGINEERING REQUIREMENTSPERTAINING TO SPECIFIC BUILDING PROJECTS.
DRYVIT SYSTEMS, INC. MAKES NO WARRANTY, EXPRESSEDOR IMPLIED, AS TO THE ARCHITECTURAL DESIGN,ENGINEERING, OR WORKMANSHIP OF PROJECTS UTILIZINGDRYVIT SYSTEMS OR PRODUCTS.
THE LIABILITIES OF DRYVIT SYSTEMS, INC. SHALL BE ASSTATED IN THE OUTSULATION PE LIMITED COMMERCIALWARRANTY. CONTACT DRYVIT SYSTEMS, INC. FOR A FULLAND COMPLETE COPY OF THE OUTSULATION PE WARRANTY.
TABLE OF CONTENTS
NOTE
OSPE 0.0.02
HEAD/SILL
DETAIL
OUTSULATION PE SYSTEM
INSULATION BOARD LAYOUT
INSULATION BOARD
FOUNDATION
PARAPET - STEEL FRAMED,
OUTSIDE CORNER- INSULATION BOARD LAYOUT
TERMINATION AT CONCRETE
PARAPET - SOLID SUBSTRATE,
INSIDE/OUTSIDE CORNERSOUTSIDE CORNER - HIGH IMPACT
METAL COPING
METAL COPING
BUILDING FACADE
JAMB
OSPE 0.0.14OSPE 0.0.13
OSPE 0.0.12
OSPE 0.0.11OSPE 0.0.10OSPE 0.0.09OSPE 0.0.08
OSPE 0.0.06
OSPE 0.0.05
OSPE 0.0.04OSPE 0.0.03
OSPE 0.0.01
OSPE 0.0.15
COMPARTMENT SEPARATION OSPE 0.0.07
SOFFIT/FASCIA INTERSECTION
VERTICAL EXPANSION JOINT OPTIONS
HORIZONTAL EXPANSION JOINT
MINOR PENETRATIONS
HORIZONTAL SLIP JOINT
MAJOR PENETRATIONS
AESTHETIC REVEALSPROJECTING GRAPHICSRECESSED GRAPHICSDRYVIT VENT ASSEMBLY™
SIGN ATTACHMENT
OSPE 0.0.16OSPE 0.0.17OSPE 0.0.18OSPE 0.0.19OSPE 0.0.20OSPE 0.0.21OSPE 0.0.22OSPE 0.0.23
STRUCTURAL EXPANSION JOINTS
OSPE 0.0.24
OSPE 0.0.26OSPE 0.0.25
The architecture, engineering and design of the project using
the Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building
codes and standards. This detail is for general information
and guidance only and Dryvit specifically disclaims any
liability for the use of this detail and for the architecture,
design, engineering or workmanship of any project. The
project design professional determines, in its sole discretion,
whether this detail or a functionally equivalent alternative is
best suited for the project. Use of a functionally equivalent
detail does not violate Dryvit's warranty. This detail is subject
to change without notice. Contact Dryvit to insure you have
the most recent version.
©
Dryvit Systems, Inc.
Issued: 10/2016
Outsulation PE System
NOTE:DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHDRYVIT PANZER® MESH PRIOR TODRYVIT REINFORCING MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
1.
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship of
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
version.
EIMASTANDARD
IMPACT
EIMAULTRA-HIGH
IMPACT
OUTSULATION® PE SYSTEM®
LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.
2.
OSPE 0.0.01
APPROVED SUBSTRATE
FRAMING
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
INSULATION BOARD
DRYVIT REINFORCING MESH
APPROVED SUBSTRATEFRAMING
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
EPS INSULATION BOARD
DRYVIT REINFORCING MESH
DRYVIT FINISHDRYVIT VENT ASSEMBLY
DRYVIT BASE COAT
PANZER® 15 OR 20 REINFORCINGMESH (SEE NOTE 1)
DRYVIT BASE COAT
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION
DRYVIT VENT TRACK™
DRYVIT FINISH
DRYVIT VENT ASSEMBLY™
DRYVIT BASE COAT
DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT TEXTUREOVER GRID TAPE™(SEE NOTE 2)DRYVIT BASE COAT
DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT TEXTUREOVER GRID TAPE LAPPED OVERDRYVIT VENT TRACK(SEE NOTE 2)
DRYVIT BASE COAT
©
Dryvit Systems, Inc.
Issued: 10/2016
Building Facade
OSPE 0.0.02
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship of
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
version.
v
v
v
v
v
v
v
v
v
v
v
v
COMPARTMENT LOCATIONSDETERMINED PER ASCE 7-10 ANDDRYVIT OUTSULATION PE SYSTEMSPECIFICATIONS DS844.
NOTES:1.
OUTSULATION® PE SYSTEM®
DRYVIT VENT ASSEMBLY™
DRYVIT VENT TRACK™(DRAIN HOLE LOCATED ATVENT ASSEMBLY)DRYVIT TRACK (NO DRAINHOLES)
305 MM (12") DRYVITCLOSURE BLOCKS TYP.
152 MM (6") DRYVITSTARTER STRIP TYP.
152 MM (6") DRYVITCLOSURE BLOCKS TYP.
COMPARTMENTSEPARATION TYP.
©
Dryvit Systems, Inc.
Issued: 10/2016
OUTSULATION® PE SYSTEM®
OUTSULATION PESYSTEM
BY OTHERS
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
Insulation Board Layout
version.
OSPE 0.0.03
FRAMING, BY OTHERS
APPROVED SUBSTRATE,BY OTHERS
INSULATION BOARD
VERTICAL DRAINAGEGROOVES (ALIGNED)
HORIZONTAL BEVELEDGROOVES
DRYVIT STARTER STRIP
DRYVIT VENT ASSEMBLY™
DRYVIT VENT TRACK™
©
Dryvit Systems, Inc.
Issued: 10/2016
305 MM(1'-0")"
OUTSULATION® PE SYSTEM®
INSTALL SQUARE EDGED CORNERCLOSURE BLOCKS ON ALTERNATINGSIDES OF OUTSIDE CORNERS.
NOTES:1.
152 MM (0'-6")
610 MM (2'-0")
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
Outside Corner - Insulation Board
version.
OSPE 0.0.04
ALTERNATING SQUAREEDGED CORNER CLOSURE
BLOCKS (TYPICAL)
DRYVIT VENTASSEMBLY™
VERTICAL DRAINAGEGROOVES (ALIGNED)
DRYVIT STARTER STRIP
MITER JOINT BETWEEN STARTER STRIPS
©
Dryvit Systems, Inc.
Issued: 10/2016
45
Insulation Board- Groove Pattern
OSPE 0.0.05
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship of
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
version.
BEVELDETAIL
51 MM (2") MIN
12.7 MM (1/2")
OUTSULATION® PE SYSTEM®
1.2 M (4'-0")
305 MM (12")
ON CENTER
610 MM(2'-0")
6.4 MM X 25 MM (14" X 1")VERTICAL DRAINAGE GROOVE
BEVEL ALONG PERIMETEROF INSULATION BOARD
©
Dryvit Systems, Inc.
Issued: 10/2016
OUTSULATION® PE SYSTEM®
FILL DRYVIT VENT TRACK ATCLOSURE BLOCK LOCATION WITH APADHESIVE PRIOR TO SETTINGCLOSURE BLOCK, TO PROVIDECOMPARTMENT CLOSURE.
ADHERE CLOSURE BLOCKS ANDSTARTER STRIPS USING "RIBBON &DAB" ADHESIVE PATTERN TOPROVIDE COMPARTMENT CLOSURE.
2.
NOTES:1.
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
Compartment Separation
version.
OUTSULATION PESYSTEM
BY OTHERS
OSPE 0.0.06
LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.
3.
VERTICAL DRAINAGEGROOVES (ALIGNED)
INSULATION BOARD
DRYVIT VENT ASSEMBLY™
INSULATION BOARD CLOSURE BLOCK(SEE NOTE 1)
DRYVIT STARTER STRIP(SEE NOTE 1)
DRYVIT VENT TRACK™
DRYVIT AP ADHESIVE(SEE NOTE 2)
DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT TEXTURE OVER GRID TAPEOVER VERTICAL LEG OF DRYVIT VENTTRACK OR TRACK (SEE NOTE 3)
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
FRAMING
©
Dryvit Systems, Inc.
Issued: 10/2016
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
of any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.DRYVIT VENT ASSEMBLY IS INSTALLED ONLYAT PUNCHOUT IN DRYVIT VENT TRACK.
OUTSULATION® PE SYSTEM® NOTE:
2.
1.
LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.
EXPANSION JOINT IS REQUIRED ALONGTOP OF FOUNDATION IF 610 MM (2'-0')DIMENSION IS EXCEEDED.
4.
3.
version.
203 MM (8") MIN.
Foundation
BY OTHERS
OSPE 0.0.07
SLOPE GRADE AWAYFROM FOUNDATION WALL
OUTSULATION PESYSTEM
19 MM (3/4") MIN.APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT VENT TRACK(SEE NOTE 4)
INSULATION BOARD
DRYVIT VENT TRACK™
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COATDRYVIT FINISH
WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT UNDERSIDEOF INSULATION
DRYVIT VENT ASSEMBLY™
DRYVIT ADHESIVE
DRYVIT AQUAFLASH SYSTEM OR DRYVITBACKSTOP NT-TEXTURE OVER GRID TAPE
©
Dryvit Systems, Inc.
Issued: 10/2016
OUTSULATION® PE SYSTEM®
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
NOTE:1. LIGHTLY SAND SURFACE OF TRACK
TO MAXIMIZE ADHESION.2.
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Termination At Concrete
BY OTHERS OUTSULATION PESYSTEM
OSPE 0.0.08
19 MM (3/4") MIN.
19 MM (3/4") MIN.
APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT VENT TRACK™
COMPATIBLE SEALANT ANDCLOSED CELL BACKER ROD,BY OTHERS
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COATDRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT VENT TRACK(SEE NOTE 2)
DRYVIT VENT ASSEMBLY™
WRAP DRYVIT DETAIL MESH® 51 MM(2") MIN. AT BACKSIDE OF INSULATION
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
DRYVIT ADHESIVEINSULATION BOARD
DRYVIT AQUAFLASH SYSTEM OR DRYVITBACKSTOP NT-TEXTURE OVER GRID TAPE
©
Dryvit Systems, Inc.
Issued: 10/2016
Head/Sill
SILL PAN FLASHING
LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.
SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship
of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
SILL
1.
2. FOR CONTINUOUS WINDOWS, USE CLOSUREBLOCKS TO TERMINATE SYSTEM AT SILL.
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
NOTE:OUTSULATION® PE SYSTEM®
3.
4.
OSPE 0.0.09
HEAD
BY OTHERS OUSTULATION PESYSTEM
AS AN OPTION, DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF AQUAFLASH SYSTEM.
5.
64 MM(2-1/2") MIN.
12.7 MM(1/2")
19 MM (3/4") MIN.
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING
DRYVIT VENT TRACK™
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT STARTER STRIP
DRYVIT FINISH
WRAP DRYVIT DETAIL MESH® 51 MM (2")MIN. AT BACKSIDE OF INSULATION BOARD
DRYVIT AQUAFLASH SYSTEM (SEE NOTE 5)
COMPATIBLE SEALANT WITHBOND BREAKER, BY OTHERS
INSULATION BOARD
INSULATION BOARD CLOSURE BLOCK
DRYVIT ADHESIVE
DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT VENT TRACK™(SEE NOTE 4)
DRYVIT AQUAFLASH SYSTEM OR DRYVITBACKSTOP NT-TEXTURE OVER GRID TAPE
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT
CONTINUOUS FLASHING, BY OTHERS
CONTINUOUS FLASHING, BY OTHERS
COMPATIBLE SEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS (SEE NOTE 3)
©
Dryvit Systems, Inc.
Issued: 10/2016
OUTSULATION® PE SYSTEM®
1. NOTE:
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
version.
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship
of any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED INLIEU OF DRYVIT AQUAFLASH SYSTEM.
SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVEON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
3.
2.
Jamb
OUTSULATION PESYSTEM
BY OTHERS
OSPE 0.0.10
19 MM(3/4" MIN)
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
COMPATIBLE SEALANT ANDCLOSED CELL BACKER ROD, BY OTHERS
DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT-TEXTURE OVERGRID TAPE™ (SEE NOTE 3)
WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD
DRYVIT ADHESIVE
APPROVED SUBSTRATE
INSULATION BOARDCLOSURE BLOCK
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT
BASE COAT
DRYVITAIR/WATER-RESISTIVE
BARRIER COATING
©
Dryvit Systems, Inc.
Issued: 10/2016
OSPE 0.0.11
Parapet - Steel Framed, Metal Coping
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
of any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOREINFORCING MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.
OUTSULATION® PE SYSTEM® NOTE:
1.
BY OTHERS
AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.
2.
version.
OUTSULATION PESYSTEM
64 MM (2 1/2") MIN.64 MM (2 1/2") MIN.
SEALANT WITH BONDBREAKER (TYP.),
BY OTHERS
INSULATION BOARDCLOSURE BLOCK
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
INSULATION BOARD
CONTINUOUS COPING,BY OTHERS
DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™(SEE NOTE 2)
APPROVED SUBSTRATE
WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION
COMPATIBLE SEALANT WITH BONDBREAKER (TYP.), BY OTHERS
DRYVIT ADHESIVE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
©
Dryvit Systems, Inc.
Issued: 10/2016
OSPE 0.0.12
professional. All systems must comply with local building codes and
of any project. The project design professional determines, in its sole
version.
Dryvit products is the responsibility of the project's design
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
The architecture, engineering and design of the project using the
BY OTHERS OUTSULATION PESYSTEM
Parapet - Solid Substrate, Metal Coping
1. NOTE:
OUTSULATION® PE SYSTEM®
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOREINFORCING MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.
2. AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.
3. DIMENSIONS GREATER THAN 600 MM(2'-0") REQUIRE SYSTEM CONFIGURATIONSIMILAR TO WALL FACE.
64 MM (2-1/2") MIN.
SOLID SUBSTRATE
INSULATION BOARDCLOSURE BLOCK
COMPATIBLE SEALANT WITHBOND BREAKER (TYP.),BY OTHERS
WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
ROOF ASSEMBLY
WRAP DRYVIT DETAILMESH 51 MM (2") MIN.
AT BACKSIDE OF INSULATION
ROOF FLASHING ANDCOUNTERFLASHING,
BY OTHERS
203 MM(8") MIN.
METAL CAP FLASHING, BY OTHERS
DRYVIT ADHESIVE
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
INSULATION BOARD
DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™(SEE NOTE 2)
(SEE NOTE 3) DRYVIT AQUAFLASHLAPPED OVER ROOF
FLASHING (SEE NOTE 2)
©
Dryvit Systems, Inc.
Issued: 10/2016
detail and for the architecture, design, engineering or workmanship of
professional. All systems must comply with local building codes and DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
OUTSULTION® PE SYSTEM® NOTE:
1.
OVERLAP 64 MM (2-1/2") MIN.
19 MM (3/4") MIN.
AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.
LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.
DRYVIT VENT ASSEMBLY IS INSTALLEDONLY AT PUNCHOUT IN DRYVIT VENTTRACK.
4.
2.
3.
The architecture, engineering and design of the project using the
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
Dryvit products is the responsibility of the project's design
version.
Soffit/Fascia Intersection
BY OTHERS OUTSULATION PESYSTEM
OSPE 0.0.13
19MM (3/4") MIN.
DRYVIT VENT ASSEMBLY™(SEE NOTE 4)
DRIP GROOVE
DRYVIT DETAIL MESH®EMBEDDED IN BASE COAT
DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT-TEXTUREOVER GRID TAPE
APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVEBARRIER COATING
INSULATION BOARD
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT VENT TRACK
DRYVIT FINISH
DRYVIT ADHESIVE
DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT-TEXTUREOVER GRID TAPE™ OVER VERTICALLEG OF DRYVIT VENT TRACK™(SEE NOTES 2 AND 3)
©
Dryvit Systems, Inc.
Issued: 10/2016
203 MM (8") MIN.SEE NOTES 2 AND 3
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship of
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
OUTSULATION® PE SYSTEM® NOTE:
1.
DO NOT LAP REINFORCING MESH WITHIN203 MM (8") OF A CORNER.
DOUBLE WRAP OUTSIDE AND INSIDECORNERS WITH REINFORCING MESH ORUSE CORNER MESH.
3.
2.
version.
Inside/Outside Corners
BY OTHERS
OSPE 0.0.14
AS AN OPTION, DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.
4.
DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT-TEXTUREOVER GRID TAPE (SEE NOTE 4)APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATINGINSULATION BOARDDRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COATDRYVIT FINISH
APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT-TEXTUREOVER GRID TAPE™ (SEE NOTE 4)INSULATION BOARDCLOSURE BLOCK
INSULATION BOARD
OUTSULATION PESYSTEM
203 MM (8") MIN.SEE NOTES 2 AND 3
DRYVIT ADHESIVE
DRYVIT ADHESIVE
©
Dryvit Systems, Inc.
Issued: 10/2016
DO NOT LAP REINFORCING MESH WITHIN203 MM (8") OF A CORNER.
OUTSULATION® PE SYSTEM®
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TODRYVIT REINFORCING MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
NOTE:1. 2.
203 MM (8") MIN
(SEE NOTE 2)
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
Outside Corner - High Impact
version.
BY OTHERS
OSPE 0.0.15
OUTSULATION PESYSTEM
DRYVIT BASE COAT
DRYVIT REINFORCING MESH OVERLAPMIN. OF 203 MM (8") AT CORNER
DRYVIT CORNER MESH
DRYVIT FINISH
DRYVIT ADHESIVE
DRYVIT BASE COAT
DRYVIT PANZER® 15 OR 20REINFORCING MESH
DRYVIT BASE COAT
INSULATION BOARDCLOSURE BLOCK
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
©
Dryvit Systems, Inc.
Issued: 10/2016
OSPE 0.0.16
Horizontal Expansion Joint
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO DRYVIT REINFORCING MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.DRYVIT VENT ASSEMBLY IS INSTALLEDONLY AT PUNCHOUT IN DRYVIT VENTTRACK.
OUTSULATION® PE SYSTEM®NOTE:
1.
2.
BY OTHERS
LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
Section A-A
5.
4.
3.
OUTSULATIONPE SYSTEM
version.
A A
LOCATION OFVENT ASSEMBLY
SEALANT AND BOND BREAKER AGAINSTDRYVIT AQUAFLASH SYSTEMAT VENT ASSEMBLY ONLY (SEE NOTE 4)
SEALANT MATERIAL,BY OTHERS
CLOSED CELL BACKERROD, BY OTHERS
DRYVIT AQUAFLASH SYSTEM(SEE NOTE 4)
INSULATION BOARD CLOSURE BLOCKWRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDE OF INSULATION
INSULATION BOARD
COMPATIBLE SEALANT WITH BONDBREAKER TAPE, BY OTHERS (SEE NOTE 5)
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT
DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT TRACK(SEE NOTE 3)
DRYVIT ADHESIVEDRYVIT AIR/WATER-RESISTIVE BARRIER COATINGAPPROVED SUBSTRATE
DRYVIT AQUAFLASH SYSTEM(SEE NOTE 4)
INSULATION BOARD
DRYVIT VENT TRACK™DRYVIT VENT ASSEMBLY™
DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT
SLOPE SURFACE TO DRAIN (MIN. 1:5)
DRYVIT FINISH
19 MM (3/4") MIN
19MM (3/4") MIN.
©
Dryvit Systems, Inc.
Issued: 10/2016
version.
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
NOTE:OUTSULATION® PE SYSTEM®
EXPANSION JOINT IN THE OUTSULATIONPE SYSTEM IS NECESSARY WHERE
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO DRYVITREINFORCING MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2.
1.
DRYVIT FLASHING TAPE SURFACE CONDITIONER™AND DRYVIT FLASHING TAPE™ MAY BE USED INLIEU OF DRYVIT AQUAFLASH SYSTEM.
LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.
LOCATE EXTERNAL SEALANT JOINT A MAXIMUMOF 51 MM (2") BELOW BREAK IN SUBSTRATE.SEALANT SHOULD NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVITFLASHING TAPE. COVER FLASHING TAPE LAPSWITH POLYETHYLENE TAPE OR BACKER ROD.
3.
6.
5.
4.
BY OTHERS
Section A-A
OUTSULATION PESYSTEM
Horizontal Slip Joint
SLIP TYPECONNECTION
A A
OSPE 0.0.17
LOCATION OF VENT ASSEMBLY
SEALANT AND BOND BREAKER AGAINSTDRYVIT AQUAFLASH SYSTEMAT VENT ASSEMBLY ONLY (SEE NOTE 6)
SEALANT MATERIAL, BY OTHERS
CLOSED CELL BACKERROD, BY OTHERS
INSULATION BOARD CLOSURE BLOCK
INSULATION BOARD
INSULATION BOARD
DRYVIT VENT ASSEMBLY™
DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT VENT TRACK™(SEE NOTE 5)
WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDE OF INSULATION
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
SLOPE SURFACE TO DRAIN (MIN. 1:5)
COMPATIBLE SEALANT WITH BOND BREAKERTAPE, BY OTHERS (SEE NOTE 4)
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COATDRYVIT FINISH
19 MM (3/4") MIN.
DRYVIT VENT TRACK
19 MM (3/4") MIN.
DRYVIT ADHESIVEDRYVIT AIR/WATER-RESISTIVE BARRIER COATINGAPPROVED SUBSTRATE
DRYVIT AQUAFLASH SYSTEM (SEE NOTE 6)
©
Dryvit Systems, Inc.
Issued: 10/2016
SIGNIFICANT DIFFERENTIAL MOVEMENTIS EXPECTED AT FLOOR LINES.
SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVEON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
19 MM (3/4") MIN.
OPTION
OUTSULATION® PE SYSTEM®
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
NOTE:1.
3.
A-A
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
Vertical Expansion Joint Options
version.
BY OTHERS
OUTSULATION PESYSTEM
OSPE 0.0.18
AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.
2.
REAR SEAL
VENT
REAR SEALFACE SEAL
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
INSULATION BOARDCLOSURE BLOCK
DRYVIT ADHESIVE
DRYVITAIR/WATER-RESISTIVE
BARRIER COATING
SOLID SUBSTRATE
COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)
WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT UNDERSIDE OF EPS
DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRIDTAPE™ OVER VERTICAL LEG OF DRYVITTRACK (SEE NOTE 2)
APPROVED SUBSTRATE
COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)
DRYVIT DEMANDIT OR COLOR PRIME
©
Dryvit Systems, Inc.
Issued: 10/2016
Structural Expansion Joints
OUTSULATION PESYSTEM
OSPE 0.0.19
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship of
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
version.
BY OTHERS
19 MM (3/4") MIN.
19 MM (3/4") MIN.
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
NOTE:1.
3. SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
2. AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ CAN BE USED.
OUTSULATION® PE SYSTEM®
OPTIONAL SECONDARYSEAL, BY OTHERSAPPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING
INSULATION BOARDCLOSURE BLOCK
WRAP DRYVIT DETAIL MESH51 MM (2") MIN. AT BACKSIDE OF INSULATION
OPTIONAL SECONDARYSEAL, BY OTHERS
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT DEMANDIT OR COLORPRIME ON SURFACES TO
RECEIVE SEALANT
DRYVIT AQUAFLASHSYSTEM (SEE NOTE 2)
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
INSULATION BOARDCLOSURE BLOCK
COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)
DRYVIT DEMANDIT® ORCOLOR PRIME™ ON SURFACES
TO RECEIVE SEALANT
WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDE
OF INSULATION
SOLID SUBSTRATE
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)
DRYVIT ADHESIVE
DRYVIT REINFORCING MESHEMBEDDED IN DRYVITBASE COAT
INSULATION BOARD
DRYVIT ADHESIVE
INSULATION BOARDDRYVIT FINISH
COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)
WRAP DRYVIT DETAIL MESH51 MM (2") MIN. AT BACKSIDE
OF INSULATION
©
Dryvit Systems, Inc.
Issued: 10/2016
19 MM (3/4") MIN.
version.
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
NOTE:DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
1. FOR LARGER PENETRATIONS REFER TODETAIL OSPE 0.0.21
2.
Minor Penetrations
102 MM (4") MAX.(SEE NOTE 2)
BY OTHERS OUTSULATION PESYSTEM
OSPE 0.0.20
19 MM (3/4") MIN.
OUTSULATION® PE SYSTEM®
AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ CAN BE USED.
3.
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 3)
COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS
OPTIONAL SECONDARY SEAL, BY OTHERS
INSULATION BOARD
WRAP DRYVIT DETAIL MESH® 51 MM(2") MIN. AT BACKSIDE OF INSULATION
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
DRYVIT ADHESIVE
©
Dryvit Systems, Inc.
Issued: 10/2016
TO MINIMIZE CRACKING AT CORNERS OFPENETRATIONS INSTALL DIAGONALREINFORCING MESH.
LOCATE INSULATION BOARDS SUCH THATBOARD EDGES DO NOT ALIGN WITHCORNERS OF PENETRATION.
OUTSULATION® PE SYSTEM®
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
NOTE:1.
3.
2.The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
without notice. Contact Dryvit to insure you have the most recent
version.
Major Penetrations
OSPE 0.0.21
EXTEND DETAIL MESH 152 MM (6") ONSILL & JAMB; HEAD & JAMB SIMILAR
241 MM X 305 MM(9-1/2" X 12") DETAILMESH® "BUTTERFLIES"
DRYVIT TRACK
INSULATION BOARD CLOSUREBLOCKS WRAPPED WITHDRYVIT DETAIL MESH®
INSULATION BOARD
WRAP DRYVIT DETAIL MESHTO BACKSIDE OF EPS MIN. 51 MM (2")
SPLICE PIECE OF DETAIL REINFORCINGMESH REQUIRED AT CORNER
©
Dryvit Systems, Inc.
Issued: 10/2016
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship of
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
OUTSULATION® PE SYSTEM® NOTE:
1.
OUTSULATIONPE SYSTEM
ENTIRE PERIMETER OF PIPE SLEEVE ISCAULKED TO PREVENT WATER ENTRYINTO WALL.
2.
BY OTHERS
version.
BY OTHERS
Sign Attachment
12.7 MM (1/2") MIN.
OSPE 0.0.22
INSULATION BOARDDRYVIT ADHESIVE
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
APPROVED SUBSTRATE
NON-CORROSIVE SLEEVE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
SIGN FIXTURE
COMPATIBLE SEALANT WITHBOND BREAKER TAPE, BY OTHERS(SEE NOTE 2)
SCREW/BOLT ATTACHMENTTO BUILDING FRAMING
BEARING WASHER
BLOCKING (SECURETO FRAMING)
©
Dryvit Systems, Inc.
Issued: 10/2016
Aesthetic Reveals
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
OUTSULATION® PE SYSTEM®
DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
NOTE:1. MIN. 51 MM (2") THICKNESS OF EPS IS
REQUIRED AT BASE OF REVEALS.2.
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
and Dryvit specifically disclaims any liability for the use of this
without notice. Contact Dryvit to insure you have the most recent
version.
64 MM (2 1/2")
BY OTHERS OUTSULATION PESYSTEM
51 MM (2") MIN.(SEE NOTE 2)
OSPE 0.0.23
SLOPE BOTTOM SURFACEFOR DRAINAGE (TYP.)
APPROVED SUBSTRATE
DRYVIT FINISHDRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
INSULATION BOARDDRYVIT DETAIL MESH®EMBEDDED IN DRYVIT BASE COAT
DRYVIT ADHESIVE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
©
Dryvit Systems, Inc.
Issued: 10/2016
BY OTHERS
does not violate Dryvit's warranty. This detail is subject to change
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
any project. The project design professional determines, in its sole
detail and for the architecture, design, engineering or workmanship of
standards. This detail is for general information and guidance only
professional. All systems must comply with local building codes and
Projecting Graphics
OSPE 0.0.24
OUTSULATIONPE SYSTEM
version.
without notice. Contact Dryvit to insure you have the most recent
and Dryvit specifically disclaims any liability for the use of this
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
OVERLAP 64 MM (2 1/2")
1.
2.
NOTE:
PERCENTAGE OF WALL AREA COVERED BY EPSFOAM SHAPES IN EXCESS OF 102 MM (4 IN) INTHICKNESS SHALL NOT EXCEED 15%.
MAXIMUM THICKNESS OF EPS BUILT OUT SHAPESSHALL NOT EXCEED 305 MM (12 INCHES) AT ANYPOINT MEASURED FROM THE SUBSTRATE.
OUTSULATION® PE SYSTEM®
SLOPE TOP SURFACE FORPOSITIVE DRAINAGE
DRYVIT FINISH
DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT
DRYVIT ADHESIVE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
INSULATION BOARD
DRYVIT FINISH
INSULATION BOARDDRYVIT ADHESIVE
DRYVIT DETAIL MESH®LAPPED 64 MM (2 1/2") MIN.ONTO ADJACENT EPS
EPS FOAM SHAPE (SEE NOTES 1 AND 2)DRYVIT ADHESIVE
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
©
Dryvit Systems, Inc.
Issued: 10/2016
SLOPE GRAPHIC FORPOSITIVE DRAINAGE
OUTSULATION® PE SYSTEM®
51 MM (2") MIN.
The architecture, engineering and design of the project using the
Dryvit products is the responsibility of the project's design
and Dryvit specifically disclaims any liability for the use of this
without notice. Contact Dryvit to insure you have the most recent
version.
OUTSULATION PESYSTEM
BY OTHERS
Recessed Graphics
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
detail and for the architecture, design, engineering or workmanship of
any project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent alternative
is best suited for the project. Use of a functionally equivalent detail
does not violate Dryvit's warranty. This detail is subject to change
OSPE 0.0.25
DRYVIT DETAIL MESH®LAPPED 64 MM (2 1/2") MIN.BENEATH DRYVIT REINFORCINGMESH EMBEDDED IN DRYVITBASE COAT
INSULATION BOARD
DRYVIT ADHESIVE
DRYVIT AIR/WATER RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
INSULATION BOARD
APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT FINISH
DRYVIT ADHESIVE
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
©
Dryvit Systems, Inc.
Issued: 10/2016
Dryvit Vent Assembly™
is best suited for the project. Use of a functionally equivalent detail
discretion, whether this detail or a functionally equivalent alternative
detail and for the architecture, design, engineering or workmanship of
professional. All systems must comply with local building codes and
OUTSULATION® PE SYSTEM®
OSPE 0.0.26
version.
without notice. Contact Dryvit to insure you have the most recent
does not violate Dryvit's warranty. This detail is subject to change
any project. The project design professional determines, in its sole
and Dryvit specifically disclaims any liability for the use of this
standards. This detail is for general information and guidance only
Dryvit products is the responsibility of the project's design
The architecture, engineering and design of the project using the
51 MM (2")
152 MM(6")
305 MM (12")
203 MM (8")
19 MM (3/4")
143 MM(5 5/8")
©
Dryvit Systems, Inc.
Issued: 10/2016