OUTSULATION® PE SYSTEM™

A Pressure – Equalized Rainscreen Exterior Insulation and Finish System With Moisture Drainage That Incorporates Continuous Insulation and An Air/Water-Resistive Barrier

Outsulation PE System Installation Details

DS846

OUTSULATION® PE SYSTEM®

- GROOVE PATTERN

DRYVIT SYSTEMS, INC. MAKES NO REPRESENTATIONREGARDING CONFORMITY OF ITS SUGGESTIONS TO MODELBUILDING CODES, ENGINEERING CRITERIA, SPECIFICAPPLICATIONS OR PROJECT LOCATIONS. ALL COMPONENTSINDICATED IN ILLUSTRATIONS, AS WELL AS OTHERS THATMAY BE REQUIRED FOR THE INTEGRITY OF THE SYSTEMSHALL BE DESIGNED, DETAILED AND ENGINEERED BYREPRESENTATIVES OF THE ARCHITECT, OWNER ORCONTRACTOR TO BE IN CONFORMANCE WITH MODEL CODES,ARCHITECTURAL AND ENGINEERING REQUIREMENTSPERTAINING TO SPECIFIC BUILDING PROJECTS.

DRYVIT SYSTEMS, INC. MAKES NO WARRANTY, EXPRESSEDOR IMPLIED, AS TO THE ARCHITECTURAL DESIGN,ENGINEERING, OR WORKMANSHIP OF PROJECTS UTILIZINGDRYVIT SYSTEMS OR PRODUCTS.

THE LIABILITIES OF DRYVIT SYSTEMS, INC. SHALL BE ASSTATED IN THE OUTSULATION PE LIMITED COMMERCIALWARRANTY. CONTACT DRYVIT SYSTEMS, INC. FOR A FULLAND COMPLETE COPY OF THE OUTSULATION PE WARRANTY.

TABLE OF CONTENTS

NOTE

OSPE 0.0.02

HEAD/SILL

DETAIL

OUTSULATION PE SYSTEM

INSULATION BOARD LAYOUT

INSULATION BOARD

FOUNDATION

PARAPET - STEEL FRAMED,

OUTSIDE CORNER- INSULATION BOARD LAYOUT

TERMINATION AT CONCRETE

PARAPET - SOLID SUBSTRATE,

INSIDE/OUTSIDE CORNERSOUTSIDE CORNER - HIGH IMPACT

METAL COPING

METAL COPING

BUILDING FACADE

JAMB

OSPE 0.0.14OSPE 0.0.13

OSPE 0.0.12

OSPE 0.0.11OSPE 0.0.10OSPE 0.0.09OSPE 0.0.08

OSPE 0.0.06

OSPE 0.0.05

OSPE 0.0.04OSPE 0.0.03

OSPE 0.0.01

OSPE 0.0.15

COMPARTMENT SEPARATION OSPE 0.0.07

SOFFIT/FASCIA INTERSECTION

VERTICAL EXPANSION JOINT OPTIONS

HORIZONTAL EXPANSION JOINT

MINOR PENETRATIONS

HORIZONTAL SLIP JOINT

MAJOR PENETRATIONS

AESTHETIC REVEALSPROJECTING GRAPHICSRECESSED GRAPHICSDRYVIT VENT ASSEMBLY™

SIGN ATTACHMENT

OSPE 0.0.16OSPE 0.0.17OSPE 0.0.18OSPE 0.0.19OSPE 0.0.20OSPE 0.0.21OSPE 0.0.22OSPE 0.0.23

STRUCTURAL EXPANSION JOINTS

OSPE 0.0.24

OSPE 0.0.26OSPE 0.0.25

The architecture, engineering and design of the project using

the Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building

codes and standards. This detail is for general information

and guidance only and Dryvit specifically disclaims any

liability for the use of this detail and for the architecture,

design, engineering or workmanship of any project. The

project design professional determines, in its sole discretion,

whether this detail or a functionally equivalent alternative is

best suited for the project. Use of a functionally equivalent

detail does not violate Dryvit's warranty. This detail is subject

to change without notice. Contact Dryvit to insure you have

the most recent version.

©

Dryvit Systems, Inc.

Issued: 10/2016

Outsulation PE System

NOTE:DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHDRYVIT PANZER® MESH PRIOR TODRYVIT REINFORCING MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

1.

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship of

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

version.

EIMASTANDARD

IMPACT

EIMAULTRA-HIGH

IMPACT

OUTSULATION® PE SYSTEM®

LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.

2.

OSPE 0.0.01

APPROVED SUBSTRATE

FRAMING

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

INSULATION BOARD

DRYVIT REINFORCING MESH

APPROVED SUBSTRATEFRAMING

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

EPS INSULATION BOARD

DRYVIT REINFORCING MESH

DRYVIT FINISHDRYVIT VENT ASSEMBLY

DRYVIT BASE COAT

PANZER® 15 OR 20 REINFORCINGMESH (SEE NOTE 1)

DRYVIT BASE COAT

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

DRYVIT VENT TRACK™

DRYVIT FINISH

DRYVIT VENT ASSEMBLY™

DRYVIT BASE COAT

DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT TEXTUREOVER GRID TAPE™(SEE NOTE 2)DRYVIT BASE COAT

DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT TEXTUREOVER GRID TAPE LAPPED OVERDRYVIT VENT TRACK(SEE NOTE 2)

DRYVIT BASE COAT

©

Dryvit Systems, Inc.

Issued: 10/2016

Building Facade

OSPE 0.0.02

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship of

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

version.

v

v

v

v

v

v

v

v

v

v

v

v

COMPARTMENT LOCATIONSDETERMINED PER ASCE 7-10 ANDDRYVIT OUTSULATION PE SYSTEMSPECIFICATIONS DS844.

NOTES:1.

OUTSULATION® PE SYSTEM®

DRYVIT VENT ASSEMBLY™

DRYVIT VENT TRACK™(DRAIN HOLE LOCATED ATVENT ASSEMBLY)DRYVIT TRACK (NO DRAINHOLES)

305 MM (12") DRYVITCLOSURE BLOCKS TYP.

152 MM (6") DRYVITSTARTER STRIP TYP.

152 MM (6") DRYVITCLOSURE BLOCKS TYP.

COMPARTMENTSEPARATION TYP.

©

Dryvit Systems, Inc.

Issued: 10/2016

OUTSULATION® PE SYSTEM®

OUTSULATION PESYSTEM

BY OTHERS

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

Insulation Board Layout

version.

OSPE 0.0.03

FRAMING, BY OTHERS

APPROVED SUBSTRATE,BY OTHERS

INSULATION BOARD

VERTICAL DRAINAGEGROOVES (ALIGNED)

HORIZONTAL BEVELEDGROOVES

DRYVIT STARTER STRIP

DRYVIT VENT ASSEMBLY™

DRYVIT VENT TRACK™

©

Dryvit Systems, Inc.

Issued: 10/2016

305 MM(1'-0")"

OUTSULATION® PE SYSTEM®

INSTALL SQUARE EDGED CORNERCLOSURE BLOCKS ON ALTERNATINGSIDES OF OUTSIDE CORNERS.

NOTES:1.

152 MM (0'-6")

610 MM (2'-0")

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

Outside Corner - Insulation Board

version.

OSPE 0.0.04

ALTERNATING SQUAREEDGED CORNER CLOSURE

BLOCKS (TYPICAL)

DRYVIT VENTASSEMBLY™

VERTICAL DRAINAGEGROOVES (ALIGNED)

DRYVIT STARTER STRIP

MITER JOINT BETWEEN STARTER STRIPS

©

Dryvit Systems, Inc.

Issued: 10/2016

45

Insulation Board- Groove Pattern

OSPE 0.0.05

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship of

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

version.

BEVELDETAIL

51 MM (2") MIN

12.7 MM (1/2")

OUTSULATION® PE SYSTEM®

1.2 M (4'-0")

305 MM (12")

ON CENTER

610 MM(2'-0")

6.4 MM X 25 MM (14" X 1")VERTICAL DRAINAGE GROOVE

BEVEL ALONG PERIMETEROF INSULATION BOARD

©

Dryvit Systems, Inc.

Issued: 10/2016

OUTSULATION® PE SYSTEM®

FILL DRYVIT VENT TRACK ATCLOSURE BLOCK LOCATION WITH APADHESIVE PRIOR TO SETTINGCLOSURE BLOCK, TO PROVIDECOMPARTMENT CLOSURE.

ADHERE CLOSURE BLOCKS ANDSTARTER STRIPS USING "RIBBON &DAB" ADHESIVE PATTERN TOPROVIDE COMPARTMENT CLOSURE.

2.

NOTES:1.

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

Compartment Separation

version.

OUTSULATION PESYSTEM

BY OTHERS

OSPE 0.0.06

LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.

3.

VERTICAL DRAINAGEGROOVES (ALIGNED)

INSULATION BOARD

DRYVIT VENT ASSEMBLY™

INSULATION BOARD CLOSURE BLOCK(SEE NOTE 1)

DRYVIT STARTER STRIP(SEE NOTE 1)

DRYVIT VENT TRACK™

DRYVIT AP ADHESIVE(SEE NOTE 2)

DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT TEXTURE OVER GRID TAPEOVER VERTICAL LEG OF DRYVIT VENTTRACK OR TRACK (SEE NOTE 3)

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

FRAMING

©

Dryvit Systems, Inc.

Issued: 10/2016

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

of any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.DRYVIT VENT ASSEMBLY IS INSTALLED ONLYAT PUNCHOUT IN DRYVIT VENT TRACK.

OUTSULATION® PE SYSTEM® NOTE:

2.

1.

LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.

EXPANSION JOINT IS REQUIRED ALONGTOP OF FOUNDATION IF 610 MM (2'-0')DIMENSION IS EXCEEDED.

4.

3.

version.

203 MM (8") MIN.

Foundation

BY OTHERS

OSPE 0.0.07

SLOPE GRADE AWAYFROM FOUNDATION WALL

OUTSULATION PESYSTEM

19 MM (3/4") MIN.APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT VENT TRACK(SEE NOTE 4)

INSULATION BOARD

DRYVIT VENT TRACK™

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COATDRYVIT FINISH

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT UNDERSIDEOF INSULATION

DRYVIT VENT ASSEMBLY™

DRYVIT ADHESIVE

DRYVIT AQUAFLASH SYSTEM OR DRYVITBACKSTOP NT-TEXTURE OVER GRID TAPE

©

Dryvit Systems, Inc.

Issued: 10/2016

OUTSULATION® PE SYSTEM®

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

NOTE:1. LIGHTLY SAND SURFACE OF TRACK

TO MAXIMIZE ADHESION.2.

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Termination At Concrete

BY OTHERS OUTSULATION PESYSTEM

OSPE 0.0.08

19 MM (3/4") MIN.

19 MM (3/4") MIN.

APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT VENT TRACK™

COMPATIBLE SEALANT ANDCLOSED CELL BACKER ROD,BY OTHERS

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COATDRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT VENT TRACK(SEE NOTE 2)

DRYVIT VENT ASSEMBLY™

WRAP DRYVIT DETAIL MESH® 51 MM(2") MIN. AT BACKSIDE OF INSULATION

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

DRYVIT ADHESIVEINSULATION BOARD

DRYVIT AQUAFLASH SYSTEM OR DRYVITBACKSTOP NT-TEXTURE OVER GRID TAPE

©

Dryvit Systems, Inc.

Issued: 10/2016

Head/Sill

SILL PAN FLASHING

LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.

SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship

of any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

SILL

1.

2. FOR CONTINUOUS WINDOWS, USE CLOSUREBLOCKS TO TERMINATE SYSTEM AT SILL.

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

NOTE:OUTSULATION® PE SYSTEM®

3.

4.

OSPE 0.0.09

HEAD

BY OTHERS OUSTULATION PESYSTEM

AS AN OPTION, DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF AQUAFLASH SYSTEM.

5.

64 MM(2-1/2") MIN.

12.7 MM(1/2")

19 MM (3/4") MIN.

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT VENT TRACK™

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT STARTER STRIP

DRYVIT FINISH

WRAP DRYVIT DETAIL MESH® 51 MM (2")MIN. AT BACKSIDE OF INSULATION BOARD

DRYVIT AQUAFLASH SYSTEM (SEE NOTE 5)

COMPATIBLE SEALANT WITHBOND BREAKER, BY OTHERS

INSULATION BOARD

INSULATION BOARD CLOSURE BLOCK

DRYVIT ADHESIVE

DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT VENT TRACK™(SEE NOTE 4)

DRYVIT AQUAFLASH SYSTEM OR DRYVITBACKSTOP NT-TEXTURE OVER GRID TAPE

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

CONTINUOUS FLASHING, BY OTHERS

CONTINUOUS FLASHING, BY OTHERS

COMPATIBLE SEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS (SEE NOTE 3)

©

Dryvit Systems, Inc.

Issued: 10/2016

OUTSULATION® PE SYSTEM®

1. NOTE:

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

version.

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship

of any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED INLIEU OF DRYVIT AQUAFLASH SYSTEM.

SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVEON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

3.

2.

Jamb

OUTSULATION PESYSTEM

BY OTHERS

OSPE 0.0.10

19 MM(3/4" MIN)

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

COMPATIBLE SEALANT ANDCLOSED CELL BACKER ROD, BY OTHERS

DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT-TEXTURE OVERGRID TAPE™ (SEE NOTE 3)

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD

DRYVIT ADHESIVE

APPROVED SUBSTRATE

INSULATION BOARDCLOSURE BLOCK

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT

BASE COAT

DRYVITAIR/WATER-RESISTIVE

BARRIER COATING

©

Dryvit Systems, Inc.

Issued: 10/2016

OSPE 0.0.11

Parapet - Steel Framed, Metal Coping

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

of any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOREINFORCING MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

OUTSULATION® PE SYSTEM® NOTE:

1.

BY OTHERS

AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.

2.

version.

OUTSULATION PESYSTEM

64 MM (2 1/2") MIN.64 MM (2 1/2") MIN.

SEALANT WITH BONDBREAKER (TYP.),

BY OTHERS

INSULATION BOARDCLOSURE BLOCK

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

INSULATION BOARD

CONTINUOUS COPING,BY OTHERS

DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™(SEE NOTE 2)

APPROVED SUBSTRATE

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION

COMPATIBLE SEALANT WITH BONDBREAKER (TYP.), BY OTHERS

DRYVIT ADHESIVE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

©

Dryvit Systems, Inc.

Issued: 10/2016

OSPE 0.0.12

professional. All systems must comply with local building codes and

of any project. The project design professional determines, in its sole

version.

Dryvit products is the responsibility of the project's design

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

The architecture, engineering and design of the project using the

BY OTHERS OUTSULATION PESYSTEM

Parapet - Solid Substrate, Metal Coping

1. NOTE:

OUTSULATION® PE SYSTEM®

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOREINFORCING MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.

3. DIMENSIONS GREATER THAN 600 MM(2'-0") REQUIRE SYSTEM CONFIGURATIONSIMILAR TO WALL FACE.

64 MM (2-1/2") MIN.

SOLID SUBSTRATE

INSULATION BOARDCLOSURE BLOCK

COMPATIBLE SEALANT WITHBOND BREAKER (TYP.),BY OTHERS

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

ROOF ASSEMBLY

WRAP DRYVIT DETAILMESH 51 MM (2") MIN.

AT BACKSIDE OF INSULATION

ROOF FLASHING ANDCOUNTERFLASHING,

BY OTHERS

203 MM(8") MIN.

METAL CAP FLASHING, BY OTHERS

DRYVIT ADHESIVE

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

INSULATION BOARD

DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™(SEE NOTE 2)

(SEE NOTE 3) DRYVIT AQUAFLASHLAPPED OVER ROOF

FLASHING (SEE NOTE 2)

©

Dryvit Systems, Inc.

Issued: 10/2016

detail and for the architecture, design, engineering or workmanship of

professional. All systems must comply with local building codes and DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

OUTSULTION® PE SYSTEM® NOTE:

1.

OVERLAP 64 MM (2-1/2") MIN.

19 MM (3/4") MIN.

AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.

LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.

DRYVIT VENT ASSEMBLY IS INSTALLEDONLY AT PUNCHOUT IN DRYVIT VENTTRACK.

4.

2.

3.

The architecture, engineering and design of the project using the

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

Dryvit products is the responsibility of the project's design

version.

Soffit/Fascia Intersection

BY OTHERS OUTSULATION PESYSTEM

OSPE 0.0.13

19MM (3/4") MIN.

DRYVIT VENT ASSEMBLY™(SEE NOTE 4)

DRIP GROOVE

DRYVIT DETAIL MESH®EMBEDDED IN BASE COAT

DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT-TEXTUREOVER GRID TAPE

APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVEBARRIER COATING

INSULATION BOARD

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT VENT TRACK

DRYVIT FINISH

DRYVIT ADHESIVE

DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT-TEXTUREOVER GRID TAPE™ OVER VERTICALLEG OF DRYVIT VENT TRACK™(SEE NOTES 2 AND 3)

©

Dryvit Systems, Inc.

Issued: 10/2016

203 MM (8") MIN.SEE NOTES 2 AND 3

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship of

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

OUTSULATION® PE SYSTEM® NOTE:

1.

DO NOT LAP REINFORCING MESH WITHIN203 MM (8") OF A CORNER.

DOUBLE WRAP OUTSIDE AND INSIDECORNERS WITH REINFORCING MESH ORUSE CORNER MESH.

3.

2.

version.

Inside/Outside Corners

BY OTHERS

OSPE 0.0.14

AS AN OPTION, DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.

4.

DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT-TEXTUREOVER GRID TAPE (SEE NOTE 4)APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATINGINSULATION BOARDDRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COATDRYVIT FINISH

APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT-TEXTUREOVER GRID TAPE™ (SEE NOTE 4)INSULATION BOARDCLOSURE BLOCK

INSULATION BOARD

OUTSULATION PESYSTEM

203 MM (8") MIN.SEE NOTES 2 AND 3

DRYVIT ADHESIVE

DRYVIT ADHESIVE

©

Dryvit Systems, Inc.

Issued: 10/2016

DO NOT LAP REINFORCING MESH WITHIN203 MM (8") OF A CORNER.

OUTSULATION® PE SYSTEM®

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TODRYVIT REINFORCING MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

NOTE:1. 2.

203 MM (8") MIN

(SEE NOTE 2)

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

Outside Corner - High Impact

version.

BY OTHERS

OSPE 0.0.15

OUTSULATION PESYSTEM

DRYVIT BASE COAT

DRYVIT REINFORCING MESH OVERLAPMIN. OF 203 MM (8") AT CORNER

DRYVIT CORNER MESH

DRYVIT FINISH

DRYVIT ADHESIVE

DRYVIT BASE COAT

DRYVIT PANZER® 15 OR 20REINFORCING MESH

DRYVIT BASE COAT

INSULATION BOARDCLOSURE BLOCK

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

©

Dryvit Systems, Inc.

Issued: 10/2016

OSPE 0.0.16

Horizontal Expansion Joint

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO DRYVIT REINFORCING MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.DRYVIT VENT ASSEMBLY IS INSTALLEDONLY AT PUNCHOUT IN DRYVIT VENTTRACK.

OUTSULATION® PE SYSTEM®NOTE:

1.

2.

BY OTHERS

LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

Section A-A

5.

4.

3.

OUTSULATIONPE SYSTEM

version.

A A

LOCATION OFVENT ASSEMBLY

SEALANT AND BOND BREAKER AGAINSTDRYVIT AQUAFLASH SYSTEMAT VENT ASSEMBLY ONLY (SEE NOTE 4)

SEALANT MATERIAL,BY OTHERS

CLOSED CELL BACKERROD, BY OTHERS

DRYVIT AQUAFLASH SYSTEM(SEE NOTE 4)

INSULATION BOARD CLOSURE BLOCKWRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDE OF INSULATION

INSULATION BOARD

COMPATIBLE SEALANT WITH BONDBREAKER TAPE, BY OTHERS (SEE NOTE 5)

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT TRACK(SEE NOTE 3)

DRYVIT ADHESIVEDRYVIT AIR/WATER-RESISTIVE BARRIER COATINGAPPROVED SUBSTRATE

DRYVIT AQUAFLASH SYSTEM(SEE NOTE 4)

INSULATION BOARD

DRYVIT VENT TRACK™DRYVIT VENT ASSEMBLY™

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT

SLOPE SURFACE TO DRAIN (MIN. 1:5)

DRYVIT FINISH

19 MM (3/4") MIN

19MM (3/4") MIN.

©

Dryvit Systems, Inc.

Issued: 10/2016

version.

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

NOTE:OUTSULATION® PE SYSTEM®

EXPANSION JOINT IN THE OUTSULATIONPE SYSTEM IS NECESSARY WHERE

DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO DRYVITREINFORCING MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2.

1.

DRYVIT FLASHING TAPE SURFACE CONDITIONER™AND DRYVIT FLASHING TAPE™ MAY BE USED INLIEU OF DRYVIT AQUAFLASH SYSTEM.

LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.

LOCATE EXTERNAL SEALANT JOINT A MAXIMUMOF 51 MM (2") BELOW BREAK IN SUBSTRATE.SEALANT SHOULD NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVITFLASHING TAPE. COVER FLASHING TAPE LAPSWITH POLYETHYLENE TAPE OR BACKER ROD.

3.

6.

5.

4.

BY OTHERS

Section A-A

OUTSULATION PESYSTEM

Horizontal Slip Joint

SLIP TYPECONNECTION

A A

OSPE 0.0.17

LOCATION OF VENT ASSEMBLY

SEALANT AND BOND BREAKER AGAINSTDRYVIT AQUAFLASH SYSTEMAT VENT ASSEMBLY ONLY (SEE NOTE 6)

SEALANT MATERIAL, BY OTHERS

CLOSED CELL BACKERROD, BY OTHERS

INSULATION BOARD CLOSURE BLOCK

INSULATION BOARD

INSULATION BOARD

DRYVIT VENT ASSEMBLY™

DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT VENT TRACK™(SEE NOTE 5)

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDE OF INSULATION

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

SLOPE SURFACE TO DRAIN (MIN. 1:5)

COMPATIBLE SEALANT WITH BOND BREAKERTAPE, BY OTHERS (SEE NOTE 4)

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COATDRYVIT FINISH

19 MM (3/4") MIN.

DRYVIT VENT TRACK

19 MM (3/4") MIN.

DRYVIT ADHESIVEDRYVIT AIR/WATER-RESISTIVE BARRIER COATINGAPPROVED SUBSTRATE

DRYVIT AQUAFLASH SYSTEM (SEE NOTE 6)

©

Dryvit Systems, Inc.

Issued: 10/2016

SIGNIFICANT DIFFERENTIAL MOVEMENTIS EXPECTED AT FLOOR LINES.

SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVEON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

19 MM (3/4") MIN.

OPTION

OUTSULATION® PE SYSTEM®

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

NOTE:1.

3.

A-A

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

Vertical Expansion Joint Options

version.

BY OTHERS

OUTSULATION PESYSTEM

OSPE 0.0.18

AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.

2.

REAR SEAL

VENT

REAR SEALFACE SEAL

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

INSULATION BOARDCLOSURE BLOCK

DRYVIT ADHESIVE

DRYVITAIR/WATER-RESISTIVE

BARRIER COATING

SOLID SUBSTRATE

COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT UNDERSIDE OF EPS

DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRIDTAPE™ OVER VERTICAL LEG OF DRYVITTRACK (SEE NOTE 2)

APPROVED SUBSTRATE

COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)

DRYVIT DEMANDIT OR COLOR PRIME

©

Dryvit Systems, Inc.

Issued: 10/2016

AutoCAD SHX Text
A
AutoCAD SHX Text
A

Structural Expansion Joints

OUTSULATION PESYSTEM

OSPE 0.0.19

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship of

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

version.

BY OTHERS

19 MM (3/4") MIN.

19 MM (3/4") MIN.

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

NOTE:1.

3. SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

2. AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ CAN BE USED.

OUTSULATION® PE SYSTEM®

OPTIONAL SECONDARYSEAL, BY OTHERSAPPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

INSULATION BOARDCLOSURE BLOCK

WRAP DRYVIT DETAIL MESH51 MM (2") MIN. AT BACKSIDE OF INSULATION

OPTIONAL SECONDARYSEAL, BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT DEMANDIT OR COLORPRIME ON SURFACES TO

RECEIVE SEALANT

DRYVIT AQUAFLASHSYSTEM (SEE NOTE 2)

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

INSULATION BOARDCLOSURE BLOCK

COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)

DRYVIT DEMANDIT® ORCOLOR PRIME™ ON SURFACES

TO RECEIVE SEALANT

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDE

OF INSULATION

SOLID SUBSTRATE

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

DRYVIT ADHESIVE

DRYVIT REINFORCING MESHEMBEDDED IN DRYVITBASE COAT

INSULATION BOARD

DRYVIT ADHESIVE

INSULATION BOARDDRYVIT FINISH

COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)

WRAP DRYVIT DETAIL MESH51 MM (2") MIN. AT BACKSIDE

OF INSULATION

©

Dryvit Systems, Inc.

Issued: 10/2016

19 MM (3/4") MIN.

version.

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

NOTE:DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

1. FOR LARGER PENETRATIONS REFER TODETAIL OSPE 0.0.21

2.

Minor Penetrations

102 MM (4") MAX.(SEE NOTE 2)

BY OTHERS OUTSULATION PESYSTEM

OSPE 0.0.20

19 MM (3/4") MIN.

OUTSULATION® PE SYSTEM®

AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ CAN BE USED.

3.

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 3)

COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS

OPTIONAL SECONDARY SEAL, BY OTHERS

INSULATION BOARD

WRAP DRYVIT DETAIL MESH® 51 MM(2") MIN. AT BACKSIDE OF INSULATION

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE

©

Dryvit Systems, Inc.

Issued: 10/2016

TO MINIMIZE CRACKING AT CORNERS OFPENETRATIONS INSTALL DIAGONALREINFORCING MESH.

LOCATE INSULATION BOARDS SUCH THATBOARD EDGES DO NOT ALIGN WITHCORNERS OF PENETRATION.

OUTSULATION® PE SYSTEM®

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

NOTE:1.

3.

2.The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

without notice. Contact Dryvit to insure you have the most recent

version.

Major Penetrations

OSPE 0.0.21

EXTEND DETAIL MESH 152 MM (6") ONSILL & JAMB; HEAD & JAMB SIMILAR

241 MM X 305 MM(9-1/2" X 12") DETAILMESH® "BUTTERFLIES"

DRYVIT TRACK

INSULATION BOARD CLOSUREBLOCKS WRAPPED WITHDRYVIT DETAIL MESH®

INSULATION BOARD

WRAP DRYVIT DETAIL MESHTO BACKSIDE OF EPS MIN. 51 MM (2")

SPLICE PIECE OF DETAIL REINFORCINGMESH REQUIRED AT CORNER

©

Dryvit Systems, Inc.

Issued: 10/2016

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship of

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

OUTSULATION® PE SYSTEM® NOTE:

1.

OUTSULATIONPE SYSTEM

ENTIRE PERIMETER OF PIPE SLEEVE ISCAULKED TO PREVENT WATER ENTRYINTO WALL.

2.

BY OTHERS

version.

BY OTHERS

Sign Attachment

12.7 MM (1/2") MIN.

OSPE 0.0.22

INSULATION BOARDDRYVIT ADHESIVE

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

APPROVED SUBSTRATE

NON-CORROSIVE SLEEVE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

SIGN FIXTURE

COMPATIBLE SEALANT WITHBOND BREAKER TAPE, BY OTHERS(SEE NOTE 2)

SCREW/BOLT ATTACHMENTTO BUILDING FRAMING

BEARING WASHER

BLOCKING (SECURETO FRAMING)

©

Dryvit Systems, Inc.

Issued: 10/2016

Aesthetic Reveals

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

OUTSULATION® PE SYSTEM®

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

NOTE:1. MIN. 51 MM (2") THICKNESS OF EPS IS

REQUIRED AT BASE OF REVEALS.2.

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

and Dryvit specifically disclaims any liability for the use of this

without notice. Contact Dryvit to insure you have the most recent

version.

64 MM (2 1/2")

BY OTHERS OUTSULATION PESYSTEM

51 MM (2") MIN.(SEE NOTE 2)

OSPE 0.0.23

SLOPE BOTTOM SURFACEFOR DRAINAGE (TYP.)

APPROVED SUBSTRATE

DRYVIT FINISHDRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

INSULATION BOARDDRYVIT DETAIL MESH®EMBEDDED IN DRYVIT BASE COAT

DRYVIT ADHESIVE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

©

Dryvit Systems, Inc.

Issued: 10/2016

BY OTHERS

does not violate Dryvit's warranty. This detail is subject to change

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

any project. The project design professional determines, in its sole

detail and for the architecture, design, engineering or workmanship of

standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and

Projecting Graphics

OSPE 0.0.24

OUTSULATIONPE SYSTEM

version.

without notice. Contact Dryvit to insure you have the most recent

and Dryvit specifically disclaims any liability for the use of this

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

OVERLAP 64 MM (2 1/2")

1.

2.

NOTE:

PERCENTAGE OF WALL AREA COVERED BY EPSFOAM SHAPES IN EXCESS OF 102 MM (4 IN) INTHICKNESS SHALL NOT EXCEED 15%.

MAXIMUM THICKNESS OF EPS BUILT OUT SHAPESSHALL NOT EXCEED 305 MM (12 INCHES) AT ANYPOINT MEASURED FROM THE SUBSTRATE.

OUTSULATION® PE SYSTEM®

SLOPE TOP SURFACE FORPOSITIVE DRAINAGE

DRYVIT FINISH

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

DRYVIT ADHESIVE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

INSULATION BOARD

DRYVIT FINISH

INSULATION BOARDDRYVIT ADHESIVE

DRYVIT DETAIL MESH®LAPPED 64 MM (2 1/2") MIN.ONTO ADJACENT EPS

EPS FOAM SHAPE (SEE NOTES 1 AND 2)DRYVIT ADHESIVE

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

©

Dryvit Systems, Inc.

Issued: 10/2016

SLOPE GRAPHIC FORPOSITIVE DRAINAGE

OUTSULATION® PE SYSTEM®

51 MM (2") MIN.

The architecture, engineering and design of the project using the

Dryvit products is the responsibility of the project's design

and Dryvit specifically disclaims any liability for the use of this

without notice. Contact Dryvit to insure you have the most recent

version.

OUTSULATION PESYSTEM

BY OTHERS

Recessed Graphics

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

detail and for the architecture, design, engineering or workmanship of

any project. The project design professional determines, in its sole

discretion, whether this detail or a functionally equivalent alternative

is best suited for the project. Use of a functionally equivalent detail

does not violate Dryvit's warranty. This detail is subject to change

OSPE 0.0.25

DRYVIT DETAIL MESH®LAPPED 64 MM (2 1/2") MIN.BENEATH DRYVIT REINFORCINGMESH EMBEDDED IN DRYVITBASE COAT

INSULATION BOARD

DRYVIT ADHESIVE

DRYVIT AIR/WATER RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

INSULATION BOARD

APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVE

BARRIER COATING

DRYVIT FINISH

DRYVIT ADHESIVE

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

©

Dryvit Systems, Inc.

Issued: 10/2016

Dryvit Vent Assembly™

is best suited for the project. Use of a functionally equivalent detail

discretion, whether this detail or a functionally equivalent alternative

detail and for the architecture, design, engineering or workmanship of

professional. All systems must comply with local building codes and

OUTSULATION® PE SYSTEM®

OSPE 0.0.26

version.

without notice. Contact Dryvit to insure you have the most recent

does not violate Dryvit's warranty. This detail is subject to change

any project. The project design professional determines, in its sole

and Dryvit specifically disclaims any liability for the use of this

standards. This detail is for general information and guidance only

Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

51 MM (2")

152 MM(6")

305 MM (12")

203 MM (8")

19 MM (3/4")

143 MM(5 5/8")

©

Dryvit Systems, Inc.

Issued: 10/2016