OUTSULATION® SMD SYSTEM™

(Formerly SPRINT® MD SYSTEM®)

An Exterior Wall Insulation and Finish System With Moisture Drainage

Outsulation SMD System Installation Details

(Formerly Sprint MD System)

DS163

Page 2: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

MINOR PENETRATIONS OSMD 0.0.28

4RS

REV:APPROVED BY:

02/09

DATE:

Outsulation SMD System

of any project. The project design professional determines, in its sole

version.

®

is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

The architecture, engineering and design of the project using the

standards. This detail is for general information and guidance only

this detail and for the architecture, design, engineering or workmanship and Dryvit specifically disclaims any liability for the use of

professional. All systems must comply with local building codes and Dryvit products is the responsibility of the project's design

OSMD 0.0.34GABLE END WITH WOOD TRIM

OSMD 0.0.37CHIMNEY ENCLOSUREOSMD 0.0.36OSMD 0.0.35TERMINATION AT PARAPET

TERMINATION AT ROOF-TO-WALL FLASHING

SOFFIT TERMINATION OSMD 0.0.31OSMD 0.0.32OSMD 0.0.33

SOFFIT WITH FRIEZE BOARDGABLE END WITH EIFS TRIM

OSMD 0.0.30OSMD 0.0.29WOOD FRAMED DECK - CROSS SECTION

WOOD FRAMED DECK - CUT AWAY

OSMD 0.0.05FASTENING

ARCHED WINDOW HEAD OSMD 0.0.16

OSMD 0.0.22DOOR HEAD WITH INTEGRAL FLASHING

OSMD 0.0.25SYSTEM CONFIGURATION AT OPENINGSOSMD 0.0.26OSMD 0.0.27

SHUTTER AND DOWN SPOUT ATTACHMENTAESTHETIC REVEALS

OSMD 0.0.23OSMD 0.0.24

DOOR HEAD WITH BRICK MOLDINSIDE / OUTSIDE CORNERS

OSMD 0.0.19WINDOW SILL

OSMD 0.0.21OSMD 0.0.20DOOR JAMB WITH INTEGRAL FLASHING

DOOR JAMB WITH BRICK MOLD

OSMD 0.0.17OSMD 0.0.18

WINDOW HEADWINDOW JAMB

OSMD 0.0.11SEALANT CONFIGURATION OPTIONS

OPENING PREP - OSMD 0.0.14

OSMD 0.0.15BACKSTOP® NT WRB/ GRID TAPE™ OPTIONWINDOW ELEVATION

OSMD 0.0.13OSMD 0.0.12

OPENING PREP - BACKSTOP® NT WRB/ AQUAFLASH® SYSTEM OPTION

OPENING PREP - SHEET TYPE WRB

OSMD 0.0.08TERMINATION ABOVE GRADE

OSMD 0.0.10OSMD 0.0.09

VERTICAL EXPANSION JOINTSEXPANSION JOINT AT FLOOR LINE

OSMD 0.0.06OSMD 0.0.07FASTENING PATTERN - OUTSIDE CORNER

FASTENING PATTERN

OSMD 0.0.02DRYVIT DRAINAGE MAT™ OPTION

OSMD 0.0.04OSMD 0.0.03

OUTSIDE CORNER - HIGH IMPACTDUPONT™ TYVEK® STUCCOWRAP® OPTION

OSMD 0.0.01OUTSULATION SMD SYSTEM

TABLE OF CONTENTS

® ™

Page 3: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

RS 02/094

DATE:REV:APPROVED BY:

Outsulation SMD System

this detail and for the architecture, design, engineering or workmanship

without notice. Contact Dryvit to insure you have the most recent

®

version.

of any project. The project design professional determines, in its sole

is best suited for the project. Use of a functionally equivalent detail does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

The architecture, engineering and design of the project using the

professional. All systems must comply with local building codes and

and Dryvit specifically disclaims any liability for the use ofstandards. This detail is for general information and guidance only

Dryvit products is the responsibility of the project's design

Outsulation SMD System

WOOD OR STEEL FRAMING

DRYVIT REINFORCING MESH

WRAP DRYVIT DETAILMESH® 51 MM (2") MIN.AT BACKSIDE OF INSULATION BOARD

Drainage TrackOption

DRYVIT FINISHDRAINAGE STRIP

DRYVIT GENESIS, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

APPROVED OSMD SYSTEM INSULATION BOARD

DRYVIT MD SPACERCODE APPROVED WATER-RESISTIVE BARRIER

SUBSTRATE

OSMD 0.0.01

® ™

Page 4: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

4 02/09RS

REV: DATE:APPROVED BY:

Outsulation SMD System

this detail and for the architecture, design, engineering or workmanship

version.

discretion, whether this detail or a functionally equivalent alternative

does not violate Dryvit's warranty. This detail is subject to change

of any project. The project design professional determines, in its sole

is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent

®

Dryvit products is the responsibility of the project's design

and Dryvit specifically disclaims any liability for the use of

The architecture, engineering and design of the project using the

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

Dryvit Drainage Mat™ Option

WOOD OR STEEL FRAMING

DRYVIT REINFORCING MESH

Drainage TrackOption

WRAP DRYVIT DETAILMESH® 51 MM (2") MIN.AT BACKSIDE OF INSULATION BOARD

DRYVIT GENESIS, GENESIS DMOR GENESIS DMS BASE COATDRYVIT FINISH

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

APPROVED OSMD SYSTEM INSULATION BOARD

DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

CODE APPROVED WATER-RESISTIVE BARRIER

DRYVIT DRAINAGE MAT

SUBSTRATE

OSMD 0.0.02

® ™

Page 5: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

REV:

RS

APPROVED BY:

02/09

DATE:

5

Outsulation SMD System

version.

®

is best suited for the project. Use of a functionally equivalent detail does not violate Dryvit's warranty. This detail is subject to change without notice. Contact Dryvit to insure you have the most recent

discretion, whether this detail or a functionally equivalent alternative of any project. The project design professional determines, in its sole

2.1. DRYVIT DRAINAGE STRIP IS REQUIRED WHENUSING STUCCOWRAP WITHOUT A DRAINAGETRACK.

THE SELECTION OF A SPECIFICWATER-RESISTIVE BARRIER IS THERESPONSIBILITY OF THE SPECIFIER AND ISOUTSIDE THE SCOPE OF THIS DOCUMENT.

The architecture, engineering and design of the project using the

standards. This detail is for general information and guidance only and Dryvit specifically disclaims any liability for the use of

this detail and for the architecture, design, engineering or workmanship

Dryvit products is the responsibility of the project's design professional. All systems must comply with local building codes and

NOTE:

Dupont Tyvek StuccoWrap Option

SUBSTRATE

DRYVIT FINISH

Drainage TrackOption

DRYVIT DRAINAGE STRIP(SEE NOTE 2)

WRAP DRYVIT DETAIL MESH® 51 MM (2") MIN.AT BACKSIDE OF INSULATION BOARD

APPROVED OSMD SYSTEM INSULATION BOARD

DRYVIT REINFORCING MESHDRYVIT GENESIS, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

DUPONT TYVEK STUCCOWRAP(REFER TO NOTES 1,2)

WOOD OR STEEL FRAMING

OSMD 0.0.03

® ™ ® ®

Page 6: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

02/09RS 4

DATE:APPROVED BY: REV:

Outsulation SMD SystemDRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

1.NOTE:

of any project. The project design professional determines, in its sole

version.

®

without notice. Contact Dryvit to insure you have the most recent

is best suited for the project. Use of a functionally equivalent detail does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATION OPTIONS.

2. The architecture, engineering and design of the project using the

this detail and for the architecture, design, engineering or workmanship

standards. This detail is for general information and guidance only professional. All systems must comply with local building codes and

and Dryvit specifically disclaims any liability for the use of

Dryvit products is the responsibility of the project's design

Outside Corner- High Impact

203 MM (8") MIN.

DRYVIT MD SPACER

APPROVED OSMD SYSTEMINSULATION BOARD

DRYVIT STANDARD OR STANDARDPLUS REINFORCING MESH OVERLAPMIN. 203 MM (8") AT CORNER

DRYVIT FINISH

DRYVIT GENESIS, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT GENESIS, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT CORNER MESH

DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT INTERMEDIATE MESH

CODE APPROVEDWATER-RESISTIVE BARRIER

SUBSTRATE

OSMD 0.0.04

® ™

Page 7: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

19 MM (3/4") MIN.

4RS 02/09

REV:APPROVED BY: DATE:

Outsulation SMD System

of any project. The project design professional determines, in its sole

version.

discretion, whether this detail or a functionally equivalent alternative

does not violate Dryvit's warranty. This detail is subject to change is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent

®

Dryvit products is the responsibility of the project's design

and Dryvit specifically disclaims any liability for the use of

The architecture, engineering and design of the project using the

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

this detail and for the architecture, design, engineering or workmanship

1. FOR NON-NAILABLE SHEATHINGSUBSTRATES, THE FASTENER MUST BEINSTALLED INTO THE FRAMING.

NOTE:

Fastening

APPROVED WASHERSUBSTRATE

25 MM (1") MIN.

MINIMUM 4.8 MM (3/16") DIAMETERCORROSION RESISTANT MASONRY SCREWAPPROVED OSMD SYSTEM INSULATIONBOARD

CONCRETE

MINIMUM NO. 6 CORROSIONRESISTANT SCREW

MINIMUM 12 GAUGE (8d) CORROSIONRESISTANT RING SHANK NAIL

NAILABLESUBSTRATE APPROVED OSMD SYSTEM INSULATION

BOARDMINIMUM NO. 6 CORROSIONRESISTANT SCREWNAILABLE SUBSTRATE

25 MM (1") MIN.

APPROVED WASHER

GYPSUM SHEATHING OR OTHERNON- NAILABLE SUBSTRATE

9.5 MM (3/8") MIN.

APPROVED WASHERMINIMUM NO. 6 SELF DRILLINGCORROSION RESISTANT SCREWAPPROVED OSMD SYSTEM INSULATIONBOARD

NON-NAILABLESUBSTRATESTEEL FRAMING

APPROVED WASHER19 MM (3/4") MIN.

25 MM (1") MIN.

GYPSUM SHEATHING OR OTHERNON- NAILABLE SUBSTRATEAPPROVED WASHERMINIMUM 12 GAUGE (8d) CORROSIONRESISTANT RING SHANK NAILAPPROVED OSMD SYSTEM INSULATIONBOARD

NON-NAILABLESUBSTRATEWOOD FRAMING

OSMD 0.0.05

® ™

Page 8: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

DRAINAGE TRACK25 MM. (1") TYP.

APPROVED BY:

RS

REV:

4

DATE:

02/09

Outsulation SMD System Fastening Pattern

of any project. The project design professional determines, in its sole

version.

®

does not violate Dryvit's warranty. This detail is subject to change without notice. Contact Dryvit to insure you have the most recent

is best suited for the project. Use of a functionally equivalent detail discretion, whether this detail or a functionally equivalent alternative

1. REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATIONOPTIONS.

Dryvit products is the responsibility of the project's design

standards. This detail is for general information and guidance only

this detail and for the architecture, design, engineering or workmanship and Dryvit specifically disclaims any liability for the use of

professional. All systems must comply with local building codes and

NOTE:The architecture, engineering and design of the project using the

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

VERTICAL INSULATION BOARDJOINT ALIGNED WITHDRYVIT MD SPACER

DRYVIT MD SPACER 3.2 MM X 76 MM (1/8" X 3")SPACED DIRECTLY BEHIND LINE OF FASTENERS

305 MM. (12")TYP. PERIMETER

DRYVIT REINFORCING MESH

APPROVED OSMD SYSTEM INSULATION BOARD

SUBSTRATE

305 MM. (12")O.C. TYP.

WOOD OR STEEL FRAMING

CODE APPROVED WATER-RESISTIVE BARRIER

406 MM. (16")O.C. TYP.

OSMD 0.0.06

® ™

Page 9: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

OFFSET INSULATION BOARDEDGES AT CORNERS

Outsulation SMD SystemDRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

1.NOTE:

REV:

4RS

APPROVED BY: DATE:

02/09

Fastening Pattern - Outside Corner

of any project. The project design professional determines, in its sole

version.

®

discretion, whether this detail or a functionally equivalent alternative

does not violate Dryvit's warranty. This detail is subject to change is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent

2. CORNER MESH MAY BE USED IN ADDITION TODRYVIT REINFORCING MESH.

Dryvit products is the responsibility of the project's design

and Dryvit specifically disclaims any liability for the use of

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

this detail and for the architecture, design, engineering or workmanship 3. REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND

0.0.03 FOR SYSTEM CONFIGURATION OPTIONS.

The architecture, engineering and design of the project using the

DRYVIT REINFORCING MESHOUTSIDE CORNER (SEE NOTE 2)

WOOD OR STEEL FRAMING

406 MM(16") TYP.

OFFSET VERTICAL JOINTS

25 MM (1") FROM BOARD EDGE (TYP.)

APPROVED OSMD SYSTEM INSULATION BOARD

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

305 MM(12") TYP.

DRYVIT MD SPACER PLACEDDIRECTLY BEHIND ROW OF FASTENERS

OSMD 0.0.07

® ™

Page 10: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

REV:APPROVED BY: DATE:

4RS 02/09

Outsulation SMD System Termination Above Grade

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

of any project. The project design professional determines, in its sole

version.

®

does not violate Dryvit's warranty. This detail is subject to change without notice. Contact Dryvit to insure you have the most recent

discretion, whether this detail or a functionally equivalent alternative is best suited for the project. Use of a functionally equivalent detail

FLOOR LINE EXPANSION JOINT IS REQUIRED IF610 MM (24") DIMENSION IS EXCEEDED.

2.1.

3. REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATION OPTIONS.

NOTE:Dryvit products is the responsibility of the project's design

standards. This detail is for general information and guidance only

this detail and for the architecture, design, engineering or workmanship and Dryvit specifically disclaims any liability for the use of

professional. All systems must comply with local building codes and

The architecture, engineering and design of the project using the

WRAP DRYVIT DETAILMESH® TO BACKSIDEOF EPS MIN. 51 MM (2")

DRAINAGE STRIP

CODE APPROVED WATER-RESISTIVEBARRIER LAPPED INTO DRAINAGE TRACKDRYVIT MD SPACER LAPPED OVERFLANGE OF DRAINAGE TRACKAPPROVED OSMD SYSTEM INSULATION BOARD

51 MM (2") MIN.610 MM (24") MAX. (SEE NOTE 2)

SEALANT WITHBOND BREAKER,

BY OTHERS

NOTCH INSULATION BOARDTO ACCOMMODATE TRACK,

WATER-RESISTIVE BARRIER,AND SPACER.

203 MM (8") MIN. ABOVE FINISHED GRADEOR AS REQUIRED BY LOCAL CODE

Drainage StripOption

SLOPED DRAINAGE TRACK

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

DRYVIT FINISH

CONCRETE CONSTRUCTION DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

WOOD OR STEEL FRAMINGSUBSTRATE

OSMD 0.0.08

® ™

Page 11: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

DRYVIT MD SPACER™

CODE APPROVED WATER-RESISTIVE BARRIER

REV:APPROVED BY: DATE:

RS 4 02/09

Outsulation SMD System Expansion Joint at Floorline

GAP PLYWOOD TO ALLOW FORCROSS-GRAIN SHRINKAGE OF THE FLOORJOISTS. OFFSET SYSTEM EXPANSION JOINTAPPROXIMATELY 25 MM (1") BELOWPLYWOOD GAP. of any project. The project design professional determines, in its sole

version.

®

does not violate Dryvit's warranty. This detail is subject to change without notice. Contact Dryvit to insure you have the most recent

discretion, whether this detail or a functionally equivalent alternative is best suited for the project. Use of a functionally equivalent detail

1. REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATION OPTIONS.

2. Dryvit products is the responsibility of the project's design

standards. This detail is for general information and guidance only

this detail and for the architecture, design, engineering or workmanship and Dryvit specifically disclaims any liability for the use of

professional. All systems must comply with local building codes and

NOTE:The architecture, engineering and design of the project using the

DRYVIT FINISH

SUBSTRATE

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

CODE APPROVED WATER-RESISTIVE BARRIERLAPPING OVER FLANGE OF DRAINAGE TRACK

19 MM (3/4") MIN.5

SEE NOTE 1

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS. (DO NOT BLOCK TRACKDRAIN HOLES)

INSULATION BOARD TO ACCOMMODATEDRAINAGE TRACK, WATER-RESISTIVE

BARRIER, AND SPACER

WRAP DRYVIT DETAILMESH® 51 MM (2") MIN.AT BACKSIDE OF INSULATION BOARD

APPROVED OSMD SYSTEM INSULATION BOARDSLOPE TOP EDGE

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

1

DRYVIT MD SPACER™ LAPPEDOVER FLANGE OF DRAINAGE TRACK

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

WOOD OR STEEL FRAMING

OSMD 0.0.09

® ™

Page 12: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

CONCRETECONSTRUCTION

REV:APPROVED BY: DATE:

4RS 02/09

Outsulation SMD System Vertical Expansion Joints

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

1.NOTE:

of any project. The project design professional determines, in its sole

version.

®

without notice. Contact Dryvit to insure you have the most recent

is best suited for the project. Use of a functionally equivalent detail does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

2. REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATION OPTIONS.

Dryvit products is the responsibility of the project's design

this detail and for the architecture, design, engineering or workmanship

standards. This detail is for general information and guidance only professional. All systems must comply with local building codes and

and Dryvit specifically disclaims any liability for the use of

The architecture, engineering and design of the project using the

CORROSIONRESISTANT "L" TRIM

CODE APPROVED WATER-RESISTIVEBARRIER PUSHED INTO JOINT

TO ACCOMMODATE MOVEMENT

WRAP DRYVIT DETAILMESH® 51 MM (2") MIN. ATBACKSIDE OF INSULATION BOARD

DRYVIT DEMANDIT® ORCOLOR PRIME™ ON

SURFACE(S) TO RECEIVE SEALANT

19 MM (3/4") MIN. DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS

OPTION

WRAP DRYVIT DETAIL MESH51 MM (2") MIN. AT BACKSIDE

OF INSULATION BOARD

DRYVIT APPROVED WASHERWITH CORROSION RESISTANT

FASTENER

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT FINISH

DRYVIT MD SPACER

APPROVED OSMD SYSTEM INSULATION BOARD

WOOD OR STEEL FRAMING

OSMD 0.0.10

® ™

Page 13: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

APPROVED OSMD SYSTEM INSULATION BOARD

REV:APPROVED BY: DATE:

4RS 02/09

Outsulation SMD System Sealant Configuration Options

WEATHER SEAL JOINTS SUCH AS AT WINDOWAND DOOR PERIMETERS CAN USE ANGLE ORRECTANGULAR BEADS. RECTANGULAR BEADSUSED AS A WEATHERSEAL REQUIRE A MINIMUM12.7 MM (1/2") WIDTH. of any project. The project design professional determines, in its sole

version.

®

does not violate Dryvit's warranty. This detail is subject to change without notice. Contact Dryvit to insure you have the most recent

discretion, whether this detail or a functionally equivalent alternative is best suited for the project. Use of a functionally equivalent detail

EXPANSION JOINTS SHALL USE RECTANGULARBEADS AND BE DESIGNED FOR MINIMUM FOURTIMES THE ANTICIPATED MOVEMENT, BUT NOTLESS THAN 19 MM (3/4").

1. 2.NOTE:

Dryvit products is the responsibility of the project's design

this detail and for the architecture, design, engineering or workmanship and Dryvit specifically disclaims any liability for the use of

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

The architecture, engineering and design of the project using the

w

t = 6.4 mm (1/4") min.w/t = 2:1

FOR RECTANGULAR BEADS:w = 12.7 mm (1/2") min. (SEE NOTES 1 AND 2)

WRAP DRYVIT DETAIL MESH51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD

APPROVED OSMD SYSTEM INSULATION BOARD

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

DRYVIT COMPATIBLE SEALANT WITHQUARTER ROUND BACKER ROD, BY OTHERS(REFER TO BOND BREAKER OPTIONS BELOW)

TRIANGULAR BACKER ROD BOND BREAKER TAPEof abutting material but not

DRYVIT DEMANDIT OR COLOR PRIMEON SURFACE(S) TO RECEIVE SEALANT

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS

DRYVIT REINFORCING MESH EMBEDDED INDRYVIT GENESIS, GENESIS DMOR GENESIS DMS BASE COAT

t

RectangularBead

less than 3.2 mm (1/8")

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD

Angle Bead BondBreaker Options

w

t = 6.4 mm (1/4") min.w = specified by manufacturer

FOR ANGLE BEADS:

tt

AngleBead

t

OSMD 0.0.11

® ™

Page 14: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

APPROVED BY: REV: DATE:

02/091RS

Outsulation SMD System Opening Prep -Sheet Type Water-Resistive Barrier

2. SHEET TYPE CODE APPROVEDWATER-RESISTIVE BARRIER SHALL BEINSTALLED IN A WEATHER BOARD FASHIONIN ACCORDANCE WITH CODE ANDMANUFACTURER'S REQUIREMENTS.

of any project. The project design professional determines, in its sole

version.

®

does not violate Dryvit's warranty. This detail is subject to change without notice. Contact Dryvit to insure you have the most recent

discretion, whether this detail or a functionally equivalent alternative is best suited for the project. Use of a functionally equivalent detail

Dryvit products is the responsibility of the project's design INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTSAND PROJECT DOCUMENTS. and Dryvit specifically disclaims any liability for the use of

this detail and for the architecture, design, engineering or workmansh

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

NOTE:1. The architecture, engineering and design of the project using the

INSTALL WINDOW UNIT AND ASSOCIATED FLASHINGSPER MANUFACTURER'S RECOMMENDATIONS, CODEREQUIREMENTS AND PROJECT DOCUMENTS.FOLD DOWN WATER-RESISTIVE BARRIER OVERHEAD FLASHING AND TAPE SEAMS WITH DRYVITFLASHING TAPE

STEP #3

3.)

APPLY DRYVIT FLASHING TAPE AND SURFACECONDITIONER ONTO HEAD AND LAP CODEAPPROVED SHEET TYPE WATER-RESISTIVEBARRIER OVER IN A WEATHER BOARD FASHION

2.)

1.)

CUT AND FOLD BACK CODE APPROVEDWATER-RESISTIVE BARRIER AT HEAD

SEE NOTE 2

4" MIN.

INSTALL DIAGONAL STRIPS OF DRYVIT FLASHINGTAPE AND SURFACE CONDITIONER AT CORNERSOVER PREVIOUSLY INSTALLED FLASHING TAPEAND WATER-RESISTIVE BARRIER

STEP #1 STEP #2

APPLY DRYVIT FLASHING TAPEAND SURFACE CONDITIONER ONTOJAMB AND OVER CODE APPROVEDSHEET TYPE WATER-RESISTIVEBARRIER

APPLY DRYVIT FLASHING TAPEAND SURFACE CONDITIONER™ ONTOSILL AND UP JAMBS LAPPING OVERCODE APPROVED SHEET TYPEWATER-RESISTIVE BARRIER 6" MIN.

(typ)

OSMD 0.0.12

® ™

Page 15: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

DATE:REV:APPROVED BY:

RS 02/092

Outsulation SMD System NOTE:

Opening Prep - Backstop® NT WRB/AquaFlash® System Option

4. APPLY CAULK BEHIND HEAD AND JAMBFLANGES OF WINDOW.

SHEET TYPE CODE APPROVEDWATER-RESISTIVE BARRIER MAY BE USEDAND SHALL BE INSTALLED IN A WEATHERBOARD FASHION IN ACCORDANCE WITH CODEAND MANUFACTURER'S REQUIREMENTS.

of any project. The project design professional determines, in its sole

version.

®

without notice. Contact Dryvit to insure you have the most recent

is best suited for the project. Use of a functionally equivalent detail does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

2. DRYVIT OPENING WRAP SHALL EXTEND TOINTERIOR FACE OF FRAMING.

3.1. APPLY DRYVIT BACKSTOP NT/-SMOOTHOR TEXTURE OVER REMAINDER OF WALLSURFACE.

Dryvit products is the responsibility of the project's design

and Dryvit specifically disclaims any liability for the use of this detail and for the architecture, design, engineering or workmanship

standards. This detail is for general information and guidance only professional. All systems must comply with local building codes and

The architecture, engineering and design of the project using the

STEP #4STEP #3

APPLY DRYVIT AQUAFLASHSYSTEM AT HEAD LAPPINGOVER JAMB APPLICATION

APPLY DRYVIT AQUAFLASHSYSTEM AT JAMBS LAPPINGOVER SILL APPLICATION

DRYVIT WATER-RESISTIVEBARRIER COATING(SEE NOTE 3)

STEP #2STEP #1

INSTALL DIAGONAL STRIPOF DRYVIT AQUAFLASHSYSTEM AT CORNERS(JAMB AND SILL)

APPLY DRYVIT AQUAFLASHSYSTEM AT SILL, EXTENDINGUP JAMBS MINIMUM 2 12"

OSMD 0.0.13

® ™

Page 16: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

APPROVED BY: REV: DATE:

APPLY DRYVIT FLASHING TAPE SURFACECONDITIONER AND DRYVIT FLASHING TAPEAT SILL, INCLUDING CORNER SPLICES. 02/091RS

Outsulation SMD System Opening Prep - Backstop® NT WRB/Backstop NT / Grid Tape™ Option

of any project. The project design professional determines, in its sole

TROWEL APPLY DRYVIT BACKSTOP NT-TEXTURE OVER THE DRYVIT GRID TAPE ALLTHE WAY TO INSIDE FACE OF OPENING. ALLVOIDS MUST BE FILLED; MULTIPLE PASSES MAYBE REQUIRED. AS AN OPTION, DRYVIT GRIDTAPE AND DRYVIT BACKSTOP NT-TEXTUREMAY ALSO BE APPLIED AT THE SILL PRIOR TODRYVIT FLASHING TAPE APPLICATION.

APPLY DRYVIT BACKSTOP NT - SMOOTHOR TEXTURE OVER REMAINDER OF WALLSURFACE.SHEET TYPE CODE APPROVEDWATER-RESISTIVE BARRIER MAY BE USEDAND SHALL BE INSTALLED IN A WEATHERBOARD FASHION IN ACCORDANCE WITH CODEAND MANUFACTURER'S REQUIREMENTS.3.

6.

®

does not violate Dryvit's warranty. This detail is subject to change without notice. Contact Dryvit to insure you have the most recent version.

discretion, whether this detail or a functionally equivalent alternative is best suited for the project. Use of a functionally equivalent detail

INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTSAND PROJECT DOCUMENTS.

APPLY DRYVIT GRID TAPE ON CORNERS OFOPENING AND SHEATHING JOINTS.

5.2.

4. NOTE:1.

Dryvit products is the responsibility of the project's design

and Dryvit specifically disclaims any liability for the use ofthis detail and for the architecture, design, engineering or workmanship

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

The architecture, engineering and design of the project using the

DRYVIT WATER RESISTIVEBARRIER COATING APPLIEDTO FACE OF WALL(SEE NOTE 5)

APPLY DRYVIT FLASHING TAPEAND SURFACE CONDITIONER(SEE NOTES 2 AND 3)

STEP #3 STEP #4

4" MIN.

6" MIN.(typ)

STEP #1 STEP #2

APPLY DRYVIT GRID TAPE(SEE NOTES 1 AND 2)

TROWEL APPLY DRYVITBACKSTOP NT-TEXTURE(SEE NOTE 2)

OSMD 0.0.14

® ™

Page 17: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

APPLY SEALANTTO FLASHING

JUNCTION

FLASHING INTEGRALWITH WINDOW

REV:APPROVED BY: DATE:

4RS 02/09

Outsulation SMD System Window Elevation

of any project. The project design professional determines, in its sole

®

does not violate Dryvit's warranty. This detail is subject to change

version.without notice. Contact Dryvit to insure you have the most recent

is best suited for the project. Use of a functionally equivalent detail discretion, whether this detail or a functionally equivalent alternative

FLASHING TRANSITION BETWEEN CURVEDAND HORIZONTAL ASSEMBLIES MUST BEPROPERLY LAPPED AND SEALED TO SHEDWATER TO THE EXTERIOR.

Dryvit products is the responsibility of the project's design

and Dryvit specifically disclaims any liability for the use of this detail and for the architecture, design, engineering or workmanship

standards. This detail is for general information and guidance only professional. All systems must comply with local building codes and

NOTE:1. The architecture, engineering and design of the project using the

FLASHINGINTEGRAL

WITH WINDOW

OSMD 0.0.15

® ™

Page 18: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

ARCHED WINDOW WITHINTEGRAL FLASHING

SUBSTRATE

FRAMING

REV:APPROVED BY: DATE:

RS 4 02/09

Outsulation SMD System Arched Window Head

discretion, whether this detail or a functionally equivalent alternative

®

does not violate Dryvit's warranty. This detail is subject to change is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent version.

FOR NON-NAILABLE SHEATHINGSUBSTRATES, FASTENERS MUST BEINSTALLED INTO THE FRAMING.

Dryvit products is the responsibility of the project's design

and Dryvit specifically disclaims any liability for the use of

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

of any project. The project design professional determines, in its sole this detail and for the architecture, design, engineering or workmanship

The architecture, engineering and design of the project using the NOTE:1.

6APPROVED OSMD SYSTEM INSULATION BOARDOR EPS TRIM (OPTIONAL) ADHEREDWITH DRYVIT GENESIS, GENESIS DM OR GENESISDMS BASE COAT OR MECHANICALLY FASTENINTO SOLID SUBSTRATE- SLOPE TOP EDGE

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARDDRYVIT MD SPACER

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERSPROVIDE AIR SEAL AROUND

INTERIOR OF WINDOW PER WINDOWMANUFACTURER'S REQUIREMENTS

12.7 MM (1/2") MIN.

DRYVIT FINISH

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COATDRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

OPENING WRAP (SEEDETAILS OSMD 0.0.12-0.0.14)

APPROVED OSMD SYSTEM INSULATION BOARD

CODE APPROVED WATER-RESISTIVEBARRIER LAPPED OVER NAILING FIN

12

OSMD 0.0.16

® ™

Page 19: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

WINDOW WITH INTEGRAL FLASHING

SUBSTRATE

REV:APPROVED BY: DATE:

4RS 02/09

Outsulation SMD System Window Head

OSMD INSULATION BOARD MAY NEED TO BENOTCHED TO ACCOMMODATEWATER-RESISTIVE BARRIER/ DRAINAGEMEDIUM.

discretion, whether this detail or a functionally equivalent alternative

®

does not violate Dryvit's warranty. This detail is subject to change without notice. Contact Dryvit to insure you have the most recent version.

is best suited for the project. Use of a functionally equivalent detail

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATIONOPTIONS.

2.

NOTE:1.

professional. All systems must comply with local building codes and

and Dryvit specifically disclaims any liability for the use of

of any project. The project design professional determines, in its sole this detail and for the architecture, design, engineering or workmanship

standards. This detail is for general information and guidance only

The architecture, engineering and design of the project using the Dryvit products is the responsibility of the project's design

CODE APPROVED WATER-RESISTIVEBARRIER AND DRAINAGE MEDIUMLAPPED OVER VINYL DRAINAGETRACK (SEE NOTE 2)

APPROVED OSMD SYSTEM INSULATION BOARDOR EPS TRIM (OPTIONAL) ADHEREDWITH DRYVIT GENESIS, GENESIS DM ORGENESIS DMS BASE COAT OR MECHANICALLYFASTEN INTO SOLID SUBSTRATE-SLOPE TOP EDGE

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

PROVIDE AIR SEAL AROUND INTERIOROF WINDOW PER WINDOW

MANUFACTURER'S REQUIREMENTS

WOOD OR STEEL FRAMING

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS.PROVIDE WEEPS WITH BAFFLES EVERY610 MM (2'-0") ON CENTER

Drainage TrackOption

13 MM (1/2") MIN.

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENERWRAP DRYVIT DETAIL MESH® 51 MM(2") MIN. AT BACKSIDE OF INSULATION BOARDDRYVIT FINISH

OPENING WRAP (SEEDETAILS OSMD 0.0.12-0.0.14)

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

CODE APPROVED WATER-RESISTIVEBARRIER LAPPED OVER NAILING FINAPPROVED OSMD SYSTEM INSULATION BOARD(SEE NOTE 2)DRYVIT MD SPACER

612

OSMD 0.0.17

® ™

Page 20: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

APPROVED OSMD SYSTEM INSULATIONBOARD OR EPS TRIM (OPTIONAL)ADHERED WITH DRYVIT GENESIS,GENESIS DM OR GENESIS DMS BASECOAT OR MECHANICALLY FASTEN INTOSOLID SUBSTRATE

WINDOW WITHINTEGRAL FLASHING

DRYVIT DEMANDIT® OR COLOR PRIMEON SURFACE(S) TO RECEIVE SEALANTDRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS

4RS 02/09

Outsulation SMD System Window Jamb

discretion, whether this detail or a functionally equivalent alternative

®REV:APPROVED BY: DATE:

without notice. Contact Dryvit to insure you have the most recent version.

does not violate Dryvit's warranty. This detail is subject to change is best suited for the project. Use of a functionally equivalent detail

FOR NON-NAILABLE SHEATHINGSUBSTRATES, THE FASTENER MUST BEINSTALLED INTO THE FRAMING.

professional. All systems must comply with local building codes and

and Dryvit specifically disclaims any liability for the use of this detail and for the architecture, design, engineering or workmanship of any project. The project design professional determines, in its sole

standards. This detail is for general information and guidance only

NOTE:1. Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

WOOD OR STEEL FRAMING

CODE APPROVEDWATER-RESISTIVE BARRIER

DRYVIT MD SPACER

OPENING WRAP (SEEDETAILS OSMD 0.0.12-0.0.14)

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT FINISH12.7 MM (1/2") MIN.

APPROVED OSMD SYSTEM INSULATIONBOARD

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

SUBSTRATE

OSMD 0.0.18PROVIDE AIR SEAL AROUNDINTERIOR OF WINDOW PER WINDOWMANUFACTURER'S REQUIREMENTS.

® ™

Page 21: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

SUBSTRATE CODE APPROVEDWATER-RESISTIVE BARRIER

REV:APPROVED BY: DATE:

RS 4 02/09

Outsulation SMD System Window Sill

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

discretion, whether this detail or a functionally equivalent alternative

®

does not violate Dryvit's warranty. This detail is subject to change is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent version.

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATION OPTIONS. professional. All systems must comply with local building codes and

and Dryvit specifically disclaims any liability for the use ofstandards. This detail is for general information and guidance only

of any project. The project design professional determines, in its sole this detail and for the architecture, design, engineering or workmanship

Dryvit products is the responsibility of the project's design The architecture, engineering and design of the project using the

NOTE:2.1.

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COATDRYVIT FINISH

APPROVED SYSTEMINSULATION BOARD

DRYVIT MD SPACER

OPENING WRAP (SEEDETAILS OSMD 0.0.12-0.0.14)

WINDOW WITH INTEGRAL FLASHING

PROVIDE AIR SEAL AROUNDINTERIOR OF WINDOW PER WINDOWMANUFACTURER'S REQUIREMENTS

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARDDRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENERAPPROVED OSMD SYSTEM INSULATIONBOARD OR EPS TRIM (OPTIONAL)ADHERED WITH DRYVIT GENESIS,GENESIS DM OR GENESIS DMS BASECOAT OR MECHANICALLY FASTEN INTOSOLID SUBSTRATE- SLOPE TOP EDGE

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS

13 MM (1/2") MIN.126

OSMD 0.0.19

® ™

Page 22: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

APPROVED OSMD SYSTEM INSULATIONBOARD OR EPS TRIM(OPTIONAL) ADHERED WITH DRYVITGENESIS, GENESIS DM OR GENESIS DMSBASE COAT OR MECHANICALLY FASTENINTO SOLID SUBSTRATEDOOR WITH INTEGRAL FLASHING

DRYVIT DEMANDIT® ORCOLOR PRIME ON SURFACE(S)TO RECEIVE SEALANTDRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS

4RS 02/09

Outsulation SMD System Door Jamb With Integral Flashing

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

discretion, whether this detail or a functionally equivalent alternative

REV:APPROVED BY:

®DATE:

without notice. Contact Dryvit to insure you have the most recent version.

is best suited for the project. Use of a functionally equivalent detail does not violate Dryvit's warranty. This detail is subject to change

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATION OPTIONS.

NOTE:1. 2.

professional. All systems must comply with local building codes and

and Dryvit specifically disclaims any liability for the use of this detail and for the architecture, design, engineering or workmanship of any project. The project design professional determines, in its sole

standards. This detail is for general information and guidance only

The architecture, engineering and design of the project using the Dryvit products is the responsibility of the project's design

DRYVIT MD SPACERSUBSTRATE

OPENING WRAP (SEEDETAILS OSMD 0.0.12-0.0.14)CODE APPROVEDWATER-RESISTIVE BARRIER

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT GENESIS®,GENESIS DM OR GENESIS DMSBASE COAT

12.7 MM (1/2") MIN.

APPROVED SYSTEMINSULATION BOARD

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

WOOD OR STEEL FRAMING

OSMD 0.0.20

PROVIDE AIR SEAL AROUNDINTERIOR OF WINDOW PER WINDOWMANUFACTURER'S REQUIREMENTS

® ™

Page 23: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

APPROVED OSMD SYSTEMINSULATION BOARD

APPROVED OSMD SYSTEM INSULATIONBOARD OR EPS TRIM (OPTIONAL)ADHERED WITH DRYVIT GENESIS,GENESIS DM OR GENESIS DMS BASECOAT OR MECHANICALLY FASTEN INTOSOLID SUBSTRATE

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

DRYVIT FINISH

4RS 02/09

Outsulation SMD System Door Jamb With Brick Mold

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

discretion, whether this detail or a functionally equivalent alternative

REV:APPROVED BY: DATE:

®

without notice. Contact Dryvit to insure you have the most recent version.

does not violate Dryvit's warranty. This detail is subject to change is best suited for the project. Use of a functionally equivalent detail

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATION OPTIONS. professional. All systems must comply with local building codes and

of any project. The project design professional determines, in its sole this detail and for the architecture, design, engineering or workmanship and Dryvit specifically disclaims any liability for the use ofstandards. This detail is for general information and guidance only

NOTE:1. 2. Dryvit products is the responsibility of the project's design

The architecture, engineering and design of the project using the

PROVIDE AIR SEAL AROUNDINTERIOR OF WINDOW PER WINDOWMANUFACTURER'S REQUIREMENTS

SUBSTRATE

WOOD OR STEEL FRAMING

DOOR WITHBRICK MOLD

DRYVIT MD SPACER

CODE APPROVEDWATER-RESISTIVE BARRIER

OPENING WRAP (SEEDETAILS OSMD 0.0.12-0.0.14)

12.7 MM (1/2") MIN.

DRYVIT DEMANDIT®OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDE

OF INSULATION BOARD

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD

OSMD 0.0.21

® ™

Page 24: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

DOOR WITH INTEGRALFLASHING

SUBSTRATE

WOOD ORSTEEL FRAMING

4RS 02/09

Outsulation SMD System Door Head With Integral Flashing

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATIONOPTIONS.

discretion, whether this detail or a functionally equivalent alternative

®APPROVED BY: REV: DATE:

without notice. Contact Dryvit to insure you have the most recent

is best suited for the project. Use of a functionally equivalent detail does not violate Dryvit's warranty. This detail is subject to change

version.

OSMD INSULATION BOARD MAY NEED TO BENOTCHED TO ACCOMMODATE DRAINAGETRACK AND BARRIER / DRAINAGE MEDIUM.

professional. All systems must comply with local building codes and

this detail and for the architecture, design, engineering or workmanship of any project. The project design professional determines, in its sole

standards. This detail is for general information and guidance only and Dryvit specifically disclaims any liability for the use of

2.

The architecture, engineering and design of the project using the Dryvit products is the responsibility of the project's design

NOTE:1.

CODE APPROVED WATER-RESISTIVEBARRIER AND DRAINAGE MEDIUMLAPPED OVER VINYL DRAINAGETRACK (SEE NOTES 1 AND 2)

6 APPROVED OSMD SYSTEM INSULATIONBOARD OR EPS TRIM (OPTIONAL)ADHERED WITH DRYVIT GENESIS,GENESIS DM OR GENESIS DMS BASECOAT OR MECHANICALLY FASTEN INTOSOLID SUBSTRATE- SLOPE TOP EDGE

DRYVIT DEMANDIT®OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD. PROVIDEWEEPS WITH BAFFLES 610 MM (2'-0")ON CENTER

Drainage TrackOption

12.7 MM (1/2") MIN.

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENEROPENING WRAP (SEEDETAILS OSMD 0.0.12-0.0.14)WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD

OSMD 0.0.22

DRYVIT MD SPACERAPPROVED OSMD SYSTEM INSULATION BOARDDRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COATDRYVIT FINISH

12

CODE APPROVED WATER-RESISTIVE BARRIER

® ™

Page 25: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

WOOD OR STEELFRAMING

SUBSTRATE

4RS 02/09

Outsulation SMD System Door Head With Brick Mold

OSMD INSULATION BOARD MAY NEED TO BENOTCHED TO ACCOMMODATEWATER-RESISTIVE BARRIER/ DRAINAGEMEDIUM.

is best suited for the project. Use of a functionally equivalent detail

REV:APPROVED BY:

®DATE:

without notice. Contact Dryvit to insure you have the most recent version.

does not violate Dryvit's warranty. This detail is subject to change

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATIONOPTIONS.

2.

NOTE:1.

professional. All systems must comply with local building codes and

this detail and for the architecture, design, engineering or workmanship

discretion, whether this detail or a functionally equivalent alternative of any project. The project design professional determines, in its sole

and Dryvit specifically disclaims any liability for the use ofstandards. This detail is for general information and guidance only

The architecture, engineering and design of the project using the Dryvit products is the responsibility of the project's design

CODE APPROVED WATER-RESISTIVEBARRIER AND DRAINAGE MEDIUMLAPPED OVER VINYL DRAINAGETRACK (SEE NOTES 1 AND 2)

APPROVED OSMD SYSTEM INSULATIONBOARD OR EPS TRIM (OPTIONAL)ADHERED WITH DRYVIT GENESIS,GENESIS DM OR GENESIS DMS BASECOAT OR MECHANICALLY FASTEN INTOSOLID SUBSTRATE- SLOPE TOP EDGE

12.7 MM (1/2") MIN.

DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD. PROVIDE WEEPS WITHBAFFLES EVERY 610 MM (2'-0") ON CENTER

DOOR WITHBRICK MOLD

Drainage TrackOption

DRIP FLASHING SETIN BED OF SEALANT

OPENING WRAP (SEEDETAILS OSMD 0.0.12-0.0.14)WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARDDRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

OSMD 0.0.23DRYVIT MD SPACERAPPROVED OSMD SYSTEM INSULATION BOARD

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COATDRYVIT FINISH

612

CODE APPROVED WATER-RESISTIVE BARRIER

® ™

Page 26: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

SUBSTRATE

DRYVIT MD SPACER

CODE APPROVED WATER-RESISTIVE BARRIER

4RS 02/09

Inside / Outside Corners

discretion, whether this detail or a functionally equivalent alternative

does not violate Dryvit's warranty. This detail is subject to change is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

of any project. The project design professional determines, in its sole this detail and for the architecture, design, engineering or workmanship

The architecture, engineering and design of the project using the

Outsulation SMD SystemDRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

DESIGNER SHALL DETERMINE THE NEED FOR ANEXPANSION JOINT AT CORNERS.

®REV:APPROVED BY: DATE:

version.

DO NOT LAP REINFORCING MESH WITHIN 203 MM(8") OF A CORNER.

3.

4.

and Dryvit specifically disclaims any liability for the use of

1.NOTE:

2. DOUBLE WRAP CORNERS WITH REINFORCINGMESH OR USE CORNER MESH.

Dryvit products is the responsibility of the project's design

MUST OVERLAP 203 MM (8") MIN.SEE ABOVE AND NOTES 2 AND 3

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS, GENESIS DMOR GENESIS DMS BASE COAT

APPROVED OSMD SYSTEM INSULATION BOARD

CODE APPROVED WATER-RESISTIVE BARRIER

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

203 MM (8") MIN.(SEE NOTES 2 AND 3)

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

203 MM (8") MIN.(SEE NOTES 2 AND 3)

DRYVIT MD SPACERDRYVIT FINISH

OSMD 0.0.24

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

APPROVED OSMD SYSTEM INSULATION BOARDSUBSTRATE

® ™

Page 27: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

4RS 02/09

Outsulation SMD System

is best suited for the project. Use of a functionally equivalent detail

®REV:APPROVED BY: DATE:

version.without notice. Contact Dryvit to insure you have the most recent does not violate Dryvit's warranty. This detail is subject to change

LOCATE INSULATION BOARDS SUCH THATBOARD EDGES DO NOT ALIGN WITHCORNERS OF PENETRATION. standards. This detail is for general information and guidance only

this detail and for the architecture, design, engineering or workmanship of any project. The project design professional determines, in its sole

and Dryvit specifically disclaims any liability for the use of

discretion, whether this detail or a functionally equivalent alternative

APPLY A PIECE OF 241 MM (9 1/2") X 305 MM(12") DRYVIT REINFORCING MESH DIAGONALLYAT EACH CORNER.

2.

professional. All systems must comply with local building codes and Dryvit products is the responsibility of the project's design The architecture, engineering and design of the project using the 1.

NOTE:

DRYVIT DETAIL MESH241 MM (9 1/2") X 305 MM (12") (TYP.)

System Configuration At Openings

OFFSET INSULATION BOARDJOINTS FROM CORNERSOF OPENINGS

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD

SPLICE PIECE OF DRYVIT DETAIL MESHREQUIRED AT CORNER

APPROVED OSMD SYSTEMINSULATION BOARD

OSMD 0.0.25

® ™

Page 28: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

CORROSION RESISTANT SCREW AND SLEEVE

Outsulation SMD SystemDRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

is best suited for the project. Use of a functionally equivalent detail

RS

APPROVED BY:

®REV:

4

DATE:

02/09

version.

does not violate Dryvit's warranty. This detail is subject to change without notice. Contact Dryvit to insure you have the most recent

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATION OPTIONS.

1. 2.NOTE:

standards. This detail is for general information and guidance only

of any project. The project design professional determines, in its sole discretion, whether this detail or a functionally equivalent alternative

and Dryvit specifically disclaims any liability for the use of this detail and for the architecture, design, engineering or workmanship

Dryvit products is the responsibility of the project's design professional. All systems must comply with local building codes and

The architecture, engineering and design of the project using the

Shutter And Downspout Attachment

DRYVIT COMPATIBLE SEALANT,BY OTHERS

DOWNSPOUT STRAP

DRYVIT COMPATIBLE SEALANTBETWEEN SYSTEM AND STRAP,BY OTHERS

DOWNSPOUT

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT FINISH

CORROSION RESISTANT SCREWCORROSION RESISTANT SLEEVESHUTTER

OSMD 0.0.2612.7 MM (1/2") MIN.

SUBSTRATE

WOOD OR STEEL FRAMING

CODE APPROVED WATER-RESISTIVE BARRIERDRYVIT MD SPACER

APPROVED OSMD SYSTEM INSULATION BOARD

® ™

Page 29: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

Outsulation SMD SystemThe architecture, engineering and design of the project using the

discretion, whether this detail or a functionally equivalent alternative

does not violate Dryvit's warranty. This detail is subject to change is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

of any project. The project design professional determines, in its sole this detail and for the architecture, design, engineering or workmanship

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATION OPTIONS.

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

®REV:

4RS

APPROVED BY: DATE:

02/09

version.

3. INSULATION BOARD THICKNESS MINUS THEDEPTH OF THE REVEAL SHALL NOT BE LESSTHAN 19 MM (3/4").

4.

and Dryvit specifically disclaims any liability for the use of

1.NOTE:

2. BOTTOM EDGES OF ALL REVEALS MUST BESLOPED FOR DRAINAGE.

Dryvit products is the responsibility of the project's design

Aesthetic Reveals

OVERLAP 64 MM (2 1/2") MIN.

19 MM (3/4") MIN. (SEE NOTE 3)

REVEAL OPTIONS

DRYVIT FINISH

CODE APPROVED WATER-RESISTIVE BARRIER

DRYVIT DETAIL MESH®241 MM (9 1/2") X 305 MM (12") (TYP.)DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

APPROVED OSMD SYSTEM INSULATION BOARD

SUBSTRATE

OSMD 0.0.27

DRYVIT MD SPACER

WOOD OR STEEL FRAMING

® ™

Page 30: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

DRYVIT FINISH

NOTE:DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

does not violate Dryvit's warranty. This detail is subject to change

®REV:APPROVED BY: DATE:

4RS 02/09

without notice. Contact Dryvit to insure you have the most recent version.

and Dryvit specifically disclaims any liability for the use of

of any project. The project design professional determines, in its sole discretion, whether this detail or a functionally equivalent alternative is best suited for the project. Use of a functionally equivalent detail

this detail and for the architecture, design, engineering or workmanship

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATION OPTIONS.

1. 2. Dryvit products is the responsibility of the project's design professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

The architecture, engineering and design of the project using the

Outsulation SMD System Minor Penetrations

DRYVIT MD SPACER

CODE APPROVED WATER-RESISTIVE BARRIER

SUBSTRATE

WOOD OR STEEL FRAMING

CAULK PERIMETER OF PENETRATIONALONG SHEATHING.

12.7 MM (1/2") MIN.

APPROVED OSMD SYSTEM INSULATION BOARD

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT DEMANDIT® OR COLOR PRIMEON SURFACE(S) TO RECEIVE SEALANT

WRAP DRYVIT DETAIL MESH® 51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS

OSMD 0.0.28

® ™

Page 31: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

DRYVIT COMPATIBLE SEALANT,BY OTHERS

WRAP DRYVIT DETAIL MESH® 51 MM (2") MIN.AT BACKSIDE OF INSULATION BOARD

FLASHING NO. 1 EXTENDUP BEHIND FLASHINGNO. 2 76 MM (3") MIN.

NOTE:DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

does not violate Dryvit's warranty. This detail is subject to change

APPROVED BY:

®REV: DATE:

4RS 02/09

without notice. Contact Dryvit to insure you have the most recent version.

1.

3. REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATION OPTIONS.

and Dryvit specifically disclaims any liability for the use of

discretion, whether this detail or a functionally equivalent alternative is best suited for the project. Use of a functionally equivalent detail

this detail and for the architecture, design, engineering or workmanship of any project. The project design professional determines, in its sole

REFER TO OSMD DETAIL 0.0.30 FOR DECKCUTAWAY DETAIL.

Dryvit products is the responsibility of the project's design

standards. This detail is for general information and guidance only professional. All systems must comply with local building codes and

The architecture, engineering and design of the project using the 2.

CODE APPROVED WATER-RESISTIVE BARRIER

SUBSTRATE

Outsulation SMD System Wood Framed Deck - Cross Section

DRYVIT MD SPACER

DRAINAGE TRACK

DRYVIT FINISH

DECK FRAMINGFLASHING NO. 2 EXTEND UP BEHIND

FLASHING NO. 3 76 MM (3") MIN.

25 MM (1") MIN.

64 MM (2-1/2") MIN.

FLASHING NO. 3 EXTENDUP BEHIND INSULATION

BOARD 76 MM (3")

SUPPORT STRIP

DECK BOARDS51 MM (2") MIN.

OSMD 0.0.29APPROVED OSMD SYSTEMINSULATION BOARDCODE APPROVED WATER-RESISTIVE BARRIER

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

DRYVIT MD SPACER™LAPPED OVER FLANGE

OF DRAINAGE TRACK

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

® ™

Page 32: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

discretion, whether this detail or a functionally equivalent alternative

does not violate Dryvit's warranty. This detail is subject to change is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent

Dryvit products is the responsibility of the project's design

and Dryvit specifically disclaims any liability for the use of

The architecture, engineering and design of the project using the

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

of any project. The project design professional determines, in its sole this detail and for the architecture, design, engineering or workmanship

Wood Framed Deck - Cut AwayNOTE:

DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO STANDARD MESH™ OR STANDARD PLUSMESH™. LOCATION OF HIGH IMPACT ZONESSHOULD BE INDICATED ON CONTRACTDRAWINGS.

REV:APPROVED BY: DATE:

4RS 02/09

version.

1. REFER TO OSMD DETAIL 0.0.29 FOR DECK-CROSS SECTION DETAIL.

2.

Outsulation SMD System

®

OSMD 0.0.30

DRAINAGE TRACK

OSMD SYSTEM

END JOIST

FLASHING NO. 3 TURNEDDOWN OVER END JOIST

WOOD DECK BOARD

FLASHING NO. 1

DRYVIT COMPATIBLESEALANT, BY OTHERS

FLASHING NO. 2 BEHINDAPPROVED OSMD BOARD

(HIDDEN)

® ™

Page 33: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

NOTE:

does not violate Dryvit's warranty. This detail is subject to change

®REV:APPROVED BY: DATE:

4RS 02/09

version.without notice. Contact Dryvit to insure you have the most recent

and Dryvit specifically disclaims any liability for the use of

discretion, whether this detail or a functionally equivalent alternative is best suited for the project. Use of a functionally equivalent detail

this detail and for the architecture, design, engineering or workmanship of any project. The project design professional determines, in its sole

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATIONOPTIONS.

1.

standards. This detail is for general information and guidance only professional. All systems must comply with local building codes and

The architecture, engineering and design of the project using the Dryvit products is the responsibility of the project's design

Outsulation SMD System Soffit Termination

SUBSTRATE

WOOD OR STEEL FRAMINGCODE APPROVED WATER-RESISTIVE BARRIER

DRYVIT MD SPACER

12.7 MM (1/2") MIN.DRYVIT DEMANDIT®OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COATAPPROVED OSMD SYSTEM INSULATION BOARD

DRYVIT FINISH

WRAP DRYVIT DETAIL MESH® 51 MM (2") MIN.AT BACKSIDE OF INSULATION BOARD

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS

OSMD 0.0.31

ROOF ASSEMBLY

® ™

Page 34: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

SUBSTRATE

CODE APPROVED WATER-RESISTIVE BARRIERDRYVIT MD SPACER

NOTE:

does not violate Dryvit's warranty. This detail is subject to change

APPROVED BY:

®REV: DATE:

4RS 02/09

without notice. Contact Dryvit to insure you have the most recent version.

INSTALL SOFFIT FRIEZE BOARD AND TRIMAFTER OSMD SYSTEM IS IN PLACE.

1.

and Dryvit specifically disclaims any liability for the use of

discretion, whether this detail or a functionally equivalent alternative is best suited for the project. Use of a functionally equivalent detail

this detail and for the architecture, design, engineering or workmanship of any project. The project design professional determines, in its sole

FOR NON-NAILABLE SHEATHING SUBSTRATES,THE FASTENERS MUST BE INSTALLED INTO THEFRAMING. standards. This detail is for general information and guidance only

professional. All systems must comply with local building codes and Dryvit products is the responsibility of the project's design The architecture, engineering and design of the project using the 2.

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COATDRYVIT FINISH

Outsulation SMD System Soffit With Frieze Board

APPROVED OSMD SYSTEM INSULATION BOARD

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS

12.7 MM (1/2") MIN.

DRYVIT DEMANDIT®OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

SPACER BLOCK

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

38 MM (1-1/2") MIN.

DRYVIT COMPATIBLE SEALANT WITHBOND BREAKER, BY OTHERS

FRIEZE BOARD

OSMD 0.0.32

ROOF ASSEMBLY

® ™

Page 35: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

CODE APPROVED WATER-RESISTIVE BARRIERDRYVIT MD SPACER

GABLE END RAFTER

NOTE:

this detail and for the architecture, design, engineering or workmanship of any project. The project design professional determines, in its sole

standards. This detail is for general information and guidance only professional. All systems must comply with local building codes and

and Dryvit specifically disclaims any liability for the use of

Dryvit products is the responsibility of the project's design

without notice. Contact Dryvit to insure you have the most recent

is best suited for the project. Use of a functionally equivalent detail does not violate Dryvit's warranty. This detail is subject to change

discretion, whether this detail or a functionally equivalent alternative

The architecture, engineering and design of the project using the

REV:APPROVED BY: DATE:

RS 4 02/09

version.

FOR RAKE WITH OVERHANG REFER TOOSMD DETAIL 0.0.32.

FOR NON-NAILABLE SHEATHING SUBSTRATES,THE FASTENER MUST BE INSTALLED INTO THEFRAMING.

1. 2.

®

Gable End With EIFS Trim

APPROVED OSMD SYSTEM INSULATION BOARD

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

Outsulation SMD System

ROOF SHINGLES

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

64 MM (2-1/2") MIN.

DRYVIT COMPATIBLE SEALANTWITH BOND BREAKER, BY OTHERS

APPROVED OSMD SYSTEM INSULATION BOARD OR EPS TRIM (OPTIONAL)ADHERED WITH DRYVIT GENESIS,GENESIS DM OR GENESIS DMS BASECOAT OR MECHANICALLY FASTEN INTOSOLID SUBSTRATE

DRYVIT FINISH

DRIP EDGE FLASHING

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD

SUBSTRATE

ROOFING PAPER

OSMD 0.0.33

SECTION A-A

® ™

Page 36: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

CODE APPROVEDWATER-RESISTIVE BARRIER

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDE

OF INSULATION BOARD

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,

BY OTHERSDRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

NOTE:

without notice. Contact Dryvit to insure you have the most recent

DATE:

4RS 02/09

REV:APPROVED BY:

®

version.

and Dryvit specifically disclaims any liability for the use of

discretion, whether this detail or a functionally equivalent alternative

does not violate Dryvit's warranty. This detail is subject to change is best suited for the project. Use of a functionally equivalent detail

of any project. The project design professional determines, in its sole this detail and for the architecture, design, engineering or workmanship

FOR NON-NAILABLE SHEATHING SUBSTRATES,THE FASTENER MUST BE INSTALLED INTO THEFRAMING.

FOR RAKE WITH OVERHANG REFER TOOSMD DETAIL 0.0.32.

1. 2.professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

The architecture, engineering and design of the project using the Dryvit products is the responsibility of the project's design

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

Outsulation SMD System Gable End With Wood Trim

DRYVIT FINISH

DRYVIT MD SPACERAPPROVED OSMD SYSTEM INSULATIONBOARD

ROOF SHINGLES

GABLE END RAFTERWOOD TRIM BOARD

38 MM (1 1/2") MIN.

DRYVIT DEMANDIT® OR COLOR PRIME™ ON SURFACE(S) TO RECEIVE SEALANT

SPACER BLOCK

SEALANT WITH BONDBREAKER, BY OTHERS 64 MM (2 1/2") MIN.

DRYVIT COMPATIBLE SEALANTWITH BOND BREAKER, BY OTHERS

13 MM (1/2") MIN.

DRIP EDGE FLASHING

SUBSTRATE

ROOFING PAPER

OSMD 0.0.34

SECTION A-A

® ™

Page 37: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

DRYVIT MD SPACER LAPPED OVERFLANGE OF DRAINAGE TRACK

CODE APPROVEDWATER-RESISTIVE BARRIER

NOTE:

without notice. Contact Dryvit to insure you have the most recent

4RS 02/09

REV:APPROVED BY: DATE:

®

version.

REFER TO DETAILS OSMD 0.0.01, 0.0.02 AND0.0.03 FOR SYSTEM CONFIGURATIONOPTIONS.

1.

this detail and for the architecture, design, engineering or workmanship

discretion, whether this detail or a functionally equivalent alternative is best suited for the project. Use of a functionally equivalent detail does not violate Dryvit's warranty. This detail is subject to change

of any project. The project design professional determines, in its sole

APPROVED OSMD INSULATION BOARD MAY NEEDTO BE NOTCHED TO ACCOMMODATEWATER-RESISTIVE BARRIER/ DRAINAGE MEDIUM.

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only and Dryvit specifically disclaims any liability for the use of

2. Dryvit products is the responsibility of the project's design The architecture, engineering and design of the project using the

Outsulation SMD System Termination at Parapet

DRAINAGE TRACK

DRYVIT COMPATIBLE SEALANTWITH BOND BREAKER, BY OTHERS

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT GENESIS®, GENESIS DMOR GENESIS DMS BASE COAT

ROOF ASSEMBLY

203 MM (8") MIN.

DRYVIT MD SPACERDrainage TrackOption

CODE APPROVEDWATER-RESISTIVE BARRIER

SUBSTRATE

ROOF FLASHING ANDCOUNTERFLASHING

WOOD OR STEEL FRAMINGAPPROVED OSMD SYSTEMINSULATION BOARD

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT, BY OTHERS

OSMD 0.0.35

WRAP DRYVIT DETAIL MESH®51 MM (2") MIN. AT BACKSIDEOF INSULATION BOARD

DRYVIT APPROVED WASHER WITHCORROSION RESISTANT FASTENER

64 MM (2 1/2") MIN.

METAL CAP FLASHING

® ™

Page 38: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

FASCIADRIP EDGE

SOLDER ALL JOINTSIN KICKOUT DIVERTER

Termination at Roof to Wall Flashing

discretion, whether this detail or a functionally equivalent alternative

does not violate Dryvit's warranty. This detail is subject to change is best suited for the project. Use of a functionally equivalent detail

without notice. Contact Dryvit to insure you have the most recent

Dryvit products is the responsibility of the project's design

and Dryvit specifically disclaims any liability for the use of

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only

of any project. The project design professional determines, in its sole this detail and for the architecture, design, engineering or workmanship

The architecture, engineering and design of the project using the NOTE:

EXTEND ROOFING PAPER 127 MM (5") MIN.UP VERTICAL WALL BEHIND METALFLASHING.

4RS 02/09

APPROVED BY: REV: DATE:

version.

METAL FLASHINGS ARE 254 MM (10") X 51 MM(2") LONGER THAN THE EXPOSED PORTION OFTHE ROOFING SHINGLE AND ARE BENT IN HALFTO ALLOW FOR TWO 127 MM (5") LEGS.ALTHOUGH NOT SHOWN, METAL FLASHINGS ARESTEP FLASHED (INTERWOVEN) WITH ROOFINGSHINGLES.

KICKOUT DIVERTER TO BE MADE FROMCORROSION RESISTANT MATERIAL MIN. 24GAGE.

3.

EXTEND KICKOUT A MINIMUM OF 25 MM (1")BEYOND FACE OF SYSTEM.

2.

1. 4.

Outsulation SMD System

®

DRYVIT MD SPACER 152 MM(6")

CODE APPROVED WATER-RESISTIVEBARRIER LAPPED OVER FLASHING

ROOF SHINGLESROOFING PAPER(SEE NOTE 3)

METAL FLASHING, BY OTHERS(SEE NOTE 4)

DRYVIT COMPATIBLESEALANT, BY OTHERS

APPROVED OSMD SYSTEMINSULATION BOARD

50MM (2") MIN.

KICKOUT DIVERTER

OSMD 0.0.36

152 MM(6")

110

100

303 MM(12")

® ™

Page 39: Outsulation SMD System Installation Details (Formerly ... · Outsulation SMD System Installation Details (Formerly Sprint MD System) DS163 . MINOR PENETRATIONS OSMD 0.0.28 RS 4 APPROVED

REFER TO DETAILS OSMD 0.0.01,0.0.02 AND 0.0.03 FOR SYSTEMCONFIGURATION OPTIONS.

1. The architecture, engineering and design of the project using the

without notice. Contact Dryvit to insure you have the most recent

DATE:

02/094RS

REV:APPROVED BY:

®

version.

this detail and for the architecture, design, engineering or workmanship

is best suited for the project. Use of a functionally equivalent detail does not violate Dryvit's warranty. This detail is subject to change

of any project. The project design professional determines, in its sole discretion, whether this detail or a functionally equivalent alternative

professional. All systems must comply with local building codes and standards. This detail is for general information and guidance only and Dryvit specifically disclaims any liability for the use of

Dryvit products is the responsibility of the project's design

Outsulation SMD SystemNOTE:

Chimney Enclosure

CRICKET FLASHING

CODE APPROVED WATER-RESISTIVEBARRIER OVER SUBSTRATE

STEP FLASH ROOFING SHINGLESAND METAL FLASHING

DIVERTER FLASHING(SEE DETAIL OSMD 0.0.36)

DRYVIT COMPATIBLESEALANT, BY OTHERS

50 MM (2") MIN. CLEARANCEBETWEEN OSMD

SYSTEM AND SHINGLES DRAINAGE STRIP

ROOFING SHINGLES

SEAL BETWEEN METAL CAP ANDDRYVIT SYSTEM USING DRYVIT

COMPATIBLE SEALANT WITHBOND BREAKER, BY OTHERS

SUBSTRATE

OSMD SYSTEM

TERMINAL RAIN CAP

OSMD 0.0.37

® ™